AXRTU-62351 Automation for Energy Crypto/Cyber
Security (IEC/TS 62351)
RTU-62351 Telecontrolling RTU with distributed system
• Overview:
– Chassis with I / O distributed in single or double ring redundancy
– Redundant configuration of CPUs and power supplies
– Native IEEE-1588 time synchronization or from GPS or IRIG-B
– Digital inputs and outputs with extended DC / AC range with Poles management
– Analogue inputs and outputs configurable with extended range in current and voltage
– Configuration and programming with IEC-61131-3 compatible tool, with .xml files
– Physical media:
∗ Serial RS-232/RS-485
∗ Ethernet 10/100 RJ-45 and multimode optic fiber (single-mode option) ST or SC con-nectors
∗ EtherCat copper and optic fiber
∗ Mobile GSM/GPRS/UMTS/EDGE/HSPA+
– Protocols:
∗ IEC 60870-5-104/101,(Armament management with Multicast and Unicast TERNAcompliance TSPSD0707 ver 5.11)
∗ IEC 62351 parts:3,5,7,8,9 (crypto/cyber security)
∗ IEC 61158-2/12/15 (Ethernet/IP - EtherCat - Modbus RTCS)
∗ IEC-61850 Master / Slave / Goose
∗ MODBUS-RTU, MODBUS-TCP/IP Master e/o Slave.
∗ M-BUS Master.
∗ WM-BUS.
∗ LoRaWan.
Energy
Managem
entSystem
• Applications also with IEC/TS 62351 (Cyber Security)
– RTU - SICAS - Automation of electrical substations LV/MV/HV
– RTU - Automation of gas and heat substations
– RTU - Central management for remote production plants as italian CEI 0-16 Allegato M
– Gateway - between 60870-5-101/104, IEC 61850, MODBUS, S7Comm
– ConCEP - Control of the power Consumption and of the Electrical Peaks
– UPDL (Unit Peripheral device for Detachment of the Loads) and UPDM (Unit Peripheraldevice for systems of Defence and Monitoring) - as TERNA specifications
• Certifications:
– TUV nr. AK 60020493 0001
– DNV/KEMA nr.74101951-MOC/INC 12-02092
for protocol 60870-5-104
Energy
Managem
entSystem
Datasheet AXRTU-62351
TECHNICAL FEATURES
RTU - Chassis and Overview
RTU 6U to rack mount front view
RTU 6U rear view with Han 72DD series or 75pconnectors
RTU 6U rear view with H.M.I. option
Example of RTU 3U
Dimensions
• Rack IEC 297 / IEC 6
• Height(H)266mm(6U) or 133mm(3U), Width(W)426.72mm(84TE, 19”), Depth(D) 220mm
• 13 Slots for power supply, CPUs and I/O cards
• Possibility to fix the basket on a 19” grid or directlyon the cabinet bottom plate
Backplane configurations
• 2 slots for redundant power supplies
• 2/4 slot for redundant CPUs MASTER with follow-ing features:
– full field visibility for both CPUs
– operation normally assigned to the CPU Mas-ter 1. In the presence of particular events, theoperation passes to the Master 2 CPU, withoutlosses in the communication sequence
– events that can cause the control to pass areprogrammable according to the type of finalfunction of the device
– Automation version
– 1/2 slots for CPU Slave cards for communica-tion
– 7/10 slots for Digital and Analog I/O cards
– Communication/Gateway version
– 8 slots for CPU Slave cards for communication
– 1 slot for Digital and Analog I/O cards
e-mail: [email protected] http://www.ailux.eu REV-05 19-2018 3
Energy
Managem
entSystem
Datasheet AXRTU-62351
Field Connections option
• 75-pin industrial connectors (configurable with maleor female pins) directly positioned on the rear panels
• Option: 72-pin industrial connectors Han 72DD se-ries configurable male/female
Diagnostics
• Power supply, BUS and auxiliary voltage via leds onthe front or rear of the rack
• Indication of which CPU Master has bus control viaLEDs and opto-isolated output on the rear rack
• 2 opto-isolated inputs on rear of the rack to forcecontrol between the Master CPUs
• for each CPU slots (master or slave) a serial line isavailable for debug / log and diagnostics
Chassis+Backplane Order codes
• 001-AXRCK-1000 (Chassis 19” x 3U x 220mm torack mount with Backplane, 2 slots for PS and 11slot with 64p DIN41612 connector)
• 002-AXRCK-1001 (Chassis 19” x 3U+2U x220mm to rack mount with Backplane, 2 slots forPS and 11 slot with 55p HARD-METRIC connec-tor)
• 003-AXRCK-2000 (Chassis 19” x 6U x 220mm torack mount with Backplane, 2 slots for PS and 11slot with 64p DIN41612 connector)
• 004-AXRCK-2001 (Chassis 19” x 6U x 220mm tobottom plate with Backplane, 2 slots for PS and 11slot with 64p DIN41612 connector)
• 005-AXRCK-2002 (Chassis 19” x 6U x 220mm torack mount with Backplane, 2 slots for PS and 11slot with 64p DIN41612 and with 72-pin industrialconnectors on rear plate)
Option Industrial H.M.I.
• Display TFT 10.1” with capacitive multitouchtouchscreen
• Operative System Android 4.4.2 KitKat
• 44 Multicolor LEDs software configurable for statesand diagnostics
HMI option Order codes
• 006-AXHMI-2000 (HMI front Panel TFT 10”Touch with 44 Status/Diagnostics multicolor LED)
• 007-AXHMI-2001 (HMI front Panel TFT 10”Touch)
• 008-AXHMI-2002 (Front Panel with 44 Sta-tus/Diagnostics multicolor LED)
e-mail: [email protected] http://www.ailux.eu REV-05 19-2018 4
Energy
Managem
entSystem
Datasheet AXRTU-62351
CPU MASTER Model CPU-DU
Microprocessor card which, as MASTER, manages theother boards connected to the backplane. Can act as a
time synchronization server via IEEE-1588, GPS orIRIG-B. It can optionally be EtherCat Master.
On-board there are Ethernet 10/100 Mbps, one Serial
interfaces and .
Features
• 32bits CPU Coldfire + crypto unit (IEC/TS 62351)
• 2MB of battery backup SRAM
• 1MB of Flash for firmware
• 1MB of Flash as disk memory
• 128KB of Flash for cache/log
• Integrated RTC 32KHz
• Micro SD slot up to 16Gb card
• USB 2.0 interface with Micro-B connector
• IEEE 1588 (Master o Slave) Syncronization or viaNTP.
• Option: Syncronization via GPS Module or viaIRIG-B.
Interfaces
• 2 Ethernet 10 / 100Mbps connectors configurable asSwitch / Trunck / Hub for connection to the controlcenter.
• One optocoupled serial RS232/RS485 port on RJ45connector
• Modbus RTU or TCP/IP. Version Master or Slave
• 2 EtherCat Master connector RJ45 or one fiber optic
connector ST/SC
Protocols
• IEC-60870-5-104/101 Controlled / Controlling e re-verse mode up to 16 contemporary sessions
• IEC-61158 :
– Ethercat
– Ethernet/IP
– Modbus RTCS.
• Modbus RTU both master and slave
• IEC-62351 parte 3,5,8,9.
• FTP/HTTP/TELNET/SNTP/SNMP
Diagnostics
• Front LEDs for Reset, BUS access control, Run,1PPS.
• Serial of debug on backplane.
Battery
• 1 CR2032 3V , for backup of SRAM and RTC.
Operating temperature
• −40◦C ÷ 85◦C
Order codes
• 029-AXCPUDU-1000 (CPU Coldfire 32Bit80MHz, 1Mb Flash, 2MB Sram, 1 serial, 2 ch Cop-per RJ45 Ethernet 10/100, GPS Precision TimeModule)
e-mail: [email protected] http://www.ailux.eu REV-05 19-2018 5
Energy
Managem
entSystem
Datasheet AXRTU-62351
CPU SLAVE Model CPU-DU GSM/GPRS
32Bit microprocessor card controlled by a CPUMASTER. Interface with GSM/GPRS/UMTS mobile
networks.
Features
• 32bits CPU Coldfire + crypto unit (IEC/TS 62351)
• 2MB of battery backup SRAM
• 1MB of Flash for firmware
• 1MB of Flash as disk memory
• 128KB of Flash for cache/log
• Integrated RTC 32KHz
• Micro SD slot up to 16Gb card
• USB 2.0 interface with Micro-B connector
Interfaces
• Module for access to mobile networks(GSM/GPRS/UMTS /EDGE/HSPA+) with SIMslot;
• Syncronization by GSM/UMTS net or by CPU-MASTER;
• One optocoupled serial RS232/RS485 port on RJ45connector;
Protocols
• IEC-60870-5-104/101 Controlled / Controlling e re-verse mode up to 16 contemporary sessions with con-nection on APN or a connection in PtoP
• IEC-61158 :
– Ethercat
– Ethernet/IP
– Modbus RTCS.
• Modbus RTU both master and slave
• IEC-62351 parts 3,5,8,9.
• FTP/HTTP/TELNET/SNTP/SNMP
Diagnostics
• Front LEDs for Reset, BUS access control, Run, SIMStatus, mobile net autentication
• Serial of debug on backplane Battery
• 1 CR2032 3V , for backup of SRAM and RTC.
Operating temperature
• −40◦C ÷ 85◦C
Order codes
• 030-AXCPUDU-1001 (CPU Coldfire 32Bit80MHz, 1Mb Flash, 2MB Sram, 1 serial,GPRS/UMTS Module)
e-mail: [email protected] http://www.ailux.eu REV-05 19-2018 6
Energy
Managem
entSystem
Datasheet AXRTU-62351
CPU SLAVE Model CPU-DUP COM
32Bit microprocessor card controlled by a CPUMASTER. Interfaces are Ethernet / Ethercat / Serials.
Onboard multiprotocol communications.
Features
• 32bits CPU Coldfire + crypto unit (IEC/TS 62351)
• 4MB of battery backup SRAM
• 1MB of Flash for firmware
• 1MB of Flash as disk memory
• 128KB of Flash for cache/log
• Integrated RTC 32KHz
• Micro SD slot up to 16Gb card
• USB 2.0 interface with Micro-B connector
Interfaces
• 3 Ethernet 10 / 100Mbps connectors configurable asSwitch / Trunck / Hub for connection to the controlcenter.
• One optocoupled serial RS232/RS485 port on RJ45connector;
• Option M-BUS master interface up to 80 slaves
• Option WM-BUS interface
• Option LoRaWan interface
• Syncronization by CPU-MASTER;
Protocols
• IEC-60870-5-104/101 Controlled / Controlling up to16 contemporary sessions.
• IEC-61850 Master /Slave /Goose
• IEC-61158 :
– Ethercat
– Ethernet/IP
– Modbus RTCS.
• Modbus RTU both master and slave
• IEC-62351 parts 3,5,8,9.
• (S)FTP/HTTP(S)/TELNET/SSH/SNTP/SNMP
Diagnostics
• Front LEDs for Reset, BUS access control, Run
• Serial of debug on backplane
Battery
• 1 CR2032 3V , for backup of SRAM and RTC.
Operating temperature
• −40◦C ÷ 85◦C
Order codes
• 031-AXCPUDU-P-1000 (CPU Coldfire 32Bit80MHz, 1Mb Flash, 4MB Sram, 1 serial, 3 ch RJ45Copper Ethernet 10/100)
e-mail: [email protected] http://www.ailux.eu REV-05 19-2018 7
Energy
Managem
entSystem
Datasheet AXRTU-62351
CPU MASTER/SLAVE Model CPU-K64
32Bit microprocessor card controlled by a CPUMASTER. Interfaces are Ethernet / Ethercat / Serials.
Onboard multiprotocol communications.
Features
• CPU ARM Cortex-M4 K64/K66 120/180MHz
• Hardware Encryption support DES, 3DES, AES(IEC/TS 62351)
• 2MB of battery backup SRAM
• 1MB of Flash for firmware
• 1MB of Flash as memory disk
• 128KB Flash for cache/log
• RTC 32KHz
• Micro SD slot up to 16Gb card
• USB 2.0 interface with Micro-B connector
Interfaces
• 1 Ethernet 10/100Mbps connettor RJ45
• 2 Ethernet 10/100Mbps fiber optic Scor ST connec-ctors. Configurable as Switch / Trunck / Hub forconnection to the control center.
• One optocoupled serial RS232/RS485 port on RJ45connector for debug or Modbus RTU;
• Syncronization by CPU-MASTER;
Protocols
• IEC-60870-5-104/101 Controlled / Controlling e re-verse mode up to 16 contemporary sessions
• IEC-61850 Master /Slave /Goose / IEEE1588
• IEC-61158 :
– Ethercat
– Ethernet/IP
– Modbus RTCS.
• Modbus RTU both master and slave
• IEC-62351 parts 3,5,7,8,9.
• (S)FTP/HTTP(S)/TELNET/SSH/SNTP/SNMP
Diagnostics
• Front LEDs for Reset, BUS access control, Run
• Serial of debug on backplane
Battery
• 1 CR2032 3V , for backup of SRAM and RTC.
Operating temperature
• −40◦C ÷ 85◦C
Order codes
• 019-AXCPUK64-1000 (CPU Arm CortexK64/K66 120MHz, 1Mb Flash, 2MB Sram, Hard-ware Encryption,1 serial, 4 ch RJ45 Copper Ethernet10/100)
• 020-AXCPUK64-1001 (CPU Arm CortexK64/K66 120MHz, 1Mb Flash, 2MB Sram, Hard-ware Encryption,1 serial, 4 ch RJ45 Copper Ethernet10/100, GPS Precision Time Module)
e-mail: [email protected] http://www.ailux.eu REV-05 19-2018 8
Energy
Managem
entSystem
Datasheet AXRTU-62351
• 021-AXCPUK64-1002 (CPU Arm CortexK64/K66 120MHz, 1Mb Flash, 2MB Sram, Hard-ware Encryption,1 serial, 3 ch RJ45 Copper Eth-ernet 10/100, 1300nm 100 Mb/s 1 ch MultimodeOptic Fiber 2 km link, SC connector)
• 022-AXCPUK64-1003 (CPU Arm CortexK64/K66 120MHz, 1Mb Flash, 2MB Sram, Hard-ware Encryption,1 serial, 3 ch RJ45 Copper Eth-ernet 10/100, 1300nm 100 Mb/s 1 ch MultimodeOptic Fiber 2 km link, ST connector)
• 023-AXCPUK64-1004 (CPU Arm CortexK64/K66 120MHz, 1Mb Flash, 2MB Sram, Hard-ware Encryption,1 serial, 2 ch RJ45 Copper Eth-ernet 10/100, 1300nm 100 Mb/s 2 ch MultimodeOptic Fiber 2 km link, SC connector)
• 024-AXCPUK64-1005 (CPU Arm CortexK64/K66 120MHz, 1Mb Flash, 2MB Sram, Hard-ware Encryption,1 serial, 2 ch RJ45 Copper Eth-ernet 10/100, 1300nm 100 Mb/s 2 ch MultimodeOptic Fiber 2 km link, ST connector)
• 025-AXCPUK64-1012 (CPU Arm CortexK64/K66 120MHz, 1Mb Flash, 2MB Sram, Hard-
ware Encryption,1 serial, 3 ch RJ45 Copper Eth-ernet 10/100, 1300nm 100 Mb/s 1 ch MultimodeOptic Fiber 2 km link, SC connector, 820nm OpticFiber input IrigB Precision Time, ST connector)
• 026-AXCPUK64-1013 (CPU Arm CortexK64/K66 120MHz, 1Mb Flash, 2MB Sram, Hard-ware Encryption,1 serial, 3 ch RJ45 Copper Eth-ernet 10/100, 1300nm 100 Mb/s 1 ch MultimodeOptic Fiber 2 km link, ST connector, 820nm OpticFiber input IrigB Precision Time, ST connector)
• 027-AXCPUK64-1014 (CPU Arm CortexK64/K66 120MHz, 1Mb Flash, 2MB Sram, Hard-ware Encryption,1 serial, 2 ch RJ45 Copper Eth-ernet 10/100, 1300nm 100 Mb/s 2 ch MultimodeOptic Fiber 2 km link, SC connector, 820nm OpticFiber input IrigB Precision Time, ST connector)
• 028-AXCPUK64-1015 (CPU Arm CortexK64/K66 120MHz, 1Mb Flash, 2MB Sram, Hard-ware Encryption,1 serial, 2 ch RJ45 Copper Eth-ernet 10/100, 1300nm 100 Mb/s 2 ch MultimodeOptic Fiber 2 km link, ST connector, 820nm OpticFiber input IrigB Precision Time, ST connector)
e-mail: [email protected] http://www.ailux.eu REV-05 19-2018 9
Energy
Managem
entSystem
Datasheet AXRTU-62351
OPTOCOUPLED DIGITAL INPUT CARD 6U
The card RTU −DIG− 32IN − 6U Digital Input is a 32optocoupled Digital Inputs.
Features
• 32 optocoupled Digital Inputs.
Signals type:
• Single signals
• Double signals
• Digital measurements: pulse counter up to 1kHZ fre-quency
Programmable SW Functions:
• digital filter
• Programmable time for inconsistent positions
• Reading inversion of logic status
Input range :
• Direct current from 12V (1mA) to 300 (7mA)
• Alternating current from 10Vac (1mA) a 250 Vac(7mA)
Resolution
• The resolution of events is 1ms
Connections
• 48p DIN41612 connector for the Inputs
Isolation
• from Input to Backplane: 5kV
Diagnostics
• front LEDs for Input status and card satus
Dimensions
• Eurocard 233.4x160mm. Front 6U x front 6TE
Operating temperature
• −40◦C ÷ 85◦C
Order codes
• 036-AXRTU-INPUT-2000 (Eurocard 6U, 32Optocoupled Inputs, 12..300 Vdc, 10..250Vac, 5kVisolation, to field with 48p DIN41612 connector)
e-mail: [email protected] http://www.ailux.eu REV-05 19-2018 10
Energy
Managem
entSystem
Datasheet AXRTU-62351
OPTOCOUPLED DIGITAL INPUT CARD 3U
The card RTU −DIG− 32IN − 3U Digital Input is a 32optocoupled Digital Inputs.
Features
• 32 optocoupled Digital Inputs.
Signals type:
• Single signals
• Double signals
• Digital measurements: pulse counter up to 1kHZ fre-quency
Programmable SW Functions:
• digital filter
• Programmable time for inconsistent positions
• Reading inversion of logic status
Input range :
• Direct current from 12V (1mA) to 300 (7mA)
• Alternating current from 10Vac (1mA) a 250 Vac(7mA)
Resolution
• The resolution of events is 1ms
Connections
• 48p DIN41612 connector for the Inputs
Isolation
• from Input to Backplane: 1kV
Diagnostics
• front LEDs for Input status and card satus
Dimensions
• Eurocard 100x160mm. Front 3U x front 6TE
Operating temperature
• −40◦C ÷ 85◦C
Order codes
• 035-AXRTU-INPUT-1000 (Eurocard 3U, 32Optocoupled Inputs, 12..300 Vdc, 10..250Vac, 1kVisolation, to field with 110p Hard-Metric connector)
e-mail: [email protected] http://www.ailux.eu REV-05 19-2018 11
Energy
Managem
entSystem
Datasheet AXRTU-62351
RELAY DIGITAL OUTPUT CARD 6U
The card RTU −DIG− 16OUT − 6U Output is a 16Relay Digital Outputs.
Features
• 16 Relay Digital Outputs
Contacts range (Finder 34 Series)
• Breaking capacity DC: 0.2A @ 110Vdc, 0.12A @220Vdc
• Rated current: 6A @ 250VacOption with controls and poles management
– Single Commands
– Double Commands (ON/OFF)
– Adjustment Controls (Increase / Decrease)
– Controls 1 pole, 1.5 poles, 2 poles.
Programmable functions SW:
– Pulse durantion
– Control of the command (locked contacts, pres-ence of command voltage, verification of the cir-cuit impedance for external short circuit anal-ysis and open circuit analysis)
Connections
• 48p DIN41612 connector for the Inputs
• Isolation
• from contacts to Backplane: 5kV
• Diagnostics
• Front LEDs for outputs status and autotest push-button
Dimension
• Eurocard 233.4x160mm. Front 6Ux6TE
Operating temperature
• −40◦C ÷ 85◦C
Order codes
• 039-AXRTU-OUTPUT-2000 (Eurocard 6U, 16Relay Output, 6A @ 250Vac, 200mA @ 110Vdc, 5kVisolation, to field with 48p DIN41612 connector)
• 040-AXRTU-OUTPUT-2001 (Eurocard 6U, 16Relay Output, 6A @ 250Vac, 200mA @ 110Vdc, 5kVisolation, Controls 1 pole, 1.5 poles, 2 poles, to fieldwith 48p DIN41612 connector)
e-mail: [email protected] http://www.ailux.eu REV-05 19-2018 12
Energy
Managem
entSystem
Datasheet AXRTU-62351
RELAY DIGITAL OUTPUT CARD 3U
The card RTU −DIG− 16OUT − 3U Output is a 16Relay Digital Outputs.
Features
• 16 Relay Digital Outputs
Contacts range (Finder 34 Series)
• Breaking capacity DC: 0.2A @ 110Vdc, 0.12A @220Vdc
• Rated current: 6A @ 250VacOption with controls and poles management
– Single Commands
– Double Commands (ON/OFF)
– Adjustment Controls (Increase / Decrease)
– Controls 1 pole, 1.5 poles, 2 poles.
Programmable functions SW:
– Pulse durantion
– Control of the command (locked contacts, pres-ence of command voltage, verification of the cir-cuit impedance for external short circuit anal-ysis and open circuit analysis)
Connections
• 48p DIN41612 connector for the Inputs
• Isolation
• from contacts to Backplane: 1kV
• Diagnostics
• Front LEDs for outputs status and autotest push-button
Dimension
• Eurocard 100x160mm. Front 3Ux6TE
Operating temperature
• −40◦C ÷ 85◦C
Order codes
• 037-AXRTU-OUTPUT-1000 (Eurocard 3U, 16Relay Output, 6A @ 250Vac, 200mA @ 110Vdc, 1kVisolation, to field with 110p Hard-Metric connector)
• 038-AXRTU-OUTPUT-1001 (Eurocard 3U, 16Relay Output, 6A @ 250Vac, 200mA @ 110Vdc, 1kVisolation, Controls 1 pole, 1.5 poles, 2 poles, to fieldwith 110p Hard-Metric connector)
e-mail: [email protected] http://www.ailux.eu REV-05 19-2018 13
Energy
Managem
entSystem
Datasheet AXRTU-62351
12 INPUT/OUTPUT ANALOG CARD 6U
The card RTU −AN − 12 − IN/OUT − 6U Analog I/Ois a 12 individually isolated analog inputs or outputs
with software configurable range
Features
• 8÷10 optocoupled analog Inputs and 2÷4 optocou-pled analog Outputs. ADC Resolution: 12bit.Each of them can be programmed as:
Currents:
• ±3, 75mA;±5mA;±7, 5mA;±10mA;±20mA; 4 ÷20mA
Voltages:
• ±1V ;±2, 5V ;±3, 75V ;±5V ;±7, 5V ;±10V
Resolution:
11bit + sign
Functions:
• Power Meter
• Ammeter
• Voltmeter
• Varmeter
• Protection functions
Connections
• 48p DIN41612 connector for the Inputs/Outputs
Isolation
• From Input/Output and Backplane: 4.2kV
Diagnostics
• Front LEDs for Input/Output status
Dimension
• Eurocard 233.4x160mm. Front 6Ux6TE
Operating temperature
• −40◦C ÷ 85◦C
Order codes
• 044-AXRTU-ANALOG-2000 (Eurocard 6U, 12Analog inputs, 12 bit, many programmable Voltageand Currents span, 4.2kV isolation, to field with 48pDIN41612 connector)
• 045-AXRTU-ANALOG-2001 (Eurocard 6U, 10Analog inputs, 2 Analog outputs,12 bit, many pro-grammable Voltage and Currents span, 4.2kV isola-tion, to field with 48p DIN41612 connector)
• 046-AXRTU-ANALOG-2002 (Eurocard 6U, 8Analog inputs, 4 Analog outputs,12 bit, many pro-grammable Voltage and Currents span, 4.2kV isola-tion, to field with 48p DIN41612 connector)
e-mail: [email protected] http://www.ailux.eu REV-05 19-2018 14
Energy
Managem
entSystem
Datasheet AXRTU-62351
12 INPUT/OUTPUT ANALOG CARD 3U
The card RTU −AN − 12 − IN/OUT − 3U Analog I/Ois a 12 individually isolated analog inputs or outputs
with software configurable range
Features
• 8÷10 optocoupled analog Inputs and 2÷4 optocou-pled analog Outputs. ADC Resolution: 12bit.Each of them can be programmed as:
Currents:
• ±3, 75mA;±5mA;±7, 5mA;±10mA;±20mA; 4 ÷20mA
Voltages:
• ±1V ;±2, 5V ;±3, 75V ;±5V ;±7, 5V ;±10V
Resolution:
11bit + sign
Functions:
• Power Meter
• Ammeter
• Voltmeter
• Varmeter
• Protection functions
Connections
• 48p DIN41612 connector for the Inputs/Outputs
Isolation
• From Input/Output and Backplane: 1kV
Diagnostics
• Front LEDs for Input/Output status
Dimension
• Eurocard 100x160mm. Front 3Ux6TE
Operating temperature
• −40◦C ÷ 85◦C
Order codes
• 041-AXRTU-ANALOG-1000 (Eurocard 3U, 12Analog inputs, 12 bit, many programmable Voltageand Currents span, 1kV isolation, to field with 110pHard-Metric connector)
• 042-AXRTU-ANALOG-1001 (Eurocard 3U, 10Analog inputs, 2 Analog outputs,12 bit, many pro-grammable Voltage and Currents span, 1kV isola-tion, to field with 110p Hard-Metric connector)
• 043-AXRTU-ANALOG-1002 (Eurocard 3U, 8Analog inputs, 4 Analog outputs,12 bit, many pro-grammable Voltage and Currents span, 1kV isola-tion, to field with 110p Hard-Metric connector)
e-mail: [email protected] http://www.ailux.eu REV-05 19-2018 15
Energy
Managem
entSystem
Datasheet AXRTU-62351
Power Supply 24-48-110Vdc-230Vac/+5V and +24V, 3U
Features
• Dimension
• Eurocard 100x160mm. Front 3Ux6TE
• Input voltages:
• 9..36 Vdc, 24Vdc nominal
• 18..75 Vdc, 48Vdc nominal
• 43..160 Vdc, 110Vdc nominal
• 90..260 Vac, 230Vac nominal
• Main Output Voltge:
• +5V, 40W
• Auxiliary Output Voltage:
• +24V, 10W
• Tolerance:
• -20 + 15 �
• Protections:
• Overcurrents input protection
• Overvoltage input protection
• EMI CISPR22/EN55022 CLASS B
• EFT IEC/EN61000-4-4 ±2KV
• SURGE IEC/EN61000-4-5 line to line ±1KV /lineto ground ±2KV
• Front Status LED:
• LED for Main and Auxiliary output voltage
Operating temperature
• −40◦C ÷ 85◦C
Order codes
• 011-AXRTU-PS-1000 (Eurocard 3U, front inletInput Voltage Range 9..36 Vdc, 24Vdc nominal,Main Vout 5Vdc 40W, Aux Vout 24Vdc 10W, EFTIEC/EN61000-4-4 2KV, SURGE IEC/EN61000-4-5line to line 1KV, line to ground 2KV)
e-mail: [email protected] http://www.ailux.eu REV-05 19-2018 16
Energy
Managem
entSystem
Datasheet AXRTU-62351
• 012-AXRTU-PS-1001 (Eurocard 3U, front inletInput Voltage Range 18..72 Vdc, 48Vdc nominal,Main Vout 5Vdc 40W, Aux Vout 24Vdc 10W, EFTIEC/EN61000-4-4 2KV, SURGE IEC/EN61000-4-5line to line 1KV, line to ground 2KV)
• 013-AXRTU-PS-1002 (Eurocard 3U, front inletInput Voltage Range 43..160 Vdc, 110Vdc nominal,Main Vout 5Vdc 40W, Aux Vout 24Vdc 10W, EFT
IEC/EN61000-4-4 2KV, SURGE IEC/EN61000-4-5line to line 1KV, line to ground 2KV)
• 014-AXRTU-PS-1003 (Eurocard 3U, front inletInput Voltage Range 90..260 Vac, 230Vac nominal,Main Vout 5Vdc 40W, Aux Vout 24Vdc 10W, EFTIEC/EN61000-4-4 2KV, SURGE IEC/EN61000-4-5line to line 1KV, line to ground 2KV)
e-mail: [email protected] http://www.ailux.eu REV-05 19-2018 17
Energy
Managem
entSystem
Datasheet AXRTU-62351
Power Supply 24-48-110Vdc-230Vac/+5V and +24V, 6U
Features
• Dimension
• Eurocard 233.4x160mm. Front 6Ux6TE
• Input voltages:
• 9..36 Vdc, 24Vdc nominal
• 18..75 Vdc, 48Vdc nominal
• 43..160 Vdc, 110Vdc nominal
• 90..260 Vac, 230Vac nominal
• Main Output Voltge:
• +5V, 40W
• Auxiliary Output Voltage:
• +24V, 20W
• Tolerance:
• -20 + 15 �
• Protections and EMC:
• Overcurrents input protection
• Overvoltage input protection
• EMI CISPR22/EN55022 CLASS B
• EFT IEC/EN61000-4-4 ±4KV
• SURGE IEC/EN61000-4-5 line to line ±2KV /lineto ground ±4KV
• Front Status LED:
• LED for Main and Auxiliary output voltage
Operating temperature
• −40◦C ÷ 85◦C
Order codes
• 015-AXRTU-PS-2000 (Eurocard 6U, rear inletInput Voltage Range 9..36 Vdc, 24Vdc nominal,Main Vout 5Vdc 40W, Aux Vout 24Vdc 20W, EFTIEC/EN61000-4-4 4KV, SURGE IEC/EN61000-4-5line to line 2KV, line to ground 4KV, 48p DIN41612connector)
e-mail: [email protected] http://www.ailux.eu REV-05 19-2018 18
Energy
Managem
entSystem
Datasheet AXRTU-62351
• 016-AXRTU-PS-2001 (Eurocard 6U, rear inletInput Voltage Range 18..72 Vdc, 48Vdc nominal,Main Vout 5Vdc 40W, Aux Vout 24Vdc 20W, EFTIEC/EN61000-4-4 4KV, SURGE IEC/EN61000-4-5line to line 2KV, line to ground 4KV, 48p DIN41612connector)
• 017-AXRTU-PS-2002 (Eurocard 6U, rear inletInput Voltage Range 43..160 Vdc, 110Vdc nominal,Main Vout 5Vdc 40W, Aux Vout 24Vdc 20W, EFT
IEC/EN61000-4-4 4KV, SURGE IEC/EN61000-4-5line to line 2KV, line to ground 4KV, 48p DIN41612connector)
• 018-AXRTU-PS-2003 (Eurocard 6U, rear inletInput Voltage Range 90..260 Vac, 230Vac nominal,Main Vout 5Vdc 40W, Aux Vout 24Vdc 20W, EFTIEC/EN61000-4-4 4KV, SURGE IEC/EN61000-4-5line to line 2KV, line to ground 4KV, 48p DIN41612connector)
e-mail: [email protected] http://www.ailux.eu REV-05 19-2018 19
Energy
Managem
entSystem
Datasheet AXRTU-62351
Fig
ure
1:
Eth
ern
etri
ng
cable
e-mail: [email protected] http://www.ailux.eu REV-05 19-2018 20
Energy
Managem
entSystem
Datasheet AXRTU-62351
Fig
ure
2:
Eth
erC
at
(dou
ble
)red
un
dan
cy
e-mail: [email protected] http://www.ailux.eu REV-05 19-2018 21
Energy
Managem
entSystem
Datasheet AXRTU-62351
Fig
ure
3:
Mod
bu
s(d
ou
ble
)rin
gca
ble
e-mail: [email protected] http://www.ailux.eu REV-05 19-2018 22
Energy
Managem
entSystem
Datasheet AXRTU-62351
Fig
ure
4:
Inte
gra
ted
sub
stati
on
au
tom
ati
on
e-mail: [email protected] http://www.ailux.eu REV-05 19-2018 23
Energy
Managem
entSystem
Datasheet AXRTU-62351
AiLux SrlLarge Via Serpente 107
25131 - Brescia - Italy (EU)Tel +39 030 3539165
e-mail : [email protected]