AXIS A1001 installation with24 volt lock
Adhere to local life safety code in all installations.Ensure that your power supplies and relays are rated for the intended purposes.Illustration does not depict cabling for reader, REX, Door monitor, battery backup and UPS.
AXIS Entry ManagerProgramming
Application
1. Con�gure Lock 1 for Relay
2. Depending on your lock type, con�gureLock 1 Relay for
Relay open = Locked for a fail-secure lockRelay open = Unlocked for a fail-safe lock
3. Wire the RELAY|PWR connector accordingto the drawing
> One-door solution with 24 V lock
Lock 1:12 V
Relay
Relay Relay open = LockedRelay open = LockedRelay open = Unlocked
READER I/O 1
DOOR IN 1 DOOR IN 2 LOCK
+MIC- +SPK-
AUDIOAUX
A- B+ A- B+ D0 D1 A- B+ A- B+ D0 D1
- 12V
IO3
IO4
IO5
IO6
READER DATA 1 READER DATA 2
DC IN
RELAY | PWR*REL*- - 12
V24V
- H1 - H2- IN1 - IN2 - IN3 - IN4- +
- 3V IO1
IO2
READER I/O 2- 12
VIO7
IO8
IO9
IO10
-+
AXIS T8127 60 W Splitter12/24 V DC
High PoE Switch (802.3at)
24 volt lock
Lock 1
AXIS A1001 installation withdual electric strikes
Voltage is determined by the power supply voltage out.
Adhere to local life safety code in all installations.Ensure that your power supplies and relays are rated for the intended purposes.Illustration does not depict cabling for reader, REX, Door monitor, battery backup and UPS.
AXIS Entry ManagerProgramming
Application
1. Con�gure Lock 1 for 12 V and Fail-secure
3. Depending on your lock type, con�gureLock 2 Relay for
Relay open = Locked for a fail-secure lockRelay open = Unlocked for a fail-safe lock
4. Wire the LOCK connector and theRELAY|PWR connector according tothe drawing
2. Con�gure Lock 2 for Relay
> Simple two-door solution with one doorusing external power
Lock 1:12 V
Relay Relay open = LockedRelay open = LockedRelay open = Unlocked
Fail-secure
Lock 2:12 V
Relay
READER I/O 1
DOOR IN 1 DOOR IN 2 LOCK
+MIC- +SPK-
AUDIOAUX
A- B+ A- B+ D0 D1 A- B+ A- B+ D0 D1
- 12V
IO3
IO4
IO5
IO6
READER DATA 1 READER DATA 2
DC IN
RELAY | PWR*REL*- - 12
V24V
- H1 - H2- IN1 - IN2 - IN3 - IN4- +
- 3V IO1
IO2
READER I/O 2- 12
VIO7
IO8
IO9
IO10
Lock 1 Lock 2
12 volt DCElectric Strike
12/24 volt DCElectric Strike
PoE Switch
Door Power Supply
12/24+12/24-
AXIS A1001 installation with duallocks and external power supply
The AXIS A1001 lock output connects to the separate auxiliaryrelay power input. 12/24 volts DC+ from a separate door powersupply connects to the C terminal of the slave relay. This transfersto the NO terminal, pushing power to the lock.
Adhere to local life safety code in all installations.Ensure that your power supplies and relays are rated for the intended purposes.Illustration does not depict cabling for reader, REX, Door monitor, battery backup and UPS.
AXIS Entry ManagerProgramming
Application
1. Con�gure Lock 1 for 12 V and Fail-secure
3. Depending on your lock type, con�gureLock 2 Relay for
Relay open = Locked for a fail-secure lockRelay open = Unlocked for a fail-safe lock
4. Wire the LOCK connector and theRELAY|PWR connector according tothe drawing
2. Con�gure Lock 2 for Relay
> Two-door solution with high current locks
> Suggested for use with existing power andrelay
Lock 1:12 V
Relay Relay open = LockedRelay open = LockedRelay open = Unlocked
Fail-secure
Lock 2:12 V
Relay
READER I/O 1
DOOR IN 1 DOOR IN 2 LOCK
+MIC- +SPK-
AUDIOAUX
A- B+ A- B+ D0 D1 A- B+ A- B+ D0 D1
- 12V
IO3
IO4
IO5
IO6
READER DATA 1 READER DATA 2
DC IN
RELAY | PWR*REL*- - 12
V24V
- H1 - H2- IN1 - IN2 - IN3 - IN4- +
- 3V IO1
IO2
READER I/O 2- 12
VIO7
IO8
IO9
IO10
Relay
Lock 1 Lock 2
Electric Strike12/24 volt DC12/24 volt DCElectric Strike
Door Power Supply
12/24+ 12/24-12/24+ 12/24-
POS+
C
NC
NO
NEG-
C
NC
NO
PoE Switch
AXIS A1001 installation withdual magnetic locks and external power supply
The AXIS A1001 lock output connects to the separate auxiliaryrelay power input. 12/24 volts DC+ from a separate door powersupply connects to the C terminal of the slave relay. This transfersto the NO terminal, pushing power to the lock.
Adhere to local life safety code in all installations.Ensure that your power supplies and relays are rated for the intended purposes.Illustration does not depict cabling for reader, REX, Door monitor, battery backup and UPS.
AXIS Entry ManagerProgramming
Application
1. Con�gure Lock 1 for 12 V and Fail-secure
3. Depending on your lock type, con�gureLock 2 Relay for
Relay open = Locked for a fail-secure lockRelay open = Unlocked for a fail-safe lock
4. Wire the LOCK connector and theRELAY|PWR connector according tothe drawing
2. Con�gure Lock 2 for Relay
> Two-door solution with high current locks
> Suggested for use with existing power andrelay
Lock 1:12 V
Relay Relay open = LockedRelay open = LockedRelay open = Unlocked
Fail-secure
Lock 2:12 V
Relay
READER I/O 1
DOOR IN 1 DOOR IN 2 LOCK
+MIC- +SPK-
AUDIOAUX
A- B+ A- B+ D0 D1 A- B+ A- B+ D0 D1
- 12V
IO3
IO4
IO5
IO6
READER DATA 1 READER DATA 2
DC IN
RELAY | PWR*REL*- - 12
V24V
- H1 - H2- IN1 - IN2 - IN3 - IN4- +
- 3V IO1
IO2
READER I/O 2- 12
VIO7
IO8
IO9
IO10
12/24 volt Magnetic Lock
Lock 1
12/24 volt Magnetic Lock
Lock 2
Door Power Supply
12/24+ 12/24-12/24+ 12/24-
PoE Switch
Relay
POS+
C
NC
NO
NEG-
C
NC
NO
AXIS A1001 installation withdual integrated locksets
The AXIS A1001 lock output connects to the separate auxiliaryrelay power input. 12/24 volts DC+ from a separate door powersupply connects to the C terminal of the slave relay. This transfersto the NO terminal, pushing power to the lock.
Adhere to local life safety code in all installations.Ensure that your power supplies and relays are rated for the intended purposes.Illustration does not depict cabling for reader, REX, Door monitor, battery backup and UPS.
> AXIS T8127 60 W Splitter 12/24 V DC
High PoE Splitter
> AXIS T81B22 DC 30 W Midspan 1-port> AXIS T8133 Midspan 30 W 1-port> AXIS T8123-E Outdoor Midspan 30 W 1-port
30 Watt Midspan options
AXIS Entry ManagerProgramming
Application
1. Con�gure Lock 1 for 12 V and Fail-secure
3. Depending on your lock type, con�gureLock 2 Relay for
Relay open = Locked for a fail-secure lockRelay open = Unlocked for a fail-safe lock
4.
2. Con�gure Lock 2 for Relay
Wire the LOCK connector and theRELAY|PWR connector according tothe drawing
> Two-door solution with high current locks
Lock 1:12 V
Relay Relay open = LockedRelay open = LockedRelay open = Unlocked
Fail-secure
Lock 2:12 V
Relay
READER I/O 1
DOOR IN 1 DOOR IN 2 LOCK
+MIC- +SPK-
AUDIOAUX
A- B+ A- B+ D0 D1 A- B+ A- B+ D0 D1
- 12V
IO3
IO4
IO5
IO6
READER DATA 1 READER DATA 2
DC IN
RELAY | PWR*REL*- - 12
V24V
- H1 - H2- IN1 - IN2 - IN3 - IN4- +
- 3V IO1
IO2
READER I/O 2- 12
VIO7
IO8
IO9
IO10
IntegratedLockset
Lock 1
Integrated Lockset
Lock 2
Data + Power Data
30 W Midspan
PoE IN
Splitter
12/24- 12/24+
Data OUT
Switch
Relay
POS+
C
NC
NO
NEG-
C
NC
NO
AXIS A1001 installation withdual external auxiliary devices
Adhere to local life safety code in all installations.Ensure that your power supplies and relays are rated for the intended purposes.Illustration does not depict cabling for reader, REX, Door monitor, battery backup and UPS.
> AXIS T8127 60 W Splitter 12/24 V DC
High PoE Splitter
> AXIS T81B22 DC 30 W Midspan 1-port> AXIS T8133 Midspan 30 W 1-port> AXIS T8123-E Outdoor Midspan 30 W 1-port
30 Watt Midspan options
AXIS Entry ManagerProgramming
Application
1. Con�gure Lock 1 for 12 V and Fail-secure
2. Con�gure Lock 2 for 12 V and Fail-secure
4. Wire the LOCK connector according tothe drawing
> Solution for using relays to control devicessuch as HVAC, gates, and other auxiliarydevices
Lock 1:12 V
Relay
Fail-secure
Lock 2:12 V
Relay
Fail-secure
READER I/O 1
DOOR IN 1 DOOR IN 2 LOCK
+MIC- +SPK-
AUDIOAUX
A- B+ A- B+ D0 D1 A- B+ A- B+ D0 D1
- 12V
IO3
IO4
IO5
IO6
READER DATA 1 READER DATA 2
DC IN
RELAY | PWR*REL*- - 12
V24V
- H1 - H2- IN1 - IN2 - IN3 - IN4- +
- 3V IO1
IO2
READER I/O 2- 12
VIO7
IO8
IO9
IO10
Data + Power Data
30 W Midspan
PoE IN Data OUT
Splitter
12/24- 12/24+
Energy Management
(add this wire for wet contact)
Switch
Relay
POS+
C
NC
NO
NEG-
C
NC
NO
Relay
POS+
C
NC
NO
NEG-
C
NC
NO
AXIS A1001 installation withdual magnetic locks
Voltage is determined by the POE splitter voltage out.
Adhere to local life safety code in all installations.Ensure that your power supplies and relays are rated for the intended purposes.Illustration does not depict cabling for reader, REX, Door monitor, battery backup and UPS.
> AXIS T8127 60 W Splitter 12/24 V DC
High PoE Splitter
> AXIS T81B22 DC 30 W Midspan 1-port> AXIS T8133 Midspan 30 W 1-port> AXIS T8123-E Outdoor Midspan 30 W 1-port
30 Watt Midspan options
AXIS Entry ManagerProgramming
Application
1. Con�gure Lock 1 for 12 V and Fail-safe
2. Con�gure Lock 2 for Relay
3. Con�gure Lock 2 Relay for
Relay open = Unlocked (fail-safe lock)
4. Wire the LOCK connector and theRELAY|PWR connector according tothe drawing
> Two-door solution with one 12 V lock andone 12 or 24 V lock
Lock 1:12 V
Relay Relay open = UnlockedRelay open = LockedRelay open = Unlocked
Fail-safe
Lock 2:12 V
Relay
READER I/O 1
DOOR IN 1 DOOR IN 2 LOCK
+MIC- +SPK-
AUDIOAUX
A- B+ A- B+ D0 D1 A- B+ A- B+ D0 D1
- 12V
IO3
IO4
IO5
IO6
READER DATA 1 READER DATA 2
DC IN
RELAY | PWR*REL*- - 12
V24V
- H1 - H2- IN1 - IN2 - IN3 - IN4- +
- 3V IO1
IO2
READER I/O 2- 12
VIO7
IO8
IO9
IO10
Data + Power Data
30 W Midspan
PoE IN Data OUT
Splitter
12/24 volt Magnetic Lock
Lock 2
12 volt Magnetic Lock
Lock 1
12/24- 12/24+
Switch