Axial Effects of Borehole Design

Embed Size (px)

Citation preview

  • 7/29/2019 Axial Effects of Borehole Design

    1/8

    The importance of axial effects for borehole design of geothermalheat-pump systems

    D. Marcotte a,b,c,*, P. Pasquier a, F. Sheriffb, M. Bernier c

    a Golder Associates, 9200 lAcadie, Montreal, (Qc), H4N 2T2 Canadab CANMET Energy Technology Centre-Varennes, 1615 Lionel-Boulet Blvd., P.O. Box 4800, Varennes, (QC), J3X 1S6 Canadac Departement des genies civil, Geologique et des mines, Ecole Polytechnique de Montreal, C.P. 6079 Succ. Centre-ville, Montreal, (Qc), H3C 3A7 Canada

    a r t i c l e i n f o

    Article history:

    Received 13 May 2008

    Accepted 18 September 2009

    Available online 23 October 2009

    Keywords:

    Infinite line source

    Finite line source

    Ground loop heat exchangers

    Hybrid systems

    Underground water freezing

    a b s t r a c t

    This paper studies the effects of axial heat conduction in boreholes used in geothermal heat pump

    systems. The axial effects are examined by comparing the results obtained using the finite and infinite

    line source methods. Using various practical design problems, it is shown that axial effects are relatively

    important. Unsurprisingly, short boreholes and unbalanced yearly ground loads lead to stronger axial

    effects. In one example considered, it is shown that the borehole length is 15% shorter when axial

    conduction effects are considered. In another example dealing with underground water freezing, the

    amount of energy that has to be removed to freeze the ground is three times higher when axial effects

    are considered.

    2009 Elsevier Ltd. All rights reserved.

    1. Introduction

    Geothermal systems using ground-coupled closed-loop heat

    exchangers (GLHE) are becoming increasingly popular due to

    growing energy costs. Such a system is presented in Fig. 1.

    The operation of the system is relatively simple: a pump circu-

    lates a heat transfer fluid in a closed circuit from the GLHE to a heat

    pump (or a series of heat pumps). Typically, GLHE consists

    of boreholes that are 100150 m deep and have a diameter of

    1015 cm. The number of boreholes in the borefield can range from

    one, for a residence, to several dozens, in commercial applications.

    Furthermore, several borehole configurations (square, rectangular,

    L-shaped) are possible. Typically, a borehole consists of two pipes

    forming a U-tube (Fig. 1). The volume between these pipes and the

    borehole wall is usually filled with grout to enhance heat transferfrom the fluid to the ground. In some situations it is advantageous

    to design so-called hybrid systems in which a supplementary heat

    rejecter or extractor is used at peak conditions to reduce the length

    of the ground heat exchanger.

    Given the relatively high cost of GLHE, it is important to design

    them properly. Among the number of parameters that can be

    varied, the length and configuration of the borefield are important.

    There are basically two ways to design a borefield. The first method

    involves using successive thermal pulses (typically 10-years 1month 6 h) to determine the length based on a given configura-tion and minimum/maximum heat pump entering water temper-

    ature [8,3]. There are design software programs that perform these

    calculations. Some use the concept of the g-functions developed by

    Eskilson [5]. The g-functions are derived from a numerical model

    that, by construction, includes the axial effects. The other approach

    is to perform hourly simulation. This last approach is essential for

    design of hybrid systems in which supplemental heat rejection/

    injection is used. There are several software packages that can

    perform hourly borehole simulations. For example, TRNSYS [9] andEnergyPlus [4] use the DST [6] and the short-time step model [5],

    respectively. Even though these packages account for axial effects,

    they necessitate a high level of expertise. Furthermore, it is not

    easily possible to obtain ground temperature distributions like the

    ones shown later in this paper. In this paper hourly simulations are

    performed using the so-called finite and infinite line source

    approximations where the borehole is approximated by a line with

    a constant heat transfer rate per unit length. These approximations

    present, in a convenient analytical form, the solution to the tran-

    sient 2-D heat conduction problem. Despite their advantages,

    hourly simulations based on the line source approximation are

    * Corresponding author. Departement des genies civil, geologique et des mines,

    Ecole Polytechnique de Montreal, C.P. 6079 Succ. Centre-ville, Montreal, (Qc),

    H3C 3A7 Canada. Tel.: 1 514 340 4711x4620; fax: 1 514 340 3970.E-mail address: [email protected] (D. Marcotte).

    Contents lists available at ScienceDirect

    Renewable Energy

    j o u r n a l h o m e p a g e : w w w . e l s e v i e r . c o m / l o c a t e / r e n e n e

    0960-1481/$ see front matter 2009 Elsevier Ltd. All rights reserved.

    doi:10.1016/j.renene.2009.09.015

    Renewable Energy 35 (2010) 763770

    mailto:[email protected]://www.sciencedirect.com/science/journal/09601481http://www.elsevier.com/locate/renenehttp://www.elsevier.com/locate/renenehttp://www.sciencedirect.com/science/journal/09601481mailto:[email protected]
  • 7/29/2019 Axial Effects of Borehole Design

    2/8

    rarely used in routine design due to the perceived computational

    burden.

    The major difference between the finite and infinite line source

    lies in the treatment of axial conduction (at the bottom and top of

    the borehole) which is only accounted for in the former. Thetheoretical basis of the finite line source, although more involved

    than for the infinite line source, was first established by Ingersoll

    et al. [7]. It has been rediscovered recently by Zeng et al. [15] who

    improved the model by imposing a constant temperature at the

    ground surface. Lamarche and Beauchamp [11] have made a useful

    contribution to speed up the computation of Zengs model. Finally,

    Sheriff[13] extended Zengs model by permitting the borehole top

    to be located at some distance below the ground surface. She also

    did a detailed comparison of the finite and infinite line source

    responses, but did not examine the repercussion on borefield

    design.

    At first glance, the axial heat-diffusion is likely to decrease

    (increase) the borehole wall temperature in cooling (heating)

    modes respectively. Therefore, designing without consideringaxial effects appears to provide a safety factor for the design. But,

    is it really always the case? Moreover, are the borehole designs

    incorporating axial effects significantly different from those

    neglecting it? Under which circumstances are we expected to

    have significant design differences? These are the main questions

    we seek to answer. The main contribution of this research is to

    describe, using synthetic case studies, the impact of considering

    axial effects on the GLHE design. Our main finding is that for

    many realistic circumstances the axial effects cannot be neglec-

    ted. Therefore, design practices should be revised accordingly to

    include the axial effects.

    We first review briefly the theory for infinite and finite linesource models. Then, we present three different design situations.

    The first two situations involve the sizing of geothermal systems

    with and without the hybrid option, under three different hourly

    ground load scenarios. The last design problem examines the

    energy required and ground temperature evolution in the context

    of ground freezing for environmental purposes.

    2. Theoretical background

    The basic building block of both infinite and finite line source

    models is the change in temperature felt at a given location and

    time due to the effect of a constant point source releasing q0 units ofheat per second [7]:

    DTr; t q0

    4pksrerfc

    r

    2ffiffiffiffiffiat

    p

    (1)

    where erfc is the complementary error function, r the distance to

    the point heat source, and a is the ground thermal diffusivity.

    The line is then represented as a series of points equally spaced.

    In the limit, when the distance between point sources goes to zero,

    Fig. 1. Sketch of a GLHE system.

    Nomenclature

    a Thermal diffusivity (m2 s1)A, B, C, D Synthetic load model parameters (kW)

    b r/H

    Cs Ground volumetric heat capacity (Jm3 K1)

    erfc (x) Complementary error function

    (erfcx 12ffiffiffip

    pRN

    x et2 dt

    EWT Temperature of fluid entering the heat pump (K or C)Fo Fourier number, Fo at/r2ks Volumetric ground thermal conductivity (Wm

    1 K1)H Borehole length (m)

    HP Heat Pump

    q0 Radial heat transfer rate (W)q Radial heat transfer rate per unit length (Wm1)

    S Borehole spacing (m)

    r Distance to borehole (m)

    rb Borehole radius (m)

    Rb Borehole effective thermal resistance (Km W1)

    t Time

    DT(r, t) Ground temperature variation at time tand distance r

    from the borehole (K or

    C)

    Tf Fluid temperature (K orC)

    Tg Undisturbed ground temperature (K orC)

    Tw Temperature at borehole wall (K orC)

    u H2ffiffiffiffiat

    px, y Spatial coordinates (m)

    z Elevation (m)

    D. Marcotte et al. / Renewable Energy 35 (2010) 763770764

  • 7/29/2019 Axial Effects of Borehole Design

    3/8

    the combined effect felt at distance rfrom the source is obtained by

    integration along the line.

    2.1. Infinite line source

    In an infinite medium, the line-integration gives the so-called

    (infinite) line source model [7]:

    DTr; t q4pks

    ZNr2=4at

    eu

    udu (2)

    2.2. Finite line source

    In the case of a finite line source, the upper boundary is

    considered at constant temperature, taken as the undisturbed

    ground temperature [15]. This condition is represented by adding

    a mirror image finite line source with the same load, but opposite

    sign, as the real finite line. Then, integrating between the limits of

    the real and image line, one obtains [15],[13]:

    DTr; t;z q4pks

    ZH

    0

    0@erfc du2ffiffiffiffiatp du

    erfc

    d0u2ffiffiffiffiatp d0u

    1Adu (3)where du

    ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffir2 z u2

    qand d0u

    ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffir2 z u2

    q, z is the

    elevation of the point where the computation is done. The left part

    of the integrand in Equation (3) represents the contribution by the

    real finite line, the right part, the contribution of the image line.

    Fig. 2 shows the vertical temperature profile obtained with

    Equation (3) at radial distance r 2 m, after 200 days, and atr 1 m, after 2000 days of heat injection. The correspondinginfinite lines-source temperature is indicated as a reference. In this

    example,the borehole is 50 m long, the groundthermal parameters

    are ks 2.1 Wm1 K1 and Cs 2e06 Jm3 K1. The ground is inti-tially at 10 oC. The applied load is 60 W per m for a total heating

    power of 3000 W. As expected, the importance of axial effects and

    the discrepancy between infinite and finite models increases with

    the Fourier number (at/r2 4.54 and 181.4 for these two cases).

    In hourly simulations, the fluid temperature (Tf in Fig. 1) is

    required. This necessitates knowledge of the borehole thermal

    resistance Rb (i.e. from the fluid to the borehole wall), and of the

    borehole wall temperature (Tw in Fig. 1) [2]. The average borehole

    wall temperature it obtained by integrating Equation (3) along z.

    However, this is computationally intensive due to the double

    integration. Lamarche and Beauchamp [11] have shown, using an

    appropriate change of variables, how to simplify Equation (3) to

    a single integration. Accounting for small typos in [11] and [15] as

    noted by Sheriff[13], the average temperature difference, between

    a point located at distance rfrom the borehole and the undisturbed

    ground temperature, is given by:

    DTr; t q2pks

    0BBB@

    Zffiffiffiffiffiffiffiffiffib21p

    b

    erfcuzffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiz2 b2

    q dz DA

    Zffiffiffiffiffiffiffiffiffib24p

    ffiffiffiffiffiffiffiffiffib21perfcuz

    ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiz2 b2

    qdz DB

    1CCCA

    (4)

    where b r/H, r is the radial distance from the borehole center,u H

    2ffiffiffiffiat

    p and DA, and DB are given by:

    DA ffiffiffiffiffiffiffiffiffiffiffiffiffiffib

    2 1q

    erfc

    u

    ffiffiffiffiffiffiffiffiffiffiffiffiffiffib

    2 1q

    b erfcub

    eu2b21 eu2b2

    uffiffiffip

    p!

    and

    DB ffiffiffiffiffiffiffiffiffiffiffiffiffiffib2 1

    qerfc

    u

    ffiffiffiffiffiffiffiffiffiffiffiffiffiffib2 1

    q 0:5

    b erfcub

    ffiffiffiffiffiffiffiffiffiffiffiffiffiffib2 4q erfcu ffiffiffiffiffiffiffiffiffiffiffiffiffiffib2 4q

    eu2b

    21

    0:5

    eu2b2 eu2

    b

    24

    uffiffiffip

    p!

    10 12 14 16 18 20 22 24

    0

    10

    20

    30

    40

    50

    60

    Temperature (oC)

    Dept

    h(m)

    Vertical temperature profile

    Infline, r=2, t=200 d

    Fline, r=2, t=200 d

    Fline average, r=2, t=200 d

    Infline, r=1, t=2000 dFline, r=1, t=2000 d

    Fline average, r=1, t=2000 d

    Fig. 2. Vertical ground temperature profile at radial distances r1 m and r2 m after

    respectively 2000 days and 200 days, Fo (r1, t2000)181.4 and Fo (r2,

    t200)4.54.Constantheat injectionof 3000 W.Thermal parameters:ks2.1 Wm1 K1,

    Cs

    2e06 Jm3

    K1

    .

    0 1000 2000 3000 4000 50000

    2

    4

    6

    8

    10

    12

    Days

    T(oC)

    Infinite

    Finite

    FEM

    Fig. 3. Comparison of Finite and Infinite line source model with finite element model

    (FEM) for a 30 m borehole. Average temperature variation computed at 0.5 m from the

    borehole axis, over the borehole length. Constant heat transfer rate of 1000 W.

    Thermal parameters: ks

    2.1 Wm1

    K1

    , Cs

    2e06 Jm3

    K1

    .

    D. Marcotte et al. / Renewable Energy 35 (2010) 763770 765

  • 7/29/2019 Axial Effects of Borehole Design

    4/8

    The particular case r rb in Equation (4) gives the borehole walltemperature.

    2.3. Numerical validation

    Fig. 3 compares the variation in temperature over time

    computed with finite and infinite line source to the numerical

    results of a finite element model (FEM) constructed within

    COMSOL. The finite element model is 2-D with axial symmetry

    around the borehole axis. The ground is represented by a 50 m long

    and 50 m radius cylinder. The borehole is represented by a 30 m

    long and 0.075 m radius cylinder delivering 1000 W. The axis ofrevolution is located at the borehole center and constitutes

    a thermal insulation boundary whereas all external boundaries are

    set to the undisturbed ground temperature. Over 6000 triangular

    elements equipped with quadratic interpolating functions are used

    to discretize the model. The agreement between the FEM model

    and the finite line source is almost perfect, the maximum absolute

    difference in temperature over the 5000 days period being only

    0.019 oC.

    Fig. 4 compares the temperature obtained with the infinite

    and finite line source models, at r 1 m and r 0.075 m (atypical value for rb), with the thermal parameters specified

    above. A 1 oC temperature difference between the infinite and

    finite models is obtained after 2.5 y and 2 y, at 1 m and 0.075 m

    respectively. Note that the temperature reaches a plateau for the

    finite line source model indicating that a steady-state condition

    has been reached. In contrast, the infinite line source model

    exhibits a linear behavior.

    Fig. 5 shows the ground temperature, computed at a distance of1 m from the borehole, for increasing values of the borehole length.

    As expected, the finite line source solution reaches the infinite line

    source solution for long boreholes.

    0.001 0.01 0.1 1 10 100 100010

    20

    30

    40

    50

    60

    70

    80

    r=0.07

    5m

    r=1m

    Ground temperature

    Time (y)

    Temperature(oC)

    Fig. 4. Comparison of Finite (solid) and Infinite (broken) line source model, computed

    at distance 1 m and 0.075 m from the borehole. Constant heat transfer rate per unitlength of 100 W/m. Thermal parameters: ks2.1 Wm

    1 K1, Cs2e06 Jm3 K1.

    0 100 200 300 400 500 600 700 800 900 100012

    12.5

    13

    13.5

    Borehole length (m)

    Temperature

    (oC)

    Average temperature vs borehole length

    Infinite linesourceFinite linesource

    Fig. 5. Infinite vs finite line source average temperature along a vertical profile. The load

    is 20 W/m, thermal parameters: ks2.1 Wm1 K1, Cs2e06 Jm

    3 K1. Temperature

    computed after one year at r

    1 m from the borehole.

    1 2 3 4 5 6

    100

    0

    100

    Cooling (+) Heating () load

    Time (h)

    Load(kw)

    1 2 3 4 5 6200

    100

    0

    100

    Load decomposition

    Load(kw)

    Fig. 6. Principle of temporal superposition for variable loads.

    0 5 10 15 20 25 30 353

    3.5

    4

    4.5

    5

    5.5

    6

    6.5

    7

    7.5

    COP vs EWT

    EWT

    COP

    Cooling

    Heating

    Fig. 7. COP as a function of EWT.

    D. Marcotte et al. / Renewable Energy 35 (2010) 763770766

  • 7/29/2019 Axial Effects of Borehole Design

    5/8

    3. Design of complete geothermal systems

    In this section we compare the design length of borefields

    obtained with the finite and infinite line source models for given

    hourly ground load scenarios. These calculations imply that single

    borehole solutions will need to be superimposed spatially. We have

    already seen an instance of this principle of superposition while

    computing the line source solution from a series of constant point

    sources along a line [7], see Equations (1 and 2). The additivity of

    effects (variation in temperature) stems from the linear relationbetween q and DT, and the fact that energy is an extensive and

    additive variable. The temporal superposition also follows the same

    general principle of addition of effects as described by Yavuzturk

    and Spitler [14] and illustrated by Fig. 6. When the load is varying

    hourly, a new pulse is applied each hour. It is simply the difference

    between the load for two consecutive hours. More formally, for the

    infinite line source as an example, with a single borehole, we have:

    DTr; t X

    i; tit

    qi

    4pk

    ZNr2=4atti

    eu

    udu (5)

    where: q*1 q1, and q*i qiqi1, i 2.I, tI t, is the incrementalload between two successive hours. With multiple boreholes,

    DTx0; t Xn

    j 1

    Xi; tit

    q0i

    4pk

    ZNkxjx0k2=4atti

    eu

    udu (6)

    where: n is the number of boreholes, xj and x0 are the coordinate

    vectors of borehole j and point where temperature is computed,

    respectively. Note that for long simulation periods, the computa-

    tional burden becomes important.

    In the test cases that follow we assume that all of the buildingheating and cooling loads are to be provided by the GLHE system,

    i.e. there is no supplementary heat rejection/injection. Synthetic

    building loads are used to enhance the reproducibility of our

    results. These building loads are simulated using:

    Qt A B cos

    t

    87602p

    C cos

    t

    242p

    D cos

    t

    242p

    cos

    2t

    87602p

    (7)

    In Equation (7), t is in hours, A controls the annual load

    unbalance, B the half-amplitude of annual load variation, C and D

    40 30 20 10 0 10 20 30 40

    40

    30

    20

    10

    0

    10

    20

    30

    40

    1

    2

    3 4

    5

    6 7

    8 9

    10

    11 12

    13

    14 15

    16 17

    18 19

    20 21

    22 23

    24 25

    26

    27 28

    29

    30 31

    32 33

    34 35

    36 37

    38 39

    40 41

    42 43

    44 45

    46

    47 48

    49

    50 51

    52 53

    54 55

    56 57

    58 59

    60 61

    62 63

    64 65

    66 67

    68 69

    70

    71 72

    73 74

    75 76

    77 78

    79 80

    81

    82 83

    84 85

    86 87

    88 89

    90 91

    92 93

    94 95

    96 97

    98 99

    100 101

    102 103

    104 105

    106 107

    108 109

    110

    111 112

    113

    114 115

    116 117

    118 119

    120 121

    122 123

    124 125

    126 127

    128 129

    130 131

    132 133

    134 135

    136 137

    138 139

    140 141

    142 143

    144 145

    146

    147 148

    149

    150 151

    152 153

    154 155

    156 157

    158 159

    160 161

    162 163

    164 165

    166 167

    168 169

    170 171

    172 173

    174 175

    176 177

    178 179

    180 181

    182 183

    184 185

    186 187

    188 189

    190 191

    192 193

    194 195

    196 197

    198 199

    200 201

    202 203

    204 205

    206 207

    208 209

    210 211

    212 213

    214 215

    216 217

    218 219

    220 221

    222 223

    224 225

    Borehole location and priority number

    Coord. x (m)

    Coord.y(m)

    Fig. 8. Borehole grid and priority number. Number indicates order of inclusion in the design when required.

    Table 1

    Number of boreholes required, complete geothermal system. Constant T assumes

    a constant ground surface temperature of 10 oC, Periodic T assumes a periodic

    ground surface temperature with an amplitude of 20 oC in phase with the heatload.

    Scenar io Borehole length Infinite li ne Fini te l in e

    Constant T Periodic T

    Balanced (A 17) 100 m 33 33 34Balanced 50 m 76 74 80

    Cooling dominant (A 17) 100 m 39 36 37Cooling dominant 50 m 93 79 81

    Heating dominant

    (A 30)100 m 57 53 56

    Heating dominant 50 m 134 115 124

    Table 2

    Number of boreholes required, hybrid system. HP capacity represents 40% of

    maximum building load. The last two column represent the percentage of the

    building load supplied by the HP for each mode.

    Scenario Borehole

    length

    Number of

    boreholes

    % Energy

    Infinite Finite Cooling Inf.

    (Fin.)

    Heating Inf.

    (Fin.)

    Balanced 100 m 19 19 69 (69) 77 (78)

    Balanced 50 m 37 37 67 (67) 72 (73)

    Cooling dominant 100 m 24 24 69 (69) 86 (86)

    Cooling dominant 50 m 41 39 70 (69) 90 (88)

    Heating dominant 100 m 37 37 67 (67) 83 (86)

    Heating dominant 50 m 55 53 72 (70) 70 (73)

    D. Marcotte et al. / Renewable Energy 35 (2010) 763770 767

  • 7/29/2019 Axial Effects of Borehole Design

    6/8

    the half-amplitude of daily load fluctuations. D/C controls the

    relative importance of the damped component used to simulate

    larger daily fluctuations in winter and summer. Coefficients A to D

    are in kW.

    We consider three different load scenarios, each with B 100,C 50, and D 25. One is approximately balanced (A 17), one isa cooling dominated load (A 17) and the other is a heating domi-natedload(A 30).Conversionof buildingloads to ground loads isdone with: qground qbuilding(1 1/COP). The heat pump COP variesas a function of entering water temperature as depicted in Fig. 7.

    For all scenarios, we consider a unique set of possible locations

    for the boreholes. The locations are at the nodes of a regular grid of

    mesh S

    6 m. The boreholes are assigned a priority number (lower

    number / highest priority), moving excentrically from the grid

    center to the fringes (see Fig. 8). The system is simulated with

    100 m and then, 50 m long boreholes. The borehole heads are

    located at the ground surface.

    For each scenario and given number of boreholes, we simulate

    the hourly fluid temperature for a 10-year period. We repeat this

    simulation for different number of boreholes and finally keep the

    lowest number of boreholes ensuring that the fluid temperature at

    the HP entrance never exceeds the HP limit specifications. We do

    this computation using both the infinite and finite line source

    models. Thermalparameters of the ground are: thermal conductivity

    ks 2 Wm1 K1, volumetric heat capacity Cs 3.4e06 Jm3 K1and borehole thermal resistance Rb 0.1 m KW1. The ground isinitially at 10 oC and all the boreholes have a radius of rb

    0.075 m.

    Table 1 gives the number of boreholes required for a specificscenario and model. The choice of model does not have a strong

    impact on the balanced load scenario. However, for cooling and

    heating dominant scenarios, the finite line source model indicates

    a reduction in the number of boreholes of approximately 7% and

    15% for the 100 m and 50 m borehole length. As expected, the

    shorter the borehole length, the greater are the discrepancies

    between both models.

    3.1. Seasonal effects

    The finite line source model assumes a constant temperature at

    the ground surface equal to the undisturbed ground temperature.

    This hypothesis would more or less correspond to the case of

    geothermal boreholes located under a building slab. However, in

    many cases, the boreholes are located outside the building area

    where the ground surface temperature varies in phase with the

    heat load. One can expect the axial effect at the ground surface will

    be less than under the constant temperature assumption. The

    influence of ground surface temperature variation on the ground

    temperature, at any depth and time, can be computed for a periodic

    signal [7]. Using the principle of superposition, the influence on the

    design can be assessed.

    Last column of Table 1 gives the number of boreholes required

    when the groundsurface temperature is periodic, in phase with the

    heat load, and shows a yearly variation of 20 oC. The boreholeheads are located at the ground surface, a feature that maximizes

    the seasonal effects on the design. As expected, the designs with

    periodic ground surface temperature require more boreholes than

    with constant ground surface temperature. For unbalanced

    scenarios, the periodic ground surface temperature solutions

    obtained are intermediate between the infinite and the finite line

    source designs.

    0 5 10 15 20 25 306

    4

    2

    0

    2

    4

    6

    8

    Time (year)

    o

    Temperature(

    C)

    Rock temperature at x=(13,5,12.0)

    Infinite linesource

    Finite linesource

    15 10 5 0 5 10 1515

    10

    5

    0

    5

    10

    15Control point

    x (m)

    y(m)

    Fig. 9. Vertical average rock temperature at point x (13.5, 12.0). Thermal parameters: ks2 Wm1 K1, Cs3.4e06 Jm

    3 K1.

    0 5 10 15 20 25 301000

    900

    800

    700

    600

    500

    400

    300

    200

    100

    0

    Time (year)

    Load(W)

    Ground cooling load / borehole

    Infinite linesource

    Finite linesource

    Fig. 10. Evolution of average load per borehole.

    D. Marcotte et al. / Renewable Energy 35 (2010) 763770768

  • 7/29/2019 Axial Effects of Borehole Design

    7/8

    4. Design of hybrid geothermal systems

    The design situation borrows its essential features (borehole

    grid, thermal parameters, heat load scenarios) from the previous

    complete geothermal system example. The main difference is that

    the HP and auxiliary system power are respectively selected at 40%

    and 60% of the maximum building load. The simulation works thesame way as previously with the following modification. Each hour,

    the fluid temperature at the HP entrance (EWT) is computed. If

    EWT, at any hour, exceeds the HP specification limit, it is assumed

    that the HP cycles to keep the EWT at its limit value, the excess load

    being taken by the auxiliary system. We keep track of all the loads

    provided by the auxiliary system. At the end of the 10-year simu-

    lation, we verify that the load to the auxiliary system never exceeds

    its capacity. If exceeded, we add more boreholes. The final design is

    obtained with the smallest number of boreholes compatible with

    the auxiliary system capacity.

    Table 2 shows the number of boreholes for a specific scenario

    and computation model. The proportion of energy provided by the

    geothermal system, relative to the total building energy required

    for the 10-year period, is also given. Unbalanced scenarios with

    short boreholes display reduction of only 6% for the number of

    boreholes required. However, comparison of Tables 1 and 2 reveals

    striking reduction in numberof boreholes. The hybrid systems need

    only between 46% and 70% of the number of boreholes for the

    complete geothermal system. Yet, the geothermal components of

    hybrid systems are able to supply between 67% and 70% of the

    cooling load and between 73% and 88% of the heating load for thevarious scenarios examined. As the borehole construction cost

    represents the main investment in a geothermal system, it indi-

    cates that hybrid systems can be economically advantageous.

    Even though hourly simulations are computationally more

    involved, efficient methods exist to speed up the computations

    [1,10,12]. For example, a hybrid system 10-years hourly simulation

    for a 45 boreholes field is computed in less than 2 min on a stan-

    dard laptop.

    5. Comparing performances for a rock freezing problem

    In some environmental problems, like those involving DNAPL

    (dense non-aqueous phase liquid), the contaminants reach the

    bedrock and then can propagate through the rock fractures. In such

    X coordinate (m)

    Ycoordinate(m

    )

    Infinite line: Temperature after 5 years

    15 10 5 0 5 10 15

    15

    10

    5

    0

    5

    10

    15

    12

    10

    8

    6

    4

    2

    0

    2

    X coordinate (m)

    Ycoordinate(m

    )

    Finite line: Temperature after 5 years

    15 10 5 0 5 10 15

    15

    10

    5

    0

    5

    10

    15

    12

    10

    8

    6

    4

    2

    0

    2

    X coordinate (m)

    Ycoordinate(m)

    Infinite line: Temperature after 20 years

    15

    10

    5

    0

    5

    10

    15

    12

    10

    8

    6

    4

    2

    0

    2

    X coordinate (m)

    Ycoordinate(m)

    Finite line: Temperature after 20 years

    15 10 5 0 5 10 15 15 10 5 0 5 10 1515

    10

    5

    0

    5

    10

    15

    12

    10

    8

    6

    4

    2

    0

    2

    Fig. 11. Ground temperature after 5 years (top) and 20 years (bottom). Infinite line source model (left) and finite line source model (right).

    D. Marcotte et al. / Renewable Energy 35 (2010) 763770 769

  • 7/29/2019 Axial Effects of Borehole Design

    8/8

    circumstances, remediation can be extremely difficult and expen-

    sive. One solution is to catch and treat all the contaminants flowing

    through the fractures. This requires designing a series of wells

    forming an hydraulic trap. The pumping andtreatment is expensive

    and it has to be maintained typically for hundreds of years. More-

    over, the flow of water to treat could be relatively important. An

    alternative is to permanently freeze the liquid within the fractures

    to avoid any movement of the contaminant.

    In the following example, we consider the problem of freezing

    water inside rock fractures, in a domain 30 m by 30 m by 30 m, for

    the purpose of long term confinement of toxic DNAPLs. A 10 10borefield is considered (see Fig. 9). Thermal parameters of the rock

    are: thermal conductivity ks 2 Wm1 K1 and volumetric heatcapacity Cs 3.4e06 Jm3 K1. The borehole thermal resistance isRb 0.1 m KW1. The rock is initially at 10 oC. The rock porosity issmall enough so as to neglect the latent heat of water and the

    increase of rock thermal conductivity occurring when water

    freezes. The total HP capacity is 100 kW (one kW per borehole)

    and the EWTlimitis 8 oC. Themass flow of the circulating fluid is19 l/s (or 0.19 l/s for each borehole). The simulation is run for 30

    years. The HP capacity is kept at its maximum until the EWT has

    reached the limiting value of

    8 oC. Then, the HP cycles to

    maintain the EWT at this temperature. The performance of thesystem is monitored by computing rock temperature at a control

    point located at the borefield periphery at (x, y) (13.5, 12) m (seeFig. 9).

    Fig. 9 shows the rock temperature obtained at this control point

    using the infinite and finite line source models. Fig. 10 shows the

    corresponding average hourly load per borehole. In both figures,

    the rugged nature of the load curves is due to intermittent opera-

    tion of the HP. As shown in Fig. 9, the rock becomes permanently

    frozen after 10 months and 2.2 years for the infinite and finite

    models, respectively. The temperature difference between both

    models increases steadily with time, to reach approximately 2 oC

    after 30 years. The finite line source model predicts that about

    150 W per borehole are required compared to only 50 W per

    borehole for the infinite line source model (Fig. 10). Thus, despitea higher heat transfer rate per borehole, the finite line source model

    predicts a higher rock temperature at the control point.

    In this next example, the same 10 10 borefield is cooled ata rate of 10 W/m (300 W/borehole) for the first year and then

    3.33 W/m (100 W/borehole) permanently. The temperature distri-

    bution in the ground is computed using the infinite and finite line

    source models after 5 and 20 years. Results are presented in Fig. 11.

    The proportion of the domain with temperature below freezing is

    79% and 100% after 5 and 20 years for the infinite line source

    calculation whereas it is only 10% and 52% with the finite line

    source model. Therefore, a design based on the use of the infinite

    line source would have wrongly predicted ground freezing. Thus,

    contrary to the two previous examples, the infinite model does not

    provide a conservative design.

    6. Conclusion

    This paper studies the effect of axial heat conduction in bore-

    holes used in geothermal heat pump systems. The axial effects are

    examined by comparing the results obtained using the finite and

    infinite line source methods. Using various practical design prob-

    lems it is shown that axial effects are relatively important. Even

    with a borehole spacing / borehole length (S/H) as lowas 0.06, the

    finite line source model indicated that 7% less boreholes are

    required,for a complete geothermal system, when the yearly load is

    unbalanced either in cooling or in heating. The reduction in the

    number of boreholes due to axial effects increases to 15% for 50 m

    long boreholes (ratio S/H 0.12). Differences between the finite

    and infinite line source models were noticeably smaller for the

    hybrid system but still indicate that less boreholes are generally

    required with the finite line source model. As sizing of geothermal

    system is a determining factor for the profitability of a project, axial

    effects should certainly be considered in similar circumstances.

    Also, the value of using hybrid systems to substantially reduce the

    number of boreholes, yet preserving most energy savings, was

    confirmed.

    In another example dealing with underground water freezing,

    the amount of energy that has to be removed to freezethe ground is

    three times higher when axial effects are considered. Furthermore,

    for this particular example, a design based on the infinite line

    source would not achieve the ground freezing goal. Indeed, while

    the infinite line source calculations show that 100% of the ground

    would be frozen, the finite line source model predicts that only 52%

    of the ground would be frozen.

    Together, these examples clearly indicate that axial effects are

    problem dependent. The magnitude of these effects is difficult to

    anticipate and cannot generally be neglected. Moreover, neglecting

    the axial effects (i.e. using the infinite line source model) does not

    always provide a conservative design. Since the computing cost of

    finite line source model, when properly implemented, is only

    slightly superior to the computing cost of the infinite line sourcemodel, there is no reason to overlook axial effects in any borefield

    design.

    Acknowledgments

    Part of this research was financed by the National Science and

    Engineering Research Council of Canada. We thank Jeremie

    Gaucher for English editing. Helpful suggestions from anonymous

    reviewers are acknowledged.

    References

    [1] Bernier M, Pinel P, Labib R, Paillot R. A multiple load aggregation algorithm forannual hourly simulations of gchp systems. HVAC&R Research2004;10(4):47187.

    [2] Bernier M. Ground-coupled heat pump system simulation. ASHRAE Trans-actions 2001;107(1):60516.

    [3] Bernier M. Closed-loop ground-coupled heat pumps systems. ASHRAE Journal2006;48(9):129.

    [4] Crawley D, Lawrie L, Pedersen C, Strand R, Liesen R, Winkelmann F, et al.Energyplus: creating a new-generation building energy simulation program.Energy and Buildings 2001;33(4):31931.

    [5] Fisher D, Rees S, Padhrmanabhan S, Murugappan A. Implementation andvalidation of ground-source heat pump system models in an integratedbuilding and system simulation environment. IJHVAC &R Research2006;13(3a):693710.

    [6] Hellstrom G. Ground heat storage. Thermal analysis of duct storage systems:Part i, theory, Ph.D. dissertation, University of Lund, Sweden, 1991.

    [7] Ingersoll L, Zobel O, Ingersoll A. Heat conduction with engineering, geologicaland other applications. New York: McGraw-Hill; 1954.

    [8] S. Kavanaugh and K. Rafferty. Ground-source heat pumps. Design of

    geothermal systems for commercial and institutional buildings. ASHRAE,editor. ASHRAE, 1997.

    [9] Klein S, Beckman W, Mitchell J, Duffie J, Duffie N, Freeman T, et al. In: S.E.Laboratory, editor. TRNSYS 16 A transient system simulation program, usermanual. Madison: University of Wisconsin; 2004.

    [10] Lamarche L. A fast algorithm for the hourly simulations of ground-source heatpumps using arbitrary response factors. Renewable Energy 2009;10:22528.

    [11] Lamarche L, Beauchamp B. A new contribution to the finite line-source modelfor geothermal boreholes. Energy and Buildings 2007;39:18898.

    [12] Marcotte D, Pasquier P. Fast fluid and ground temperature computation forgeothermal ground-loop heat exchanger systems. Geothermics 2008;37:65165.

    [13] F. Sheriff. "Generation de facteurs de reponse pour champs de puits geo-thermiques verticaux." Masters thesis, Ecole Polytechnique de Montreal.2007.

    [14] Yavuzturk C, Spitler J. A short time step response factor model for verticalground loop heat exchangers. ASHRAE Transactions 1999;105:47585.

    [15] Zeng H, Diao N, Fang Z. A finite line-source model for boreholes in geothermal

    heat exchangers,". Heat Transfer - Asian Research 2002;31:55867.

    D. Marcotte et al. / Renewable Energy 35 (2010) 763770770