  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    AVJ Engineering Consultants

    9/14/2016 1

    MAGNADRI.WMV

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    • AVJ Engineering Consultants was established in the year 2009 after I worked for 36 years and is based at:

    Flat No.1, Plot No.21,

    Mahabali Housing Society,

    9/14/2016 2

    Mahabali Housing Society,

    Karve Nagar,

    Pune – 411052

    Telefax: 912025460104

    Mobile: 919923413733

    Mail ID: [email protected]

    Website: www.avjengineering.com

    AVJ Engineering Consultants will be known as AVJ Engineering & Marketing Pvt. Ltd.

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    Presentation Presentation on Reduction on Reduction in in Auxiliary Power Consumption Auxiliary Power Consumption and and Reduction in Reduction in

    O&M Cost ThroughO&M Cost Through

    9/14/2016 3

    MagnaDrive Magnetic Couplings and Adjustable Speed Drives (ASD)

    “The Next Industrial Revolution”

    By

    Vinod Malhotra

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    MagnaDrive, Seattle USA

    Flownetix, UK

    Electromagnetic & Ultrasonic Flow

    Meters

    About AVJ Engineering Consultants

    AVJ is Distributor & Marketing Associates for:

    9/14/2016 4

    Meters

    Jyoti Limited, Baroda – Pumps, Motors &

    Switch Gears

    Essential Power Transmission for Gear

    Box.

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    Magnadrive Couplings and ASDMagnadrive Couplings and ASD Jyoti PumpsJyoti Pumps

    9/14/2016 5

    Flownetix Ultrasonic SmartFlownetix Ultrasonic Smart

    Water MetersWater Meters

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    MagnaDrive’s Value Proposition

    “MagnaDrive’s revolutionary disconnected

    MagnaDrive Benefits

    MagnaDrive is the Only GREEN Technology

    Which Offers Dual Benefits - Saves Energy &

    Reduces O&M Cost also

    9/14/2016

    torque-transfer technology reduces your total cost of ownership by lowering maintenance and operating costs, increasing process availability, and

    improving system reliability.”

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    • Founded in 1999

    • Technology of the Year by Industry Weekfor 2001

    • 20 Domestic Patents and More than 200 International Patents

    About MagnaDrive

    9/14/2016 7

    International Patents

    • Installed on Over 35,000 Systems and in India 61 Systems.

    • Recently Awarded $2.7 million Contract by U.S. Navy

  • AVJ Engineering ConsultantsAVJ Engineering Consultants About MagnaDrive

    • 2004 Inc. 500 Fastest Growing Private Companies

    9/14/2016

  • AVJ Engineering ConsultantsAVJ Engineering Consultants About MagnaDrive

    • 2004 Inc. 500 Fastest Growing Private Companies

    9/14/2016

    • 2004 Deloitte 500 Fastest Growing Technology Companies

  • AVJ Engineering ConsultantsAVJ Engineering Consultants About MagnaDrive

    • Inc. 500 Fastest Growing Private Companies

    9/14/2016

    • Deloitte 500 Fastest Growing Technology Companies

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    • MagnaDrive Produces Magnetic Adjustable Speed Drives and Couplings that eliminate the physical link between the motor and load and instead uses a Magnetic field to transmit torque across an air gap. It’s a simple but effective mechanical technology that is GREEN gives following advantages

    – Reduces energy consumption

    – Reduces motor stress at start-up

    9/14/2016 11

    – Reduces motor stress at start-up

    – Cushions shock loads and eliminates motor seizure– FGC Demo.wmv

    – Tolerates misalignment and thermal expansion

    – Extends equipment life and reduces maintenance requirements through reduced vibration and cavitations

  • AVJ Engineering ConsultantsAVJ Engineering Consultants Principle of Operation

    Magnet & Copper Penny Demo.wmv

    9/14/2016 12

  • AVJ Engineering ConsultantsAVJ Engineering Consultants MagnaDrive Benefits

    A Mechanical,A Mechanical,

    ImagineOperates While Misaligned

    Controls Load Speed

    Cushioned Start

    Cushions Shock Loads

    13

    A Mechanical,

    Non-Electronic Device

    A Mechanical,

    Non-Electronic DeviceEasy to Install

    Easily UnderstoodEliminates Motor Seizure

    Extends Equipment Life Reduces Vibration

    Compact

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    • Pumps

    Application Types

    Target Market

    9/14/2016 14

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    • Pumps

    • Fans

    Application Types

    Target Market

    9/14/2016 15

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    • Pumps

    • Fans

    • Blowers

    Application Types

    Target Market

    9/14/2016 16

    • Blowers

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    • Pumps

    • Fans

    • Blowers

    Application Types

    Target Market

    9/14/2016 17

    • Blowers

    • Centrifuges

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    • Pumps

    • Fans

    • Blowers

    Application Types

    Target Market

    9/14/2016 18

    • Blowers

    • Centrifuges

    • Bulk Handling

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    • MagnaDrive is not only a Drive but a “Total Solution”to Achieve Lower Total Cost of Ownership

    A

    B

    S

    O

    L

    MagnaDrive is Solution

    MagnaDrive “THE” Solution Module

    9/14/2016 19

    MagnaDrive

    Energy Zero Vibration Works in Misalignment

    No Throttling Lower O&M cost No Motor Seizure

    L

    U

    T

    E

    S

    A

    V

    I

    N

    G

    S

    Lower Motor Ratings

    LOWER COST OF OWNERSHIP

    RESULT Lower Starting Current

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    • Couplings

    Product Lines

    9/14/2016 20

    • Couplings• Adjustable Speed Drives (ASDs)

  • AVJ Engineering ConsultantsAVJ Engineering Consultants Coupling Range and Models

    • Constant and Variable Torque

    • 2 to 2500 KW Applications

    • Four Models:

    Magnetic Couplings

    9/14/2016 21

    • Four Models:

    – First Generation Coupling (FGC)

    – Delay (MGD)

    – Torque Limiting (MGTL)

    – Vortex

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    • FGC - First Generation Coupling

    • MGD – Magnaguard Delay

    Couplings:FGC

    MGD

    Permanent Magnet

    Couplings

    9/14/2016

    • MGD – Magnaguard Delay

    • MGTL- MagnaDrive Torque Limiting

    • VORTEX

    MGTL

  • AVJ Engineering ConsultantsAVJ Engineering Consultants Product Overview -Couplings

    FGC Product Line

    • 2 to 2500 KW @1500• Variable and Constant

    Torque applications • Can deliver higher starting

    torques

    9/14/2016

    torques• Cushioned start desired• Shafts: standard or

    special sizes• Dist. Between Shaft ends

    (DBSE): within or beyond standard range

  • AVJ Engineering ConsultantsAVJ Engineering Consultants FGC Coupling

    CONDUCTOR STEEL

    COPPER CONDUCTORCOPPER CONDUCTOR

    CONDUCTOR STEEL

    MAGNETS

    AIR GAP SPACER

    SHRINK DISC SHRINK DISC

    9/14/2016

    LOAD HUBMOTOR HUB

    ALUMINUM MAGNET ROTOR

    AIR CLEARANCE (GAP)

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    • Range 16 to 625 KW

    • Air Gap Increases from 1/8 to 3/16 inch During Start Up

    MGD Product Line

    Product Overview -

    Couplings

    9/14/2016

    3/16 inch During Start Up

    • Gap Change Reduces Torque Transfer About 50% for Cushioned Smooth Start

    • MGD Also Has Partial Disconnect Feature Built In

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    CONDUCTOR STEEL

    COPPER CONDUCTORCOPPER CONDUCTOR

    CONDUCTOR STEEL

    ALUMINUM MAGNET ROTORS

    MAGNETS

    AIR GAP SPACER

    SHRINK DISCSHRINK DISC

    Product Overview -

    MGD

    9/14/2016

    LOAD HUBMOTOR HUB

    AIR CLEARANCE (GAP)

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    • All the Features of the MGD, Plus MGTL has Complete Disconnect Feature Built In

    • Complete Disconnection Results when High Torque Repelling

    MGTL Product Line

    Product Overview –

    Couplings

    9/14/2016

    when High Torque Repelling Magnetic Force Occurs Due to Additional Slip

    • Repelling Force Completely Uncouples Motor from Load for Complete Protection

    • Self Resetting when Motor is Turned Off

  • AVJ Engineering ConsultantsAVJ Engineering ConsultantsCoupling Benefits - MGTL

    CONDUCTOR STEEL

    COPPER CONDUCTORCOPPER CONDUCTOR

    CONDUCTOR STEEL

    ALUMINUM MAGNET ROTORS

    MAGNETS

    AIR GAP SPACER

    SHRINK DISCSHRINK DISC

    9/14/2016

    LOAD HUBMOTOR HUB

    AIR CLEARANCE (GAP)

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    • Offers Low Maintenance

    • Simple Installation

    • Efficient Torque Transfer

    • Permits Shock Loadings (Load is Cushioned & Slips)

    Coupling Benefits:FGC & MGE

    MGD

    Product Overview -

    Couplings

    9/14/2016

    (Load is Cushioned & Slips)

    • Greater Misalignment Tolerance

    • Ideal for Applications Subject to:– Vibration

    – Periodic Load Seizure

    – Pulsating Loads

    – Thermal Expansion

    – Higher Starting Inertia/Torque

    MGTL

  • AVJ Engineering ConsultantsAVJ Engineering Consultants Type of Loads

    • Centrifugal Loads

    • Centrifugal loads are rotating loads, such as centrifugal pumps, fans, and mixers. They closely follow the affinity laws, which dictate how flow, horsepower, and torque change as speed changes:

    • New Flow = Original Flow × Δ Speed

    • New Torque = Original Torque × Δ Speed2

    9/14/2016 30

    • New HP = Original HP × Δ Speed3

    • In other words, flow varies proportionally with change in speed (Δ Speed, expressed as a percentage of the original speed), torque varies with the square of the change in speed, and horsepower varies with the cube of the change in speed.

    • It is important to understand that torque is demanded by the load. Attach a 2-hp motor to a 2-hp load, then attach a 10,000-hp motor to the same load and both motors will generate 2-hp (ignoring losses).

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    (HP1 / HP2) = (Flow1 / Flow2)3

    TechnologyTechnology

    Affinity (or “Fan”) Laws

    Proportion of Max

    Flow Flow Reduction Power Consumed Power Saved

    (Flow1/Flow2) (1-Flow1/Flow2) (HP1/HP2) (1-HP1/HP2)

    99% 1% 97% 3%

    98% 2% 94% 6%

    • Torque Transmitted & Flow Are Reduced By Increasing the ASD Air Gap

    • A 1% Reduction in

    9/14/2016 31

    98% 2% 94% 6%

    97% 3% 91% 9%

    96% 4% 88% 12%

    95% 5% 86% 14%

    90% 10% 73% 27%

    85% 15% 61% 39%

    80% 20% 51% 49%

    70% 30% 34% 66%

    60% 40% 22% 78%

    50% 50% 13% 88%

    40% 60% 6% 94%

    Speed and Flow Yields a 3% Energy Savings

    • A 10% Reduction in Speed and Flow Yields a 27% Energy Savings

    • A 50% Reduction in Speed and Flow Yields a 88% Energy Savings

    Energy Savings May be Greater

    Due to Reduced Vibration and

    Misalignment Tolerance of

    MagnaDrive Air Gap

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    Why pump should not be operated at full Valve Opening?

    Pump Curve:

    Pump curve for 150 KW ECW pump.pdf

    9/14/2016 32

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    • Non-Centrifugal Loads• Other loads, such as screw compressors, positive displacement pumps,

    positive displacement blowers, paper roll machines, conveyor belts, punch presses, and rock crushers, do not follow the affinity laws.

    • Flow varies proportionally with speed.

    • Torque and horsepower may decrease, remain constant or increase—it depends on the application.

    • Speed changes for non-centrifugal loads do not generate the same large energy saving as with centrifugal loads, but changes in speed may be desirable for process control reasons. In other words, you may want to control the speed

    9/14/2016 33

    for process control reasons. In other words, you may want to control the speed of the process, even though you are not saving any energy.

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    Rigid CouplingsRigid Couplings

    Rigid Chain Gear Disc

    Fixed Speed – Mechanical Couplings

    Fixed Speed – Mechanical Couplings

    9/14/2016 34

    Flexible / Elastomeric CouplingsFlexible / Elastomeric Couplings

    Flexible ShaftRubber (Tire) Jaw Pin

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    Misalignment

    • All couplings are subject to:

    Fixed Speed – Mechanical Couplings

    Fixed Speed – Mechanical Couplings

    9/14/2016 35

    Parallel / Offset

    Misalignment

    Axial Misalignment

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    • MagnaDrive has a unique design:

    Permanent Magnet

    Rotor

    Permanent Magnet

    Rotor

    Copper Conductor

    Rotor

    Copper Conductor

    Rotor

    Fixed Speed –Mechanical Couplings

    Fixed Speed –Mechanical Couplings

    9/14/2016 36

    Motor Shaft Load Shaft

    Air GapAir Gap

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    Motor Shaft Load Shaft

    Fixed Speed –Mechanical Couplings

    Fixed Speed –Mechanical Couplings

    9/14/2016 37

    MagnaDrive

    can operate with

    Angular Misalignment

    MagnaDrive

    can operate with

    Angular Misalignment

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    Motor Shaft Motor Shaft Load Shaft Motor Shaft Load Shaft

    Fixed Speed –Mechanical Couplings

    Fixed Speed –Mechanical Couplings

    9/14/2016 38

    MagnaDrive

    can operate with

    Parallel Misalignment

    MagnaDrive

    can operate with

    Parallel Misalignment

    MagnaDrive

    can operate with

    Axial Misalignment

    MagnaDrive

    can operate with

    Axial Misalignment

    MagnaDrive

    can operate with

    Angular Misalignment

    MagnaDrive

    can operate with

    Angular Misalignment

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    • Lower Inrush at

    Startup

    Cushioned Start

    Coupling Technology

    Reduced starting power requirementReduced starting power requirement

    9/14/2016 39

    • Lowers Peak

    Demand

    • Immediate Restarts

    Energy Savings as a resultEnergy Savings as a result

    of removing system of removing system

    inefficiencies inefficiencies

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    • Motor Characteristics– Up to 5000 HP Motors @ 1500 RPM– Up to 3000 HP Motors @ 3000 RPM

    • Vibration Isolation • MagnaDrive Corp - Pump - No Vibration - Lorain,

    OH, USA.wmv

    Couplings

    9/14/2016 40

    OH, USA.wmv• Alignment Problems• ..\Misalignment Demo.wmv• Need for Cushion Start • Thermal Expansion Issues• Shaft Seizure Issues• Mechanical Seals are Present• Need to Protect Critical Equipment

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    Rigid & Flexible CouplingsRigid & Flexible Couplings MagnaDrive (MGE/FGC/MGD/MGTL)MagnaDrive (MGE/FGC/MGD/MGTL)

    • All mechanical couplings are somehow physically connected causing:

    �Misalignment

    �Vibration transfer

    �Premature equipment failure

    �Energy waste due to misalignment

    • The disconnected nature of the MagnaDrive connection (air gap) provides:

    �Misalignment allowance up to 3 degrees

    �No vibration transfer

    �Longer equipment life (bearings, seals, etc.)

    �Energy savings due to motor/load disconnection

    • Installation, operation, & maintenance issues: • Installation, operation, & maintenance issues:

    Fixed Speed –Mechanical Couplings

    Fixed Speed –Mechanical Couplings

    9/14/2016 41

    • Installation, operation, & maintenance issues:

    �Time and money spent on laser alignment

    �Time and money spent maintaining equipment

    �Production downtime costs

    �No overload torque protection

    �Some types require grease/oil

    �“Hard” start causes extra stress on equipment and energy spikes

    �No speed adjustability

    • Installation, operation, & maintenance issues:

    �Virtually no time and money spent on alignment

    �Less time and money spent maintaining equip.

    �Lower production downtime costs

    �Overload protection

    �MagnaDrive is a GREEN technology

    � “Cushioned” and delayed start increases equipment life and provides lower peak demand and inrush (additional energy savings)

    �MagnaDrive couplings can be fine tuned to save energy

    Increased cost

    of ownership

    Lower cost

    of ownership

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    • Fluid Couplings

    • Applications:

    • Bulk Material Systems Conveyors:

    9/14/2016 42

    • Bulk Material Systems Conveyors:

    • Coal Handling

    • Ash Handling

  • AVJ Engineering ConsultantsAVJ Engineering Consultants Fixed Speed –Fluid / Hydraulic Couplings

    Fixed Speed –Fluid / Hydraulic Couplings

    9/14/2016 43

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    Fluid Coupling Issues - OilFluid Coupling Issues - Oil

    Fixed Speed –Fluid / Hydraulic Couplings

    Fixed Speed –Fluid / Hydraulic Couplings

    9/14/2016 44

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    Fluid Coupling Issues – High MaintenanceFluid Coupling Issues – High Maintenance

    "Replacement parts for fluid couplings are notoriouslyexpensive. However, we had no choice but to keeppaying out as the Dryer-Pulveriser Mill is such a keyelement within the refinery process. Unfortunately wewere in a lose-lose situation, when the applicationfaltered it not only cost us money to fix it, it was alsocosting us money for the duration it was off-line.“

    Fixed Speed –Fluid / Hydraulic

    Couplings

    Fixed Speed –Fluid / Hydraulic

    Couplings

    9/14/2016 45

    costing us money for the duration it was off-line.“

    "The coupling requires inspection every 12 weeks withfrequent oil top ups, the oil used within a fluid coupling ishighly volatile. The coupling incorporates a fusible drainplug which is designed to discharge oil if the operatingtemperature is too high. This feature was causing aconsiderable health and safety risk to operators, we hadexperienced several fires in the past caused by hot oilblowing the fusible plug and consequently igniting.”

    http://www.hub-4.com/news/696/wbb-minerals-grind-down-maintenance-costs-using-siemens-soft-startersSource:

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    Fluid Coupling Issues - HazardousFluid Coupling Issues - Hazardous

    Fixed Speed –Fluid / Hydraulic Couplings

    Fixed Speed –Fluid / Hydraulic Couplings

    9/14/2016 46

  • AVJ Engineering ConsultantsAVJ Engineering Consultants Fixed Speed –Fluid / Hydraulic Couplings

    Fixed Speed –Fluid / Hydraulic Couplings

    Fluid Coupling Issues - HazardousFluid Coupling Issues - Hazardous

    9/14/2016 47

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    2002 Fatality Accident with a

    major brand Fluid Coupling

    at Lone Star Quarry & Mill

    Fixed Speed –Fluid / Hydraulic Couplings

    Fixed Speed –Fluid / Hydraulic Couplings

    Fluid Coupling Issues - HazardousFluid Coupling Issues - Hazardous

    9/14/2016 48

    http://www.msha.gov/fatals/2002/ftl02m17.htm

    at Lone Star Quarry & Mill

    Lone Star Industries, Inc.

    Cape Girardeau, MO

    For Official Accident Report Go To:

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    “Curbing the killer Conveyors”

    “Recently a steel worker was injured when an inclined conveyor ranbackwards, out of control, and the fluid coupling in the drive trainexploded like a bomb, spreading shrapnel and hot hydraulic oileverywhere. It should never have happened”.

    Fixed Speed –Fluid / Hydraulic Couplings

    Fixed Speed –Fluid / Hydraulic Couplings

    Fluid Coupling Issues - HazardousFluid Coupling Issues - Hazardous

    9/14/2016 49

    “The fluid coupling is sized to soft-start the conveyor and protect themotor/drive package from overloads. It is made from aluminum and isintended to run, in this case, at 1,500 to 1,800rpm. If it is run at speedsof up to 6,000rpm then the aluminum casing will be put under massivecentrifugal loads sufficient to make the whole thing explode like abomb”.

    “Then, when the drive train fails and the conveyor back-drives, thefluid coupling becomes a bomb just waiting to explode”.

    http://www.renold.com/Company/News/Curbing_the_killer_conveyors.aspSource:

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    “An undermanager and a deputy on a backshiftwere attempting to change the oil in a leaking fluidcoupling. The men were inexperienced in this task

    Fixed Speed –Fluid / Hydraulic Couplings

    Fixed Speed –Fluid / Hydraulic Couplings

    Fluid Coupling Issues - HazardousFluid Coupling Issues - Hazardous

    9/14/2016 50

    which resulted in the deputy receiving oil burns tohis face”.

    http://www.cfmeu.com.au/storage/documents/Apr00CC.pdfSource:

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    Performance of Magnetic Couplings in Bulk Material Handling Systems:

    MAGNADRIVE - BWE - ThyssenKrupp, Australia.wmv

    MAGNADRIVE - CONVEYOR - 1400 Ton Per Hour Conveyor in Australia.wmv

    MAGNADRIVE+-+CONVEYOR+-+Australia+-+SWCC+-+Thiess.wmv

    9/14/2016 51

    Apprehensions:

    Weather Magnetic Couplings will work in dusty environment?

    +Chile.wmvDust Flying MAGNADRIVE - Tura - TURKEY (1).wmv

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    • Comparative Study between VFD and Magnadrive on Energy Savings in Conveyor:

    MAG Drive kilo Watt

    30

    35

    Power consumption for Magnetic Drive

    0

    5

    10

    15

    20

    25

    30

    1 5 9 1317 21 2529 3337 41 4549 5357 61

    60 Minute Interval

    kW

    MAG Drive kilo Watt

    Power Consumption per hour - 1600.16 kWhAverage Power per hour - 26.23 kW

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    VSD Drive kilo Watt

    40

    50

    60

    Power consumption for Variable Speed Drive

    0

    10

    20

    30

    40

    1 5 9 13 17 21 25 29 33 37 41 45 49 53 57 61

    60 Minute Interval

    kW

    VSD Drive kilo Watt

    Power Consumption per hour - 1933.08 kWhAverage Power per hour - 31.68 kW

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    • Magnadrive/VSD Power Consumption Comparison Graph

    MAG/VSD Comparison Graph

    40

    50

    60

    0

    10

    20

    30

    40

    1 5 9 1317 21 2529 3337 41 4549 5357 61

    60 Minute Interval

    kWMAG Drive kilo Watt

    VSD Drive kilo Watt

    Energy Savings in conveyor Mooikraal Drive Recordings.xls

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    Fluid CouplingsFluid Couplings

    • Fluid Couplings are not totally disconnected and are subject to:�Misalignment and vibration transfer

    �Premature equipment failure (gear boxes, bearings, seals, etc.)

    �Energy waste due to misalignment and additional fluid friction losses inside the coupling

    • The disconnected nature of the connection (air gap) provides:�No misalignment and vibration issues

    �Longer equipment life (bearings, seals, gear boxes, etc.)

    �Energy savings due to the motor/load disconnection. Because MagnaDrive operates with a cushion of air, a 3-5% savings in power can be attained in relation to the same work done by a Fluid Coupling

    • Installation, operation, & maintenance issues:�Time and money spent on laser alignment

    Fixed Speed –Fluid / Hydraulic Couplings

    Fixed Speed –Fluid / Hydraulic Couplings

    MagnaDrive (FGC/MGD/MGTL)MagnaDrive (FGC/MGD/MGTL)

    9/14/2016 55

    Fluid Coupling�Time and money spent on laser alignment

    �Fluid Couplings are difficult to install and maintain

    �Time and money spent maintaining equipment

    �Most Fluid Couplings can not operate in both directions of rotation

    �Fluid Couplings are filled with oil which is a hazard for the environment and people

    �The Fluid Coupling overtorque protection is provided by a fusible plug which melts and sprays oil all around. When the plug fails to melt, the Fluid Coupling literately becomes a time bomb

    • Installation, operation, & maintenance issues:�Virtually no time and money spent on alignment

    �MagnaDrive Couplings have no oil, are lighter, and easier to install

    �Less time and money spent maintaining equip.

    �MagnaDrive Couplings transmit the same torque in either direction of rotation

    �MagnaDrive is a GREEN technology and does not use any oil

    �MagnaDrive Couplings basically slip if there is an overtorque condition, and certain models (MGTL) also offer a complete disconnect feature

    Increased cost

    of ownership Lower cost

    of ownership

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    Adjustable Speed Drive

    (ASD)

    9/14/2016 56

    (ASD)

  • AVJ Engineering ConsultantsAVJ Engineering Consultants Variable Speed –Valve / Damper Systems

    Variable Speed –Valve / Damper Systems

    9/14/2016 57

  • AVJ Engineering ConsultantsAVJ Engineering Consultants Variable Speed –VFDs (Variable Frequency Drives)

    Variable Speed –VFDs (Variable Frequency Drives)

    9/14/2016 58

  • AVJ Engineering ConsultantsAVJ Engineering Consultants Variable Speed –VFDs (Variable Frequency Drives)

    Variable Speed –VFDs (Variable Frequency Drives)

    Principle of OperationPrinciple of Operation

    9/14/2016 59

  • AVJ Engineering ConsultantsAVJ Engineering Consultants Variable Speed – VFDs (Variable Frequency Drives)

    Variable Speed – VFDs (Variable Frequency Drives)

    VFD Issues – Installation Complexity and Space RequirementVFD Issues – Installation Complexity and Space Requirement

    9/14/2016 60

    Building to house VFDsBuilding to house VFDs

    MagnaDrive minimal space requirement and

    simple installation

    MagnaDrive minimal space requirement and

    simple installation

  • AVJ Engineering ConsultantsAVJ Engineering Consultants Product Lines

    • Variable Gap – For Adjustable Speed

    • Air-Cooled:

    – Sizes 20 to 500 Hp @ 1500 RPM

    – Horizontal & Vertical Applications

    • Water-Cooled

    Adjustable Speed Drives

    9/14/2016 61

    • Water-Cooled

    – 500 through 4,500 Hp @ 1500 RPM

    – Horizontal & Vertical Applications

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    • Variable Speed Control for Energy Savings

    • Low System Maintenance

    • Accepts Greater Misalignment

    • Eliminates Vibration Transfer Between

    ASD Benefits

    9/14/2016 62

    • Eliminates Vibration Transfer Between Motor and Load

    • Unloaded Startup, Controlled Ramp-Up

    • Permits Shock Loading

    • Increased Seal & Bearing Life

    • Eliminates Electronic Harmonics

    • Unaffected By Power Quality Issues

    • Lightning Strikes

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    Adjustable Speed Drive (ASD)

    • For Speed Control and Energy Savings

    – ASD Energy Savings Demo.wmv

    9/14/2016 63

    – ASD energy savings New.wmv

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    VFDsVFDs MagnaDrive ASDsMagnaDrive ASDs

    Variable Speed –VFDs (Variable Frequency Drives)

    Variable Speed –VFDs (Variable Frequency Drives)

    • Special issues and installation requirements:�Require inverter duty motors�Are susceptible to dirty power�Require environment control (temp, dust, hum.)�Complexity of equipment and installation�Are expensive in medium/high voltage�Rapid obsolesce (6-7 years)/throw away�Motors control space requirement

    • Operation & maintenance issues:�Harmonics

    • MagnaDrive ASDs:�Operates with any kind of motor�Is not affected by dirty power�Is not affected by temperature, dust, humidity and other factors in the operating environment�Are simple to install and maintain�Have a life span of 20 – 25 years, depending on operating conditions

    • Operation & maintenance issues:�No issues with harmonics�No issues with bearing fluting

    9/14/2016 64

    • The disconnected nature of the connection (air gap) provides:�No misalignment and vibration issues�Less time and money spent aligning and maintaining equipment�Longer equipment life�Cushioned start�No load start�Energy savings due to motor / load disconnection�Overload protection

    Increased cost

    of ownership

    Lower cost

    of ownership

    • Equipment connected with VFDs still has a physical connection between the motor and load shaft causing:�Misalignment and vibration transfer�Premature equipment failure�Energy waste due to misalignment�No overload protection

    �Harmonics�Bearing Fluting�No rapid restart capability

    �No issues with bearing fluting�Rapid restart capability

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    Case Study for Hindalco Muri for ID Fan and PA Fan

    ID FAN Curve.pdf

    PA Fan Curve -- markup.pdf

    ASD Sizing for 26.5-28.5 for PA Fan for Hindalco Ranachi.xlsx

    Case Study

    9/14/2016 65

    ASD sizing for WC-1000 for ID fan for Hindalco Ranchi.xlsx

  • AVJ Engineering ConsultantsAVJ Engineering Consultants Magnadrive Capability

    Magnadrive has supplied 6 Nos. ASDs WH – 4000 for 3037 HP / 980 RPM

    ID Fan To China Power Plant.

    MagnaDrive WH-4000 in China.pdf

    9/14/2016 66

  • AVJ Engineering ConsultantsAVJ Engineering Consultants Success Stories

    List Of Customers

    List of Indian Customers as on 6th June

    2016.xlsx

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    • Pictures of Magnadrive Couplings at NALCO Damanjodi

    • Installation of Magnadrive Couplings at NALCO Damanjodi.pdfNALCO Damanjodi.pdf

    • Magnadrive Coupling Operating

    • DSCN0276.AVI

    9/14/2016 68

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    • Installation of Magnadrive Couplings in NTPC Plants.

    • Magnadrive Coupling Pictures in NTPC Plants.pdfPlants.pdf

    • Performance of Magnadrive Couplings in NTPC.pdf

    9/14/2016 69

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    NTPC Kayamkulam: 132 KW / 1500 rpm

    DMCW Pump installation on 10.07.2014

    Performance Results:

    Performance Results.pdf

    Success Stories

    9/14/2016 70

    Before Installation of Magnadrive Coupling Power consumption was 135.61 KW and After Installation of Magnadrive Coupling power consumption reduced to 113.54 Savings of 22.07 KW.

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    • NTPC AuraiyaPerformance Data of Clarified Pump Coupled with Magnadrive Coupling:

    – Pump Model: CPRG-80-40

    – Flow: 60M3/Hr.

    – Head: 45 Meters

    Success Stories

    – Rating in KW: 18.5 KW

    – Speed in RPM: 1470

    Before Magnadrive: 421.5 Volts, 24.6 Amps, 0.79 PF, 4 Kg/Cm2 Head, 14.1 KW

    After Magnadrive: 416 Volts, 22.2 Amps, 0.77 PF, 4 Kg/Cm2 Head, 12.4 KW

    Power Saving: 12.06%

    71

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    • NTPC Tanda:

    Magnadrive Coupling

    Model: FGC 18.5S.

    Conveyor: 2B

    Motor Rating: 110 KW

    Success Stories

    Motor Rating: 110 KW

    Speed: 1450 RPM

    No Load Current with

    Fluid Coupling: 57 Amps

    No Load Current with

    Magnadrive Coupling: 52 Amps9/14/2016 72

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    Vandana Global Ltd, Raipur

    Application: ACW Pump

    Rating: 30 KW

    Energy Savings: 19.36%

    Success Stories

    9/14/2016 73

    Energy Savings: 19.36%

    Coupling Model: FGC 10.5S

    Performance of FGC 10.5S at Vandana Global.pdf

  • AVJ Engineering ConsultantsAVJ Engineering Consultants Quantified Business Results

    9/14/2016 74

    Plant Head Mr. Nandi Inaugurating Magnadrive Magnetic Coupling Model FGC 18.5S on Conveyor No. 6A At Dahanu Thermal Power Station

  • AVJ Engineering ConsultantsAVJ Engineering Consultants Quantified Business Results

    Client: Dahanu Thermal Power StationApplication: ConveyorMotor Rating: 110 KWSpeed of Motor: 1485 RPMArea: Coal Handling PlantOriginal Drive: Fluid CouplingPower Consumed With Fluid Coupling: 39.5 KWPower Consumed with

    9/14/2016 75

    Magnadrive Magnetic Coupling Model FGC 18.5S At Dahanu Thermal Power Station

    Power Consumed withMagnadrive : 37.36 KWEnergy Savings: 2.14KWHEnergy Savings / Yr: 18747 KWH

    Energy Saving / Yr. in Rs.: 93732.00

    Other Benefits

    �Reduction in Vibration Level�Zero Maintenance�Increased MTBF

    Performance report of FGC 18.5S on 110 KW Conveyor at Dahanu Thermal Power.pdf

  • AVJ Engineering ConsultantsAVJ Engineering Consultants Quantified Business Results

    �Client: Delhi Jal Board�Project: Rithal ETP�Application: Pump�Liquid: Water�Motor Power: 280 KW�Voltage: 3.3 KV�Speed of Pump: 1466 RPM�Quantities: 8 Nos.Performance Parameters:

    9/14/2016 76

    Performance Parameters:

    Full Load Current: 63 Amps

    Magnadrive Coupling: FGC 21.0S

    Current Drawn with

    Magnadrive Coupling: 46 Amps

    Energy Savings: 78 KWH

    Energy Saving in Rs. 40.80L / Yr.

    Magnadrive Magnetic Coupling

    Model FGC 21.0S

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    �Client: SAIL�Project: BSP�Application: Pump�Liquid: Hot Benzyl�Flow: 40m3/Hr�Motor Power: 45 KW�Voltage: 415 Volts�Speed of Pump: 2980 RPM�Quantities: 4 Nos.

    Quantified Business Results

    9/14/2016 77

    �Quantities: 4 Nos.Performance Parameters:

    Current before

    Magnadrive: 53 Amps

    Magnadrive Coupling: MGE - 11

    Current Drawn with

    Magnadrive Coupling: 43 Amps

    Energy Saving in Rs. 201480 / Yr.

    Reduction in CO2

    Emission: 1 Ton / Day from 4 Couplings.

    Magnadrive Coupling Model MGE-11 At Coke Oven Bhilai Steel PlantPerformance Certificate for MGE-11 from BSP Coke Oven.pdfE:\VKM OWN\BSP\Coke Oven\Minutes of the Meeting.pdf

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    �Client: SAIL�Project: BSP WMD�Application: Pump�Liquid: Water�Motor Power: 110 KW�Voltage: 415 Volts�Speed of Pump: 1480 RPM�Quantities: 6 Nos.Performance Parameters:

    Current before

    Quantified Business Results

    9/14/2016 78

    Current before

    Magnadrive: 163 Amps

    Magnadrive Coupling: FGC – 16.5

    Current Drawn with

    Magnadrive Coupling: 134 Amps

    Energy Savings: 17 KWH

    Energy Saving in Rs. 438000 / Yr.

    Performance_certificate_from_WMD.pdf

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    �Client: Tata Motors Pune�Project: ETP�Application: Pump�Liquid: Effluent �Motor Power: 15 KW�Voltage: 415 Volts�Speed of Pump: 1480 RPM�Quantities: 1 Nos.Performance Parameters:

    Power before

    Quantified Business Results

    9/14/2016 79

    Power before

    Magnadrive: 9.77 KW

    Magnadrive Coupling: MGE-11

    Power Consumed with

    Magnadrive Coupling: 6.91 KWH

    Energy Savings: 2.9 KWH

    Energy Saving in %. 25%

    Performance Report for MGE 11 from Tata Motors.pdf

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    �Client: Tata Steel Tata Nagar�Location: Power House - 4�Application: Pump�Liquid: Effluent �Motor Power: 75 KW�Voltage: 415 Volts�Speed of Pump: 1480 RPM�Quantities: 1 Nos.Performance Parameters:

    Power before

    Quantified Business Results

    9/14/2016 80

    Power before

    Magnadrive: 50.6 KW

    Magnadrive Coupling: FGC 16.5S

    Power Consumed with

    Magnadrive Coupling: 44.27 KWH

    Energy Savings: 6.3 KWH

    Energy Saving in %. 12.45%

    Magnadrive Magnetic Coupling Model

    FGC 16.5S at Tata Steel

    PERFORMANCE REPORT FOR FGC 16.5S for pump by AVJ.pdf

  • AVJ Engineering ConsultantsAVJ Engineering Consultants Quantified Business Results

    �Client: Tata Steel Tata Nagar�Location: Coal Plant �Application: Conveyor No. 4A�Motor Power: 75 KW�Voltage: 415 Volts�Speed of Pump: 1480 RPM�Quantities: 1 Nos.Performance Parameters:

    Power Consumption Before

    Magnadrive: 54.1 KW

    9/14/2016 81

    Magnadrive: 54.1 KW

    Magnadrive Coupling: FGC 16.5S

    Power Consumed with

    Magnadrive Coupling: 50.1 KW

    Energy Savings: 4.0 KWH

    Energy Saving in %. 8%

    Continue

    FGC 16.5S on Conveyor No. 4AAt Tata Steel Ltd.

  • AVJ Engineering ConsultantsAVJ Engineering Consultants Quantified Business Results

    Study Report by Tata Steel Ltd for 75 KW Conveyor

    Study Report of MAGNA Drive r1 for conveyor of Tata Steel.pdf

    9/14/2016 82

  • AVJ Engineering ConsultantsAVJ Engineering Consultants Quantified Business Results

    9/14/2016 83

    Magnadrive Magnetic Adjustable Speed Drive Model ASD 26.5 for 190 KW IDFan at Jindal Steel & Power Ltd. RaigarhPerformance parameters for ASD 26.5 from JSPL.pdf

  • AVJ Engineering ConsultantsAVJ Engineering Consultants Quantified Business Results

    9/14/2016 84

    Magnadrive Magnetic Adjustable Speed Drive Model ASD 26.5 for 190 KW 6.6 KV ID Fan at Jindal Steel & Power Ltd. Raigarh Energy Savings around 73 KWH

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    The starting current reduced by: 27%Power Reduction by: 2.25 KW

    Quantified Business Result for MGE 07 at Infosys Hyderabad.pdf

    9/14/2016 85

    % Energy savings: 26%Pay Back period:

    KWH saved: 2.25Hrs of operation: 18Hrs / Year: 6570Cost of Power in Rs.: 6Per Year Energy savings: 2.25X6570X6 = Rs. 88695Per Month Saving in Rs.: 88695 / 12 = Rs. 7392Cost of MGE 07: Rs. 70478.00 Pay Back Period: 9.5 Months.

  • AVJ Engineering ConsultantsAVJ Engineering Consultants Competitive Analysis

    Mag

    na

    Dri

    ve A

    SD

    Mag

    na

    Dri

    ve C

    ou

    plin

    g

    V

    FD

    Ed

    dy

    Cu

    rren

    tM

    ech

    an

    ica

    l D

    evic

    es

    Flu

    id a

    nd

    Belt

    Dri

    ves

    Mag

    na

    Dri

    ve A

    SD

    Mag

    na

    Dri

    ve C

    ou

    plin

    gV

    FD

    Ed

    dy

    Cu

    rren

    tM

    ech

    an

    ica

    l D

    evic

    es

    Flu

    id a

    nd

    Belt

    Dri

    ves

    Operation Mechanical Benefits

    Variable Speed X X X s Non-contact Power Transfer X X s s

    Process Control X X X s s Reduce Vibration X X

    9/14/2016 86

    Process Control X X X s s Reduce Vibration X XEnergy Efficiency X X s s Reduce Wear X X s

    Overload/Failure Protection s X s Misalignment Tolerance X XConstant Load s X s X X Reduce Power In-Rush X X X X s

    Hi/Medium Voltage (High HP) X X s X s Soft Start/Stop X X X X s

    Increase Bearing, Seal, Eqpt Life X X

    Cost Benefits Electrical/Electronics Issues

    Ease of Installation X X s Complex to Install/Support XTroubleshooting Ease X X X s Extensive Infrastructure X

    Lower Maintenace Costs X X s Sensitive to Power Quality XMaintained In-house X X X s Harmonic Distortion XLonger Service Life X X X s Frequent Parts Replacement X

    Reliability/Reduce Downtime X X s Parts Obsolescence XLower Total Cost (1-50HP) XLower Total Cost (50HP+) X

    X = Very Characteristics = Somewhat Characteristic

  • AVJ Engineering ConsultantsAVJ Engineering Consultants

    9/14/2016 87