Publication: Rev First Printing 06/99 Copyright 9 2421 00 990 None Revised - 1999 Basler Electric Phone 618 654-2341 Route 143 Box 269 Highland IL 62249 USA Power Systems Group Fax 618 654-2351 http://www.basler.com [email protected] INSTRUCTIONS FOR VOLTAGE REGULATOR MODEL: AVC32-4 9 2421 00 101 INTRODUCTION The AVC32-4 Voltage Regulator is designed for use on 50/60 Hz brushless generators. The regulator includes frequency compensation, overexcitation foldback, selectable sensing taps, dual power inputs, droop, and a solid state build- up circuit. ELECTRICAL SPECIFICATIONS Dc Output Power: 4 Adc at 32 Vdc (128 W) maximum continuous Ac Power Input: Power is supplied from two generator windings. One winding connects to terminals X1 and X2 and delivers a voltage proportional to generator terminal voltage at a frequency equal to generator frequency. The other winding connects to terminals Z1 and Z2 and delivers a voltage proportional to generator output current at three times generator frequency. X1-X2: 35.7 to 55.2 Vac at 50 Hz 42.8 to 66.2 Vac at 60 Hz Z1-Z2: 7.2 to 27.6 Vac at 150 Hz 8.7 to 33.1 Vac at 180 Hz Sensing Input: Low Range: 95 to 140 Vac, single phase, 50/60 Hz Medium Range: 180 to 252 Vac, single phase, 50/60 Hz High Range: 330 to 504 Vac, single phase, 50/60 Hz Regulation Accuracy: Better than ±2%, no load to full load Underfrequency: Excitation is reduced when generator frequency falls below the adjustable setpoint. (See V/HZ Corner Frequency Selection and Adjustment for description). Overexcitation: Excitation current from the regulator folds back and latches to a reduced level after a time delay if the current exceeds the adjustable setpoint. (See Overexcitation / Current Limit for description). Voltage Build-Up: Internal provisions for automatic build-up from generator residual voltages as low as 2 Vac. Droop: Adjustable up to 5% when excitation voltage varies from 7.5 to 30 Vdc. Terminations: One-quarter inch Fast-On terminals. Adjustments: VOLT - Voltage regulation setpoint LIM - Output current limit STAT - Droop STAB - Stability V/Hz - Underfrequency corner PHYSICAL SPECIFICATIONS Operating Temperature: -40C (-40F) to +65C (+149F). Storage Temperature: -55C (-67F) to +85C (+185F). Vibration: Withstands 1.5 Gs at 5 to 29 Hz; 0.036" double amplitude at 29 to 52 Hz; and 5 Gs at 52 to 500 Hz. Shock: Withstands up to 15 Gs in each of three mutually perpendicular axes. Weight: 14.38 oz. (0.41kg) net. Fuses: Although the AVC32-4 has internal fuses, it is recommended that fuses with high interruption capability be installed per the interconnection diagram to protect from faults before the regulator. Refer to the Interconnection Diagrams. V/HZ CORNER FREQUENCY SELECTION AND ADJUSTMENT The regulator is preset for use with 50 Hz systems. Cutting the orange jumper (JP2) sets the regulator for use with 60 Hz systems. The corner frequency can be set by adjusting the V/Hz rheostat on the AVR. Clockwise rotation results in raising the corner frequency (shifting the curve to the right). To set the V/Hz rheostat: 1. Adjust the V/Hz rheostat fully counter clockwise (CCW). 2. Start the generator and set at rated voltage. 3. Adjust the generator to the desired corner frequency. 4. Slowly adjust the V/Hz rheostat clockwise (CW) until the generator voltage just begins to decrease. OVEREXCITATION CURRENT LIMIT The regulator features a hard current limit that is adjustable from 3 Amps to 8 Amps with the LIM rheostat. The regulator begins timing at 55% (typ) of the hard limit setpoint. After time out, output current is latched to a reduced level of 0.5 Amps (typ). The time delay is typically 11 seconds. The regulator can be reset by removing input power to the regulator. This may be accomplished by stopping the prime mover or by interrupting the regulator input with a reset switch. STABILITY ADJUST The STAB potentiometer provides adjustment to the response rate of the generator output voltage to a change in load. The regulator features two ranges of response. The regulator is preset for the slower range of response. Cutting the blue jumper (JP1) selects the faster range of response. OPERATION General: The following system operation procedures provide instructions for adjusting the AVC32-4 regulator. Symptoms resulting from a faulty regulator and certain generator system problems are included, together with suggested remedies. Complete the following steps before proceeding with the system start-up. CAUTION Fuses should be sized to meet the application. The internal fuses included with the AVC32-4 are sized to allow for maximum rated output from the regulator. The customer may want to replace these with fuses having a lower current rating for the specific application. CAUTION Meggers and high potential test equipment must not be used. Incorrect use of such equipment could damage the semiconductors contained on the regulator. Note A 22 k$ customer supplied potentiometer may be added in series with the sensing input to allow a ±5% variation of the voltage setpoint. Note Fuses must be installed per the interconnect diagrams to avoid interrupting the field current.

AVC 32-4

Embed Size (px)

Citation preview

Page 1: AVC 32-4

Publication: Rev First Printing 06/99 Copyright

9 2421 00 990 None Revised - 1999

Basler Electric

Phone 618 654-2341

Route 143 Box 269

Highland IL 62249 USA

Power Systems Group

Fax 618 654-2351

http://www.basler.com

[email protected]

INSTRUCTIONSFOR

VOLTAGE REGULATORMODEL: AVC32-4

9 2421 00 101

INTRODUCTION

The AVC32-4 Voltage Regulator is designed foruse on 50/60 Hz brushless generators. Theregulator includes frequency compensation,overexcitation foldback, selectable sensing taps,dual power inputs, droop, and a solid state build-up circuit.

ELECTRICAL SPECIFICATIONS

Dc Output Power:4 Adc at 32 Vdc (128 W) maximum continuous

Ac Power Input:

Power is supplied from two generator windings.One winding connects to terminals X1 and X2 anddelivers a voltage proportional to generatorterminal voltage at a frequency equal to generatorfrequency. The other winding connects toterminals Z1 and Z2 and delivers a voltageproportional to generator output current at threetimes generator frequency.

X1-X2:35.7 to 55.2 Vac at 50 Hz42.8 to 66.2 Vac at 60 Hz

Z1-Z2:7.2 to 27.6 Vac at 150 Hz8.7 to 33.1 Vac at 180 Hz

Sensing Input:

Low Range:95 to 140 Vac, single phase, 50/60 Hz

Medium Range:180 to 252 Vac, single phase, 50/60 Hz

High Range:330 to 504 Vac, single phase, 50/60 Hz

Regulation Accuracy:

Better than ±2%, no load to full load

Underfrequency:

Excitation is reduced when generator frequencyfalls below the adjustable setpoint. (See V/HZCorner Frequency Selection and Adjustment fordescription).

Overexcitation:

Excitation current from the regulator folds backand latches to a reduced level after a time delay ifthe current exceeds the adjustable setpoint. (SeeOverexcitation / Current Limit for description).

Voltage Build-Up:

Internal provisions for automatic build-up fromgenerator residual voltages as low as 2 Vac.

Droop:

Adjustable up to 5% when excitation voltagevaries from 7.5 to 30 Vdc.

Terminations:

One-quarter inch Fast-On terminals.

Adjustments:

VOLT - Voltage regulation setpointLIM - Output current limitSTAT - DroopSTAB - StabilityV/Hz - Underfrequency corner

PHYSICAL SPECIFICATIONS

Operating Temperature:

-40�C (-40�F) to +65�C (+149�F).

Storage Temperature:-55�C (-67�F) to +85�C (+185�F).

Vibration:

Withstands 1.5 Gs at 5 to 29 Hz; 0.036" doubleamplitude at 29 to 52 Hz; and 5 Gs at 52 to 500Hz.

Shock:

Withstands up to 15 Gs in each of three mutuallyperpendicular axes.

Weight:

14.38 oz. (0.41kg) net.

Fuses:

Although the AVC32-4 has internal fuses, it isrecommended that fuses with high interruptioncapability be installed per the interconnectiondiagram to protect from faults before the regulator.Refer to the Interconnection Diagrams.

V/HZ CORNER FREQUENCY SELECTION ANDADJUSTMENT

The regulator is preset for use with 50 Hzsystems. Cutting the orange jumper (JP2) setsthe regulator for use with 60 Hz systems.

The corner frequency can be set by adjusting theV/Hz rheostat on the AVR. Clockwise rotationresults in raising the corner frequency (shifting thecurve to the right).

To set the V/Hz rheostat:1. Adjust the V/Hz rheostat fully counterclockwise (CCW).2. Start the generator and set at rated voltage.3. Adjust the generator to the desired cornerfrequency.4. Slowly adjust the V/Hz rheostat clockwise(CW) until the generator voltage just begins todecrease.

OVEREXCITATION CURRENT LIMIT

The regulator features a hard current limit that isadjustable from 3 Amps to 8 Amps with the LIMrheostat. The regulator begins timing at 55% (typ)of the hard limit setpoint. After time out, outputcurrent is latched to a reduced level of 0.5 Amps(typ). The time delay is typically 11 seconds.

The regulator can be reset by removing inputpower to the regulator. This may be accomplishedby stopping the prime mover or by interrupting theregulator input with a reset switch.

STABILITY ADJUST

The STAB potentiometer provides adjustment tothe response rate of the generator output voltageto a change in load. The regulator features tworanges of response. The regulator is preset forthe slower range of response. Cutting the bluejumper (JP1) selects the faster range of response.

OPERATION

General:

The following system operation proceduresprovide instructions for adjusting the AVC32-4regulator. Symptoms resulting from a faultyregulator and certain generator system problemsare included, together with suggested remedies.

Complete the following steps before proceedingwith the system start-up.

CAUTIONFuses should be sized to meet theapplication. The internal fuses included withthe AVC32-4 are sized to allow for maximumrated output from the regulator. Thecustomer may want to replace these withfuses having a lower current rating for thespecific application.

CAUTIONMeggers and high potential test equipmentmust not be used. Incorrect use of suche q u i p m e n t c o u l d d a m a g e t h esemiconductors contained on the regulator.

NoteA 22 k� customer supplied potentiometer maybe added in series with the sensing input toallow a ±5% variation of the voltage setpoint.

NoteFuses must be installed per the interconnectdiagrams to avoid interrupting the field current.

Page 2: AVC 32-4

Publication: Rev First Printing 06/99 Page

9 2421 00 990 None Revised - 2

GENERATOR

A

B

C

AVC32-4

3802201100

22k

Exciter Field

F+ F-

ShuntAuxiliary Windings

X2 Z1X1E-E+

2

1

Z2

Series

2

1

1ExcitationON/OFF(If Used)

RemoteAdjust

2

1 Items not supplied by Basler Electric.

Select fuses based on system requirements and with high interrupting capacity

D2851-05.vsd06-30-99

1

Figure 1. Interconnection Diagram

NoteAll voltage reading are to be taken with anRMS reading voltmeter.

AVC32-4

380

400 V

200 V

0

IndicatorLamp

X1E-E+

1

Z2

2

1 Items not supplied by Basler Electric.

Select fuses based on system requirements and with high interrupting capacity

D2851-06.vsd06-30-99

2

12:1

��� 9$&�

����� +]

50 V

200 V

11:41

Figure 2. Operational Test

127(6�

������

����

������

����

���

���

�������

�������

��� ',$����

���

�������

�������

������

7<3� � 3/&6

��� ',0(16,216 ,1 3$5(17+(6,6 $5( ,1 ,1&+(6�

���� ',$�

������

7<3� � 3/&6

-3�

-3�

'��������YVG

��������

Figure 3. Overall Dimensions, Top View

127(6�

��� ',0(16,216

,1 3$5(17+(6,6

$5( ,1 ,1&+(6�

'��������YVG

��������

����

�������

���

���

�����

������

����

�������

��

��

92/7

67$7

9�+]

67$%

/,0

6�1

;;;;;;

02'(/12�

Figure 4. Overall Dimensions, SideView

Preliminary Set-up:

1. Verify that the voltage regulator specificationsconform with the generator system requirements.

2. Ensure the voltage regulator is correctlyconnected to the generator system.

3. Install the fuses as described in FUSES.

4. Set the regulator VOLT, LIM, STAT, and V/HZadjustments fully CCW (minimum).

5. Set the regulator STAB adjust and the remotevoltage adjust (if used) to mid range.

System Start-up:

1. Perform preliminary set-up as described in theabove paragraphs.

2. Start the prime mover and bring up to ratedspeed.Result: Voltage should build up. If not, performfield flashing.

3. Slowly turn the regulator VOLT adjust CW untilthe generator output voltage reaches the nominalvalue. If used, adjust the remote pot to set thegenerator voltage to the exact value desired.

4. Check the regulator under normal operatingconditions.Result: Voltage regulation should be better than+/- 2% no load to full load. If regulation is notwithin this range, verify the prime mover is at ratedspeed. Voltage reduction under load may be due

to speed change from no load to full load, causingthe frequency compensation (V/Hz) circuit toreduce voltage at lower frequencies.

OPERATIONAL TEST

1. Connect the test setup as shown in Figure 2. Do not apply power. Ensure that the light bulb israted for 120V and is less than 100W.

2. Turn the VOLT adjust to maximum CW and theSTAB adjust to mid range.

3. Apply 200 Vac, 50/60 Hz to the test set.Result: The light bulb should illuminate.

4. Slowly turn the VOLT adjust CCW.Result: At the regulation point, the light bulbshould extinguish. Small adjustments above andbelow this level should cause the light bulb to goon and off.