INDEX OF DRAWINGS:
SITE LOCATION MAP
Warner Robins
Central Georgia Technical CollegeBuilding C - South WingAutomotive Lab HVAC
ENGINEERSCONSULTING
250 Charter Lane,
Suite 100
Macon, Georgia 31210
Macon (478) 405-8301
Fax (478) 405-8210
WWW.AHPENGR.COM
ANDREWS, HAMMOCK & POWELL, INC.
ELECTRICAL OVERALL FLOOR PLAN
MECHANICAL LEGEND, GENERAL NOTES AND SCHEDULES
MECHANICAL DETAILS
MECHANICAL AND ELECTRICAL NEW WORK FLOOR PLAN
TITLE SHEET
E101
M601
M501
M101
T1
SCALE:
MECHANICAL FLOOR PLAN1/8"=1'-0"
M101
MECHANICAL FLOOR PLAN
CTH
WMH
24 X 24
5
6
S
10
4 4
T
T
T T
T
T
1
1
1 1
1
1
2
2
3
3
T
RTAC-1
MVD37 X 20
87
7
9
(THIS SHEET ONLY)NOTES:
(TYP)
(TYP)
A4515
RTAC-1
11
LOCATION AS NECESSARY.
EXISTING PROPELLER FAN TO REMAIN AT THIS APPROXIMATE LOCATION. FIELD VERIFY EXACT 11
ACCORDANCE WITH CONDENSATE PIPE SUPPORT ON ROOF DETAIL.
DOWNSPOUT ADJACENT TO TRENCH DRAIN AS INDICATED. SUPPORT DRAIN PIPING IN
LOCATION. ENSURE PIPE TERMINATION POINT IS SUCH THAT CONDENSATE DISCHARGES INTO
FULL SIZE CONDENSATE DRAIN LINE DISCHARGES INTO ROOF GUTTER AT THIS APPROXIMATE 10
TO STRUCTURE IN ACCORDANCE WITH MANUFACTURERS INSTALLATION INSTRUCTIONS.
MOUNT SUPPLY DROP BOX WITH TOP ELEVATION AT BOTTOM OF BAR JOISTS. SECURE DROP BOX 9
ANGLE IRON FRAME.
COVER INLET OF RETURN DUCT WITH 1X1 WELDED WIRE FABRIC SECURED TO DUCTWORK WITH 8
JOISTS IF POSSIBLE). FIELD VERIFY EXACT JOIST LOCATIONS.
DUCTWORK OF INDICATED SIZE IS ROUTED AS HIGH AS POSSIBLE IN SPACE (BETWEEN BAR 7
BETWEEN ROOF JOISTS AS INDICATED.
37X13 RETURN DUCT DROPS FROM CONNECTION TO UNIT, ELBOWS 37X20 AND IS ROUTED 6
DROP, ELBOWS 24X24 AND IS ROUTED BETWEEN ROOF JOISTS AS INDICATED.
29X14 SUPPLY DUCT DROPS FROM CONNECTION TO UNIT, TRANSITIONS TO 29X24 IN VERTICAL 5
VERIFY EXACT LOCATION AS NECESSARY.
EXISTING SIDEWALL SUPPLY GRILLES TO REMAIN AT THIS APPROXIMATE LOCATION. FIELD 4
VERIFY EXACT LOCATION AS NECESSARY.
EXISTING UNIT HEATER THERMOSTAT TO REMAIN AT THIS APPROXIMATE LOCATION. FIELD 3
AS NECESSARY.
EXISTING PIPING TO REMAIN AT THIS APPROXIMATE LOCATION. FIELD VERIFY EXACT LOCATION 2
EXACT LOCATION AS NECESSARY.
EXISTING HYDRONIC UNIT HEATER TO REMAIN IN THIS APPROXIMATE LOCATION. FIELD VERIFY 1
D
D
SUBJECT TO GENERAL
COPYRIGHT LAWS c
ROEG
GIA
PROFESSIONAL
No. 17029
ENGINEER
REGISTERED
JAMES A. ANDREWS,
JR
.
DATE:
NUMBER:PROJECT
TITLE:
SHEET NUMBER:
REVISIONS
DATE DESCRIPTION
DRAWN BY:
CHECKED BY:
2019112
EN
GIN
EE
RS
CO
NS
ULTIN
G
250 C
harter
Lane,
Suite 1
00
Macon,
Georgia 3
1210
Macon (478) 405-8
301
Fax (478) 405-8
210
WW
W.A
HP
EN
GR.C
OM
AN
DR
EW
S,
HA
MM
OC
K & P
OW
EL
L, IN
C.
Georgia
Warn
er
Robins
Auto
motive S
hop H
VA
CCentral
Georgia T
echnical C
ollege
April 8, 2019
C549
QUICKSTART
BAY #2 BAY #3 BAY #4 BAY #5
C550
AUTOMOTIVE TECH LAB
C557
STORAGE
C556
TOOL ROOM
C554
MECHANICAL ROOM
C553
OFFICE
C551
WOMEN
C552
MEN
C559
CLASSROOM
C551
CLASSROOM
C560
ENTRY
C562
AUTO TECHNOLOGY LAB
C563
CLASSROOM
C558
CORRIDOR
ABOVE
SKYLIGHT
C523
STORAGE
C501
STORAGE
FAMMABLE
TRENCH DRAIN
BAY #1
M501
CTH
WMH
SEE CONDENSATE DRAIN TRAP DETAIL.
ACCUMULATION OF CONDENSATE.
LOCATION THAT WILL NOT CAUSE
SPILL CONDENSATE ON ROOF IN A
ROOF CURB. SEE ROOF CURB DETAIL.
SIZE TO DUCT SIZES SHOWN ON DRAWINGS.
TRANSITION FROM RTAC SUPPLY AND RETURN CONNECTION
DUCT SO FLEXIBLE DUCT CONNECTION IS NOT STRAINED.
ARRANGEMENT, AND FOR LINER REQUIREMENTS. SUPPORT
SEE FLOOR PLANS FOR EXACT SUPPLY AND RETURN DUCT
ROOFTOP AIR CONDITIONING UNIT (RTAC UNIT)
FLEXIBLE DUCT CONNECTION (TYPICAL)
UTILITY OPENING IN BASE OF UNIT.
OUTLET CIRCUIT INSIDE CURB, AND THRU FACTORY INSTALLED
ROUTE POWER CIRCUIT, CONTROLS CIRCUIT, AND CONVENIENCE
OVER STRUCTURAL MEMBERS.
SO SUPPLY AND RETURN DUCT DROPS ARE NOT CENTERED
FOR EXACT LOCATION AND SIZE. SHIFT RTAC AS REQUIRED
WITH STRUCTURAL MEMBERS. SEE STRUCTURAL DRAWINGS
CARFULLY COORDINATE DUCT DROPS AND RTAC LOCATION
SU
PP
LY
RE
TU
RN
D
3. MAINTAIN MINIMUM 6 FEET TO ROOF EDGE.
INTAKE TO EXHAUST FANS, VTR'S, ETC.
2. MAINTAIN MINIMUM 10 FEET FROM ROOFTOP UNITS OUTDOOR AIR
AROUND UNIT.
1. MAINTAIN MANUFACTURERS RECOMMENDED SERVICE CLEARANCE
GENERAL NOTES:
ROOFTOP AIR CONDITIONING UNIT DETAILSCALE: NONE
GYP BOARD FOR SOUND ATTENUATION.
"85OF CURB SHALL BE PROVIDED WITH 4 LAYERS OF
WHERE SPECIFICALLY SHOWN ON DRAWINGS, INTERIOR
UNION
3"
AC UNIT
OPEN END NIPPLE
CONDENSATE DRAIN TRAP DETAILSCALE: NONE
IN SPECIFICATIONS
SLOPE AS REQUIRED
PIPE NIPPLE
DRAIN CONNECTION
PIPE REQUIRED MATERIAL
SEE DRAWINGS FOR
ON THE DRAIN PAN CONNECTION
THE SAME DIAMETER AS THE NIPPLE
DRAIN PIPE SHALL BE AT LEAST
"211
ROOF CURB DETAIL - NEW CURB ON EXISTING ROOFSCALE: NONE
GASKET SEALER
PRESSURE TREATED WOOD NAILER
RIGID INSULATION
METAL ROOF CURB
14"
CU
RB H
EIG
HT
EQUIPMENT
LOCATION WITH MECH. UNIT
COORDINATE DUCT OPENING
BENEATH ENTIRE ROOF CURB,
ROOF DECK TO EXTEND
MINIMUM 2 SCREWS PER SIDE.
SCREWS ON 18" CENTERS. PROVIDE
" (MINIMUM) HEX HEAD21" X 116
5
EXISTING ROOF
ROOF MANUFACTURER'S BOND REQUIREMENTS.
OF NEW ROOF CURB IN ACCORDANCE WITH
RE-WORK ROOFING FOR INSTALLATION
DUCT
UNDER ROOF CURB.
FULL PERIMETER STRUCTURAL STEEL FRAMING
LAG BOLT
THICKNESS.
AS REQUIRED TO MATCH INSULATION
PRESSURE TREATED BLOCKING
ANCHOR TO DECK
EXISTING METAL DECK
MECHANICAL DETAILS
SCALE: NONE
CONDENSATE PIPE SUPPORT ON ROOF DETAIL
6"
FRONT VIEW SIDE VIEW
4"
VERIFY SIZE (TYP)
CONDENSATE PIPE,
(TYPICAL)
FITTINGS (ERICO CADDY PYRAMID RPSE)
ON MAXIMUM 8 FT. CENTERS AND 24" OF
DIAMETER BEING SUPPORTED. SPACED
RUBBER PIPE SUPPORT. VERIFY PIPE
UV - STABILIZED, EPDM ADJUSTABLE
VA
RIE
S
SHALL USE ERICO CADDY PYRAMID ST ADJUSTABLE STRUCT SUPPORT OR EQUAL BY MIRO .
ELEVATIONS ABOVE ROOF OF 7" OR LESS. CONDENSATE ELEVATIONS ABOVE 8"
GENERAL: THIS CONDENSATE SUPPORT SHALL BE USED WITH DRAIN
LED CONFIRMING IONIZATION OPERATION
NEEDLEPOINT ELECTRODES
BI-POLAR IONIZATION CONTROL DETAILNONESCALE:
INSIDE UNIT IN SUPPLY AIRSTREAM.
BI-POLAR IONIZATION UNIT MOUNTED
RTAC'S
SUPPLY FAN FOR
MAY BE MOUNTED / REQUIRED
FOR QUANTITY. MORE THAN ONE
BIPOLAR UNIT. SEE SCHEDULE
SCHEDULE FOR TYPE
TO 24VAC TERMINALS AT RTAC. SEE
24VAC (RTAC'S)
FRAMING UNDER CURB.
PROVIDE FULL PERIMETER STRUCTURAL
SUBJECT TO GENERAL
COPYRIGHT LAWS c
ROEG
GIA
PROFESSIONAL
No. 17029
ENGINEER
REGISTERED
JAMES A. ANDREWS,
JR
.
DATE:
NUMBER:PROJECT
TITLE:
SHEET NUMBER:
REVISIONS
DATE DESCRIPTION
DRAWN BY:
CHECKED BY:
2019112
EN
GIN
EE
RS
CO
NS
ULTIN
G
250 C
harter
Lane,
Suite 1
00
Macon,
Georgia 3
1210
Macon (478) 405-8
301
Fax (478) 405-8
210
WW
W.A
HP
EN
GR.C
OM
AN
DR
EW
S,
HA
MM
OC
K & P
OW
EL
L, IN
C.
Georgia
Warn
er
Robins
Auto
motive S
hop H
VA
CCentral
Georgia T
echnical C
ollege
April 8, 2019
M601
CTH
WMH
GENERAL NOTES
11. INSTALL DUCT PENETRATIONS THROUGH NON-RATED WALLS AS SHOWN IN "DUCT PENETRATION THRU WALL DETAIL".
10. PROVIDE PIPE HANGERS FOR ALL SUSPENDED PIPING AS SHOWN IN HANGER DETAILS. PROVIDE PIPE STAND FOR ALL FLOOR/ GRADE MOUNTED PIPING AS SHOWN IN PIPE STAND DETAIL.
9. PROVIDE PIPE SLEEVE THRU ALL WALLS AND THRU ALL FLOOR SLABS. SEE PIPE SLEEVE DETAIL.
DETAILS OR REINFORCEMENT DETAILS. WHERE ARCHITECTURAL DRAWINGS INDICATE SOUND RATED WALLS, PROVIDE WALL SLEEVES FOR PIPE AND DUCTS PRIOR TO FILLING WITH SAND.
8. PROVIDE STRUCTURAL FRAMING AROUND FULL PERIMETER OF ALL ROOF OPENINGS/EQUIPMENT. PROVIDE STRUCTURAL LINTELS ABOVE ALL WALL OPENINGS. SEE STRUCTURAL FOR LINTEL
TRANSFERRED THROUGH TRANSFER DUCTS, SMOKE DAMPERS, ETC.
BASED ON ASTM E84 TEST. RETURN AIR FROM SOME CONDITIONED SPACES IS TRANSFERRED TO ABOVE CEILINGS THRU SUPPLEMENTARY TRANSFER GRILLES WHERE INDICATED. AIR IS THEN
7. MOST AREAS ABOVE CEILINGS ARE USED AS RETURN AIR PLENUMS. ALL MATERIAL IN PLENUM SPACE SHALL HAVE MAXIMUM FLAME SPREAD OF 25 AND MAXIMUM SMOKE DEVELOPMENT OF 50
BUILDING STRUCTURAL MEMBERS TO SUPPORT ALL SYSTEMS INSIDE THE BUILDING.
6. SUPPORT ALL DUCTS, PIPING AND EQUIPMENT FROM PRIMARY BUILDING STRUCTURAL MEMBERS AND PROVIDE SUPPLEMENTAL STRUCTURAL FRAMING AS REQUIRED BETWEEN PRIMARY
ETC.) OF ALL MECHANICAL EQUIPMENT PRIOR TO ORDERING/INSTALLING EQUIPMENT.
5. REFER TO THE ELECTRICAL DRAWINGS FOR VOLTAGE, PHASE, MAXIMUM ALLOWABLE CURRENT DRAW AMPERAGE AND CONNECTION ARRANGEMENT (SINGLE OR MULTI-POINT CONNECTION,
4. DUCT SIZES INDICATED ON THE PLANS ARE CLEAR INSIDE DIMENSIONS REQUIRED. WHERE LINER IS INDICATED, INCREASE DUCT SIZE.
CEILING PLANS FOR EXACT LOCATION.
3. COORDINATE LOCATION OF CEILING REGISTERS WITH LIGHTING LAYOUT, SPRINKLER HEADS AND CEILING GRID SYSTEMS AND APPURTENANCES. REFER TO ARCHITECTURAL REFLECTED
SHIFT EQUIPMENT AS REQUIRED TO AVOID CONFLICTS WITH OTHER INSTALLATIONS.
2. COORDINATE DUCT AND PIPE ROUTING AND EQUIPMENT LOCATION WITH PLUMBING AND ELECTRICAL INSTALLATIONS AND WITH BUILDING STRUCTURAL MEMBERS. OFF-SET DUCTS/PIPING AND
1. SEE ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR EXACT BUILDING ARRANGEMENT, DIMENSIONS AND DETAILS. THESE DRAWINGS ARE DIAGRAMMATIC AND ARE NOT TO BE SCALED.
MECHANICAL SCHEDULES
ROOFTOP AIR CONDITIONING UNITS
TAG
MBH
COOLING
TOTAL
MBH
COOLING
SENSIBLE
CFM
SUPPLY
TOTAL
CFM
OA
MBH
INPUT
HEATING
MBH
OUTPUT
HEATING
NOTES:
IN. WG
SUPPLY ESP
APPROX.
RTAC-1
STAGES
MIN
COOL HEAT DB WB
40
AIR ºF
ENTERING
COOLING ºF
AMBIENT
MINIMUM
50TC-E14 4515 150 2 0 76.5 66.1150.5 101.5
TAG
BPIU-1
EQUIPMENT
ASSOCIATEDCFM NOTES:
MODEL #
SOLUTIONS
GLOBAL PLASMA
RTAC-1
BI-POLAR IONIZATION UNITS
1:2:3:4
PROVIDE MULTIPLE BIPOLAR UNITS OF QUANTITY INDICATED.*
UNIT SHALL BE MOUNTED INSIDE RTAC.4.
BIPOLAR UNIT FROM ASSOCIATED EQUIPMENT'S 24V FAN TERMINAL.
PROVIDE FACTORY FURNISHED 24 VAC INPUT TERMINAL FOR POWERING 3.
PROVIDE LED TO VERIFY IONIZATION.2.
NEEDLES. SEE BIPOLAR IONIZATION CONTROL DETAIL.
STEEL HOUSING, AND CARBON OR STAINLESS STEEL IONIZATION
NEEDLE POINT TYPE IONIZER WITH ABS PLASTIC OR POWDER COATED 1.
(2) GPS-FC-3BAS
GRILLES
TAG
LENGTH
OR
SIZE
FINISH THROW NOTES:
A WHITE
LEGEND
500
AGRILLE, REGISTER, DIFFUSER DESIGNATION ABOVE WITH CFM SHOWN BELOW FOR TAB AGENT TO BALANCE DEVICE AT
16 X 12 DUCT SIZE: FIRST DIMENSION IS SIDE DRAWN
RIGID ROUND DUCTWORK OR FLUE PIPING
FLEXIBLE CONNECTION
RECTANGULAR - TO - ROUND DUCT TRANSITION
SQUARE ELBOW WITH TURNING VANES
45° BRANCH ENTRY FITTING
MVD MVD MANUAL VOLUME DAMPER (OPPOSED BLADE)
AP ACCESS PANEL IN SIDE OF DUCT
SUPPLY DUCT TO OR FROM ABOVE
RETURN OR EXHAUST DUCT TO OR FROM ABOVE
INDICATES EQUIPMENT ON ROOF
DUCT OR PIPE OFFEST: ARROW HEAD INDICATES DIRECTION OF RISE
RETURN OR EXHAUST AIR FLOW
SD 10/6 DUCTWORK SPLITTER DAMPER: SPLIT DIMENSION INDICATED
T THERMOSTAT/SENSOR WITH LOCKING PLASTIC OR METAL COVER AS SPECIFIED
T WALL MOUNTED DDC TEMPERATURE SENSOR W/THUMBWHEEL ADJUSTMENT [AND PUSHBUTTON OVERIDE]
S DUCT MOUNTED SMOKE DETECTOR (PROVIDED AND WIRED BY ELEC. AND INSTALLED BY MECH.)
D CONDENSATE DRAIN PIPING
R REFRIGERANT PIPING
PIPE SLEEVE THRU WALL OR FLOOR. SEE PIPE SLEEVE DETAIL.
DROPPING OR RISING PIPE
PIPE TO OR FROM ABOVE
ELBOW - 45°; ELBOW - 90°
TEE
DB, WB DRY BULB, WET BULB
FPM FEET PER MINUTE
CFM,cf CUBIC FEET PER MINUTE
OA OUTDOOR AIR
MBH BTU/HR x 1000
APPROX. APPROXIMATELY
ESP IN WG EXTERNAL STATIC PRESSURE INCHES WATER GUAGE
HP HORSEPOWER
RPM REVOLUTIONS PER MINUTE
AFF ABOVE FINISHED FLOOR
KW KILOWATTS
Δt TEMPERATURE DIFFERENCE
B.E. T.E. BOTTOM ELEVATION, TOP ELEVATION
LIMIT OF SCOPE OF WORK
2
M1
SECTION OR DETAIL IDENTIFICATION NUMBER
SHEET NUMBER ON WHICH SECTION OR DETAIL IS DRAWN
C POWER CONTACTOR PROVIDED BY MECHANICAL
H DDC HUMIDITY SENSOR
T DDC TEMPERATURE SENSOR
UC "43UNDERCUT DOOR
" THICK OR 1" THICK, RESPECTIVELY21ACOUSTICAL/THERMAL DUCT LINER -
NUMBER
MODEL
CARRIER
- - .6 3.42
BHP
MOTOR
SUPPLY
NUMBER
MODEL
PLENUMS, INC
342420 DL2010 4-WAY
4515
24 X 20 NECK, (4) 20 X 10 DRUM LOUVERS 1:2
PLUS OR MGM PRODUCTS.
2. HEAVY GAUGE STEEL SUPPLY DROP BOX WITH 1" THICK, 1.5 LB. INSULATION AND ALUMINUM DRUM LOUVER GRILLES. BOX SHALL BE PROVIDED BY PLENUMS INC., ALADDIN SHEET METAL, CURBS
1. NC LEVEL NOT TO EXCEED NC 35.
16. PROVIDE FORWARD CURVED BELT DRIVE INDOOR FAN WITH ADJUSTABLE SHEAVE. ALL BELT DRIVE FANS SHALL HAVE SELF-ADJUSTING BELT TENSIONERS (IF AVAILABLE AS OPTION).
15. PROVIDE FACTORY FURNISHED BAROMETRIC RELIEF DAMPERS.
IONIZATION CONTROL DETAIL.
PRESCRIPTIVE PROCEDURE. THIS UNIT SHALL BE PROVIDED WITH A CONTRACTOR INSTALLED NEEDLE POINT BI-POLAR IONIZATION UNIT TO REDUCE CONTAMINENT LEVELS TO THOSE EQUAL TO OR LOWER THAN THE VENTILATION RATE PROCEDURE. SEE BI-POLAR
14. OUTDOOR AIR CFM FOR THIS UNIT AND AREA HAS BEEN DETERMINED BASED ON ASHRAE 62.1 INDOOR AIR QUALITY PROCEDURE RATHER THAN THE PRESCRIPTIVE VENTILATION RATE PROCEDURE. THE OUTDOOR AIR RATES USING THIS PROCEDURE ARE LOWER THAN THE
13 PROVIDE INTEGRAL HOT GAS REHEAT DEHUMIDIFICATION COIL CIRCUIT. UNIT SHALL HAVE MINIMUM EER AT AHRI OF 11.0.
12. PROVIDE HINGED ACCESS DOORS.
11. PROVIDE LOUVERED CONDENSER COIL HAIL GUARDS.
INTEGRATED ECONOMIZER CONTROLS TO ALLOW SIMULTANEOUS ECONOMIZER/COMPRESSOR OPERATION.
10. PROVIDE DRY BULB TYPE OUTDOOR AIR ECONOMIZER AND INTAKE HOOD WITH MINIMUM O.A. POSITION SETTING AND MODULATING ULTRA LOW LEAKAGE ECONOMIZER DAMPERS. INTAKE HOOD/ECONOMIZER SHALL BE DESIGNED FOR UP TO 100% OF SUPPLY CFM. PROVIDE
9. PROVIDE ELECTROMECHANICAL CONTROLLER.
8. PROVIDE FACTORY INSTALLED POWERED G.F.I. CONVENIENCE OUTLET.
RTAC UNIT AND NEW UNIT SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER.
ALL BE ROUTED UP INSIDE THE CURB. CONTRACTOR SHALL ROUTE UTILITIES IN FACTORY DESIGNATED LOCATION. UNDER NO CIRCUMSTANCES SHALL CONTRACTOR CUT OPENINGS IN BOTTOM OF RTAC UNIT. FIELD CUTTING OF RTAC UNIT SHALL RESULT IN REJECTION OF
7. PROVIDE FACTORY INSTALLED 'INSIDE THE CURB' UTILITY PROVISIONS (POWER CIRCUIT, AND CONTROLS CIRCUIT) SO THAT NO ELECTRICAL UTILITIES ARE OUTSIDE UNIT CASING. GAS CONNECTION SHALL BE OUTSIDE CASING. POWER CIRCUIT, AND CONTROL CIRCUIT SHALL
6. PROVIDE FACTORY INSTALLED NON-FUSED DISCONNECT SWITCH. .
5. STATIC PRESSURE SCHEDULED DOES NOT INCLUDE WET COOLING COIL, FILTER, HEATING PLANT OR SYSTEM EFFECT LOSSES.
4. UNIT SHALL HAVE VERTICAL DISCHARGE AND RETURN MOUNTED ATOP FULL PERIMETER, MINIMUM 14" TALL, ROOF CURB. SEE ROOF CURB DETAIL.
3. PROVIDE TRAPPED CONDENSATE DRAIN. SEE CONDENSATE DRAIN TRAP DETAIL.
AIR CONDITIONING UNIT DETAIL.
2. COOLING CAPACITIES BASED ON AIR ENTERING EVAPORATOR AT SCHEDULED CONDITION AND 95ºF AMBIENT AIR TEMPERATURE. UNIT SHALL PROVIDE MECHANICAL COOLING DOWN TO SCHEDULED TEMPERATURE. UNIT SHALL UTILIZE R-410a REFRIGERANT. SEE ROOFTOP
1. COOLING ONLY, PACKAGED DX ROOFTOP UNIT.
1:2:3:4:5:6:7:8:9:10:11:12:13:14:15:16
SUBJECT TO GENERAL
COPYRIGHT LAWS c
ROEG
GIA
PROFESSIONAL
No. 17029
ENGINEER
REGISTERED
JAMES A. ANDREWS,
JR
.
DATE:
NUMBER:PROJECT
TITLE:
SHEET NUMBER:
REVISIONS
DATE DESCRIPTION
DRAWN BY:
CHECKED BY:
2019112
EN
GIN
EE
RS
CO
NS
ULTIN
G
250 C
harter
Lane,
Suite 1
00
Macon,
Georgia 3
1210
Macon (478) 405-8
301
Fax (478) 405-8
210
WW
W.A
HP
EN
GR.C
OM
AN
DR
EW
S,
HA
MM
OC
K & P
OW
EL
L, IN
C.
Georgia
Warn
er
Robins
Auto
motive S
hop H
VA
CCentral
Georgia T
echnical C
ollege
April 8, 2019
MPC1
HIGH BAYHIGH BAYLOW BAYLOW BAY
HIGH BAY
1
MPC1- 2
RTAC-1
SCALE:
ELECTRICAL OVERALL FLOOR PLAN1/16"=1'-0"
(THIS SHEET ONLY)NOTES:
FA
FA
FA
7
6
4
E101
S
S
33333
AREAS TO MINIMIZE DISTURBANCE OF DAY TO DAY ACTIVITIES.
SHALL WORK WITH OWNER'S SCHEDULING FOR ACCESS TO THESE
CONDUIT PATHWAY GOES THRU MULTIPLE CLASSROOMS. CONTRACTOR
GENERAL CONDUIT ROUTING NOTE:
KAB
KAB
PLAN
ELECTRICAL OVERALL FLOOR
ALARM CONTROL PANEL IS LOCATED IN ROOM 'A150' ON GROUND FLOOR OF BUILDING 'A'.
DEVICE TO NEW DUCT MOUNTED DETECTOR AND REPROGRAM SYSTEM. EXISTING FIRE
CONTRACTOR SHALL EXTEND EXISTING FIRE ALARM 'SLC' LOOP FROM EXISTING INITIATING 7
DEVICE SHALL BE COMPATIBLE WITH EXISTING EDWARDS ANALOG ADDRESSABLE SYSTEM.
DETECTOR SHALL BE PROVIDED BY ELECTRICAL INSTALLED BY MECHANICAL CONTRACTOR.
PROVIDE NEW ADDRESSABLE DUCT MOUNTED SMOKE DETECTOR FOR NEW ROOF TOP UNIT. 6
DISCONNECT.
COMPARTMENT OF UNIT. MAKE CONNECTION TO UNIT MOUNTED SINGLE POINT POWERED
CONTRACTOR SHALL ROUTE CONDUIT VIA MECHANICAL ROOF CURB UP INTO ELECTRICAL 5
CONDUIT SHALL BE ROUTED ABOVE / AROUND THIS EQUIPMENT.
CONTRACTOR SHALL BE AWARE OF EXISTING OVERHEAD CRANE TRACK SYSTEM IN THIS BAY. 4
PRIOR TO BID. EXISTING WALL FIRE RATINGS SHALL BE MAINTAINED.
STRUCTURE. CONTRACTOR IS ENCOURAGED TO WALK SITE TO DETERMINE CONDUIT PATHWAY
CONCTRACTOR MAY ROUTE CONDUIT ALONG EXISTING BUILDING WALLS OR THRU CIELING
GENERAL: THIS CIRCUIT PATH HAS BOTH HIGH AND LOW BAY AREAS ALONG THE ROUTE.3
1" SPARE CONDUIT STUBBED OUT OF PANEL TO GAIN ENTRY.
3#6, #8G, 1"C FROM NEW BREAKER TO ROOFTOP UNIT. CONTRACTOR MAY UTILZE EXISTING
CONTRACTOR SHALL PROVIDE A 40A/3P BREAKER FOR EXISTING PANEL 'MPC1'. ROUTE 2
EXISTING SQUARE-D I-LINE PANELBOARD 'MPC1' (480/277V, 3PH, 4W, 400AMP) TO REMAIN. 1
LOW BAY
RACEWAY IN CEILING OR WALL
ONE CROSSMARK PER WIRE, 2 WIRES UNLESS SHOWN
HOMERUN - ONE ARROW PER CIRCUIT
FA=FIRE ALARM, IC=INTERCOM, TV=TELEVISION, C=COMPUTER
EXPOSED RACEWAY
FLEXIBLE RACEWAY
CONDUIT - UP, DOWN
HEAT DETECTOR
SPEAKER - CEILING PENDENT (WP=WEATERPROOF)
SMOKE DETECTOR - WALL, CEILING
DUCT MOUNTED SMOKE DETECTOR
COMMUNICATION AND PROTECTION
120/208V, 3PH, 4W OR 240V, 1PH, 3W
480/277V, 3PH, 4W
FIRE VOICE EVACUATION AND POWER SUPPLY PANEL (FAA=ANNUNCIATOR PANEL, FAP BATT.=SUB PANEL)
ELECTRICAL LEGEND
FA
FAP
S
H
S SP
S
S
PANELS
CIRCUITS
RACEWAY IN CEILING OR WALL
ONE CROSSMARK PER WIRE, 2 WIRES UNLESS SHOWN
HOMERUN - ONE ARROW PER CIRCUIT
FA=FIRE ALARM, IC=INTERCOM, TV=TELEVISION, C=COMPUTER
EXPOSED RACEWAY
FLEXIBLE RACEWAY
CONDUIT - UP, DOWN
HEAT DETECTOR
SPEAKER - CEILING PENDENT (WP=WEATERPROOF)
SMOKE DETECTOR - WALL, CEILING
DUCT MOUNTED SMOKE DETECTOR
COMMUNICATION AND PROTECTION
120/208V, 3PH, 4W OR 240V, 1PH, 3W
480/277V, 3PH, 4W
FIRE VOICE EVACUATION AND POWER SUPPLY PANEL (FAA=ANNUNCIATOR PANEL, FAP BATT.=SUB PANEL)
ELECTRICAL LEGEND
FA
FAP
S
H
S SP
S
S
PANELS
CIRCUITS
C513
POWERPLANT LAB
C502
ROOM #1
BATT.
C503
ROOM #2
BATT.
C504
AREA
COMPRESSOR
C514
AIRFRAME LAB
C515
HANGER
C516
WELDING & JOINING TECHNOLOGY
C517
CHILLERS
C507
STORAGE
GAS
C508
ROOM
ELECTRICAL
MAIN
C509
ENTRY ROOM
TELEPHONE
C511
STORAGE
GENERAL
C512
OFFICE
RECEIVING
MAINT./
C522
DRAFTING
C521
BLUEPRINT
C519
STORAGEC510
STORAGE
TECHNOLOGY
ELECTRONIC
C520
MANAGEMENT LAB
ENVIRONMENTAL WASTE
C534
REFERENCE
C518
BOILER
C533
ELEC.#2
C532
STORAGEC531
TOOL ROOM
C530
REFERENCE
AVIATION MAINT.
C528
MOCK-UP STORAGE
C529
MECHANICAL ROOM
C527
DATA
TELE/C526
ELEC.#1
C525
STORAGE
QUALITY CONTROL
C524
TOOL ROOM
C548
JAN.
C536
LAB
CONTROL
QUALITY
C537
CLASSROOM #1
QUALITY CONTROL
C538
CLASSROOM #2
QUALITY CONTROL
C539
WORK
C540
MENC541
WOMEN
C542
10 OFFICE AREA
SKYLIGHT
C543
CLASSROOM #1
AVIATION MAINT. TECH.
C544
CLASSROOM #2
AVIATION MAINT. TECH.
C545
NAVIGATION LAB
COMMUNICATIONS &
C546
CLASSROOM
WELDING/JOINING
C547
STORAGE
C548
STORAGE
SKYLIGHTSKYLIGHT
C549
QUICKSTART
BAY #2 BAY #3 BAY #4 BAY #5
C550
AUTOMOTIVE TECH LAB
C557
STORAGE
C556
TOOL ROOM
C554
MECHANICAL ROOM
C553
OFFICE
C551
WOMEN
C552
MEN
C559
CLASSROOM
C551
CLASSROOM
C560
ENTRY
C562
AUTO TECHNOLOGY LAB
C563
CLASSROOM
C558
CORRIDOR
ABOVE
SKYLIGHT
C523
STORAGE
C501
STORAGE
FAMMABLE
TRENCH DRAIN
BAY #1
SUBJECT TO GENERAL
COPYRIGHT LAWS c
ROEG
GIA
PROFESSIONAL
No. 17029
ENGINEER
REGISTERED
JAMES A. ANDREWS,
JR
.
DATE:
NUMBER:PROJECT
TITLE:
SHEET NUMBER:
REVISIONS
DATE DESCRIPTION
DRAWN BY:
CHECKED BY:
2019112
EN
GIN
EE
RS
CO
NS
ULTIN
G
250 C
harter
Lane,
Suite 1
00
Macon,
Georgia 3
1210
Macon (478) 405-8
301
Fax (478) 405-8
210
WW
W.A
HP
EN
GR.C
OM
AN
DR
EW
S,
HA
MM
OC
K & P
OW
EL
L, IN
C.
Georgia
Warn
er
Robins
Auto
motive S
hop H
VA
CCentral
Georgia T
echnical C
ollege
April 8, 2019
T
T
T T
T
T