SPRINKLER OPERATION: The operating mechanism is a frangible glass bulb which contains a heat responsive liquid. During a fire, the ambient temperature rises causing the liquid in the bulb to expand. When the ambient tem- perature reaches the rated temperature of the sprinkler, the bulb shatters. As a result, the waterway is cleared of all sealing parts and water is discharged towards the deflector. The deflector is designed to distribute the water in a pattern that is most effective in controlling the fire. COVERAGE: Residential spray coverage up to 400 sq. ft./37.2sq. m room sizes per NFPA 13. TECHNICAL SPECIFICATIONS: Models: V2730, V2732 Style: Pendent and Recessed Pendent Nominal Orifice Size: 7/16"/12 mm K-Factor: V2730 – 4.9 Imp./7.1 S.I.^ for room sizes up to 16'/4.9 m. V2732 – 4.9 Imp./7.1 S.I.^ for room sizes 18 to 20'/5.5 and 6.1 m. Nominal Thread Size: 1/2" NPT/15 mm Max. Working Pressure: 175 psi/1200 kPa Factory Hydrostatic Test: 100% @ 500 psi/3450 kPa Min. Operating Pressure: 7psi/48 kPa Temperature Rating: See chart on page 2 Material Specifications Pendent Deflector: Bronze per UNS C51000 Bulb: Glass with glycerin solution. Bulb Nominal Diameter: Quick Response: 3.0mm Load Screw: Bronze per UNS C65100 Pip Cap: Bronze per UNS C65100 Seal: Teflon* tape Frame: Die cast brass 65-30 Accessories Installation Wrench: Open End: V27 Recessed: V27-2 Sprinkler Finishes: Plain brass Chrome plated White painted** Custom painted** For escutcheons, cabinets and other accessories refer to separate sheet. ^ For K-Factor when pressure is measured in Bar, multiply S.I. units by 10.0. * Teflon is a registered trademark of Dupont Co. ** UL Listed for corrosion resistance. NOTE: Weather resistant recessed escutcheons available upon request. These Model V27 residential sprinklers are designed to meet the requirements of NFPA 13, 13D and 13R for residential use in a variety of room sizes, depending upon available operating pres- sure and room configuration. Models V2730 and V2732 are UL Listed for use under smooth flat horizontal ceilings. The design incorporates state-of-the-art, heat responsive, frangible glass bulb design (quick response) for prompt, precise operation. The die cast frame is more streamlined and attractive than traditional sand cast frames. It is cast with a hex-shaped wrench boss to allow easy tightening from many angles, reducing assembly effort. This sprinkler is available in various finishes to meet many design requirements. Exaggerated for Clarity V2732 or V2730 40.41_1 V27, K4.9 Residential Pendent, Recessed Pendent V2730 QUICK RESPONSE V2732 QUICK RESPONSE 40.41 FIRE PROTECTION PRODUCTS – AUTOMATIC SPRINKLERS PENDENT (V2730) RECESSED PENDENT (V2732) JOB/OWNER CONTRACTOR ENGINEER System No. ______________________________ Submitted By ____________________________ Spec Sect _______________ Para ___________ Location ________________________________ Date ___________________________________ Approved _______________________________ Date ___________________________________ www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2013 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_F SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS DISCONTINUED PRODUCT

AUTOMATIC SPRINKLERS 40.41 V27, K4 - … · is cleared of all sealing parts and water is discharged ... to distribute the water in a pattern that is most effective in controlling

Embed Size (px)

Citation preview

SPRINKLER OPERATION: The operating mechanism is a frangible glass bulb which contains a heat responsive liquid. During a fire, the ambient temperature rises causing the liquid in the bulb to expand. When the ambient tem-perature reaches the rated temperature of the sprinkler, the bulb shatters. As a result, the waterway is cleared of all sealing parts and water is discharged towards the deflector. The deflector is designed to distribute the water in a pattern that is most effective in controlling the fire.

COVERAGE: Residential spray coverage up to 400 sq. ft./37.2sq. m room sizes per NFPA 13.

TECHNICAL SPECIFICATIONS: Models: V2730, V2732Style: Pendent and RecessedPendentNominal Orifice Size: 7/16"/12 mmK-Factor:

• V2730–4.9Imp./7.1S.I.^forroomsizesupto16'/4.9m.• V2732–4.9Imp./7.1S.I.^forroom sizes 18 to 20'/5.5 and 6.1 m.

Nominal Thread Size: 1/2" NPT/15 mmMax. Working Pressure: 175 psi/1200 kPaFactory Hydrostatic Test:

100% @ 500 psi/3450 kPaMin. Operating Pressure: 7psi/48 kPaTemperature Rating:Seechartonpage2

Material SpecificationsPendent Deflector:BronzeperUNSC51000Bulb: Glass with glycerin solution.Bulb Nominal Diameter:

• QuickResponse:3.0mmLoad Screw:BronzeperUNSC65100Pip Cap:BronzeperUNSC65100Seal: Teflon* tapeFrame: Die cast brass 65-30

AccessoriesInstallation Wrench:

• OpenEnd:V27• Recessed:V27-2

Sprinkler Finishes:• Plainbrass• Chromeplated• Whitepainted**• Custompainted**

For escutcheons, cabinets and other accessories refer to separate sheet.

^ ForK-FactorwhenpressureismeasuredinBar,multiplyS.I.unitsby10.0.

* TeflonisaregisteredtrademarkofDupontCo.** UL Listed for corrosion resistance.NOTE:Weatherresistantrecessedescutcheonsavailable upon request.

These Model V27 residential sprinklers are designed to meet the requirements of NFPA 13, 13D and 13R for residential use in a variety of room sizes, depending upon available operating pres-sure and room configuration. Models V2730 and V2732 are UL Listed for use under smooth flat horizontal ceilings. The design incorporates state-of-the-art, heat responsive, frangible glass bulb design (quick response) for prompt, precise operation.

Thediecastframeismorestreamlinedandattractivethantraditionalsandcastframes.Itiscastwith a hex-shaped wrench boss to allow easy tightening from many angles, reducing assembly effort. This sprinkler is available in various finishes to meet many design requirements.

Exaggerated for Clarity

V2732or

V2730

40.41_1

V27, K4.9Residential Pendent, Recessed Pendent

V2730 QUICK RESPONSEV2732 QUICK RESPONSE

40.41FIRE PROTECTION PRODUCTS – AUTOMATIC SPRINKLERS

PENDENT(V2730)

RECESSED PENDENT (V2732)

JOB/OWNER CONTRACTOR ENGINEER

SystemNo. ______________________________ SubmittedBy ____________________________ SpecSect _______________ Para ___________

Location ________________________________ Date ___________________________________ Approved _______________________________

Date ___________________________________

www.victaulic.comVICTAULICISAREGISTEREDTRADEMARKOFVICTAULICCOMPANY.©2013VICTAULICCOMPANY.ALLRIGHTSRESERVED.

REV_F

SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS

DISCONTIN

UED PRODUCT

APPROVALS/LISTINGSModel

Orifice Size

Nominal K-Factor Response Deflector Type

Approved Temperature Ratings ˚F/˚C ‡

Inches mm

Imperial S.I.^

Standard or Quick cULus NYC/MEA† CSFM §

V2730 7/16 4.9 Quick Pendent 155, 175 68, 79

155, 175 68, 79

155, 175 68, 7912 7.1

V2730 7/16 4.9 Quick Recessed Pendent Up to 1/2" Adjustment

155, 175 68, 79

155, 175 68, 79

155, 175 68, 7912 7.1

V2732 7/16 4.9 Quick Pendent 155, 175 68, 79

155, 175 68, 79

155, 175 68, 7912 7.1

V2732 7/16 4.9 Quick Recessed Pendent Up to 1/2" Adjustment

155, 17568, 79

155, 17568, 79

155, 17568, 7912 7.1

‡ Listings and approval as of printing.^ For K-Factor when pressure is measured in Bar, multiply S.I. units by 10.0. † MEA #62-99-E.§CSFM#7690-0531:112

RATINGS Allglassbulbsareratedfortemperaturesfrom–67°F/–55°Ctothoseshownintablebelow.

Sprinkler Temperature Classification

Victaulic Part

Identification

Temperature – ºF/ºC

Nominal Temperature Rating

Maximum Ambient Temperature Allowed Glass Bulb Color

Ordinary C 155 100 Red68 38

Intermediate E 175 150 Yellow79 66

40.41_2

40.41FIRE PROTECTION PRODUCTS – AUTOMATIC SPRINKLERS

V27, K4.9Residential Pendent, Recessed Pendent

V2730 QUICK RESPONSEV2732 QUICK RESPONSE

VICTAULICISAREGISTEREDTRADEMARKOFVICTAULICCOMPANY.©2013VICTAULICCOMPANY.ALLRIGHTSRESERVED.

REV_F

DISCONTIN

UED PRODUCT

ORDERING INFORMATION Pleasespecifythefollowingwhenordering:

Sprinkler Model Number

Style

Temperature Rating

K-Factor

Thread Size

Quantity

Sprinkler Finish

Escutcheon Finish

Wrench Model Number

40.41_3

40.41FIRE PROTECTION PRODUCTS – AUTOMATIC SPRINKLERS

V27, K4.9Residential Pendent, Recessed Pendent

V2730 QUICK RESPONSEV2732 QUICK RESPONSE

www.victaulic.comVICTAULICISAREGISTEREDTRADEMARKOFVICTAULICCOMPANY.©2013VICTAULICCOMPANY.ALLRIGHTSRESERVED.

REV_F

DISCONTIN

UED PRODUCT

WARNING WARNING

• Always read and understand installation, care, and maintenance instructions, supplied with each box of sprinklers, before proceeding with installation of any sprinklers.

• Always wear safety glasses and foot protection.

• Depressurize and drain the piping system before attempting to install, remove, or adjust any Victaulic piping products.

• Installation rules, especially those governing obstruction, must be strictly followed.

• Painting, plating, or any re-coating of sprinklers (other than that sup-plied by Victaulic) is not allowed.

Failure to follow these instructions could result in serious personal injury and/or property damage.

The owner is responsible for maintaining the fire protection system and devices in proper operating condition. For minimum maintenance and inspection requirements, refer to the current National Fire Protection Association pamphlet that describes care and maintenance of sprinkler systems. In addition, the authority having jurisdiction may have addi-tional maintenance, testing, and inspection requirements that must be followed.

If you need additional copies of this publication, or if you have any questions about the safe installation of this product, contact Victaulic World Headquarters: P.O. Box 31, Easton, Pennsylvania 18044-0031 USA, Telephone: 001-610-559-3300.

AVAILABLE WRENCHESSprinkler Type Open End Recessed

V2730, V2732 – Pendent V27 V27-2

V2730, V2732 – RecessedPendent — V27-2

40.41_4

40.41FIRE PROTECTION PRODUCTS – AUTOMATIC SPRINKLERS

V27, K4.9Residential Pendent, Recessed Pendent

V2730 QUICK RESPONSEV2732 QUICK RESPONSE

VICTAULICISAREGISTEREDTRADEMARKOFVICTAULICCOMPANY.©2013VICTAULICCOMPANY.ALLRIGHTSRESERVED.

REV_F

DISCONTIN

UED PRODUCT

DIMENSIONS

½" Adjustment Recessed – V2730 (drawing not to scale)

23⁄8"(61 mm)

15⁄8"(42 mm)

15⁄32"(29 mm)

23⁄8"/60 mmMax. Hole

2"/51 mmMin. Hole

9⁄16"/14 mm

111⁄16"/44 mm

215⁄16"/75 mm

Typical Ceiling Tile

Finished Surface

Typical Ceiling Tile

Finished Surface

MAXIMUM EXTENSION

13⁄16"/30 mm

13⁄16"/30 mm

MAXIMUM RECESS

11⁄16"/18 mm

23⁄8" (60 mm)Max. Hole

2" (51 mm)Min. Hole

9⁄16"(14 mm)

111⁄16"(44 mm)

215⁄16"(75 mm)

Typical Ceiling Tile

Finished Surface

Typical Ceiling Tile

Finished Surface

MAXIMUM EXTENSION

11⁄16"(27 mm)

13⁄16"(30 mm)

MAXIMUM RECESS

11⁄16"(18 mm)

23⁄8"(61 mm)

15⁄8"(42 mm)

15⁄32"(29 mm)

½" Adjustment Recessed – V2732 (drawing not to scale)

Standard Pendent - V2730 Standard Pendent - V2732

40.41_5

40.41FIRE PROTECTION PRODUCTS – AUTOMATIC SPRINKLERS

V27, K4.9Residential Pendent, Recessed Pendent

V2730 QUICK RESPONSEV2732 QUICK RESPONSE

www.victaulic.comVICTAULICISAREGISTEREDTRADEMARKOFVICTAULICCOMPANY.©2013VICTAULICCOMPANY.ALLRIGHTSRESERVED.

REV_F

DISCONTIN

UED PRODUCT

DIMENSIONS AND ROOM SIZE VictaulicV2730,4.9K-FactorPendentSprinkler ForCeilingtypesrefertoNFPA13,13Ror13D2013Editions

Max.Coverage

Area(a)

Ordinary TempRating

155°F/68°C

Intermediate TempRating

175°F/79°CDeflector to

CeilingInstallation

TypeMinimum Spacing

Ft. x Ft.m x m

Flow(b)

GPML/min

Pressure(b)

PSIbar

Flow(b)

GPML/min

Pressure(b)

PSIbar

Ft.m

12 X 12 13 7.0 13 7.0

1 3/16 to 4 inch

1/2” recessed Escutcheon or non-recessed per NFPA 13, 13R or 13D

8.02.4

3.7 X 3.7 49.2 0.48 49.2 0.48

14 X 14 13 7.0 13 7.04.3 X 4.3 49.2 0.48 49.2 0.48

16 X 16 13 7.0 13 7.04.9 X 4.9 49.2 0.48 49.2 0.48

18 X 18 N/A N/A N/A N/A5.5 X 5.5

20 X 20 N/A N/A N/A N/A6.1 X 6.1

Notes: ^ For K-Factor when pressure is measured in Bar, multiply S.I. units by 10.0. (a) For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) For NFPA 13 residential applications, the greater of 0.1gpm/ft2 over the design area of the flow in accordance with the criteria in the table must be used.

VictaulicV2732,4.9K-FactorPendentSprinkler ForCeilingtypesrefertoNFPA13,13Ror13D2013Editions

Max.Coverage

Area(a)

Ordinary TempRating

155°F/68°C

Intermediate TempRating

175°F/79°CDeflector to

CeilingInstallation

TypeMinimum Spacing

Ft. x Ft.m x m

Flow(b)

GPML/min

Pressure(b)

PSIbar

Flow(b)

GPML/min

Pressure(b)

PSIbar

Ft.m

12 X 12 13 7.0 13 7.0

1 3/16 to 4 inch

1/2" recessed Escutcheon or non-recessed per NFPA 13, 13R or 13D

8.02.4

3.7 X 3.7 49.2 0.48 49.2 0.48

14 X 14 17 12 17 124.3 X 4.3 64.3 0.83 64.3 0.83

16 X 16 17 12 17 124.9 X 4.9 64.3 0.83 64.3 0.83

18 X 18 17 12 17 125.5 X 5.5 64.3 0.83 64.3 0.83

20 X 20 20 16.7 20 16.76.1 X 6.1 75.7 1.15 75.7 1.15

Notes: ^ For K-Factor when pressure is measured in Bar, multiply S.I. units by 10.0. a) For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) For NFPA 13 residential applications, the greater of 0.1gpm/ft2 over the design area of the flow in accordance with the criteria in the table must be used.

40.41_6

40.41FIRE PROTECTION PRODUCTS – AUTOMATIC SPRINKLERS

V27, K4.9Residential Pendent, Recessed Pendent

V2730 QUICK RESPONSEV2732 QUICK RESPONSE

VICTAULICISAREGISTEREDTRADEMARKOFVICTAULICCOMPANY.©2013VICTAULICCOMPANY.ALLRIGHTSRESERVED.

REV_F

DISCONTIN

UED PRODUCT

NOMINAL WETTING PATTERNS

Model V2732 K4.9 Residential Pendent and Recessed Pendent

13GPM/49.2LPM–12'x12'/3.6x3.6mcoveragearea

Model V2730 K4.9 Residential Pendent and Recessed Pendent

13GPM/49.2LPM–12'x12'/3.6x3.6mcoveragearea

8'2,4 m

5'1,5 m

7'2,1 m

6'1,8 m

4'1,2 m

1'0,3 m 2'

0,6 m

4'1,2 m

6'1,8 m

4'1,2 m

2'0,6 m

0'

3'0,9 m

2'0,8 m

0'CLOF ROOM

MODEL V2730K4.9 RESIDENTIAL PENDENT AND RECESSED PENDENT

13 GPM (49,2 LPM)

NOMINAL WETTING PATTERN12' x 12' COVERAGE AREA

8'2,4 m

5'1,5 m

7'2,1 m

6'1,8 m

4'1,2 m

1'0,3 m 2'

0,6 m

4'1,2 m

6'1,8 m

4'1,2 m

2'0,6 m

0'

3'0,9 m

2'0,8 m

0'CLOF ROOM

MODEL V2732K4.9 RESIDENTIAL PENDENT AND RECESSED PENDENT

13 GPM (49,2 LPM)

NOMINAL WETTING PATTERN12' x 12' COVERAGE AREA

40.41_7

40.41FIRE PROTECTION PRODUCTS – AUTOMATIC SPRINKLERS

V27, K4.9Residential Pendent, Recessed Pendent

V2730 QUICK RESPONSEV2732 QUICK RESPONSE

www.victaulic.comVICTAULICISAREGISTEREDTRADEMARKOFVICTAULICCOMPANY.©2013VICTAULICCOMPANY.ALLRIGHTSRESERVED.

REV_F

DISCONTIN

UED PRODUCT

NOMINAL WETTING PATTERNS

Model V2732 K4.9 Residential Pendent and Recessed Pendent

17GPM/64.3LPM–18'x18'/5.5x5.5mcoveragearea

Model V2730 K4.9 Residential Pendent and Recessed Pendent

13GPM/49.2LPM–14'x14'/4.3x4.3mcoveragearea

8'2,4 m

5'1,5 m

7'2,1 m

6'1,8 m

4'1,2 m

1'0,3 m

3'0,9 m

2'0,8 m

0'

2'0,6 m

4'1,2 m

6'1,8 m

6'1,8 m

4'1,2 m

2'0,6 m

0'

CL OF ROOM

7'

NOMINAL WETTING PATTERN14' x 14' COVERAGE AREA

MODEL V2730K4.9 RESIDENTIAL PENDENT AND RECESSED PENDENT

13 GPM (49,2 LPM)

8'2,4 m

5'1,5 m

7'2,1 m

6'1,8 m

4'1,2 m

1'0,3 m

3'0,9 m

2'0,8 m

0'2'

0,6 m

4'1,2 m

6'1,8 m

8'2,4 m

8'2,4 m

6'1,8 m

4'1,2 m

2'0,6 m

0'9'

CLOF ROOM

MODEL V2732K4.9 RESIDENTIAL PENDENT AND RECESSED PENDENT

17 GPM (64,3 LPM)

NOMINAL WETTING PATTERN18' x 18' COVERAGE AREA

40.41_8

40.41FIRE PROTECTION PRODUCTS – AUTOMATIC SPRINKLERS

V27, K4.9Residential Pendent, Recessed Pendent

V2730 QUICK RESPONSEV2732 QUICK RESPONSE

VICTAULICISAREGISTEREDTRADEMARKOFVICTAULICCOMPANY.©2013VICTAULICCOMPANY.ALLRIGHTSRESERVED.

REV_F

DISCONTIN

UED PRODUCT

NOTES:

1 Data shown is approximate and can vary due to differences in installation.

2 These graphs illustrate approximate wall-wetting patterns for these specific Victaulic FireLock AutomaticSprinklers.Theyareprovidedasinformationforguidanceandshouldnotbeusedasminimumsprinklerspacingrulesforinstallation.Sprinklerlocationshallbeinaccordancewiththe obstruction rules for residential sprinklers in NFPA 13 (2002 or later revision). Failure to follow these guidelines could adversely affect the performance of the sprinkler and will void all Listings, Approvals and Warranties.

3 All patterns are symmetrical to waterway.

NOMINAL WETTING PATTERNS

Model V2732 K4.9 Residential Pendent and Recessed Pendent

20GPM/75.7LPM–20'x20'/6.1x6.1mcoveragearea

Model V2730 K4.1 Residential Pendent and Recessed Pendent

13GPM/49.2LPM–16'x16'/4.9x4.9mcoveragearea

8'2,4 m

5'1,5 m

7'2,1 m

6'1,8 m

4'1,2 m

1'0,3 m

3'0,9 m

2'0,8 m

0'

2'0,6 m

4'1,2 m

6'1,8 m

8'2,4 m

6'1,8 m

4'1,2 m

2'0,6 m

0'

CLOF ROOM

MODEL V2730K4.9 RESIDENTIAL PENDENT AND RECESSED PENDENT

13 GPM (49,2 LPM)

NOMINAL WETTING PATTERN16' x 16' COVERAGE AREA

MODEL V2732K4.9 RESIDENTIAL PENDENT AND RECESSED PENDENT

20 GPM (75,7 LPM)

NOMINAL WETTING PATTERN20' x 20' COVERAGE AREA

8'2,4 m

5'1,5 m

7'2,1 m

6'1,8 m

4'1,2 m

1'0,3 m

3'0,9 m

2'0,8 m

0'

0'

CL OF ROOM2'0,6 m

4'1,2 m

8'2,4 m6'

1,8 m

6'1,8 m

8'2,4 m

10'3,0 m

4'1,2 m

2'0,6 m

0'

40.41_9

40.41FIRE PROTECTION PRODUCTS – AUTOMATIC SPRINKLERS

V27, K4.9Residential Pendent, Recessed Pendent

V2730 QUICK RESPONSEV2732 QUICK RESPONSE

www.victaulic.comVICTAULICISAREGISTEREDTRADEMARKOFVICTAULICCOMPANY.©2013VICTAULICCOMPANY.ALLRIGHTSRESERVED.

REV_F

DISCONTIN

UED PRODUCT

WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details.

This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations.

NOTE

40.41

V27, K4.9Residential Pendent, Recessed Pendent

V2730 QUICK RESPONSEV2732 QUICK RESPONSE

40.41FIRE PROTECTION PRODUCTS – AUTOMATIC SPRINKLERS

For complete contact information, visit www.victaulic.com40.41 3533 REV F UPDATED 04/2013VICTAULICISAREGISTEREDTRADEMARKOFVICTAULICCOMPANY.©2013VICTAULICCOMPANY.ALLRIGHTSRESERVED.

DISCONTIN

UED PRODUCT