Automatic Detectors Series IQ8Quad (Intelligent Addressable) Automatic intelligent fire detectors with high reliability, used for premises and items of property with medium and high concentration of valuable assets. Detector series IQ8Quad features, system advantages designed for optimal operation on System 8000 and IQ8Control fire alarm systems with multisensor detectors for the detection of all types of fires, even under the most diffi- cult operating conditions detector with and without loop isolator Different options of installation -wiring in loop and spur combination, e.g. -maximum number of detectors with cable lengths of up to 3500 m with installation cable for fire detection, e.g. cables I-Y(St)Yn x 2 x 0.8 mm -up to 127 detectors and detector zones per loop installation -up to 32 detectors per zone Easy commissioning -automatic detector addressing -fixed address assignment of detector location, even after detectors have been replaced or added -localization of wire breaks and short circuits on loop -detector-LED used as alarm indicator and as an indicator for detectors in service -adaptation to changing operating conditions -dedicated LED for indicating operation (green LED) -disconnection of individual detectors, detector zones and detection areas -disconnection of individual sensors or several sensors at once within a multisensor detector; either manually or depending on programmed time of the day Automatic adaptation to varying environmental conditions -compensation of changing levels of air pressure, humidity, smoke concentration according to the double chamber principle -electronic compensation of long-term influences like aging or pollution Reliable detection -constant alarm sensitivity of multisensor detector for all types of fire -large signal to noise ratio due to the special design of the sensors and the electronics to suppress electromagnetic interference Reliable false alarm suppression -high immunity against false alarms by means of timed evaluation of different sensor criteria -signal patterns not typical for fires are eliminated by using special filter algorithms -automatic self-monitoring of detector electronics -continuous loop monitoring even during short-circuits through isolating the relevant segment -automatic monitoring of all sensors to guarantee operational capacity and correct condi- tion. Increased operating reliability -short-circuit and wire break tolerant through monitoring from both ends of the loop -alarm decision inside detector -fail-safe circuit activated if communication fails Maintenance -automatic maintenance request -heat detector identification through a black circle on the light transmission plate -multisensor gas detector identification through a golden loop on the circle transmission plate -operating time-, alarm- and fault counter in each detector -automatic, cyclic loop check -complete status interrogation from the control panel -interrogation of operating data from all detectors on loop via standard service PC and detector interface Comprehensive range of accessories -standard detector base and relay base -base adapter for ceiling mounting -dust cover for fire detector or detector base -kit for suspended ceiling mounting -RF base www.esser-systems.com

Automatic Detectors Series IQ8Quad (Intelligent Addressable)...Marquage spécial pour le détecteur de chaleur sur le diffuseur lumineux: Cercle noir. ¬q8hA ¬qBhU ¬q8jG 802371 803371

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Automatic Detectors Series IQ8Quad (Intelligent Addressable)...Marquage spécial pour le détecteur de chaleur sur le diffuseur lumineux: Cercle noir. ¬q8hA ¬qBhU ¬q8jG 802371 803371

Automatic Detectors Series IQ8Quad (Intelligent Addressable)

Automatic intelligent fire detectors with high reliability, used for premises and items of property with medium and high concentration of valuable assets.Detector series IQ8Quad features, system advantagesdesigned for optimal operation on System 8000 and IQ8Control fire alarm systemswith multisensor detectors for the detection of all types of fires, even under the most diffi-cult operating conditionsdetector with and without loop isolatorDifferent options of installation-wiring in loop and spur combination, e.g.-maximum number of detectors with cable lengths of up to 3500 m with installation cable for fire detection, e.g. cables I-Y(St)Yn x 2 x 0.8 mm-up to 127 detectors and detector zones per loop installation-up to 32 detectors per zoneEasy commissioning-automatic detector addressing-fixed address assignment of detector location, even after detectors have been replaced or added-localization of wire breaks and short circuits on loop-detector-LED used as alarm indicator and as an indicator for detectors in service-adaptation to changing operating conditions-dedicated LED for indicating operation (green LED)-disconnection of individual detectors, detector zones and detection areas-disconnection of individual sensors or several sensors at once within a multisensor detector; either manually or depending on programmed time of the dayAutomatic adaptation to varying environmental conditions-compensation of changing levels of air pressure, humidity, smoke concentration according to the double chamber principle-electronic compensation of long-term influences like aging or pollutionReliable detection-constant alarm sensitivity of multisensor detector for all types of fire-large signal to noise ratio due to the special design of the sensors and the electronics to suppress electromagnetic interferenceReliable false alarm suppression-high immunity against false alarms by means of timed evaluation of different sensor criteria-signal patterns not typical for fires are eliminated by using special filter algorithms-automatic self-monitoring of detector electronics-continuous loop monitoring even during short-circuits through isolating the relevant segment-automatic monitoring of all sensors to guarantee operational capacity and correct condi-tion.Increased operating reliability-short-circuit and wire break tolerant through monitoring from both ends of the loop-alarm decision inside detector-fail-safe circuit activated if communication failsMaintenance-automatic maintenance request-heat detector identification through a black circle on the light transmission plate-multisensor gas detector identification through a golden loop on the circle transmission plate-operating time-, alarm- and fault counter in each detector-automatic, cyclic loop check-complete status interrogation from the control panel-interrogation of operating data from all detectors on loop via standard service PC and detector interfaceComprehensive range of accessories-standard detector base and relay base-base adapter for ceiling mounting-dust cover for fire detector or detector base-kit for suspended ceiling mounting-RF base

www.esser-systems.com

Page 2: Automatic Detectors Series IQ8Quad (Intelligent Addressable)...Marquage spécial pour le détecteur de chaleur sur le diffuseur lumineux: Cercle noir. ¬q8hA ¬qBhU ¬q8jG 802371 803371

¬q6h=

¬q6h§/G&

802171

802171.F

Fixed heat detector IQ8Quad

Fixed heat detector IQ8Quad - France

Automatic heat detector with fast semiconductor sensor to guarantee reliable detection of fires with strong heat generation. Intelligent fire detector with decentralised intelligence, automatic function self-test, CPU failure mode, alarm and operating data memory, alarm indicator, soft-addressing and operating indication.The detector is provided with an integrated isolator. A parallel detector indicator can be connected.

As 802171, but with NF-Approval Mark at the backside.

Automatic Detectors Series IQ8Quad (Intelligent Addressable)

Detector without integrated alarm devices

Detector base is not supplied as standard

Accessories

767800 mounting bracket805590 Standard detector base for IQ8Quad805591 Detector base with relay contact for IQ8Quad

Technical Data

Operating voltage 8 ... 42 V DCAlarm current w/o communication curtain approx. 18 mAAir speed 0 ... 25.4 m/sStorage temperature -25 °C ... 75 °CAir Humidity < 95 % (non-condensing)Type of protection IP 43 (with base + option)Material ABS plasticColor white, similar to RAL 9010Weight approx. 110 gDimensions Ø: 117 mm H: 49 mm (62 mm incl. base)

VdS, CNBOP, BOSEC

CNMIS

Approval:

Approval:

Technical Data

Quiescent current @ 19 V DC approx. 40 μAArea to be monitored max. 30 m²Height to be monitored max. 7.5 mApplication temperature -20 °C ... 50 °CDetector specification EN 54 - 5 A1S / -17

Technical Data

Operating voltage 8 ... 42 V DCQuiescent current @ 19 V DC approx. 40 μAHeight to be monitored max. 7.5 mApplication temperature -20 °C ... 50 °CDetector specification EN 54 - 5 A1S, EN54-17

Special-colour on demand

The detectors part no. 802271, 803271, 802371, 803371, 802373, 802374 and 803374 are approved in the scope of the DIBt system authorization for the operation with an Automatic Door System.

Special marking for heat detector on the light pipe: black ring.

Marquage spécial pour le détecteur de chaleur sur le diffuseur lumineux: Cercle noir.

Fire detector with base

117

62

1

2

3

4

5

6

7

8

9

10

11

12

17

16

13

14

15

1

Page 3: Automatic Detectors Series IQ8Quad (Intelligent Addressable)...Marquage spécial pour le détecteur de chaleur sur le diffuseur lumineux: Cercle noir. ¬q8hA ¬qBhU ¬q8jG 802371 803371

¬q6nO

¬q7h?

¬q7h§/G(

¬qAhS

802177

802271

802271.F

803271

Fixed heat detector class B IQ8Quad

Rate-of-rise heat detector IQ8Quad

Rate-of-rise heat detector IQ8Quad - France

IQ8Quad Rate-of-rise detector without loop isolator

As 802171, but for increased operating temperature according to EN 54-5 Class B.

Automatic heat detector with fast semiconductor sensor to guarantee reliable detection of fires with rapidly rising temperatures and integrated fixed temperature function for the detection of fires with slowly rising temperatures. Intelligent fire detector with decentral-ised intelligence, automatic function self-test, CPU failure mode, alarm and operating data memory, alarm indicator, soft-addressing and operating indication.The detector is provided with an integrated isolator. A parallel detector indicator can be connected.

As 802271, but with NF-Approval Mark at the backside.

As 802271 but without loop isolator.The detector can be operated in a standard detector group as well as independently.

Automatic Detectors Series IQ8Quad (Intelligent Addressable)

VdS

VdS, CNBOP, BOSEC

CNMIS

VdS, CNBOP

Approval:

Approval:

Approval:

Approval:

Technical Data

Quiescent current @ 19 V DC approx. 40 μAArea to be monitored max. 30 m²Height to be monitored max. 6 mApplication temperature -20 °C ... 65 °CDetector specification EN 54-5 BS / -17

Technical Data

Quiescent current @ 19 V DC approx. 40 μAArea to be monitored max. 30 m²Height to be monitored max. 7.5 mApplication temperature -20 °C ... 50 °CDetector specification EN 54-5 A1 / -17

Technical Data

Operating voltage 8 ... 42 V DCQuiescent current @ 19 V DC approx. 40 μAHeight to be monitored max. 7.5 mApplication temperature -20 °C ... 50 °CDetector specification EN 54-5 A1R, EN 54-17

Technical Data

Quiescent current @ 19 V DC approx. 40 μAArea to be monitored max. 30 m²Height to be monitored max. 7.5 mApplication temperature -20 °C ... 50 °CDetector specification EN 54-5 A1DIBt approval Z-6.5-1764 license system 8000-FSA Z-6.5-1759

license system IQ8FSA 8619 Z-6.5-1808 license system 8000-FSA-PLus

Special marking for heat detector on the light pipe: black ring.

Special marking for heat detector on the light pipe: black ring.

Marquage spécial pour le détecteur de chaleur sur le diffuseur lumineux: Cercle noir.

www.esser-systems.com

Page 4: Automatic Detectors Series IQ8Quad (Intelligent Addressable)...Marquage spécial pour le détecteur de chaleur sur le diffuseur lumineux: Cercle noir. ¬q8hA ¬qBhU ¬q8jG 802371 803371

¬q8hA

¬qBhU

¬q8jG

802371

803371

802373

Optical smoke detector IQ8Quad

IQ8Quad Optical smoke detector without loop isolator

OT multisensor detector IQ8Quad

Optical smoke detector to guarantee safe and early detection of fire. Intelligent fire detector with decentralised intelligence, automatic function self-test, CPU failure mode, alarm and operating data memory, alarm indicator, soft-addressing and operating indication. The detector is provided with an integrated isolator. A parallel detector indicator can be connected.

As 802371 but without loop isolator.The detector can be operated in a standard detector group as well as independently.

Multisensor detector with integrated optical detector and heat detector, with time- controlled signal analysis and weighted data combination of both detector functions for detecting smouldering fires and fires with extreme heat generation. Intelligent detector with decentralised intelligence, self function test, CPU redundancy mode, automatic adaptation to the environments, alarm and operating data storage, alarm indication and soft addressing.The loop isolator is integrated in the detector. A parallel detector indicator is additionally attachable.

Automatic Detectors Series IQ8Quad (Intelligent Addressable)

VdS, CNBOP, BOSEC

VdS, CNBOP

VdS

Approval:

Approval:

Approval:

Technical Data

Quiescent current @ 19 V DC approx. 50 μAArea to be monitored max. 110 m²Height to be monitored max. 12 mApplication temperature -20 °C ... 72 °CDetector specification EN 54-7 / -17

Technical Data

Quiescent current @ 19 V DC approx. 50 μAArea to be monitored max. 110 m²Height to be monitored max. 12 mApplication temperature -20 °C ... 72 °CDetector specification EN 54-7DIBt approval Z-6.5-1764 license system 8000-FSA Z-6.5-1759

license system IQ8FSA 8619 Z-6.5-1808 license system 8000-FSA-PLus

Technical Data

Quiescent current @ 19 V DC approx. 50 μAArea to be monitored max. 110 m²Height to be monitored max. 12 mApplication temperature -20 °C ... 50 °CDetector specification EN 54-7/-5 A2 /-17, CEA 4021

1

2

3

4

5

6

7

8

9

10

11

12

17

16

13

14

15

1

Page 5: Automatic Detectors Series IQ8Quad (Intelligent Addressable)...Marquage spécial pour le détecteur de chaleur sur le diffuseur lumineux: Cercle noir. ¬q8hA ¬qBhU ¬q8jG 802371 803371

¬q8lM

¬q8l§/G6

¬q8kJ

802375

802375.F

802374

OTblue multisensor detector IQ8Quad

OTblue multisensor IQ8Quad - France

O2T multisensor IQ8Quad

Multisensor with integrated optical detector and heat detector. The optical measurement chamber is provided with a newly developed sensor technology, enabling the detection of open fires, smouldering fires and fires with high heat generation. Especially for open fires, the classical ionisation technology implemented in ionisation detectors is replaced by the new detection technology. The detector is capable of identifying the TF1 and TF6 test fires described in the EN 54-9:1982 specification.The OTblue multisensor is an intelligent detector with time-related signal analysis, signal correlation of the sensor data, decentralised intelligence, automatic function self-test, CPU failure mode, automatic adaptation to environmental conditions, alarm and operating data memory, alarm indicator and soft-addressing.The detector is provided with an integrated isolator and a parallel detector indicator can be connected.

As 803275, but with NF-Approval Mark at the backside.

Multisensor detector provided with two built-in optical smoke sensors with different scattered light angles as well as additional heat detector sensor evaluation to guarantee the detection of different types of fire from smouldering fires to open fires with constant sens-itivity level. Smoke sensor signal identification to ensure smoke classification and reduc-tion of deceptive alarms caused, for instance, by water vapour or dust.Because of its excellent detection characteristics, the detector is also able to identify the standardized TF1 and TF6 test fires. The O²T multisensor detector is also suitable for applications with higher temperatures of up to +65 °C. The detector is provided with an integrated isolator. A parallel detector indicator can be connected.

Automatic Detectors Series IQ8Quad (Intelligent Addressable)

VdS

NF-SSI

VdS, CNBOP, BOSEC

Approval:

Approval:

Approval:

Technical Data

Quiescent current @ 19 V DC approx. 50 μAArea to be monitored max. 110 m²Height to be monitored max. 12 mApplication temperature -20 °C ... 50 °CDetector specification EN 54-7/-5 A2 /-17, CEA 4021

Technical Data

Operating voltage 8 ... 42 V DCQuiescent current @ 19 V DC approx. 50 μAHeight to be monitored max. 12 mApplication temperature -20 °C ... 50 °CDetector specification EN 54-7/5 A2, EN54-17

Technical Data

Quiescent current @ 19 V DC approx. 60 μAArea to be monitored max. 110 m²Height to be monitored max. 12 mApplication temperature -20 °C ... 65 °CDetector specification EN 54-7/-5 B /-17, CEA 4021

www.esser-systems.com

Page 6: Automatic Detectors Series IQ8Quad (Intelligent Addressable)...Marquage spécial pour le détecteur de chaleur sur le diffuseur lumineux: Cercle noir. ¬q8hA ¬qBhU ¬q8jG 802371 803371

¬q8k§/G3

¬qBk^

¬q9jI

802374.F

803374

802473

O2T multisensor IQ8Quad - France

IQ8Quad O2T Intelligent detector without loop isolator

OTG multisensor (CO) IQ8Quad

As 802374, but with NF-Approval Mark at the backside.

As 802374 but without Loop isolator.The detector can be operated in a standard detector group as well as independently.

Multisensor detector with integrated smoke detector, heat detector and gas sensor (CO) for preventive and early detection of fires ranging from smouldering fires to open fires through combined evaluation of scattered light, temperature and gas. An alarm is actuated at carbon monoxide (CO) concentration levels that are life-threatening for humans. The detector is provided with an integrated isolator. A parallel detector indicator can be connected.

Automatic Detectors Series IQ8Quad (Intelligent Addressable)

NF-SSI

VdS, CNBOP

VdS

Approval:

Approval:

Approval:

Technical Data

Operating voltage 8 ... 42 V DCQuiescent current @ 19 V DC approx. 60 μAHeight to be monitored max. 12 mApplication temperature -20 °C ... 65 °CDetector specification EN 54-7/5 B, EN54-17

Technical Data

Quiescent current @ 19 V DC approx. 60 μAArea to be monitored max. 110 m²Height to be monitored max. 12 mApplication temperature -20 °C ... 65 °CDetector specification EN 54-7/-5 B, CEA 4021DIBt approval Z-6.5-1764 license system 8000-FSA Z-6.5-1759

license system IQ8FSA 8619 Z-6.5-1808 license system 8000-FSA-PLus

Technical Data

Quiescent current @ 19 V DC approx. 65 μAArea to be monitored max. 110 m²Height to be monitored max. 12 mApplication temperature -20 °C ... 50 °CDetector specification EN 54-7/-5 A2 /-17, CEA 4021

In the course of installation, we recommend testing the integrated CO sensor with our CO test gas (part no. 805583) or CO capsule (part no. 805553).

Programmable CO-alarm-thresholds: 10-150 ppm.

Gas sensors (CO) mainly react to the carbon monoxide arising from a fire (CO). They have, however, also a cross sensitivity to other gases, as for example hydrogen (H2), acetylene (C2H2) or nitric oxide (NO).

Special marking for gas detector on the light pipe: black ring.

1

2

3

4

5

6

7

8

9

10

11

12

17

16

13

14

15

1

Page 7: Automatic Detectors Series IQ8Quad (Intelligent Addressable)...Marquage spécial pour le détecteur de chaleur sur le diffuseur lumineux: Cercle noir. ¬q8hA ¬qBhU ¬q8jG 802371 803371

O2T Detector with integrated alarm devices

The IQ8Quad smoke detectors with built-in alarm device incorporate up to 4 different func-tionalities (detect, flash, sound, and/or speech) depending on the type (O²T/F, O²T/So, O²T/ Sp, O²T/FSp) of detector.

- fire detection as per EN 54-7- integrated heat sensor as per EN 54-5- optical alarm via flash lamp- acoustic alarm via sounder as per as per EN 54-3- acoustic alarm speech messages

DetectionMultisensor detectors with two built-in optical smoke sensors with different scattered light angles as well as additional heat detector sensor evaluation for detecting everything from smouldering fires to open fires with consistent response performance. Smoke sensor signal identification to ensure smoke classification and reduction of false alarms caused, for instance, by water vapour or dust. Each detector is provided with an integrated isolator.

Alarm signalingThe alarm signaling device is activated by the control panel. No further short address needs to be allocated. It is programmed with tools 8000 as of software version 1.05.

Alarm tone / speech message programmingFor detectors with speech message and/or alarm tone function with up to five language options, up to 4 signals can be programmed. Two signals are reserved for alarm signaling and evacuation in the case of fire. Two further signals can be programmed for other events. Each signal can consist of up to four signal components, enabling one signal to be programmed as a DIN tone combined with subsequent speech messages in three different languages.

Alarm tones can be chosen from a table with various tone types. For application in schools, a break signal to signify the breaks between class can be activated.Four different speech messages, each in three languages, are available:

- "An incident has been reported in the building. Please await further instructions.”- "Attention” please. This is an emergency. Please leave the building by the nearest avail-able exit.”- "This is a fire alarm. Please leave the building immediately by the nearest available exit.”- “This is a test message. No action is required. “

When the basic setting is selected, signals / signal components can be continuously repeated until the signalling function is interrupted by the control panel. They can also be programmed with a repetition rate of one to three times. Thus, the break signal in schools can be deliberately set to only one repetition. In the same way, the total signal can be set to continuous repetition, with the DIN tone being played only once while subsequent speech messages are played up to three times.

Sound pressure programmingThe sound level [dB (A)] can be set to eight levels, from approximately 64dB (A) to approx-imately 92dB (A).

All the security you need in one housing with four functions detection, flasher, sounder and speech alarm.

Automatic Detectors Series IQ8Quad (Intelligent Addressable)

Features

Detection• The reliable O²T multisensor principle for

consistent response performance at the highest level of security against false alarms

Flash lamp• Loop powered - no need for external power

supply• No additional short address• Automatic synchronization of various IQ8Quad

alarm signaling devices• High flash energy

• Loop powered - no need for external power supply

• No additional short address• Automatic synchronization of various IQ8Quad

alarm signaling devices• Maximum sound level: 92 dB (A) at 1 m• Maximum sound pressure can be set• Multiple signal patterns can be combined to one

signal• Signal pattern and repetition rates can be set• 20 different signal tones, incl. DIN-tone

Speech massage with sounder• Loop powered - no need for external power

supply• No additional short address• Automatic synchronization of various IQ8Quad

alarm signaling devices• Maximum sound level: 92 dB (A) at 1 m• Maximum sound pressure can be set• Multiple signal patterns can be combined to one

signal• Signal pattern and repetition rates can be set• 20 different signal tones, incl. DIN-tone• Speech messages can be played in up to 5

languages• 5 alarm messages per languages are prepro-

grammed

www.esser-systems.com

Page 8: Automatic Detectors Series IQ8Quad (Intelligent Addressable)...Marquage spécial pour le détecteur de chaleur sur le diffuseur lumineux: Cercle noir. ¬q8hA ¬qBhU ¬q8jG 802371 803371

Automatic Detectors Series IQ8Quad (Intelligent Addressable)

sequence 2 sequence 1 signal 1 (evacuation)

sequence 2 sequence 3 sequence 1 sequence 4

sequence 3 sequence 4

signal 2 (alarm)

sequence 2 sequence 3 sequence 1 sequence 4 signal 3 (event 1)

sequence 2 sequence 3 sequence 1 sequence 4 signal 4 (event 2)

Signals

All IQ8Quad detectors with built-in alarm devices can only be operated on the powered loop. For physical reasons, an increased sound level leads to a higher current consumption rate of the alarm device, the respective load factor must be considered when calculating the maximum number on the loop. Altogether up to 127 bus devices per loop can still be connected.

Please consider that an extra training is required when dealing with IQ8Quad with a built-in alarm device. The training includes installation planning and commisioning techniques. For further information take a look at our training brochure. Information concerning the calculation can be found in the "Project Planning Support“ chapter.

1

2

3

4

5

6

7

8

9

10

11

12

17

16

13

14

15

1

Page 9: Automatic Detectors Series IQ8Quad (Intelligent Addressable)...Marquage spécial pour le détecteur de chaleur sur le diffuseur lumineux: Cercle noir. ¬q8hA ¬qBhU ¬q8jG 802371 803371

O2T/Optical detector with integrated alarm devices

1 School bell complex complex

2 FP 1063.1 TelecomsBS 5839 Pt1

3 BS 5839 Pt1

4 BS 5839 Pt1

5 BS 5839 Pt1

6 BS 5839 Pt1

7 BS 5839 Pt1

8 BS 5839 Pt1

9 BS 5839 Pt1

10 DIN Tone DIN 33404 Part 3

11 French fire sound

12 NL - Slow Whoop

13 US - Horn

14 US - Horn with Temporal Pattern

15US - March Time

16 US - Slow Whoop

17 US - Siren

18 US - Hi/Lo

19 US - NFPA Whoop

20 IMOGA-Signal

0,5 sec.

0,5 sec.1,5 sec.

0,5 sec.

0,5 sec.1,5 sec.

0,5 sec.

0,5 sec.1,5 sec.

0,5 sec.

0,5 sec.

0,25 sec.

0,25 sec.

1,0 sec.0,25 sec.

10 ms

1,0 sec.

0,25 sec.

0,25 sec.

0,25 sec.

0,25 sec.

0,85 sec. 1,0 sec.

1,0 sec.

1,0 sec.

1,0 sec.

t

t

t

t

t

t

t

t

t

t

t

t

t

t

t

t

t

t

t

f

f

f

f

f

f

f

f

f

f

f

f

f

f

f

f

f

f

f

No. Description Frequency Pulse rate

Alternating 800 / 970 Hz at 2 Hz

Alternating 800 / 970 Hz at 1 Hz

Intermittent 970 Hz at 1 Hz 0.5 sec.

Intermittent 2850 Hz at 1 Hz 0.5 sec.

Intermittent 970 Hz 1/4 sec. ON - 1 sec. OFF

Continious 970 Hz

Sweep tone 800 Hz tp 970 Hz at 7 Hz

Sweep tone 800 Hz to 970 Hz at 1 Hz

1200 - 500 Hz at 1 Hz

554 Hz / 100 ms + 440 Hz / 400 ms + 10 %

500 Hz - 1200 Hz at 3.5 sec. break of 0.5 sec.

Continious 485 Hz

Intermittent 485 Hz (0,5 sec. ON; 0.5 sec. OFF; 3 times; 1.5 sec. OFF; Repeat)Alternating 485 Hz (0,25 sec. ON; 0.25 sec. OFF; Repeat)Sweep tone 500 Hz to 1200 Hz (4.0 sec. ON; 0.5 sec. OFF; Repeat)Sweep tone 600 Hz to 1200 Hz (1,0 sec. ON, Repeat)Alternating 100 Hz / 800 Hz (0.25 sec. ON; Alternate; 0.25 sec. ON; Alternate; Repeat)Sweep tone 422 Hz to 775 Hz (upwards sweep 0.85 sec.; 3 times; 1 sec. OFF; Repeat)Intermittent 800 Hz (1,0 sec. ON; 1,0 sec. OFF: 7 times; 2.0 sec. ON: 2.0 sec. OFF; Repeat)

1,0 sec.

0,1 sec.0,4 sec.

3,5 sec. 0,5 sec.

4,0 sec. 0,5 sec.

Germany(DE)

de

Dies ist ein Feueralarm. Bitte verlassen Sie das Gebäude um-gehend über dienächsten Flucht-wege. Die Feuer-wehr ist alarmiert.

Achtung, Achtung! Dies ist eine Gefahr-enmeldung. Bitte verlassen Sie das Gebäude über die nächstenAusgänge.

Achtung, im Ge-bäude ist eine Gefahrensituation gemeldet worden. Bitte bleiben Sie ruhig, und wartenSie auf weitere Anweisungen.

Dies ist eine Testdurchsage.

France(FR)

Ceci est une alarmeincendie,veuillez évacuer immédiatement les locaux par la sortie la plus proche.

fr

Votre attention s'il vous plaît, ceci est une alarme. Veuillez évacuer les locaux par la sortie la plus proche.

Un incident est signalé dans le batiment. Merci de garder votre calme et attendez les prochaines instructions.

Ceci est un test.

L'alarme est à présent annulée. Veuillez nous excuser pour le désagrément.

Die Gefahrensituationist jetzt behoben. Wir entschuldigen uns für jegliche Unannehmlichkeiten.

Great Britain(GB)

en

This is a fire alarm. Please leave the building immedia-tely by the nearest available exit.

Attention please. This is an emergen-cy. Please leave the building by the nearest available exit.

An incident has been reported in thebuilding. Please await further instructions.

This is a test message. No action is required.

The emergency is now cancelled. Weapologize for anyinconvenience.

Spain(ES)

es

Esto es una alarma de incendio. Abandonen por favor el edificio inmediatamentepor la salida de evacuaciónmás cercana.

Atención. Esto es una emergencia. Por favor abandonen el edificio por la salida de evacuación más cercana.

Atención, se ha reportado un incidente en el edificio.Aguarden por favor otras instrucciones.

Esto es un mensaje de prueba.No se requiere ninguna acción.

La emergencia ha sido cancelada.Pedimos disculpas por las molestias causadas.

Country code acc. to ISO 3166 -Alpha-2

Languagecode acc. to ISO 639-1 Evacuation 1 Evacuation 2 Alarm Test-message All-Clear

Standard speech messages of IQ8Quad detectors and IQ8Alarm

IQ8Quad detector and IQ8Alarm tone table

Italy(IT)

it

Attenzione.Allarme incendio.Abbandonare l'edificio tramite l'uscita di emergenza più vicina.

Attenzione.Allarme in corso.Vi preghiamo di recarvi pressol'uscita di emergenza più vicina.

Attenzione.E' stato rilevato un allarme.Ulteriori disposizioni vi verranno comunicate appena possibile.

Attenzione.E' in corso una prova di allarme.Non è richiesta alcuna azione.

Attenzione. Cessato allarme.La situazione di normalità è stata ripristinata.

Automatic Detectors Series IQ8Quad (Intelligent Addressable)

www.esser-systems.com

Page 10: Automatic Detectors Series IQ8Quad (Intelligent Addressable)...Marquage spécial pour le détecteur de chaleur sur le diffuseur lumineux: Cercle noir. ¬q8hA ¬qBhU ¬q8jG 802371 803371

Automatic Detectors Series IQ8Quad (Intelligent Addressable)

Detector with integrated alarm devices

Accessories

767800 mounting bracket805590 Standard detector base for IQ8Quad

esserbus-PLusLoop length max. 3.5 km

esserbus transponder

flash speechsignal

IQ8Control C

speechsound

speech

flash

Application example

Technical Data

Operating voltage 8 ... 42 V DCArea to be monitored max. 110 m²Height to be monitored max. 12 mAir speed 0 ... 25.4 m/sApplication temperature -20 °C ... 65 °CStorage temperature -25 °C ... 75 °CAir humidity 95% (ohne Betauung)Type of protection IP 42Material ABS plasticColor white, similar to RAL 9010Weight approx. 145 gDetector specification En 54-7/5 B, CEA 4021Dimensions Ø: 117 mm H: 59 mm

Detector bases are not supplied as standard.

The 769836 demo package is available for presentations. Further data can be viewed in the accessories section for automatic detectors. For calculating the battery capacity of fire alarm control panels, the detector data "quiescent current @ FACP battery" can be added.

Special-colours on demand!

It is not possible to use the detector base with relay contact (part no. 805591).

Fire detector with base

117

65

1

2

3

4

5

6

7

8

9

10

11

12

17

16

13

14

15

1

Page 11: Automatic Detectors Series IQ8Quad (Intelligent Addressable)...Marquage spécial pour le détecteur de chaleur sur le diffuseur lumineux: Cercle noir. ¬q8hA ¬qBhU ¬q8jG 802371 803371

¬q8te

¬q8sb

802383

802382

O2T/F multisensor IQ8Quad

O/So optical smoke detector IQ8Quad

In addition to smoke detection with the conventional O²T multisensor technology, the detector is provided with a built-in flash lamp.

Scatter smoke detector for safe and early detection of smouldering fires with light smoke generation. Intelligent detector with decentralised intelligence, automatic function self-test, CPU failure mode, alarm and operating data memory, alarm indicator, soft-addressing and operating indication. The detector is provided with a loop isolator.

Along with smoke detection components, the detector is provided with a built-in sounder.

Automatic Detectors Series IQ8Quad (Intelligent Addressable)

VdS

VdS

O²T/F multisensor IQ8Quad with integrated flasher

O/So optical smoke detector IQ8Quad with integrated sounder

Approval:

Approval:

Technical Data

Quiescent current @ 19 V DC approx. 75 μAQuiescent current @ FACP battery approx. 400 μALoad factor 2Lighting energy ca. 3 JStrength of light max. 15,8 cd peak / 2,63 cd effectiveSignal flashing lamp red

Technical Data

Quiescent current @ 19 V DC approx. 80 μALoad factor 2Sound level max. 92 dB (A), +/- 2 db (A) @ 1m for DIN toneDetector specification EN54-7, EN 54-17

Not suitable for application in relay base 805591!

Not suitable for application in relay base 805591!

www.esser-systems.com

Page 12: Automatic Detectors Series IQ8Quad (Intelligent Addressable)...Marquage spécial pour le détecteur de chaleur sur le diffuseur lumineux: Cercle noir. ¬q8hA ¬qBhU ¬q8jG 802371 803371

¬q8s§/G1T

¬q8uh

802382.F0

802384

O/So optical smoke detector IQ8Quad - France

O2T/So multisensor IQ8Quad

Scatter smoke detector for safe and early detection of smouldering fires with light smoke generation. Intelligent detector with decentralised intelligence, automatic function self-test, CPU failure mode, alarm and operating data memory, alarm indicator, soft-addressing and operating indication. The detector is provided with a loop isolator.

Along with smoke detection components, the detector is provided with a built-in sounder.

In addition to smoke detection with the conventional O²T multisensor technology, the detector is provided with a built-in alarm signalling device. The sound level can be set to eight different levels.

Automatic Detectors Series IQ8Quad (Intelligent Addressable)

VdS

VdS

O/So optical smoke detector IQ8Quad with integrated sounder

O²T/So multisensor IQ8Quad with integrated sounder

Approval:

Approval:

Technical Data

Quiescent current @ 19 V DC approx. 80 μALoad factor 2Sound level max. 92 dB (A), +/- 2 db (A) @ 1m for DIN toneDetector specification EN54-7, EN 54-17

Technical Data

Quiescent current @ 19 V DC approx. 80 μAQuiescent current @ FACP battery approx. 450 μALoad factor 2Sound level max. 92 dB (A), +/- 2 db (A) @ 1m for DIN toneSpecification EN 54-3 acoustic signalling device

Not suitable for application in relay base 805591!

Not suitable for application in relay base 805591!

1

2

3

4

5

6

7

8

9

10

11

12

17

16

13

14

15

1

Page 13: Automatic Detectors Series IQ8Quad (Intelligent Addressable)...Marquage spécial pour le détecteur de chaleur sur le diffuseur lumineux: Cercle noir. ¬q8hA ¬qBhU ¬q8jG 802371 803371

¬q8wn

¬q8vk

802386

802385

O2T/Sp multisensor IQ8Quad

O2T/FSp multisensor IQ8Quad

In addition to smoke detection with conventional O²T multisensor technology, the detector is provided with a built-in voice alarm device. It can be set to eight different levels.

In addition to smoke detection with the conventional O²T multisensor technology, the detector is provided with a built-in voice alarm device. It can be set to eight different levels.

Automatic Detectors Series IQ8Quad (Intelligent Addressable)

VdS

VdS

O²T/Sp multisensor IQ8Quad with integrated sounder and speech

O²T/FSp multisensor IQ8Quad with integrated flasher, sounder and speech

Approval:

Approval:

Programmed with 5 standard national languages (DE/GB/FR/ES/IT).

Programmed with 5 standard national languages (DE/GB/FR/ES/IT).

Technical Data

Quiescent current @ 19 V DC approx. 90 μAQuiescent current @ FACP battery approx. 500 μALoad factor 3Sound level max. 92 dB (A), +/- 2 db (A) @ 1m for DIN toneSpecification EN 54-3 acoustic signalling device

EN 54-3 acoustic speech signalling device (Q2/2011)

Technical Data

Quiescent current @ 19 V DC approx. 90 μAQuiescent current @ FACP battery approx. 500 μALoad factor 3Sound level max. 92 dB (A), +/- 2 db (A) @ 1m for DIN toneLighting energy ca. 3 JStrength of light max. 15,8 cd peak / 2,63 cd effectiveSignal flashing lamp redSpecification EN 54-3 acoustic signalling device

EN 54-3 acoustic speech signalling device (Q2/2011)

Not suitable for application in relay base 805591!

Not suitable for application in relay base 805591!

www.esser-systems.com

Page 14: Automatic Detectors Series IQ8Quad (Intelligent Addressable)...Marquage spécial pour le détecteur de chaleur sur le diffuseur lumineux: Cercle noir. ¬q8hA ¬qBhU ¬q8jG 802371 803371

¬q8v§/TW:9¦

¬q8v§/TW::&

802385.SV98

802385.SV99

802385.N0

O2T/FSp multisensor detector IQ8Quad with composition of other languages

O2T/FSp multisensor detector IQ8Quad as customized version

O2T/FSp multisensory IQ8Quad – Nordic

As with 802385, but with an individual combination of national languages.

As 802385, but with individual text and/or sounds. The max. recording time per device is 169 seconds.

Automatic Detectors Series IQ8Quad (Intelligent Addressable)

VdS

VdS

O²T/FSp multisensor IQ8Quad with integrated flasher, sounder and speech

O²T/FSp multisensor IQ8Quad with integrated flasher, sounder and speech

Approval:

Approval:

Programmed with an individual combination of up to 5 national languages.

Programmed according to customer specifications.

When ordering, please note the "Ordering information for IQ8Quad and IQ8Alarm" printed in the appendix.

Cancellations or returns are not possible.

Not suitable for application in relay base 805591!

When ordering, please note the "Ordering information for IQ8Quad and IQ8Alarm" printed in the appendix.

Costs for the recording of customer-specific texts and/or tones can be obtained by request.

Cancellations or returns are not possible.

Not suitable for application in relay base 805591!

1

2

3

4

5

6

7

8

9

10

11

12

17

16

13

14

15

1

Page 15: Automatic Detectors Series IQ8Quad (Intelligent Addressable)...Marquage spécial pour le détecteur de chaleur sur le diffuseur lumineux: Cercle noir. ¬q8hA ¬qBhU ¬q8jG 802371 803371

¬q8vk802385.F0 O2T/FSp multisensor IQ8Quad

In addition to smoke detection with the conventional O²T multisensor technology, the detector is provided with a built-in voice alarm device. It can be set to eight different levels.

Automatic Detectors Series IQ8Quad (Intelligent Addressable)

VdS

O²T/FSp multisensor IQ8Quad with integrated flasher, sounder and speech

Approval:

Programmed with 5 standard national languages (DE/GB/FR/ES/IT).

Technical Data

Quiescent current @ 19 V DC approx. 90 μAQuiescent current @ FACP battery approx. 500 μALoad factor 3Sound level max. 92 dB (A), +/- 2 db (A) @ 1m for DIN toneLighting energy ca. 3 JStrength of light max. 15,8 cd peak / 2,63 cd effectiveSignal flashing lamp redDetector specification EN 54-7, EN54-17Specification acoustic signalling device EN 54-3

acoustic signalling device EN 54-3

Not suitable for application in relay base 805591!

www.esser-systems.com