mile! You’re at the best WordPress.com site ever CATEGORY ARCHIVES: AUTO CHANGEOVER SCHEME AUTO CHANGEOVER SCHEME Posted on March 26, 2013 under Auto changeover scheme 1 Auto changeover scheme 2 Independent Mode,Manual Mode,Auto Mode,Feeder Requ… 3 General Requirement, 4 Manual Mode 5 Manual Mode Tripping conditions 6 Auto Mode 7 Additional Points. 1 Comment ADDITIONAL POINTS. Posted on March 26, 2013 under Auto changeover scheme Additional Points. If Earth switch or Cable earthing truck & Bus earthing truck is available, than some additional interlocks shall be provided. If 4 No Incomer feeders & 1 No Bus coupler are available, than additional interlocks shall be provided Additional Interlocks It will not be possible to OPEN the front DOOR when the circuit breaker is switched “ON”in service position.

Autochangeover - 1 BC 2 INCOMERS

Embed Size (px)

DESCRIPTION

Autochangeover for 1 buscoupler & 2 incomers

Citation preview

Page 1: Autochangeover  -  1 BC 2 INCOMERS

mile! You’re at the best WordPress.com site ever

CATEGORY ARCHIVES: AUTO CHANGEOVER SCHEME

AUTO CHANGEOVER SCHEMEPosted on March 26, 2013 under Auto changeover scheme

1  Auto changeover scheme2  Independent Mode,Manual Mode,Auto Mode,Feeder Requ…3  General Requirement,4  Manual Mode5  Manual Mode Tripping conditions6  Auto Mode7  Additional Points.

1 Comment

ADDITIONAL POINTS.Posted on March 26, 2013 under Auto changeover scheme

Additional Points.

If Earth switch or Cable earthing truck & Bus earthing truck is

available, than some additional interlocks shall be provided.

If 4 No Incomer feeders & 1 No Bus coupler are available, than

additional interlocks shall be provided

Additional Interlocks

It will not be possible to OPEN the front DOOR when the circuit

breaker is switched “ON”in service position.

It will not be possible to rack “OUT”the Vacuum Circuit Breaker

trolley from Service to Test position when the breaker is switched

“ON”

Page 2: Autochangeover  -  1 BC 2 INCOMERS

Similarly, it will not be possible to rack “IN”the Vacuum Circuit

Breaker from Test to Service position when Vacuum Circuit

Breaker is switched “ON”.

It will not be possible to rack “IN”the Vacuum Circuit Breaker

when the front Vacuum Circuit Breaker chamber door is open.

(However, a suitable defeat interlock mechanism shall be

provided for emergency purpose.)

It will be only possible to switch “ON”the earthling switch if

provided, when the withdrawable truck is in Test position.

It will not be possible to rack “IN”Vacuum Circuit Breaker from

Test to service position, in case the earthing switch is “ON”.

Earthing trolleys can be also supplied. Electro-magnetic interlocks

to be provided on earthing trolley for incomers and ties feeders.

It will be not possible to switch “ON”the circuit breaker when

ISOLATOR is Open.

It will be not possible to OPEN the isolator when circuit breaker is

ON.

It will be not possible to “CLOSE”the earth switch when circuit

breaker is “ON”.

It will be not possible to “CLOSE”the earth switch when isolator is

“CLOSED”.

Similarly, it will be not possible to “CLOSE”the circuit breaker &

isolator when earth switch is “ON”.

Page 3: Autochangeover  -  1 BC 2 INCOMERS

Schematic diagram of interlocks

Go Back…

Leave a comment

AUTO MODEPosted on March 26, 2013 under Auto changeover scheme

Closing conditions-B/C

Page 4: Autochangeover  -  1 BC 2 INCOMERS

Closing conditions-B/C

When fault (U/V) on bus side-A Than it checks,

Selector switch is on Auto Mode.

Incomer-1 off & no fault trip.

Incomer-2 On & in service.

Bus PT-1 unhealthy.

Bus PT-2 healthy.

This conditions are satisfy than contactor will be pick up & close

the breaker.

When fault (U/V) on bus side-B Than it checks,

Selector switch is on Auto Mode.

Incomer-2 off & no fault trip.

Incomer-1 On & in service.

Bus PT-2 unhealthy.

Bus PT-1 healthy.

This conditions are satisfy than contactor will be pick up & close

the breaker.

Closing For B/C-Manual mode

Page 5: Autochangeover  -  1 BC 2 INCOMERS

Closing For B/C-Manual mode

Go to Next page…

Go Back…

Leave a comment

MANUAL MODE TRIPPING   CONDITIONS

Posted on March 26, 2013 under Auto changeover scheme

Manual Mode Tripping conditions-I/C-2

Trip selector switch on I/C-2

Incomer-1 On & in Service

Bus coupler On & in Service

After some time delay, I/C-2 will be trip.

Page 6: Autochangeover  -  1 BC 2 INCOMERS

Tripping For I/C-2-Manual mode

———————————————————————————-

Manual Mode Closing conditions-B/C

Mode selector switch in Manual mode

Supply is Synchronize

Incomer-1 On & in Service

Incomer-2 On & in Service

Trip selector switch on I/C-1

Trip selector switch on I/C-2

Page 7: Autochangeover  -  1 BC 2 INCOMERS

Closing For B/C-Manual mode

———————————————————————————-

Manual Mode   Tripping conditions-B/C

Trip selector switch on B/C

Incomer-1 On & in Service

Incomer-2 On & in Service

After some time delay, I/C-2 will be trip.

If in any condition I/C-1 & I/C-2 become OFF, Then B/C will be OFF

Page 8: Autochangeover  -  1 BC 2 INCOMERS

Tripping For B/C-Manual mode

Go to Next page…

Go Back…

Leave a comment

MANUAL MODEPosted on March 26, 2013 under Auto changeover scheme

Manual Mode

Closing conditions-I/C-1

Mode selector switch in Manual mode

Supply is Synchronize

Incomer-2 On & in Service

Bus coupler On & in Service

Trip selector switch on B/C

Trip selector switch on I/C-2

Page 9: Autochangeover  -  1 BC 2 INCOMERS

Closing For I/C-1-Manual mode

Manual Mode

Tripping conditions-I/C-1

Trip selector switch on I/C-1

Incomer-2 On & in Service

Bus coupler On & in Service

After some time delay, I/C-1 will be trip.

Page 10: Autochangeover  -  1 BC 2 INCOMERS

Tripping For I/C-1-Manual mode

Manual Mode

Closing conditions-I/C-2

Mode selector switch in Manual mode

Supply is Synchronize

Incomer-1 On & in Service

Bus coupler On & in Service

Trip selector switch on B/C

Trip selector switch on I/C-1

Page 11: Autochangeover  -  1 BC 2 INCOMERS

Closing For I/C-2-Manual mode

Go to Next page…

Go Back…

Leave a comment

GENERAL REQUIREMENT,Posted on March 26, 2013 under Auto changeover scheme

General Requirement

Bus Pt for measuring Bus voltage & checking bus is healthy or

unhealthy.

Line Pt for measuring Line voltage & Synchronizing between two

sources.

Numerical relays with maximum BI-BO & breaker with maximum aux.

contacts.

Page 12: Autochangeover  -  1 BC 2 INCOMERS

If synchronizing is required, then synchronizing function should be

available in numerical relay of bus coupler.

General Schematic Diagram

General Singe Line Diagram

Independent Mode

Closing conditions-I/C-1

 Mode selector switch in independent mode Bus PT-1 Unhealthy

 Incomer-2 Off & no fault trip Bus coupler Off & no fault trip

Page 13: Autochangeover  -  1 BC 2 INCOMERS

Closing For incomer-1 Ind. mode

Independent Mode

Mode selector switch in independent mode

Bus PT-2 Unhealthy

Incomer-1 Off & no fault trip

Bus coupler Off & no fault trip

Closing For incomer-2-Ind. mode

Page 14: Autochangeover  -  1 BC 2 INCOMERS

Independent Mode

Closing conditions-B/C

Mode selector switch in independent mode

Bus PT-1 Unhealthy

Bus PT-2 Unhealthy

Incomer-1 Off & no fault trip

Incomer-2 Off & no fault trip

For Bus Coupler-Ind. mode

Page 15: Autochangeover  -  1 BC 2 INCOMERS

Go to Next page…

Go Back…

Leave a comment

INDEPENDENT MODE,MANUAL MODE,AUTO

MODE,FEEDER   REQUIRED Posted on March 26, 2013 under Auto changeover scheme

In this mode, Two Breakers can close at the same time.

For e.g.:- 

INCOMER-1 ON

INCOMER-2 ON

BUSCOUPLER OFF

INCOMER-1 ON

INCOMER-2 OFF

BUSCOUPLER ON

Page 16: Autochangeover  -  1 BC 2 INCOMERS

INCOMER-1 OFF

INCOMER-2 ON

BUSCOUPLER ON

Manual Mode

In this mode, When supply is Synchronize, Then Three Breakers

can close at the same time. But after some time delay, one

breaker will be Trip by using Trip Selector Switch.

For e.g.:-

I/C-1 & B/C are ON & if I/C-2 ON than I/C-1 will be trip after some time

delay. (if Trip selector switch is on I/C-1)

Auto Mode

This mode is only for Bus coupler.

If two incomer is On & Bus coupler is Off. If one incomer trip due

to under voltage. At that time B/C is On automatically.

Feeder Required

Incomer-1 with Line Pt-1

Incomer-2 with Line Pt-2

Bus Coupler

Bus Pt-1

Bus Pt-2

Outgoing Feeders

Go to Next page…

Go Back…

Leave a comment

AUTO CHANGEOVER SCHEMEPosted on March 26, 2013 under Auto changeover scheme

Page 17: Autochangeover  -  1 BC 2 INCOMERS

What is Auto Change Over?

Load can be transfer from one Bus to another Bus by using Auto

Change Over Scheme.

It means, within specific conditions, load can be transferred on

another bus by automatically ON or OFF the breakers, without

disturbing any load.

Different Mode for changeover

Independent Mode

Manual Mode / Synchronizing Mode

Auto Mode

Blackout Condition

 Different Switches for changeover Mode Selector Switch:- This switch is on Bus coupler.  This switch is 3 pole, 3 position switch.

Three positions are, (1) Auto(2) Independent(3) Manual

 Trip Selector Switch:- This switch is on Bus coupler.  This switch is 3 pole, 3 position switch.

Three positions are, (1) Incomer-1 trip(2) Incomer-2 trip(3) Bus coupler trip