STANDARD DETAILS INDEX
Service Connection Detail 5/8" or 1" MeterWater Service Connection (Plan & Profile)Typical Connection for Multiple Services (Three or More)1-1/2" and 2" Meter DetailTypical Above Ground Meter (3" or Larger)Fire Hydrant Installation Detail & NotesPotable Water Flushing HydrantSampling Point DetailDouble Valve Detail and Fill/Flush ConnectionPressure-Type Vacuum Breaker (P.V.B.)(Irrigation System)Reduced Pressure Backflow Preventer-Single Service 3/4" - 2"Reduced Pressure Backflow Preventer-Dual Service 3/4" - 2"Reduced Pressure Backflow Preventer-Single Service (3" or larger-45° ELL)Reduced Pressure Backflow Preventer-Single Service (3" or larger-90° ELL)Reduced Pressure Backflow Preventer Assemblies (4"-10" Dia.)Fireline Double Check Detector AssemblyValve Setting DetailUnderground Air Release Valve and BoxPressure Pipe Conflict DetailMechanical Joint Anchoring RequirementsAir Gap SeparationTypical Trench DetailFlexible Pavement Replacement Detail
Casing Installation DetailTypical Utilities Canal CrossingPile Cap Support Detail Dual Pipe (Elevation)Pile Cap Support Detail Dual Pipe (View C-C)Concrete Pile DetailConcrete Pile NotesFan Guard DetailProtective Slab for PipeTypical Sewer Service ConnectionSanitary Sewer Lateral DetailSewer Service Cleanout (For Traffic Areas)Terminal Cleanout DetailStandard ManholeShallow ManholeFlat Top Precast ManholeInvert Flow Channel Detail
34
6
101112131414A15
2627
31
232425
27A
27C282930
323334353637
27B
2
5
789
16171819202122
Concrete Pavement Replacement Detail
XVI - STANDARD DETAILS INDEXDrawing # Title1A,1B,1C,1D,1E General Notes, Specifications and Separation Statement
Sanitary Sewer Manhole Frame & CoverDrop Manhole and Service DropForce Main Entering Shallow Manhole
3940
38
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
Service Connection Detail 5/8" or 1" MeterWater Service Connection (Plan & Profile)Typical Connection for Multiple Services (Three or More)1-1/2" and 2" Meter DetailTypical Above Ground Meter (3" or Larger)Fire Hydrant Installation Detail & NotesPotable Water Flushing HydrantSampling Point DetailDouble Valve Detail and Fill/Flush ConnectionPressure-Type Vacuum Breaker (P.V.B.)(Irrigation System)Reduced Pressure Backflow Preventer-Single Service 3/4" - 2"Reduced Pressure Backflow Preventer-Dual Service 3/4" - 2"Reduced Pressure Backflow Preventer-Single Service (3" or larger-45° ELL)Reduced Pressure Backflow Preventer-Single Service (3" or larger-90° ELL)Reduced Pressure Backflow Preventer Assemblies (4"-10" Dia.)Fireline Double Check Detector AssemblyValve Setting DetailUnderground Air Release Valve and BoxPressure Pipe Conflict DetailMechanical Joint Anchoring RequirementsAir Gap SeparationTypical Trench DetailFlexible Pavement Replacement Detail
Casing Installation DetailTypical Utilities Canal CrossingPile Cap Support Detail Dual Pipe (Elevation)Pile Cap Support Detail Dual Pipe (View C-C)Concrete Pile DetailConcrete Pile NotesFan Guard DetailProtective Slab for PipeTypical Sewer Service ConnectionSanitary Sewer Lateral DetailSewer Service Cleanout (For Traffic Areas)Terminal Cleanout DetailStandard ManholeShallow ManholeFlat Top Precast ManholeInvert Flow Channel Detail
34
6
101112131414A15
2627
31
232425
27A
27C282930
323334353637
27B
2
5
789
16171819202122
Concrete Pavement Replacement Detail
XVI - STANDARD DETAILS INDEXDrawing # Title1A,1B,1C,1D,1E General Notes, Specifications and Separation Statement
Sanitary Sewer Manhole Frame & CoverDrop Manhole and Service DropForce Main Entering Shallow Manhole
3940
38
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
STANDARDS DETAIL INDEX Index01JUNE 2014
Force Main Entering Deep ManholeTYPE 'A'-Typical Lift Station Site Plan LayoutTYPE 'A'-Typical Lift Station (Section)TYPE 'A'-Wet Well Section Retainer StrapTYPE 'A'-Lift Station Tremie Pour DetailTYPE 'A'-Required Lift Station InformationTYPE 'A'-Standard Aluminum Cover
Water Service Detail at Lift Station (TYPES 'A' & 'B')
TYPE 'A'-Typical Lift Station Control PanelTYPE 'A'-Lift Station (Control Center)TYPE 'A'-Lift Station Control Panel
TYPE 'A'-Lift Station Control Panel Wiring Diagram, 480/240 Volt, 3 Phase
TYPE 'A'-Lift Station Control Panel Wiring Diagram, 230 Volt, 1 PhaseTYPE 'A'-Control Panel Bill of Materials, 230 Volt, 1 Phase
Fence Detail at Lift Station (TYPES 'A' & 'B')
42
4647484950
50A51-51C
63
60
62
41
434445
52-52C
53-53B54
5859
XVI - STANDARD DETAILS INDEX
TYPE 'A'-Lift Station Control Panel Notes
51D TYPE 'A'-Control Panel Bill of Materials, 480/240 Volt, 3 Phase
52D
Drawing # Title
55
57
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
TYPE 'B'-Typical Lift Station (Section)TYPE 'B'-Required Lift Station InformationTYPE 'B'-Typical Lift Station Control Panel
TYPE 'B'-Lift Station Control Panel Backpanel Layout-Three PhaseTYPE 'B'-Lift Station Control Panel Enclosure & Deadfront Layout-Single Phase
61
63A
TYPE 'B'-Lift Station Control Panel Enclosure & Deadfront Layout-Three Phase
TYPE 'B'-Lift Station Control Panel Backpanel Layout-Single Phase64-64A TYPE 'B'-Lift Station Control Panel Wiring Diagram-Three Phase
66-66A TYPE 'B'-Lift Station Control Panel NotesDouble Compartment Grease Trap & Oil SeparatorReclaimed Water Metering Facility (Bulk User)Reclaimed Water Metering Facility Plan (Bulk User)Reclaimed Water Metering Facility Control Schematic (Bulk User)
Reclaimed Water Metering Facility Lake Stilling Well (Bulk User)
7273
697071
74
7677
75
6768
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
56 ...................TYPE 'B'-Typical Lift Station Site Plan Layout
TYPE 'B'-Lift Station Details (Control Center)TYPE 'B'-Lift Station Control Panel Specifications
...................
...................
...................
...................
...................62A
Reclaimed Water Metering Facility Control Panel (Bulk User)Reclaimed Water Metering Facility Control Panel Details (Bulk User)Reclaimed Water Metering Facility Control Panel-Back View (Bulk User)
...................
...................
...................
...................
...................
Reclaimed Water Metering Facility Reclaimed Water Signage (Bulk User)
TYPE 'A'-Emergency Dry-Priming Sewage Pump Specifications
Reclaimed Water Flushing Hydrant (Bulk and Pressurized)Reclaimed Water Valve Setting Detail (Bulk and Pressurized)
64B TYPE 'B'-Lift Station Control Panel Bill of Materials-Three Phase...................65-65A TYPE 'B'-Lift Station Control Panel Wiring Diagram-Single Phase...................
65B TYPE 'B'-Lift Station Control Panel Bill of Materials-Single Phase...................
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
STANDARDS DETAIL INDEX Index02JUNE 2014
78
79
...................
Pressurized Reclaimed Water System - Point of Connection Detail82
86878889909192
81
838485
94
9697
XVI - STANDARD DETAILS INDEX
93
95
Drawing # Title
98
100
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
99...................
...................
...................
Pressurized Reclaimed Water System - Point of Connection PlanPressurized Reclaimed Water System - Control Panel, FrontPressurized Reclaimed Water System - Typical Control CenterPressurized Reclaimed Water System - Typical Control Valve SchematicPressurized Reclaimed Water System - 3-Rod Grounding Grid Detail
Vacuum Sewer - Isolation Valve & Box with Optional Gauge Tap
Vacuum Sewer - Minimum Spacing between Connections
Vacuum Sewer - Lift Detail and Slope Schedule
Vacuum Sewer - Branch to Main Connection AssemblyVacuum Sewer - Valve Pit to Main Connection
Vacuum Sewer - Valve Pit Bedding and Backfill
Vacuum Sewer - Standard 1-Piece Valve Pit SectionsVacuum Sewer - Valve Pit Flexible ConnectionVacuum Sewer - Valve Pit - Prior to House ConnectionVacuum Sewer - Standard Valve Pit Orientation
Vacuum Sewer - Vacuum Main Change of Direction
Vacuum Sewer - Valve Pit 6" Dedicated Air Terminal (Plan)
Vacuum Sewer - Standard 1-Piece Valve Pit
Vacuum Sewer - Valve Pit 6" Dedicated Air Terminal (Elevation)
80...................
Pressurized Reclaimed Water System
Pressurized Reclaimed Water System
Pressurized Reclaimed Water System - 2" Meter Detail...................
................... Service Connections Plan/Profile-Single & Double
Service Connection Detail, 5/8" or 1" Meter (Pressurized)
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
STANDARDS DETAIL INDEX Index03JUNE 2014
GENERAL NOTES:
FOR THE PURPOSE OF THE GENERAL NOTES BELOW, THE TERM DEPARTMENT SHALL MEAN "MARTINCOUNTY UTILITIES & SOLID WASTE DEPARTMENT".
1. ALL CONNECTIONS TO EXISTING MAINS SHALL BE OBSERVED BY THE DEPARTMENT. VALVESON EXISTING MAINS SHALL BE OPERATED BY DEPARTMENT PERSONNEL OR UNDER THEIR DIRECTSUPERVISION. TAPPING SLEEVE AND VALVE SHALL BE PRESSURE TESTED PRIOR TO TAPPING. IFSERVICE MUST BE CUT OFF TO EXISTING CUSTOMERS, THE DEPARTMENT MUST HAVE THREE DAYSNOTICE TO MAKE NECESSARY NOTIFICATIONS. THE CONTRACTOR MAY BE REQUIRED TO ASSIST INNOTIFICATIONS. IN THIS EVENT, CONTRACTOR SHALL BE READY TO PROCEED WITH AS MUCHMATERIAL PREASSEMBLED AS POSSIBLE AT THE SITE TO MINIMIZE THE LENGTH OF SERVICEINTERRUPTION. THE DEPARTMENT WILL POSTPONE A SERVICE CUT OFF IF THE CONTRACTOR IS NOTREADY TO PROCEED ON SCHEDULE. SUCH CONNECTIONS SHALL BE MADE AT NIGHT TO MINIMIZEEFFECTS UNLESS OTHERWISE AUTHORIZED BY THE DEPARTMENT. NO CUSTOMER SHOULD BEWITHOUT SERVICE FOR MORE THAN FOUR HOURS.
LOCAL CHLORINATION WILL BE REQUIRED FOR ALL PIPE AND FITTINGS USED TO COMPLETECONNECTIONS WITH POTABLE WATER.
2. THE CONTRACTOR SHALL HAVE AVAILABLE AT THE JOB SITE AT ALL TIMES ONE COPY OFMARTIN COUNTY UTILITIES MINIMUM DESIGN AND CONSTRUCTION STANDARDS, ONE COPY OF THECONTRACT DOCUMENTS, INCLUDING PLANS, SPECIFICATIONS AND SPECIAL PROVISIONS, AND COPIESOF ANY REQUIRED CONSTRUCTION PERMITS.
3. THE CONTRACTOR SHALL CONTACT ALL CONCERNED UTILITIES AT LEAST 48 HOURS INADVANCE OF CONSTRUCTION OPERATIONS.
4. THE LOCATION AND SIZE OF ALL EXISTING UTILITIES SHOWN ON THE PLANS ARE APPROXIMATEAND ARE BASED ON THE BEST AVAILABLE INFORMATION. THE CONTRACTOR SHALL BE RESPONSIBLEFOR THE LOCATION OF ALL EXISTING UTILITIES. THE CONTRACTOR SHALL VERIFY ALL UTILITIES BYELECTRONIC METHOD AND BY HAND EXCAVATION IN COORDINATION WITH ALL UTILITY COMPANIESPRIOR TO BEGINNING ANY CONSTRUCTION OPERATIONS. ANY AND ALL CONFLICTS OF EXISTINGUTILITIES WITH PROPOSED IMPROVEMENTS SHALL BE RESOLVED BY THE ENGINEER AND DEPARTMENTPRIOR TO BEGINNING ANY CONSTRUCTION OPERATIONS. THIS WORK BY THE CONTRACTOR SHALL BECONSIDERED INCIDENTAL TO THE CONTRACT AND NO ADDITIONAL COMPENSATION SHALL BE ALLOWED.
5. LOCATION OF PROPOSED FACILITIES WILL BE STAKED BY CONTRACTOR. CONTRACTOR MUSTGIVE 48 HOURS NOTICE TO THE DEPARTMENT IN ADVANCE OF LAYOUT.
6. PROJECT SUPERINTENDENT: THE CONTRACTOR SHALL PROVIDE A QUALIFIED SUPERINTENDENTTO REMAIN ON THE JOB SITE AT ALL TIMES WHEN WORK IS BEING PERFORMED. THESUPERINTENDENT SHALL BE PRESENT AT THE PRE-CONSTRUCTION MEETINGS. THE CONTRACTORSHALL NOTIFY THE DEPARTMENT BY LETTER PRIOR TO THE PRE-CONSTRUCTION MEETINGAPPOINTING THE SUPERINTENDENT FOR THIS PROJECT INCLUDING A FORMAL RESUME SHOWINGQUALIFICATIONS. IN THE EVENT THE SUPERINTENDENT WILL NOT BE PRESENT FOR ANY PERIOD OFTIME DURING CONTRACT WORK THE CONTRACTOR SHALL PROVIDE 48 HOURS NOTICE IN WRITING TOTHE DEPARTMENT, INCLUDING THE APPOINTMENT OF A QUALIFIED REPLACEMENT SUPERINTENDENTWHO WILL BE PRESENT DURING THE CONSTRUCTION. WORK SHALL NOT BE ALLOWED TO PROCEEDUNLESS THE ASSIGNED SUPERINTENDENT IS PRESENT.
7. IT IS THE CONTRACTOR'S RESPONSIBILITY TO ENSURE HIS COMPLETE FAMILIARITY WITH THEPROJECT SITE AND COMPONENTS TO INCLUDE SUBSURFACE CONDITIONS OF SOIL ANDGROUNDWATER TABLE.
WARNING: EXACT LOCATION OF UNDERGROUND UTILITIES IS NOT KNOWN NOR IS THIS DRAWING TOBE CONSTRUED AS DEPICTING THE LOCATION OF ALL UNDERGROUND UTILITIES OR STRUCTURES.THE CONTRACTOR IS RESPONSIBLE FOR DETERMINATION OF LOCATION PRIOR TO COMMENCEMENT OFWORK. THE CONTRACTOR IS RESPONSIBLE, THEREFORE, FOR ALL DAMAGE AND REPAIR COSTS.
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.GENERAL NOTES, SPECIFICATIONS
AND SEPARATION STATEMENT 1AJUNE 2014
GENERAL NOTES (Cont.):
8. DENSITY TESTS OF TRENCH BACKFILL MATERIAL SHALL BE REQUIRED AT INTERVALS OF NOTMORE THAN 500 FEET. DENSITY TESTS OF PAVEMENT OPEN-CUT AREAS INCLUDING ROADS,TURNLANES, AND DRIVES SHALL BE REQUIRED AT EACH OPEN-CUT AT INTERVALS OF NOT MORETHAN 50 FEET. ALL TESTS SHALL COMMENCE AT THE TOP OF CONDUIT AND EVERY 12 INCHES TOTHE FINISH GRADE. COMPACTION SHALL BE IN ACCORDANCE WITH MARTIN COUNTY UTILITIESCONSTRUCTION STANDARDS "TYPICAL TRENCH DETAIL" AND "FLEXIBLE PAVEMENT REPLACEMENTDETAIL". FLORIDA BEARING TESTS FOR THE STABILITY OF EXISTING SUBSOIL SHALL BE TAKEN ATINTERVALS OF NOT MORE THAN 500 FEET, AND CLOSER AS MIGHT BE NECESSARY IN THE EVENTOF VARIATIONS IN THE STRATA. A CERTIFIED COPY OF THE TESTS SHALL BE PROVIDED TO THEDEPARTMENT AND THE FLORIDA DEPARTMENT OF TRANSPORTATION OR MARTIN COUNTY ENGINEERINGDEPARTMENT DEPENDING ON JURISDICTION. CONTRACTORS BID PRICE SHALL INCLUDE PAYMENT FORALL TESTS CONDUCTED BY AN INDEPENDENT TESTING LAB.
9. ANY LANDSCAPING DISTURBED, UNLESS OTHERWISE SHOWN ON THE PLANS, SHALL BEREPLACED BY THE CONTRACTOR TO THE SATISFACTION OF THE DEPARTMENT AT THE CONTRACTORSEXPENSE.
10. ANY SIDEWALK, CURB AND GUTTER OR PAVEMENT DISTURBED, UNLESS OTHERWISE SHOWN ONPLANS, SHALL BE REPLACED BY THE CONTRACTOR AT THE CONTRACTOR'S EXPENSE. UNLESSOTHERWISE SPECIFIED OR INDICATED, ALL CONCRETE SHALL HAVE A MINIMUM COMPRESSIVESTRENGTH OF 3000 psi AT 28 DAYS AND ALL CONCRETE WORK SHALL COMPLY WITH THE CURRENTEDITION OF THE AMERICAN CONCRETE INSTITUTE (ACI) BUILDING CODE AND THE APPLICABLEBUILDING CODES HAVING JURISDICTION IN THE AREA. ALL CONSTRUCTION SHALL MEET ADAREQUIREMENTS. THIS INCLUDES, BUT IS NOT LIMITED TO, DETECTABLE WARNING SURFACES.
11. ALL SOD IS TO BE PLACED FOR THE FULL WIDTH DISTURBED AT THE PER LINEAR FOOT UNITPRICE FOR SOD. SOD SHALL BE REPLACED TO MATCH EXISTING KIND UNLESS OTHERWISE SHOWNON PLANS.
12. CONTRACTOR SHALL PROVIDE PROPER BENDS TO MAINTAIN REQUIRED DEPTH AND ALIGNMENTOF PIPE. COST OF BENDS NOT DESIGNATED ON PLANS SHALL BE INCLUDED WITH THE UNIT PRICEFOR PIPE.
13. ANY TREES AND/OR SCRUB OR OTHER VEGETATION NOT TO BE REPLACED SHALL BE REMOVEDFROM THE PROJECT AT THE CONTRACTOR'S EXPENSE.
14. ALL RUBBLE AND UNSUITABLE MATERIAL MUST BE REMOVED FROM THE PROJECT ANDDISPOSED OF PROPERLY BY THE CONTRACTOR AT THE CONTRACTOR'S EXPENSE.
15. MAILBOXES MUST BE CAPABLE OF RECEIVING MAIL AT ALL TIMES.
16. DEFLECT PIPE AS NECESSARY TO OBTAIN THE REQUIRED ALIGNMENT. USE APPROPRIATEFITTINGS WHEN DEFLECTION EXCEEDS 75% OF MANUFACTURER'S RECOMMENDED MAXIMUMDEFLECTION.
17. ALL FITTINGS SHALL BE MECHANICALLY RESTRAINED. REFER TO MARTIN COUNTY UTILITIESDEPARTMENT MINIMUM DESIGN & CONSTRUCTION STANDARDS (LATEST EDITION).
18. ALL CONSTRUCTION DEWATERING (WELL POINTS, SUMPS, ETC.) WILL REQUIRE A DEWATERINGPERMIT FROM SOUTH FLORIDA WATER MANAGEMENT DISTRICT. THIS SHALL BE OBTAINED BY THECONTRACTOR AT THE CONTRACTOR'S EXPENSE PRIOR TO BEGINNING OF CONSTRUCTION.
19. THE "TRENCH SAFETY ACT" SHALL BE INCORPORATED INTO THIS CONTRACT AS ENACTED BYTHE LEGISLATURE OF THE STATE OF FLORIDA TO BE IN EFFECT AS OF OCTOBER 1, 1990.
20. A U-2 PERMIT IS REQUIRED FOR ALL WORK WITHIN COUNTY RIGHT-OF-WAY. THIS PERMITMUST BE OBTAINED BY THE CONTRACTOR FROM THE MARTIN COUNTY ENGINEERING DEPARTMENT.ALL COSTS PAYABLE BY THE CONTRACTOR. A COPY OF THIS PERMIT MUST BE MAINTAINED ON THEPROJECT SITE AT ALL TIMES DURING CONSTRUCTION.
21. ALL CONCRETE AND ASPHALT DRIVES MUST BE REPLACED FROM SAW CUT TO EDGE OFPAVEMENT.
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.GENERAL NOTES, SPECIFICATIONS
AND SEPARATION STATEMENT 1BJUNE 2014
GENERAL NOTES (Cont.):
22. LOCATIONS OF FIRE HYDRANTS AND AIR RELEASE VALVES ARE APPROXIMATE ONLY. FINALLOCATIONS WILL BE DETERMINED BY DEPARTMENT PERSONNEL IN FIELD.
23. MAXIMUM LENGTH OF WATER MAIN AND FORCE MAIN PRESSURE TEST SHALL BE 1500 FEET.WATER SOURCE FOR FLUSHING, FILLING AND PRESSURE TESTING THE WATER MAIN SHALL BE FROMA TREATED SOURCE APPROVED BY THE DEPARTMENT.
24. THE CONTRACTOR IS RESPONSIBLE FOR THE PROTECTION AND RESTORATION (IF DAMAGED) OFALL EXISTING STRUCTURES WITHIN THE CONSTRUCTION LIMITS OF THE PROJECT, INCLUDING BUT NOTLIMITED TO WALLS, FENCES, POWER POLES, MAIL BOXES, DRAINAGE PIPES AND STRUCTURES, ETC.
25. THE CONTRACTOR SHALL VERIFY THE LOCATION OF EXISTING WATER SERVICES PRIOR TOCONSTRUCTION. THE CONTRACTOR SHALL PROTECT THE EXISTING WATER SERVICES FROM DAMAGEAND REPAIR ANY BREAKS IMMEDIATELY.
26. "RECORD DRAWINGS" SHALL INCLUDE FURNISHING MARTIN COUNTY UTILITIES DEPARTMENT WITHALL INFORMATION NECESSARY FOR A COMPLETE SET OF RECORD DRAWINGS AS STIPULATED IN THEMARTIN COUNTY UTILITIES DEPARTMENT MINIMUM DESIGN AND CONSTRUCTION STANDARDS (LATESTEDITION).
27. MECHANICALLY RESTRAIN LENGTHS, AS INDICATED ON DRAWING No. 20, ON EACH SIDE OF ALLBENDS AND AS INSTRUCTED IN MARTIN COUNTY UTILITIES DEPARTMENT SPECIFICATIONS.MECHANICAL RESTRAINTS SHALL BE EITHER MEG-A-LUG, TYLER OR UNIFLANGE. THE CONTRACTORSBID PRICE FOR PIPE, GATE VALVES AND FITTINGS SHALL INCLUDE MECHANICAL RESTRAINT.
28. THE CONTRACTOR SHALL PROTECT EXISTING UTILITIES FROM DAMAGE DURING CONSTRUCTIONOPERATIONS. THE CONTRACTOR SHALL SUPPORT UTILITIES AND SHORE TRENCH AS REQUIRED TOPROTECT AND MAINTAIN EXISTING UTILITIES. THE CONTRACTOR SHALL NOTIFY EACH UTILITY PRIORTO ATTEMPTING TO SUPPORT THEIR FACILITIES. IF THE UTILITY REQUIRES THAT ONLY THEIR CREWSSHALL BE ALLOWED TO SUPPORT THEIR FACILITIES, THEN IT SHALL BE THE CONTRACTORSRESPONSIBILITY TO COORDINATE WORK AND PAY THE UTILITY FOR THEIR EXPENSES IF REQUIRED.ALL COSTS FOR THIS WORK SHALL BE AT THE CONTRACTORS EXPENSE AND INCLUDED IN THECONTRACTORS BID PRICE.
29. ALL PRESSURE TESTS SHALL BE IN ACCORDANCE WITH AWWA STANDARDS.
30. AIR RELEASE VALVE VAULT COVERS SHALL BE CONSTRUCTED PER DETAIL AS SHOWN IN THEDEPARTMENTS MINIMUM DESIGN AND CONSTRUCTION STANDARDS.
31. ALL WATER SERVICES SHALL BE DIRECTIONALLY DRILLED UNDER EXISTING PAVEMENT.
32. VALVE STEM RISER SHALL BE REQUIRED WHERE OPERATING NUT DEPTH EXCEEDS 4 FEET.THE RISER SHALL BE BOLTED TO THE VALVE NUT. METHOD AND MATERIALS SHALL BE APPROVEDBY THE DEPARTMENT. COST FOR THIS WORK SHALL BE INCLUDED IN THE CONTRACTORS BID UNITPRICE FOR GATE VALVES.
33. THE CONTRACTOR SHALL CLEAN MAINS USING APPROVED POLYURETHANE PIG(S). TEMPORARYCLEANING STATIONS SHALL BE CONSTRUCTED BY THE CONTRACTOR. THE CONTRACTOR SHALLPROVIDE A CLEANING PLAN SHOWING METHOD OF FILLING AND CLEANING MAINS PRIOR TO STARTOF CONSTRUCTION. THE CLEANING PLAN SHALL BE APPROVED BY THE DEPARTMENT PRIOR TOCONSTRUCTION. ALL COSTS FOR FILLING AND CLEANING SHALL BE AT THE CONTRACTORS EXPENSE.
34. A FLORIDA DEPARTMENT OF TRANSPORTATION PERMIT IS REQUIRED FOR ALL WORK, EXCEPTPERPENDICULAR CONNECTIONS, WITHIN THE STATE RIGHT-OF-WAY. A COPY OF THIS PERMIT MUSTBE MAINTAINED ON THE PROJECT SITE AT ALL TIMES DURING CONSTRUCTION.
35. THE CONTRACTOR SHALL INSTALL TESTING POINTS FOR PRESSURE & BACTERIOLOGICAL TESTINGOF WATER MAINS. THE CONTRACTOR SHALL INSTALL AND REMOVE AND PLUG CORP. STOPS PERMARTIN COUNTY UTILITIES STANDARDS "SAMPLE POINT DETAIL". THE LOCATION OF TEST POINTSSHALL BE APPROVED BY THE DEPARTMENT.
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.GENERAL NOTES, SPECIFICATIONS
AND SEPARATION STATEMENT 1CJUNE 2014
GENERAL NOTES (Cont.):
48 HOURS BEFORE DIGGINGCALL TOLL-FREE
1-800-432-4770SUNSHINE STATE ONE CALL
OF FLORIDA, INCUNDERGROUND UTILITIES NOTIFICATION CENTER
NOTE: MARTIN COUNTY UTILITIES DEPARTMENT'S MINIMUM DESIGN ANDCONSTRUCTION STANDARDS (LATEST EDITION), ARE TO BE ADHERED TOAND WILL BE ENFORCED TO AT LEAST THESE MINIMUM STANDARDS.
L= LEAKAGE IN GALLONS
D= DIAMETER OF PIPE IN INCHES P= TEST PRESSURE IN PSI. N= NUMBER OF JOINTS IN TEST SECTIONWHERE:
7400L=ND P
36. WATER MAIN DISINFECTION SHALL BE IN ACCORDANCE WITH CURRENT AWWA, BULLETINC-651.
37. WATER MAINS AND APPURTENANCES SHALL BE IN ACCORDANCE WITH CURRENT AWWA,FDEP AND NSF STANDARDS.
38. MINIMUM COVER TO FINISHED GRADE OVER WATER MAINS SHALL BE 30 INCHES UP TO8" DIAMETER; 10" OR LARGER SHALL HAVE 36" COVER OR GREATER TO PROVIDE A MINIMUM18" COVER OVER OPERATING NUT OF GATE VALVES.
39. ALL MAINS SHALL BE TESTED FOR LEAKAGE. WATER SHALL BE SUPPLIED TO THE MAINAND PUMPED TO THE REQUIRED 150 PSI PRESSURE. THE MAIN TESTED SHALL EITHER BEISOLATED FROM PRESENTLY POTABLE LINES OR PROTECTED FROM LEAKAGE BY A DOUBLEVALVE ARRANGEMENT.
40. NEWLY CONSTRUCTED FIRE HYDRANTS THROUGHOUT THE PROJECT SHALL HAVE A RED"OUT OF SERVICE" DISK (JOSEPH G. POLLARD CO. OR EQUAL) ATTACHED TO 4" PUMPERNOZZLE CAP. DISK TO BE REMOVED AFTER WATER SYSTEM HAS BEEN APPROVED FORSERVICE BY THE DEPARTMENT.
THE DEPARTMENT SHALL BE NOTIFIED AT LEAST 48 HOURS IN ADVANCE OF ANY TESTINGPROCEDURES. AFTER FLUSHING IS COMPLETED, LINE PRESSURE SHALL BE APPLIED TO THEWATER SYSTEM TO DETERMINE IF ANY MAJOR DEFECTS ARE PRESENT. THE COMPLETE WATERSYSTEM SHALL THEN BE TESTED AT A PRESSURE OF 150 PSI FOR A PERIOD OF NOT LESSTHAN TWO HOURS. THE DEPARTMENT MAY, AT ITS DISCRETION, INCREASE THE PERIOD TOFOUR HOURS. MAXIMUM LENGTH OF LINE TO BE TESTED AT ONE TIME SHALL NOT EXCEED1500 LINEAR FEET. AN OIL FILLED PRESSURE GAUGE UP TO 200 PSI AT 2 POUNDINCREMENTS SHALL BE USED FOR ALL PRESSURE TESTS. NO VISIBLE MOVEMENT OF THESYSTEM SHALL OCCUR AND LEAKAGE SHALL NOT EXCEED:
PER HOUR
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.GENERAL NOTES, SPECIFICATIONS
AND SEPARATION STATEMENT 1DJUNE 2014
STANDARD WATER/SEWER SEPARATION STATEMENT
62-555.314 Location of Public Water System Mains.For the purpose of this section, the phrase “ water mains” shall mean mains, including treatment plant process piping, conveyingeither raw, partially treated, or finished drinking water; fire hydrant leads; and service lines that are under the control of a publicwater system and that have an inside diameter of three inches or greater.
(1) Horizontal Separation Between Underground Water Mains and Sanitary or Storm Sewers, Wastewater or Stormwater ForceMains, Reclaimed Water Pipelines, and On-Site Sewage Treatment and Disposal Systems.
(a) New or relocated, underground water mains shall be laid to provide a horizontal distance of at least three feet betweenthe outside of the water main and the outside of any existing or proposed storm sewer, Stormwater force main, or pipelineconveying reclaimed water regulated under Part III of Chapter 62-610, F.A.C.
(b) New or relocated, underground water mains shall be laid to provide a horizontal distance of at least three feet, andpreferably ten feet, between the outside of the water main and the outside of any existing or proposed vacuum-type sanitarysewer.
(c) New or relocated, underground water mains shall be laid to provide a horizontal distance of at least six feet, andpreferably ten feet, between the outside of the water main and the outside of any existing or proposed gravity- or pressure-typesanitary sewer, wastewater force main, or pipeline conveying reclaimed water not regulated under Part III of Chapter 62-610, F.A.C.The minimum horizontal separation distance between water mains and gravity-type sanitary sewers shall be reduced to three feetwhere the bottom of the water main is laid at least six inches above the top of the sewer.
(d) New or relocated, underground water mains shall be laid to provide a horizontal distance of at least ten feet between theoutside of the water main and all parts of any existing or proposed “ on-site sewage treatment and disposal system” as defined inSection 381.0065(2), F.S., and Rule 64E-6.002, F.A.C.
(2) Vertical Separation Between Underground Water Mains and Sanitary or Storm Sewers, Wastewater or Stormwater Force Mains,and Reclaimed Water Pipelines.
(a) New or relocated, underground water mains crossing any existing or proposed gravity- or vacuum-type sanitary sewer orstorm sewer shall be laid so the outside of the water main is at least six inches, and preferably 12 inches, above or at least 12inches below the outside of the other pipeline. However, it is preferable to lay the water main above the other pipeline.
(b) New or relocated, underground water mains crossing any existing or proposed pressure-type sanitary sewer, wastewater orstormwater force main, or pipeline conveying reclaimed water shall be laid so the outside of the water main is at least 12 inchesabove or below the outside of the other pipeline. However, it is preferable to lay the water main above the other pipeline.
(c) At the utility crossings described in paragraphs (a) and (b) above, one full length of water main pipe shall be centeredabove or below the other pipeline so the water main joints will be as far as possible from the other pipeline. Alternatively, at suchcrossings, the pipes shall be arranged so that all water main joints are at least three feet from all joints in vacuum-type sanitarysewers, storm sewers, stormwater force mains, or pipelines conveying reclaimed water regulated under Part III of Chapter 62-610,F.A.C., and at least six feet from all joints in gravity- or pressure-type sanitary sewers, wastewater force mains, or pipelinesconveying reclaimed water not regulated under Part III of Chapter 62-610, F.A.C.
(3) Separation Between Water Mains and Sanitary or Storm Sewer Manholes.(a) No water main shall pass through, or come into contact with, any part of a sanitary sewer manhole.(b) Effective August 28, 2003, water mains shall not be constructed or altered to pass through, or come into contact with,
any part of a storm sewer manhole or inlet structure. Where it is not technically feasible or economically sensible to comply withthis requirement (i.e., where there is a conflict in the routing of a water main and a storm sewer and where alternative routing ofthe water main or the storm sewer is not technically feasible or is not economically sensible), the Department shall allow exceptionsto this requirement (i.e., the Department shall allow construction of conflict manholes), but suppliers of water or persons proposingto construct conflict manholes must first obtain a specific permit from the Department in accordance with Part V of this chapterand must provide in the preliminary design report or drawings, specifications, and design data accompanying their permit applicationthe following information:
1. Technical or economic justification for each conflict manhole.2. A statement identifying the party responsible for maintaining each conflict manhole.3. Assurance of compliance with the design and construction requirements in sub-subparagraphs a. through d. below.a. Each water main passing through a conflict manhole shall have a flexible, watertight joint on each side of the manhole to
accommodate differential settling between the main and the manhole.b. Within each conflict manhole, the water main passing through the manhole shall be installed in a watertight casing pipe
having high impact strength (i.e., having an impact strength at least equal to that of 0.25-inch-thick ductile iron pipe).c. Each conflict manhole shall have an access opening, and shall be sized, to allow for easy cleaning of the manhole.d. Gratings shall be installed at all storm sewer inlets upstream of each conflict manhole to prevent large objects from
entering the manhole.(4) Separation Between Fire Hydrant Drains and Sanitary or Storm Sewers, Wastewater or Stormwater Force Mains,
Reclaimed Water Pipelines, and On-Site Sewage Treatment and Disposal Systems. New or relocated fire hydrants with undergrounddrains shall be located so that the drains are at least three feet from any existing or proposed storm sewer, stormwater forcemain, or pipeline conveying reclaimed water regulated under Part III of Chapter 62-610, F.A.C.; at least three feet, and preferablyten feet, from any existing or proposed vacuum-type sanitary sewer; at least six feet, and preferably ten feet, from any existing orproposed gravity- or pressure-type sanitary sewer, wastewater force main, or pipeline conveying reclaimed water not regulated underPart III of Chapter 62-610, F.A.C.; and at least ten feet from any existing or proposed “ on-site sewage treatment and disposalsystem” as defined in Section 381.0065(2), F.S., and Rule 64E-6.002, F.A.C.
(5) Exceptions. Where it is not technically feasible or economically sensible to comply with the requirements in subsection (1)or (2) above, the Department shall allow exceptions to these requirements if suppliers of water or construction permit applicantsprovide technical or economic justification for each exception and provide alternative construction features that afford a similar levelof reliability and public health protection. Acceptable alternative construction features include the following:
(a) Where an underground water main is being laid less than the required minimum horizontal distance from another pipelineand where an underground water main is crossing another pipeline and joints in the water main are being located less than therequired minimum distance from joints in the other pipeline:
1. Use of pressure-rated pipe conforming to the American Water Works Association standards incorporated into Rule62-555.330, F.A.C., for the other pipeline if it is a gravity- or vacuum-type pipeline;
2. Use of welded, fused, or otherwise restrained joints for either the water main or the other pipeline; or3. Use of watertight casing pipe or concrete encasement at least four inches thick for either the water main or the other pipeline.
(b) Where an underground water main is being laid less than three feet horizontally from another pipeline and where anunderground water main is crossing another pipeline and is being laid less than the required minimum vertical distance from theother pipeline:
1. Use of pipe, or casing pipe, having high impact strength (i.e., having an impact strength at least equal to that of0.25-inch-thick ductile iron pipe) or concrete encasement at least four inches thick for the water main; and
2. Use of pipe, or casing pipe, having high impact strength (i.e., having an impact strength at least equal to that of0.25-inch-thick ductile iron pipe) or concrete encasement at least four inches thick for the other pipeline if it is new and isconveying wastewater or reclaimed water.
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.GENERAL NOTES, SPECIFICATIONS
AND SEPARATION STATEMENT 1EJUNE 2014
30" MIN. COVE
R 8" MIN.
NOTES:
1. MIN. SERVICE LINES SHALL BE AS FOLLOWS: 1" FOR SINGLE AND DOUBLE SERVICES WHEREMETER SIZE IS 5/8"; 2" FOR SINGLE AND DOUBLE SERVICES WHERE METER SIZE IS 1".
2. COMPRESSION FITTINGS SHALL BE SUITABLE FOR TUBING USED AND REQUIRE METAL (S.S.)INSERTS.
3. DOUBLE SERVICES REQUIRE "U" BRANCH WITH ANGLE CURB STOPS.
4. POLYETHYLENE SHALL BE AS DEFINED BY A.S.T.M. D2737 SDR9 COPPER TUBE SIZE (CTS) ANDA.W.W.A. 901, LATEST EDITION, AND BE PRESSURE RATED FOR 200 PSI AND SHALL BE"ENDOPURE" BY ENDOT INDUSTRIES, INC., ROCKAWAY, N.J., OR APPROVED EQUAL.
5. TUBING SHALL BE MARKED WITH SIZE, MANUFACTURERS NAME, WORKING PRESSURE, NATIONALSANITATION FOUNDATION APPROVAL, A.S.T.M. SPECIFICATION AND PRODUCTION CODE. TUBINGSHALL HAVE AN OUTSIDE DIAMETER EQUIVALENT TO THE OUTER DIAMETER OF COPPER TUBING.
6. SERVICE LOCATOR WIRE SHALL BE LAID IN THE TRENCH WITH ALL SERVICES, CONNECTED TOTHE MAIN WIRE AND WRAPPED AROUND THE SERVICE PIPING OR TUBING. WIRE FOR POTABLEWATER SHALL BE BLUE IN COLOR.
R/W LINE AT PROPERTY CORNERMETER(BY MCU)
METER BOXTO BE SUPPLIEDBY CONTRACTORSEE APPROVEDPRODUCT LIST
COLOR-CODED SERVICE TUBING1" TO 2" SHALL BE POLYETHYLENE
CORP STOP
DOUBLE STRAP TAPSADDLE TAPPEDAWWA THREADS
RESIDENTIAL DUALCHECK VALVE(BY MCU)
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.SERVICE CONNECTION DETAIL
5/8" OR 1" METER 2JUNE 2014
PL
ROADWAY
3
2
1
8
9
LP
PL
5' MIN.
PLAN
ROADWAY
30"
36"
MIN.
MIN.
PROFILE
NOTES:
1. HOUSE SERVICE LATERAL UNDER PAVEMENT SHALL BE INSTALLED THROUGHA 2" MINIMUM PVC SCH. 80 CASING OR HDPE CASING (EXISTING ROADWAYS).
P PL L
4' 4'
2' GUTTER
R/W
R/W
2. TAPPING SADDLE AND CORPORATION STOP MUST BE PLACED IN ACCESSABLE AREAS, OUT FROM UNDER ANY PAVED AREAS.
EASEMENT (TYP.)
3. SERVICE LOCATOR WIRE SHALL BE LAID IN THE TRENCH WITH ALL SERVICES,CONNECTED TO THE MAIN WIRE AND WRAPPED AROUND THE SERVICE PIPINGOR TUBING. WIRE FOR POTABLE WATER SHALL BE BLUE IN COLOR.
CASINGWATER MAIN
POLY TUBING
METER ASSEMBLY
CASING
WATER MAIN
WATER METER
SINGLE SERVICE
DOUBLE SERVICE
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.WATER SERVICE CONNECTIONS (SINGLE OR DOUBLE)
PLAN / PROFILE 3JUNE 2014
WATER M
AIN
DOUBLE STRAP SADDLEAND CORPORATION STOP
SEE TYPICAL SERVICE
TYPICAL MULTIPLE SERVICE SIZESNo. OF UNITS LINE SIZES
3 -12 2" OR 4"
SPACING TO ACCOMODATEMETER BOXES
NOTES:
1. CONTRACTOR TO BUILD ALL METER MANIFOLDS.
POLY (TYP)
(TYP)BRASS TEE
2" RESILIENT SEAT GATEVALVE (RSGV) AND BOX(2" SQUARE OPERATINGNUT)
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.TYPICAL CONNECTION FOR MULTIPLE SERVICES
(THREE OR MORE) 4JUNE 2014
FLOW
VARIES
BY CONTRACTOR
M
NOTES:
1. ALL VALVES TO BE STRAIGHT 1-1/2" BALL VALVES FOR 1-1/2" METER AND 2" BALL VALVES FOR2" METER WITH LOCK-WING. (FLANGE AT METER) FORD OR APPROVED EQUAL.
2. SEE TYPICAL SERVICE DETAIL FOR MAIN CONNECTION.
3. METER BOX SHALL BE POLYMER CONCRETE AND FIBER REINFORCED POLYESTER.
4. PIPING SHALL BE 1-1/2" HDPE FOR 1-1/2" METER AND 2" HDPE FOR 2" METER, DR 9 WITHBRONZE COMPRESSION FITTINGS.
METER(BY MCU)
PROVIDE NIPPLEw/ TEMP. CAP
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
1-1/2" AND 2" METER DETAIL 5JUNE 2014
ITEM QUANTITY DESCRIPTION1234567891011
MATERIALS
111
12
14
2
2 2
3
3
3
13
4
5 TYP.
6
8
7
7 TYP,9
9
10
11
11
TO B.F.P.ASSEMBLY
33
VARIES4414121* CONC. SLAB, 2500# PSI
2" TAP WITH LOCKING BALL VALVED.I. BYPASS TEE, (FLANGE - FLANGE), (SIZE VARIES)3",4",6",8" WATER METER STRAINER, (FLANGE - FLANGE)4",6",8" D.I. SPOOL PIECE, 12" MIN. LENGTH, F - F3",4",6",8" METER, (FLANGE - FLANGE)16"x16"X16" CONC. FOUNDATION, 2500# PSI
4",6",8" PIPE, DUCTILE IRON, (FLANGE - FLANGE)4",6",8" BEND - 90 , (FLANGE - FLANGE)4",6",8" VALVE, GATE, C.I., (FLANGE - FLANGE) OS&Y
12"
12"
12"
16"TYP.
10" TYP.
12"
3O" MIN.
6"
12"15
2" IRON PIPE
15141312 1
VARIES11
4",6",8" VALVE, GATE, MJ4",6",8" PIPE4",6",8" BEND-90°, (MJ-MJ) W/ RETAINER GLANDS4",6",8" ADAPTER, FLANGE, DIP
4(typ)
NOTES:
1. ALL ABOVE GRADE PIPING SHALL BE DUCTILE IRON WITH FLANGED ENDS2. FOR 3" METER AND STRAINER, USE 4" D.I. PIPE WITH 4"x3" REDUCER WITH FLANGED ENDS ON
BOTH SIDES OF THE METER/STRAINER ASSEMBLY.3. FIELD ADJUST AND CUT D.I. PIPE TO THE PROPER LENGTH AS REQUIRED.4. METER BYPASS SHALL BE A MIN. OF 4" DIA. AND SIZED TO MEET REQUIRED FLOWS5. ALL EXPOSED DUCTILE IRON PIPING AND FITTINGS SHALL BE PAINTED "BLUE". PAINT SPECIFICATIONS
MUST BE SUBMITTED TO MARTIN COUNTY UTILITIES PRIOR TO APPLICATION.6. METER SHALL BE BADGER COMPOUND METER, BRONZE BODY, POLYMER BOTTOM PLATE WITH
INTEGRAL MOUNT ITRON 100W FN ENDPOINT.
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.TYPICAL ABOVE GROUND METER
(3" OR LARGER) 6JUNE 2014
LOCK HYDRANT TEE
24" MAX.
18" MIN.
6" DUCTILE IRON PIPEUNDISTURBED SOIL
6" GATE VALVE(SEE VALVE
FINISH GRADEGROUND OR
PAVEMENTSURFACE
24"X24"X6" CONCRETEPAD
36"X36"X6" CONCRETEPAD
SETTING DETAIL)
UNDISTURBED
PLAN
ELEVATION
VARIES
30" MIN.
6" M
AX.
SOIL
GRADE LOK WHERE APPLICABLE
NOTES:
1. HYDRANTS SHALL BE INSTALLED PLUMB AND TRUE.
2. VALVES SHALL BE PLACED ADJACENT TO MAIN, AND TIED TO TEE.
3. ANCHOR TEES ARE REQUIRED.
4. ALL HYDRANTS SHALL BE TEE'D OFF OF MAIN.
5. HYDRANTS SHALL NOT BE PLACED IN SIDEWALK, ROADWAYS OR BIKEPATHS.
6. PIPE FROM VALVE TO HYDRANT SHALL BE RESTRAINED.
7. HYDRANT BARREL AND BONNET COLOR TO BE OSHA YELLOW.
8. THE CONNECTOR PIPE SHALL BE CEMENT LINED DUCTILE IRON, CLASS 350 AND POSITIONED BETWEEN THE FIREHYDRANT AND GATE VALVE.
9. THE CONNECTOR PIPE SHALL HAVE AN ANCHORING FEATURE AT BOTH ENDS SO THAT WHEN USED WITH M.J. SPLITGLANDS A RESTRAINED JOINT IS PROVIDED.
10. HYDRANT EXTENSIONS SHALL NOT BE ALLOWED.
11. NEWLY CONSTRUCTED FIRE HYDRANTS THROUGHOUT THE PROJECT SHALL HAVE A RED "OUT OF SERVICE" DISK(JOSEPH G. POLLARD CO. OR EQUAL) ATTACHED TO 4" PUMPER NOZZLE CAP. DISK TO BE REMOVED AFTER WATERSYSTEM HAS BEEN APPROVED FOR SERVICE BY THE DEPARTMENT.
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
FIRE HYDRANT INSTALLATION DETAIL AND NOTES 7JUNE 2014
TO BE SUPPLIED BY CONTRACTOR ( POLYMERCONCRETE AND FIBER REINFORCED POLYESTER.)
2 1/2" BRASS NSFTDISCHARGE WITH CAPAND CHAIN
VALVE STEM
BRONZE BODY BALL VALVEWITH AUTOMATIC WEEP
90° BEND
FLUSHING ASSEMBLY
CAP OR PLUG
MAIN
2" BALL VALVE
2" POLYETHYLENE PIPE
NOTES:
3'MIN.
W/ 2" TAP
(THREADED)
FLUSH HYDRANT BOX w/ LID LABELED "WATER"
1. FLUSHING HYDRANT ASSEMBLY SHALL BE GIL INDUSTRIES, AQUARIUS ONE-O-ONE OR WATER PLUS VB2000 2" POST FLUSHING HIDDEN HYDRANT.
2. MAIN TO BE RESTRAINED FOR THREE FULL LENGTHS.
6"#57STONE
17"x30" CDR SYSTEMS, OR APPROVED EQUAL.
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
POTABLE WATER FLUSHING HYDRANT 8JUNE 2014
SUPPORT WITH 2"X4" STAKE HOSE BIBB
SAMPLE POINT
1" DIA. MIN. POLYETHYLENE
CORPORATION STOP
DOUBLE STRAP SADDLE
WATER MAIN
NOTES:
1. SAMPLE POINT SHOULD BE A SERVICE LINE OR FIRE HYDRANT IF POSSIBLE.
2. AFTER SAMPLING IS COMPLETED AND APPROVED, SHUT OFF CORP. STOP, REMOVE TUBING, PLUG WITH BRASS PLUG AND LOCATE FOR RECORD DRAWINGS.
2'-6" M
IN.
2'-0" M
IN.
POINT - DO NOT TURN OFF"3. MOUNT METAL OR PLASTIC TAG INDICATING "SAMPLE
(SMOOTH END,NO THREAD)
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
SAMPLE POINT DETAIL 9JUNE 2014
18"MIN.
18"MIN.
DOUBLE STRAP SADDLE ANDCORPORATION STOP REQUIRED.
POTABLE WATER SUPPLY.
EXIST. OR NEWVALVE #1
NEW VALVE #2
FILLING ASSEMBLY FITTINGS & EQUIPMENT SHALL BE 2" MAX.
MIN.18"
WATERMAIN
SEE DETAIL "A"FOR FILLINGASSEMBLY
TEST TO VALVE #2 TEST LIMITS
VALVEMETER A.W.W.A. - RPZ
VALVEUNION BACKFLOW PREVENTER
DETAIL "A"
BLIND FLANGEw/CORPORATIONSTOP
NOTES:
1. BOTH VALVES SHALL BE KEPT CLOSED EXCEPT FOR FILLING, FLUSHING ANDBACTERIOLOGICAL TESTING PURPOSES.
2. DEPARTMENT SHALL BE NOTIFIED BEFORE FILLING AND FLUSHING.3. PRESSURE TEST PUMP CONNECTS TO SERVICE LINE OR BLOWOFF. NO EXTRA TAPS
ARE PERMITTED UNLESS PRECEEDING ARE NOT PRESENT IN TEST SECTION.4. PRESSURE GAUGE TO BE LOCATED IN VICINITY OF TEST PUMP CONNECTION.5. GAUGE AND RISER TO BE REMOVED AFTER PRESSURE TEST.6. REMOVE TEMPORARY CONNECTION AT CORPORATION STOPS AFTER FILLING AND
FLUSHING HAS BEEN COMPLETED.7. INJECT CHLORINE ON PROJECT SIDE OF BACKFLOW PREVENTER.8. CONTRACTOR TO PROVIDE AN RPZ CERTIFICATION (LESS THAN 1 YEAR) PRIOR TO
INSTALLATION.
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.DOUBLE VALVE DETAIL AND
FILLING AND FLUSHING CONNECTION 10JUNE 2014
12" MIN.
SUPPLY
SPRINKLER
THE PRESSURE VACUUM BREAKER (P.V.B.) CANNOT BE INSTALLED WHERE ITWILL BE SUBJECTED TO BACK PRESSURE. IT PROVIDES PROTECTION AGAINSTBACK-SIPHONAGE OF BOTH POLLUTANTS AND CONTAMINANTS.
EACH P.V.B. SHALL BE INSTALLED IN AN ACCESSIBLE LOCATION TOFACILITATE INSPECTION AND SERVICING.
EACH P.V.B. SHALL BE INSTALLED ON THE MAIN LINE TO THE IRRIGATIONSYSTEM AND AT LEAST 12 INCHES ABOVE THE HIGHEST SPRINKLER HEAD OROUTLET. (VALVES MAY BE LOCATED DOWNSTREAM FROM THE DEVICE).
NOTES:1.
2.
3.
ALL ABOVE GROUND PIPING WILL BE TYPE "K" OR "L" COPPER TUBING WITHSWEAT FITTINGS.
4.
IN LIEU OF PRESSURE VACUUM BREAKER.IF CHEM FEED IS USED IN IRRIGATION LINE, THEN USE RPZ. RPZ MAY BE USED 5.
SS UNISTRUT w/SS STRAP
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.PRESSURE - TYPE VACUUM BREAKER (P.V.B.)
(IRRIGATION SYSTEM) 11JUNE 2014
1
3 5
4
5
6
7
METER SERVICE
12" MIN.
4"
8
MATERIALSITEM QUANT. DESCRIPTION12345678
12124
2" BACKFLOW PREVENTER
2" COUPLING - COMPRESSION2" X 90°2" X 6" PEA GRAVEL
FILTER FABRIC FINISHED GRADE
NOTES:1. INSTALLATION SHOWN ABOVE IS FOR A 2" SERVICE. CHANGE PIPING MATERIALS ACCORDINGLY FOR SERVICE SIZE.
55
12"TYP.
1" S.S. UNISTRUT W/ S.S. STRAPS
NIPPLES ELBOW
2. USE COPPER, BRASS OR STAINLESS STEEL FOR FITTINGS AND PIPE MATERIAL.
2 2
9
29 BALL VALVE
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.REDUCED PRESSURE BACKFLOW PREVENTER
SINGLE SERVICE 3/4", 1", 1-1/2" AND 2" 12JUNE 2014
METER
SERVICE
MATERIALSITEM QUANT. DESCRIPTION1234567
242414
2" BACKFLOW PREVENTER2" X 6"2" COUPLING - COMPRESSION2" X 90°2" X 4"
PEA GRAVEL FILTER FABRIC
NOTES:1. INSTALLATION SHOWN ABOVE IS FOR A 2" SERVICE. CHANGE PIPING MATERIALS ACCORDINGLY FOR SERVICE SIZE.
2 3 21
5
4
5
6
7
8
5
'
12" MIN.
NIPPLESTEE 2 2"
8**
PIPE MATERIAL.USE COPPER, BRASS OR STAINLESS STEEL FOR FITTINGS AND2.
12"TYP.
12"
4"
ELBOW
NIPPLES
OPTIONAL 9
BALL VALVES49
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.REDUCED PRESSURE BACKFLOW PREVENTER
DUAL SERVICE 3/4", 1", 1-1/2" AND 2" 13JUNE 2014
1
16"
*16"
MATERIALITEM QUANT. DESCRIPTION
2"
3", 4", 6", 8"
4", 6", 8"
4", 6", 8"
4", 6", 8"4", 6", 8"
3", 4", 6", 8"
1
2
3
45
6
78
9
1
2
*
22
2
21
2
BEND _ 45° ( FLANGE-FLANGE )
PIPE, DUCTILE IRON ( CLASS 350 )
ADAPTER, FLANGE, D.I.P.PIPE, P.V.C. ( DR-18 )
GATE VALVE, C.I., ( FLANGE-FLANGE )
IRON PIPE / CONCRETE FOUNDATIONCONCRETE SLAB
BEND - 45° ( MJ-MJ )
METER
SERVICE
24"TYP.
6"
FROM
BACKFLOW TO BE THE SAME DISTANCE ABOVE GRADE AS METER*
6"
CONC. SLAB SEE METER DETAIL
TEST COCK
8
6
2
4
3FINAL GRADE
7
95
NOTES:
1. FIELD ADJUST AND CUT ITEM 3 TO PROPER LENGTH. THIS TYPE OFCONSTRUCTION IS DESIGNED FOR LIMITED WORKING AREA.
2. ALL EXPOSED DUCTILE IRON PIPES AND FITTINGS SHALL BE PAINTED"BLUE". PAINT SPECIFICATIONS MUST BE SUBMITTED TO MARTINCOUNTY UTILITIES PRIOR TO APPLICATION.
3. FOR 3" BACKFLOW ASSEMBLY, USE 4" D.I. PIPE WITH 4"x3" REDUCERWITH FLANGED ENDS ON BOTH SIDES OF THE BACKFLOW ASSEMBLY.
VALVE, O.C. BACKFLOW PREVENTER
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.REDUCED PRESSURE BACKFLOW PREVENTER
SINGLE SERVICE (3" OR LARGER-45° ELL) 14JUNE 2014
*
FROM
SERVICE
24"TYP.
16"
16"
6"
METER
BACKFLOW TO BE THE SAME DISTANCE ABOVE GRADE AS METER*
BEND - 90° ( MJ-MJ )
CONCRETE SLAB
MATERIAL
VALVE, O.C. BACKFLOW PREVENTER
BEND _ 90° ( FLANGE-FLANGE )
PIPE, DUCTILE IRON ( CLASS 350 )
ADAPTER, FLANGE, D.I.P.PIPE, P.V.C. ( DR-18 )
GATE VALVE, C.I., ( FLANGE-FLANGE )
IRON PIPE / CONCRETE FOUNDATION
3", 4", 6", 8"11
9
87
6
3
54
2
2
12
2
22
2
*4", 6", 8"
4", 6", 8"
4", 6", 8"4", 6", 8"
3", 4", 6", 8"
6"
2"
QUANT.ITEM DESCRIPTION
1 6
95
TEST COCK
4
3
2
7
8
NOTES:
1. FIELD ADJUST AND CUT ITEM 3 TO PROPER LENGTH. THIS TYPE OFCONSTRUCTION IS DESIGNED FOR LIMITED WORKING AREA.
2. ALL EXPOSED DUCTILE IRON PIPES AND FITTINGS SHALL BE PAINTED"BLUE". PAINT SPECIFICATIONS MUST BE SUBMITTED TO MARTINCOUNTY UTILITIES PRIOR TO APPLICATION.
3. FOR 3" BACKFLOW ASSEMBLY, USE 4" D.I. PIPE WITH 4"x3" REDUCERWITH FLANGED ENDS ON BOTH SIDES OF THE BACKFLOW ASSEMBLY.
FINAL GRADE
CONC. SLABSEE METER DETAIL
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.REDUCED PRESSURE BACKFLOW PREVENTER
SINGLE SERVICE (3" OR LARGER-90° ELL) 14AJUNE 2014
E
38-9/16
46-1/16
58-1/16
SIZE OF ALL FITTINGS LISTED INDICATES NOMINAL INSIDE DIAMETER OF PORT
32-5/16
DIMENSIONS (INCH) AND WEIGHT (LBS)
10 16 84-3/161-3/16
E = CENTER TO FACE OF RELIEF VALVE ASSEMBLYD = CENTER TO TOP OF MAIN VALVE BODY
FLANGEINCHES
8
6
4
13-1/2
11
9
SIZE DIA. OFTHICK.
67-3/16
59-11/16
50-7/16
1-1/8
1
15/16
AFLANGE
KEY TO TABLE OF DIMENSIONS
B = FACE TO FACE, INSIDEC = CENTER TO TOP OF GATE VALVE
A = FACE TO FACE, OUTSIDE
D
C
30 22 198216
12-1/217-3/8
26
21-1/4
CB
18
14
11
D
SECTION
399
964
711
WEIGHT
15
14
E
A
B
PLAN
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.REDUCED PRESSURE BACKFLOW PREVENTER ASSEMBLIES
(4 INCH TO 10 INCH DIA.) 15JUNE 2014
FLOW
SERVICE
IRON PIPE / CONCRETE FOUNDATION
GATE VALVE, C.I., ( FLANGE-FLANGE ) OS&Y
PIPE ADAPTER, FLANGE, D.I.P.
PIPE, DUCTILE IRON ( CLASS 350 )
TEE ( FLANGE-FLANGE )
DOUBLE CHECK DETECTOR BACKFLOW PREVENTER
BEND - 90° ( MJ-MJ )
8
NOTE:
2.
1.
9
6
7
54
3
2
1
ITEM
6"1 CONCRETE SLAB
3
2", 4", 6", 8"
2
2
22
2"
*
2
QUANT.1
DESCRIPTION
MATERIAL
OPTIONAL:FIRE DEPT.CONNECTIONw/ WAFERCHECK VALVE
2", 4", 6", 8"
2", 4", 6", 8"
2", 4", 6", 8"
2", 4", 6", 8"
2", 4", 6", 8"
FLOW
FIELD ADJUST AND CUT ITEM 3 TO PROPER LENGTH. THIS TYPE OFCONSTRUCTION IS DESIGNED FOR LIMITED WORKING AREA.ALL EXPOSED DUCTILE IRON PIPES AND FITTINGS SHALL BE PAINTED"RED". PAINT SPECIFICATIONS MUST BE SUBMITTED TO MARTINCOUNTY UTILITIES PRIOR TO APPLICATION.
3. DETECTOR METER SHALL READ IN GALLONS AND SHALL BE 5/8"NEPTUNE MAGNETIC DRIVE, MODEL T-10.
SPOOLPIECE, IFREQUIRED
2
4
3FINALGRADE
24" (typ)
59
7
8
1 6
16"
16"
CONC.SLAB
6"
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.FIRE LINE
DOUBLE CHECK DETECTOR ASSEMBLY 16JUNE 2014
PLAN
ELEVATION
8"
24"
8"
24"6"
CONCRETE COLLAR
POUR CONCRETE TO GRADE
COVER, C.I. OR BRONZE, MARKED"WATER" OR "SEWER"
CONTINUOUS STRANDED COPPER WIRETERMINATING IN CURB STOP BOX IN PAD,10 GAUGE FOR ALL OPEN CUT CONSTRUCTION,8 GAUGE FOR ALL DIRECTIONALLY DRILLEDCONSTRUCTION
2" BRASS CLEANOUT TOPAND PVC THREADED BOX
TOP OFPAVEMENT
C.I. ADJUSTABLE VALVE BOX(INSIDE SCREW TYPE)
SQUARE NUT
VALVE STEM RISER REQUIREDFOR DEPTHS EXCEEDING 4'
APPROVED MECHANICALJOINT VALVE
HALF HITCH(typ)
NOTE:
1. A LOCATION BALL (3M EMS BALL MARKERS; WATER/BLUE, MODEL No. 1403-XR;SEWER/GREEN, MODEL No. 1404-XR) SHALL BE INSTALLED AT EACH FITTING AND/OREVERY 100 FEET OF SEPARATION.
PROVIDE 18" LOOP, WRAPPED IN BOX
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
VALVE SETTING DETAIL 17JUNE 2014
NOTE:
1. AIR RELEASE VALVE SHALL BE A.R.I. MODEL #D-025 SIZED APPROPRIATELY FOR SERVICE INTENDED.
2. ALL PIPING TO BE 316 STAINLESS STEEL.
3. TYPE II CEMENT; CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 4000 PSI AT 28 DAYS.
4. CONCRETE STRUCTURE REINFORCEMENT SHALL MEET ASTM C478 SPECS.
5. CONCRETE STRUCTURE AND D.I. COVER SHALL MEET H-20 LOADING REQUIREMENTS.
6. FOR MINIMUM PIPING AND AIR RELEASE VALVE SIZES, REFER TO M.C.U. APPROVED PRODUCT LIST. ENGINEEROF RECORD SHALL BE RESPONSIBLE FOR SIZING.
SEWER, FORCEOR RECLAIMEDWATER MAIN
SIZE BY ENGINEER-1" (min) BRONZE CORP STOP
SIZE BY ENGINEER-1" (min.) S.S. BALL VALVEDOUBLE
STRAP TAPSADDLE
AUTOMATIC AIRRELEASE VALVE,A.R.I. MODEL #D-025
SIZE BYENGINEER-
1" (min) 316S.S. PIPING
(typ)
BRICK TO GRADEBY CONTRACTOR
VARIES
8"8"
10"±
6" 6" 4'-0" Ø REINFORCEDCONCRETE AIR
RELEASE MANHOLE
32" Ø PAMREXRING AND HINGED COVER
6" 6"
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.UNDERGROUND AIR RELEASE
VALVE AND BOX 18JUNE 2014
DEFLECTION TYPE
FITTING TYPE
MIN. COVE
R30
"
MIN.
12"
MIN.
12"
NOTES:
1. THESE METHODS ARE TO BE USED WHEN INSUFFICIENT COVER EXISTS TO ALLOW PRESSUREPIPE TO CROSS ABOVE CONFLICT PIPE WITH 6" VERTICAL SEPARATION AND MAINTAINREQUIRED COVER TO FINISHED GRADE.
2. FITTINGS SHALL BE RESTRAINED WITH RETAINER GLANDS.
3. THE DEFLECTION TYPE CROSSING IS PREFERRED.
4. DO NOT EXCEED 75% OF MANUFACTURER'S RECOMMENDED MAXIMUM JOINT DEFLECTION.
CONFLICTPIPE
CENTER A FULL LENGTH OF PIPEAT POINT OF CROSSING
SEE NOTE # 4 FORACCEPTABLE DEFLECTION
SLOPE UP TOMIN. COVER
BELL CLAMPS (typ)2 JOINTS EACH SIDE
OF CONFLICT
CENTER A FULL LENGTH OF PIPEAT POINT OF CROSSING
(NO JOINTS BETWEEN FITTINGS)
CONFLICTPIPE
22-1/2° (PREFERRED)OR45° ELBOWS
MECHANICALLYRESTRAINEDJOINTS (typ)
PRESSURE PIPE
FINISHED GRADE
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
PRESSURE PIPE CONFLICT DETAIL 19JUNE 2014
MIN. LENGTH (IN FEET) OF PIPE TO BE RESTRAINED
24"
6
12
26
6220"
5
11
22
5416"
4
9
19
4512"
4
7
15
3510"
3
6
13
308"
3
5
11
256"
2
4
8
204"
1
3
6
14
PIPE SIZEFITTING TYPE
90° HORIZ. BEND
45° HORIZ. BEND
22.5° HORIZ. BEND
11.25° HORIZ. BEND
29 41 53 64 74 95 115 134UPPERBENDLOWERBEND 7 10 13 16 19 25 30 35
OFFSET90° VERT.
4
19
BENDLOWERBENDUPPER
45° VERT.OFFSET
3
12
12
48
76
24 29
108
34 39
15
56
BEND 2
9UPPERBENDLOWER
22.5° VERT.OFFSET
1
6
6
2312
4 4
14
4
17
5
19
7
27
411.25° VERT.
LOWERBENDUPPER
BENDOFFSET
1
3
3
11
1 1
6
2
7
2
8
2
9
3
13
IN-LINE VALVE
PLUG (DEAD END) 32 45 59 70 83 107 151129
4532 45 45 45 55
23 - -- - - - -4"X Ø
356"X Ø 21 - - - - - -
348"X Ø 18 47 - - - - -
3210"X Ø 16 46 58 - - - -
3012"X Ø 13 44 57 69 - - -
2616"X Ø 7 41 55 67 90 - -
2120"X Ø 1 38 52 65 88 109 -
1624"X Ø 1 10834 49 62 86 12930"X Ø36"X Ø42"X Ø48"X Ø
8"X Ø
10"X Ø
12"X Ø
16"X Ø
20"X Ø
24"X Ø
123 116
146 140
99
72
57
90
60
43
6"X Ø
38 25
45
81
111
105107
132 131
78
24
44
75
41
-
45
82 45
-
-
-
-
-
-
-
-
-
- - - - -
-
-
-
-
-
-
TEE(BRANCHRESTRAINT)
23 - - - - - --
REDUCER(LARGERPIPE
RESTRAINT)
65 80
10683 127
103
100
80
77
9773 120
122
124
442881
39
33
221
151
2771
1
1
1
58
54
44
49
(SOURCES: EBAA IRON RESTRAINT LENGTH CALCULATION PROGRAM FOR PVC PIPE, RELEASE 3.1,AND DIPRA THRUST RESTRAINT FOR DUCTILE IRON PIPE, RELEASE 3.2)
NOTES:1. THE DATA IN THE ABOVE TABLE ARE BASED UPON THE FOLLOWING INSTALLATION CONDITIONS:
SOIL TYPE-SAND TEST PRESSURE-150 PSI DEPTH OF BURY-3'TRENCH TYPE-3 SAFETY FACTOR- 1.5 VERTICAL OFFSET-3'MINIMUM PIPE LENGTH ALONG TEE RUN-5'
2. THE RESTRAINED PIPE LENGTHS APPLY TO DUCTILE IRON AND PVC PIPE.3. ALL JOINTS BETWEEN UPPER AND LOWER BENDS SHALL BE RESTRAINED.4. RESTRAINED PIPE LENGTHS APPLY TO PIPE ON BOTH SIDES OF VALVES AND FITTINGS.
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.MECHANICAL JOINT ANCHORING
REQUIREMENTS 20JUNE 2014
PUMP
FEED LINESUPPLYLINE '
RECEIVINGTANK
PROPERTYLINE
LOCATION SHALL BE APPROVED BY MARTIN COUNTY UTILITIES
"D" (PIPE DIA.)
2X"D" OR 1" MIN.
AN AIR GAP SEPARATION MEANS THE UNOBSTRUCTED VERTICAL DISTANCETHROUGH THE FREE ATMOSPHERE BETWEEN THE LOWEST OPENING FROM ANYPIPE OR FAUCET SUPPLYING WATER TO A TANK, PLUMBING FIXTURE OR OTHERDEVICE AND THE FLOOD LEVEL OR OVERFLOW RIM OF THE RECEPTACLE.
THE "APPROVED AIR GAP SEPARATION" SHALL BE AT LEAST DOUBLE THE DIAMETER OF THE SUPPLY PIPE MEASURED VERTICALLY ABOVE THE OVERFLOWRIM OF THE VESSEL AND IN NO CASE SHALL THE GAP BE LESS THAN ONE (1)INCH IN DIAMETER.
1.
2.
NOTES:
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
AIR GAP SEPARATION 21JUNE 2014
12" MAX. 12" MAX.
18" MIN.
12"
MIN.
4" MIN.
BEDDING MATERIAL
EXISTING GROUND
NOTES:
1. BEDDING MATERIAL SHALL BE HAND PLACED IN 6" LIFTS AND SHALL
AS MUCK, DEBRIS AND LARGER ROCK SHALL BE REMOVED.
2. THE PIPE SHALL BE FULLY SUPPORTED FOR ITS ENTIRE LENGTHWITH APPROPRIATE COMPACTION UNDER THE PIPE HAUNCHES.
3. THE PIPE SHALL BE PLACED IN A DRY TRENCH.
5. BACKFILL TO BE COMPACTED ALONG THE SIDES OF THE PIPE AND TOA POINT ONE FOOT ABOVE THE TOP OF THE PIPE TO 100% MAXIMUM
REMAINING BACKFILL SHALL BE COMPACTED IN 6 INCH LAYERS AND
B. WHERE "NO" PAVEMENT IS TO BE CONSTRUCTED OVER THE PIPE
REMAINING BACKFILL6" MAX. SIZE
LIMEROCK 3/8"-7/8" SIZING. UNSUITABLE IN-SITU MATERIALS SUCH
DENSITY AS DETERMINED BY AASHTO T-99.
6. A. WHERE PAVEMENT IS TO BE CONSTRUCTED OVER THE PIPE THE
THE REMAINING FILL SHALL BE COMPACTED IN 6 INCH LAYERS TO A DENSITY
,
,
4. BACKFILL SHALL BE DONE WITH APPROVED MATERIAL, CLEAN ANDFREE OF ROCKS, MUCK AND OTHER DELETERIOUS MATTER AND COMPACTED BENEATH THE HAUNCHES OF THE PIPE USING MECHANICALTAMPERS TO 100% MAXIMUM DENSITY AS DETERMINED BY AASHTO T-99.
COMPACTED TO 95% MAXIMUM DENSITY AS DETERMINED BY AASHTO T-180.
90% MAXIMUM DENSITY AS DETERMINED BY AASHTO T-180.
GRANULAR BACKFILL
CONSIST OF IN-SITU GRANULAR MATERIAL OR WASHED AND GRADED
7. CONTRACTOR SHALL COMPLY WITH ALL STATE AND LOCAL TRENCHSAFETY REGULATIONS
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
TYPICAL TRENCH DETAIL 22JUNE 2014
18" 18"W
VARIES
A D
B
BOTTOM, LEFT, & RIGHTSIDES TO BE 12" MIN.
C
A. OVERLAY 25.0 FROM CENTER LINE OF TRENCH, BOTH SIDES OF OPENCUT WITH 1" MINIMUM TYPE S-III ASPHALT OR MATCH EXISTING
SURFACE MATERIAL WHEN POSSIBLE.B. CONSTRUCT 2.0' DEEP X WIDTH AND LENGTH OF TRENCH WITH CEMENTED COQUINA OR LIMEROCK. SEE SPECIFICATIONS #2 BELOW FOR COMPACTION REQUIREMENTS.C. PROVIDE CLEAN BACKFILL. BACKFILL SHALL BE REPLACED IN 6" LAYERS. EACH LAYER SHALL BE MECHANICALLY COMPACTED TO A
MINIMUM 100% DENSITY AS DETERMINED BY AASHTO T-99, METHOD "C".
1. REPLACED BASE MATERIAL OVER DITCH SHALL BE AS SHOWN ABOVE.2. BASE MATERIAL SHALL BE PLACED IN 6" LAYERS OR AS OTHERWISE APPROVED AND EACH LAYER THOROUGHLY MECHANICALLY COMPACTED TO
(98%) DENSITY AS DETERMINED BY AASHTO T-180.3. ASPHALT CONCRETE PAVEMENT JOINTS SHALL BE LAPPED AND FEATHERED.4. ALL PAVEMENT JOINTS SHALL BE MECHANICALLY SAWED.5. SURFACE MATERIAL WILL BE CONSISTENT WITH EXISTING SURFACE OR
6. A MINIMUM OF TWO DENSITY TESTS SHALL BE TAKEN FOR EACH SIX (6) INCH LIFT OF SUBGRADE AND EACH OPEN CUT CROSSING. WHEN THE SPECIFIED COMPACTED BASE IS GREATER THAN SIX AND ONE-HALF (6-1/2) INCHES THE BASE SHALL BE CONSTRUCTED IN TWO OR MORE COURSES. PROCTORS FOR MATERIALS USED IN BACK-FILLING SHALL BE OBTAINED BY A CERTIFIED LABORATORY. DENSITY TESTS SHALL BE CONDUCTED BY A CERTIFIED LABORATORY OR THE PERMITTEE'S CONSULTANTS. THE PERCENTAGE OF MAXIMUM DENSITY REQUIRED SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE FLORIDA DEPARTMENT OF TRANSPORTATION STANDARD SPECIFICATIONS. A COPY OF ALL COMPLETED AND ACCEPTED DENSITY TESTS SHALL BE FURNISHED TO THE COUNTY ENGINEER'S OFFICE PRIOR TO FINAL INSPECTION.
D. DITCH WIDTH (W)+12", MATCH EXISTING TYPE AND THICKNESS OFASPHALT OR TYPE S-III.
25'
NOTES:
25'
2' MIN. 2' MIN.
6"6"2'
3' M
IN.
OVERLAY OVERLAY
WITH FDOT REQUIREMENTS.AS OTHERWISE DIRECTED (TYPE S-III) AND PLACED IN ACCORDANCE
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
FLEXIBLE PAVEMENT REPLACEMENT DETAIL 23JUNE 2014
VARIES
MONOLITHIC SLAB10' MIN. 10' MIN.10' MIN.
T
4"18"
2' MIN. 2' MIN.
4"
12" MIN.
T OR8" MIN.
REPLACEMENTPAVEMENT
DIA. VARIES
SEE LOCATION CRITERIA
NEAREST JOINT IN PAVEMENT
EXIST. CONC.PAVEMENT
BA
REPLACEMENT OF CONCRETE PAVEMENTFOR PERMITTED PAVEMENT CUT
DENSITY PROCEDURES:
A
B
THE PERMITTEE SHALL PROVIDE ADEQUATE COMPACTED FILL BENEATH THEHAUNCHES OF THE PIPE, USING MECHANICAL TAMPS SUITABLE FOR THISPURPOSE. THIS COMPACTION APPLIES TO THE MATERIAL PLACED BENEATH THEHAUNCHES OF THE PIPE AND ABOVE ANY BEDDING REQUIRED.
THE PERMITTEE SHALL OBTAIN A WELL COMPACTED BED AND FILL ALONG THESIDES OF THE PIPE AND TO A POINT INDICATING THE BOTTOM OFREPLACEMENT PAVEMENT.
GENERAL NOTES:1.
2.
3.
3000 P.S.I. CONCRETE, BY USE OF HIGH EARLY STRENGTH CEMENT, TO BEUSED FOR REPLACEMENT, OR OTHER APPROVED HIGH STRENGTH, FAST SETMATERIALS.CONCRETE PAVEMENT JOINTS SHALL BE MECHANICALLY SAWED TO CONFORMWITH ADJOINING SLABS.BACKFILL MATERIAL SHALL BE EITHER OF THE SAME TYPE AND COMPOSITIONAS THE MATERIAL REMOVED, OR OF EQUAL OR GREATER STRUCTURALADEQUACY. MATERIALS CONTAMINATED WITH DELETERIOUS SUBSTANCES DURINGEXCAVATION SHALL NOT BE USED.
THE BACKFILL FOR A AND B SHALL BE PLACED IN 6" LAYERS (COMPACTED THICKNESS ) AND SHALL BE COMPACTED TO 100% OF MAXIMUM DENSITY AS DETERMINED BY AASHTO T-99 METHOD "C".
12" MIN.
NEAREST JOINT IN PAVEMENT
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
CONCRETE PAVEMENT REPLACEMENT DETAIL 24JUNE 2014
10' ROADWAY 10'
30"
(MIN.)
4"6"8"10"12"16"18"20"24"
12"16"18"20"24"30"30"36"36"
.250
.250
.312
.375
.375
.500
.500
.562
.562
CARRIERPIPE SIZE
MINIMUMSTEEL CASING
MINIMUMWALL THICKNESS
NOTE:
1. LOCATOR WIRE SHALL BE MIN. #10 GAUGEMULTI-STRAND WIRE FOR ALL BORE & JACKING
DUCTILE IRON M.J. PIPEWITH RETAINING GLANDS ANDCASING SPACERS INSTALLED PERMANUFACTURER'S SPECIFICATIONS
POLYMER CONCRETE AND FIBERREINFORCED POLYESTER METERBOX WITH 8" OF 3/4" STONE
PVC VENT
PAVING
ROCK BASE
3/4" MIN. TO 2" MAX.PVC THROUGH GROUTED
END OF CASING
ENDS SEALED WITHCEMENT GROUT
DUCTILE IRON TO EXTENDONE LENGTH MINIMUM
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
CASING INSTALLATION DETAIL 25JUNE 2014
RIPRAP
4'-0"
CORPORATION STOP TO BE LOCATEDWITH DOUBLE STRAP SADDLE ANDAUTOMATIC AIR RELEASE VALVE
RESTRAIN PIPE JOINTS
MIN.
30"
NEAR MOST ACCESSIBLE PILE
1 1/4" GALVANIZED OVERFLOW PIPING (FOR FORCE MAINS ONLY)
WATER-TIGHT W/TRAFFIC BEARING LID
MIN.
NOTES1.
2.3.
4.5.6.7.8.9.
10.
11.12.
13.
ALL EXPOSED PIPES SHALL BE DUCTILE IRON WITH FLANGED FITTINGS.RETAINER GLANDS. UNIFLANGE TYPE FITTINGS ARE NOT TO BESUBSTITUTED FOR FLANGED FITTINGS.SPAN HEIGHT AS REQUIRED BY PERMITTING AGENCY.MAXIMUM SUPPORT SPACING SHALL BE IN ACCORDANCE TO MANUFACTURERS
FAN GUARDS ARE REQUIRED, SEE STANDARD DETAIL.ALL EXPOSED PIPING, GUARDS AND FITTINGS SHALL BE PAINTED.PIPE SHALL BE CRADLED ON NEOPRENE.TIE-DOWN STRAPS MUST PROPERLY FIT AND SECURE PIPE IN CRADLE.
ALL PAINT SPECIFICATIONS MUST BE SUBMITTED AND APPROVED BY MARTINCOUNTY UTILITIES PRIOR TO APPLICATION.CONCRETE IN C.I.P. CAP SHALL HAVE A 28 DAY COMPRESSIVE STRENGTH OF3,400 p.s.i.ALL REINFORCING STEEL SHALL BE ASTM A615 GRADE 60.THE PILES SHALL BE DRIVEN TO A MINIMUM PENETRATION OF 20'-0" UNLESSTHE PRESENCE OF POOR SOILS (N<3) NECESSITATE A DEEPER PENETRATION.PROVIDE TWO FULL LENGTHS OF RESTRAINED D.I.P. BOTH SIDES OF CROSSING.
FOR CONCRETE PILES SEE DETAILS
12"x12" PRESTRESS CONC. PILETYPE 1A (MIN. ONE PER JOINT)
MEAN HIGHWATER ELEV.
(BOTH SIDES)
RECOMMENDATION.
CONCRETE OVERFLOW VESSEL (FORFORCE MAINS ONLY). 50 GAL CAPACITY
CONTINUE LOCATOR WIRE ACROSS CANAL CROSSING.14.
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
TYPICAL UTILITIES CANAL CROSSING 26JUNE 2014
C PIPEL C PIPEL
C PILE & CAPL
DUCTILE IRON PIPE DUCTILE IRON PIPE
SEE DETAIL BELOW
3"
3"
MIN.
(TYP
)
12"CONC. PILE
ELEVATION
3/8" X 3" STAINLESS STEELANCHOR STRAPTOP OF PILE CAP AT120° BEARING
3/4" ANCHOR BOLTAND HEX NUT
CHAMFER ALLEDGES ONE INCH
NEOPRENE WIRED TOPIPE BEFORE CAP ISPOURED
2"
4"
1"120°
DETAIL
4"
C
CA A
3"
24"
4"
3"
12"
12"
B
NOTE:1. ALL REINF. STEEL SHALL BE No. 4 BARS.2. ALL HARDWARE SHALL BE STAINLESS STEEL.3. SEE SHEET 26A FOR ADDITIONAL DIMENSIONS.
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
PILE CAP SUPPORT DETAIL DUAL PIPE (ELEVATION) 27JUNE 2014
D.I. PIPE3/8" X 3" STAINLESSSTEEL ANCHOR
No. 4 BAR
No. 4 BAR STIRRUP
No. 4 BAR OVER PILE(BARS TO BE CUT TOCLEAR THE PILE)
C PILE & CAPL
12" CONCRETE PILE
No. 4 STRAIGHT BARS3"
TYP.
VIEW C-C
PIPEDIA.
PILESIZE
DIMENSIONS
A B
4" 12"x12" 16" 16"
8" 20" 16"
12"
16"
26" 16"
16"30"
12"x12"
12"x12"
12"x12"
24"
12"
24"
NOTE: ALL HARDWARE SHALL BE STAINLESS STEEL.
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
PILE CAP SUPPORT DETAIL DUAL PIPE (VIEW C-C) 27AJUNE 2014
16 TURNS; 3" PITCH 16 TURNS3" PITCH
9" PITCH3/4"
5 TURNS1" PITCH1" PITCH
5 TURNS
No. 5 GAGE SPIRAL TIES
3" COVER( TYP. )
ELEVATION OF 12" X 12" PILE
SECTION "A-A"
A
A
3"
TIP
HEA
D
B
B
8 - 1/2" O S.R. - AS - 0.144 in. - 250K @ 24.100# EA. SPACED 2 1/2" CTRS.
3"
3/4" X 3" CHAMFER3" X 3" CHAMFER OR3/4" X 3/4" CHAMFER
SPIRAL 1"TIESPACING
MAXIMUM LENGTH - 50' SINGLE POINT PICK-UPMAXIMUM LENGTH - 70' DOUBLE POINT PICK-UPOVER 70' TRIPLE POINT PICK-UP SEE F.D.O.TSTD. DRAWINGS INDEX No. 60012"
12"
12"
,
12"
8 - 7/16" O L.R.S. - AS - 0.115 in. - 270K @ 21.700# EA. SPACED 2 9/16" CTRS.
12 - 3/8" O L.R.S. - AS - 0.085 in. - 270K @ 14.800# EA. SPACED 1 11/16" CTRS.12 - 3/8" O S.R. - AS - 0.085 in. - 270K @ 15.600# EA. SPACED 1 11/16" CTRS.
SECTION "B-B"
1"1"
1"1"
3" COVER( TYP. )
PRESTRESSED STRANDSSEE SECTION "A-A"
CENTER LINE12" X 12" PILE
PROVIDE 4 - 1 3/4" HOLESFOR 4 - No. 10 DOWELS4 - 10" LG. GR. 60
2
22
2
,,
,
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
CONCRETE PILE DETAIL 27BJUNE 2014
BE MANUFACTURED FROM STOCK MEETING REQUIREMENTS OF ANY GRADE OF
NOTES:1.
2.
3.
4.
5.
6.
7.
8.
PILE BUILD-UP, WHEN REQUIRED, SHALL BE ACCOMPLISHED WITH 4 #10DOWEL 3" LONG SET IN 1 3/4" DIA. DRILLED HOLES WITH EPOXY MORTAR. PROVIDE 4 #5 LONGITUDINAL BARS AS LONGITUDINAL REINFORCING. SPIRALTIES SHALL BE #5 CONTINUOUS. SPIRALS SHALL BE TIED TO AT LEAST TWOLONGITUDINAL BARS FOR EACH WRAP.
PILING AS PER F.D.O.T. STANDARD SPECIFICATION SECTION 455.
SPIRAL TIES: EACH WRAP OF SPIRALS SHALL BE TIED TO AT LEAST TWOCORNER STRANDS. ONE TURN REQUIRED FOR SPIRAL SPLICES. SPIRALS MAY
REINFORCING STEEL OR HARD DRAWN STEEL.
CONCRETE CLASS: CONCRETE FOR ALL PILES SHALL BE CLASS V (SPECIAL).CLASS V (SPECIAL) CONCRETE SHALL CONFORM TO THE REQUIREMENTS FORCLASS V CONCRETE EXCEPT FOR THE 28 DAY STRENGTH AS NOTED BELOW.
CONCRETE STRENGTH: THE CYLINDER STRENGTH SHALL BE 6,000 p.s.i.MINIMUM AT 28 DAYS AND 4,000 p.s.i. MINIMUM AT TRANSFER OF THEPRESTRESSING FORCE.
PILES SHALL BE MARKED AT PICK-UP POINTS TO INDICATE PROPER POINTSFOR ATTACHING HANDLING LINE.
REINFORCING STEEL: ALL REINFORCING STEEL SHALL BE EITHER GRADE 40OR 60. UNLESS OTHERWISE NOTED. SEE ENVIRONMENTAL REQUIREMENTSNOTE FOR SPLICE REINFORCING ONLY (SPIRAL TIES AND PRESTRESSINGSTRAND ARE UNCOATED FOR ALL ENVIRONMENTAL CLASSES).
STRAND NOMENCLATURE: S.R. = STRESS RELIEVED STRAND L.R.S = LOW-RELAXATION STRAND
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
CONCRETE PILE NOTES 27CJUNE 2014
BAR1/2" X 2" FLAT
8'-0"
5/8" DIA.
1/2" X 2" FLAT BAR
4'-4"
5/8" X 1 1/2" FLAT BAR
5/8" X 2" FLAT BAR
NOTES:
1. FAN GUARDS SHALL BE PLACED AT EACH END OF CANAL CROSSING.
2. FAN GUARD AND ALL MOUNTING BRACKETS TO BE HOT DIP GALVANIZED ANDMOUNTING HARDWARE TO BE STAINLESS STEEL.
3. 1/2" THICK NEOPRENE PAD TO INSULATE PIPE FROM CONTACT WITH ALL MOUNTINGHARDWARE, FAN GUARD HARDWARE, AND CONCRETE SURFACES.
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
FAN GUARD DETAIL 28JUNE 2014
x
IN 4" MAX. LAYERS
xxx x x x x x x
PROTECTIVE SLAB
MIN.
WELL TAMPEDBACKFILL PLACED
SEE
NOTE 2
VARIES
TOP OF PAVEMENTOR FINISHED GRADE
NOTES:1. CONCRETE PROTECTIVE SLAB SHALL BE 2500 P.S.I. WITH 6"X6"-10/10 W.W. MESH AND 12" MIN. BEARING EACH SIDE OF TRENCH.2. PROTECTIVE SLAB REQUIRED WHERE COVER FOR MAINS IS LESS THAN 30" AND LATERALS WHEN LESS THAN 24".
6"
6"
12"
6'6"
d+24"
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
PROTECTIVE SLAB FOR PIPE 29JUNE 2014
TEE BRANCH
SEWER MAINMAKE 4" SERVICE
SERVICE LATERALS SHALL TERMINATE AT P AT A DEPTH OF (3)FEET, PLUGGED
R/W OR EASEMENT LINE
MAX
.
60°
ROTATE BEND AS REQUIRED
LAY ON UNDISTURBED SOIL
WYE BRANCH
ROTATE BENDS AS REQUIRED
L
SLOPE UP TO P1/8"/FT. MIN.
L
L1/8"/FT. MIN.SLOPE UP TO P
WHERE GREATER SEWER DEPTHADDITIONAL RISER AND BENDALTERNATE:
FLOW
SANITARY
PROPERTY LINE
CONNECTION AT R/W LINE
AT PLUGELECTRONIC MARKER
WATERTIGHT AND MARKED WITH 2"x2" TREATED STAKE AND ELECTRONIC MARKER
NOTE:
4" MIN. SERVICE LINE (SINGLE CONNECTION)6" MIN. SERVICE LINE (DOUBLE CONNECTION)
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
TYPICAL SEWER SERVICE CONNECTION 30JUNE 2014
LATERAL24" MIN.
FIN. GRADEC LOW POINT OF SWALEL
HOUSE
PROPERTY LINE
TYPE "B" BEDDING(TYPICAL)
MIN. SLOPE1/8"/FT.
SEWERMAIN
ANGLE VARIES (ROTATE WYE BRANCHAND BEND AS REQUIRED)
TYPE "B-2" WELL COMPACTED SOIL BEDDING@ WYE & CURVE (TYPICAL)
DEPTH OF SEWER MAIN PERMITS.
MAINSEWER
WATERTIGHT P.V.C. STOPPER W/
PROPERTY LINE
STAKE AND ELECTRONIC MARKER(TYPICAL)
6"X6"x4"X4" P.V.C. "Y"FOR DOUBLE CONN.
NOTES:1.
2.
3.
INVERT OF LATERAL TO BE 36" FROM FINISHED GRADE EXCEPT ON " WATERLINE SIDE " OF STREET R/W WHERE IT SHALL DROP TO 48" AS SOON AS
THIS DETAIL TO BE USED WHEN TOP OF SEWER MAIN IS LESS THAN 7'-0"DEEP.INSTALL MAGNETIC MARKERS AT THE END OF EACH SERVICE LINE OROPPOSITE WYES AND RECORD LOCATION.
VARIES36
" MIN.
2"x2" STAKE
48" MAX.
4" SINGLE CONNECTION
6" DOUBLE CONNECTION
P.V.C. WYEOR T-WYE
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
SANITARY SEWER LATERAL DETAIL 31JUNE 2014
6"x4" - 45° P.V.C. WYE
C.L. OF RISER PIPE
6"
2'-6" M
IN.
P.V.C. CAP 6" P.V.C. MIN.AT TERMINUS
4"-45° P.V.C. ELBOWENCASEMENT. KEEP CLEARONE CUBIC YARD OF CONCRETE
FROM HORIZONTAL PIPE
C.I/ VALVE BOX AND LID
CONCRETE ALL AROUND
#4 ROD.
MATCH EXIST. SURFACE
COVER MARKED "S"
3"
6"
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.SEWER SERVICE CLEANOUT
(FOR TRAFFIC AREAS) 32JUNE 2014
CLEANOUT FRAME &
BEND
PLUG
2'-4"
2'-4"
COVER TO BE CLOW
CONCRETE ENCASEMENT
No. 5385 OR EQUAL
8" X 6" WYE BRANCH
6" X 30° L.R.
FINISHED GRADE
6"
1'-2"
SECTION
PLAN
6"6"
DEP
TH TO G
RADE
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
TERMINAL CLEANOUT DETAIL 33JUNE 2014
#4 @ 12" E.W.
No. 4 WIRE 3 x 6 MESH48" MAX.
30" MIN.
PER FT.
FINISH GRADE FRAME & COVER ( SEE DETAIL )
BRICK WITH MORTAR FINISH( 2 COURSES MIN., 5COURSES MAX. )
PRECAST REINFORCEDCONCRETE SECTION( KEYED TO LOWER WALL )
PIPE O.D. PLUS 4" ALLAROUND WITH KEYWAY
8" CONCRETE SLAB( MONOLITHIC POUR WITHFIRST WALL SECTION )
A.S.T.M. SPEC. 20 OR#4 @ 12" E.W.
BRICK RUBBLE BEDDEDAND COVERED WITH GROUT OR CONCRETESLOPE 3/4"
2'-0"
NOTES:
1. PROVIDE 0.1' DROP THROUGH MANHOLE.
2. PRECAST CONCRETE TYPE II, 4000 P.S.I.
3. "RAMNEK" OR EQUAL AT ALL RISER JOINTS (1/2" THICK WITH WIDTH AT LEAST 1/2 THEWALL THICKNESS) WITH GROUT ON INSIDE AND OUTSIDE.
4. ALL OPENINGS SHALL BE SEALED WITH A WATERPROOF NON-SHRINKING GROUT.
5. FLOW CHANNELS SHALL BE CONSTRUCTED TO DIRECT INFLUENT INTO FLOW STREAM. (SEEDETAIL)
6. LIFT HOLES ARE PERMITTED.
7. ALL PIPE HOLES SHALL BE PRECAST OR CORE-DRILLED.
8. SAND COLLAR OR APPROVED RUBBER BOOT MUST BE USED WITH P.V.C. PIPE.
9. MANHOLE TO RECEIVE 2 COATS WATER BASED EPOXY (PRO TECH EW-1 OR APPROVED EQUAL)ON THE INTERIOR AND EXTERIOR. TERMINAL MANHOLES, i.e. THE LAST MANHOLE PRIOR TODISCHARGE TO A LIFT STATION, SHALL RECEIVE 2 COATS OF WATER BASED EPOXY ON THEEXTERIOR (PRO TECH EW-1 OR APPROVED EQUAL) AND 120 MILS OF REZCLAD 1255-AROR MIN. 1/2" SEWPER COAT OR IET SYSTEMS COATING (10 MILS PRIMARY COAT, 30 MILSINTERMEDIATE COAT, 5-10 MILS FINISH COAT) TO THE INTERIOR.
6" 8"
4'-0" MIN.
PRECAST RING OR
DEP
TH G
REA
TER THAN 6
'-0"
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
STANDARD MANHOLE 34JUNE 2014
8"
MIN.2'-0"
( MONOLITHIC POUR WITH8" CONCRETE SLAB
#4 @ 12" E.W.
18" MIN.
24" MAX.
6'-0" U
SE S
TANDARD M
ANHOLE
IF D
EPTH
TO INVE
RT IS G
REA
TER THAN
MINIMUM D
EPTH
4'-0"
4'-0"
6"
( 2 COURSES MIN., 5BRICK WITH MORTAR FINISH
COURSES MAX. )
PRECAST RING OR
PRECAST REINFORCED
( KEYED TO LOWER WALL )CONCRETE SECTION
A.S.T.M. SPEC. 20 ORNo. 4 WIRE 3 x 6 MESH
#4 @ 12" E.W.
GROUT OR CONCRETE
BRICK RUBBLE BEDDEDAND COVERED WITH
PIPE O.D. PLUS 4" ALLAROUND WITH KEYWAY
FIRST WALL SECTION )
NOTES:
1. PROVIDE 0.1' DROP THROUGH MANHOLE.
2. PRECAST CONCRETE TYPE II, 4000 P.S.I.
3. "RAMNEK" OR EQUAL AT ALL RISER JOINTS (1/2" THICK WITH WIDTH AT LEAST 1/2 THEWALL THICKNESS) WITH GROUT ON INSIDE AND OUTSIDE.
4. ALL OPENINGS SHALL BE SEALED WITH A WATERPROOF NON-SHRINKING GROUT.
5. FLOW CHANNELS SHALL BE CONSTRUCTED TO DIRECT INFLUENT INTO FLOW STREAM. (SEEDETAIL)
6. LIFT HOLES ARE PERMITTED.
7. ALL PIPE HOLES SHALL BE PRECAST OR CORE-DRILLED.
8. SAND COLLAR OR APPROVED RUBBER BOOT MUST BE USED WITH P.V.C. PIPE.
9. MANHOLE TO RECEIVE 2 COATS WATER BASED EPOXY (PRO TECH EW-1 OR APPROVED EQUAL)ON THE INTERIOR AND EXTERIOR. TERMINAL MANHOLES, i.e. THE LAST MANHOLE PRIOR TODISCHARGE TO A LIFT STATION, SHALL RECEIVE 2 COATS OF WATER BASED EPOXY ON THEEXTERIOR (PRO TECH EW-1 OR APPROVED EQUAL) AND 120 MILS OF REZCLAD 1255-AROR MIN. 1/2" SEWPER COAT OR IET SYSTEMS COATING (10 MILS PRIMARY COAT, 30 MILSINTERMEDIATE COAT, 5-10 MILS FINISH COAT) TO THE INTERIOR.
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
SHALLOW MANHOLE 35JUNE 2014
8"8"
8"
12 1/4"
3"
TRAFFIC AREA
FINISHED PAVEMENT MIN.
FINISHED GRADE
SET FRAME IN MORTAR BEDOR NON-SAG COLMA BED SEALER
MANHOLE RING AND COVER - TRAFFIC BEARING
DIA.
PRECAST CONC.MANHOLE
3/4" SLOPE
SMOOTH FINISH 1/2"CEMENT MORTAR INSIDEAND OUT OF BRICK ORCONC. GRADE RINGS.
STANDARD PRECASTFLAT TOP w/ ECCENTRICOPENING
CONCRETE OR MORTARBENCH & CHANNELSTROWEL FINISH
2'-0"
'
4'-0"
VARIES
6"
18"
NOTES:
1. PROVIDE 0.1' DROP THROUGH MANHOLE.
2. PRECAST CONCTETE MANHOLES SHALL CONFORM TO ASTM C478, SHALL BE TYPE II ACIDRESISTANT CEMENT AND SHALL ATTAIN A MINIMUM COMPRESSIVE STRENGTH OF 4000 PSI IN28 DAYS.
3. USE ONLY WHERE APPROVED AND SPECIFIED ON PLANS.
4. "RAMNEK" OR EQUAL AT ALL RISER JOINTS (1/2" THICK WITH WIDTH AT LEAST 1/2 THEWALL THICKNESS) WITH GROUT ON INSIDE AND OUTSIDE.
5. ALL OPENINGS SHALL BE SEALED WITH A WATERPROOF NON-SHRINKING GROUT.
6. FLOW CHANNELS SHALL BE CONSTRUCTED TO DIRECT INFLUENT INTO FLOW STREAM. (SEEDETAIL)
7. LIFT HOLES ARE PERMITTED.
8. ALL PIPE HOLES SHALL BE PRECAST OR CORE-DRILLED.
9. SAND COLLAR OR APPROVED RUBBER BOOT MUST BE USED WITH P.V.C. PIPE.
9. MANHOLE TO RECEIVE 2 COATS WATER BASED EPOXY (PRO TECH EW-1 OR APPROVED EQUAL)ON THE INTERIOR AND EXTERIOR. TERMINAL MANHOLES, i.e. THE LAST MANHOLE PRIOR TODISCHARGE TO A LIFT STATION, SHALL RECEIVE 2 COATS OF WATER BASED EPOXY ON THEEXTERIOR (PRO TECH EW-1 OR APPROVED EQUAL) AND 120 MILS OF REZCLAD 1255-AROR MIN. 1/2" SEWPER COAT OR IET SYSTEMS COATING (10 MILS PRIMARY COAT, 30 MILSINTERMEDIATE COAT, 5-10 MILS FINISH COAT) TO THE INTERIOR.
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
FLAT TOP PRECAST MANHOLE 36JUNE 2014
NOTES:
1. ALL INVERT CHANNELS ARE TO BE CONSTRUCTED FOR SMOOTH FLOWWITHOUT OBSTRUCTION.
2. PROPERLY SHAPED SPILLWAYS SHALL BE CONSTRUCTED BETWEEN PIPESWITH DIFFERENT INVERT ELEVATIONS TO PROVIDE FOR SMOOTH FLOWS.
3. BRICK AND CONCRETE RUBBLE PERMITTED AS FLOW CHANNEL BUILDUP.
4. SIDEWALLS OF FLOW CHANNEL SHALL BE AT LEAST HALF OF PIPEHEIGHT AT ALL POINTS.
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
INVERT FLOW CHANNEL DETAIL 37JUNE 2014
6"FINISHED GRADE
5'x 5'x 6" THICKCONCRETE COLLARWITH WIRE MESHREINFORCING.
OR5'x 5'x 8" COLLARWITHOUT REINFORCING.
PICK HOLE
SEWER
SANIT YRA
NOTES:
1. COLLAR IS REQUIRED ONLY WHEN MANHOLE IS OUT OFPAVEMENT.
2. MINIMUM WEIGHTS: COVER - 160 LBS., FRAME - 240 LBS.
3. FRAME AND COVER SHALL BE U.S. FOUNDRY 420-C ORAPPROVED EQUAL.
4. MANHOLE COVER SHALL HAVE THE WORDS "SANITARY SEWER"CAST IN METAL.
5. MANHOLE COVER SHALL MEET H-20 TRAFFIC LOADING.
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.SANITARY SEWER MANHOLE
FRAME AND COVER 38JUNE 2014
NOTES:
1. ALL DETAILS AND SPECIFICATIONS FOR STANDARD MANHOLES AREAPPLICABLE EXCEPT FOR REFERENCES TO DROP ASSEMBLY AND COATINGS.
2. THE PRECAST BASE SHALL EXTEND FULLY UNDER THE DROP ASSEMBLY.
3. MASONRY CONSTRUCTION ABOVE THE EXTENDED PRECAST BASE ISPERMISSIBLE IF FILLED WITH CONCRETE.
4. BRICK AND CONCRETE RUBBLE ARE PERMITTED AS FILLER IN DROPENCASEMENT.
5. DROP CONNECTIONS SHALL BE REQUIRED WHENEVER AN INFLUENT INVERTIS LOCATED 2.0 FEET OR MORE ABOVE THE MAIN INVERT CHANNEL. DROPCONNECTIONS SHOULD NOT BE DESIGNED FOR LESS THAN A 24-INCHDROP.
6. SOLVENT TYPE JOINT P.V.C. FITTINGS MAY BE UTILIZED IN THE DROPASSEMBLY ONLY.
7. EXTERIOR TO RECEIVE 2 COATS OF WATER BASED EPOXY (PRO TECHEW-1 OR APPROVED EQUAL) AND INTERIOR TO RECEIVE COATING OF 120MILS OF REZCLAD 1255-AR OR MIN. 1/2" SEWPER COAT OR IETSYSTEMS COATING (10 MILS PRIMARY COAT, 30 MILS INTERMEDIATE COAT,5-10 MILS FINISH COAT)
6" 8"
4'-0" MIN.
6"
5" MAX.
CL160 PVC 45° BEND
TWO STAINLESS STEEL STRAPSANCHORED TO MANHOLE WITHSTAINLESS STEEL FASTENERS
CORE DRILL MANHOLEGROUT IN BOOT OR SANDCOLLAR COUPLING WITHNON-SHRINK GROUT
DROP BOWL
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
DROP MANHOLE AND SERVICE DROP 39JUNE 2014
SYSTEMGRAVITY
FORCE MAIN
MANHOLE
6' M
AX.
NOTES:
1. FORCE MAIN TO ENTER MANHOLE AS CLOSE AS POSSIBLE TO 180° TOGRAVITY OUTLET.
2. THE INVERT LEVEL OF FORCE MAIN AT POINT OF ENTRY SHALL BE 6"ABOVE INVERT OF MANHOLE.
3. CORE ENTRY ONLY INTO EXISTING MANHOLES. SAND COLLAR ORAPPROVED RUBBER BOOT MUST BE USED WITH PVC PIPE.
4. FLOW CHANNEL REQUIRED.
5. EXTERIOR TO RECEIVE 2 COATS OF WATER BASED EPOXY (PRO TECHEW-1 OR APPROVED EQUAL) AND INTERIOR TO RECEIVE COATING OF120 MILS OF REZCLAD 1255-AR OR MIN. 1/2" SEWPER COAT ORIET SYSTEMS COATING (10 MILS PRIMARY COAT, 30 MILS INTERMEDIATECOAT, 5-10 MILS FINISH COAT).
C-900 PVC PIPE (DR-14)(MECHANICALLYRESTRAINED)
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
FORCE MAIN ENTERING SHALLOW MANHOLE 40JUNE 2014
PLUG
TEE
GRAVITYSEWER
FINISH GRADE OR PAVEMENT
FORCE MAIN
6" WIDE X 1/2" THICKSTAINLESS STEEL BRACE
3/4" STAINLESS STEELANCHOR
4' MIN.30
" MIN
NOTES:
1. DROP PIPE AND FITTINGS MUST BE PVC.
2. PRECAST CONCRETE TYPE II, 4000 P.S.I.
3. "RAMNEK" OR EQUAL AT ALL RISER JOINTS (1/2" THICK WITH WIDTH ATLEAST 1/2 THE WALL THICKNESS) WITH GROUT ON INSIDE AND OUTSIDE.
4. ALL OPENINGS SHALL BE SEALED WITH A WATERPROOF NON-SHRINKINGGROUT.
5. FLOW CHANNELS SHALL BE CONSTRUCTED TO DIRECT INFLUENT INTO FLOWSTREAM. ( SEE DETAIL )
6. LIFT HOLES ARE PERMITTED.
7. ALL PIPE HOLES SHALL BE PRECAST OR CORE-DRILLED.
8. SAND COLLAR OR APPROVED RUBBER BOOT MUST BE USED WITH PVC PIPE.
9. EXTERIOR TO RECEIVE 2 COATS OF WATER BASED EPOXY (PRO TECH EW-1OR APPROVED EQUAL) AND INTERIOR TO RECEIVE COATING OF 120 MILS OFREZCLAD 1255-AR OR MIN. 1/2" SEWPER COAT OR IET SYSTEMS COATING(10 MILS PRIMARY COAT, 30 MILS INTERMEDIATE COAT, 5-10 MILS FINISHCOAT).
PROVIDE MIN.1/4"x2" STAINLESSSTEEL STRAPS w/STAINLESS STEELANCHORS (MIN. TWO)
PUSH-ON JOINTS
ONE LENGTH OF C-900PVC PIPE (DR-14)
CORE HOLE & SEALWITH NON-SHRINK GROUT
90° BEND, ROTATEIN DIRECTION OFGRAVITY SEWER
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
FORCE MAIN ENTERING DEEP MANHOLE 41JUNE 2014
PUMP #
2PUMP #
1
MIN.
12"
3'-0"
3'-0"
CONC. PED
ESTA
L12'H x 5
'W x 6
" TH
ICK
(5' BURY). CHAMFER A
LLEX
POSE
D C
ONC. ED
GES
10'-0" A
CCES
S DRIVE
E.O.P.
E.O.P.
NOTES:
1.ACCES
S ROAD S
HALL C
ONSIST O
F:•12" TH
ICK S
TABILIZED
SUBBASE
, STABILIZED
TO N
OT LESS
THAN 5
0 FB
V AND C
OMPACTED
TO N
OT LESS
THAN 9
8% M
AXIMUM D
ENSITY A
S DETER
MINED
BY
AASH
TO T-180
•8" THICK R
OCK B
ASE
, COMPACTED TO N
OT LESS
THAN 9
8% M
AXIMUM D
ENSITY A
SDETER
MINED
BY
AASH
TO T-180
•8" THICK C
ONCRETE w/FIBER
GLASS
MES
H R
EINFO
RCEM
ENT.
2.PUMP M
ANUFA
CTU
RER
SHALL P
ROVIDE TEMPORARY
4", 0-
60 psig, O
IL FILLED P
RES
SURE GAUGE
FOR S
TART UP.
CONSTRUCTION O
F VA
ULT S
HALL B
E PREC
AST
CONCRETE, P
OURED
IN P
LACE CONCRETE, O
RCONCRETE BLOCK, ALL W
ITH S
TEEL R
OD
REINFO
RCEM
ENT. (MIN. WALL THICKNES
S 5")
X
X X X X
XX
XX
XX
X
XXXX
XX
X
MIN. 4
FT. CLEAR A
LLAROUND EASE
MEN
TFO
R M
AINTENANCE
1" H
OSE
CONNEC
TION &
3/4"
HOSE
BIBB (LOCATE IN A
NY
CORNER
, COORDINATE W
/ O
WNER
)
1" W
ATER S
ERVICE
(2) 2" A
.R.V. w/DOUBLE
STRAP TAPPING S
ADDLES
6' H
IGH
CHAIN-LINK
FENCE
3'-6"
4'-0"
12"
6" (typ)
ALL
AROUND
TOOUTSIDE
EDGE OF
SLAB O
NGRADE
CONTR
OL
PANEL
6' D
IA.
WET W
ELL
GRAVITY S
EWER
C-90
0 PVC
DR-14
1" R
PZ
BACKFLOW A
SSEM
BLY
RTU
METER
PRIMARY
DISCONNEC
T
VENT
4" EMER
GEN
CY
BY-
PASS
90° ELB
OW (UP)
90° ELB
OW
GATE V
ALVE w/ B
OX
DOUBLE S
TRAP TAPPING
SADDLES, 1/2" S
.S. BALL
VALVES
AND P
LUGS
FOR
PRES
SURE GAUGES
12"
MIN
12"MIN
12"MIN
12"
MIN
D.I.P.
FORCE
MAIN
TEE
(TYP
)
(2) 6' W
IDE
GATES
CEN
TERED
ON W
ET W
ELL
℄ W
ET W
ELL
℄ WET WELL
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No. TYPE "A" - TYPICAL
LIFT STATION SITE PLAN LAYOUT 42JUNE 2014
6" 2'-6"
6" M
IN.
8" M
IN.
6'-0" M
IN.
12"
2'-6"
6"
1'-6"
12"
2'-0"
12"
1'-6"
8"MIN.
PUMPS
OFF EL.
1st PUMP S
TART EL.
2nd PUMP S
TART EL.
ALARM EL.
INVE
RT EL.
MIN.
MIN.
MIN.
MIN.
MIN. 12"
MIN.
6"
8'-0" M
IN. FO
R
NOTE
:
1.WET W
ELL TO
REC
EIVE
MIN. 120
MILS
OF REZ
CLAD
1255
-AR O
R M
IN. 1" S
EWPER
COAT OR IET S
YSTEMS
COATING (MIN. 5
MILS
PRIMARY
COAT, M
IN. 50
MILS
INTERMED
IATE C
OAT, M
IN. 5
MILS
FINISH C
OAT)
2.VA
LVE PIT TO R
ECEIVE
2 C
OATS W
ATER B
ASE
D EPOXY
.3.
FLOATS S
HALL B
E ANCHOR S
CIENTIFIC S
30N0
ROTO
-FLOATS O
R EQUAL.
STAINLESS
STEEL C
ABLE S
UPPORT MOUNTED
ON H
INGED
SIDE OF HATC
H. 2n
d SU
PPORT
MOUNTED O
PPOSITE ELECTR
ICAL PANEL.
PRIMARY
DISCONNEC
T,METER
& RTU
6"BACKUP S
TART EL.
100
YR.
FLOOD
ELEV
.____
(ENGINEER TO
PROVIDE)
TOP O
FSTATION
ELEV
____
(2) 2" A
.R.V. w/DOUBLE
STRAP TAPPING S
ADDLES
C-90
0 PVC
DR-14
(MIN.) INFLUEN
T
6" FINISH S
LAB
FIBER
GLASS
MES
HREINFO
RCED
(TYP)
ALUMINUM H
ATC
H w
/STAINLESS
STEEL
HARDWARE. W
ETWELL
HINGED
DOOR TO
OPEN
TOWARD P
ANEL
ALUMINUM H
ATC
H w
/STAINLESS
STEEL H
ARDWARE.
WETWELL HINGED
DOOR TO
AWAY
FROM P
ANEL
4" R
ETURN B
END D
IP
4" C
OMPANION FLANGE
w/ H
ARDWARE CLOTH
.
BRASS
MALE
COMPANION FLANGE
w/ C
AM-LOK
EMER
GEN
CY
BY-
PASS
CONC. PED
ESTA
L
CONTR
OL PANEL
GATE V
ALVE
___" D.I.P.
GATE V
ALVE
HORIZ. SW
ING C
HEC
K V
ALVE w/
LEVE
R A
ND W
EIGHT.
SLOPE FILLET 1/4"
PER
FOOT
DOUBLE S
TRAP TAPPING S
ADDLES, 1/2" S
.S.
BALL V
ALVES
AND P
LUGS
FOR P
RES
SURE GAUGES
___" D.I.P.
2" P
VC D
RAIN
W/ P
-TR
AP
LIFT C
ABLE B
ASE
AND FIRST W
ALL
SECTION -
MONOLITH
IC P
OUR.
BASE
THICKNES
S INCREA
SED A
SNEC
ESSA
RY
TO P
REV
ENT FLOTA
TION
MINIMUM 1/2" S
TAINLESS
STEEL BOLTS
w/ N
UTS
AND W
ASH
ERS, C
OATED
WITH H
EAVY
BITUMASTIC
AFTER
FINAL ASS
EMBLY.
6" D
ISCH. PIPING
ALL FORCE MAINS
TO H
AVE
TEE,
PLUG &
EXTEN
SION TO W
ITHIN
2' O
F BOTTOM O
F WETWELL
POWER
CABLE
LEVE
L CONTR
OLLER
S
CAULK W
ATERTIGHT
AFTER
INSTALLATION
2" D
IA. SLEEVE
SFO
R C
ONDUITS
( 3
REQ
'D. )
TEE
w/
PLUGSE
AL
CABLES
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.TYPE "A" - TYPICAL
LIFT STATION (SECTION) 43JUNE 2014
1.00"
2.00"
30.00"
2.00"
2.00"
3.00"
2.00"
1/2" THICK STEEL PLATE
3/4" DIA. HOLE(TYP)(4 PLACES)
NOTE: 6 RETAINER STRAPS PER JOINT.
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.TYPE "A" - WET WELL SECTION
RETAINER STRAP 44JUNE 2014
ALL AROUNDKEYWAY-2"X4"
WALL BASTM C76 CLASS III
MIN. TREMIE POUR
SECTION
8" MIN.
T & G W/RAMNEK O/E
MINIMUM 1/2" STAINLESS STEEL BOLTSW/NUTS & WASHER COAT W/ HEAVYBITUMASTIC AFTER FINAL ASSEMBLY
INFLUENT
#5 @ 12" O.C., EWUPPER & LOWER
GROUT FILL
15"
18"
REINFORCEMENT PER
MIN.
MIN.
6'-0" MIN. AS NECESSARY TOPREVENT FLOTATION.
NOTES:
1. CONCRETE WETWELL SECTIONS SHALL BE CONNECTED BY STEEL STRAPS, SIX PER JOINT.CONTRACTOR SHALL SUBMIT METHOD TO UTILITIES FOR APPROVAL ALONG WITH SHOP DRAWING.
2. SEE TYPICAL LIFT STATION DETAILS FOR ADDITIONAL DESIGN AND CONSTRUCTION STANDARDS.
3. TREMIE SEAL MINIMUM 5'-0" THICK.
4. DESIGN CALCULATIONS TO BE SUBMITTED FOR APPROVAL.
5. WET WELL TO RECEIVE MIN. 120 MILS OF REZCLAD 1255-AR OR MIN. 1" SEWPER COAT OR IETSYSTEMS COATING (MIN. 5 MILS PRIMARY COAT, MIN. 50 MILS INTERMEDIATE COAT, MIN. 5 MILSFINISH COAT)
PAINT OUTSIDE OFWETWELL W/2 COATSHEAVY BITUMASTIC
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.TYPE "A" - LIFT STATION
TREMIE POUR DETAIL 45JUNE 2014
PUMP DATA:
OPERATING CONDITIONS:
WET WELL:
ELECTRICAL:
MANUFACTURER,
MOD. No., IMP. No., MOTOR,
RPM, PHASE, 60 HERTZVOLTS,
GPM AT
SIZED FOR MINIMUM PUMP CYCLE TIME OF 10 MINUTES AND A MAXIMUMOF 6 PUMP STARTS PER HOUR. WORKING DEPTH FT. WORKINGVOLUME GALS.
FEEDERS AND CONDUIT MAIN SWITCH POLES AMPS
TDH.
HP,
GPM AT TDH.PUMP NO. 1
GPM AT TDH.PUMP NO. 2
NOTE:
THE FOLLOWING VOLTAGE STANDARDS FOR LIFT STATION PUMPS ARE REQUIRED PERFPL AND MCU:
WHERE 3-PHASE POWER IS AVAILABLE• LESS THAN OR EQUAL TO 20 HP: 120/230 3-PHASE, 4 WIRE, OPEN DELTA• MORE THAN 20 HP: 277/480 3-PHASE, 4 WIRE, OPEN DELTA• COORDINATE WITH FPL FOR SUPPLY
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.TYPE "A" - REQUIRED
LIFT STATION INFORMATION 46JUNE 2014
7 1/
2"
LC
COVER
DROP HANDLE
NOTES:
1. COVER TO BE ALUMINUM DIAMOND PLATE, HINGED, TRAFFICBEARING WITH POSITIVE LOCKING ARM AND LOCKING HASP.
2. MINIMUM COVER DIMENSIONS - - - 30"x 48"
3. COVER SHALL BE CAST IN PLACE (BILCO TYPICAL).
4. SPLIT COVER IS ACCEPTABLE FOR LARGER SIZES.
5. RECESSED HASP IS REQUIRED IN WALKWAYS AND TRAFFIC AREAS.
6. LID TO BE H-20 LOADING.
7. HANDLE TO BE SECURED BY STAINLESS STEEL NUTS.
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
TYPE "A" - STANDARD ALUMINUM COVER 47JUNE 2014
5'-6" +
/- 6
"
8"
6"
6"
MIN. 5' D
EEP
PRECAST CONCRETE SUPPORT PLANK12' H x 5' W x 6" THICK w/ #4 REBAR @ 12" O.C.3/4" CHAMFER ON ALL EXPOSED EDGES.
NOTES:
1. ELECTRIC METER AND PRIMARY DISCONNECT MOUNTED ON BACK SIDE OF PANEL.2. EMERGENCY GENERATOR RECEPTACLES: RUSSELL & STOLL, JRSB 1044FR (FOR 100 amp SERVICE),
2044FR (FOR 200 amp SERVICE).3. ALL POWER AND CONTROLS LINES SHALL BE CONTINUOUS (NO SPLICES).4. POWER SUPPLY MECHANICALLY INTERLOCKED.5. PHASE MONITOR ON ALL THREE PHASES (480 & 230 3Ø); VOLTAGE MONITOR REQUIRED ON 1Ø.6. GROUND FAULT INTERRUPTER ON CONVENIENCE RECEPTACLE.7. 1.5 K.V.A. TRANSFORMER IN ALL CONTROL PANELS.8. PANEL MOUNTED TO S/S UNI-STRUT BY WELDED TABS.9. CONTROL PANEL SHALL BE UL LISTED AS A UNIT.10. TELEMETRY CONDUIT SHALL BE INSTALLED BY THE CONTRACTOR WITH SWEEP 90 DEGREE BEND.11. ALL HARDWARE, NUTS & BOLTS, AND APPURTENANCES ABOVE GROUND SHALL BE 316 STAINLESS
STEEL.12. ALL CONDUIT NOT ENTERING WETWELL SHALL BE SCHEDULE 80 P.V.C.13. PANEL MOUNTING SHALL ALLOW FOR UNRESTRICTED VIEW OF ALARM LIGHT.14. MOUNT RTU PANEL TO ALLOW FOR UNRESTRICTED LINE-OF-SIGHT TO ANTENNA FROM ALL
DIRECTIONS.15. INSTALL PANFLEX STRAIN RELIEF ON PUMP POWER LEADS IN J-BOX JUST ABOVE SLAB ON GRADE
(THOMAS AND BETTS OR APPROVED EQUAL)16. INSTALLATION IS NOT CLASSIFIED. SEALOFFS ARE USED SOLELY FOR THE PURPOSE OF LIMITING
CORROSIVE CHEMICALS INTO THE ELECTRICAL EQUIPMENT.
TO WET WELL
#4 @ 12"O.C.E.W.
FLASH RED WARNING LIGHTWITH AUDIBLE ALARM
STAINLESS STEEL SERVICEPANEL (DEADFRONT)
GENERATOR RECEPTACLE
J-BOX, S.S. OR ALUMINUM, WITHCROUSE HINDS OR APPROVED EQUAL.SEALOFFS ON TOP OF BOX TO LIMITCORROSION IN TO PANEL. SEALS ATSEALOFFS TO BE POURED EPOXY.
TO POWER SOURCE
FINISH GRADE
TO BACKFLOWPREVENTER
TO VALVE PIT
TO RTU
SPARE
5/8" Ø S.S. EYEBOLT, THRUBOLTED WITH S.S. FENDER
WASHER & S.S. NYLOCK NUTON OPPOSITE SIDE OF CONC.
PEDESTAL FOR SAFETYLANYARD SYSTEM
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
TYPE "A" - TYPICAL LIFT STATION CONTROL PANEL 48JUNE 2014
PRIMARY DISCONNECT
LIGHTNING ARRESTER
1 - #6 IN 3/4" CONDUIT
BRASS GROUNDING ROD CLAMP
FIN. GRADE
TO F.P. & L. CO. SERVICE HANDHOLE/POLE
COPPER WELL GROUND ROD3/4" X 8'-0" LONG
BACK VIEW OF L.S. CONTROL PANEL
SURGE ARRESTOR
NOTES:
1. NO PENETRATION THROUGH PANEL TOPS.
2. TWENTY INCHES ON RIGHT SIDE OF SUPPORT PLANK (MEASURED FROMINSIDE EDGE OF RIGHT BEVEL) IS RESERVED FOR RTU AND ACCESSORIES.
PRECAST CONCRETESUPPORT PLANK
FEEDERS & CONDUITSCH. 80 PVC, TYP.UNLESS OTHERWISECALLED OUT.
RTU (16"x16")
S.S. CONTROL PANEL MOUNTED ONOPPOSITE SIDE OF CONCRETESTRUCTURE
F.P. & L. CO.SERVICE METER CANPER FPLREQUIREMENTS
20"
4' TO 5'
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
TYPE "A" - LIFT STATION (CONTROL CENTER) 49JUNE 2014
ENCLOSURE & DEADFRONT LAYOUT
OL RESETSRESET RESET
BREAKERS
GR
OFF
ON
OFF
ON
ENCLOSURE & DEADFRONT LAYOUT
TOTAL TIME DELAY
PS1
T1
LIQUID LEVELCONTROL
LIQUID LEVELCONTROL
16
TERMINALS
OFF ONRELAY ON
5122561286432
T2
IN SECONDS
COMBINE FOR
21
84
F1-7
190-270 VAC3O 50/60 HZ
MIN MAX
PHASE SEQUENCE ANDLOSS MONITOR
FA,FB,FC
GROUNDBUS
PDB
OFF
ON ON
OFF
BACKPLATE LAYOUT
R1 R2 R3 R4
MS1 MS1RBSFR2SFR1RSPR
MOTORGF
MONITOR
MOTORGF
MONITOR
NOTE:
PANEL PILOT DEVICESPER CONTROL PANELSCHEMATIC DIAGRAM
BREATHER BOXLEVEL XDUCER
(DOOR SHOWN OPEN)
HUBSTYP.
RDC
BATT BATT
SILENCEBUTTON
LIGHT LIGHT
LIGHT LIGHT
LIGHT LIGHT
SWITCH SWITCH
SWITCH
SWITCH
EP SEALOFFS, TYP. FOR ALLCONDUITS ENTERING WETWELL
AH
AL
3-POINTLATCH
DRIP SHIELD
INTRUSIONSWITCH
ISR ISR ISR ISR ISR
SFM SFM TD
FUSE
XFMR
FUSE_BLOCK
PM
MCB ECB
PCB1,2QOU1
QOU1
QOU1
TERMINALS
2" C, TO POWER SOURCE
NEMA 4X 304 S.S. JUNCTION BOX10"H X 24"W X 6"D W/ SUBPANELU.L. 508
1" C, TO RTU
3/4" C, TO VALVE PIT
3/4" C, TO BACKFLOW PREVENTER
CR GFI
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
TYPE "A" - LIFT STATION CONTROL PANEL 50JUNE 2014
ALL CONDUITS ENTERING THE WETWELL SHALL PVC COATED RGS, SIZED PER PLANS,3.PERMACOAT, ROBROY OR AN APPROVED EQUAL.
ALL CONTROL CIRCUITS ENTERING WETWELL SHALL BE INSTALLED THROUGH INTRINSICALLY4.SAFE RELAYS, PHOENIX CONTACT OR TURCK, OR AN APPROVED EQUAL.THE PUMP MOTOR CIRCUITS SHALL BE INSTALLED WITH GROUND FAULT MONITORS,5. AS MANUFACTURED BY BENDER OR AN APPROVED EQUAL.
LIFT STATION CONTROL PANEL NOTES1. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND
APPLICABLE LOCAL CODES. THE PANEL MAKER SHALL BE A U.L. LISTED SHOP.
2. THE CONTROL PANEL SHALL BE FURNISHED COMPLETELY ASSEMBLED AND WIRED WITH THE FOLLOWING MINIMUM FEATURES:
A. ENCLOSURE SHALL BE STAINLESS STEEL, MODIFIED NEMA 3R, 14 GAUGE, TYPE 304 SS,WITH WELDED SEAMS AND DRIP SHIELD. ALL HARDWARE SHALL BE STAINLESS STEEL. PROVIDEBLANK OUTSIDE DOOR WITH PIANO HINGE, NEOPRENE GASKET, 3 POINT CAPTIVE LATCH WITHNYLON ROLLERS OPERATED FROM A SINGLE PADLOCKABLE HANDLE, WITH DRAWING POCKET.PROVIDE ALUMINUM DEAD FRONT HINGED INNER DOOR FOR MOUNTING CONTROL COMPONENTS;EXTEND CIRCUIT BREAKER HANDLES, RESET BUTTONS, ETC. THROUGH THE DEAD FRONT INNERDOOR. PROVIDE SUB PLATE OF ENAMELED STEEL OR ALUMINUM.
B. MAIN BREAKER, MECHANICALLY INTERLOCKED WITH EMERGENCY BREAKER.GROUND BUS.SEPARATE CIRCUIT BREAKERS FOR THE CONTROL CIRCUITS ETC.20A DUPLEX RECEPTACLE, GFI, WITH SEPARATE BREAKER.SURGE ARRESTER ON THE INCOMING POWER FEEDER
POWER MONITOR WHICH DISCONNECT THE CONTROL POWER FOR ABNORMAL POWER CONDITIONSINCLUDING VOLTAGE DEGRADATION OR PHASE LOSS AND WILL AUTOMATICALLY, WHEN POWERRETURNS, RETURN TO NORMAL. EQUAL TO DIVERSIFIED SLA SERIES.
PROVIDE SQD NEMA SIZED STARTER CONTROLLER WITH OVERCURRENTPROTECTION, SHORT CIRCUIT PROTECTION AND DISCONNECT FOR EACH MOTOR.HOA, MAINT.LIGHT SW. AND PILOT LIGHTS
ALL SELECTOR SWITCHES, PUSH BUTTONS, AND PILOT LIGHTS SHALL BE THE HEAVY DUTY,OIL TIGHT, EQUAL TO SQ.D. TYPE K. ALL PILOT LIGHTS SHALL NOT BE TRANSFORMER TYPE
120V/12V POWER SUPPLY FOR THE FLOAT TYPE LEVEL SWITCH RELAYS AND ANALOG SIGNAL.SURGE CAPACITOR ON THE LOAD SIDE OF THE MAIN BREAKER EQUAL TO GE 9118BAB301.NUMBERED WIRES AND CORRESPONDING TERMINALS. COLOR CODED WIRING TO DISTINGUISHPANEL WIRING OF DIFFERING VOLTAGES AND INCOMING FOREIGN CIRCUITS.
M.L.K.
J.
H.
G.
F.
I.
E.D.C.
AND NOT BE PRESS TO TEST.
N.SIGNALS TO THE WWTP COMPUTER SYSTEM USING THE OWNER'S AND I/O SYSTEM.CONTROL PANEL AND RTU SHALL BE PROVIDED AND CONFIGURED TO SEND & RECEIVE
ALL CONFIGURATION AT THE CONTROL COMPUTER SHALL BE PROVIDED SEPARATELYBY THE OWNER. CONFIGURATION, STARTUP, TESTING AND CHECK-OUT SHALL BE PROVIDEDBY THE RTU MANUFACTURER. CONTRACTOR SHALL PROVIDE AND INSTALLRADIO/MODEM AND I/O SYSTEM IN AGREEMENT WITH THE OWNER'S STANDARD
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
TYPE "A" - LIFT STATION CONTROL PANEL NOTES 50AJUNE 2014
CONTINUED ON 51A
R4
R311
12
ALARM SILENCE
RSSW4
RS
14 S
13
RTU POWER
PCB2
PCB1
FX3
2
2
R2
R1
1
2
PM
CCB
RB
RB
SW2
SW1
7
3
8
4
CRCB
15 AMP
RTUCB
SW3
OFF-ON
PDB FX2
FX1
480 / 240 VAC
3 WIRE3 PHASE
GROUND BAR
ECB
INTERLOCK
MCB
FB
FC
FA
MS2
MS1
PUMP 1 ON
17
2
13
1
189
145
PUMP 2 ON
OL2 10
OL1 6
MOTOROLA ACE RTU
CR
1.5 KVA
MAINT. LIGHT
(FLUORESCENT)
480/240 VAC
1 L1
XF1
GOOD POWER
GFI
P
N
120 VAC
2
1 AMP
1 AMP
1 AMP
MS2
MS1
1
1
GFM1
GFM2
GFM1
GFM2
28
29
PM
FLA:HP:M
FLA:HP:M
MT
MT
GPL
R
GPL
GPL
LAGR
VHOA
VHOA
AL
H
R
SC
NOTE:COORDINATE PANEL WIRING, GR RECEPTACLE WIRING, AND ENGINE-GENERATOR WIRING SUCHTHAT THE CENTER WIRE ON THE BREAKER AND AT ALL POINTS IS THE HIGH LINE.
NEUTRAL
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No. TYPE "A" - LIFT STATION CONTROL PANEL
WIRING DIAGRAM (480 / 240 V, 3-PHASE, 3 WIRE) 51JUNE 2014
CONTINUED ON 51B
CONTINUED ON 51
SFM2
1
+12 VDC
1
1
SFM2
12 VDC+ -
PS1
21
20
1SFM1
12
11
6SFM1
28
19
16
15
57
MOTORTO
RUNNING IN BACKUP
PUMP 2 SEAL FAIL
RSFR2
RB
SFR1R
-12 VDC
N
N
N
PUMP 1 SEAL FAIL
57
82
6
18
17
16
15 TOMOTOR
N
N
ISR3
FS 4
BACKUP
87
RDC
67 68
PL
A
PL
A
PL
A
TDV
BACKUP
SW5
XOENABLE DISABLE
TO PAGE 51C
BATT12 VDC
+ -
21
+ - 43
H N 1112
FU3 1 AMP
316
TD1
5
2 10
32
ISR3
N120 V
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.TYPE "A" - LIFT STATION CONTROL PANEL
WIRING DIAGRAM (480/240 VOLT, 3 PHASE, 3 WIRE) 51AJUNE 2014
CONTINUED ON 51A
100 mAFU7
FU6
FU5
FU4
100 mA
100 mA
100 mA
22
18
14
10
36 21 SPARE
35
34
17
13
33 9 PT SLOT 1
for self-powered loops.* Removeable jumper
23*
24
19
15
11
*
*
20
16
*12
- 12 VDC
FUTURELEVEL XMTR
ISR1 CHANNEL A
FS 1
ALL OFF
21
ISR1 CHANNEL B
FS 2
LEAD ON
43
+ 12 VDC
63 64
61 62
FORCEMAIN
PT
WATER
MOTOROLA ACE RTU
AI-4+(38)
AI-3+(36)
AI-2+(34)
AI-1+(32)
AI-4-(39)
SLOT 1
AI-3-(37)
AI-2-(35)
AI-1-(33)
5
8
7
27
26
4 23
24 R2
ALARM HORN CMD
ALARM LIGHT CMD
R4
R3
PUMP 1 CMD
PUMP 2 CMD
R1SLOT 1
NO1(20)
COM2 (24)
COM4 (30)
COM3 (27)
COM1 (21)
MOTOROLA ACE RTU
NO2(23)
NO4(29)
NO3(26)
4225
ISR2 CHANNEL A
FS 3
LAG ON
65
ISR2 CHANNEL B
FS 5
HIGH ALARM
109
69 70
65 66
BLU-2BLU-1
BLU-4
BLU-15
BLU-17
BLU-3
BLU-14
BLU-16
BLU-26BLU-
BLU-27E
BLU-29BLU-
BLU-30BLU-
BLU-31BLU-13
+ 12 VDCRTU Power Supply
- 12 VDCRTU Power Supply
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.TYPE "A" - LIFT STATION CONTROL PANEL
WIRING DIAGRAM (480/240 VOLT, 3 PHASE, 3 WIRE) 51BJUNE 2014
Wire #s 37-39, 57-59 not used
SPARE
SW2
SFR2
DOOR OPEN
23
LS
RP
SW1OOX
SFR1
MS1
41
40
39
38
24
22
56
54
55
53
37
36
35
34
33
32
31
30
29
28
OOX
RB52
51
50
49
48
MS246
47
45
44
43
27
26
25
42
41
40
SLOT 1
ISR1, CHNL. A
ISR1, CHNL. B
ISR2, CHNL. A
ISR2, CHNL. B
RDCN.O.
D16 (16)
D14 (14)
D15 (15)
D13 (13)
D11 (11)
D12 (12)
D10 (10)
D8 (8)
D9 (9)
D7 (7)
D6 (6)
D5 (5)
D4 (4)
D3 (3)
D1 (1)
D2 (2)
SLOT 1
SW5OX
TO PAGE 51B
+ 12V RTU Power Supply
BLU-5
BLU-13
BLU-6
BLU-7
BLU-8
BLU-9
BLU-10
BLU-11
BLU-12
BLU-18
BLU-19
BLU-20
BLU-21
BLU-22
BLU-23
BLU-24
BLU-25
HIGH ALARM
LAG ON
LEAD ON
ALL OFF
PUMP 1 RUNNING
PUMP 2 RUNNING
SEAL FAILURE PUMP 1
PUMP 1 IN AUTO
PUMP 2 IN AUTO
CONTROL POWER 120VAC
RUNNING IN BACKUP
INTRUSION ALARM
12v DC POWER ON
SEAL FAILURE PUMP 2
BACKUP DISABLED
SPARE
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.TYPE "A" - LIFT STATION CONTROL PANEL
WIRING DIAGRAM (480/240 VOLT, 3 PHASE, 3 WIRE) 51CJUNE 2014
Abbrv.
ENC
ALBATTCCBCRCRCBECB
FA-FCFX1, FX2FX3FU1-FU3FU4-FU7GFM1,2GR
HISR1-3LA
MCBMS1, MS2
PCB1,2PDBPLPS1PM
R1-R4RB, RP, RSRDCRTUCBSFM1, SFM2SFR1, SFR2SW1 - 3, SW5SW4TBTD1XF1SC
Description
Enclosure
Alarm Light (Red Bulb)Battery, 12V DCControl Circuit BreakerConvenience Recept, GFI TypeConvenience Recept, CBEmergency Circuit Breaker
Fuse, Phase Monitor PowerFuse, Transformer PrimaryFuse, Transformer SecondaryFuseFuseMotor Ground Fault MonitorGenerator Receptacle
HornIntrinsically Safe RelaysLightning Arrestor
Main Circuit BreakerMotor Starters
Pump Circuit BreakerPower Distribution BlockPilot Light, color as notedPower Supply, 12 DCPhase Monitor
Control RelayControl RelayControl RelayRTU Circuit BreakerSeal Fail MonitorControl Relay, Seal Fail RelaySwitchAlarm Silence PushbuttonTerminal BlocksTime Delay RelayTransformerSurge Capacitor
Manufacturer
Hoffman or equal
RABPower SonicSquare DPass and SeymourSquare DSquare D
FerrazFerrazFerrazBussBussBenderRussell-Stoll
FederalIngram ProductsDitek
Square DSquare D
Square DMarathonSquare DAstrodyneDiversified
OmronOmronOmronSquare DSSACSquare DSquare DSquare DWagoSSACSquare DSquare D
Part Number
Custom, Nema 3R, 304SS w/rainshield and 3 Pt. latchRAB-VP100DGPS-1270QOU1101595-I and Weatherproof BoxQOU115Size as required
ATQR-1ATQR-X (460 V) or ATQR-15 (230 V)FNM15GDB-1AGDB-100MaRCM460/465 SeriesJRS1044FR or JRS2044FR(as required)350-WB-120ISR2-12V-100KDTK-240-3CM or DTK-480-3CM(as required)Size as requiredClass 8536 NEMA series,Size as requiredSize as required1333555Class 9001 Type SKAD55-ASLA-230-ASA or SUA-460-ASA(as required)MY2N-DC12VMK2PS-AC120MY2N-DC12VQOU110LC54BAClass 8501 Type KPClass 9001 Type SKClass 9001 Type SK280 SeriesTRDU12D3Class 9070 T1500-D16671-SDSA3650
NO EXCEPTIONS will be allowed as to manufacturer of Generator Receptacle, Breakers or MotorStarters. Upon submittal and approval, substitution of other parts on an "As Equal" basis may be allowedif they are directly interchangeable with parts specified. APPROVAL OF A SUBMITTED ITEM AS AN"EQUAL" SHALL BE AT THE SOLE DISCRETION OF THE DEPARTMENT.
CONTROL PANEL PARTS LIST
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.TYPE "A" - CONTROL PANEL BILL OF MATERIALS
(480/240 VOLT, 3 PHASE, 3 WIRE) 51DJUNE 2014
CONTINUED ON 52A
29
28
GFM2
GFM1
GFM2
GFM1
MS1
MS2
1 AMP
1 AMP
2
120 VAC
N
P
GFI
GOOD POWER
XF1
L11
230 VAC
(FLUORESCENT)
MAINT. LIGHT
1.5 KVA
CR
MOTOROLA ACE RTU
6OL1
10OL2
PUMP 2 ON
514
918
1
13
2
17
MT
MT
PUMP 1 ON
GPL
R
RS1
GPL
GPL
RS2
FA
FC
MCBINTERLOCK
ECB
GROUND BAR
1 PHASE3 WIRE
230 VAC
FX1
FX2
PDB
OFF-ON
SW3
RTUCB
15 AMP
CRCB
4
8
3
7
VHOA
SW1
SW2
RB
RB
VHOA
CCB
VM
2
1
R1
R2
2
2
FX3
PCB1
PCB2
RTU POWER
13
S14
RS
SW4RS
ALARM SILENCE
AL
H
R
12
11R3
R4
GR
FLA:HP:M
FLA:HP:M
V21
MS2
VFD
MS1
VFD
V11
V22
1
RS2
V12RS1
1
VMLA
SC
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.TYPE "A" - LIFT STATION CONTROL PANEL
WIRING DIAGRAM (230 VOLT, 1 PHASE, 3 WIRE) 52JUNE 2014
CONTINUED ON 52B
CONTINUED ON 52
SFM2
1
1
1
SFM2
12 VDC+ -
PS1
21
20
1SFM1
12
11
6SFM1
28
19
16
15
57
MOTORTO
RUNNING IN BACKUP
PUMP 2 SEAL FAIL
RSFR2
RB
SFR1R
N
N
N
PUMP 1 SEAL FAIL
57
82
6
18
17
16
15 TOMOTOR
N
N
PL
A
PL
A
PL
A
TDV
BATT12 VDC
+ -
21
+ - 43
H N 1112
FU3 1 AMP
316
TD1
5
2 10
32
ISR3
+12 VDC -12 VDC
ISR3
FS 4
BACKUP
87
RDC
67 68
BACKUP
SW5
XOENABLE DISABLE
TO PAGE 52C
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.TYPE "A" - LIFT STATION CONTROL PANEL
WIRING DIAGRAM (230 VOLT, 1 PHASE, 3 WIRE) 52AJUNE 2014
CONTINUED ON 52A
100 mAFU7
FU6
FU5
FU4
100 mA
100 mA
100 mA
22
18
14
10
36 21 SPARE
35
34
17
13
33 9 PT SLOT 1
for self-powered loops.* Removeable jumper
23*
24
19
15
11
*
*
20
16
*12
FUTURELEVEL XMTR
ISR1 CHANNEL A
FS 1
ALL OFF
21
ISR1 CHANNEL B
FS 2
LEAD ON
43
63 64
61 62
FORCEMAIN
PT
WATER
MOTOROLA ACE RTU
AI-4+(38)
AI-3+(36)
AI-2+(34)
AI-1+(32)
AI-4-(39)
SLOT 1
AI-3-(37)
AI-2-(35)
AI-1-(33)
ISR2 CHANNEL A
FS 3
LAG ON
65
ISR2 CHANNEL B
FS 5
HIGH ALARM
109
69 70
65 66
BLU-2BLU-1
BLU-4
BLU-15
BLU-17
BLU-3
BLU-14
BLU-16
- 12 DC+ 12 DC
5
8
7
27
26
4 23
24 R2
ALARM HORN CMD
ALARM LIGHT CMD
R4
R3
PUMP 1 CMD
PUMP 2 CMD
R1SLOT 1
NO1(20)
COM2 (24)
COM4 (30)
COM3 (27)
COM1 (21)
MOTOROLA ACE RTU
NO2(23)
NO4(29)
NO3(26)
4225
BLU-26BLU-
BLU-27E
BLU-29BLU-
BLU-30BLU-
BLU-31BLU-13
+ 12 VDCRTU Power Supply
- 12 VDCRTU Power Supply
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.TYPE "A" - LIFT STATION CONTROL PANEL
WIRING DIAGRAM (230 VOLT, 1 PHASE, 3 WIRE) 52BJUNE 2014
Wire #s 37-39, 57-59 not used
SPARE
SW2
SFR2
DOOR OPEN
23
LS
RP
SW1OOX
SFR1
MS1
41
40
39
38
24
22
56
54
55
53
37
36
35
34
33
32
31
30
29
28
OOX
RB52
51
50
49
48
MS246
47
45
44
43
27
26
25
42
41
40
SLOT 1
ISR1, CHNL. A
ISR1, CHNL. B
ISR2, CHNL. A
ISR2, CHNL. B
RDCN.O.
D16 (16)
D14 (14)
D15 (15)
D13 (13)
D11 (11)
D12 (12)
D10 (10)
D8 (8)
D9 (9)
D7 (7)
D6 (6)
D5 (5)
D4 (4)
D3 (3)
D1 (1)
D2 (2)
SLOT 1
SW5OX
TO PAGE 52B
+ 12V RTU Power Supply
BLU-5
BLU-13
BLU-6
BLU-7
BLU-8
BLU-9
BLU-10
BLU-11
BLU-12
BLU-18
BLU-19
BLU-20
BLU-21
BLU-22
BLU-23
BLU-24
BLU-25
HIGH ALARM
LAG ON
LEAD ON
ALL OFF
PUMP 1 RUNNING
PUMP 2 RUNNING
SEAL FAILURE PUMP 1
PUMP 1 IN AUTO
PUMP 2 IN AUTO
CONTROL POWER 120VAC
RUNNING IN BACKUP
INTRUSION ALARM
12v DC POWER ON
SEAL FAILURE PUMP 2
BACKUP DISABLED
SPARE
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.TYPE "A" - LIFT STATION CONTROL PANEL
WIRING DIAGRAM (230 VOLT, 1 PHASE, 3 WIRE) 52CJUNE 2014
Abbrv.
ENC
ALBATTCCBCRCRCBECB
FA-FCFX1, FX2FX3FU1-FU3FU4-FU7GFM1,2GR
HISR1-3LA
MCBMS1, MS2
PCB1,2PDBPLPS1VM
R1-R4RB, RP, RSRDCRTUCBSFM1, SFM2SFR1, SFR2SW1 - 3, SW5SW4TBTD1XF1SC
Description
Enclosure
Control Circuit BreakerConvenience Recept, GFI TypeConvenience Recept, CBEmergency Circuit Breaker
Fuse, Phase Monitor PowerFuse, Transformer PrimaryFuse, Transformer SecondaryFuseFuseMotor Ground Fault MonitorGenerator Receptacle
HornIntrinsically Safe RelaysLightning Arrestor
Main Circuit BreakerMotor Starters
Pump Circuit BreakerPower Distribution BlockPilot Light, color as notedPower Supply, 12 DCVoltage Monitor
Control RelayControl RelayControl RelayRTU Circuit BreakerSeal Fail MonitorControl Relay, Seal Fail RelaySwitchAlarm Silence PushbuttonTerminal BlocksTime Delay RelayTransformerSurge Capacitor
Manufacturer
Hoffman or equal
Square D
Square DSquare D
BussBussBenderRussell-Stoll
FederalIngram ProductsDitek
Square DYaskawa-iQ Pump
Square D
Square D
Diversified
OmronOmronOmronSquare DSSAC
Square DSquare DWagoSSACSquare D
Part Number
Custom, Nema 3R, 304SS w/rainshield and 3 Pt. latch
QOU110
QOU115Size as required
GDB-1AGDB-100MaRCM460/465 SeriesJRS1044FR or JRS2044FR(as required)350-WB-120ISR2-12V-100KDTK-240-3CM(as required)Size as required
Size as required
Size as required
Class 9001 Type SK
VBA-120-ALA(as required)MY2N-DC12VMK2PS-AC120MY2N-DC12VQOU110LC54BA
Class 9001 Type SKClass 9001 Type SK280 SeriesTRDU12D3Class 9070 T1500-D1
NO EXCEPTIONS will be allowed as to manufacturer of Generator Receptacle, Breakers or MotorStarters. Upon submittal and approval, substitution of other parts on an "As Equal" basis may be allowedif they are directly interchangeable with parts specified. APPROVAL OF A SUBMITTED ITEM AS AN"EQUAL" SHALL BE AT THE SOLE DISCRETION OF THE DEPARTMENT.
CONTROL PANEL PARTS LIST
Controller Series
Square D
Square D
Class 8501 Type KP
6671-SDSA3650
Battery, 12V DC Power Sonic PS-1270
Pass and Seymour 1595-I and Weatherproof Box
FerrazFerrazFerraz
ATQR-1ATQR-15 (230 V)FNM15
Marathon
Astrodyne
1333555
AD55-A
Alarm Light (Red Bulb) RAB RAB-VP100DG
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.TYPE "A" - CONTROL PANEL BILL OF MATERIALS
230 VOLT, 1 PHASE, 3 WIRE 52DJUNE 2014
The unit shall be a 4 inch x 4 inch vacuum-assisted horizontal sewage pump driven by awater-cooled diesel engine. The pump shall be fully automatic, self-priming from dry conditionsand capable of handling large volumes of air, water, and solids. Pump unit shall include asound attenuation enclosure covering both the engine and pump for noise abatement. The unitshall be a Thompson model 4JSVM-DYST-3TNV88-MC or engineer approved equal.
1.1 The complete pump-set shall be manufactured in a plant that is registered toISO9001:2008 and a copy of the Certificate shall be provided with the shop drawing submittal.
1.0 GENERAL DESCRIPTION
Model 4JSVM-DYST-3TNV88-MC Thompson - Towable 4" x 4" Vacuum Assisted, Dry Priming Sewage Pump
2.0 CENTRIFUGAL PUMP2.1 The centrifugal pump shall be a horizontal end suction solids handling centrifugal type.2.2 The pump casing shall be constructed of high grade class 30 cast iron with a minimum
pressure rating of 100 psi.2.3 Pump casing shall contain a cleanout cover for removing debris from the impeller without
disturbing the suction or discharge piping.2.4 The pump casing shall be constructed so that the suction flow path is in axial alignment
with the impeller eye. There shall be no turns, chambers, obstructions or straightening vanes between the suction line and the impeller.
2.5 The impeller shall be a high efficiency non-clog type, 2-vane, enclosed design with fullfront and rear shrouds, containing back pump out vanes, constructed of high grade class30 cast iron and capable of passing a 3 inch spherical solid. Open type impellers andimpellers that contain balancing ” holes shall not be considered.2.6 Pump seal shall be an inside-mounted, self-cleaning John Crane type 2 component style
mechanical seal with tungsten carbide rotating and silicon carbide stationary faces with vitonelastomers and stainless steel spring and hardware. Outside mounted seals and seals thatuse the same material for both the rotating and stationary seal faces which are prone toheat checking shall not be considered.
2.7 The seal chamber shall include a tapered bore design to remove solids and abrasivematerial
away from the seal area and purge air and gas pockets. Straight bore designs that areprone to vapor buildup and clogging will not be considered.
2.8 An oil reservoir shall be provided for automatically circulating lubricant to the seal facespermitting indefinite dry running.
2.9 Shaft shall be constructed of modified SAE1144 stress proof alloy steel, machined andpolished to transmit full drive output. Shaft shall be tapered for maximum strength.
2.10 Bearing frame shall be constructed of class 30 cast iron.2.11 Bearings shall be of sufficient size to withstand the radial and axial thrust loads incurred
during service. Bearings shall have a minimum L-10 bearing life of 100,000 hours.Bearings shall be grease lubricated.2.12 The pump shall have an efficiency of 79% at best efficiency point. The pump curveshowing efficiencies shall be provided with the shop drawing submittal. Pump curves that failto comply with this requirement will not be considered.2.13 Centrifugal pump shall be capable of delivering a maximum flow at 2200 rpm of 1450
USGPM at 26 ft. TDH.2.14 Centrifugal pump shall be capable of generating a closed discharge valve (shutoff) head of
no less than 130 feet at 2200 rpm. The pump must be capable of delivering 1,000 USGPMat 66' TDH and 20' suction lift and minimum 78% efficiency. Pumps not capable of
meeting these requirements will not be considered.2.15 Pump shall be capable of handling suction pressures up to 100 psi.2.16 Centrifugal pump shall be capable of handling up to 3 inch diameter non-compressible
spherical solids.2.17 The pump inlet shall be equipped with a 4 inch MNPT fitting.2.18 The pump outlet shall be equipped with a 4 inch, steel 90 degree elbow complete with a 4
inch ANSI 125-lb. flange on one side and a 4 inch male quick connect, cam-lock stylefitting on the other side.3.0 ENGINE
3.1 The engine shall be a EPA Interim Tier IV approved, three cylinder four-cycle water-cooleddiesel engine, capable of producing 28 continuous duty horsepower at 2,200 rpm.
3.2 The engine shall drive the pump via an elastomeric torsion drive coupling.3.3 An industrial type battery shall be provided with the engine and have 175-amp hour rating
and minimum 760 cold-cranking amps.
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.TYPE "A" - EMERGENCY DRY-PRIMING
SEWAGE PUMP SPECIFICATIONS 53JUNE 2014
4.0 OIL-LESS VACUUM PRIMING SYSTEM
3.4 A 12-volt starter and alternator charging system shall be provided.3.5 An industrial-style muffler shall be provided.3.6 Governor shall be mechanical type. Engine speed shall be adjustable to operate the pump
between maximum and minimum design operating speeds.3.7 Engine shall have safety shutdown switches for low oil pressure and high coolant
temperature.3.8 A control panel shall be provided in an enclosure mounted inside the sound enclosure on
rubber isolators to reduce vibration.3.9 Control panel shall contain the following instrumentation and controls: key switch,
tachometer, hourmeter, oil pressure gauge and temperature gauge.
4.1 The priming system shall be fully automatic eliminating the need to pre-fill the pumpcasing with water to achieve initial prime.
4.2 The priming system shall work in combination with the centrifugal pump to remove largevolumes of air required for WellPoint service.
4.3 An air separation chamber shall be provided to prevent any carryover of the pumping fluidinto the vacuum pump. Units not meeting this requirement shall not be considered.
4.4 The air separation chamber shall contain a single float and ball valve assembly mounted ona steel plate that can be easily removed as a unit without tools.
4.5 The air separation chamber shall not include any screens that can clog creating amaintenance nuisance and cause the priming system to fail.
4.6 The vacuum pump shall be a rotary claw, air-cooled oil-less version and have a nominalrating of 97 cubic feet per minute.
4.7 The vacuum pump shall be driven by a v-belt with belt tensioner that can be easilyreplaced in the field without having to remove the pump from the engine. A spare v-belt
shall be pre-installed around the shaft and ready for immediate placement in the event of afailure to the primary v-belt.4.8 A flapper type discharge check valve shall be provided to prevent pulling air through the
discharge during priming.4.9 The priming system shall be capable of automatically priming the pump with a 15-foot
static suction lift and no water in the pump or suction piping within 15 seconds. Units notmeeting this requirement shall not be considered.
5.0 FRAME / FUEL TANK5.1 The pump set shall be mounted on a combination frame/fuel tank constructed of steel with
a minimum fuel capacity of 50 US gallons.5.2 A centralized removable lifting bail shall be provided for lifting the entire pump set.5.3 Fuel tank shall have two clean-out ports located at opposite ends of the tank.5.4 Fuel tank shall have a removable basket strainer mounted in the fill port and a lockable
cap. This fill port is to be located in the front (towards hitch end of unit) of the fuel tankframe to prevent spillage.
5.5 An in-line fuel filter shall be provided to protect the engine from contaminants.5.6 Unit shall be equipped with a mechanical, direct reading, frame-mounted fuel gauge.
6.0 TRAILER6.1 The complete pump set shall be factory mounted on a detachable highway trailer meeting
NHTSA, DOT Part 571 standards 108, 119 and 120.6.2 Trailer shall include the following:
• 5,200 LB. capacity single torsion axle with electric brakes• Two ST225/75R15-D tires with metal valve stems• Tongue assembly with 3 inch adjustable lunette eye hitch and safety chains• Removable steel diamond plate fenders• One top wind swivel 5000 lbs. capacity 15 inch retractable height tongue-mounted jack stand• Four stabilizing stands• DOT light package including stop, turn, tail and side marker lights and license bracket.• Metal valve stems
7.0 PAINTING7.1 A minimum 5-mil thick layer of epoxy-coated primer shall be applied to the entirepumpset prior to the finish coat. A minimum 5-mil thick layer of industrial enamel paint shallbe applied over the primer coat. The color shall be blue.
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.TYPE "A" - EMERGENCY DRY-PRIMING
SEWAGE PUMP SPECIFICATIONS 53AJUNE 2014
8.0 WARRANTY8.1 The manufacturer of the pumping unit shall warrant for a period of one year from the date
of shipment that the entire unit and all equipment therein shall be free from defects indesign, material, and workmanship.
9.0 MANUALS9.1 One complete set of operation and maintenance manuals, stored inside a rainproof
document box, shall be furnished with the unit.
10.0 TESTING10.1 The complete pump set shall be factory tested by a certified quality technician. A test
report shall be submitted to the County prior to acceptance.
11.0 AUTOMATIC START/STOP SYSTEM11.1 An automatic engine controller shall be provided to start and stop the diesel engine in
response to varying liquid levels via float switches.11.2 The automatic start-stop engine controller will be part of the main instrument panel.
Multiple control panels shall not be considered.11.3 The system shall contain a safety back-up feature allowing the unit to be operated
manually and retain safety shutdown protection in the event of automatic engine controllerfailure.
11.4 The automatic engine controller shall be fully field programmable and contain pass codeprotection.
11.5 The automatic engine controller shall contain automatic and manual start modes.11.6 The automatic start-stop system shall contain two mechanically activated hermetically
sealed liquid level control floats; one to turn the pump on and one to turn pump off.Single float designs that are prone to frequent cycling leading to excessive component wearwill not be considered.
11.7 The floats shall be clearly marked, top or bottom, for easy installation into wet well. Floatsshall be provided with 40-feet of cable.
11.8 The two floats shall be connected together with a single pin terminal for easy connectionto control box.
12.0 SOUND ENCLOSURE12.1 The entire unit including the pump and engine shall be completely enclosed in a lockable
enclosure. Units not meeting this requirement shall not be considered.12.2 The enclosure shall reduce operating noise below 70 dBa measured at 7 meters @ full
speed. Units not meeting this requirement will not be considered.12.3 The enclosure shall be constructed with a modular galvanized steel frame and 2 inch thick
reinforced galvanized steel panels. Fiberglass or plastic enclosures shall not be considered.12.4 The individual panels shall be constructed of a sandwich construction of an 18-gauge solid
galvanized steel outer shell, 2 inch thick 8lb density mineral wool fill encapsulated in a1-mil polyester moisture barrier, damping sheet and 22-gauge perforated galvanized steelinner liner. Unprotected open-cell foams with adhesive-style mounting systems shall not be
considered.12.5 The enclosure shall contain a minimum of 6 lockable-hinged doors; three sides, two rear
and one front door to allow unrestricted access to all compartments for servicing withouthaving to disassemble and remove panels. The enclosure shall contain a modular lift offpanel on top. Enclosures that must be disassembled in order to facilitate routinemaintenance will not be considered.
12.6 The enclosure shall contain two rear doors that can be opened and permit complete accessto the pump and priming system for routine maintenance without having to disconnect thesuction or discharge piping.
12.7 The enclosure shall be fully detachable as a single unit to facilitate major repairs such asreplacing the engine or pump.
12.8 Hose racks for discharge and suction hoses13.0 ADDITIONAL ACCESSORIES
13.1 (2) 4 inch x 50 foot Lay-Flat Discharge Hose, Double Banded C x E13.2 (2) 4 inch x 20 foot Suction Hoses, PVC Double Banded, C x E
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.TYPE "A" - EMERGENCY DRY-PRIMING
SEWAGE PUMP SPECIFICATIONS 53BJUNE 2014
NOTES:
1. ALL ABOVE GRADE PIPING SHALL BE BRASS. FITTINGS SHALL BE BRONZE.
2. ALL JOINTS SHALL BE THREADED.
3. FOR LIFT STATION TO BE OWNED BY M.C.E.S. USE RPZ BACKFLOW PREVENTER BY FEBCO MODEL825Y, AMES SERIES 4000 SS (SILVER BULLET), OR APPROVED EQUAL.
4. MIN. 24" CLEARANCE BETWEEN RPZ BACKFLOW PREVENTER AND CONTROL PANEL REQUIRED.
5. THREADED AREAS OF CORPORATION STOP AND OTHER FITTINGS SHALL BE SPIRAL WRAPPED WITHTWO WRAPS OF TEFLON TAPE.
PIPE SUPPORT DETAIL
18" MAX.
12" MIN.
XX
6" THICK CONC. PAD w/#96"x6" WWF (BROOM FINISH)
3" MIN.
18"-
24"
PIPE SUPPORT(TYP. SEE DETAIL)
3/4" HOSE BIBB
1" LOCKING VALVE
BRASSCOVER
XX
6"x 3"x 3/8" THICKALUMINUM PLATE
3/16
1" FIREHOSE THREADw/CAP
1" BALL VALVE w/METER BOX SHALLBE LOCATED OUTSIDE CONC. AREA
1-1/2" PVCPIPE SLEEVE
6"(typ) 12"-18"
6" PIPE NIPPLE1" USC APPROVEDBACKFLOW PREVENTER
6" PIPENIPPLE
FENCE
1" PIPE
PIPE
FENCE
WRAP PIPE WITH 1/4"NEOPRENE AT U-BOLTS
3/8" STAINLESS STEEL WEDGETYPE CONC. ANCHOR (2 REQUIRED)
STD. STAINLESS STEEL3/8" U-BOLT
2"x 2"x 1/4" ALUMINUM ANGLE
1/4" CHAMFER(ALL AROUND)
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.WATER SERVICE DETAIL AT LIFT STATION
(TYPES "A" & "B") 54JUNE 2014
TOP RAIL 1 5/8" O.D.GSP SCHD. 40
2 1/2" O.D. GSPSCHD. 40 SPACEDAT 10'-0" MAX.
7 GA. AL. COATEDSPR. COIL TENSIONWIRE
CONCRETE FTG.
DIAGONALBRACE W/TURNBUCKLE
STRETCHERBAR
HORIZONTALBRACE
3" O.P. GST. SCHD.40 AT CORNER
6'-0"
3'-6"
12"
6"
12"
6'-0"
LINE POST CORNER POST
12"
6"
3'-6"
WATERPROOF CAP
HINGE (2)
4" O.D. GSP SCHD.40 AT GATE OPENING
HORIZONTAL BRACEDIAGONAL BRACE W/TURNBUCKLE
CONCRETE FTG.
HOR,BRACE
VERT.BRACE
GATE RAIL & POSTS 1 5/8"O.D. GSP SCHD. 40
STRETCHER BAR
DIAGONAL BRACEROD W/ TURNBUCKLE
GATE
GATE POST
9 GA. BLACKVINYL COATEDSTEEL FABRIC
GALVANIZED CHAINW/ PADLOCK
NOTES:
1. GATE TO BE 12'-0" CLEAR OPENING.
2. BLACK VINYL COATED STEEL WOVEN WIRE FABRIC TO BE STRETCHED TAUT W/ STRETCHER BARSAND STRAPS AND FASTENED TOP & BOTTOM AND AT LINE POSTS WITH GALV. PIG RING TIES.
3. GATE TO BE SECURED OPEN WITH GATE STOP SET IN CONCRETE.
4. ALL RAILS, POSTS AND HARDWARE TO BE VINYL COATED. ALL VINYL COATING SHALL BE BLACK.
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.FENCE DETAIL AT LIFT STATION
(TYPES "A" & "B") 55JUNE 2014
2" S
CH. 80
PVC
FM
DEFLECT FM
TO
ACHIEVE
30" M
IN C
OVE
R
1" WATER
SERVICE
1" R
PZ
BACKFLOW
ASS
EMBLY
1"HOSE
CONNEC
TION
& 3
/4" H
OSE
BIBB
(LOCATE IN A
NY
CORNER
,COORDINATE W
/ O
WNER
)
E.O.P.
4'-0"
6' H
IGH C
HAIN
LINK FEN
CE
(2) - 6
' WIDE GATES
CEN
TERED
ON W
ET W
ELL
10'-0" A
CCES
S DRIVE
E.O.P.
PU
MP
# 2
PU
MP
# 1
3'-0"
2'-0"
3'-0"
3'-0"
3'-0"
X
X
X X X X
XX
XX
XX
XXXX
XX
X
MIN. 4
FT. CLEAR A
LL A
ROUND
EASE
MEN
T FO
R M
AINTENANCE
4" C
ONCRETE
SLAB 4
,000
PSI
CLA
SS A
WITH FIBER
MES
HREINFO
RCEM
ENT
U.S. FO
UNDRY
BPS-
48 A
LUMINUM
HATC
H C
OVE
RW/ 2
4" x 3
6"ACCES
S DOOR
U.S. FO
UNDRY
APS-
150
ALUMINUM V
ALVE
BOX
COVE
R W
/24
" x 34
"ACCES
S DOOR
DOUBLE S
TRAP TAPPING
SADDLES, 1/2" S
.S.
BALL V
ALVES
& P
LUGS
FOR P
RES
SURE GAUGES
12" MIN.
2" P
LUG
VALVE @
R.O.W (typ)
CONTR
OL
PANEL
PRIMARY
DISCONNEC
TMETER
RTU
℄ W
ET W
ELL
℄ WET WELL
VENT
GRAVITY S
EWER
-C90
0 PVC
4' D
IA W
ET W
ELL
6" TO O
UTSIDE
OF
SLAB O
N G
RADE
(typ)
NOTES:
1.ACCES
S ROAD S
HALL C
ONSIST O
F:•12" TH
ICK S
TABILIZED
SUBBASE
, STABILIZED
TO N
OT LESS
THAN 5
0 FB
V AND C
OMPACTED TO N
OT LESS
THAN 9
8%MAXIMUM D
ENSITY A
S DETER
MINED
BY
AASH
TO T-180
•8" THICK R
OCK B
ASE
, COMPACTED TO N
OT LESS
THAN 9
8% M
AXIMUM D
ENSITY A
S DETER
MINED
BY
AASH
TO T-180
•8" THICK C
ONCRETE w/FIBER
GLASS
MES
H R
EINFO
RCEM
ENT.
2.PUMP M
ANUFA
CTU
RER
SHALL P
ROVIDE TEMPORARY
4", 0-
60 psig, O
IL FILLED P
RES
SURE GAUGE FO
R S
TART UP.
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
TYPE "B" - TYPICAL LIFT STATION SITE PLAN LAYOUT 56JUNE 2014
48"
54" MIN.
18"
TOP ELEV.
STAINLESS
STEEL LIFT
CABLES
CPC M
ODEL 3
2RES
ILIENT MOUNT
SEALING S
YSTEM
OR EQUAL
2" S
CHED
. 80
PVC
P-TR
AP (HUBS
ON
BASIN &
VALVE
BOX
P-TR
AP FIELD
MOUNTED &
SUPPLIED
BY
CONTR
ACTO
R)
INV. ELEV.
HIGH W
ATER A
LARM ELEV.
LAG P
UMP O
N ELEV.
LEAD P
UMP O
N ELEV.
PUMPS
OFF ELEV.
BOTTOM ELEV.
NOTES :
PIPE MATERIAL SH
ALL B
ESC
H. 40
316 S
TAINLESS
STEEL
WITHIN W
ET W
ELL AND 2
" SC
H. 80
PVC
OUTSIDE WET W
ELL AND
INSIDE VA
LVE VA
ULT.
EMER
GEN
CY
PUMP-OUT
WITH 2
" MALE C
AMLOCK FITTING
100
YR. FLOOD ELEV.
(ENGINEER TO P
ROVIDE)
12"
MIN.
2" S
CHED
ULE 8
0 PVC
GATE/ B
ALL V
ALVE
DOUBLE S
TRAP TAPPING
SADDLES, 1/2" S
.S. BALL
VALVES
AND P
LUGS
FOR
PRES
SURE GAUGE
2" S
CHED
ULE 8
0 PVC
UNION TYP
E BALL C
HEC
K V
ALVE
MOUNT ELEC
TRICAL COMPONEN
TS O
N TWO (2)
4" A
LUMINUM P
OSTS
WITH S
TAINLESS
STEEL U
NISTR
UTS.
EMBED
IN 12" D
IA B
Y 4' D
EEP C
ONCRETE BASE
.
U.S. FO
UNDRY
APS-
150
ALUMINUM V
ALVE BOX
COVE
R W
/ 2
4" x 3
4"ACCES
S DOOR
ANTI-FLOATA
TION R
ING
LIFT-OUT RAIL
SYSTEM
CONCRETE FILLET W
ITH 1:1
RATIO FIELD INSTALLED
BY
CONTR
ACTO
R
FIBER
GLASS
BASIN
CONCRETE BALLAST
(FIELD INSTALLED
)
1" S
TAINLESS
GUIDE RAILS
2" S
CHED
ULE 4
0316
STAINLESS
STEEL PIPING
U.S. FO
UNDRY
BPS-
48ALUMINUM H
ATC
H C
OVE
RW/ 2
4" x 3
6" A
CCES
S DOOR
STAINLESS
STEEL
UPPER
GUIDE
BRACKETS
SERVICE
DISCONNEC
T
NEM
A 3
R S
TAINLESS
STEEL JUNCTION B
OX
WITH TER
MINALS
4" C
ONC. SLAB
4,00
0 PSI
CLASS
A w
/FIBER
MES
HREINFO
RCEM
ENT
THREE (3)
2" C
ONDUITS
THREE (3)
2" C
ONDUIT
HUBS
2" S
CHED
ULE 8
0 PVC
GATE/ B
ALL V
ALVE
FIBER
GLASS
VALVE BOX
CPC M
ODEL 3
2 RES
ILIENT
MOUNT SE
ALING S
YSTEM
OR EQUAL
CONCRETE FILLET S
LOPING TO
P-TR
AP FIELD INSTALLED
BY
CONTR
ACTO
R
12"
MIN.C
ONTR
OL PANEL
NEM
A 3
RSTAINLESS
STEEL
2" P
VC V
ENT
(SEE P
LAN V
IEW FOR
VENT LOCATION)
STAINLESS
STEEL
CABLE R
ACK
CU. FT. (B
Y EN
GINEER)
6" MIN.
6" MIN.
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
TYPE "B" - TYPICAL LIFT STATION (SECTION) 57JUNE 2014
PUMP DATA:
OPERATING CONDITIONS:
WET WELL:
ELECTRICAL:
MANUFACTURER,MOD. No. IMP. No. MOTOR, HP,RPM, PHASE, 60 HERTZVOLTS,
GPM AT
SIZED FOR MINIMUM PUMP CYCLE TIME OF 10 MINUTES AND A MAXIMUMOF 6 PUMP STARTS PER HOUR. WORKING DEPTH FT. WORKINGVOLUME GALS.
FEEDERS AND CONDUIT MAIN SWITCH POLES AMPS
TDH. % EFFICIENCY
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
TYPE "B" - REQUIRED LIFT STATION INFORMATION 58JUNE 2014
4'-5'
6"
3"
NOTES:
1. ELECTRIC METER AND PRIMARY DISCONNECT MOUNTED TO UNI-STRUT ON BACK SIDEOF PANEL.
2. ALL POWER AND CONTROLS LINES SHALL BE CONTINUOUS ( NO SPLICES ).
3. GROUND FAULT INTERRUPTER ON CONVENIENCE RECEPTACLE.
4. PANEL MOUNTED TO S/S UNI-STRUT BY WELDED TABS.
5. ALUMINUM POSTS IN CONCRETE SHALL BE COATED WITH BITUMASTIC.
6. CONTROL PANEL SHALL BE UL LISTED AS A UNIT.
7. ALL HARDWARE, NUTS & BOLTS, AND APPURTENANCES ABOVE GROUND SHALL BE316 STAINLESS STEEL.
8. TELEMETRY CONDUIT SHALL BE INSTALLED BY THE CONTRACTOR WITH SWEEP 90DEGREE BEND.
9. ALL CONDUIT NOT ENTERING WETWELL SHALL BE SCHEDULE 80 P.V.C.
10. PANEL MOUNTING SHALL ALLOW FOR UNRESTRICTED VIEW OF ALARM LIGHT.
11. MOUNT RTU PANEL TO ALLOW FOR UNRESTRICTED LINE-OF-SIGHT TO ANTENNAFROM ALL DIRECTIONS.
12. INSTALLATION IS NOT CLASSIFIED. SEALOFFS ARE USED SOLELY FOR THE PURPOSEOF LIMITING CORROSIVE CHEMICALS INTO THE ELECTRICAL EQUIPMENT.
4" ALUMINUM POST
4" FINISH GRADE
CONTROL PANEL
TO POWER SOURCETOWETWELL
ALARMLIGHT
TO RTU
J-BOX, S.S. OR ALUMINUM, WITHCROUSE HINDS OR APPROVED EQUAL.SEALOFFS ON TOP OF BOX TO LIMITCORROSION IN TO PANEL. SEALS ATSEALOFFS TO BE POURED EPOXY.
5/8" Ø S.S. EYEBOLT, THRUBOLTED WITH S.S. FENDER
WASHER & S.S. NYLOCK NUTON OPPOSITE SIDE OFALUMINUM POST FOR
SAFETY LANYARD SYSTEM
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
TYPE "B" - TYPICAL LIFT STATION CONTROL PANEL 59JUNE 2014
BACK VIEW OF CONTROL PANEL
NOTES:1. TWENTY INCHES ON RIGHT SIDE OF SUPPORT POST
IS RESERVED FOR RTU AND ACCESSORIES.
S.S. CONTROL PANELMOUNTED ON FRONT SIDE
20"
4' TO 5
'
6"
3" 3"
4"
PRIMARY DISCONNECT 316S.S
F.P. & L. CO.SERVICE METER
316 S.S. OR ALUM.
RTU (16"x16")
4" ALUM. POSTS
FINISH GRADE
1 - #6 IN3/4" CONDUIT
THERM-O-WELD
FEEDERS & CONDUITSCH. 80 PVC, TYP.UNLESS OTHERWISE
CALLED OUT.
COPPER WELL GROUND ROD(SEE ELECTRICAL SHEETS)
TO F.P. & L. CO.TRANSFORMER
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
TYPE "B" - LIFT STATION DETAILS (CONTROL CENTER) 60JUNE 2014
SPECIFICATIONS FOR DUPLEX(FDEP TYPE) CONTROL PANEL
EACH PANEL SHALL CONTROL 2, 3, 5 OR 7.5 HP, 230 VOLT, THREE PHASE (PREFERRED), 60 Hz PUMPS.230 VOLT, SINGLE PHASE w/VFD DRIVES WILL BE ACCEPTED ONLY WHERE THREE PHASE IS NOT AVAILABLE.
A NEUTRAL SHALL BE SUPPLIED TO THE PANEL FOR 120 VOLT CONTROL POWER.
PANEL ENCLOSURE
ENCLOSURE SHALL BE NEMA 3R, FABRICATED FROM 304 STAINLESS STEEL
OUTER DOOR SHALL HAVE HINGES AND MEANS FOR PAD LOCKING, INNER DEADFRONT DOOR SHALL BE5052-H32 ALLOY ALUMINUM. ALL MOUNTING HOLES SHALL BE DRILLED AND TAPPED, SELF TAPPING SCREWNOT ACCEPTABLE. ALL BOLTS, NUTS, LOCK WASHERS, AND MACHINE SCREWS SHALL BE STAINLESS STEEL.
THE FOLLOWING MAJOR COMPONENTS ARE REQUIRED:
1) MAIN BREAKER2) EMERGENCY BREAKER AND GENERATOR RECEPTACLE-RUSSELL STOLL JRS1044FR (FOR 100 AMP SERVICE)3) PUMP BREAKERS4) CONTROL CIRCUIT BREAKER5) ALTERNATOR6) HIGH LEVEL FLASHING ALARM LIGHT7) HIGH LEVEL HORN ALARM WITH SILENCE - WHEN SILENCE LIGHT STAYS ON8) LIGHTNING ARRESTOR9) SURGE SUPPRESOR10) PHASE/UNDER VOLTAGE MONITORING RELAY IF 3 PHASE, UNDER VOLTAGE MONITORING RELAY IF SINGLEPHASE11) NEMA RATED MOTOR STARTERS WITH OVERLOAD PROTECTION FOR ALL POWER LEGS12) ELAPSE TIME METERS13) YASKAWA VFD ON SINGLE PHASE SYSTEM.
TYPICAL SEQUENCE OF OPERATION:
ON RISE LEVEL:
LOWEST FLOAT WILL CLOSE CIRCUIT TO RELAY.LEAD PUMP ON FLOAT CLOSES TO BRING LEAD PUMP ON.IF LEAD DOES NOT RECEDE AND CONTINUES TO RISE, THE LAG FLOAT WILL CLOSE AND BRING ON THE LAGPUMP. FURTHER RISING OF LEVEL IN WETWELL WILL CLOSE 4TH FLOAT (HIGH LEVEL) AND ACTIVATE THE HIGHLEVEL ALARM LIGHT AND HORNS.
ON FALLING LEVEL:
ALL PUMPS WILL DE-ENERGIZE AT THE OPENING OF THE LOWEST (OFF) FLOAT
CONTROL CIRCUITRY WILL BE SUCH THAT NO FLOAT WILL DEPEND ON ANOTHER FLOAT FOR ITS CONTROLPOWER.
CONTROL PANEL SCHEMATICS, IN PLASTIC LAMINATE, IS TO BE AFFIXED TO THE INSIDE OF THE OUTER DOOR.
ALL WIRING SHALL BE NUMBERED.
IN THE EVENT THE PUMPS BEING FURNISHED REQUIRE SEAL FAILURE COMPONENTS AND INDICATION TOVALIDATE WARRANTY, THESE COMPONENTS SHALL BE FURNISHED AS REQUIRED.
ALL COMPONENT LABELS SHALL BE OF THE LASER PRINTED MYLAR PLASTIC LABELS.
A 24 HOUR EMERGENCY TELEPHONE CONTACT SHALL BE ATTACHED TO CONTROL PANEL COVER"FOR EMERGENCIES CONTACT MARTIN COUNTY UTILITIES AT TEL : 772-221-1442"
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.TYPE "B" - LIFT STATION CONTROL PANEL
SPECIFICATIONS 61JUNE 2014
ASBGFI
HOURSHOURS
HOA
ETM
RL
SFM
OL RESETSRESET
BREAKERS
RESET
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ENCLOSURE AND DEADFRONT LAYOUTTHREE PHASE
100AGENERATORRECEPTACLE
GRALARMLIGHT
ALARMHORN
3-POINTLATCH
24"
30"
AL
AH
MAIN ENCLOSURE : NEMA 3R RATED, FABRICATED FROM 304 STAINLESS STEEL(3 PT. LATCH ON OUTER DOOR).BACKPANEL : 12 GAUGE STEEL WITH WHITE ENAMEL.HINGED INNER DOOR : FABRICATED FROM .080 ALUMINUM.
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.TYPE 'B' - LIFT STATION CONTROL PANEL
ENCLOSURE AND DEADFRONT LAYOUT-THREE PHASE 62JUNE 2014
BACKPANEL LAYOUT - THREE PHASE
LOSS
MONITOR
TERMINALS F
F1
B100LP7JK
XFMR
CONTROLLIQUID LEVEL
SFMASRVO
LTAGE
SEQUEN
CE
AND
POS. 1
POS. 2
ALT
G
190-
270
VAC
1O 5
0/60
HZ
MIN
PMMAX
PDBG
MLB
MS1 MS2
OFF
ON
PCB2
OFF
ON
PCB1
OFF
ON
OFF
ON
OFF
ON
OFF
ON
MCB ECB
R1 R2 R3
R4 SL1 SL2
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.TYPE "B" - LIFT STATION CONTROL PANEL
BACKPANEL LAYOUT-THREE PHASE 62AJUNE 2014
100AGENERATORRECEPTACLE
36"
HOURSHOURS
GFI
ETM
HOA
SFM
RL
OFF
ON
OFF
ON
OFF
ON
OFF
ON
AH
AL
ENCLOSURE AND DEADFRONT LAYOUTSINGLE PHASE
GR
36"
BREAKERS
ALARMLIGHT
ALARMHORN
3-POINTLATCH
MAIN ENCLOSURE : NEMA 3R RATED, FABRICATED FROM 304 STAINLESS STEEL(3 PT. LATCH ON OUTER DOOR).BACKPANEL : 12 GAUGE STEEL WITH WHITE ENAMEL.HINGED INNER DOOR : FABRICATED FROM .080 ALUMINUM.
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.TYPE "B" - LIFT STATION CONTROL PANEL
ENCLOSURE & DEADFRONT LAYOUT-SINGLE PHASE 63JUNE 2014
VFD1 VFD2
MCB
ECB
OFF
ON
PCB2
OFF
ON
GFICB
TERMINALS F
OFF
ON
PCB1
OFF
ON
CCB
MLB
XFMR
F1
R1
CONTROLLIQUID LEVEL
SFM
POS. 1
POS. 2
ALT ASR VM
VOLTAGE SE
QUEN
CE AND
LOSS
MONITOR MAX
MIN
190-
270
VAC
1O 5
0/60
HZ
G
PDB
R2 R3
R4 SL1 SL2
BACKPANEL LAYOUT - SINGLE PHASE
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.TYPE "B" - LIFT STATION CONTROL PANEL
BACKPANEL LAYOUT-SINGLE PHASE 63AJUNE 2014
24V
120V
XFMR
ASR
ASR AH
ASBASR
AL
RS1
ETM
RL
O AH
PM
FS1T1 T2 FS2T3 T4
THERMAL #1
T10 T11
THERMAL #2
T13 T14
OFF LEAD
LAG
FS3T5 T6
T9
SFM187 1
56 4
2
R
R2
LINE#
MLB PDB
MECHANICALINTERLOCK
0101
0102
0103
0104
0105
0106
0107
0108
0109
0110
0111
0112
0113
0114
0115
0116
0117
0118
4-WIRE
230v,3Ø
L1
L2
L3
R3
R1R1
R2R2
FS4T7 T8R3
R1
O AH
F13A
250V
SL1
R4
HIGH LEVEL ALARM
SEAL PROBES
GFI
RF
G
*PCB1(50A)
*PCB2(50A)
0119
0120
0121
0122
0123
SEALFAIL #1
IL
T12
SFM287 1
56 4
2
R
SL2
SEALFAIL #2
IL
CCB15A
GFICB15A
OL
RS2
ETM
RLG
* MCB, ECB AND PCB'sSIZED PER N.E.C.
FS5 HIGH LEVEL ALARM (NON-POWERED)DIRECT CONNECT TO SCADA TERMINAL STRIP FORNON-POWERED ACTIVATION OF HIGH LEVEL ALARM
N
LA
GR
*ECB (100A)
*MCB (100A)
SS
PM
M1
RS2
M2
RS1
ALT2
1
7
5 6 8OL
RTUCB15A
RTU POWER 1 L1 N 2
MOTOROLAACE RTU
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.TYPE "B" - LIFT STATION CONTROL PANEL
WIRING DIAGRAM-THREE PHASE 64JUNE 2014
50.0 in/lb.45.0 in/lb.40.0 in/lb.
WIRE SIZE TORQUETERMINAL TORQUE35.0 in/lb.
AWG 6 - 4AWG 8AWG 14 - 10
AWG 3 - 2
GROUND LUGRECOMMENDED TIGHTENING TORQUE
SIZE 35.0 26.5 in/lb.SIZE 16.0 10.6 in/lb.SIZE 6.0 7.0 in/lb.SIZE 4.0 4.4 in/lb.
4.4 in/lb.SIZE 2.5
CONTROL TERMINALSRECOMMENDED TIGHTENING TORQUE
120VAC HOT RED 24VDC POSITIVE (+) ORANGE
WHITE
BLUE
YELLOW
120VAC NEUTRAL
24VAC HOT
POWER FROM OUTSIDE
BROWN
RED
BLACK
24VDC NEGATIVE (-)
12VDC POSITIVE (+)
12VDC NEGATIVE (-)
CONTROL TERMINAL IN MAIN PANEL
NEUTRAL TERMINAL AND GROUND LUGS IN MAIN PANEL
FIELD WIRING (EXTERNAL TO CONTROL PANEL)
PANEL WIRING
SEAL ALL CONDUITS ENTERING CONTROL PANEL
CONTROL PANEL IS UL508A LABELED
INSTALL IN ACCORDANCE WITH ARTICAL 504 OF THE N.E.C.
MINIMUM #16 AWG WIRE AT 600V
TERMINAL IN JUNCTION BOX
4.
8.
9.
5.
6.
7.
1.
2.
3.
PANEL SOURCE &RTU CONNECTIONS
BLUE - TYPICAL OF ALL
17 18 1920 21222324252627282930 3132333435363738
PUMP 1RUNNING
PUMP 2RUNNING
PUMP 1SEALLEAK
PUMP 2SEALLEAK
PUMPSOFFLEVEL
LEADSTARTLEVEL
LAGSTARTLEVEL
HIGHLEVELALARMNON
POWERED
POWER/PHASELOSS
PUMP 1HOAAUTO
PUMP 2HOAAUTO
RS1 RS2 SL1 SL2 FS5 R4 R1 R2 VM
TERMINAL STRIP IN CONTROL PANEL FOR SCADAOH A OH A
TORQUE TABLES
CONTROL WIRE COLOR CODE
NOTES:
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.TYPE 'B' - LIFT STATION CONTROL PANEL
WIRING DIAGRAM-THREE PHASE 64AJUNE 2014
ALARM
8
FS4
OFFFS1
1 2
FS3LAG
LEADFS2
543 76
THER
MAL SEN
SOR
MOISTU
RE SEN
SOR
THER
MAL SEN
SOR
THER
MAL SEN
SOR
MOISTU
RE SEN
SOR
PUMP CORD
M1 M2
119 10 1213
THER
MAL SEN
SOR
14
SMALL DIAMETER
TERMINAL STRIP IN JUNCTION BOX & CONTROL PANEL
NOTES:
* PUMP MANUFACTURER SHALLSIZE THESE BREAKERS. SUBMITSIZING CONFIRMATION WITHPANEL SHOP DRAWINGS.
** CONTROL POWER TRANSFORMERTO BE SIZED FOR ALL LOADSOPERATING SIMULTANEOUSLYPLUS ONE SIZE LARGER.
SQ.D, 6671-SDSA3650
SQ.D, 6671-SDSA3650BUSS, GDB 3A
SQ.D, 8501-KU13-V14
HUBBEL GF151L
INGRAM, SSF-150W
EATON, C0100E1B OR SQ. D, 9070T SERIES **
SQ.D, QOU115
SQ.D, 8501-KU13-V20
SSAC, LLC54BA
EATON, C22-L-XR-120 & M22-XLH-RSQ.D, 9001-SKP38-G9
SQ.D, 9001-SKS43BH13
SQ.D, 9001-SKR1BH5
RAB VAPORPROOF VP100DGFEDERAL VIBRATONE, 350-100V, SERIES B1
DIVERSIFIED, ARB-120-AEAEATON, 6-T-3H-508RPM-406
DIVERSIFIED, SLA-230-ASA
RUSSELL STOLL, JRSB1044FR
SQ.D, 8536-SCO3-V02S
SQ.D, QOU115
SQ.D, QOU330 *SQ.D, QOU360 *SQ.D, QOU360 *HOFFMAN, 30Hx24Wx12D-3R
BILL OF MATERIALS
SURGE SUPPRESSOR
LIGHTNING ARRESTOR
CONTROL RELAY 24V
GFI RECEPTACLE
TRANSFORMER 120V/24V
ALARM SILENCE RELAY 120V
SEAL FAIL MODULE
INDICATING LIGHT
HAND OFF AUTO SWITCH
ALARM SILENCE BUTTON
ELAPSED TIME METER
GENERATOR RECEPTACLE
RUN LIGHT
FUSE 3A 250VFLASHER
ALARM LIGHTALARM HORN
ALTERNATOR
PHASE MONITORGFI CIRCUIT BREAKER
MOTOR STARTER
CONTROL CIRCUIT BREAKER
PUMP CIRCUIT BREAKEREMERGENCY CIRCUIT BREAKERMAIN CIRCUIT BREAKERENCLOSURE, 304SS, NEMA 3R/12
4
1
11
1
2
21
2
1
2
1
1
1
1
12
1
1
1
2
2
1
1
11
MANUFACTURER, PART#QTY. ABBR. DESCRIPTION
WAGO 280 SERIES 22 CONTROL TERMINALS
GFICB
PCB1,2
CCB
ENCMCBECB
2 SL1,2 SEAL FAIL RELAY 120V SQ.D, 8501-KU13-V20
MS1,2
XFMR
GR
PM
ETMALT
AL
F
AHASB
HOA
RLILGFI
SFM1,2
ASR
R1-4
F1LA
SS
SQ.D, B-28OVERLOAD HEATER6 OL
CUSTOM EQUIPMENT, 10X24X61 JUNCTION BOX, 304SS, NEMA 4XJ-BOXMARATHON, 13335552 PUMP TERMINALSP-TER
1 SC SURGE CAPACITOR
1 RTU CIRCUIT BREAKER SQ.D, QOU115RTUCB
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.TYPE "B" - LIFT STATION CONTROL PANEL
BILL OF MATERIALS-THREE PHASE 64BJUNE 2014
24V
120V
XFMR
RG
ASR
ASR AH
ASBASR
AL
ALT2
1
RS1
ETM
RL
O AH
VM
FS1T1 T2 FS2T3 T4
THERMAL #1
T10 T11
THERMAL #2
T13 T14
OFF LEAD
LAG
FS3T5 T6
T9
SFM187 1
56 4
2
R
LINE#
M1
VFD1
MLB PDB
SS
MECHANICALINTERLOCK
0101
0102
0103
0104
0105
0106
0107
0108
0109
0110
0111
0112
0113
0114
0115
0116
0117
0118
3-WIRE
230v,1Ø
L1
L2
N
VM
LA
R3
R1R1
R2R2
FS4T7 T8R3
O AH
F13A
250V
SL1
R4
HIGH LEVEL ALARM
SEAL PROBES
GFI
RF
G
*PCB1(50A)
*PCB2(50A)
T1 T2 T3
L2L1
RS1SP
S1+1+2
M2
VFD2
T1 T2 T3
L2L1SP
S1+1+2
RS2
DC
REA
CTO
R
0119
0120
0121
0122
0123
SEALFAIL #1
IL
T12
SFM287 1
56 4
2
R
SL2
SEALFAIL #2
IL
CCB15A
GFICB15A
VFD1MC MB
VFD1M1 M2
RS2
ETM
RLG
VFD2MC MB
VFD2M1 M2
*MCB (100A)
*ECB (100A)
* MCB, ECB AND PCB'sSIZED PER N.E.C.
FS5 HIGH LEVEL ALARM (NON-POWERED)DIRECT CONNECT TO SCADA TERMINAL STRIP FORNON-POWERED ACTIVATION OF HIGH LEVEL ALARM
R2
R1
7
5 6 8
RTUCB15A
RTU POWER 1 L1 N 2
MOTOROLAACE RTU
DC
REA
CTO
R
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.TYPE "B" - LIFT STATION CONTROL PANEL
WIRING DIAGRAM-SINGLE PHASE 65JUNE 2014
50.0 in/lb.45.0 in/lb.40.0 in/lb.
WIRE SIZE TORQUETERMINAL TORQUE35.0 in/lb.
AWG 6 - 4AWG 8AWG 14 - 10
AWG 3 - 2
GROUND LUGRECOMMENDED TIGHTENING TORQUE
SIZE 35.0 26.5 in/lb.SIZE 16.0 10.6 in/lb.SIZE 6.0 7.0 in/lb.SIZE 4.0 4.4 in/lb.
4.4 in/lb.SIZE 2.5
CONTROL TERMINALSRECOMMENDED TIGHTENING TORQUE
120VAC HOT RED 24VDC POSITIVE (+) ORANGE
WHITE
BLUE
YELLOW
120VAC NEUTRAL
24VAC HOT
POWER FROM OUTSIDE
BROWN
RED
BLACK
24VDC NEGATIVE (-)
12VDC POSITIVE (+)
12VDC NEGATIVE (-)
CONTROL TERMINAL IN MAIN PANEL
NEUTRAL TERMINAL AND GROUND LUGS IN MAIN PANEL
FIELD WIRING (EXTERNAL TO CONTROL PANEL)
PANEL WIRING
SEAL ALL CONDUITS ENTERING CONTROL PANEL
CONTROL PANEL IS UL508A LABELED
INSTALL IN ACCORDANCE WITH ARTICAL 504 OF THE N.E.C.
MINIMUM #16 AWG WIRE AT 600V
TERMINAL IN JUNCTION BOX
4.
8.
9.
5.
6.
7.
1.
2.
3.
PANEL SOURCE &RTU CONNECTIONS
BLUE - TYPICAL OF ALL
17 18 1920 21222324252627282930 3132333435363738
PUMP 1RUNNING
PUMP 2RUNNING
PUMP 1SEALLEAK
PUMP 2SEALLEAK
PUMPSOFFLEVEL
LEADSTARTLEVEL
LAGSTARTLEVEL
HIGHLEVELALARMNON
POWERED
POWER/PHASELOSS
PUMP 1HOAAUTO
PUMP 2HOAAUTO
RS1 RS2 SL1 SL2 FS5 R4 R1 R2 VM
TERMINAL STRIP IN CONTROL PANEL FOR SCADAOH A OH A
TORQUE TABLES
CONTROL WIRE COLOR CODE
NOTES:
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.TYPE "B" - LIFT STATION CONTROL PANEL
WIRING DIAGRAM-SINGLE PHASE 65AJUNE 2014
THER
MAL SEN
SOR
OFFFS1
PUMP CORD
M1 M2
ALARMFS4
LAGFS3
LEADFS2
THER
MAL SEN
SOR
MOISTU
RE SEN
SOR
THER
MAL SEN
SOR
THER
MAL SEN
SOR
MOISTU
RE SEN
SOR
CUSTOM EQUIPMENT, 10X24X6MARATHON, 1333555
DIVERSIFIED, ARB-120-AEA
DIVERSIFIED, UOA-240-ALA Check this
RUSSELL STOLL, JRSB1044FR
SSAC, LLC54BA
FEDERAL VIBRATONE, 350-100V, SERIES B1
SQ.D, 6671-SDSA1175
SQ.D, 6671-SDSA1175
SQ.D, 9001-SKS43BH13
MANUFACTURER, PART#
21 JUNCTION BOX, 304SS, NEMA 4X
START RELAY MARS, 19007
ABBR.
2
1
1
2
1
4
1
2
1
22
11
2
1
1
1
21
1
1
1
2
1
2
111
QTY.
SEAL FAIL MODULE
GFI RECEPTACLE
ALARM SILENCE RELAY 120V
CONTROL RELAYS 24V
INDICATING LIGHT
SURGE SUPPRESSOR
LIGHTNING ARRESTOR
PUMP TERMINALS
FUSE 3A 250V
RUN LIGHT, GREEN
VOLTAGE MONITOR
GENERATOR RECEPTACLE
ALARM SILENCE BUTTON
ELAPSED TIME METER
TRANSFORMER 120V/24V
ALTERNATOR
ALARM HORNALARM LIGHTHAND OFF AUTO SWITCH
FLASHERBUSS, GDB 3A
EATON, C22-L-XR-120 & M22-XLH-RSQ.D, 9001-SKP38-G9
HUBBELL GF15IL
SQ.D, 8501-KU13-V20
A.B. 700-HC14A24
EATON, C0100E1B or SQ.D. 9070T Series **
INGRAM, SSF-150W
RAB VAPORPROOF VP100DG
EATON, 6-T-3H-508RPM-406
SQ.D, 9001-SKR1BH5
BILL OF MATERIALS
EMERGENCY CIRCUIT BREAKER
CONTROL CIRCUIT BREAKER
PUMP CIRCUIT BREAKER
GFI CIRCUIT BREAKER
VARIABLE FREQUENCY DRIVES
MAIN CIRCUIT BREAKER
DESCRIPTION
DC BUS REACTOR (OPEN TYPE)
ENCLOSURE, 304 SS, NEMA3R/12 HOFFMAN, 36x36x12-3RSQ.D, QOU250 *SQ.D, QOU250 *SQ.D, QOU225 *
SQ.D, QOU115SQ.D, QOU115
YASKAWA CIMR-PW2A0056FAAYASKAWA URX000059
TERMINAL STRIP IN JUNCTION BOX & CONTROL PANEL
2 SEAL FAIL RELAY 120V SQ.D, 8501-KU13-V20
81 2 543 76 119 10 121314
GFICB
PCB1,2
LA
SS
R1-4
F1
GFI
SFM1,2
ASR
RLIL
AHASB
HOAAL
F
VM
ETMALT
XFMR
GR
VFD1,2
CCB
ENCMCBECB
P-TERJ-BOXSR
SL1,2
1 SC SURGE CAPACITOR REFER TO ELECTRICAL DWGS.WAGO 280 SERIES 22 CONTROL TERMINALS
NOTES:
* PUMP MANUFACTURER SHALLSIZE THESE BREAKERS. SUBMITSIZING CONFIRMATION WITHPANEL SHOP DRAWINGS.
** CONTROL POWER TRANSFORMERTO BE SIZED FOR ALL LOADSOPERATING SIMULTANEOUSLYPLUS ONE SIZE LARGER.
1 RTU CIRCUIT BREAKER SQ.D, QOU115RTUCB
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.TYPE "B" - LIFT STATION CONTROL PANEL
BILL OF MATERIALS-SINGLE PHASE 65BJUNE 2014
THE PUMP SHALL HAVE AN INTEGRALLY BUILT IN GRINDER UNIT AND SUBMERSIBLE TYPEMOTOR. THE PUMP SHALL BE SUSPENDED IN THE BASIN BY TWO (2) 1" GUIDE RAILS ANDQUICK DISCONNECT LIFT OUT MOUNTING ASSEMBLY. SOLIDS SHALL BE FED IN AN UPFLOWDIRECTION TO THE GRINDER MECHANISM WITH NO OBSTRUCTIONS BELOW THE GRINDER INLET.
THE GRINDER UNIT SHALL BE CAPABLE OF CUTTING SOLID MATERIAL FOUND IN NORMALDOMESTIC SEWAGE, INCLUDING REASONABLE AMOUNTS OF FOREIGN OBJECTS, SUCH AS WOODPLASTIC, GLASS, RUBBER, SANITARY NAPKINS, DISPOSABLE DIAPERS AND PANTY HOSE INTO AFINE SLURRY THAT WILL PASS FREELY THROUGH THE PUMP, SERVICE LINE AND FORCE MAIN.
MOTORTHE PUMP MOTOR SHALL BE OF THE SUBMERSIBLE TYPE RATED FOR 2 - 7.5HORSEPOWER AT 3450 RPM. MOTOR SHALL BE THREE PHASE (PREFERRED) ORSINGLE PHASE, 230 VOLT, 60 HERTZ (ONLY WHERE THREE PHASE POWER IS NOTAVAILABLE). SINGLE PHASE MOTORS SHALL BE OF THE INVERTER DUTY TYPE.
THE STATOR WINDING SHALL BE THE OPEN TYPE WITH CLASS F INSULATION RATED FOR 105° CMAXIMUM OPERATING TEMPERATURE. THE WINDING HOUSING WILL BE FILLED WITH CLEAN DIELECTRICOIL THAT WILL LUBRICATE BEARINGS, SEALS AND TRANSFER HEAT FROM THE WINDINGS TO THEOUTER SHELL. THE MOTOR STATOR IS TO BE PRESSED INTO THE MOTOR HOUSING FOR OPTIMUMCONCENTRICITY AND ALIGNMENT, AND MAXIMUM HEAT TRANSFER. THE MOTOR SHALL BE CAPABLEOF OPERATING OVER FULL RANGE OF PERFORMANCE CURVE WITHOUT OVERLOADING MOTOR ANDCAUSING ANY OBJECTIONAL NOISE OR VIBRATION.
THE MOTOR SHALL HAVE TWO BEARINGS TO SUPPORT THE ROTOR; AN UPPER BALL BEARING TOACCOMMODATE THRUST LOADS AND A LOWER BALL BEARING TO TAKE RADIAL LOADS. BALLBEARINGS SHALL BE DESIGNED FOR A LB-10 LIFE (50,000 HOURS).
A HEAT SENSOR THERMOSTAT AND OVERLOAD SHALL BE ATTACHED TO THE TOP END OF THE MOTORWINDINGS AND SHALL STOP THE MOTOR IF THE MOTOR WINDING TEMPERATURE REACHES 200° F.THE HIGH TEMPERATURE SHUTOFF WILL CAUSE THE PUMP TO CEASE OPERATION, SHOULD ACONTROL FAILURE CAUSE THE PUMP TO RUN IN A DRY WET WELL. THE THERMOSTAT SHALL RESETAUTOMATICALLY WHEN THE MOTOR COOLS TO A SAFE OPERATING TEMPERATURE.
TYPE "B" PACKAGED FIBERGLASS PUMP LIFT STATIONS,PACKAGED FIBERGLASS VALVE BOXES, AND
STANDARD CONTROL PANELS
FURNISH AND INSTALL A COMPLETE PACKAGED TYPE "B" GRINDER PUMP STATION ASDESCRIBED BELOW:
SPECIFICATIONSDESIGN CONDITIONS
MODEL
VOLT
DISCHARGE
GPM TDH
IMPELLER
PHASE
H.P.
PUMP: MILWAUKEE, MYERS, HYDROMATIC, FLYGT, BARNES - GRINDER PUMP 2.0 - 7.5 H.P.
CONTINUED ON 66A
THE MOTOR SHALL BE PROTECTED BY TWO (2) ROTARY SHAFT SEALS MOUNTED IN TANDEM WITHAN OIL FILLED CHAMBER SEPARATING THE SEALS. THE SEALS SHALL HAVE CARBON / CERAMIC /SILICON SEAL FACES DIAMOND LAPPED TO A TOLERANCE OF ONE LIGHT BAND. METAL PARTS ANDSPRINGS FOR SEALS SHALL BE STAINLESS STEEL. AN ELECTRICAL SENSING PROBE SHALL BEMOUNTED IN THE SEAL CHAMBER TO DETECT ANY WATER LEAKAGE PAST THE LOWER SEAL.
SEAL CHAMBER
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
TYPE "B"-LIFT STATION CONTROL PANEL NOTES 66JUNE 2014
THE GRINDER ASSEMBLY SHALL CONSIST OF A ROTATING RADIAL CUTTER AND A STATIONARYSHREDDING RING, AND SHALL BE MOUNTED DIRECTLY BELOW THE VOLUTE PASSAGE. THEROTATING CUTTER SHALL BE THREADED ONTO THE STAINLESS STEEL SHAFT AND SHALL BELOCKED WITH A SCREW AND WASHER. THE STATIONARY SHREDDING RING SHALL BE PRESSEDONTO AN IRON HOLDING FLANGE FOR EASY REMOVAL. THE FLANGE SHALL BE PROVIDED WITHTAPPED BACK-OFF HOLES SO THAT SCREWS CAN BE USED TO PUSH THE SHREDDING RINGFROM THE HOUSING. BOTH THE RADIAL CUTTER AND SHREDDING RING SHALL BE REMOVABLEFROM THE OUTSIDE WITHOUT DISMANTLING PUMP. GRINDER ASSEMBLY SHALL BE OF SUCHCONSTRUCTION THAT NO CLEARANCE ADJUSTMENTS ARE REQUIRED WHEN ASSEMBLING. ALLGRINDING OF SOLIDS SHALL BE FROM THE ACTION OF THE RADIAL CUTTER AGAINST THESHREDDING RING. THE RADIAL CUTTER AND SHREDDING RING SHALL BE OF #440 STAINLESSSTEEL HARDENED TO 58-60 ROCKWELL C.
THE PUMP IMPELLER SHALL BE OF THE RECESSED TYPE TO PROVIDE AN OPEN UNOBSTRUCTEDPASSAGE THROUGH THE VOLUTE FOR THE GROUND SOLIDS. THE IMPELLER SHALL BECONSTRUCTED OF CAST IRON AND SHALL HAVE PUMP OUT VANES ON THE BACK SIDE OF THEIMPELLER TO KEEP SOLIDS FROM LOWER SEAL AND REDUCE PRESSURE AT THE SEAL FACES.IMPELLER SHALL BE THREADED ONTO THE STAINLESS STEEL SHAFT.
ALL IRON CASTING SHALL BE OF HIGH TENSILE CAST IRON AND SHALL BE PROPERLY CLEANED,PRE-TREATED WITH CHROMIC RINSE, AND PAINTED WITH A HIGH QUALITY ENAMEL PAINT. ALLPUMP COMPONENTS THAT ARE NOT CAST IRON OR STAINLESS STEEL SHALL BE GALVANIZED ORPAINTED WITH BAKED-ON EPOXY. ALL FASTENERS SHALL BE #302 STAINLESS STEEL.
SHALL BE A FILAMENT WOUND FIBERGLASS BASIN USING A COMMERCIAL GRADE OF GLASS FIBERHAVING A COUPLING AGENT WHICH WILL PROVIDE A SUITABLE BOND BETWEEN THE GLASSREINFORCEMENT AND THE RESIN. THE LAMINATE SHALL CONSIST OF AN INNER SURFACE, ANINTERIOR LAYER, AND AN EXTERIOR LAYER OF LAMINATE BODY. THE INNER SURFACE SHALL BEFREE OF CRACKS AND CRAZING WITH A SMOOTH FINISH. SOME WAVINESS IS PERMISSIBLE ASLONG AS THE SURFACE IS SMOOTH AND FREE OF PITS. BETWEEN 0.010 AND 0.020 INCHESOF RESIN-RICH SURFACE SHALL BE PROVIDED. THE BASIN SHALL BE PROVIDED WITH ANANTI-FLOATATION RING TO PREVENT RISING.
SHALL BE CPC MODEL VB3242 FIBERGLASS VALVE BOX WITH U.S. FOUNDRY APS-150ALUMINUM VALVE BOX COVER. VALVE BOX SHALL BE PRE-PLUMBED USING ALL SCHEDULE 80PVC PIPING AND FITTINGS, AND SHALL INCLUDE TWO (2), 2" SCHEDULE 80 PVC BALL CHECKVALVES, AND THREE (3), 2" SCHEDULE 80 PVC GATE VALVES. (ONE (1) 2" GATE VALVE ISSUPPLIED AS AN EMERGENCY PUMP-OUT). PVC PIPING IN VALVE BOX, AND WET WELL SHALLBE CONNECTED AND HELD IN PLACE BY CPC MODEL 32 RESILIENT MOUNT SEALING SYSTEM TOCOMPENSATE FOR POSSIBLE UNEVEN SETTLING OF BASIN OR VALVE BOX. SYSTEM SHALL BEPRESSURE TESTED AT 150 P.S.I. PRIOR TO SHIPMENT.
SHALL BE FABRICATED FROM 1/4" ALUMINUM DIAMOND PLATE AND BUILT TO WITHSTAND A LOADOF 150 LB. P.S.F. AND SHALL BE MANUFACTURED BY U.S. FOUNDRY, HALLIDAY, OR EQUAL.STAINLESS STEEL BOLTS, NUTS AND HINGES - LOCKING STAPLE.
SHALL BE ANCHOR SCIENTIFIC S30N0 ROTO-FLOATS OR EQUAL.
-- STAINLESS STEEL UPPER GUIDE BRACKETS -- STAINLESS STEEL GUIDE RAILS -- STAINLESS STEEL CABLE RACK -- STAINLESS STEEL LIFT CABLES
CONCRETE IS REQUIRED TO PREVENT FLOATATION OF THE FIBERGLASS BASIN. THE ENGINEEROF RECORD SHALL PROVIDE SIGNED AND SEALED BUOYANCY CALCULATIONS TO UTILITYDEPARTMENT.
ANTI-FLOATATION
ACCESSORIES
FLOATS
ALUMINUM HATCH COVERS
VALVE BOX
WET WELL
PUMP & MOTOR CASTINGS
PUMP IMPELLER
GRINDER ASSEMBLY & CONSTRUCTION
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.
TYPE "B"-LIFT STATION CONTROL PANEL NOTES 66AJUNE 2014
TOP VIEW
SECTION
8"
(TYP.)22"
NOTES:1. GREASE TRAPS (SEPTIC TANKS) SHALL BE MANUFACTURED BY FLORIDA SEPTIC INC., SEBRING SEPTIC, AVERETT SEPTIC, OR APPROVED
EQUAL. STATEMENT: "THIS CONCRETE STRUCTURE MEETS OR EXCEEDS ALL THE REQUIREMENTS FOR GREASE INTERCEPTORS/SEPTICTANKS AS REQUIRED BY THE FLORIDA ADMINISTRATIVE CODE (F.A.C.), CHAPTERS 64E-6.013". TANK MUST BE EQUAL TO OR GREATERTHAN 750 GALLONS AS REQUIRED BY THE F.A.C.. SIZING CALCULATIONS, (3 COPIES MINIMUM), SHALL THEN BE SIGNED AND SEALEDBY THE ENGINEER-OF-RECORD AND FORWARDED TO THE DEPARTMENT FOR APPROVAL. NOTE THAT GENERATION RATES FOR ORDINARYRESTAURANTS SHALL BE 16 GPD PER SEAT PER MARTIN COUNTY UTILITY DEPARTMENTAL POLICY.
2. LID TYPES:A) 4" REGULAR LIDB) 8" TRAFFIC BEARING LID
3. ALL INTERNAL COMPONENTS WILL BE CONSTRUCTED BY GREASE TRAP INSTALLER.4. TANK INSPECTIONS WILL OCCUR WITH TANK ABOVE GROUND.5. BAFFLE SHALL BE INSTALLED 1/2 (ONE HALF) TO 2/3 (TWO THIRDS) 'D'.6. MEETS H-20 LOAD REQUIREMENTS.
U.S. FOUNDRY 420-CRING AND COVER OR
APPROVED EQUAL
INLET OUTLET
8"-18" MIN.
D
8" MIN.
6" MIN.
6" MIN.
6" MIN.
SOLIDCONCRETE
BRING CLEAN OUT TOGRADE (TYPICAL BOTHINFLUENT AND EFFLUENTLINES)
CONCRETECOLLAR AROUNDCLEAN OUT
WORDS "GREASE TRAP" OR"GREASE INTERCEPTOR"TO BE CAST IN COVER
4" MIN.INLET
OPENING
4" MIN. OUTLET OPENING(FILL OPENING AROUNDPIPE WATER TIGHT WITHWATER-PROOF GROUT -TYPICAL)
STAINLESS STEEL BRACES,BRACKETS, NUTS ANDBOLTS, OR PVCCOMPANION FLANGEw/TEE AND S.S. BOLTS(TYPICAL)
LID (SEENOTE 2) WATER
LEVEL
BAFFLE
1/2 to 2/3 D 6" MIN.
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.DOUBLE-COMPARTMENT GREASE TRAP
AND OIL SEPARATOR 67JUNE 2014
NOTES:
SUPPORT PIERS
METER
1' S
POOL PIECE
2'-0" TEE. R
ESTR
AIN M
IN.
MOTO
R A
CTU
ATED
TO P
OND
BASE
BEN
D
TWO FULL P
IPE
LENGTH
S DOWNSTREA
M
TEE. R
ESTR
AIN M
IN.
LENGTH
S UPSTREA
MTW
O FULL P
IPE
FLOW C
ONTR
OL VA
LVE
XX
XX
FLOW FOR M
ETER
ACCURACY
SPOOL PIECE
SIZE
D FOR A
DEQ
UATE
FENCE
PG
PIT
FLANGED
MANUAL
BUTTER
FLY
VALVE
W/ G
EAR B
OX
&HANDWHEE
L
PRES
SURE
GAUGE
w/PRES
S.INDICATO
R TRANSM
ITTER
ECCEN
TRIC R
EDUCER
(TYP.)
(IF NEC
ESSA
RY)
2" A
UTO
MATIC A
IR A
ND V
ACUUM V
ALVE
ASS
EMBLY W
/ C
ORP. STOP DBL. S
TRAP
SADDLE P
ER A
PPROVE
D P
RODUCT LIST
1.ALL FLANGED
PIPE AND FITTINGS
SHALL B
E DUCTILE IRON, CEM
ENT LINED
.
2.MEC
HANICAL JOINT FITTINGS
REQ
UIRED
BELOW G
RADE AND FLANGED
FITTINGS
FOR A
BOVE
GRADE USE
.
3.ALL A
BOVE
GRADE MATERIAL SH
ALL B
E COATED W
ITH P
ANTO
NE PURPLE 5
22 P
AINT PER
THE SP
ECIFICATIONS.
4.CONCRETE SU
PPORTS S
HALL B
E INSTALLED
AS
SHOWN. A
LL C
ONCRETE SH
ALL B
E 30
00 P
SI.
5.ALL A
BOVE
GROUND B
OLTING S
HALL B
E STAINLESS
STEEL.
6.PIPE SH
ALL B
E SIZE
D B
Y EN
GINEER.
7.CONCRETE MONOLITH
IC S
LAB P
OURED
TO 6
" OUTSIDE OF FENCING.
RSG
V (B
YPASS
VALVE)
w/ E
XTEN
SION &
BOX
MEC
HANICAL JO
INTS TO
BE
RES
TRAINED
(typ)
6" (typ)
6" (typ)
BULK U
SER R
ECLAIMED
WATER S
YSTEM
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.RECLAIMED WATER METERING FACILITY
(BULK USER) 68JUNE 2014
CONTROL PANEL
FPL METER
PRIMARY DISCONNECT
3'-6"
3'
12'
22'
4'-0"TO
POND
XX
XX
XX
XX
XXXX
XX
XX
XX
XX
X X
2" AUTOMATIC AIR/VACUUMVALVE ASSEMBLY W/ CORP.STOP DBL. STRAP SADDLE
PER APPROVED PRODUCT LIST
ECCENTRIC REDUCER(TYP.-IF NECESSARY)
6" THICK CONCRETEPAD WITH 6X6 WWF
POURED TO 6" OUTSIDEOF FENCING (typ)
6" (typ)
MOTOR ACTUATED FLOWCONTROL VALVE
FLOW METER
PRESSURE GAUGE w/PRESSURE INDICATOR
TRANSMITTER
MJ RSGV (BYPASS VALVE)W/ EXTENSION & BOX
(LID MARKED "RECLAIMED")AND CONC. SLAB
FLANGED MANUALBUTTERFLY VALVE
W/ GEAR BOX& HANDWHEEL
6' HIGH CHAIN LINK FENCE(SEE FENCE DETAILS, DWG # 55& SPECIFICATIONS, SECTION VII) 6' WIDE GATE
BULK USER RECLAIMED WATER SYSTEM
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.RECLAIMED WATER METERING FACILITY PLAN
(BULK USER) 69JUNE 2014
POSITIONER
CONTROL VALVEMETERFLOW
OUTPUTPULSE
CONVERTER
POSITION SIGNAL
PERIOD FLOW TOTAL
LOSS OF POWER
VALVE POSITION
VALVE CLOSE END OF CYCLE
HIGH LEVEL
FLOW
CONTROLLERSCADA P.L.C.
AND TIMERESET ALLOCATION
MODBUS SIGNAL
AUTOOPEN/CLOSE
VALVE
FIELD
PANE
L
LEVEL SENSOR
VALVE
RECEIVING LAKE
LEVEL READOUT
FIELD
COM
PONE
NTS
4-20mA
AT C
ENTR
AL S
TATION
FULLY OPEN/FULLY CLOSED(4-20 mA)
PRESSURE TRANSMITTER
MANUALSTAFFGAUGE
BULK USER RECLAIMED WATER SYSTEM
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.RECLAIMED WATER METERING FACILITY
CONTROL SCHEMATIC (BULK USER) 70JUNE 2014
20' x 3/4" GROUND ROD
RECLAIMED WATERMETERINGPANEL
PRESS.TRANSMITTER
FLOWMETER
CONTROL VALVECONTROLS
INDICATORPOSITION
CONTROL VALVE
3/4" PVC CONDUIT
3/4" PVC, 2#18SHLD, 1#12G.
3/4" PVC, 2#18 SHLD, 1#12G.
3/4" PVC, 6#14
1" LEVEL TRANSMITTER
1" PVC, 3#10 TOFPL SERVICE
CONDUIT SCHEMATIC
CONTROL PANEL DEADFRONT LAYOUT (BULK USER)
FLOW
OPEN CLOSE
LEVEL
VALVE
SEE INSTRUCTIONS
TEST TEST
RESET R
ESET
TEST MONTHLY
BULK U
SER R
ECLAIMED
WATER S
YSTEM
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.RECLAIMED WATER METERING FACILITY
CONTROL PANEL (BULK USERS) 71JUNE 2014
NOTES:
5'-6" +
/- 6
"
8"
POWER SOURCE
#4 @ 12" O.C.E.W.
FINISH GRADE
OR STAINLESS STEEL3" CONCRETE, ALUMINUM,
CONTROL PANEL
6"
6"
POSTS
1.
2.
3.
4.5.
ELECTRIC METER AND PRIMARY DISCONNECT MOUNTED TO UNI-STRUT ON BACKSIDE OF PANEL.ALL POWER AND CONTROLS LINES SHALL BE CONTINUOUS ( NO SPLICES ).
GROUND FAULT INTERRUPTER ON CONVENIENCE RECEPTACLE.
PANEL MOUNTED TO S/S UNI-STRUT BY WELDED TABS.
CONTROL PANEL SHALL BE UL LISTED AS A UNIT.6.
7. ALL HARDWARE, NUTS & BOLTS, AND APPURTENANCES ABOVE GROUND SHALLBE 316 STAINLESS STEEL.
ALUMINUM POSTS IN CONCRETE SHALL BE COATED WITH BITUMASTIC.
3/4" CONDUIT FORPRESS. TRANSMITTER
BULK USER RECLAIMED WATER SYSTEM
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.RECLAIMED WATER METERING FACILITY
CONTROL PANEL DETAILS (BULK USER) 72JUNE 2014
BACK VIEW OF CONTROL PANEL
TRANSFORMERTO F.P. & L. CO.
FIN. GRADE
FEEDERS & CONDUIT
OR S.S. POSTS3" CONC., ALUM.,
SERVICE METERF.P. & L. CO.
3/4" X 8'-0" LONGCOPPER CLAD GROUND ROD
1 - #6 IN 3/4" CONDUIT
S.S. CONTROL PANEL
SURGE ARRESTOR
THERM-O-WELD
LIGHTNING ARRESTER
PRIMARY DISCONNECT
S.S. OR ALUM.
BULK USER RECLAIMED WATER SYSTEM
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.RECLAIMED WATER METERING FACILITY
CONTROL PANEL - BACK VIEW (BULK USER) 73JUNE 2014
12" Ø x ___ FT LONG CORRUGATEDALUMINUM DRAINPIPE FOR STILLING WELL
BLUE RIBBON BIRDCAGE MODEL 3112
FLEX CONDUIT
ALUMINUM BREATHERHOUSING WITH TRANSMITTER
10' MIN. SETBACKFROM TOP OF BANK
CONTRACTOR TOINSTALL WIRING COMPLETE
RIP RAP HEADWALL (ENGINEER OFRECORD TO DETERMINE DIMENSIONS)
12" Ø CMP (ALUMINUM)INVERT EL. =
3" PVC STILLPIPE WITH3/8" Ø PERFORATIONS
BOTTOM OFRECEIVING
LAKE4'-0" M
IN.
SUBMER
GEN
CE
ELECTRICALCONDUIT
10 YR-1 DAYSTORM EVENTWATER EL.=
MAX WET SEASONWATER EL.=
4'-0" M
IN.
EMBED
MEN
T
GALVANIZEDSIGN POSTWITH STAFF
GAUGE
15'-0"
NOTES:
1. SIGN POST SHALL BE 12' LONG, STEEL, U-CHANNEL SIGN POST FOR LAKE LEVELSTAFF GAUGE ATTACHMENT, USA BLUEBOOK ITEM # 53759 OR APPROVED EQUAL.TRIM AS NECESSARY.
2. LAKE LEVEL GAUGE SHALL BE 4" WIDE FIBERGLASS STREAM GAUGE MARKED ININCREMENTS OF FEET, TENTHS AND HUNDREDTHS, BEN MEADOWS ITEM #8JH-12511* (*=WATER LEVEL) OR APPROVED EQUAL.
A. A LICENSED SURVEYOR MUST SET THE GAUGE TO ACCURATELY DISPLAYELEVATION IN NGVD 1929.
B. GAUGE MUST BE VISIBLE 1 FOOT ABOVE THE TOP OF BANK AND THE BOTTOMOF THE GAUGE MUST TOUCH THE BOTTOM OF THE LAKE. THE GAUGE SHALL BEPLACED IN A DEEP PART OF THE POND TO ENSURE VISIBILITY AS THE WATERRECEDES DURING THE DRY SEASON.
BULK USER RECLAIMED WATER SYSTEM
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.RECLAIMED WATER METERING FACILITY
LAKE STILLING WELL (BULK USER) 74JUNE 2014
NOTE: FOR POSTING IN AREAS THAT IRRIGATEWITH RECLAIMED WATER
NOTE: FOR POSTING AROUND STORAGE LAKES/PONDSTHAT USE RECLAIMED WATER.
RECLAIMED WATERLAKE CONTAINS
"NO NADAR"
"DO NOT SWIM"
"NO BEBER"
"DO NOT DRINK"
A Water Conscious Community
A Water Conscious Community
RECLAIMED WATERUsed for Irrigation
"DO NOT DRINK"
"NO BEBER"
A
O
IR
TR
MTY FO
S C
OETA
T
F LF
UO
N
AD
I N
A
O
IR
TR
MTY FO
S C
OETA
T
F LF
UO
N
AD
I N
RT I
R I DA
N
OFYT M
OU
TTA
CS
FE
O OLF
N ART I
R I DA
N
OFYT M
OU
TTA
CS
FE
O OLF
N A
BULK USER RECLAIMED WATER SYSTEM
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.RECLAIMED WATER METERING FACILITY
RECLAIMED WATER SIGNAGE (BULK USER) 75JUNE 2014
CONCRETE COLLAR
PLAN
ELEVATION
8"
24"
8"
24"
6"
RECLAIMED WATER SYSTEM(BULK AND PRESSURIZED)
POUR CONCRETE TO GRADE
COVER, C.I. OR BRONZE, MARKED"RECLAIMED WATER"(PURPLE PANTONE 522)
CONTINUOUS STRANDED COPPER WIRETERMINATING IN CURB STOP BOX IN PAD,10 GAUGE FOR ALL OPEN CUT CONSTRUCTION,8 GAUGE FOR ALL DIRECTIONALLY DRILLEDCONSTRUCTION (PURPLE PANTONE 522)
2" BRASS CLEANOUT TOPAND PVC THREADED BOX
C.I. ADJUSTABLE VALVE BOX(INSIDE SCREW TYPE)
SQUARE NUT
VALVE STEM RISER REQUIREDFOR DEPTHS EXCEEDING 4'
APPROVED MECHANICALJOINT VALVE HALF HITCH
(typ)
PROVIDE 18" LOOP, WRAPPED IN BOX
TOP OFPAVEMENT
NOTE:
1. A LOCATION BALL (3M EMS BALL MARKERS; RECLAIMED WATER/PURPLE,MODEL No. 1408-XR) SHALL BE INSTALLED AT EACH FITTING AND/OREVERY 100 FEET OF SEPARATION.
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.RECLAIMED WATER VALVE SETTING DETAIL
(BULK USER AND PRESSURIZED SYSTEMS) 76JUNE 2014
2 1/2" BRASS NSFTDISCHARGE WITH CAPAND CHAIN
VALVE STEM
BRONZE BODY BALL VALVEWITH AUTOMATIC WEEP
90° BEND
FLUSHING ASSEMBLY
CAP OR PLUG
MAIN
2" BALL VALVE
2" POLYETHYLENE
NOTES:
3'MIN.
W/ 2" TAP
(THREADED)
OR COPPER
LOCATOR WIRE
1. FLUSHING HYDRANT ASSEMBLY SHALL BE GIL INDUSTRIES, AQUARIUS ONE-O-ONE2" POST FLUSHING HIDDEN HYDRANT.
2. MAIN TO BE RESTRAINED FOR TWO FULL LENGTHS.
3. LID SHALL BE LOCKABLE AND MARKED "RECLAIMED WATER".
6"#57STONE
FLUSH HYDRANT BOX w/ LID LABELED "RECLAIMED WATER"TO BE SUPPLIED BY CONTRACTOR ( POLYMER CONCRETEAND FIBER REINFORCED POLYESTER-PERMANENT PURPLEPANTONE 522 COLOR) 17"x30" CDR SYSTEMS, ORAPPROVED EQUAL.
RECLAIMED WATER SYSTEM(BULK AND PRESSURIZED)
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.RECLAIMED WATER FLUSHING HYDRANT
(BULK USER AND PRESSURIZED SYSTEMS) 77JUNE 2014
R/W LINE AT PROPERTY CORNER
SERVICE TUBING 1" TO 2" SHALL BEPOLYETHYLENE
DOUBLE STRAP TAP SADDLETAPPED AWWA THREADS
CORP STOP
NOTES:
30" MIN. COVE
R 8"
1.
2.
3.
4.
5.
MIN.
6.
RECLAIMED WATERMAIN
METER TO HAVE "PURPLE" COLLAR.METER BOX TO BE SUPPLIED BYCONTRACTOR AND SHALL BEPERMANANT PURPLE IN COLOR (CDR& BOXES) WITH LID MARKED"RECLAIMED WATER".
MIN. SERVICE LINES SHALL BE AS FOLLOWS: 1" FOR SINGLE AND DOUBLESERVICES WHERE METER SIZE IS 5/8"; 2" FOR SINGLE AND DOUBLESERVICES WHERE METER SIZE IS 1".
COMPRESSION FITTINGS SHALL BE SUITABLE FOR TUBING USED AND REQUIREMETAL (S.S.) INSERTS.
DOUBLE SERVICES REQUIRE "U" BRANCH WITH ANGLE CURB STOPS.
POLYETHYLENE SHALL BE AS DEFINED BY A.S.T.M. D2737 SDR9 ANDA.W.W.A. 901, LATEST EDITION, AND BE PRESSURE RATED FOR 200 PSI.(COLORED PURPLE PANTONE 522).
TUBING SHALL BE MARKED WITH SIZE, MANUFACTURERS NAME, WORKINGPRESSURE, NATIONAL SANITATION FOUNDATION APPROVAL, A.S.T.M.SPECIFICATION AND PRODUCTION CODE. TUBING SHALL HAVE AN OUTSIDEDIAMETER EQUIVALENT TO THE OUTER DIAMETER OF COPPER TUBING.
SERVICE LOCATOR WIRE SHALL BE LAID IN THE TRENCH WITH ALL SERVICES,CONNECTED TO THE MAIN WIRE AND WRAPPED AROUND THE SERVICE PIPINGOR TUBING. WIRE FOR RECLAIMED WATER SHALL BE PURPLE IN COLOR.
PRESSURIZED RECLAIMED WATER SYSTEM
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.PRESSURIZED RECLAIMED WATER SYSTEM
SERVICE CONNECTION DETAIL - 5/8" OR 1" METER 78JUNE 2014
ROADWAY
3
2
1
8
9
LP
5' MIN.
PLAN
METER ASSEMBLY
POLYTUBING
ROADWAY
CASING
30"
36"
MIN.
MIN.
PROFILE
NOTES:
P PL L
RECLAIMED WATER MAIN
4' 4'
2' GUTTER
R/W
R/W
EASEMENT (TYP.)
SSSS
SS12
" M
AX
.(T
YP
)
1. HOUSE SERVICE LATERAL UNDER PAVEMENT SHALL BE INSTALLED THROUGH A2" BLACK IRON PIPE OR PVC SCH. 80 CASING.
2. TAPPING SADDLE AND CORPORATION STOP MUST BE PLACED IN ACCESSABLEAREAS, OUT FROM UNDER ANY PAVED AREAS.
3. RECLAIMED WATER SERVICE TO BE LOCATED ADJACENT TO SANITARY SERVICELOCATIONS.
12" MAX.(TYP)
WM
WM
WM
WM
PL7
LP
PL
WATER MAINSANITARY SEWER
RECLAIMEDWATER METER (typ)
TYPICAL SINGLERECLAIMED SERVICE
TYPICAL DOUBLE SAN.SERVICE LATERAL W/
CLEAN OUT
DOUBLE WATERSERVICE
RECLAIMEDWATER MAIN
TYPICAL DOUBLERECLAIMED SERVICE
DOUBLE WATER SERVICE
BFPASSEMBLY (typ)
WATER MAIN
CASING
CASING
PRESSURIZED RECLAIMED WATER SYSTEM
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.PRESSURIZED RECLAIMED WATER SYSTEM
SERVICE CONNECTIONS PLAN & PROFILE (SINGLE AND DOUBLE) 79JUNE 2014
PROVIDE NIPPLEw/ TEMP. CAP
TRANSITION BETWEENPOLYTUBE AND P.V.C.
FLOW
W/ FORD OR MUELLER2" COUPLING
VARIES
BY CONTRACTOR
NOTES:
1. ALL VALVES TO BE STRAIGHT 2" BALL VALVES WITH LOCK- WING.(FLANGE AT METER) FORD OR APPROVED EQUAL.
2. SEE TYPICAL SERVICE DETAIL FOR MAIN CONNECTION.
3. METER BOX SHALL BE POLYMER CONCRETE FIBER REINFORCEDPOLYESTER, AND "PURPLE" IN COLOR. (PANTONE 522)
4. PIPING SHALL BE 2" SCHEDULE 80 PVC WITH SCHEDULE 80FITTINGS.
5. LID SHALL BE PURPLE AND MARKED "RECLAIMED WATER".
PRESSURIZED RECLAIMED WATER SYSTEM
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.PRESSURIZED RECLAIMED WATER SYSTEM
2" METER DETAIL 80JUNE 2014
TUBE, M
IN. SIZE
-2".
ENTIRE
MANIFOLD (EX
CLU
DING
ELEC
TRICAL CONNEC
TIONS
AND
ADJU
STING C
ONTR
OLS) SH
ALL
BE
PRIMED
AND P
AINTED,
(SEE
DETAIL #
RU-06
)
( S
EE N
OTE A
T RIGHT)
*MANIFOLD FABRICATION: MANIFOLDS
TO B
E FA
BRICATED U
SING D
UCTILE
IRON, BRASS
PIPING, OR C
OPPER
BRASS
TRUE
UNION
CONTR
OL VA
LVE: -
AMES
CO. MODEL 9
51-65
1A-15-43
-02
-38
-85
-2-
PG O
R95
1-65
1-AD-15-43
-02
-38
-2-
PG C
OMBINATION R
ATE O
F FLOW/ P
RES
SURE
RED
UCING/SO
LENOID S
HUT OFF (120
VAC.) N
.C. ANGLE C
ONFIGURATION FLANGED
.VA
LVE BODY
TO B
E EP
OXY
COATED W
ITH S
TAINLESS
STEEL TRIM. ORIFICE PLATE A
SSP
ECIFIED. SIZE
TO B
E DETER
MINED
BY
IRRIGATION D
ESIGNER
.
FOR 2
" AND S
MALLER
USE
FORD B
ALL V
ALVE
CURB S
TOP W
ITH R
ECLA
IMED
WATER TEE
-HEA
D &
PADLO
CK W
INGS
(2"-
Mod
el B
RW11-78
8W,
ADJU
ST M
ODEL FOR S
IZE). FO
R 2
-1/
2" O
RGREA
TER U
SE A
MER
ICAN R
ESILIENT SE
AT GATE
VALVE
WITH G
ALV. CHAIN &
COUNTY P
ADLO
CK
DISTA
NCE
VARIES
24" MIN.HEIGHT
ORIFICE
PLA
TE: SIZE
DTO
MATC
H V
ALVE, S
HOP
DRAWING S
UBMITTA
LREQ
UIRED
TO V
ERIFY
FLOW R
ATE.
FLOW S
ENSO
R: WATER
SPEC
IALTIES
PROPELLER
ML-
04-D
3 PIPE
DIA.
3-5
PIPE
DIA.
NOTES:
1.TW
O (2) G
LYCER
IN FILLED/SS
BODY
PRES
SURE
GAUGES
SHALL B
E INSTALLED
ON H
IGH A
ND LOW S
IDE
PORTS O
F CONTR
OL VA
LVE.
2.FENCE:
48" HIGH, VINYL-COATED, w/ 4
8" W
IDE
LOCKABLE G
ATE.
3.ALL P
RES
SURIZED
REC
LAIMED
FACILITIES
TO B
E PAINTED P
ER S
PEC
IFICATIONS
FOR R
ECLA
IMED
WATER S
YSTEMS
(PAGE
49).
REC
LAIMED
WATER
SUPPLY LINE
POINT OF CONNEC
TION
MEG
-A-LU
G R
ETAINER
S(TYP
) WHEN
C-90
0OR D
.I.P. IS U
SED
*WHEN
REU
SE W
ATER S
UPPLY LINE
IS D
.I.P. OR P
VC (C-90
0) INLET
RISER
PIPE
SHALL B
E D.I.P. WITH C
OMPANION FLA
NGE
CONNEC
TED TO
CONTR
OL VA
LVE. W
HEN
SUPPLY LINE
IS 2
" PVC
SCH 8
0, A
PVC
FEMALE A
DAPTER S
HALL B
E USE
D A
T TH
E DOWNSTREA
M S
IDE
OF TH
EBEN
D A
ND R
ISER
PIPE
SHALL B
E BRASS
.
PIPE
FROM P
OINT OF CONNEC
TION TO
MANIFOLD TO B
E C-90
0 PURPLE P
VC O
RDIP A
S REQ
UIRED
, SIZE
PER
POINT OF
CONNEC
TION TO B
ASE
OF MANIFOLD
5 PIPE
DIA.
GLYCER
INFILLED
GAUGE
0-100
PSIG
GLYCER
IN FILLED
GAUGE
0-150
PSIG
CONDUIT
PRIVATE OWNERSHIPMCU OWNERSHIP
XXX
XXX
RISER
PIPE*
PRES
SURIZED
REC
LAIMED
WATER S
YSTEM
BRASS
OR C
OPPER
TUBE
TOIRRIGATION
SYSTEM
RS
GATE V
ALVE
STANDARD
(REC
LAIMED
) VA
LVE
BOX
FINISHED
GRADE
90° B
END
4" THICK, 40
00 p
si, CLA
SS II,
CONCRETE
PAD W
ITH 6
x6 W
WF,
POURED
TO 6
" OUTSIDE
OF
FENCING (typ)
6" (typ)
90° B
END
6" (typ)
FENCE
(SEE
NOTE 2
)
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.PRESSURIZED RECLAIMED WATER SYSTEM
POINT OF CONNECTION DETAIL-CONNECTION CONTROLS 81JUNE 2014
OUTLET
METER
X
XXXX
XX
XX
XX
X
X X X X
XX
XX
XX
INLET
TR 2
8
PRES
SURIZED
REC
LAIMED
WATER S
YSTEM
RECLAIMED CONTROLPANEL (RCP)
4" THICK, 40
00 p
si,
CLA
SS II, CONCRETE
PAD W
ITH 6
x6 W
WF,
POURED
TO 6
"OUTSIDE
OF
FENCING (typ)
6" (typ)
48" HIGH, VINYL-COATED FEN
CE
FLOW
SENSO
R
48" LO
CKABLE S
WING G
ATE.
COORDINATE LOCATION
WITH M
CU &
SW
3/4"
CONDUITS
FP&L
CONDUIT
CONTR
OL
VALVE
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.PRESSURIZED RECLAIMED WATER SYSTEM
POINT OF CONNECTION PLAN-CONNECTION CONTROLS 82JUNE 2014
FRONT VIEW
(N.T.S.)
SEE
INSTRUCTIONS
TEST
TEST
RESET
RESET
TEST M
ONTH
LY
FLOW
OPE
NCLOSE
REC
LAIMED
WATER ENCLOSU
RE
DEA
D FRONT DOOR LAYO
UT
(N.T.S.)
REC
LAIMED
WATER E
NCLO
SURE
NEM
A 3
R/12, SS
, WHITE PAINTED EXTER
IOR
(24"Wx30"Hx8"D)
MOUNT ON R
EAR O
FREC
LAIMED
POWER
PED
ESTA
L(SEE
DWG N
o. 8
5)
26.00
20.50
30.00
24.00
VALVE
PRES
SURIZED
REC
LAIMED
WATER S
YSTEM
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.PRESSURIZED RECLAIMED WATER SYSTEM
CONTROL PANEL (FRONT) - CONNECTION CONTROLS 83JUNE 2014
FP&L POWER IN
TO VALVETO FLOW METER
PRESSURIZED RECLAIMED WATER SYSTEM
MOUNT CONTROL PANELAND ELECTRICAL COMPONENTSON TWO (2)~4" ALUMINUMPOSTS WITH STAINLESS STEELUNI-STRUTS. EMBED IN 1' ØBY 4' DEEP CONCRETE BASE.
JUNCTION BOX
CONDUIT
STAINLESS STEELNEMA 4 ELECTRICALDISCONNECT BOX
TR 28
3/4" CONDUIT
FINISHED GRADEGROUNDWIRE
TOGROUNDROD
5.0' ±
4.0' (typ)
1.0'(typ)
NOTES:
1. CONTRACTOR SHALL FURNISH AND INSTALL ALUMINUM POSTS W/ UNI-STRUTS AND STAINLESS STEEL NEMA 4DISCONNECT SWITCH AND ENCLOSURE.
2. CONTRACTOR SHALL FURNISH AND INSTALL ALL CONDUIT AND WIRES BETWEEN FIXTURES AND CONTROL PANEL.3. ELECTRIC METER AND PRIMARY DISCONNECT MOUNTED TO UNI-STRUT ON BACK SIDE OF PANEL.4. ALL POWER AND CONTROLS LINES SHALL BE CONTINUOUS (NO SPLICES).5. PANEL MOUNTED TO S/S UNI-STRUT BY WELDED TABS.6. ALUMINUM POSTS IN CONCRETE SHALL BE COATED WITH BITUMASTIC, BOTH EXTERIOR AND INTERIOR.7. ALL HARDWARE, NUTS & BOLTS, AND APPURTENANCES ABOVE GROUND SHALL BE 316 STAINLESS STEEL.
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.PRESSURIZED RECLAIMED WATER SYSTEM
TYPICAL CONTROL CENTER - CONNECTION CONTROLS 84JUNE 2014
4
DOWNSTREAM OF MAIN VALVE OUTLET.INSTALLED 3 TO 5 PIPE DIAMETERSORIFICE PLATE ASSEMBLY SHOULD BE
6
2. ISOLATION COCKS1. CONTROL VALVE
8. RATE OF FLOW PILOT9. ORIFICE PLATE ASSEMBLY
7. PRESSURE REDUCING PILOT
4. RESTRICTION FITTING5. OPENING SPEED CONTROL6. TWO-WAY SOLENOID (120VAC)
3. LARGE CONTROL FILTER
RATE OF FLOW, PRESSURE REDUCING & SOLENOID SHUTOFF VALVEEQUIPPED WITH LARGE CONTROL FILTER AND SPEED CONTROL
2
3 5
NOTE:
91
7
2
8
222
PRESSURIZED RECLAIMED WATER SYSTEM
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.PRESSURIZED RECLAIMED WATER SYSTEM
TYPICAL CONTROL VALVE SCHEMATIC-CONNECTION CONTROLS85JUNE 2014
3
MODEL SB-18SS, MFG. BY: V.T.I.
12
5
4 3
5
7
6
4
8FT. MIN.
8FT. MIN.
8FT. MIN.
GROUND ROD LAYOUT GROUND ROD ASSEMBLY
LEGEND:
1. RCP PANEL.2. #10 AWG SOLID BARE COPPER WIRE FROM GROUNDING ROD TO RCP. MAKE WIRE AS SHORT AND STRAIGHT AS
POSSIBLE.3. COVER GROUNDING ROD WITH 10" ROUND VALVE BOX.4. 5/8" X 8' COPPER CLAD GROUNDING ROD. INSTALL RODS IN SOIL IN A TRIANGULAR PATTERN SPACED A MINIMUM
OF 8' APART FROM EACH OTHER. GROUNDING GRID TO HAVE A RESISTANCE OF 5 OHMS OR LESS.5. #10 AWG BARE COPPER BETWEEN GROUNDING RODS.6. BRASS WIRE CLAMP. USE SEPARATE CLAMP FOR EACH WIRE.7. FINISH GRADE.
3-ROD GROUNDING GRID INSTALLATIONTHE 3 RODS SHALL BE DRIVEN INTO THE GROUND WITH THE TOP OF THE ROD AT LEAST 6" BELOW THE FINISHGRADE. THE RODS SHALL BE TIED TOGETHER BELOW GRADE WITH #10 GAUGE OR LARGER BARE COPPER WIRE. THEWIRE SHALL BE ATTACHED TO THE ROD USING A BRASS CLAMP. A SEPARATE BRASS CLAMP SHALL BE USED FOREACH ATTACHMENT. NOTE! NO MORE THAN ONE WIRE SHALL BE USED IN ANY INDIVIDUAL CLAMP - MULTIPLE WIRESSHALL NOT BE ALLOWED. ANY ROD THAT HAS A GROUND WIRE CONNECTED TO IT, COMING FROM THE SURGEARRESTOR AT THE EQUIPMENT OR GROUNDING THE EQUIPMENT, SHALL HAVE A 6" AMETEK OR CARSON VALVE BOX,PURPLE COLOR INSTALLED AROUND THE TOP OF THE ROD. THIS SHALL PROVIDE FUTURE ACCESS FOR MAINTENANCE.
PRESSURIZED RECLAIMED WATER SYSTEM
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.PRESSURIZED RECLAIMED WATER SYSTEM
3-ROD GROUNDING GRID DETAIL-CONNECTION CONTROLS 86JUNE 2014
DISTANCE ATWHICH (B) GOVERNS
MINIMUM FALL BETWEEN LIFTS *USE GREATER VALUE OF (A) OR (B)PIPE DIA.
0.2% x DISTANCE > 125 FT10" 0.25 FT
* WHEN NOT BETWEEN LIFTS, USE 0.2% SLOPE
0.2% x DISTANCE4" 0.25 FT
6" 0.25 FT
0.25 FT8" 0.2% x DISTANCE
0.2% x DISTANCE
(A)
3" 0.20 FT 0.2% x DISTANCE
(B)
> 125 FT
> 125 FT
> 125 FT
> 100 FT
SLOPE SCHEDULE
3' MAX. IN ANY ONE LIFT
45° PVC ELBOW
45° PVC ELBOW
VACUUM MAIN
FLOW
SCH 40 OR SDR-21PVC PIPE
NOTE:
1. MAGNETIC MARKERS SHALL BE PLACED AT EVERY FITTING, LIFT,AND EVERY 100 ft. ALONG THE VACUUM MAIN INSTALLATION. (EMSMARKER SYSTEM, OMNI MARKER; SEWER/GREEN, USA BLUEBOOKITEM No. 75027)
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.VACUUM SEWER
LIFT DETAIL AND SLOPE SCHEDULE 87JUNE 2014
VACUUM MAIN
45° BEND W/ REIBERGASKET (TYP.)
24"MIN.
45° BEND W/ REIBERGASKET (TYP.)
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.VACUUM SEWER
VACUUM MAIN - CHANGE OF DIRECTION 88JUNE 2014
3/8" BARB ADAPTORWITH CAP
3/4" FPT, COMPRESSION FITTING,FLO-CONTROL #831-07
3/4", SDR-7, 200 PSI,POLYETHYLENE TUBING
6" PVC PIPE EXTENSION
3/4" MPT, COMPRESSION FITTING,FLO-CONTROL #830-07
STAINLESS STEEL BAND FITTINGWITH 3/4" MPT CONNECTIONAND RUBBER SEAL RING TO PIPE
OPTIONAL GAUGE TAP
COMPACTED FILL
FLOW
GRADE
DIVISION VALVE SUPPORT INFORMATION
SUPPORT SIZE1" THICK X 1.75' SQUARE1" THICK X 2.25' SQUARE1" THICK X 3.00' SQUARE1" THICK X 3.50' SQUARE
VALVE SIZE4"6"8"10"
CONTINUOUS 10 GAUGE STRANDEDCOPPER WIRE, COLOR BROWN,TERMINATING IN CURB STOP BOX INPAD, FOR ALL OPEN CUT CONSTRUCTION.
BLOCKS OR MASS CONCRETE
PIPE EMBEDMENTMATERIAL
STANDARD CAST IRONADJUSTABLE VALVE BOX
VALVE EXTENSIONWITH 2" SQUARE NUT
C.I. COVER, MARKED "SEWER"
2" BRASS CLEANOUTTOP AND PVCTHREADED BOX
HALF HITCH(typ)
CAST IRON VALVE BOXCOVERCONCRETE COLLAR
POUR CONCRETE TO GRADE
PLAN
8"
24"
8"
24"
CONCRETE COLLAR
PROVIDE 18"LOOP, WRAPPEDIN BOX
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.VACUUM SEWER
ISOLATION VALVE & BOX W/ OPTIONAL GAUGE TAP 89JUNE 2014
20' MIN.
FROM A
LIFT
45°
VACUUM BRANCH
FLOW
PLAN VIEW
FLOW
WYE ROLLED AT 45°
45° ELBOW
6' MIN. FROM TOP OFLIFT
6"±
45° ELBOW
LIMIT OF ASSEMBLY
A
VACUUM MAIN
VACUUM SEWER BRANCH
45° ELBOW
SECTION A-A
VACUUM LINE VIEWEDINTO/OUT OF SHEET
BOTTOM OF BRANCH IS2" MINIMUM ABOVETOP OF MAIN
VACUUMBRANCH
ISOLATIONVALVE
24"MIN.
A
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.VACUUM SEWER
BRANCH TO MAIN CONNECTION ASSEMBLY 90JUNE 2014
11.86"
12.84"
9.32"
10.21"
10 x 10 x 3
8 x 8 x 3
6 x 6 x 3
WYE SIZE
4 x 4 x 3
3 25/32"
3 25/32"
3 25/32"
14 3/8"
10 1/2"
13"
3 25/32"
A
9 1/4"
B
*1
C
1.00'
1.10'
0.85'
D- INVERT
0.78'
CD
B
A
*
*2
FROM VALVE PIT
FLOW
*2 - 90° ELL TURNED TO SIDE
FLOW
*1 - WYE FITTING VACUUM MAIN
PLAN VIEW
ELEVATION
DIMENSIONS BASED ON SPEARS MANUFACTURING1. 45 DEG WYE, SOCKET x SOCKET x SOCKET2. 90 DEG ELL, SOCKET x SOCKET
3" SERVICE LATERAL, 2" OR0.2% FALL FROM VALVE TOMAIN. (MIN.)FL
OW
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.VACUUM SEWER
VALVE PIT TO MAIN CONNECTION 91JUNE 2014
FLOW
RIGHT-OF-WAY
EXISTING PAVEMENT
VACUUM SEWER MAIN
RIGHT-OF-WAY
AIRVAC VALVE PITASSEMBLY (TYP.)
VACUUM SEWER LATERAL (TYP.)
5' MIN.
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.VACUUM SEWER
MINIMUM SPACING BETWEEN CONNECTIONS 92JUNE 2014
TYPICAL VALVE PIT ASSEMBLY
FINISHED GRADE
4" THICK X 6" WIDE CONCRETERING AS REQUIRED
COMPACTED SELECT FILLMATERIAL WITH MINIMUMDENSITY OF 100 LBS PERCUBIC FOOT
SAND OR OTHER SUITABLEFILL MATERIAL, MAY BE THESAME AS ABOVEANTI-BOUYANCY COLLAR
COMPACTED GRANULAR BEDDINGFROM BOTTOM OF EXCAVATION TOCENTER LINE OF GRAVITYSTUB-OUT IN SUITABLE MATERIALSUCH AS #57 STONE, CRUSHEDSEA SHELL, "PEA" GRAVEL, DONOT BED IN OTHER MATERIALWITHOUT AIRVAC APPROVAL
UNDISTURBED SOIL
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.VACUUM SEWER
VALVE PIT BEDDING AND BACKFILL 93JUNE 2014
2'-0"
GRADE
'A''A'
'B''B'
1'-5"(MIN)
VACUUM SEWER MAIN(DIRECTION OF FLOWINTO PAPER)
3" SUCTION LINE
2" SENSOR LINE
3'-6"
4" THICK X 6" WIDE CONCRETERING AS REQUIRED
AIRVAC FLEXIBLECONNECTOR
MODEL VP3030WT
NEENAH R5900, CAST IRON FRAME AND LIDRATED FOR H20 LOADING, OPTIONALNON-TRAFFIC CAST IRON LID IS AVAILABLE
4" OR 6" GRAVITYSTUB-OUT WITH GLUED CAP(TYP.)
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.VACUUM SEWER
STANDARD 1-PIECE VALVE PIT 94JUNE 2014
INTERGRAL ANTI-BUOYANCY COLLARAIRVAC 3"VACUUM VALVE
4" OR 6" SDR 21 OR SCHEDULE40 PVC PIPE, SEE SPECIFICATIONS
SECTION 'A'-A'4'-0"
℄ 3" VACUUMLATERAL ANDAIRVAC VALVE
℄ 3" VACUUM LATERALAND AIRVAC VALVE
6' MIN. LENGTHGRAVITY STUB-OUTWITH GLUED ON CAP
GLUE HALF OF A SLIPCOUPLING IN PLACE4" FROM END OFGRAVITY STUB-OUT TOACT AS A STOP
SHOWING UP TO 4 GRAVITYCONNECTIONS TO SUMP
SECTION 'B'-'B'
4" ± 18 "
4" OR 6" GRAVITYSTUB-OUT WITHGLUED CAP (TYP.)
NOTE:
1. EVIDENCE THAT COUPONS FROM GRAVITY SEWER LATERAL CONNECTIONS TO THE VALVEPIT SUMP MUST BE PRESENTED TO THE MCU INSPECTOR PRIOR ACCEPTANCE ANDPLACEMENT OF VALVE PIT INTO OPERATION
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.VACUUM SEWER
STANDARD 1-PIECE VALVE PIT (SECTIONS) 95JUNE 2014
4'-6"
8'-2"
3'-8"
3"SCHEDULE40 COUPLING
3"SCHEDULE
40 COUPLING
3" SPECIAL PVC FLEXIBLE HOSEWITH OD CONTROLLED TO PIPE
TOLERANCES (BY AIRVAC)
3" SCHEDULE 21PVC PIPE
NOTE:1. FLEXIBLE CONNECTOR USED TO CONNECT VALVE PIT TO 3" VACUUM SERVICE LATERAL2. FLEXIBLE CONNECTOR LENGTH MAY NOT BE ALTERED, DO NOT CUT PVC PIPE OF
FLEXIBLE HOSE
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.VACUUM SEWER
VALVE PIT FLEXIBLE CONNECTION 96JUNE 2014
3" VACUUM SERVICE LATERALPREVIOUSLY INSTALLED AND
CONNECTED TO VACUUM BRANCHOR MAIN
GRADE
2' M
IN.
FLOW
FLOW
4" OR 6" GRAVITYSTUB-OUT WITH GLUEDCAP (TYP.)
AIRVAC VALVE PITLOCATED WITHIN
RIGHT-OF-WAY (TYP.)
EXISTINGHOUSE
FLOW
PLACE MAGNETIC MARKER AT PLUG.(EMS MARKER SYSTEM, OMNI MARKER;SEWER/GREEN, USA BLUEBOOK ITEMNo. 75027)
RIGHT-
OF-
WAY
APPROX. 3'-6"(CAN BE AS MUCHAS 7' W/ 8-1/2'
PIT)
EXISTING GRAVITY SERVICELATERAL FROM RESIDENCE
NOTE:DO NOT INSTALL AIRVAC VALVE UNTIL 4" AIR-INTAKE ASSEMBLY IS IN PLACE
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.VACUUM SEWER
VALVE PIT - PRIOR TO HOUSE CONNECTION 97JUNE 2014
5' MIN.
AIRVACVALVE PITASSEMBLY
45° ELBOW(HORIZONTAL)
45° ELBOWWYE WITH45° ELBOW
NOTE:REFER TO PLANAND PROFILE FORSERVICE LINEORIENTATION ANDDEVIATIONS FROMSTANDARD DETAIL.
45°
VACUUM M
AIN
FLOW
5' MIN.
45°
45°
45°
METHOD "B"
METHOD "A"
AIRVAC FLEXIBLECONNECTOR
(TYP.)
6' MIN. LENGTHGRAVITY STUB-OUTWITH GLUED CAP
RIGHT-OF-WAYPRIVATE PROPERTY
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.VACUUM SEWER
STANDARD VALVE PIT ORIENTATION 98JUNE 2014
PLAN
℄ 3" VACUUM LATERALAND AIRVAC VALVE
RIGHT-OF-WAY
ELEV VIEW ELEV VIEW
GRAVITY STUB-OUT (TYP.)
PROPERTY LINE
4" OR 6" GRAVITYSTUB-OUT UP TO 3
PER VALVE PIT
FLOW
PROPERTY LINE
RIGHT-OF-WAY
ALTERNATE ARRANGEMENT
3" VACUUM LATERAL
VACUUM MAIN
ELEV VIEWELEV VIEW
AIRVAC 1 PIECEMOLDED HDPE AIRTERMINAL
AIRVAC 1 PIECE MOLDED HDPE AIRTERMINAL, NO SEWAGE FLOW ALLOWED
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.VACUUM SEWER
6" DEDICATED AIR TERMINAL (PLAN) 99JUNE 2014
SCH 40 PRESSURERATED FITTINGSGLUE HALF OF A 6"
COUPLING AT 4" FROM ENDOF PIPE TO ACT AS A STOP
60' MAXIMUM LENGTH *
SEAL FOR FINAL SUMPTESTING AND UNTIL
TERMINAL IS IN PLACE
AIRVAC 1 PIECE MOLDEDHDPE AIR TERMINAL
REDUCE BY 10 LF FOR EACH ADDITIONAL 45° ELL
NO SEWAGE FLOW ALLOWED
ELEVATION
6" SDR 21 PVC, PRESSURE RATEDPIPE TO BE A DEDICATED AIR PIPEFROM THE SEWAGE HOLDING SUMPWITH NO SEWAGE FLOW
12" MIN
ENLARGED VIEW OF ACCESSDOOR, INCLUDES AIR INLET WITHSLOTS FOR AIR FLOW. POSITIONABOVE HIGHEST FLOOD WATERLEVEL.
WHERE FLOOD LEVELWILL ALLOW, TERMINAL
MAY BE INSTALLEDMAX, 12" BELOW
GRADE
35-1/2"
MARTIN COUNTY CONSTRUCTION STANDARDS & DETAILSREVISION DWG No.VACUUM SEWER
6" DEDICATED AIR TERMINAL (ELEVATION) 100JUNE 2014