Displacement 41
Waterloo 6.0 Tel: +44 (0) 1622 717861
Auditorium TerminalsGWR
IntroductionThe GWR series terminals are installed in the stair riser of auditoria to provide displacement ventilation. The terminals are designed to be installed in the step of a graded/sloping room configuration, using the space below as a pressure chamber.
The supply temperature should not be lower than 3K under-temperature in the occupied zone (Δtu).
The terminal consists of a perforated front panel installed into a frame, with or without flanges. An air distribution plate with nozzles sits behind the removable front panel, which is fixed with screws as standard.
Product DescriptionGWR Auditorium terminal with a 15mm flange for surface mounting
GWR /O Auditorium terminal, flangeless, for recess mounting
Features• Vertical air supply in theatre, cinema etc.• Installation in stair riser• Flush mounting• Standard and special sizes are available
MaterialFront plate: 1.25mm hot-dipped galvanised steel
Frame: 1mm electro-galvanised steel
Front panel and frame powder coated in RAL9010 or RAL9011.
Other RAL or NCS colours are available on request.
Specials and Accessories• Other dimensions are available on request
Dimensions GWR 04-01
Technical Data GWR 04-01
System
120 150
430
40
GWR
400
120
40
GWR/O
0.20
0.15
30
∆pt Pa v m/s0.2
l/s
LWA dB(A)
L0.2 m∆tu 3K
50 m³/h
104 40
100
20
50
10
5
25
20
20
20
100
0.5
0.3
0.8
Order Example
GWR/0/400/120/0/RAL9010
TypeFlange – 0 Flangeless, 1 Flange 15mmWidth Neck – 400mm as standardHeight Neck– 120mm as standardSpigot position – 0 Top, 1 BottomFinish
8-12Pa