2011 Report II AUCA 11_04_26 Prof. Kai Schlenther, Bishkek, April 2011 [AUCA REPORT II]

[AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 [email protected]

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

2011

Report II AUCA 11_04_26 Prof. Kai Schlenther, Bishkek, April 2011

[AUCA REPORT II]

Page 2: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 2

Report no. II

for

Energy Efficient and Sustainable Development of

University Campus for American University of Central Asia in

Bishkek, Kyrgyz Republic

Client American University of Central Asia 205 Abdymomunov St. 720040 Bishkek, Kyrgyz Republic

Consultant OcOO House of Sustainability Prof. Kai Schlenther, Managing Director

Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 [email protected]

Page 3: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 3

Content

1. Introduction……………………………………………………………………… 4 2. Balance Calculation………………………………………………………..…… 5 3. Zoning…………………………………………………………………………….. 5 4. Energy balance………………………………………………………………..... 17 5. Lighting, external gains, external gains…………………………………….. 18 6. Heating…………………………………………………………………………… 23 7. Cooling…………………………………………………………………………… 28 8. Ventilation………………………………………………………………………. 33 9. Summarized loads by zones…………………………………………………. 38 10. Summarized loads by areas………………………………………………… 39 11. General recommendations for construction………………………………. 44 12. Geothermal system……………………………………………………………. 49 13. Heat pump………………………………………………………………………. 50 14. Floor plans………………………………………………………………………. 51

Page 4: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 4

1. Introduction

1.1.1. The project started with Phase 1 in February 2011, defining a strategy for improvement of

energy efficiency for University Campus of American University of Central Asia “AUCA” in Bishkek, Kyrgyzstan.

1.1.2. Within the first phase an overall reduction of thermal losses has been identified with a cost benefit analysis

To achieve proposed efficiency, detailed calculations have to be undertaken. These calculations include requirements for zoned spaces.

1.1.3. This report as second phase of consultancy shows detailed calculation of balances and

zones for Lighting External gains Internal gains Heating requirements Cooling requirements Airhandling and ventilation requirements

1.1.4. Furthermore, recommendations for construction and recommendations for geothermal use

of energy (borehole grid / heating pumps) are explained.

Page 5: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 5

2. Balance Calculation

2.1. General In the following, the calculations for determining the energy balance of the building are described and specified using applicable equations. Prior to determining the energy balance the building is divided into zones. Areas are grouped together into zones where they have the same type of use and where are no significant differences in the mode or other zone criteria.

2.2. Requirements related to the energy balance Principles of the energy balance are described in terms of energy needs and delivered energy for all types of conditioning or all types of building services (heating, cooling, ventilation and lighting). Hot water supply has not been taken into consideration yet. The energy being delivered is calculated by energy requirements of the building as well as system losses due to control, distribution and storage.

3. Zoning 3.1. The building has been divided into zones (partitioned) prior to carrying out the balance calculations.

All relevant characteristics are determined once for each zone. The most important characteristics of a zone are same use, orientation and same mode of conditioning in all spaces it comprises. Allocation of zones is shown as follows:

3.1.1. Zone 1 – Rooms facing North and West

Name Area [m2]

Volume [m2]

Perimeter [m2]

External enclosure

[m2]

0,30 Stair 5 17,63 66,12 17,58 47,65 0,31 Stair 4 24,25 87,31 21,30 39,41 1,07 Class 1 45,66 232,85 27,40 79,65 1,08 Class 10 46,00 234,60 27,50 78,40 1,09 Class 11 45,20 230,52 27,30 32,40 1,10 Class 2 65,12 332,09 34,35 99,77 1,11 Class 3 46,14 235,33 27,55 32,40 1,12 Class 4 46,14 235,33 27,55 32,40 1,13 Class 5 46,14 235,33 27,55 32,40 1,14 Class 6 46,00 234,60 27,50 32,40 1,15 Class 7 46,00 234,60 27,50 78,40 1,16 Class 8 46,00 234,60 27,50 78,40 1,17 Class 9 46,00 234,60 27,50 78,40 1,18 Clubs Volunteers 50,12 202,99 29,05 82,52 1,21 Corridor 131,46 670,45 76,80 32,19 1,22 Corridor North 113,17 577,19 68,33 92,98 1,23 Dean Students 11,86 48,03 14,00 11,86 1,31 JC 5,18 26,43 9,23 0,00 1,33 Med Suite 18,13 73,42 18,44 44,72 1,34 Med room 25,31 102,50 29,33 25,80 1,44 Porch north 12,94 65,98 16,00 34,58 1,46 Receive 39,89 203,43 32,07 53,24 1,47 Reception med 27,69 112,15 29,96 13,44 1,49 Sound Studio 11,60 46,99 13,88 11,60 1,52 Stair 4 19,30 98,44 18,30 18,90 1,53 Stair 5 17,63 71,41 17,58 27,84 1,58 Stud Coordinator 50,14 203,05 29,05 50,14 1,59 Toilets F 29,05 148,14 29,50 0,00 1,60 Toilets M 32,12 163,79 30,75 0,00

Page 6: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 6

1,62 Stair 3 19,89 47,74 18,25 0,00 2,01 Acquisitions + Catal. 46,73 154,20 27,68 72,00 2,11 Class 20 73,67 243,12 35,93 69,73 2,12 Class 21 49,35 162,86 28,55 21,00 2,13 Copy 23,84 78,66 20,99 0,00 2,14 Corridor 190,28 627,93 138,68 0,00 2,18 Group study 21,04 69,42 26,30 0,00 2,19 Group study 11,81 38,98 14,16 0,00 2,20 Group study 11,86 39,14 14,13 0,00 2,21 Group study 15,13 49,91 22,00 0,00 2,22 Group study 7,91 26,09 11,25 0,00 2,23 IT Equipment 41,68 137,55 34,95 0,00 2,25 JC 4,90 16,17 9,02 0,00 2,26 Library 23,56 75,39 21,40 0,00 2,27 Library 63,81 261,64 34,15 81,89 2,28 Library 69,30 252,95 35,10 0,00 2,29 Library 74,50 245,84 36,00 0,00 2,30 Literacy 69,20 228,36 36,10 49,43 2,31 Meeting 16,44 52,60 17,00 0,00 2,32 Meeting Research 32,13 106,04 22,68 0,00 2,37 Office Lib 11,97 39,52 14,00 0,00 2,38 Research 132,78 438,18 53,24 87,30 2,39 Room 12,38 40,84 20,00 0,00 2,40 Room 49,35 162,86 28,55 21,60 2,41 Room 74,61 246,21 40,80 43,20 2,44 Stair 4 19,14 63,16 18,20 12,67 2,45 Stair 5 17,63 58,18 17,58 22,21 2,50 Toilets F 29,22 96,41 29,38 0,00 2,51 Toilets M 29,55 97,52 28,35 0,00 2,52 Writing center 65,61 216,51 34,80 43,20 3,17 Director IRT 15,29 50,44 16,75 34,02 3,18 Director Library 12,36 40,80 14,35 10,80 3,22 ACCT Director 12,36 40,80 14,35 10,80 3,23 IT Electric Util 12,54 41,38 14,50 0,00 3,24 IT Electric Util 28,79 94,99 25,90 0,00 3,25 IT Electric Util 7,02 23,17 10,60 0,00 3,27 JC 4,49 14,82 8,77 0,00 3,28 Meeting Library 10,56 34,84 13,13 10,80 3,29 Meeting Multimedia 10,91 36,01 13,38 10,80 3,30 Meeting 12,36 40,80 14,35 10,80 3,31 Multimedia 143,67 474,10 54,57 54,00 3,36 Pantry 31,22 103,02 29,94 0,00 3,37 Stacks 288,88 953,30 80,93 53,90 3,38 Staff ACCT/Library 132,46 437,12 54,57 87,30 3,41 Stair 4 18,89 62,35 18,05 12,78 3,42 Stair 5 17,63 63,47 17,58 23,40 3,44 Storage 10,14 33,45 13,70 8,86 3,46 Toilets F 28,24 93,18 29,23 0,00 3,47 Toilets M 29,73 98,11 28,25 0,00 4,12 Class 40 72,95 466,45 35,80 242,62 4,13 Class 41 46,00 192,28 27,50 90,07 4,14 Class 42 46,00 192,28 27,50 90,01 4,15 Class 43 46,00 258,29 27,50 96,12 4,16 Class 44 46,00 325,91 27,50 107,96 4,17 Class 45 93,29 543,97 39,30 258,30 4,18 Class 46 74,77 390,24 34,70 206,91 4,23 Corridor 95,71 526,81 63,10 126,34 4,26 IT Equipment 5,45 31,96 9,45 7,19 4,28 JC NW 5,49 36,39 9,46 7,25 4,33 Performance 47 233,19 1431,43 64,38 434,35 4,39 Stair 4 19,30 138,83 18,30 48,07 4,40 Stair 5 17,63 119,94 17,58 76,58 4,42 Toilet F 27,98 139,78 29,04 36,93 4,43 Toilet M 31,86 158,73 29,67 42,06

4160,30 17705,69 2633,25 3965,13

Page 7: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 7

3.1.2. Zone 2 – Rooms facing South

Name Area [m2]

Volume [m2]

Perimeter [m2]

External enclosure

[m2]

0,29 Stair 3 27,73 74,86 22,55 66,92 1,51 Stair 3 20,62 49,48 18,63 51,21 1,63 Stair 4 18,65 44,75 17,90 0,00 2,03 Class 12 43,03 142,01 26,55 94,08 2,04 Class 13 32,67 107,81 22,88 36,04 2,05 Class 14 46,00 151,80 27,50 36,04 2,06 Class 15 46,00 151,80 27,50 38,38 2,07 Class 16 46,00 151,80 27,50 36,04 2,08 Class 17 46,00 151,80 27,50 36,04 2,09 Class 18 47,40 156,42 27,85 36,04 2,10 Class 19 46,00 151,80 27,50 22,43 2,43 Stair 3 20,62 68,03 18,62 10,80 3,03 Class 22 42,75 141,08 26,45 51,44 3,04 Class 23 32,13 106,04 22,67 21,60 3,05 Class 24 46,00 151,80 27,50 21,60 3,06 Class 25 46,00 151,80 27,50 23,04 3,07 Class 26 46,00 151,80 27,50 21,60 3,08 Class 27 46,80 154,44 27,70 21,60 3,09 Class 28 47,40 156,42 27,85 21,60 3,40 Stair 3 25,19 90,70 21,15 10,80 4,02 Cafe/Study 52,66 337,21 30,15 156,30 4,03 Class 31 32,70 183,63 22,88 81,60 4,04 Class 32 46,00 192,28 27,50 90,72 4,05 Class 33 46,00 192,28 27,50 90,72 4,06 Class 34 46,14 267,25 27,55 104,66 4,07 Class 35 46,00 335,37 27,50 109,63 4,08 Class 36 46,80 305,06 27,70 106,21 4,09 Class 37 47,40 231,30 27,85 103,37 4,38 Stair 3 20,39 144,16 18,50 61,97

1157,08 4694,98 737,93 1562,48

Page 8: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 8

3.1.3. Zone 3 – Rooms in Admin Section East

Name Area [m2]

Volume [m2]

Perimeter [m2]

External enclosure

[m2]

0,02 Corridor Ante Admin 12,50 41,23 14,63 12,50 0,03 Corridor Admin 38,35 126,55 33,44 38,35 0,06 Faculty Lounge 65,95 217,62 35,83 116,47 0,10 Int Recruit 10,06 33,21 12,75 21,22 0,11 JC 3,54 11,70 7,98 3,54 0,14 Lockers F 17,36 57,29 20,75 17,36 0,15 Lockers M 24,77 81,74 25,30 36,38 0,19 Meeting 10,06 33,21 12,75 20,86 0,23 Registrar 40,97 135,20 25,75 62,12 0,25 Room 24,06 79,41 23,00 42,20 0,26 Showers F 40,06 132,19 25,55 67,06 0,27 Showers M 39,91 131,72 26,26 90,31 0,32 Storage 15,01 49,52 16,63 15,01 0,33 Storage 25,19 83,12 20,35 46,34 0,34 Toilet M Adm 21,98 72,53 19,90 44,03 0,35 Toilets F Adm 21,98 72,53 19,90 21,98 0,36 Visa 10,06 33,21 12,75 10,06 0,37 Visa 10,10 33,32 12,78 10,10 1,01 Administration 217,85 653,54 65,07 99,83 1,02 Administration 79,68 239,03 40,68 51,15 1,04 COT 7,02 28,43 10,60 9,83 1,06 Career Service 13,66 40,99 15,03 10,63 1,19 Copier 8,45 25,34 11,63 0,00 1,20 Corridor 20,41 61,22 20,09 0,00 1,27 Green Room 19,77 59,31 19,20 0,00 1,28 HR Director 10,78 32,34 13,25 10,30 1,35 Meeting 12,84 38,51 14,45 0,00 1,36 Meeting 19,52 58,56 18,02 0,00 1,37 Meeting 8,16 24,47 11,43 9,57 1,41 Office Security 7,87 31,85 11,25 0,00 1,45 President 16,23 48,68 16,20 0,00 1,50 Stair 1 18,90 56,70 19,65 9,49 2,16 Faculty chair 100,77 332,55 40,60 76,10 2,24 IT Workstations 203,37 671,13 58,62 109,01 2,33 Office 1 10,23 33,74 12,84 21,60 2,34 Office 2 10,23 33,74 12,84 0,00 2,35 Office 3 10,64 35,10 13,10 0,00 2,36 Office 4 11,08 36,57 13,35 0,00 2,42 Stair 1 19,08 62,96 19,38 10,80 3,02 Chairs 100,27 330,88 40,50 77,04 3,10 Class 29 46,00 151,80 27,50 23,13 3,26 IT Workstations 203,13 670,32 58,30 108,90 3,32 Office 1 10,27 33,89 12,86 0,00 3,33 Office 2 10,23 33,74 12,84 0,00 3,34 Office 3 10,35 34,14 12,91 0,00 3,35 Office 4 10,64 35,10 13,08 0,00 3,39 Stair 1 18,91 68,06 19,25 10,80 4,10 Class 38 46,00 298,71 27,50 110,45 4,11 Class 39 100,27 649,21 40,50 256,73 4,27 IT Workstations 203,13 1313,76 58,30 423,75 4,29 Office 1 10,38 70,87 12,96 13,70 4,30 Office 2 10,52 71,87 13,03 13,89 4,31 Office 3 10,64 72,66 13,10 14,04 4,32 Office 4 10,77 73,46 13,15 14,22 4,37 Stair 1 18,91 106,03 19,25 34,39

Zone 3 2078,87 8044,56 1218,61 2195,24

Page 9: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 9

3.1.4. Zone 4 – Forum and open areas

Name Area [m2]

Volume [m2]

Perimeter [m2]

External enclosure

[m2]

1,03 Arcade 105,99 540,54 49,30 24,28 1,05 Cafe 13,47 54,54 14,85 0,00 1,25 Forum 547,18 2216,09 148,47 235,78 1,26 Forum 56,13 227,33 31,13 0,00 1,43 Porch South 20,14 81,58 18,33 0,00 1,54 Stair 6 60,22 243,88 33,50 0,00 1,57 Storage 67,55 334,37 34,89 0,00 2,02 Cafe Study 55,80 184,15 31,25 89,62 2,15 Corridor 78,44 258,85 64,97 0,00 2,17 Forum 584,37 1928,42 104,99 0,00 2,46 Stair 6 43,88 144,79 27,05 37,95 2,47 Study Lounge 217,20 716,77 84,40 0,00 2,48 Study space 259,07 854,94 138,81 0,00 2,49 Study space 71,52 271,76 54,75 0,00 3,01 Cafe / Study 57,58 190,02 31,73 62,58 3,11 Conference 31,91 105,31 22,60 0,00 3,12 Corridor 47,89 158,03 51,89 0,00 3,13 Corridor 96,89 319,73 88,14 0,00 3,14 Corridor 96,98 320,03 62,05 0,00 3,15 Corridor 228,52 754,12 116,44 0,00 3,19 Forum 439,59 1582,52 103,98 0,00 3,43 Stair 6 44,44 159,97 27,18 21,60 3,45 Study Balcony 62,86 207,43 54,40 0,00 4,01 Study Balcony 64,01 404,04 55,30 84,49 4,20 Conference 31,91 86,16 22,60 42,12 4,21 Corridor 133,34 738,28 72,44 176,01 4,22 Corridor 212,89 1148,57 116,36 281,01 4,24 Corridor 97,04 621,42 85,50 128,09 4,25 Forum 441,15 3396,06 104,19 582,32 4,41 Stair 6 44,48 180,19 27,20 88,49

4312,44 18429,89 1878,69 1854,35

3.1.5. Zone 5 – Gym

Name Area [m2]

Volume [m2]

Perimeter [m2]

External enclosure

[m2]

3,16 Dance Studio 72,95 240,72 35,80 69,73 3,20 Gym 551,74 5189,56 97,43 309,65 3,21 Gym coach 15,04 49,64 17,25 0,00

Zone 5 639,73 5479,92 150,48 379,38

3.1.6. Zone 6 – Rooms West IV, Performance

Name Area [m2]

Volume [m2]

Perimeter [m2]

External enclosure

[m2]

4,19 Class 47 24,01 177,28 21,04 31,69 4,33 Performance 47 233,19 1431,43 64,38 434,35 4,34 Performance G 18,62 132,71 19,01 56,02 4,35 Performance MEC 19,48 107,18 19,75 25,71 4,36 Sound Engineer 13,06 86,70 15,75 17,24

Zone 6 308,36 1935,30 139,93 565,02

Page 10: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 10

3.1.7. Zone 7 – Kitchen and Dining Areas

Name Area [m2]

Volume [m2]

Perimeter [m2]

External enclosure

[m2]

1,24 Dining 378,92 1932,50 94,88 202,83 1,29 IT Electric Util 9,36 43,50 12,33 0,00 1,30 IT Wiring 7,98 19,16 11,33 0,00 1,32 Kitchen 123,61 296,65 59,00 0,00 1,38 Office kitchen 11,55 48,51 13,78 15,24 1,39 Office phys plant 10,80 45,36 13,40 15,24 1,40 Office 44,94 208,99 27,05 0,00 1,42 Porch service entry 7,57 31,78 11,02 34,27 1,48 Refrigerator 16,18 38,82 17,08 16,45 1,55 Storage 10,01 46,52 12,71 0,00 1,56 Storage 15,14 36,33 16,73 0,00 1,61 Mezzanine 288,16 691,58 119,27 0,00

Zone 7 924,22 3439,70 408,58 284,01

3.1.8. Zone 8 / 1 – Basement conditioned

Name Area [m2]

Volume [m2]

Perimeter [m2]

External enclosure

[m2]

0,01 Cashier 17,72 66,45 18,23 41,83 0,05 Excercise 117,75 388,57 49,76 190,49 0,13 Lockers 307,42 1152,82 95,19 386,16 0,16 Lounge 77,73 291,48 37,01 127,10 0,20 Meeting 8,30 31,13 11,52 8,30 0,21 Meeting 9,45 35,44 12,32 22,50 0,24 Room 76,54 252,58 37,83 149,78 0,34 Toilet M Adm 21,98 72,53 19,90 44,03 0,35 Toilets F Adm 21,98 72,53 19,90 21,98

Zone 8 / 1 conditioned 658,87 2363,53 301,66 992,16

3.1.9. Zone 8 – Basement low unconditioned

Name Area [m2]

Volume [m2]

Perimeter [m2]

External enclosure

[m2]

0,04 Corridor West 58,74 211,46 59,82 58,74 0,07 IT Electric Util West 152,53 549,12 76,53 264,21 0,08 IT Electric Util North East 198,69 745,10 60,60 428,97 0,09 IT Electric Util 5,24 18,86 9,28 5,24 0,12 Library Storage 283,83 965,02 83,96 331,08 0,17 Mechanical North West 382,36 1376,48 100,00 720,76 0,18 Mechanical 2 138,23 497,62 48,90 245,68 0,22 Ramp 48,55 160,23 46,82 48,55 0,28 Stair 1 18,55 61,22 19,30 28,99

Zone 8 1286,72 4585,11 505,21 2132,22

3.2. The energy needs (for heating, cooling, ventilation and lighting) are determined separately for each zone of the building. For heating and cooling this is done by comparing the heat sources and heat sinks in the relevant zone.

Page 11: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 11

3.3. Zones Basement

Zone 1 North – West

Zone 2 South

Zone 3 South West

Zone 4 Forum

Zone 5 Gymnasium

Zone 6 West Performance

Zone 7 West Kitchen and Dining

Zone 8 Basement conditioned

Zone 8 Basement unconditioned

Page 12: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 12

3.4. Zones First Floor

Zone 1 North – West

Zone 2 South

Zone 3 South West

Zone 4 Forum

Zone 5 Gymnasium

Zone 6 West Performance

Zone 7 West Kitchen and Dining

Zone 8 Basement conditioned

Zone 8 Basement unconditioned

Page 13: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 13

3.5. Zones Mezzanine Floor

Zone 1 North – West

Zone 2 South

Zone 3 South West

Zone 4 Forum

Zone 5 Gymnasium

Zone 6 West Performance

Zone 7 West Kitchen and Dining

Zone 8 Basement conditioned

Zone 8 Basement unconditioned

Page 14: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 14

3.6. Zones Second Floor

Zone 1 North – West

Zone 2 South

Zone 3 South West

Zone 4 Forum

Zone 5 Gymnasium

Zone 6 West Performance

Zone 7 West Kitchen and Dining

Zone 8 Basement conditioned

Zone 8 Basement unconditioned

Page 15: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 15

3.7. Zones Third Floor

Zone 1 North – West

Zone 2 South

Zone 3 South West

Zone 4 Forum

Zone 5 Gymnasium

Zone 6 West Performance

Zone 7 West Kitchen and Dining

Zone 8 Basement conditioned

Zone 8 Basement unconditioned

Page 16: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 16

3.8. Zones Fourth Floor

Zone 1 North – West

Zone 2 South

Zone 3 South West

Zone 4 Forum

Zone 5 Gymnasium

Zone 6 West Performance

Zone 7 West Kitchen and Dining

Zone 8 Basement conditioned

Zone 8 Basement unconditioned

Page 17: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 17

4. Energy balance 4.1. General

Determination of energy requirements results directly from conditions of use as well as from utilities being provided. Energy requirement is to be classified as follows: - Lighting; electrical energy required to ensure adequate lighting of building, zone or room - Heating; quantity of supplementary heat to be provided to the building, zone or room in a

demand-controlled manner in order to maintain the internal set-point temperature. - Cooling; quantity of supplementary cooling energy to be provided to the building, zone or room

in a demand-controlled manner in order to maintain the internal set-point temperature. - Ventilation; amount of energy which has to be transferred to or from ventilation or AC-system

for heating and cooling in order to maintain the required air quality.

4.2. Tables on the following pages show detailed results and allocation of thermal losses and gains

Page 18: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 18

5. Lighting, internal gains and external gains 5.1. Zones overview

Zone Internal gain

(lighting) [W]

Internal gain

(Users) [W]

External gain

(insolation) [W]

Zone 1 39349 108800 31280 Zone 2

8673

44100 25938

Zone 3

21223

48200 24118 Zone 4

29677

103800 16767

Zone 5

3090

22200 1440 Zone 6

2347

21100 2440

Zone 7

7728

27700 27043 Zone 8 / 1 conditioned

3371

6600 0

Zone 8 / 2 unconditioned

7008

1300 0

122466 383800 129027

5.2. Table basement

Basement Name Illumination [lx] Internal

gain (lighting)

[W]

Users Internal gain

(Users) [W]

External gain

(insolation) [W]

0,01 Cashier 1000 285 3 300 0 0,02 Corridor Ante Admin 150 30 1 100 0 0,03 Corridor Admin 150 93 1 100 0 0,04 Corridor West 150 142 1 100 0 0,05 Excercise 300 569 14 3500 0 0,06 Faculty Lounge 500 531 20 2000 432 0,07 IT Electric Util West 150 368 1 100 0

0,08 IT Electric Util North East 150 480 1 100 0

0,09 IT Electric Util 150 13 1 100 0 0,10 Int Recruit 1000 162 2 200 216 0,11 JC 200 11 1 100 0 0,12 Library Storage 1000 4570 5 500 0 0,13 Lockers 200 990 1 100 0 0,14 Lockers F 200 56 5 500 0 0,15 Lockers M 200 80 8 800 162 0,16 Lounge 500 626 10 1000 0

0,17 Mechanical North West 150 924 1 100 0

0,18 Mechanical 2 150 334 1 100 0 0,19 Meeting 500 81 4 400 216 0,20 Meeting 500 67 4 400 0 0,21 Meeting 500 76 4 400 0 0,22 Ramp 150 117 1 100 0 0,23 Registrar 1000 660 7 700 432 0,24 Room 500 616 1 100 0 0,25 Room 150 58 1 100 0 0,26 Showers F 200 129 5 1500 0 0,27 Showers M 200 129 5 1500 323 0,28 Stair 1 200 60 1 100 0 0,29 Stair 3 200 89 1 100 0 0,30 Stair 5 200 57 1 100 0 0,31 Stair 4 200 78 1 100 0 0,32 Storage 500 121 1 100 0 0,33 Storage 500 203 1 100 0 0,34 Toilet M Adm 200 71 4 400 0 0,35 Toilets F Adm 200 71 4 400 0 0,36 Visa 1000 162 2 200 0 0,37 Visa 1000 163 2 200 0

Page 19: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 19

5.3. Table 1st floor

1st floor Name Illumination [lx] Internal

gain (lighting)

[W]

Users Internal gain

(Users) [W]

External gain

(insolation) [W]

1,01 Administration 1000 3508 27 2700 1512 1,02 Administration 1000 1283 12 1200 1789 1,03 Arcade 500 853 10 1000 0 1,04 COT 1000 113 1 100 367 1,05 Cafe 500 108 2 200 0 1,06 Career Service 1000 220 3 300 367 1,07 Class 1 500 368 20 2000 3690 1,08 Class 10 500 370 20 2000 0 1,09 Class 11 500 364 20 2000 0 1,10 Class 2 500 524 30 3000 1872 1,11 Class 3 500 371 20 2000 0 1,12 Class 4 500 371 20 2000 0 1,13 Class 5 500 371 20 2000 0 1,14 Class 6 500 370 20 2000 0 1,15 Class 7 500 370 20 2000 0 1,16 Class 8 500 370 20 2000 0 1,17 Class 9 500 370 20 2000 0

1,18 Clubs Volunteers 700 565 18 1800 0

1,19 Copier 500 68 1 100 0 1,20 Corridor 150 49 1 100 0 1,21 Corridor 150 318 1 100 0 1,22 Corridor North 150 273 1 100 0 1,23 Dean Students 1000 191 3 300 0 1,24 Dining 500 3051 152 15200 25891 1,25 Forum 500 4406 273 27300 0 1,26 Forum 500 452 28 2800 0 1,27 Green Room 1000 318 6 600 0 1,28 HR Director 1000 174 3 300 252 1,29 IT Electric Util 150 23 1 100 0 1,30 IT Wiring 150 19 1 100 0 1,31 JC 200 17 1 100 0 1,32 Kitchen 500 995 10 1000 0 1,33 Med Suite 1000 292 2 200 450 1,34 Med room 1000 408 4 400 899 1,35 Meeting 500 103 6 600 0 1,36 Meeting 500 157 6 600 0 1,37 Meeting 500 66 4 400 551 1,38 Office kitchen 1000 186 3 300 288 1,39 Office phys plant 1000 174 3 300 288 1,40 Office 1000 724 3 300 0 1,41 Office Security 1000 127 1 100 0

1,42 Porch service entry 300 37 1 100 288

1,43 Porch South 300 97 10 1000 0 1,44 Porch north 300 63 1 100 0 1,45 President 1000 261 3 300 0 1,46 Receive 1000 642 3 300 576 1,47 Reception med 1000 446 3 300 450 1,48 Refrigerator 300 78 1 100 288 1,49 Sound Studio 300 56 3 300 0 1,50 Stair 1 200 61 1 100 306 1,51 Stair 3 200 66 1 100 392 1,52 Stair 4 200 62 1 100 979 1,53 Stair 5 200 57 1 100 216 1,54 Stair 6 200 194 1 100 9178 1,55 Storage 300 48 1 100 0 1,56 Storage 300 73 1 100 0 1,57 Storage 300 326 1 100 0

1,58 Stud Coordinator 1000 807 18 1800 0

1,59 Toilets F 200 94 3 300 0 1,60 Toilets M 200 103 3 300 0

Page 20: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 20

5.4. Table Mezzanine Floor

Mezzanine Name Illumination [lx] Internal

gain (lighting)

[W]

Users Internal gain

(Users) [W]

External gain

(insolation) [W]

1,61 Mezzanine 500 2320 100 10000 0 1,62 Stair 3 200 64 1 100 0 1,63 Stair 4 200 60 1 100 0

5.5. Table 2nd floor

2nd floor Name Illumination [lx] Internal

gain (lighting)

[W]

Users Internal gain

(Users) [W]

External gain

(insolation) [W]

2,01 Acquisitions + Catal. 1000 752 3 300 2066

2,02 Cafe Study 1000 899 15 1500 2203 2,03 Class 12 500 346 20 2000 734 2,04 Class 13 500 263 16 1600 1224 2,05 Class 14 500 370 20 2000 734 2,06 Class 15 500 370 20 2000 1224 2,07 Class 16 500 370 20 2000 734 2,08 Class 17 500 370 20 2000 1224 2,09 Class 18 500 382 20 2000 734 2,10 Class 19 500 370 20 2000 1224 2,11 Class 20 500 593 41 4100 1440 2,12 Class 21 500 397 20 2000 0 2,13 Copy 1000 384 3 300 0 2,14 Corridor 200 613 1 100 0 2,15 Corridor 200 253 39 3900 0 2,16 Faculty chair 1000 1623 16 1600 2822 2,17 Forum 500 4705 0 0 0 2,18 Group study 1000 339 10 1000 0 2,19 Group study 1000 190 6 600 0 2,20 Group study 1000 191 6 600 0 2,21 Group study 1000 244 8 800 0 2,22 Group study 1000 127 4 400 0 2,23 IT Equipment 150 101 1 100 0 2,24 IT Workstations 500 1637 46 4600 1728 2,25 JC 200 16 1 100 0 2,26 Library 1000 379 6 600 0 2,27 Library 1000 1028 15 1500 3466 2,28 Library 1000 1116 16 1600 0 2,29 Library 1000 1200 17 1700 0 2,30 Literacy 500 557 25 2500 0 2,31 Meeting 1000 265 6 600 0

2,32 Meeting Research 1000 517 10 1000 0

2,33 Office 1 1000 165 4 400 720 2,34 Office 2 1000 165 4 400 0 2,35 Office 3 1000 171 2 200 0 2,36 Office 4 1000 178 4 400 0 2,37 Office Lib 1000 193 2 200 0 2,38 Research 1000 2138 10 1000 720 2,39 Room 1000 199 1 100 0 2,40 Room 1000 795 4 400 0 2,41 Room 1000 1201 10 1000 0 2,42 Stair 1 200 61 1 100 216 2,43 Stair 3 200 66 1 100 216 2,44 Stair 4 200 62 1 100 367 2,45 Stair 5 200 57 1 100 432 2,46 Stair 6 200 141 1 100 1224 2,47 Study Lounge 500 1749 60 6000 0 2,48 Study space 500 2086 50 5000 0 2,49 Study space 500 576 16 1600 0 2,50 Toilets F 200 94 3 300 0 2,51 Toilets M 200 95 3 300 0 2,52 Writing center 1000 1057 15 1500 0

Page 21: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 21

5.6. Table 3rd floor

3rd floor Name Illumination [lx] Internal

gain (lighting)

[W]

Users Internal gain

(Users) [W]

External gain

(insolation) [W]

3,01 Cafe / Study 500 464 15 1500 2203 3,02 Chairs 1000 1615 16 1600 2714 3,03 Class 22 500 344 20 2000 1944 3,04 Class 23 500 259 12 1200 734 3,05 Class 24 500 370 20 2000 1224 3,06 Class 25 500 370 20 2000 734 3,07 Class 26 500 370 20 2000 734 3,08 Class 27 500 377 20 2000 1224 3,09 Class 28 500 382 20 2000 1224 3,10 Class 29 500 370 20 2000 734 3,11 Conference 1000 514 8 800 0 3,12 Corridor 200 154 24 2400 0 3,13 Corridor 200 312 48 4800 0 3,14 Corridor 200 312 48 4800 0 3,15 Corridor 200 736 114 11400 0 3,16 Dance Studio 300 352 20 2000 1440 3,17 Director IRT 1000 246 3 300 1584 3,18 Director Library 1000 199 3 300 360 3,19 Forum 500 3539 1 100 0 3,20 Gym 300 2665 200 20000 0 3,21 Gym coach 300 73 2 200 0 3,22 ACCT Director 150 30 1 100 360 3,23 IT Electric Util 150 30 1 100 0 3,24 IT Electric Util 150 70 1 100 0 3,25 IT Electric Util 150 17 1 100 0 3,26 IT Workstations 500 1635 50 5000 2160 3,27 JC 200 14 1 100 0 3,28 Meeting Library 1000 170 4 400 360

3,29 Meeting Multimedia 1000 176 4 400 0

3,30 Meeting 1000 199 4 400 360 3,31 Multimedia 500 1157 40 4000 0 3,32 Office 1 1000 165 4 400 0 3,33 Office 2 1000 165 4 400 0 3,34 Office 3 1000 167 2 200 0 3,35 Office 4 1000 171 4 400 0 3,36 Pantry 500 251 7 700 0 3,37 Stacks 1000 4652 40 4000 1512

3,38 Staff ACCT/Library 1000 2133 25 2500 720

3,39 Stair 1 200 61 1 100 216 3,40 Stair 3 200 81 1 100 216 3,41 Stair 4 200 61 1 100 367 3,42 Stair 5 200 57 1 100 432 3,43 Stair 6 200 143 1 100 734 3,44 Storage 200 33 1 100 0 3,45 Study Balcony 500 506 18 1800 0 3,46 Toilets F 200 91 3 300 0 3,47 Toilets M 200 96 3 300 0

Page 22: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 22

5.7. Table 4th floor

4th floor Name Illumination [lx] Internal

gain (lighting)

[W]

Users Internal gain

(Users) [W]

External gain

(insolation) [W]

4,01 Study Balcony 500 515 18 1800 0 4,02 Cafe/Study 500 424 15 1500 2635 4,03 Class 31 500 263 12 1200 1224 4,04 Class 32 500 370 20 2000 734 4,05 Class 33 500 370 20 2000 1224 4,06 Class 34 500 371 20 2000 734 4,07 Class 35 500 370 20 2000 1224 4,08 Class 36 500 377 20 2000 734 4,09 Class 37 500 382 20 2000 734 4,10 Class 38 500 370 20 2000 1224 4,11 Class 39 500 807 50 5000 2714 4,12 Class 40 500 587 20 2000 1440 4,13 Class 41 500 370 20 2000 0 4,14 Class 42 500 370 20 2000 0 4,15 Class 43 500 370 20 2000 0 4,16 Class 44 500 370 20 2000 0 4,17 Class 45 500 751 50 5000 1080 4,18 Class 46 500 602 35 3500 2426 4,19 Class 47 500 193 5 500 0 4,20 Conference 1000 514 12 1200 0 4,21 Corridor 200 429 67 6700 0 4,22 Corridor 200 686 107 10700 0 4,23 Corridor 200 308 1 100 0 4,24 Corridor 200 313 49 4900 0 4,25 Forum 500 3552 1 100 0 4,26 IT Equipment 200 18 1 100 0 4,27 IT Workstations 500 1635 50 5000 1728 4,28 JC NW 200 18 1 100 0 4,29 Office 1 1000 167 4 400 0 4,30 Office 2 1000 169 4 400 0 4,31 Office 3 1000 171 2 200 0 4,32 Office 4 1000 173 4 400 0 4,33 Performance 47 500 1878 200 20000 2440 4,34 Performance G 500 150 2 200 0

4,35 Performance MEC 200 63 1 100 0

4,36 Sound Engineer 300 63 3 300 0 4,37 Stair 1 200 61 1 100 216 4,38 Stair 3 200 66 1 100 216 4,39 Stair 4 200 62 1 100 0 4,40 Stair 5 200 57 1 100 216 4,41 Stair 6 200 143 1 100 1224 4,42 Toilet F 200 90 3 300 0 4,43 Toilet M 200 103 3 300 0

Page 23: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 23

6. Heating requirement according to thermal losses 6.1. Basement

Basement Heating capacity in zones [kW] Name Basement

[Zone 8/1] Zone

1 Zone

2 Zone

3 Zone

4 Zone

5 Zone

6 Zone

7 Basement [Zone 8/2]

0,01 Cashier

0,58 0,02 Corridor Ante Admin

0,15

0,03 Corridor Admin

0,45 0,04 Corridor West 0,00

0,05 Excercise

2,50 0,06 Faculty Lounge

2,54

0,07 IT Electric Util West 0,00

0,08 IT Electric Util North East 0,00

0,09 IT Electric Util 0,00 0,10 Int Recruit

0,43 0,11 JC

0,04

0,12 Library Storage 0,00 0,13 Lockers

4,82 0,14 Lockers F

0,20

0,15 Lockers M

0,58 0,16 Lounge

1,67

0,17 Mechanical North West 0,00

0,18 Mechanical 2 0,00 0,19 Meeting

0,43 0,20 Meeting

0,10

0,21 Meeting

0,31 0,22 Ramp 0,00

0,23 Registrar

1,10 0,24 Room

2,02

0,25 Room

0,56 0,26 Showers F

0,88

0,27 Showers M

1,46 0,28 Stair 1 0,00

0,29 Stair 3

0,93 0,30 Stair 5 0,64

0,31 Stair 4 0,52 0,32 Storage

0,18

0,33 Storage

0,62 0,34 Toilet M Adm

0,60

0,60

0,35 Toilets F Adm

0,26

0,26 0,36 Visa

0,12

0,37 Visa

0,12

0,00 1,15 0,93 10,71 0,00 0,00 0,00 0,00 12,84

6.2. 1st floor

1st floor Zoning Name Basement

[Zone 8/1] Zone

1 Zone

2 Zone

3 Zone

4 Zone

5 Zone

6 Zone

7 Basement [Zone 8/2]

1,01 Administration

3,18 1,02 Administration

1,63

1,03 Arcade

0,29 1,04 COT

0,29

1,05 Cafe

0,00 1,06 Career Service

0,31

1,07 Class 1 2,94 1,08 Class 10 1,77 1,09 Class 11 1,08 1,10 Class 2 3,37 1,11 Class 3 1,22 1,12 Class 4 1,08

Page 24: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 24

1,13 Class 5 1,22 1,14 Class 6 1,08 1,15 Class 7 1,62 1,16 Class 8 1,77 1,17 Class 9 1,62

1,18 Clubs Volunteers 1,08

1,19 Copier

0,00 1,20 Corridor

0,00

1,21 Corridor 0,38 1,22 Corridor North 1,09 1,23 Dean Students 0,14 1,24 Dining

13,94

1,25 Forum

2,77 1,26 Forum

0,00

1,27 Green Room

0,00 1,28 HR Director

0,33

1,29 IT Electric Util

0,00 1,30 IT Wiring

0,00

1,31 JC 0,00 1,32 Kitchen

0,00

1,33 Med Suite 1,55 1,34 Med room 1,00 1,35 Meeting

0,00

1,36 Meeting

0,00 1,37 Meeting

0,36

1,38 Office kitchen

0,43 1,39 Office phys plant

0,43

1,40 Office

0,00 1,41 Office Security

0,00

1,42

Porch service entry

0,96

1,43 Porch South

0,00 1,44 Porch north 1,92

1,45 President

0,00 1,46 Receive 1,45

1,47 Reception med 0,51 1,48 Refrigerator

0,45

1,49 Sound Studio 0,14 1,50 Stair 1

0,35

1,51 Stair 3 1,05 1,52 Stair 4 0,68

1,53 Stair 5 0,57

1,54 Stair 6

0,00

1,55 Storage

0,00 1,56 Storage

0,00

1,57 Storage

0,00

1,58 Stud Coordinator 0,59

1,59 Toilets F 0,00 1,60 Toilets M 0,00

0,00 29,86 1,05 6,46 3,06 0,00 0,00 16,20 0,00

6.3. Mezzanine floor

Mezzanine Zoning Name Basement

[Zone 8/1] Zone

1 Zone

2 Zone

3 Zone

4 Zone

5 Zone

6 Zone

7 Basement [Zone 8/2]

1,61 Mezzanine

0,00 1,62 Stair 3 0,00

1,63 Stair 4 0,00

0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00

Page 25: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 25

6.4. 2nd floor

2nd floor Zoning Name Basement

[Zone 8/1] Zone

1 Zone

2 Zone

3 Zone

4 Zone

5 Zone

6 Zone

7 Basement [Zone 8/2]

2,01 Acquisitions + Catal. 2,12

2,02 Cafe Study

2,63 2,03 Class 12

2,94

2,04 Class 13

1,28 2,05 Class 14

1,09

2,06 Class 15

1,32 2,07 Class 16

1,09

2,08 Class 17

1,28 2,09 Class 18

1,09

2,10 Class 19

0,83 2,11 Class 20 2,33

2,12 Class 21 0,81 2,13 Copy 0,00 2,14 Corridor 0,00 2,15 Corridor

0,00

2,16 Faculty chair

2,52 2,17 Forum

0,00

2,18 Group study 0,00 2,19 Group study 0,00 2,20 Group study 0,00 2,21 Group study 0,00 2,22 Group study 0,00 2,23 IT Equipment 0,00 2,24 IT Workstations

3,51

2,25 JC 0,00 2,26 Library 0,00 2,27 Library 4,23 2,28 Library 0,00 2,29 Library 0,00 2,30 Literacy 1,60 2,31 Meeting 0,00

2,32 Meeting Research 0,00

2,33 Office 1

0,82 2,34 Office 2

0,00

2,35 Office 3

0,00 2,36 Office 4

0,00

2,37 Office Lib 0,00 2,38 Research 3,08 2,39 Room 0,00 2,40 Room 0,62 2,41 Room 1,44 2,42 Stair 1

0,31

2,43 Stair 3

0,31 2,44 Stair 4 0,34

2,45 Stair 5 0,63 2,46 Stair 6

1,36 2,47 Study Lounge

0,00

2,48 Study space

0,00 2,49 Study space

0,00

2,50 Toilets F 0,00 2,51 Toilets M 0,00 2,52 Writing center 1,44

0,00 18,64 11,23 7,16 3,99 0,00 0,00 0,00 0,00

Page 26: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 26

6.5. 3rd floor

3rd floor Zoning Name Basement

[Zone 8/1] Zone

1 Zone

2 Zone

3 Zone

4 Zone

5 Zone

6 Zone

7 Basement [Zone 8/2]

3,01 Cafe / Study

2,01 3,02 Chairs

2,47

3,03 Class 22

1,76 3,04 Class 23

0,62

3,05 Class 24

0,82 3,06 Class 25

0,64

3,07 Class 26

0,62 3,08 Class 27

0,82

3,09 Class 28

0,82 3,10 Class 29

0,65

3,11 Conference

0,00 3,12 Corridor

0,00

3,13 Corridor

0,00 3,14 Corridor

0,00

3,15 Corridor

0,00 3,16 Dance Studio

2,04

3,17 Director IRT 1,25 3,18 Director Library 0,41 3,19 Forum

0,00

3,20 Gym

6,49 3,21 Gym coach

0,00

3,22 ACCT Director 0,41 3,23 IT Electric Util 0,00 3,24 IT Electric Util 0,00 3,25 IT Electric Util 0,00 3,26 IT Workstations

3,80

3,27 JC 0,00 3,28 Meeting Library 0,41

3,29 Meeting Multimedia 0,41

3,30 Meeting 0,41 3,31 Multimedia 1,85 3,32 Office 1

0,00

3,33 Office 2

0,00 3,34 Office 3

0,00

3,35 Office 4

0,00 3,36 Pantry 0,00

3,37 Stacks 1,84

3,38 Staff ACCT/Library 2,89

3,39 Stair 1

0,31 3,40 Stair 3

0,31

3,41 Stair 4 0,34 3,42 Stair 5 0,65 3,43 Stair 6

0,62

3,44 Storage 0,14 3,45 Study Balcony

0,00

3,46 Toilets F 0,00 3,47 Toilets M 0,00

0,00 11,00 6,41 7,22 2,63 8,52 0,00 0,00 0,00

Page 27: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 27

6.6. 4th floor

4th floor Zoning Name Basement

[Zone 8/1] Zone

1 Zone

2 Zone

3 Zone

4 Zone

5 Zone

6 Zone

7 Basement [Zone 8/2]

4,01 Study Balcony

0,82 4,02 Cafe/Study

3,99

4,03 Class 31

1,49 4,04 Class 32

1,34

4,05 Class 33

1,53 4,06 Class 34

1,55

4,07 Class 35

1,82 4,08 Class 36

1,57

4,09 Class 37

1,52 4,10 Class 38

1,83

4,11 Class 39

4,47 4,12 Class 40 4,14

4,13 Class 41 1,33 4,14 Class 42 1,52 4,15 Class 43 1,42 4,16 Class 44 1,80 4,17 Class 45 4,77 4,18 Class 46 3,87 4,19 Class 47

0,31

4,20 Conference

0,41 4,21 Corridor

1,71

4,22 Corridor

2,72 4,23 Corridor 1,22

4,24 Corridor

1,24 4,25 Forum

5,65

4,26 IT Equipment 0,07 4,27 IT Workstations

7,33

4,28 JC NW 0,07 4,29 Office 1

0,13

4,30 Office 2

0,13 4,31 Office 3

0,14

4,32 Office 4

0,14 4,33 Performance 47

6,57

4,34 Performance G

0,72

4,35 Performance MEC

0,25

4,36 Sound Engineer

0,17 4,37 Stair 1

0,53

4,38 Stair 3

0,94 4,39 Stair 4 0,59

4,40 Stair 5 1,69 4,41 Stair 6

1,51

4,42 Toilet F 0,36 4,43 Toilet M 0,41

0,00 23,27 15,76 14,71 14,06 0,00 8,01 0,00 0,00

Page 28: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 28

7. Cooling requirements according to thermal gains 7.1. Basement

Basement Cooling capacity in zones [kW] Name Basement

[Zone 8/1] Zone

1 Zone

2 Zone

3 Zone

4 Zone

5 Zone

6 Zone

7 Basement [Zone 8/2]

0,01 Cashier

0,90 0,02 Corridor Ante Admin

0,21

0,03 Corridor Admin

0,44

0,04 Corridor West 0,38

0,05 Excercise

5,44 0,06 Faculty Lounge

4,36

0,07 IT Electric Util West 0,00

0,08 IT Electric Util North East 0,00

0,09 IT Electric Util 0,00

0,10 Int Recruit

0,82

0,11 JC

0,13

0,12 Library Storage 0,00

0,13 Lockers

3,73 0,14 Lockers F

0,67

0,15 Lockers M

1,36

0,16 Lounge

2,54

0,17 Mechanical North West 0,00

0,18 Mechanical 2 0,00

0,19 Meeting

0,93

0,20 Meeting

0,52 0,21 Meeting

0,65

0,22 Ramp 0,00

0,23 Registrar

2,39

0,24 Room

1,82 0,25 Room

0,47

0,26 Showers F

2,11

0,27 Showers M

2,75

0,28 Stair 1 0,00

0,29 Stair 3

0,70

0,30 Stair 5 0,35

0,31 Stair 4 0,28

0,32 Storage

0,32

0,33 Storage

0,64

0,34 Toilet M Adm

0,80

0,80 0,35 Toilets F Adm

0,61

0,61

0,36 Visa

0,43

0,37 Visa

0,43

0,38 0,63 0,70 19,87 0,00 0,00 0,00 0,00 17,02

7.2. 1st floor

1st floor Zoning Name Basement

[Zone 8/1] Zone

1 Zone

2 Zone

3 Zone

4 Zone

5 Zone

6 Zone

7 Basement [Zone 8/2]

1,01 Administration

9,46

1,02 Administration

5,17

1,03 Arcade

2,01

1,04 COT

0,74

1,05 Cafe

0,31

1,06 Career Service

1,06

1,07 Class 1 7,67

1,08 Class 10 3,34

1,09 Class 11 2,96

1,10 Class 2 7,25

1,11 Class 3 3,04

1,12 Class 4 2,96

Page 29: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 29

1,13 Class 5 3,04

1,14 Class 6 2,96

1,15 Class 7 3,26

1,16 Class 8 3,34

1,17 Class 9 3,26

1,18 Clubs Volunteers 2,96

1,19 Copier

0,17

1,20 Corridor

0,15

1,21 Corridor 0,63

1,22 Corridor North 0,97

1,23 Dean Students 0,57

1,24 Dining

51,80

1,25 Forum

33,23

1,26 Forum

3,25

1,27 Green Room

0,92

1,28 HR Director

0,91

1,29 IT Electric Util

0,12 1,30 IT Wiring

0,12

1,31 JC 0,12

1,32 Kitchen

2,00

1,33 Med Suite 1,79

1,34 Med room 2,26

1,35 Meeting

0,70

1,36 Meeting

0,76

1,37 Meeting

1,22

1,38 Office kitchen

1,01

1,39 Office phys plant

1,00 1,40 Office

1,02

1,41 Office Security

0,23

1,42 Porch service entry

0,95

1,43 Porch South

1,10

1,44 Porch north 1,22

1,45 President

0,56

1,46 Receive 2,31

1,47 Reception med 1,47

1,48 Refrigerator

0,71

1,49 Sound Studio 0,43

1,50 Stair 1

0,66

1,51 Stair 3 1,13

1,52 Stair 4 1,51

1,53 Stair 5 0,69

1,54 Stair 6

9,47

1,55 Storage

0,15 1,56 Storage

0,17

1,57 Storage

0,43

1,58 Stud Coordinator 2,93

1,59 Toilets F 0,39

1,60 Toilets M 0,40

0,00 63,74 1,13 22,70 49,79 0,00 0,00 59,04 0,00

7.3. Mezzanine

Mezzanine Zoning Name Basement

[Zone 8/1] Zone

1 Zone

2 Zone

3 Zone

4 Zone

5 Zone

6 Zone

7 Basement [Zone 8/2]

1,61 Mezzanine

12,32

1,62 Stair 3 0,16

1,63 Stair 4 0,16

0,00 0,32 0,00 0,00 0,00 0,00 0,00 12,32 0,00

Page 30: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 30

7.4. 2nd floor

2nd floor Zoning Name Basement

[Zone 8/1] Zone

1 Zone

2 Zone

3 Zone

4 Zone

5 Zone

6 Zone

7 Basement [Zone 8/2]

2,01 Acquisitions + Catal. 4,28

2,02 Cafe Study

6,05

2,03 Class 12

4,69

2,04 Class 13

3,79

2,05 Class 14

3,70

2,06 Class 15

4,32

2,07 Class 16

3,70

2,08 Class 17

4,30

2,09 Class 18

3,71

2,10 Class 19

4,05

2,11 Class 20 7,41

2,12 Class 21 2,84

2,13 Copy 0,68

2,14 Corridor 0,71

2,15 Corridor

4,15

2,16 Faculty chair

7,43

2,17 Forum

4,70

2,18 Group study 1,34

2,19 Group study 0,79

2,20 Group study 0,79

2,21 Group study 1,04

2,22 Group study 0,53

2,23 IT Equipment 0,20

2,24 IT Workstations

9,89

2,25 JC 0,12

2,26 Library 0,98

2,27 Library 8,31

2,28 Library 2,72

2,29 Library 2,90

2,30 Literacy 3,94

2,31 Meeting 0,86

2,32 Meeting Research 1,52

2,33 Office 1

1,73

2,34 Office 2

0,56

2,35 Office 3

0,37

2,36 Office 4

0,58

2,37 Office Lib 0,39

2,38 Research 5,55

2,39 Room 0,30

2,40 Room 1,54

2,41 Room 2,99

2,42 Stair 1

0,55

2,43 Stair 3

0,55

2,44 Stair 4 0,72

2,45 Stair 5 0,94

2,46 Stair 6

2,21

2,47 Study Lounge

7,75

2,48 Study space

7,09

2,49 Study space

2,18

2,50 Toilets F 0,39

2,51 Toilets M 0,40

2,52 Writing center 3,35

0,00 58,52 32,82 21,12 34,13 0,00 0,00 0,00 0,00

Page 31: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 31

7.5. 3rd floor

3rd floor Zoning Name Basement

[Zone 8/1] Zone

1 Zone

2 Zone

3 Zone

4 Zone

5 Zone

6 Zone

7 Basement [Zone 8/2]

3,01 Cafe / Study

5,27

3,02 Chairs

7,28

3,03 Class 22

5,25

3,04 Class 23

2,53

3,05 Class 24

4,04

3,06 Class 25

3,46

3,07 Class 26

3,45

3,08 Class 27

4,05

3,09 Class 28

4,05

3,10 Class 29

3,46

3,11 Conference

1,31

3,12 Corridor

2,55

3,13 Corridor

5,11

3,14 Corridor

5,11

3,15 Corridor

12,14

3,16 Dance Studio

4,91

3,17 Director IRT 2,82

3,18 Director Library 1,08

3,19 Forum

3,64

3,20 Gym

26,23

3,21 Gym coach

0,27

3,22 ACCT Director 0,71

3,23 IT Electric Util 0,13

3,24 IT Electric Util 0,17

3,25 IT Electric Util 0,12

3,26 IT Workstations

10,88

3,27 JC 0,11

3,28 Meeting Library 1,15

3,29 Meeting Multimedia 0,80

3,30 Meeting 1,18

3,31 Multimedia 6,17

3,32 Office 1

0,57

3,33 Office 2

0,56

3,34 Office 3

0,37

3,35 Office 4

0,57

3,36 Pantry 0,95

3,37 Stacks 11,18

3,38 Staff ACCT/Library 6,94

3,39 Stair 1

0,55

3,40 Stair 3

0,57

3,41 Stair 4 0,72

3,42 Stair 5 0,95

3,43 Stair 6

1,32

3,44 Storage 0,21

3,45 Study Balcony

2,31

3,46 Toilets F 0,39

3,47 Toilets M 0,40

0,00 36,17 27,41 24,24 38,76 31,41 0,00 0,00 0,00

Page 32: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 32

7.6. 4th floor

4th floor Zoning Name Basement

[Zone 8/1] Zone

1 Zone

2 Zone

3 Zone

4 Zone

5 Zone

6 Zone

7 Basement [Zone 8/2]

4,01 Study Balcony

2,77

4,02 Cafe/Study

6,75

4,03 Class 31

3,51

4,04 Class 32

3,84

4,05 Class 33

4,44

4,06 Class 34

3,96

4,07 Class 35

4,59

4,08 Class 36

3,97

4,09 Class 37

3,95

4,10 Class 38

4,60

4,11 Class 39

10,98

4,12 Class 40 6,30

4,13 Class 41 3,10

4,14 Class 42 3,21

4,15 Class 43 3,15

4,16 Class 44 3,36

4,17 Class 45 9,45

4,18 Class 46 8,66

4,19 Class 47

0,17

4,20 Conference

1,94

4,21 Corridor

8,07

4,22 Corridor

12,88

4,23 Corridor 1,08

4,24 Corridor

5,89

4,25 Forum

6,75

4,26 IT Equipment 0,16

4,27 IT Workstations

12,39

4,28 JC NW 0,16

4,29 Office 1

0,64

4,30 Office 2

0,64

4,31 Office 3

0,45

4,32 Office 4

0,65

4,33 Performance 47

3,60

4,34 Performance G

0,39

4,35 Performance MEC

0,14

4,36 Sound Engineer

0,09

4,37 Stair 1

0,67

4,38 Stair 3

0,90

4,39 Stair 4 0,49

4,40 Stair 5 1,30

4,41 Stair 6

2,30

4,42 Toilet F 0,59

4,43 Toilet M 0,63

0,00 41,61 35,91 31,01 40,59 0,00 4,40 0,00 0,00

Page 33: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 33

8. Air handling and Ventilation 8.1. Basement

Basement Airflow capacity in zones [cfm] Name Area

[m2] Volume

[m3] Basement [Zone 8/1]

Zone 1

Zone 2

Zone 3

Zone 4

Zone 5

Zone 6

Zone 7

Basement [Zone 8/2]

0,01 Cashier 17,72 66,45

78 0,02 Corridor Ante Admin 12,50 41,23

24

0,03 Corridor Admin 38,35 126,55

74

0,04 Corridor West 58,74 211,46 124

0,05 Excercise 117,75 388,57

915 0,06 Faculty Lounge 65,95 217,62

256

0,07 IT Electric Util West 152,53 549,12 323

0,08 IT Electric Util North East 198,69 745,10 439

0,09 IT Electric Util 5,24 18,86 11

0,10 Int Recruit 10,06 33,21

39

0,11 JC 3,54 11,70

14

0,12 Library Storage 283,83 965,02 1136

0,13 Lockers 307,42 1152,82

2036 0,14 Lockers F 17,36 57,29

101

0,15 Lockers M 24,77 81,74

144

0,16 Lounge 77,73 291,48

686

0,17 Mechanical North West 382,36 1376,48 810

0,18 Mechanical 2 138,23 497,62 293

0,19 Meeting 10,06 33,21

39

0,20 Meeting 8,30 31,13

37 0,21 Meeting 9,45 35,44

42

0,22 Ramp 48,55 160,23 94

0,23 Registrar 40,97 135,20

159

0,24 Room 76,54 252,58

149 0,25 Room 24,06 79,41

47

0,26 Showers F 40,06 132,19

467

0,27 Showers M 39,91 131,72

465

0,28 Stair 1 18,55 61,22 36

0,29 Stair 3 27,73 74,86

44

0,30 Stair 5 17,63 66,12 39

0,31 Stair 4 24,25 87,31 51

0,32 Storage 15,01 49,52

29

0,33 Storage 25,19 83,12

49

0,34 Toilet M Adm 21,98 72,53

256

256 0,35 Toilets F Adm 21,98 72,53

256

256

0,36 Visa 10,06 33,21

39

0,37 Visa 10,10 33,32

39

8.2. 1st floor

1st floor Airflow capacity in zones [cfm] Name Area

[m2] Volume

[m3] Basement [Zone 8/1]

Zone 1

Zone 2

Zone 3

Zone 4

Zone 5

Zone 6

Zone 7

Basement [Zone 8/2]

1,01 Administration 217,85 653,54

769

1,02 Administration 79,68 239,03

281

1,03 Arcade 105,99 540,54

636

1,04 COT 7,02 28,43

33

1,05 Cafe 13,47 54,54

128

1,06 Career Service 13,66 40,99

48

1,07 Class 1 45,66 232,85

274

1,08 Class 10 46,00 234,60

276

1,09 Class 11 45,20 230,52

271

1,10 Class 2 65,12 332,09

391

1,11 Class 3 46,14 235,33

277

1,12 Class 4 46,14 235,33

277

1,13 Class 5 46,14 235,33

277

1,14 Class 6 46,00 234,60

276

Page 34: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 34

1,15 Class 7 46,00 234,60

276

1,16 Class 8 46,00 234,60

276

1,17 Class 9 46,00 234,60

276

1,18 Clubs Volunteers 50,12 202,99

239

1,19 Copier 8,45 25,34

30

1,20 Corridor 20,41 61,22

36

1,21 Corridor 131,46 670,45

395

1,22 Corridor North 113,17 577,19

340

1,23 Dean Students 11,86 48,03

57

1,24 Dining 378,92 1932,50

4550

1,25 Forum 547,18 2216,09

5217

1,26 Forum 56,13 227,33

535

1,27 Green Room 19,77 59,31

70

1,28 HR Director 10,78 32,34

38

1,29 IT Electric Util 9,36 43,50

26 1,30 IT Wiring 7,98 19,16

11

1,31 JC 5,18 26,43

31

1,32 Kitchen 123,61 296,65

1397

1,33 Med Suite 18,13 73,42

173

1,34 Med room 25,31 102,50

241

1,35 Meeting 12,84 38,51

45

1,36 Meeting 19,52 58,56

69

1,37 Meeting 8,16 24,47

29

1,38 Office kitchen 11,55 48,51

114

1,39 Office phys plant 10,80 45,36

107 1,40 Office 44,94 208,99

246

1,41 Office Security 7,87 31,85

37

1,42 Porch service entry 7,57 31,78

150

1,43 Porch South 20,14 81,58

384

1,44 Porch north 12,94 65,98

311

1,45 President 16,23 48,68

57

1,46 Receive 39,89 203,43

239

1,47 Reception med 27,69 112,15

132

1,48 Refrigerator 16,18 38,82

46

1,49 Sound Studio 11,60 46,99

111

1,50 Stair 1 18,90 56,70

33

1,51 Stair 3 20,62 49,48

29

1,52 Stair 4 19,30 98,44

58

1,53 Stair 5 17,63 71,41

42

1,54 Stair 6 60,22 243,88

144

1,55 Storage 10,01 46,52

27 1,56 Storage 15,14 36,33

21

1,57 Storage 67,55 334,37

197

1,58 Stud Coordinator 50,14 203,05

239

1,59 Toilets F 29,05 148,14

349

1,60 Toilets M 32,12 163,79

386

8.3. Mezzanine

Mezzanine Airflow capacity in zones [cfm] Name Area

[m2] Volume

[m3] Basement [Zone 8/1]

Zone 1

Zone 2

Zone 3

Zone 4

Zone 5

Zone 6

Zone 7

Basement [Zone 8/2]

1,61 Mezzanine 288,16 691,58

1628

1,62 Stair 3 19,89 47,74

28

1,63 Stair 4 18,65 44,75

26

Page 35: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 35

8.4. 2nd floor

2nd floor Airflow capacity in zones [cfm] Name Area

[m2] Volume

[m2] Basement [Zone 8/1]

Zone 1

Zone 2

Zone 3

Zone 4

Zone 5

Zone 6

Zone 7

Basement [Zone 8/2]

2,01 Acquisitions + Catal. 46,73 154,20

182

2,02 Cafe Study 55,80 184,15

434

2,03 Class 12 43,03 142,01

167

2,04 Class 13 32,67 107,81

127

2,05 Class 14 46,00 151,80

179

2,06 Class 15 46,00 151,80

179

2,07 Class 16 46,00 151,80

179

2,08 Class 17 46,00 151,80

179

2,09 Class 18 47,40 156,42

184

2,10 Class 19 46,00 151,80

179

2,11 Class 20 73,67 243,12

286

2,12 Class 21 49,35 162,86

192

2,13 Copy 23,84 78,66

93

2,14 Corridor 190,28 627,93

370

2,15 Corridor 78,44 258,85

152

2,16 Faculty chair 100,77 332,55

391

2,17 Forum 584,37 1928,42

4540

2,18 Group study 21,04 69,42

82

2,19 Group study 11,81 38,98

46

2,20 Group study 11,86 39,14

46

2,21 Group study 15,13 49,91

59

2,22 Group study 7,91 26,09

31

2,23 IT Equipment 41,68 137,55

162

2,24 IT Workstations 203,37 671,13

790

2,25 JC 4,90 16,17

19

2,26 Library 23,56 75,39

89

2,27 Library 63,81 261,64

308

2,28 Library 69,30 252,95

298

2,29 Library 74,50 245,84

289

2,30 Literacy 69,20 228,36

269

2,31 Meeting 16,44 52,60

62

2,32 Meeting Research 32,13 106,04

125

2,33 Office 1 10,23 33,74

40

2,34 Office 2 10,23 33,74

40

2,35 Office 3 10,64 35,10

41

2,36 Office 4 11,08 36,57

43

2,37 Office Lib 11,97 39,52

47

2,38 Research 132,78 438,18

516

2,39 Room 12,38 40,84

48

2,40 Room 49,35 162,86

192

2,41 Room 74,61 246,21

290

2,42 Stair 1 19,08 62,96

37

2,43 Stair 3 20,62 68,03

40

2,44 Stair 4 19,14 63,16

37

2,45 Stair 5 17,63 58,18

34

2,46 Stair 6 43,88 144,79

85

2,47 Study Lounge 217,20 716,77

844

2,48 Study space 259,07 854,94

1006

2,49 Study space 71,52 271,76

320

2,50 Toilets F 29,22 96,41

227

2,51 Toilets M 29,55 97,52

230

2,52 Writing center 65,61 216,51

255

Page 36: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 36

8.5. 3rd floor

3rd floor Airflow capacity in zones [cfm] Name Area

[m2] Volume

[m2] Basement [Zone 8/1]

Zone 1

Zone 2

Zone 3

Zone 4

Zone 5

Zone 6

Zone 7

Basement [Zone 8/2]

3,01 Cafe / Study 57,58 190,02

224

3,02 Chairs 100,27 330,88

389

3,03 Class 22 42,75 141,08

166

3,04 Class 23 32,13 106,04

125

3,05 Class 24 46,00 151,80

179

3,06 Class 25 46,00 151,80

179

3,07 Class 26 46,00 151,80

179

3,08 Class 27 46,80 154,44

182

3,09 Class 28 47,40 156,42

184

3,10 Class 29 46,00 151,80

179

3,11 Conference 31,91 105,31

124

3,12 Corridor 47,89 158,03

93

3,13 Corridor 96,89 319,73

188

3,14 Corridor 96,98 320,03

188

3,15 Corridor 228,52 754,12

444

3,16 Dance Studio 72,95 240,72

850

3,17 Director IRT 15,29 50,44

59

3,18 Director Library 12,36 40,80

48

3,19 Forum 439,59 1582,52

3726

3,20 Gym 551,74 5189,56

18327

3,21 Gym coach 15,04 49,64

175

3,22 ACCT Director 12,36 40,80

48

3,23 IT Electric Util 12,54 41,38

24

3,24 IT Electric Util 28,79 94,99

56

3,25 IT Electric Util 7,02 23,17

14

3,26 IT Workstations 203,13 670,32

789

3,27 JC 4,49 14,82

17

3,28 Meeting Library 10,56 34,84

41

3,29 Meeting Multimedia 10,91 36,01

42

3,30 Meeting 12,36 40,80

48

3,31 Multimedia 143,67 474,10

558

3,32 Office 1 10,27 33,89

40

3,33 Office 2 10,23 33,74

40

3,34 Office 3 10,35 34,14

40

3,35 Office 4 10,64 35,10

41

3,36 Pantry 31,22 103,02

243

3,37 Stacks 288,88 953,30

1122

3,38 Staff ACCT/Library 132,46 437,12

515

3,39 Stair 1 18,91 68,06

40

3,40 Stair 3 25,19 90,70

53

3,41 Stair 4 18,89 62,35

37

3,42 Stair 5 17,63 63,47

37

3,43 Stair 6 44,44 159,97

94

3,44 Storage 10,14 33,45

20

3,45 Study Balcony 62,86 207,43

244

3,46 Toilets F 28,24 93,18

2578

3,47 Toilets M 29,73 98,11

231

Page 37: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 37

8.6. 4th floor

4th floor Airflow capacity in zones [cfm] Name Area

[m2] Volume

[m2] Basement [Zone 8/1]

Zone 1

Zone 2

Zone 3

Zone 4

Zone 5

Zone 6

Zone 7

Basement [Zone 8/2]

4,01 Study Balcony 64,01 404,04

476

4,02 Cafe/Study 52,66 337,21

397

4,03 Class 31 32,70 183,63

216

4,04 Class 32 46,00 192,28

226

4,05 Class 33 46,00 192,28

226

4,06 Class 34 46,14 267,25

315

4,07 Class 35 46,00 335,37

395

4,08 Class 36 46,80 305,06

359

4,09 Class 37 47,40 231,30

272

4,10 Class 38 46,00 298,71

352

4,11 Class 39 100,27 649,21

764

4,12 Class 40 72,95 466,45

549

4,13 Class 41 46,00 192,28

226

4,14 Class 42 46,00 192,28

226

4,15 Class 43 46,00 258,29

304

4,16 Class 44 46,00 325,91

384

4,17 Class 45 93,29 543,97

640

4,18 Class 46 74,77 390,24

459

4,19 Class 47 24,01 177,28

209

4,20 Conference 31,91 86,16

101

4,21 Corridor 133,34 738,28

435

4,22 Corridor 212,89 1148,57

676

4,23 Corridor 95,71 526,81

310

4,24 Corridor 97,04 621,42

366

4,25 Forum 441,15 3396,06

7995

4,26 IT Equipment 5,45 31,96

38

4,27 IT Workstations 203,13 1313,76

1546

4,28 JC NW 5,49 36,39

43

4,29 Office 1 10,38 70,87

83

4,30 Office 2 10,52 71,87

85

4,31 Office 3 10,64 72,66

86

4,32 Office 4 10,77 73,46

86

4,33 Performance 47 233,19 1431,43

3370

4,34 Performance G 18,62 132,71

312

4,35 Performance MEC 19,48 107,18

252

4,36 Sound Engineer 13,06 86,70

204

4,37 Stair 1 18,91 106,03

62

4,38 Stair 3 20,39 144,16

85

4,39 Stair 4 19,30 138,83

82

4,40 Stair 5 17,63 119,94

71

4,41 Stair 6 44,48 180,19

106

4,42 Toilet F 27,98 139,78

329

4,43 Toilet M 31,86 158,73

374

8.7. lkjh

Page 38: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 38

9. Summarized loads by zones Name Area

[m2] Volume

[m3] Heating

load (kW)

Cooling load (kW)

Airflow [CFM]

Zone 1 4160,30 17705,69 83,92

201,01

21495,63 Zone 2 1157,08 4694,98 35,37

97,97

5222,59

Zone 3 2078,87 8044,56 46,27

118,94

10551,45 Zone 4 4312,44 18429,89 23,73

163,27

29633,40

Zone 5 639,73 5479,92 8,52

31,41

19352,15 Zone 6 308,36 1935,30 8,01

4,40

4138,93

Zone 7 924,22 3439,70 16,20

71,36

8322,71 Zone 8 / 1 conditioned 658,87 2363,53 12,84

17,02

4454,14

Zone 8 / 2 unconditioned 1286,72 4585,11 0,00

0,38

3266,68 Total 15526,59 66678,68 234,86 705,77 106437,67

Name Area [m2]

Volume [m3]

Heating load

(MBH)

Cooling load

(Tons)

Airflow [CFM]

Zone 1 4160,30 17705,69 286,41195

57,153867

21495,63 Zone 2 1157,08 4694,98 120,71056

27,855563

5222,59

Zone 3 2078,87 8044,56 157,91886

33,820005

10551,45 Zone 4 4312,44 18429,89 81,006143

46,424485

29633,40

Zone 5 639,73 5479,92 29,094219

8,9310802

19352,15 Zone 6 308,36 1935,30 27,332051

1,2501304

4138,93

Zone 7 924,22 3439,70 55,284524

20,291292

8322,71 Zone 8 / 1 conditioned 658,87 2363,53 43,821949

4,8393899

4454,14

Zone 8 / 2 unconditioned 1286,72 4585,11 0

0,107977

3266,68

Total 15526,59 66678,68 801,58025 200,67379 106437,67

Page 39: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 39

10. Summarized loads by areas 10.1. Basement

Basement Name Area

[m2] Volume

[m3] Heating

load (kW)

Heating load

(W/m2)

Cooling load (kW)

Cooling load

(W/m2)

Heating load (kW) VAC

Heating load

(W/m2) VAC

Cooling load (kW) VAC

Cooling load

(W/m2) VAC

0,01 Cashier 17,72 66,45 0,58 33 0,90 0 0,81 46 0,44 25 0,02 Corridor Ante Admin 12,50 41,23 0,15 12 0,21 0 0,50 40 0,27 22 0,03 Corridor Admin 38,35 126,55 0,45 12 0,44 0 1,54 40 0,84 22 0,04 Corridor West 58,74 211,46 0,00 0 0,38 0 0,00 0 1,41 24 0,05 Excercise 117,75 388,57 2,50 21 5,44 0 4,72 40 2,59 22 0,06 Faculty Lounge 65,95 217,62 2,54 39 4,36 0 2,64 40 1,45 22 0,07 IT Electric Util West 152,53 549,12 0,00 0 0,00 0 0,00 0 0,00 0 0,08 IT Electric Util North East 198,69 745,10 0,00 0 0,00 0 0,00 0 0,00 0 0,09 IT Electric Util 5,24 18,86 0,00 0 0,00 0 0,00 0 0,00 0 0,10 Int Recruit 10,06 33,21 0,43 43 0,82 0 0,40 40 0,22 22 0,11 JC 3,54 11,70 0,04 12 0,13 0 0,14 40 0,08 22 0,12 Library Storage 283,83 965,02 0,00 0 0,00 0 0,00 0 0,00 0 0,13 Lockers 307,42 1152,82 4,82 16 3,73 0 13,99 46 7,68 25 0,14 Lockers F 17,36 57,29 0,20 12 0,67 0 0,70 40 0,38 22 0,15 Lockers M 24,77 81,74 0,58 23 1,36 0 0,99 40 0,54 22 0,16 Lounge 77,73 291,48 1,67 21 2,54 0 3,54 46 1,94 25 0,17 Mechanical North West 382,36 1376,48 0,00 0 0,00 0 0,00 0 0,00 0 0,18 Mechanical 2 138,23 497,62 0,00 0 0,00 0 0,00 0 0,00 0 0,19 Meeting 10,06 33,21 0,43 43 0,93 0 0,40 40 0,22 22 0,20 Meeting 8,30 31,13 0,10 12 0,52 0 0,38 46 0,21 25 0,21 Meeting 9,45 35,44 0,31 33 0,65 0 0,43 46 0,24 25 0,22 Ramp 48,55 160,23 0,00 0 0,00 0 0,00 0 0,00 0 0,23 Registrar 40,97 135,20 1,10 27 2,39 0 1,64 40 0,90 22 0,24 Room 76,54 252,58 2,02 26 1,82 0 3,07 40 1,68 22 0,25 Room 24,06 79,41 0,56 23 0,47 0 0,96 40 0,53 22 0,26 Showers F 40,06 132,19 0,88 22 2,11 0 1,60 40 0,88 22 0,27 Showers M 39,91 131,72 1,46 37 2,75 0 1,60 40 0,88 22 0,28 Stair 1 18,55 61,22 0,00 0 0,00 0 0,00 0 0,00 0 0,29 Stair 3 27,73 74,86 0,93 33 0,70 0 0,91 33 0,50 18 0,30 Stair 5 17,63 66,12 0,64 36 0,35 0 0,80 46 0,44 25 0,31 Stair 4 24,25 87,31 0,52 21 0,28 0 1,06 44 0,58 24 0,32 Storage 15,01 49,52 0,18 12 0,32 0 0,60 40 0,33 22 0,33 Storage 25,19 83,12 0,62 25 0,64 0 1,01 40 0,55 22 0,34 Toilet M Adm 21,98 72,53 1,19 54 1,60 0 0,88 40 0,48 22 0,35 Toilets F Adm 21,98 72,53 0,52 24 1,23 0 0,88 40 0,48 22 0,36 Visa 10,06 33,21 0,12 12 0,43 0 0,40 40 0,22 22 0,37 Visa 10,10 33,32 0,12 12 0,43 0 0,40 40 0,22 22

10.2. 1st floor

1st floor Name Area

[m2] Volume

[m3] Heating

load (kW)

Heating load

(W/m2)

Cooling load (kW)

Cooling load

(W/m2)

Heating load (kW) VAC

Heating load

(W/m2) VAC

Cooling load (kW) VAC

Cooling load

(W/m2) VAC

1,01 Administration 217,85 653,54 3,18 15 9,46 0,04 7,93 36 4,36 20

1,02 Administration 79,68 239,03 1,63 20 5,17 0 2,90 36 1,59 20 1,03 Arcade 105,99 540,54 0,29 3 2,01 0 6,56 62 3,60 34 1,04 COT 7,02 28,43 0,29 42 0,74 0 0,35 49 0,19 27 1,05 Cafe 13,47 54,54 0,00 0 0,31 0 0,66 49 0,36 27 1,06 Career Service 13,66 40,99 0,31 23 1,06 0 0,50 36 0,27 20 1,07 Class 1 45,66 232,85 2,94 64 7,67 0 2,83 62 1,55 34 1,08 Class 10 46,00 234,60 1,77 38 3,34 0 2,85 62 1,56 34 1,09 Class 11 45,20 230,52 1,08 24 2,96 0 2,80 62 1,54 34 1,10 Class 2 65,12 332,09 3,37 52 7,25 0 4,03 62 2,21 34 1,11 Class 3 46,14 235,33 1,22 27 3,04 0 2,86 62 1,57 34 1,12 Class 4 46,14 235,33 1,08 23 2,96 0 2,86 62 1,57 34 1,13 Class 5 46,14 235,33 1,22 27 3,04 0 2,86 62 1,57 34 1,14 Class 6 46,00 234,60 1,08 23 2,96 0 2,85 62 1,56 34

Page 40: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 40

1,15 Class 7 46,00 234,60 1,62 35 3,26 0 2,85 62 1,56 34 1,16 Class 8 46,00 234,60 1,77 38 3,34 0 2,85 62 1,56 34 1,17 Class 9 46,00 234,60 1,62 35 3,26 0 2,85 62 1,56 34 1,18 Clubs Volunteers 50,12 202,99 1,08 22 2,96 0 2,46 49 1,35 27 1,19 Copier 8,45 25,34 0,00 0 0,17 0 0,31 36 0,17 20 1,20 Corridor 20,41 61,22 0,00 0 0,15 0 0,74 36 0,41 20 1,21 Corridor 131,46 670,45 0,38 3 0,63 0 8,14 62 4,47 34 1,22 Corridor North 113,17 577,19 1,09 10 0,97 0 7,01 62 3,85 34 1,23 Dean Students 11,86 48,03 0,14 12 0,57 0 0,58 49 0,32 27 1,24 Dining 378,92 1932,50 13,94 37 51,80 0 23,46 62 12,88 34 1,25 Forum 547,18 2216,09 2,77 5 33,23 0 26,90 49 14,77 27 1,26 Forum 56,13 227,33 0,00 0 3,25 0 2,76 49 1,51 27 1,27 Green Room 19,77 59,31 0,00 0 0,92 0 0,72 36 0,40 20 1,28 HR Director 10,78 32,34 0,33 30 0,91 0 0,39 36 0,22 20 1,29 IT Electric Util 9,36 43,50 0,00 0 0,12 0 0,53 56 0,29 31 1,30 IT Wiring 7,98 19,16 0,00 0 0,12 0 0,23 29 0,13 16 1,31 JC 5,18 26,43 0,00 0 0,12 0 0,32 62 0,18 34 1,32 Kitchen 123,61 296,65 0,00 0 2,00 0 3,60 29 1,98 16 1,33 Med Suite 18,13 73,42 1,55 85 1,79 0 0,89 49 0,49 27 1,34 Med room 25,31 102,50 1,00 40 2,26 0 1,24 49 0,68 27 1,35 Meeting 12,84 38,51 0,00 0 0,70 0 0,47 36 0,26 20 1,36 Meeting 19,52 58,56 0,00 0 0,76 0 0,71 36 0,39 20 1,37 Meeting 8,16 24,47 0,36 44 1,22 0 0,30 36 0,16 20 1,38 Office kitchen 11,55 48,51 0,43 37 1,01 0 0,59 51 0,32 28 1,39 Office phys plant 10,80 45,36 0,43 40 1,00 0 0,55 51 0,30 28 1,40 Office 44,94 208,99 0,00 0 1,02 0 2,54 56 1,39 31 1,41 Office Security 7,87 31,85 0,00 0 0,23 0 0,39 49 0,21 27 1,42 Porch service entry 7,57 31,78 0,96 126 0,95 0 0,39 51 0,21 28 1,43 Porch South 20,14 81,58 0,00 0 1,10 0 0,99 49 0,54 27 1,44 Porch north 12,94 65,98 1,92 149 1,22 0 0,80 62 0,44 34 1,45 President 16,23 48,68 0,00 0 0,56 0 0,59 36 0,32 20 1,46 Receive 39,89 203,43 1,45 36 2,31 0 2,47 62 1,36 34 1,47 Reception med 27,69 112,15 0,51 18 1,47 0 1,36 49 0,75 27 1,48 Refrigerator 16,18 38,82 0,45 28 0,71 0 0,47 29 0,26 16 1,49 Sound Studio 11,60 46,99 0,14 12 0,43 0 0,57 49 0,31 27 1,50 Stair 1 18,90 56,70 0,35 19 0,66 0 0,69 36 0,38 20 1,51 Stair 3 20,62 49,48 1,05 51 1,13 0 0,60 29 0,33 16 1,52 Stair 4 19,30 98,44 0,68 35 1,51 0 1,19 62 0,66 34 1,53 Stair 5 17,63 71,41 0,57 32 0,69 0 0,87 49 0,48 27 1,54 Stair 6 60,22 243,88 0,00 0 9,47 0 2,96 49 1,63 27 1,55 Storage 10,01 46,52 0,00 0 0,15 0 0,56 56 0,31 31 1,56 Storage 15,14 36,33 0,00 0 0,17 0 0,44 29 0,24 16 1,57 Storage 67,55 334,37 0,00 0 0,43 0 4,06 60 2,23 33 1,58 Stud Coordinator 50,14 203,05 0,59 12 2,93 0 2,46 49 1,35 27 1,59 Toilets F 29,05 148,14 0,00 0 0,39 0 1,80 62 0,99 34 1,60 Toilets M 32,12 163,79 0,00 0 0,40 0 1,99 62 1,09 34

10.3. Mezzanine

Mezzanine Name Area

[m2] Volume

[m3] Heating

load (kW)

Heating load

(W/m2)

Cooling load (kW)

Cooling load

(W/m2)

Heating load (kW) VAC

Heating load

(W/m2) VAC

Cooling load (kW) VAC

Cooling load

(W/m2) VAC

1,61 Mezzanine 288,16 691,58 0,00 0 12,32 0 8,39 29 4,61 16

1,62 Stair 3 19,89 47,74 0,00 0 0,16 0 0,58 29 0,32 16 1,63 Stair 4 18,65 44,75 0,00 0 0,16 0 0,54 29 0,30 16

Page 41: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 41

10.4. 2nd floor

2nd floor Name Area

[m2] Volume

[m3] Heating

load (kW)

Heating load

(W/m2)

Cooling load (kW)

Cooling load

(W/m2)

Heating load (kW) VAC

Heating load

(W/m2) VAC

Cooling load (kW) VAC

Cooling load

(W/m2) VAC

2,01 Acquisitions + Catal. 46,73 154,20 2,12 45 4,28 0 1,87 40 1,03 22

2,02 Cafe Study 55,80 184,15 2,63 47 6,05 0 2,24 40 1,23 22 2,03 Class 12 43,03 142,01 2,94 68 4,69 0 1,72 40 0,95 22 2,04 Class 13 32,67 107,81 1,28 39 3,79 0 1,31 40 0,72 22 2,05 Class 14 46,00 151,80 1,09 24 3,70 0 1,84 40 1,01 22 2,06 Class 15 46,00 151,80 1,32 29 4,32 0 1,84 40 1,01 22 2,07 Class 16 46,00 151,80 1,09 24 3,70 0 1,84 40 1,01 22 2,08 Class 17 46,00 151,80 1,28 28 4,30 0 1,84 40 1,01 22 2,09 Class 18 47,40 156,42 1,09 23 3,71 0 1,90 40 1,04 22 2,10 Class 19 46,00 151,80 0,83 18 4,05 0 1,84 40 1,01 22 2,11 Class 20 73,67 243,12 2,33 32 7,41 0 2,95 40 1,62 22 2,12 Class 21 49,35 162,86 0,81 16 2,84 0 1,98 40 1,09 22 2,13 Copy 23,84 78,66 0,00 0 0,68 0 0,95 40 0,52 22 2,14 Corridor 190,28 627,93 0,00 0 0,71 0 7,62 40 4,18 22 2,15 Corridor 78,44 258,85 0,00 0 4,15 0 3,14 40 1,72 22 2,16 Faculty chair 100,77 332,55 2,52 25 7,43 0 4,04 40 2,22 22 2,17 Forum 584,37 1928,42 0,00 0 4,70 0 23,41 40 12,85 22 2,18 Group study 21,04 69,42 0,00 0 1,34 0 0,84 40 0,46 22 2,19 Group study 11,81 38,98 0,00 0 0,79 0 0,47 40 0,26 22 2,20 Group study 11,86 39,14 0,00 0 0,79 0 0,48 40 0,26 22 2,21 Group study 15,13 49,91 0,00 0 1,04 0 0,61 40 0,33 22 2,22 Group study 7,91 26,09 0,00 0 0,53 0 0,32 40 0,17 22 2,23 IT Equipment 41,68 137,55 0,00 0 0,20 0 1,67 40 0,92 22 2,24 IT Workstations 203,37 671,13 3,51 17 9,89 0 8,15 40 4,47 22 2,25 JC 4,90 16,17 0,00 0 0,12 0 0,20 40 0,11 22 2,26 Library 23,56 75,39 0,00 0 0,98 0 0,92 39 0,50 21 2,27 Library 63,81 261,64 4,23 66 8,31 0 3,18 50 1,74 27 2,28 Library 69,30 252,95 0,00 0 2,72 0 3,07 44 1,69 24 2,29 Library 74,50 245,84 0,00 0 2,90 0 2,98 40 1,64 22 2,30 Literacy 69,20 228,36 1,60 23 3,94 0 2,77 40 1,52 22 2,31 Meeting 16,44 52,60 0,00 0 0,86 0 0,64 39 0,35 21 2,32 Meeting Research 32,13 106,04 0,00 0 1,52 0 1,29 40 0,71 22 2,33 Office 1 10,23 33,74 0,82 80 1,73 0 0,41 40 0,22 22 2,34 Office 2 10,23 33,74 0,00 0 0,56 0 0,41 40 0,22 22 2,35 Office 3 10,64 35,10 0,00 0 0,37 0 0,43 40 0,23 22 2,36 Office 4 11,08 36,57 0,00 0 0,58 0 0,44 40 0,24 22 2,37 Office Lib 11,97 39,52 0,00 0 0,39 0 0,48 40 0,26 22 2,38 Research 132,78 438,18 3,08 23 5,55 0 5,32 40 2,92 22 2,39 Room 12,38 40,84 0,00 0 0,30 0 0,50 40 0,27 22 2,40 Room 49,35 162,86 0,62 13 1,54 0 1,98 40 1,09 22 2,41 Room 74,61 246,21 1,44 19 2,99 0 2,99 40 1,64 22 2,42 Stair 1 19,08 62,96 0,31 16 0,55 0 0,76 40 0,42 22 2,43 Stair 3 20,62 68,03 0,31 15 0,55 0 0,83 40 0,45 22 2,44 Stair 4 19,14 63,16 0,34 18 0,72 0 0,77 40 0,42 22 2,45 Stair 5 17,63 58,18 0,63 36 0,94 0 0,71 40 0,39 22 2,46 Stair 6 43,88 144,79 1,36 31 2,21 0 1,76 40 0,96 22 2,47 Study Lounge 217,20 716,77 0,00 0 7,75 0 8,70 40 4,78 22 2,48 Study space 259,07 854,94 0,00 0 7,09 0 10,38 40 5,70 22 2,49 Study space 71,52 271,76 0,00 0 2,18 0 3,30 46 1,81 25 2,50 Toilets F 29,22 96,41 0,00 0 0,39 0 1,17 40 0,64 22 2,51 Toilets M 29,55 97,52 0,00 0 0,40 0 1,18 40 0,65 22 2,52 Writing center 65,61 216,51 1,44 22 3,35 0 2,63 40 1,44 22

Page 42: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 42

10.5. 3rd floor

3rd floor Name Area

[m2] Volume

[m3] Heating

load (kW)

Heating load

(W/m2)

Cooling load (kW)

Cooling load

(W/m2)

Heating load (kW) VAC

Heating load

(W/m2) VAC

Cooling load (kW) VAC

Cooling load

(W/m2) VAC

3,01 Cafe / Study 57,58 190,02 2,01 35 5,27 0 2,31 40 1,27 22

3,02 Chairs 100,27 330,88 2,47 25 7,28 0 4,02 40 2,20 22 3,03 Class 22 42,75 141,08 1,76 41 5,25 0 1,71 40 0,94 22 3,04 Class 23 32,13 106,04 0,62 19 2,53 0 1,29 40 0,71 22 3,05 Class 24 46,00 151,80 0,82 18 4,04 0 1,84 40 1,01 22 3,06 Class 25 46,00 151,80 0,64 14 3,46 0 1,84 40 1,01 22 3,07 Class 26 46,00 151,80 0,62 14 3,45 0 1,84 40 1,01 22 3,08 Class 27 46,80 154,44 0,82 17 4,05 0 1,87 40 1,03 22 3,09 Class 28 47,40 156,42 0,82 17 4,05 0 1,90 40 1,04 22 3,10 Class 29 46,00 151,80 0,65 14 3,46 0 1,84 40 1,01 22 3,11 Conference 31,91 105,31 0,00 0 1,31 0 1,28 40 0,70 22 3,12 Corridor 47,89 158,03 0,00 0 2,55 0 1,92 40 1,05 22 3,13 Corridor 96,89 319,73 0,00 0 5,11 0 3,88 40 2,13 22 3,14 Corridor 96,98 320,03 0,00 0 5,11 0 3,88 40 2,13 22 3,15 Corridor 228,52 754,12 0,00 0 12,14 0 9,15 40 5,03 22 3,16 Dance Studio 72,95 240,72 2,04 28 4,91 0 2,92 40 1,60 22 3,17 Director IRT 15,29 50,44 1,25 82 2,82 0 0,61 40 0,34 22 3,18 Director Library 12,36 40,80 0,41 33 1,08 0 0,50 40 0,27 22 3,19 Forum 439,59 1582,52 0,00 0 3,64 0 19,21 44 10,55 24 3,20 Gym 551,74 5189,56 6,49 12 26,23 0 62,99 114 34,58 63 3,21 Gym coach 15,04 49,64 0,00 0 0,27 0 0,60 40 0,33 22 3,22 ACCT Director 12,36 40,80 0,41 33 0,71 0 0,50 40 0,27 22 3,23 IT Electric Util 12,54 41,38 0,00 0 0,13 0 0,50 40 0,28 22 3,24 IT Electric Util 28,79 94,99 0,00 0 0,17 0 1,15 40 0,63 22 3,25 IT Electric Util 7,02 23,17 0,00 0 0,12 0 0,28 40 0,15 22 3,26 IT Workstations 203,13 670,32 3,80 19 10,88 0 8,14 40 4,47 22 3,27 JC 4,49 14,82 0,00 0 0,11 0 0,18 40 0,10 22 3,28 Meeting Library 10,56 34,84 0,41 39 1,15 0 0,42 40 0,23 22 3,29 Meeting Multimedia 10,91 36,01 0,41 37 0,80 0 0,44 40 0,24 22 3,30 Meeting 12,36 40,80 0,41 33 1,18 0 0,50 40 0,27 22 3,31 Multimedia 143,67 474,10 1,85 13 6,17 0 5,75 40 3,16 22 3,32 Office 1 10,27 33,89 0,00 0 0,57 0 0,41 40 0,23 22 3,33 Office 2 10,23 33,74 0,00 0 0,56 0 0,41 40 0,22 22 3,34 Office 3 10,35 34,14 0,00 0 0,37 0 0,41 40 0,23 22 3,35 Office 4 10,64 35,10 0,00 0 0,57 0 0,43 40 0,23 22 3,36 Pantry 31,22 103,02 0,00 0 0,95 0 1,25 40 0,69 22 3,37 Stacks 288,88 953,30 1,84 6 11,18 0 11,57 40 6,35 22 3,38 Staff ACCT/Library 132,46 437,12 2,89 22 6,94 0 5,31 40 2,91 22 3,39 Stair 1 18,91 68,06 0,31 16 0,55 0 0,83 44 0,45 24 3,40 Stair 3 25,19 90,70 0,31 12 0,57 0 1,10 44 0,60 24 3,41 Stair 4 18,89 62,35 0,34 18 0,72 0 0,76 40 0,42 22 3,42 Stair 5 17,63 63,47 0,65 37 0,95 0 0,77 44 0,42 24 3,43 Stair 6 44,44 159,97 0,62 14 1,32 0 1,94 44 1,07 24 3,44 Storage 10,14 33,45 0,14 13 0,21 0 0,41 40 0,22 22 3,45 Study Balcony 62,86 207,43 0,00 0 2,31 0 2,52 40 1,38 22 3,46 Toilets F 28,24 93,18 0,00 0 0,39 0 1,13 40 0,62 22 3,47 Toilets M 29,73 98,11 0,00 0 0,40 0 1,19 40 0,65 22

Page 43: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 43

10.6. 4th floor

4th floor Name Area

[m2] Volume

[m3] Heating

load (kW)

Heating load

(W/m2)

Cooling load (kW)

Cooling load

(W/m2)

Heating load (kW) VAC

Heating load

(W/m2) VAC

Cooling load (kW) VAC

Cooling load

(W/m2) VAC

4,01 Study Balcony 64,01 404,04 0,82 13 2,77 0 4,90 77 2,69 42

4,02 Cafe/Study 52,66 337,21 3,99 76 6,75 0 4,09 78 2,25 43 4,03 Class 31 32,70 183,63 1,49 46 3,51 0 2,23 68 1,22 37 4,04 Class 32 46,00 192,28 1,34 29 3,84 0 2,33 51 1,28 28 4,05 Class 33 46,00 192,28 1,53 33 4,44 0 2,33 51 1,28 28 4,06 Class 34 46,14 267,25 1,55 34 3,96 0 3,24 70 1,78 39 4,07 Class 35 46,00 335,37 1,82 40 4,59 0 4,07 88 2,23 49 4,08 Class 36 46,80 305,06 1,57 34 3,97 0 3,70 79 2,03 43 4,09 Class 37 47,40 231,30 1,52 32 3,95 0 2,81 59 1,54 33 4,10 Class 38 46,00 298,71 1,83 40 4,60 0 3,63 79 1,99 43 4,11 Class 39 100,27 649,21 4,47 45 10,98 0 7,88 79 4,33 43 4,12 Class 40 72,95 466,45 4,14 57 6,30 0 5,66 78 3,11 43 4,13 Class 41 46,00 192,28 1,33 29 3,10 0 2,33 51 1,28 28 4,14 Class 42 46,00 192,28 1,52 33 3,21 0 2,33 51 1,28 28 4,15 Class 43 46,00 258,29 1,42 31 3,15 0 3,14 68 1,72 37 4,16 Class 44 46,00 325,91 1,80 39 3,36 0 3,96 86 2,17 47 4,17 Class 45 93,29 543,97 4,77 51 9,45 0 6,60 71 3,63 39 4,18 Class 46 74,77 390,24 3,87 52 8,66 0 4,74 63 2,60 35 4,19 Class 47 24,01 177,28 0,31 13 0,17 0 2,15 90 1,18 49 4,20 Conference 31,91 86,16 0,41 13 1,94 0 1,05 33 0,57 18 4,21 Corridor 133,34 738,28 1,71 13 8,07 0 8,96 67 4,92 37 4,22 Corridor 212,89 1148,57 2,72 13 12,88 0 13,94 65 7,65 36 4,23 Corridor 95,71 526,81 1,22 13 1,08 0 6,39 67 3,51 37 4,24 Corridor 97,04 621,42 1,24 13 5,89 0 7,54 78 4,14 43 4,25 Forum 441,15 3396,06 5,65 13 6,75 0 41,22 93 22,63 51 4,26 IT Equipment 5,45 31,96 0,07 13 0,16 0 0,39 71 0,21 39 4,27 IT Workstations 203,13 1313,76 7,33 36 12,39 0 15,95 79 8,75 43 4,28 JC NW 5,49 36,39 0,07 13 0,16 0 0,44 80 0,24 44 4,29 Office 1 10,38 70,87 0,13 13 0,64 0 0,86 83 0,47 45 4,30 Office 2 10,52 71,87 0,13 13 0,64 0 0,87 83 0,48 46 4,31 Office 3 10,64 72,66 0,14 13 0,45 0 0,88 83 0,48 46 4,32 Office 4 10,77 73,46 0,14 13 0,65 0 0,89 83 0,49 45 4,33 Performance 47 233,19 1431,43 6,57 28 3,60 0 17,37 75 9,54 41 4,34 Performance G 18,62 132,71 0,72 39 0,39 0 1,61 87 0,88 47 4,35 Performance MEC 19,48 107,18 0,25 13 0,14 0 1,30 67 0,71 37 4,36 Sound Engineer 13,06 86,70 0,17 13 0,09 0 1,05 81 0,58 44 4,37 Stair 1 18,91 106,03 0,53 28 0,67 0 1,29 68 0,71 37 4,38 Stair 3 20,39 144,16 0,94 46 0,90 0 1,75 86 0,96 47 4,39 Stair 4 19,30 138,83 0,59 31 0,49 0 1,69 87 0,93 48 4,40 Stair 5 17,63 119,94 1,69 96 1,30 0 1,46 83 0,80 45 4,41 Stair 6 44,48 180,19 1,51 34 2,30 0 2,19 49 1,20 27 4,42 Toilet F 27,98 139,78 0,36 13 0,59 0 1,70 61 0,93 33 4,43 Toilet M 31,86 158,73 0,41 13 0,63 0 1,93 60 1,06 33

Page 44: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 44

11. General recommendations for construction 11.1. For typical exterior construction, the following sketch is drafted by the architect:

Comments: - A window-ledge has to be considered outside - Respecting seismic requirements, the masonry should be choosen at low density. (U-

value is calculated based on concrete backer, therefore any reduction in weight will have a positive impact.)

- Waterproof membrane shall be avoided

Page 45: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 45

11.2. Calculation od layers

In general, the external wall consists of 250 mm reinforced concrete [or any other masonry / the lighter, the better]. Instead of a patching mortar, an adhesive layer of synthetic resin should be used for mounting Styrofoam (12 mm) layers. The reinforced plaster consists of cementitius plaster with reinforcement mats and a final topcoated exterior rendering.

Temperatures within the construction are shown as follows:

Temperature

Interior [cm] exterior

This graph shows the temperature (black line) with an ambient interior temperature of +20°C and an ambient exterior temperature of -10°C. The blue line shows the temperature of the dew point. At this temperature water vapor condenses. As long as the temperature is beyond the dew point temperature, no condensate occurs. The graph shows no contact of the lines, therefore no water has to be expected within the construction layers. U-value: 0.30 W/m2K Moisture: 0 g/m2 Heat storage capacity: 151 Wh/m2K Temp. surface inside: 18.8 °C Temp. surface outside: -9.6 °C The temperature on the inner surface is 11.7°C and surface moisture is 85% based on above mentioned conditions. Mould formation already starts at a moisture of 80%! Mould has to be expected!

Temperature Dew point Melting water Gypsum plaster 10 mm Concrete reinforced 250 mm Synt. resin plaster 20 mm Styrofoam 120 mm Reinforced plaster 25 mm topcoated

Page 46: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 46

Vapour pressure and saturated vapour pressure:

Interior [cm] exterior

Air moisture: The temperature on the inner surface of the construction will be 18.8 °C, therefore the relative humidity at the surface will be at 54%. Within these conditions mold will not arise. The following diagram shows the percentage of vapour saturation pressure:

Interior [cm] exterior

Vapour pressure Saturation pressure Gypsum plaster 10 mm Concrete reinforced 250 mm Synt. resin plaster 20 mm Styrofoam 120 mm Reinforced plaster 25 mm topcoated

Vapour saturation pressure (%) Gypsum plaster 10 mm Concrete reinforced 250 mm Synt. resin plaster 20 mm Styrofoam 120 mm Reinforced plaster 25 mm topcoated

Page 47: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 47

11.3. Required glazing specifications:

Advanced architectural glazing [Guardian sunguard specifications are available in Kyrgyzstan] is available as follows:

SuperNeutral 68 (#2) SuperNeutral Outboard Substrate: CrystalGray Inboard Substrate: Clear Exterior Appearance: Light Gray

Transmission Visible Light %: 49 UV %: 17 Solar Energy %: 24

Reflectivity Visible Light Out %: 8 Visible Light In %: 11 Solar Energy %: 16

U-Value Winter Nighttime: 0.29 Summer Daytime: 0.28

Relative Heat Gain: 72 Shading Coefficient: 0.34 Solar Heat Gain Coefficient: 0.30

Light-to-Solar Gain: 1.65

1 2 3 4

Exterior

Interior

Page 48: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 48

SNX 62/27 (#2) SuperNeutral Outboard Substrate: UltraWhite™ Inboard Substrate: UltraWhite™ Exterior Appearance: Ultra Clear

Transmission Visible Light %: 63 UV %: 6 Solar Energy %: 24

Reflectivity Visible Light Out %: 11 Visible Light In %: 12 Solar Energy %: 48

U-Value Winter Nighttime: 0.28 Summer Daytime: 0.27

Relative Heat Gain: 65 Shading Coefficient: 0.30 Solar Heat Gain Coefficient: 0.27

Light-to-Solar Gain: 2.37

1 2 3 4

Exterior

Interior

Page 49: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 49

12. Shallow geothermal energy utilization 12.1. Interior system:

12.1.1. Total heat pump capacity to be installed for HVAC: 1,200 kW (ca. 340 tons) 12.1.2. No. of heat pumps: 20 (each 60 kW) 12.1.3. 2 central pumping systems for two grids

12.2. Ground-source system: [in-situ tests required]

12.2.1. Geologic Materials: Basin filled sediments 12.2.2. Mean annual ground temperature at - 10 m: > 11°C 12.2.3. Mean annual ground temperature at – 200 m: > 17°C 12.2.4. Type: Vertical closed loop, duplex U-tubes 12.2.5. Configuration: 69 boreholes on two equilateral-triangle grid-pattern

Grid 1: Quad North, 30 boreholes Grid 2: Quad south, 39 boreholes

12.2.6. Borehole per kW: 11.5 m/kW

12.3. Plan, schematic

Page 50: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 50

13. Heating pump Sample of available product (European standard) in Kyrgyzstan

Тепловые насосы Logatherm WPS Тепловые насосы Buderus Logatherm WPS рассол-вода. Мощность 22, 33, 43, 52, 60 кВт

Применение

Здания гражданского и промышленного назначения. Объекты, где предъявляются повышенные требования по экологии либо отсутствует доступ к традиционным энергоносителям, прежде всего газу и жидкому топливу.

Принцип действия

Принцип действия теплового насоса основан на использовании тепловой энергии, извлеченной из воздуха, воды или почвы, для обогрева помещения. Высокий коэффициент преобразования позволяет получить до 5 кВт тепловой энергии, затратив при этом всего 1 кВт электрической.

Увеличить

Тепловые насосы Buderus Logatherm WPS рассол-вода

Тепловой насос Buderus Logatherm WPS рассол-вода

Высочайшее качество исполнения оборудования, основанное на отлаженном производственном процессе, многолетнем опыте производителя;

Рассольно / водяные тепловые насосы Buderus мощностью 22, 33, 43, 52, 60 кВт;

Эффективная система отопления и ГВС с температурой подачи до 65 0C;

Высокий коэффициент преобразования до 5 единиц; Встроенное цифровое управление, русифицированное меню; Эффективный теплообменник; Независимый герметичный контур хладагента (<6кг); Легкость в обслуживании, доступ через открывающуюся

переднюю панель; Мягкий старт снижает пиковые нагрузки при старте; 4 встроенных циркуляционных насоса для рассола и горячей

воды; Чрезвычайно тихая работа. Виброзащита компрессора и

шумоизоляция (40 dB WPS22); Компактность оборудования, обеспечивающая экономию

места и удобство при монтаже; Возможность интеграции в интеллектуальные системы

управления зданием;

Page 51: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 51

14. Floor plans 14.1. Site plan

Page 52: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 52

14.2. Basement

Page 53: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 53

14.3. 1st floor

Page 54: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 54

14.4. Mezzanine

Page 55: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 55

14.5. 2nd floor

Page 56: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 56

14.6. 3rd floor

Page 57: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 57

14.7. 4th floor

Page 58: [AUCA REPORT II] · 2011. 5. 10. · OcOO House of Sustainability Prof. Kai Schlenther, Managing Director Manas 38 Bishkek, Kyrgyz Republic +997 312 31 26 29 +996 771 10 24 80 kaischlenther@ymail.com

© House of Sustainability 2011 Report 2011_AUCA_ph2_Page 58