Upload
aande-aande-aande
View
2.418
Download
588
Tags:
Embed Size (px)
Citation preview
Transfer Panel ATITechnical Instruction Manual
2 SOCOMEC - Rf.: 678 623 G GB
GENERAL SAFETY INSTRUCTIONSa. This leaflet provides indispensable
instructions in terms of the safety,the connection and the operation ofthe automatic transfer switch.
b. This system must exclusively beinstalled by specialised, qualifiedpersonnel.
c. Before making the connections, it isessential that the earth cable be con-nected.
d. Keep the cabinet clean using a drycloth.
e. It is recommended that this leafletbe kept in a place easily accessibleto all those who may need it.
f. The maintenance operations mustbe carried out exclusively by autho-rised and appropriately trained per-sonnel.
g. This system complies with the com-munity directives applicable to thisproduct. Thus, it bears the CE mark.
h. Compliance with IEC 60947-6-1.
i. Information available in this instruc-tion manual are not contractual.
SOCOMEC - Rf.: 678 623 G GB 3
ENGL
ISH
INTRODUCTION________________________________________________ 4 - 6GENERAL INTRODUCTION ____________________________________ 4ATI TRANSFER PANEL RANGE_________________________________ 4NEW MOTORIZED CHANGEOVER SWITCH _____________________ 4OPTIONS AVAILABILITY _______________________________________ 5ENVIRONMENT ______________________________________________ 6
TECHNICAL CARACTERISTICS_____________________________________ 6
ENCLOSURES INSTALLATION _________________________________ 7 - 37 FIRST OPERATIONS ______________________________________ 7 - 10BOTTOM CABLE ENTRY ENCLOSURES ___________________ 11 - 16TOP CABLE ENTRY ENCLOSURES _______________________ 17 - 22OPTIONAL CONNECTIONS ______________________________ 23 - 34GENERAL POINTS___________________________________________ 34
VOLTAGE CONFIGURATIONS _________________________________ 35 - 42VOLTAGE OPTIONS__________________________________________ 35CABLE CONNECTIONS BETWEEN SWITCHAND ELECTRONIC MODULE _________________________________ 35ELECTRONIC MODULE CONNECTIONS _______________________ 36
INPUTS AND OUTPUT CONTACTS ________________________________ 40
CURRENT INPUTS (for metering) __________________________________ 40
BASIC PRODUCT USE________________________________________ 42 - 62 GENERAL INTRODUCTION ___________________________________ 42ELECTRONIC MODULE USAGE __________________________ 42 - 43PROGRAMMING ACCESS____________________________________ 43PROGRAMMING EXIT________________________________________ 43PROGRAMMING MENUS_____________________________________ 44SETUP MENU___________________________________________ 45 - 46VOLTAGE MENU ________________________________________ 47 - 48FREQUENCY MENU _____________________________________ 48 - 49TIMERS MENU__________________________________________ 49 - 50COMMUNICATION MENU ________________________________ 50 - 52MANUAL MODE_____________________________________________ 53AUTOMATIC MODE__________________________________________ 54LOSS OF MAINS AUTOMATIC SEQUENCE _____________________ 55MAINS RETURN AUTOMATIC SEQUENCE _________________ 56 - 57TEST MODE ACCESS________________________________________ 58TEST MODE EXIT____________________________________________ 58OFF LOAD TESTING _________________________________________ 59ON LOAD TESTING __________________________________________ 60
METERING PRODUCT USE _______________________________________ 61 GENERAL INTRODUCTION ___________________________________ 61ELECTRONIC MODULE USAGE __________________________ 61 - 62PROGRAMMING ACCESS____________________________________ 62PROGRAMMING EXIT________________________________________ 62PROGRAMMING MENUS_____________________________________ 63SETUP MENU___________________________________________ 64 - 65VOLTAGE MENU ________________________________________ 66 - 67FREQUENCY MENU _____________________________________ 67 - 68TIMERS MENU__________________________________________ 68 - 69COMMUNICATION MENU ____________________________________ 69PRODUCT METERING ___________________________________ 70 - 71MANUAL MODE_____________________________________________ 72MAINS RETURN AUTOMATIC SEQUENCE _____________________ 72TEST MODE ACCESS________________________________________ 73TEST MODE EXIT____________________________________________ 73
COMMUNICATION ___________________________________________ 74 - 77LIST OF PARAMETERS TO BE DISPLAYED_________________ 74 - 77SAVED COMMAND __________________________________________ 77
MAINTENANCE ______________________________________________ 78 - 81
FAULT FINDING GUIDE ___________________________________________ 82
4 SOCOMEC - Rf.: 678 623 G GB
INTRODUCTION
GENERAL INTRODUCTION
NEW ATI enclosure integrates a new4-pole changeover switch includingelectronics control to meet standardIEC 60947-6-1. Thanks to the chan-geover switch technology, it is alwayspossible to manually operate the sys-tem to guarantee the changeover paneloperation in any situation.The new enclosure design allowsswitch front panel access to: Avoid opening of the enclosure for
manual operation Allow electronic module access for
programming and monitoring
Simplify connections between themechanical switch and the electronicmodule.
With the mode switch in manual posi-tion, Padlocking, as well as handleinsertion operations are then directlyaccessible from the front panel.The electronic module, also accessiblefrom the front panel, includes: Sources monitoring Metering display (V and f as standard) Test operations and Sequences pro-
gramming using keypad.
ATI 1000 A ATI 1250 A ATI 1600 A
New ATI range modelsMODEL ATI 250 A ATI 400 A ATI 630 A ATI 800 A
ATI TRANSFER PANEL RANGE
The new ATI panel range will be available from 250 A to 1600 A.
1. A mechanical switch.2. A motorized block to operate the switch electrically.3. An electronic module on the top of the motorized block, driving loss of mains
and mains return sequence.4. A reset button.
NEW MOTORIZED CHANGEOVER SWITCH
The new switch included in the enclosure is made of 3 different parts:
Standard offer includes Bottom cable entry. Top cable entry is offered as anoption.
Features and benefits: The new Motorisation block is inclu-
ded in a moulded case It is possible to remove the motorized
block and the electronic modulewithout being obliged to disconnectthe power cables
Manual operation directly acts on theshaft of the mechanical switch forbetter reliability
The complete enclosure meets stan-dard IEC 60947-6-1 (ATS applications)
The enclosure is self-powered (fromMain and Gen sources). There is noneed for an external power source toallow automatic sequence after lossof power
All thresholds and timers can be setusing the display and the keypad, orvia modbus (optional)
The standard product integratesvoltage and frequency control forbetter diagnostic
Main sensing circuit is 3 phases andGen sensing circuit is single phase
Standard product includes, phase tophase + phase to neutral voltagemeasurement and displays systemfrequency (phase 1) and switch num-ber of operations.
The product including metering allowscurrent measurement as well as powermetering (kW, kVar, kVA and PF).
12
3
4
ATI
035
A
SOCOMEC - Rf.: 678 623 G GB 5
ENGL
ISH
Option 9: Top Cable Entry. For cables to be
routed through the top rather thanbottom. Option code is TICT.
Option 6: Auxiliary contacts for switch posi-
tion information, padlocking andAuto/Manual mode information areoptionally available. Option code isTAUX.
INTRODUCTION (continued)
OPTIONS AVAILABILITY
Factory options are delivered pre-installed in the enclosures
Option 5: A switch allowing 277 Vac specific
voltage option for customers requi-ring voltage code V601 (480/277 Vac).Option code is THVM.
Option 1: A metering module allowing standard
features + current and power meter-ing facilities on a larger backlit display.This option also integrates option 6(TAUX). Option code is TMET & TAUX.
Option 7: 2IN/2OUT.1 plug in module allowing
auxiliary contacts for Main andGenerator available information is alsoavailable as an option. Option code isTIO2.
Option 8: 1 plug in communication module,
JBUS / MODBUS protocole, canoptionally be ordered allowing remotecommunication of the changeoversystem. Option code is TCOM.
Option 2: IP54 protection rating is available as
an option. A specific protection win-dow must be installed on the frontpanel of the enclosure to avoid waterinfiltration in the enclosure. Optioncode is TIP5.
Option 3: Solid neutral link is available as an
option on the switch itself, whenswitching of the neutral cable is notrequired. Option code is TLNK.
Option 4: Lightning protection is also available
as an option to avoid ATS damage incase of a strike on the power cables.This option is highly recommendedin stormy areas. Option code is TLPRand TI02 is included.
Loose options are available, for customer mounting in the enclosures
Option 2IP54 Protection Kit
Option 72In / 2Out
Option 3Solid NeutralOption 6
Auxiliary contacts
Option 4Lightning Protection
Option 1Metering Option
Option 5Voltage 277 VAC
Option 8Communication
Option 9Top Cable Entry
ATI
036
A G
B
6 SOCOMEC - Rf.: 678 623 G GB
ENVIRONMENT
Ingress protection of IP41 with overallrating of IP21
Operating temperature of 10 C to40 C without de-rating
Operating temperature of 40 C to65 C with de-rating
The complete enclosure meets following environmental requirements:
INTRODUCTION (continued)
TECHNICAL CARACTERISTICSCharacteristicsThermal Current Ith (40 C) 250 A 400 A 630 A 800A 1000A 1250 A 1600 AAssigned isolement voltage Ui (V) 800 800 1000 1000 1000 1000 1000Assigned voltage to chocks Uimp (kV) 8 8 12 12 12 12 12
IEC 60947-6-1 CharacteristicsAssigned current Ie (A) (B categorie)415 Vac AC31B 250 400 630 800 1000 1250 1600Operating ClassMaterial class PC PC PC PC PC PC PCMaximum short circuit current using gG DIN fuseMax short circuit (kA eff) 50 18 70 50 100 100 100Fuse size (A) 250 400 630 800 1000 1250 2 x 800Peak current value: withstand and closing operation (kA peak) 23 23 45 48 75 75 75Short circuit OperationRated short time withstand current (kA eff) 10 10 12.6 16 20 25 32Rated short circuit making capacity (kA max) 17 17 25.2 27.2 40 52.5 67
Other CharacteristicsCommutation durationI-II ou II-I (s) (1) 1.3 1.3 1.3 2.6 2.6 2.8 2.8I-o ou II-0 (s) (1) 0.85 0.85 0.85 1.6 1.6 1.7 1.7Black time durating during commutation under Un (ms) 600 600 600 1 500 1500 1700 1700Power input230 Vac mini /maxi (V) 184/276 184/276 184/276 184/276 184/276 210/310 210/310277 Vac mini /maxi (V) - Option 5 221/332 221/332 221/332 221/332 221/332 240/380 240/380Consumption during switching operation230 Vac maxi /average (VA) 400/100 400/100 420/110 450/120 450/120 470/128 470/128277 Vac maxi /average (VA) - Option 5 400/110 400/110 420/115 450/125 450/125 470/128 470/128Mechanical characteristicsNumber of commutation (durability) 8000 8000 5000 4000 4000 3000 3000Weight (complete std enclosure) kg 39 44 66 125 130 230 330
All these characteristics are given as information and are not contractual(1): Between order sent and final position (under nominal conditions)
Temperature DeratingNominal Rating Cable Size De rate IEC 947-3
(40 C Max) 50 C 60 C 65 C 40 C 415 V 60 C 415 V(A) (mm2) (A) (A) (A) AC 22 AC 23 AC 22 AC 23250 120 250 220 200 AC23A 250A AC23A 200A400 240 360 300 250 AC22A 400A AC23A 250A AC23A 250A630 2 x 185 550 500 400 AC22A 630A AC23A 500A AC23A 400A800 2 x 240 720 640 540 AC22A 800A AC23A 800A AC23A 540A
1000 4 x 150 880 800 680 AC22A 1000A AC23A 1000A AC23A 680A1250 4 x 240 1150 1000 820 AC22A 1250A AC22A 1000A1600 5 x 240 1300 1100 930 AC22A 1600A AC22A 1100A
Single phase configurationTable available for single phase configurations using a 4 poles switch and connecting 2 poles in parrallelMax ambiant Temperature = 40 C
Nominal Rating 3 phase configuration Nominal Rating 1phase configuration(A) (2 poles in //) (A)250 400 (1) Short circuit level required for 630A400 630 (1) not acceptable for 400A version630 800 (2) (2) Short circuit level required for 800A800 1250 not acceptable for 630A version
1000 1600 (3) (3) Short circuit level required for 1600A1250 1800 not acceptable for 1000A version1600 2500 (4) (4) Short circuit level required for 2500A
not acceptable for 1600A version
Metering accuracyVoltage and frequency: 1% on power input range.
95 % humidity non condensing at40 C
Maximum operating altitude withoutswitch de-rating is 2 000 m above sea level.
Maximum storage is one year at:- Maximum temperature +55C- 95% humidity non condensing
80 % humidity non condensing at55 C
SOCOMEC - Rf.: 678 623 G GB 7
ENGL
ISH
ENCLOSURES INSTALLATION
FIRST OPERATIONS
400A / 630A
The system is delivered in position 0 inmanual mode, start generator contactclosed.
Remove the shroud to allow terminalsaccess.
Remove the plastic protection of theplexiglas cover.
Shroud
ATI
037
A
For a correct use in hardenvironmental conditions, it isessential to use the cablegland plate, in order toprotect the product.
8 SOCOMEC - Rf.: 678 623 G GB
ENCLOSURES INSTALLATION (continued)
x1
Fix the handle + chain on the enclo-sure itself.
Handle with chain
ATI
038
A
SOCOMEC - Rf.: 678 623 G GB 9
ENGL
ISH
ENCLOSURES INSTALLATION (continued)
M6
x4
x4
x4
x4
Use the mounting brackets deliveredin a bag inside the enclosure to fix theenclosure on a wall.
Wall mounting brackets
ATI
039
A
10 SOCOMEC - Rf.: 678 623 G GB
ENCLOSURES INSTALLATION (continued)
1
2
3
Cut the voltage sensing kit clips toallow cables connections usingscrews/nuts/contact washers delive-red in a bag inside the enclosure.
Voltage sensing kit
ATI
040
A
SOCOMEC - Rf.: 678 623 G GB 11
ENGL
ISH
ENCLOSURES INSTALLATION (continued)
BOTTOM CABLE ENTRY ENCLOSURES
250 A rating
Phase and neutral cable 150 mm2 or 2 x 70 mm2 (Max)
Earth cable 120 mm2
or 2 x 50 mm2 (Max)
A
A
Generator Main
Load
A-A
Torque : M8 M10
13 Nm (Max) 26 Nm (Max)
600
435
648
495
82.5
858
641
655
348
12.5
900
185
245
60
323
39
15
7
97.
5 3917
Power Cables Connection
1 2 3 N
Power Cables Connection
ATI
042
A G
B
12 SOCOMEC - Rf.: 678 623 G GB
400A rating
Phase and neutral cable 240 mm2 or 2 x 120 mm2 (Max)
Earth cable 120 mm2
or 2 x 70 mm2 (Max)
Generator
Main
Load
Torque : M10 M12
26 Nm (Max) 45 Nm (Max)
A
A
435
648
600
495
82.5
858
641
655
348
12.5
900
185
245
60323
39
15
7
97.
5 3917
Power Cables Connection
1 2 3 N
Power Cables Connection
ENCLOSURES INSTALLATION (continued)A
TI 0
43 A
GB
SOCOMEC - Rf.: 678 623 G GB 13
ENGL
ISH
ENCLOSURES INSTALLATION (continued)
600
605
545
328
320
200
288
495455
30
30 46
72.5
14
423398
900
Torque : M10 M12
26 Nm (Max) 45 Nm (Max)
Phase and neutral cable 2 x 240 mm2 (Max)
Earth cable 240 mm2 (Max)
Generator
Main
Load
A
A
A-A
1 2 3 N
630 A rating
Power Cables Connection
ATI
044
A
AA
623600
1175
200
775
720
520
30
28
80
50
50
80
536
480
50
120
14
14
536
480
1375
Torque: M10 26Nm (Max) M12 45Nm (Max)
Phase and neutral cable800A:3x240mm2 or 2x300mm2 (Max)1000A:4x240mm2 or 2x300mm2 (Max)
Earth cable:-800A:2x120mm2 or 1x300mm2 (Max)-1000A:2x240mm2 or 1x300mm2 (Max)
A-A
Main
Load
Generator
14 SOCOMEC - Rf. : 678 623 G GB
800A/1000 A ratings
Power Cables Connection
ATY
S 1
27 A
GB
ENCLOSURES INSTALLATION (continued)
SOCOMEC - Rf. : 678 623 G GB 15
ENGL
ISH
ENCLOSURES INSTALLATION (continued)1250 A rating
Power Cables Connection
A
A-A
Main
Load
Generator
Torque: M12 45Nm (Max)
A
A
798
775
1600
1800
800
555
100
100
100
100
100
555
100
800
100
200
100
803
1800
1000
58
81
79
58
Earth cable2 x 240 mm2
or 1 x 300 mm2 (Max)
Phase and neutral cable2 x 300 mm2 or 4 x 240 mm2 (Max)
ATY
S 1
31 B
GB
ENCLOSURES INSTALLATION (continued)1600 A rating
Power Cables Connection
ATY
S 1
32 B
GB
798
775
1600
1800
800
555
100
100
100
100
100
555
100
800
100
200
100
803
1800
1000
58
81
79
58
Earth cable2 x 300 mm2
or 3 x 240 mm2 (Max)
Phase and neutral cable6 x 240 mm2 or 4 x 300 mm2 (Max)
A-A
Main
Load
Generator
Torque: M12 45Nm (Max)
A
A
A
A
16 SOCOMEC - Rf. : 678 623 G GB
SOCOMEC - Rf. : 678 623 G GB 17
ENGL
ISH
ENCLOSURES INSTALLATION (continued)
TOP CABLE ENTRY ENCLOSURES
250A ratings - Top cable entry
648
858
641
655
348
12.5
900
323
39
15
7
97.
5 3917
600
435
495
82.5
185245
60Phase and neutral cable 150 mm2 or 2 x 70 mm2 (Max)
Earth cable 120 mm2
or 2 x 50 mm2 (Max)A
A
Generator
Main
Load
A-A
Torque : M8 M10
13 Nm (Max) 26 Nm (Max)
1 2 3 N
ATI
046
A G
B
Power Cables Connection
18 SOCOMEC - Rf.: 678 623 G GB
ENCLOSURES INSTALLATION (continued)400A ratings - Top cable entry
648
858
641
655
348
12.5
900
323
39
15
7
97.
5 3917
600
435
495
82.5
185245
60
Earth cable 120 mm2
or 2 x 70 mm2 (Max)
Torque : M10 M12
26 Nm (Max) 45 Nm (Max)
Phase and neutral cable 240 mm2 or 2 x 120 mm2 (Max)
A
A
Generator
MainLoad
A-A
1 2 3 N
ATI
047
A G
B
Power Cables Connection
SOCOMEC - Rf.: 678 623 G GB 19
ENGL
ISH
ENCLOSURES INSTALLATION (continued)630A ratings - Top cable entry
600
600
540
328
280
288
495455
30
50 46
72.5
13
423398
1150
Torque : M10 M12
26 Nm (Max) 45 Nm (Max)
Phase and neutral cable 2x240 mm2 (Max)
Earth cable 240 mm2 (Max)
Load
A
Generator
Main
A A-A
1 2 3 N
200
ATI
048
A
Power Cables Connection
20 SOCOMEC - Rf.: 678 623 G GB
ENCLOSURES INSTALLATION (continued)800 A/1000 A ratings Top cable entry
A
A
536
480
520
72028
30
14
200
775
1175
600
623
1375
80
50
50
80
536
480
120
50
14
1213
1 3
Torque: M10 26Nm (Max) M12 45Nm (Max)
Phase and neutral cable:800A:3x240mm2 or 2x300mm2 (Max)1000A:4x240mm22 or 2x300mm2 (Max)
Earth cable:-800A:2x120mm2 or 1x300mm2 (Max)-1000A:2x240mm2 or 1x300mm2 (Max)
A-A
Main
Load
Generator
ATI
048
C G
B
Power Cables Connection
SOCOMEC - Rf. : 678 623 G GB 21
ENGL
ISH
ENCLOSURES INSTALLATION (continued)1250 A rating Top cable entry
Power Cables Connection
A
A-A
Main
Load
Generator
Torque : M12 45Nm (Maxi)
A
A
798
775
1600
1800
800
555
100
100
100
100
100
555
100
800
100
200
100
803
1800
1000
58
81
79
58
Earth cable2 x 240 mm2
or 1 x 300 mm2 (Max)
Phase and neutral cable2 x 300 mm2 or 4 x 240 mm2 (Max)
ATY
S 1
33 B
GB
22 SOCOMEC - Rf. : 678 623 G GB
ENCLOSURES INSTALLATION (continued)1600 A rating Top cable entry
Power Cables Connection
ATY
S 1
34 B
GB
798
775
1600
1800
800
555
100
100
100
100
100
555
100
800
100
200
100
803
1800
1000
58
81
79
58
A-A
Main
Load
Earth cable2 x 300 mm2
or 3 x 240 mm2 (Max)Generator
Torque M12 45Nm (Maxi)
Phase and neutral cable6 x 240 mm2 or 4 x 300 mm2 (Max)
A
A
A
A
SOCOMEC - Rf.: 678 623 G GB 23
ENGL
ISH
OPTIONAL CONNECTIONS
ENCLOSURES INSTALLATION (continued)
Metering :- (Sensing) CTS- Specific Metering Display
f
1 2 0 A/M Padlocking
g h i j
20/13
21/14
22/24
23/34
24/43
25/44
26/53
27/54
Option 1
Metering + Auxiliary contacts OptionAvailable from third release 2004. Thisoption is factory fitted and includes aspecific metering display + meteringCTs to allow current + power metering.
Auxiliary contacts for 0,1,2 position,padlock and Auto/Manual Mode.Available from factory.
Verify there is no voltageon the terminals beforemounting the options.
ATI
049
B G
B
Contact f, g and h are closed when theswitch is in position 1, 2 or 0.Contact i is closed when the switch is
in Automatic mode.Contact j is closed when the switch ispadlocked.
Identification Terminals Type Feature Ratingf 13-14 Output Position 1 Auxiliary contact
or 20-21 Contact closed whenswitch is in position 1
g 13-24 Output Position 2 Auxiliary contactor 20-22 Contact closed when
switch is in position 2h 13-34 Output Position 0 Auxiliary
or 20-23 contact Contact closedwhen switch is in position 0
i 43-44 Output Auto/Manu informationor 24-25 Contact closed when
Automatic mode is activej 53-54 Output Padlocking information
or 26-27 Contact closed whenthe switch is padlocked
Res
istiv
e lo
ad: 1
0 A
In
duc
tive
load
: 3 A
Max
Vac
: 250
- M
ax o
per
atio
ns: 5
x 1
07
24 SOCOMEC - Rf.: 678 623 G GB
ENCLOSURES INSTALLATION (continued)
354
92
254 25
M5
x4
x1
x4
x1
x1
7
1
23
4
Option 2
IP54 protection kit
ATI
050
B
SOCOMEC - Rf.: 678 623 G GB 25
ENGL
ISH
Option 3
x3
x1
1
x1
x2
x1
x3 M8/M10 x 20
2
3
Solid neutral kit250A rating
ATI
052
A
Torque : M8 > 13 Nm (Max)M10 > 26 Nm (Max)
ENCLOSURES INSTALLATION (continued)
26 SOCOMEC - Rf. : 678 623 G GB
ENCLOSURES INSTALLATION (continued)
1
2
3
M10 / M12
x2
x4x1
x1
x1x1
x2
x4 M10 x 30400A :x4 M12 x 35630A :
ATI
053
A
Torque: M10 > 26 Nm (max)M12 > 45 Nm (max)
Option 3
Solid neutral kit400A/630A rating
SOCOMEC - Rf. : 678 623 G GB 27
ENGL
ISH
ENCLOSURES INSTALLATION (continued)Option 3
Solid neutral kit800A rating
x1
x1
x1
x1
M10: x2M12: x4
M10: x2M12: x4
M10: x2M12: x4
M10x40: x2M12x35: x1M12x40: x2M12x45: x1
see detail A
detail A
1/2
M12x45 (x2)
M10x40 (x2)M12x40 (x2)
M12x35 (x1)
Torque: M10 > 26 Nm (max)M12 > 45 Nm (max)
ATY
S 1
29 A
GB
28 SOCOMEC - Rf.: 678 623 G GB
ENCLOSURES INSTALLATION (continued)A
TI 0
53 A
M10: x8M12: x4
M10: x8M12: x4
M10: x8M12: x4
M10x35: x4M10x45: x4M12x40: x2M12x50: x2
x1
x1
x1
x1
detail A 1/2 M10x45 (x4)
M12x50 (x2)
M10x35 (x4)
M12x40 (x2)
see detailA
Option 3
Solid neutral kit1000A rating
Torque: M10 > 26 Nm (max)M12 > 45 Nm (max)
ATY
S 1
30 A
SOCOMEC - Rf. : 678 623 G GB 29
ENGL
ISH
ENCLOSURES INSTALLATION (continued)Option 3
Solid neutral kit1250A rating
A
SECTION A-A
detail A
see detailA
A
A
x1
x 2 M12: x18
M12: x18
M12: x18
M12X45: x18
x1
ATY
S 1
35 B
30 SOCOMEC - Rf. : 678 623 G GB
ENCLOSURES INSTALLATION (continued)Option 3
Solid neutral kit1600A rating
A
SECTION A-A
A
A
detail A
see detailA
M12: x18
M12: x18
M12: x18
M12X45: x18
x1
x 4
x1
ATY
S 1
36 B
SOCOMEC - Rf.: 678 623 G GB 31
ENGL
ISH
5
4
x1
x2
M8
x1
x1
x2
Bottom Connection
1 / 2
Top Connection
B
A
C
1 23 N
M6
5
4
ATIElectronic module
SU
RG
YS
CO
NTA
CTS
FUS
EC
ON
TAC
T Q
2 3P
FUS
EC
ON
TAC
T Q
2 1P
2IN/2OUTOption
AB
C
10/2
107/
207
A specific menu in the metering architecture allows monitoring of theprotection. Cf variable LIP in the mo-nitoring menu.LIP variable = 1 as soon as the pro-tection operates (fuse blow or lightningprotection operation).This information is verified every5 seconds.Error led also blinks to inform of LIPoperation.It might then either be required tochange a fuse or the lightning module.
Option 4
Lightning protection
A 3 minutes power offaction is required beforestartup to allow optionrecognition.
ATI
054
C G
BENCLOSURES INSTALLATION (continued)
32 SOCOMEC - Rf.: 678 623 G GB
ENCLOSURES INSTALLATION (continued)
201202
203204
205206
101
102
103
104
105
106
Pow
er 230 Vac G Voltage S
ensing
Volta
ge S
ensi
ng
OO
P
ower
230
Vac
L3 L2 L1 N
L3 L2 L1 N
14 14
11
14
11
14
1111
50A
RMS 50
Q2
4mm2
4mm2
0.75mm2
FUS
EC
ON
TAC
T Q
2 3P
FUS
EC
ON
TAC
T Q
2 1P
SU
RG
YS
CO
NTA
CTS
D40
L/N
D40
L/N
D40
L/N
D40
L/N
SURGYS
6mm2
14 13
2IN/2OUTOption
ATI Electronic Module
+ -C+
Opt.2 Opt.1
7/207
8/208
9/209
10/210
11/73
12/74
Lightning protection equipment Connection diagram
ATI
055
B G
B
Option 4 (continued)
SOCOMEC - Rf.: 678 623 G GB 33
ENGL
ISH
ENCLOSURES INSTALLATION (continued)Option 5
277 Vac optionSwitch is available in 277 Vac version.
Auxiliary contacts for 0,1,2 position, padlock and Auto/Manual Mode.Available from factory.
Option 6
Contact f, g and h are closed when theswitch is in position 1, 2 or 0.Contact i is closed when the switch isin Automatic mode.Contact j is closed when the switch ispadlocked.
1 2 3 N
f
1 2 0 A/M Padlocking
g h i j
20/13
21/14
22/24
23/34
24/43
25/44
26/53
27/54
Identification Terminals Type Feature Ratingf 13-14 Output Position 1 Auxiliary contact
or 20-21 Contact closed whenswitch is in position 1
g 13-24 Output Position 2 Auxiliary contactor 20-22 Contact closed when
switch is in position 2h 13-34 Output Position 0 Auxiliary
or 20-23 contact Contact closedwhen switch is in position 0
i 43-44 Output Auto/Manu informationor 24-25 Contact closed when
Automatic mode is activej 53-54 Output Padlocking information
or 26-27 Contact closed whenthe switch is padlocked
Res
istiv
e lo
ad: 1
0 A
In
duc
tive
load
: 3 A
Max
Vac
: 250
- M
ax o
per
atio
ns: 5
x 1
07
ATI
056
B G
B
34 SOCOMEC - Rf.: 678 623 G GB
ENCLOSURES INSTALLATION (continued)
x1
1
OUT
9 / 10 : Main Available output contact
11/12 : Gen Available output contact
1 / 2
2
9 10 11 12
a b
Option 7
2 IN/2 OUT option
Main available /Gen available outputcontacts.
The contact closes as soon as thesource is available.
A 3 minutes power offaction is required beforestartup to allow optionrecognition.
Identification Terminals Type Feature Ratinga 9-10 Output Main available information
b 11-12 Output Gen available information
230
Vac
- 5
A -
115
0 VA
Max
op
erat
ions
10
5-
Gal
vani
c in
sula
tion
2,5
kV (1
min
50
Hz)
ATI
057
A G
B
SOCOMEC - Rf.: 678 623 G GB 35
ENGL
ISH
ENCLOSURES INSTALLATION (continued)
x1
1
1 / 2
2
GENERAL POINTS
For standard configurations, an RS485 link is used to connect up to 31ATI with a PC or a PLC over a distanceof 1 500 metres, using JBUS / MOD-BUS protocol.
N 1 N 2 N nR = 120
1500 M
R = 120
Programmablecontrollers
Other systems
N 1R = 120
RS485
0+- -+0N n
R = 120
1500 M 1500 M
Programmablecontrollers
Other systems
repetor
DIR
IS 1
09 B
DIR
IS 1
10 B
Recommendations:You should use a shielded twisted pair(LIYCY type). In a disturbed environ-ment or large network (in terms oflength) we recommend the use of2 shielded pairs (type LIYCY-CY). Inthis case, one pair is used for the+ and the , and another pair, wherethe 2 wires are short-circuited, for the0 V.A repeater (1 channel) or an arrestor(4 channels) should be used if youintend to exceed the distance(1 500 m) and / or maximum number(31) of ATI. Please contact us formore information.
NB:A 120 ohm resistance (found on theadditional module) must be fixed atboth ends of the link.
Other solutions are available (modem,optical fibre, etc.). Please contact us.
A 3 minutes power offaction is required beforestartup to allow optionrecognition.
RS485 2 or 3 wires half duplexProtocol JBUS/MODBUS protocol /RTU modeSpeed 2400, 4800, 9600, 14400, 19200, 28800, 38400 BaudsGalvanic insulation 4 kV (1 min 50 Hz)
Option 8
Communication moduleRead paragraph communication forinstructions.Installation of this module allows RS485connection. Protocoles avaible areJBUS/MODBUS.
ATI
058
A G
B
36 SOCOMEC - Rf.: 678 623 G GB
VOLTAGE CONFIGURATIONS
VOLTAGE OPTIONS
Standard 230Vac +/- 20%
50 Hz 3 phase 4 wires - 3P4L 60 Hz 3 phase 4 wires 3P4LStar connections Star connections
FG Wilson Voltage FG Wilson Voltageoption code option codeV502 415/240V V603 440/254V (2)
V503 400/230V V605 380/220VV504 380/220V V608 220/127VV507 220/127V V610 208/120V (3)
V510 200/115V (1) V611 240/139V(1): +20%/-12%(2): +13%/-20%(3): +20%/-15%
50 Hz 3 phase 3 (4) wires - 3P3(4)L 60 Hz 3 phase 3 (4) wires 3P3(4)LDelta connections Delta connections
V506 230/115V V606 240/120VV508 220/110V V607 230/115V
V609 220/110V
50 Hz single phase 3 wire 1P3L 60 Hz single phase 3 wire 1P3LV522 240/120V V622 240/120VV524 230/115V V624 230/115VV526 220/110V V626 220/110V
50 Hz single phase 2 wire 1P2L 60 Hz single phase 2 wire 1P2LV521 240V V621 240VV523 230V V623 230VV525 220V V625 220V
Optional 277 Vac (+/-20% for rating below 630 A, +20/-15% for rating 800 A and above)
50 Hz 3 phase 4 wires - 3P4L 60 Hz 3 phase 4 wires 3P4LStar connections Star connections
FG Wilson Voltage FG Wilson Voltageoption code option code
V601 480/277V
To meet all voltages required by the market, 2 ATI versions have been developed:
CABLE CONNECTIONS BETWEEN SWITCHAND ELECTRONIC MODULE
A voltage sensing kit is used to providesensing and power connections fromthe switch terminals to the electronicmodule terminals.The ATI enclosures are delivered asstandard for 3 phases 4 wires applica-tions, 400/230 Vac nominal voltage.In some 3 phase 4 wires, all 3 phases 3wires, or single phase 2 or 3 wiresapplications, sensing connections keepthe same, but power connections mustbe modified according to guidelinesincluded before connection diagrams.
In standard ATI (bottomentry) generator cable isred and main cable is black.In top entry ATI main cableis red and generator cableis black.
SOCOMEC - Rf.: 678 623 G GB 37
ENGL
ISH
LOAD
Genset controller
201202
203204
205206
101
102
103
104
105
106
1
2
3
N
Pow
er 230 Vac Voltage Sensing Vo
ltage
Sen
sing
O
O
Pow
er 2
30 V
ac
1-2
3-4
5-6
7-8 1-2
3-4
5-6
7-8
AB
AB
VOLTAGE CONFIGURATIONS (continued)
ELECTRONIC MODULE CONNECTIONS
The Voltage sensing kit provides powerand sensing to the electronic modulefrom the generator and the main side.
Main sensing is 3 phases sensing:103: Neutral104: Phase 3105: Phase 2106: Phase 1
Gen sensing is single phase sensing:203: Phase 1205: Phase 3
A. No wiring change required from standard deliveryConfigurations:V502 415/240 Vac 50 HzV503 400/230 Vac 50 HzV504 380/220 Vac 50 HzV603 440/254 Vac 60 HzV605 380/220 Vac 60 HzV601 480/277 Vac 60 Hz - Special Voltage Option 5 = 277Vac
3 Phases 4 Wires connections-3P4L
Verify voltage between101/102 & 201/202= 220/240 Vac20%
ATI
059
B G
B
38 SOCOMEC - Rf.: 678 623 G GB
VOLTAGE CONFIGURATIONS (continued)
3 Phases 3 (4) Wires connections-3P3(4)L
a
b
LOAD
Genset controller
201202
203204
205206
101
102
103
104
105
106
1
2
3
M
1-2
3-4
5-6
7-8 1-2
3-4
5-6
7-8
Pow
er 230 Vac Voltage Sensing
Volta
ge S
ensi
ng
OO
P
ower
230
Vac
AB
AB
a
b
LOAD
Genset controller
201202
203204
205206
101
102
103
104
105
106
1
2
3
N
Pow
er 230 Vac Voltage Sensing
Volta
ge S
ensi
ng
OO
P
ower
230
Vac
1-2
3-4
5-6
7-8 1-2
3-4
5-6
7-8
AB
AB
B. Wiring change required from standarddelivery: A & B power wires from ter-minals 206 & 103 must be connectedto terminals 205 & 104 to provide220/230 Vac or 240 Vac to the powerinputs 101/102 and 201/202.
Configurations:V507 220/127 Vac 50 HzV510 200/115 Vac 50 HzV608 220/127 Vac 60 HzV610 208/120 Vac 60 HzV611 240/139 Vac 60 Hz
3 Phases 4 Wires connections-3P4L
Wiring change required from stan-dard delivery: A & B power wires fromterminals 206 & 103 must be con-nected to terminals 205 & 104 to pro-vide 220/230 Vac or 240 Vac to thepower inputs 101/102 and 201/202.
Configurations:V506 230/115 Vac 50 HzV508 220/110 Vac 50 HzV606 240/120 Vac 60 HzV607 230/115 Vac 60 HzV609 220/110 Vac 60 Hz
ATI
060
A G
BA
TI 0
61 A
GB
SOCOMEC - Rf.: 678 623 G GB 39
ENGL
ISH
Wiring change required from stan-dard delivery: A & B power wires fromterminals 206 & 103 must be con-nected to terminals 205 & 104 to pro-vide 220/230 Vac or 240 Vac to thepower inputs 101/102 and 201/202.
V521 240 Vac 50 HzV523 230 Vac 50 HzV525 220 Vac 50 HzV621 240 Vac 60 HzV623 230 Vac 60 HzV625 220 Vac 60 Hz
1 Phase 2 Wires connections-1P2L
LOAD
Genset controller
201202
203204
205206
101
102
103
104
105
106
1
3
1-2
3-4
5-6
7-8 1-2
3-4
5-6
7-8
Pow
er 230 Vac Voltage Sensing
Volta
ge S
ensi
ng
OO
P
ower
230
Vac
AB
AB
VOLTAGE CONFIGURATIONS (continued)1 Phase 3 Wires connections-1P3L
LOAD
Genset controller
201202
203204
205206
101
102
103
104
105
106
1
2
3
1-2
3-4
5-6
7-8 1-2
3-4
5-6
7-8P
ower 230 Vac Voltage S
ensing
Volta
ge S
ensi
ng
OO
P
ower
230
Vac
AB
AB
Wiring change required from stan-dard delivery: A & B power wiresfrom terminals 206 & 103 must beconnected to terminals 205 & 104to provide 220/230 Vac or 240 Vacto the power inputs 101 / 102 and201/202.
Configurations:V522 240/120 Vac 50 HzV524 230/115 Vac 50 HzV526 220/110 Vac 50 HzV622 240/120 Vac 60 HzV624 230/115 Vac 60 HzV626 220/110 Vac 60 Hz
ATI
062
B G
BA
TI 0
63 A
GB
40 SOCOMEC - Rf.: 678 623 G GB
VOLTAGE CONFIGURATIONS (continued)
Split phase network / single phasegenerator.
This configuration must be used onapplications using single phase gen-erators to supply 2 phases networksfeeding single phase loads.
1PAP
LOAD
Genset controller
201202
203204
205206
101
102
103
104
105
106
1
N
N
1
1
N.C.
N
2
1-2
3-4
5-6
7-8 1-2
3-4
5-6
7-8
Pow
er 230 Vac Voltage Sensing
Volta
ge S
ensi
ng
OO
P
ower
230
Vac
AB
AB
Three phase network /single phasegenerator.
This configuration must be used onapplications using single phase ge-nerators to supply 3 phases networksfeeding single phase loads.Wiring change required. Change 5-6and 7-8 on 205 & 206.
LOAD
Genset controller
201202
203204
205206
101
102
103
104
105
106
1
1
N
1
1
3
N
2
1-2
3-4
7-8
5-6 1-2
3-4
5-6
7-8
Pow
er 230 Vac Voltage Sensing
Volta
ge S
ensi
ng
OO
P
ower
230
Vac
AB
AB
ATI
064
B G
BA
TI 0
65 B
GB
SOCOMEC - Rf.: 678 623 G GB 41
ENGL
ISH
INPUTS AND OUTPUT CONTACTS
a
b
c
d
e
Opt. 2 Opt. 1
to lightning protectionoption
206 106
ensing
Volta
ge
7-8
7/207
11/73
12/74
8/208
9/209
10/210
ATI
066
B G
B
Identification Terminals Type Feature Rating
a 207 Inputs Common terminalor 7
b 207-208 Input AT Timer inhibit inputor 7-8 Dry contact to close between terminals
7-8 to inhibit AT timer
c 207-209 Input Remote test on load inputor 7-9 Dry contact to close between terminals 7-9 to start
remotely a test on load (onlyavailable in automatic mode)
d 210 or 10 (+ ) Power supply Power supply dedicatedto lightning option
207 or 7 ( - ) 5 Vdc < V7-10 < 16 Vdc without load9 Vdc < V7-10 < 10 Vdc for 1 to 2 inputs
e 73-74 Output Start Gen signalor 11-12 30 V DC 1 A
- M
ax d
irect
vol
tage
30
Vdc
- M
in d
irect
vol
tage
10
Vdc
- M
ax in
vers
e vo
ltage
30
Vdc
- G
alva
nic
insu
latio
n 3
kV
(1 m
in 5
0H
z)
- M
in p
ulse
dur
atio
n 1
s
- M
ax n
umbe
r of o
pera
tions
108
CURRENT INPUTS (for METERING)
201202
203204
205206
101
102
103
104
105
106
1
3
N
2
1
3
N
2
Puissance 230 V
AC
- - Mesure d
e tensionM
esur
e d
e te
nsio
n
OO
Pui
ssan
ce 2
30 V
AC
R1 R2 S1 S2 T1 T2
R1 R2 S1 S2 T1 T2
I1 I2 I3
T2T1S2S1R2R1
LOAD
R1 R2 S1 S2 T1 T2
R1 R2 S1 S2 T1 T2
R1 R2 S1 S2 T1 T2
R1 R2 S1 S2 T1 T2
Short circuit plug delivered with the spare part
R1 R2 S1 S2 T1 T2
ATI
090
B G
B
If the load is supplied, before discon-necting the main connector, it isnecessary to short-circuit the secondaryof the current transformer (short-circuitplug to be mounted).
42 SOCOMEC - Rf.: 678 623 G GB
Source availability 2 green Leds to indicate if
Gen and Mains sources are available (voltage and frequency measurement)
- Led is on = source available- Led is off = source missing
Retransfer Inhibit 1 yellow Led, linked to
retransfer inhibit pushbutton- Led is on = retransfer
inhibit feature is active- Led is off = retransfer
inhibit inactive- Led is blinking = retransfer
is blocked, waiting for a push on the retransfer inhibit pushbutton to allow retransfer
Switch state 2 green Leds to indicate if
the switch is opened or closed- Led is on = switch is closed- Led is off = switch is opened
1 Yellow led to indicate if both switches are in 0 position- Led is on = both switches opened- Led is off = Gen or Mains
switch closed
Error Led 1 red led to indicate a fault
- Led is on = switch errorAction from software not confirmed by an auxiliary contact. Reset after power off- Led blinks in case of lightning protection operation No reset required (blinking disappears once input is low)
Power Led 1 green led
- Blinks slowly as soon as the product is powered and software runs correctly
- Always on = Power OK and software error
- Always off = Power off or software error if another led is on and LCD is OK
Keyswitch Insert key to allow switch
operational mode modification Turn right to access automatic mode Turn left to access manual mode
Padlock Pull the yellow handle to allow padlock insertion Padlocking possible in position 0,1 or 2
but only in Manual mode (keyswitch position), handle out of housing.
Keypad
Switch Position Indications 0, 1 or 2 position display
Manual Operation Insert handle to manually
operate the switch. Manual operation only possible
in Manual mode (keyswitch), when not padlocked
Modes annunciation and Tests 1 Top yellow led for Manual Mode position linked
to the key position 1 green led for Automatic Mode position linked
to the key position 2 Bottom yellows leds for Test On and
Off Load position Linked to the test pushbutton pressSymbols are represented to make comprehension easier
LCD 7 digits to display information 14 pointers to inform about displayed information unit or source:
- : Mains information - Com: communication active - : Generator information - V: Volt- L1, L2, L3 : Information - Hz: Hertz
regarding Phase 1,2 or 3 - %: percentage- : Timer active - sec: second- PROG: Programming active - min: minute
- n: number of commutations
Push button
: Home push button during programming
: Lamps test button
BASIC PRODUCT USE
GENERAL INTRODUCTION
The product provides sources availabil-ity monitoring, Automatic / ManualRetransfer, Manual/Automatic or Testoperation monitoring, voltage and fre-quency metering, and good operation orerror information.
The product requires at least one typeof network configuration and a networknominal voltage configuration to be inputvia the keypad by the user.Other default values can be kept or mo-dified according to hereafter program-ming guidelines.
ELECTRONIC MODULE USAGE
The electronic module is directlymounted on the motorized block.It integrates the following features:- Voltage and frequency metering- Automatic transfer controls
Following diagram introduces prod-uct front panel.Led indication is only active oncethe product is powered (power ledactivated).
Front Panel Introduction
Verify power applied on theelectronic module power inputsterminals 101-102 or 201-202before powering up the unit.
ATI
067
A
ATI
068
A
SOCOMEC - Rf.: 678 623 G GB 43
ENGL
ISH
BASIC PRODUCT USE (continued)
Software version is displayed on theunit after reset (powering up action after3 minutes power off to discharge theunit).
Software version
{ {
Version Number
Product Programming is possible inAutomatic Mode in position 1 when theMains Source is available, or in Manualmode.
It is not accessible when a test or anautomatic sequence is activated.
Programming mode is accessible bypressing and holding the validation push-button for 5 seconds and then enteringthe code 1000:
Product ProgrammingBefore first product use,
access programming modeand verify product programming parameters.
PROGRAMMING ACCESS
To exit the Programming and comeback to visualisation mode, hold thevalidation pushbutton for 5 seconds.Parameters saved permanently once exit.
PROGRAMMING EXIT
Press for 5 seconds
Press once to display 1
Validate
Access to programming Menus
ATI
068
A G
B
ATI
070
A
44 SOCOMEC - Rf.: 678 623 G GB
Default values areloaded as standard.
BASIC PRODUCT USE (continued)
Setup: Network parametersVolt: Voltage detection levelsFr: Frequency detection levelstim: Automatic timer settingsComm: Communication parameters (Optional), communication module
must be plugged.
PROGRAMMING MENUS
Setup parameters must always be verified/modified in accordance to theapplication.
Architecture and navigation
Optional
The first menu to access is the Setup menu
The programming mode integrates 5 Menus
ATI
071
A
ATI
072
A
SOCOMEC - Rf.: 678 623 G GB 45
ENGL
ISH
BASIC PRODUCT USE (continued)
The setup menu integrates 5 parame-ters described in the table hereunder.The table explains parameters definition,settings possibilities, and default values.
Press Down push button to access parameter required.
Press Up push button to come back to previous value, or press
or Home push button to come back to .
SETUP MENU
Un: Phase-Phasenominal voltage.
From 200 to 480 V 400 V AC
nt: Network configuration.Type of metering (1P or 3P phases).Number of active wires (2L, 3L or 4L) definition.
1P2L, 1P3L, 3P4L 3P4L3P3L, 1PAP
Fn: Nominal frequency. 50 or 60 Hz 50 Hz
trI: Retransfer inhibit feature:press on RTI button required toallow retransfer from gen tomain.
Yes or No No
Crs: Reset number of commutationcounter (from Main to Gen).Displays no once reset.
Yes or No No
Definition Setting range Default value
Parameter Display
ATI
073
A
46 SOCOMEC - Rf.: 678 623 G GB
BASIC PRODUCT USE (continued)
To return to Setup menu press home pushbutton or press down to continue.
Press to access the first digit (blinking)
Press twice to display 2 (blinking)
Press to access the second digit (blinking)
Press 3 times to display 3 (blinking)
Press to validate the value
Press to return to Setup menu Press to reach next parameter
Parameter modification
Display the required parameter formodification.Apply the same procedure describedhereunder for network voltage modifica-tion, to all other parameters. Possible
settings are described in the previoustable.Example:We want to modify network voltagefrom 400V to 230V.
ATI
074
A
ATI
075
A
ATI
076
A
SOCOMEC - Rf.: 678 623 G GB 47
ENGL
ISH
BASIC PRODUCT USE (continued)
To reach voltage menu from Setup menu press once .
The voltage menu integrates 8 parame-ters described in the table hereunder.The table explains parameters defini-tion, settings possibilities, and defaultvalues.Over and Under voltage conditions areverified on Mains and Generator side toallow operation as per the flow chart.Mains sensing is 3 phase and
Generator sensing single phase.Over and under voltage detection lev-els + hysteresis are defined as per-centage of nominal voltage.Hysteresis levels allow under and overvoltage conditions reset (voltage needsto pass hysteresis level to reset).
Press Down push button to access parameter required.
Press Up push button to come back to previous value
or Home push button to come back to .
VOLTAGE MENU
oU: Main Over voltage detection 102 - 120% 115%
oUh: Main Over voltage hysteresisdetection
101 - 119% 110%
uU: Main Under voltage detection 80 - 98% 85%
uUh: Main Under voltage hysteresisdetection
81 - 99% 95%
oU: Generator over voltage detection 102 - 120% 115%
oUh: Generator over voltagehysteresis detection
101 - 119% 110%
uU: Generator under voltagedetection
80 - 98% 85%
uUh: Generator under voltagehysteresis detection
81 - 99% 95%
Definition Setting range Default value
Note:These values only need to bechanged if a value is required otherthan the default.
Parameter Display
ATI
077
A
48 SOCOMEC - Rf.: 678 623 G GB
To reach frequency menu from voltage menu press once .
FREQUENCY MENU
BASIC PRODUCT USE (continued)
Display the required parameter formodification.Apply the same procedure as describedin Setup Menu for network voltage mo-
dification. Possible settings are describedin the previous table.
The frequency menu integrates 8 parameters described in the table hereunder.
The table explains parameters definition,settings possibilities, and default values.Over and Under frequency conditions areverified on Mains and Generator side toallow operation following operational flowchart.
Over and under frequency detection levels+ hysterisis are defined as percentage ofnominal frequency.Hysteresis levels allow under and overfrequency conditions reset (frequencyneeds to pass hysteresis level to reset).
Press Down push button to access parameter required.
Press Up push button to come back to previous value
or Home push button to come back to .
Parameter modification
Parameter Display
oF: Main over frequency detection 101 - 120% 105%
oFh: Main over frequency hysteresis 100.5 - 119.5% 103%
Definition Setting range Default value
uF: Main under frequency 80 - 99% 95%
uFh: Main Under frequency hystere-sis
80.5 - 99.5% 97%
oF: Generetor over frequency 101 - 120% 105%
oFh: Generator over frequencyhysteresis
100.5 - 119.5% 103%
uF: Generator under frequency 80.5 - 99.5% 95%
uFh: Generator under frequencyhysteresis
80 - 99% 97%
ATI
078
A
SOCOMEC - Rf.: 678 623 G GB 49
ENGL
ISH
To reach timer menu from frequency menu press once .
TIMERS MENU
BASIC PRODUCT USE (continued)
Display the required parameter formodification.Apply the same procedure as describedin the Setup Menu for network voltage
modification. Possible settings aredescribed in the previous table.
The timers menu integrates 5 para-meters described in the tablebelow.
The table explains parameters definition,settings possibilities, and default values.Timers operation is described in opera-tional flow chart page.
Press Down push button to access parameter required.
Press Up push button to come back to previous value
or Home push button to come back to .
Parameter modification
Parameter Display
2Mt: loss of mains validation timer. 0 to 60 sec. 5 sec.Once mains has disappeared, 2Mt is started. If Mains comes back before 2Mt ends, the commutation cycle is not started. (Delay on Gen start.)
At: Generator voltage and frequency 0 to 60 sec. 5 sec.stabilisation timer. Generator needs to be stable during AT to allow transfer from Mains.
1Mt: Mains Return validation timer. 0 to 30 min. 2 min.Once main is back 1Mt is started. If Mains disappears before 1Mt ends, the load is not switched back to the Mains.
rot: Run on time timer. Once the 0 to 10 min. 4 min.load is switched back from the Generator to the Mains, ROT is started and the Generator will stop once ROT is finished (allows generator cool down).
dbt: Dead Band timer. This timer is 0 to 20 sec. 5 sec.counted down before transferring the load from the Mains source to the Generator or vice versa. It allows the load residual voltage to decrease under a non critical value before transfer (Necessary in case of rotating loads).
Definition Setting range Default value
ATI
079
A
50 SOCOMEC - Rf.: 678 623 G GB
To reach timer menu from frequency menu press once .
COMMUNICATION MENU (OPTIONAL)
BASIC PRODUCT USE (continued)
Display the required parameter formodification.Apply the same procedure as describedin the Setup Menu for network voltage
modification. Possible settings aredescribed in the previous table.
The COMM menu integrates 4parameters described in the tablehereunder.The table explains parameters definition,settings possibilities, and default values.
Communication operation is described inparagraph 5.
Press Down push button to access parameter required.
Press Up push button to come back to previous value
or Home push button to come back to .
Parameter modification
Parameter Display
Slave Jbus/Modbus adress 001 to 247 005
Communication Speed 2400,4800,9600,(baud) 14400,19200,
28800, 38400 9600
Stop Bit 0,1,2 1
Parity No, Eve (Even), NoOdd
Definition Setting range Default value
This menu is only accessible when the optionhas been purchased and is present in the optional slots.Once plugged into the elec-tronic module, a 3 minutespower off action is requiredfor option identification bysoftware.
ATI
080
A
SOCOMEC - Rf.: 678 623 G GB 51
ENGL
ISH
To access requested value press , , or .
BASIC PRODUCT USE (continued)
Metering is active as soon as the unit ispowered.Commutation cycles have priority overVisualisation mode and display timerscount down as soon as they are active.Any value available in this mode canbe kept on the screen once displayed.excepted during commutation cycle;comes back to timer count down after5 s.
After commutation cycle, the displaycomes back to Mains voltage L1N (firstvariable of the mode).Visualisation mode architecture is asdescribed hereunder.
Product metering
General comments
General comments
Optional
If lightning protectionoption is fitted, LIP menu isavailable. cf option 4.
ATI
081
A
52 SOCOMEC - Rf.: 678 623 G GB
BASIC PRODUCT USE (continued)
Main Voltage L1-N
Main Voltage L2-N
Main Voltage L3-N
Main Voltage L1-L2
Main Voltage L2-L3
Main Voltage L3-L1
Main frequency
Generator Voltage L3-L1
Generator Frequency
Loss of Mains validation Timer
Delay on transfer Timer
Mains return validation timer
Run on timer (Generator cool down period)
Dead Band timer
Main -> Gen commutation Counter
Lightning protection operation (0 or 1)
Reminder:Mains sensing is 3 phases.Generator sensing is single phase.
3P4LMain U1, U2, U3
U12, U23, U31Gen U31
1P3LMain U12, U23, U31Gen U31
1P2LMain U31Gen U31
3P3LMain U12, U23, U31Gen U31
1PAPMain U1, U2, U3Gen U31
Values definition
LIP = option
All these values are notaccessible on all networks :
SOCOMEC - Rf.: 678 623 G GB 53
ENGL
ISH
BASIC PRODUCT USE (continued)
To access Manual Mode turn the frontkeyswitch to manual position.
Take the handle, attached to the chain,on the right side of the enclosure, tomanually operate the switch.Verify the switch position on the frontposition label before any manual operation.
from Position 1 turn clockwise toreach position 0
from position 0 turn clockwise toreach position 2
from position 2 turn anti clockwiseto reach position 0
from position 0 turn anti clockwiseto reach position 1
MANUAL MODE
Manual operation
Padlock is only possible in manualposition. handle must be out of its housing to
padlock padlock is possible in position 0, 1, 2.Manually pull the padlock handle toallow padlock insertion in the hole.
Padlocking
Once in manual mode it is possible: To access programming and
visualisation menus To padlock the switch To operate the switch with the handle To start the Gen using test off load
pushbutton.
Manual mode operation
Programming Visualisation PadlockingHandle
OperationStart Generator(Test off Load)
MANUAL MODE
Do not force the product
Do not leave the manualhandle in automatic mode.
54 SOCOMEC - Rf.: 678 623 G GB
BASIC PRODUCT USE (continued)
Turn the keyswitch from Manual toAutomatic position.The automatic mode must be activatedas soon as automatic starting of thegenerator and source switching isrequired after loss of mains condition.
The unit integrates a power capacitorsource to provide enough power duringblack out (loss of mains) to wait for gen-erator starting. (It does not have power todrive the switch to zero position). Furtherexternal protection will be required ifphasing is a concern.
AUTOMATIC MODE
Once in automatic mode it is possible: To access programming and visuali-
sation menus To start off load or on load testing To start a loss of Mains sequence To start a Mains return sequence
Possible actions
As soon as the unit is switched fromManual to Automatic mode, the auto-matic cycle is started.
Mains and Generator voltage & frequency are verified to define thenew stable position of the switch.
The same table is considered after acomplete power off action (PowerCap must be completely discharged= 3 minutes).
Manual-automatic mode/power return condition
Programming VisualisationOff loadtesting
On loadtesting
Loss of Mainssequence
Mains Returnsequence
AUTO MODE
Original switch position Status of supply New position
Mains Available, genset available or unavailable Mains
Mains Mains unavailable for 2MT time period, Genset. If genset unavailable startgenset available or unavailable genset first and wait for AT timer
period before transfer
Genset Genset on load, mains unavailable Genset
Genset Genset on load, mains available Mainsfor 1MT time period
Zero Mains available, genset unavailable Genset to count down 1MT before transfer to Mains
Zero Mains available, genset available Mains
Zero Mains unavailable, genset available Genset
Zero Mains unavailable, genset unavailable No action (because no supply).When supply becomes availablechange to mains or genset
New stable switch position:
The switch immediately transfers as soon as the keyswitch is turned fromManual to Automatic mode or as soon as Power comes back.
Read timers definition for 1MT or 2MTunderstanding.
SOCOMEC - Rf.: 678 623 G GB 55
ENGL
ISH
BASIC PRODUCT USE (continued)
This Sequence is started as soon asthe switch is in automatic mode and inposition 1.Position 1: Mains is available Switch is in position 1 (Mains) Generator is on or off
Remote AT timer InhibitIt is possible to bypass the At timerusing the ATI input (closing the contact)when At timer setting is at its maximumvalue = 60s. Active when At = At Max = 60 s
(cf programming mode). When input ATI (terminals 7-8) is high,
At is bypassed.
LOSS OF MAINS AUTOMATIC SEQUENCE Specific features
Sequence description
Reset 2MT
Stop gen
Automatic mode
Power Cap Activation until Genset availability
Loss of main?
Count down 2MT
Reset AT
Start Genset
No
No
No
No
No
Gen fails
Yes
Yes
Yes
Yes
Yes
AT = 0
2MT = 0
Main comes backbefore 2MT ends?
Loss ofmains?
Genset start up
Transfer 1 >2
ATI = ATmax ?
Mains avaible ?
Generatoravailable?
Count down AT
Transfer 1 > 0
Count down DBT
Transfer 0 > 2 Transfer 1 > 2
Go to mains return automatic
sequence
DBT 0 ?NoYes
DBT = 0
ATI = 1 ?
ATI
083
A
56 SOCOMEC - Rf.: 678 623 G GB
BASIC PRODUCT USE (continued)
This sequence is started as soon as theunit is in automatic mode and in posi-tion 2.Position 2: Mains is not available Switch is in position 2 (Generator) Generator is off
Retransfer Inhibit Feature Once the Mains is back, it might be
preferable not to immediately transferthe load from the generator to themains.
If Retransfer inhibit feature has beenenabled in the programming mode,the RTI led is on (default value).
Once retransfer from the Generatorto the Mains is ready, RTI featureblocks the retransfer and the RTI ledis blinking.
A manual press on the RTI push but-ton is necessary to start retransfer.
MAINS RETURN AUTOMATIC SEQUENCE
Specific features
RTI Led
RTI pushbutton
ATI
084
A G
B
SOCOMEC - Rf.: 678 623 G GB 57
ENGL
ISH
BASIC PRODUCT USE (continued)Sequence description
Reset 1MT
Main not availableGenerator running &Switch in position 2
Stop generatorposition 1
Back to mains control
Mains return?
Count down 1MT
Transfer 2 > 0
Count Down DBT
Transfer 0 > 1 Transfer 2 > 1
No
Yes
Yes
Yes
Yes
Yes
DBT = 0
No
No No
No
1MT = 0
Mains lost againbefore 1MTtimes out?
Mainsreturn
Manual re-transfer
DBT 0?
To loss of mains sequence
RTI PBpressed ?
Loss of mains
ROT = 0
Count Down ROT
Loss ofMains ?
Reset ROT
RTIactivated?
Transfer 2 >1
ATI
085
A G
B
58 SOCOMEC - Rf.: 678 623 G GB
BASIC PRODUCT USE (continued)Test Mode
Press and hold the test pushbutton for5 seconds to allow test modes access.
Enter code = 4000
Press during 5 sec
Press 4 times to display 4
Validate
TEST MODE EXIT
TEST MODE ACCES
Press and hold the test pushbutton for5 seconds to exit test mode and comeback to visualisation mode after testachievement.
TEST
ATI
086
A
SOCOMEC - Rf.: 678 623 G GB 59
ENGL
ISH
BASIC PRODUCT USE (continued)
OFF LOAD TESTING
This test is possible in automatic inposition 1 when the mains is avai-lable or in manual mode. It can beconsidered as a Generator manualstart in manual mode.
This mode allows generator testingwithout load transfer from the Mainsto the Generator.
The generator is started and stoppednormally
This test is possible in automatic ormanual mode
This test is not possible when anautomatic sequence is running.
Description
Press Test pushbutton to make test offload Led blink and press validationpushbutton to start.
Sequence
Start Gen
Validate
Validate
Validate
Press Test Push button
Test off Load Led blinks ?
Stop G ?
Gen ?
Yes
Yes
No
No
No
TESTPress Test Push button
5 seconds to exit
TEST
ATI
087
A G
B
60 SOCOMEC - Rf.: 678 623 G GB
BASIC PRODUCT USE (continued)
ON LOAD TESTING
This test is only possible in automa-tic mode in position 1 and Mainsavailable.
Description: This test simulates a loss of mains
condition. Loss of Mains sequence isstarted and Mains return sequenceautomatically activated as soon asgenerator is available.
All timers are run following their set-ting.
The retransfer inhibit feature isalways activated during test on load(from keypad).
Press Test pushbutton to make teston load Led blinking and press vali-dation pushbutton to start the cycle,Following Loss of Mains + Mainsreturn sequences.
Keypad activation
It is possible to remotely start the teston load closing contacts 7 and 9 onthe electronic module.The cycle is started as soon as theinput is closed.The retransfer from generator to mainsis blocked, and only allowed once theinput is de activated.
Remote activation via remote teston load input
Source availability 2 green Leds to indicate if
Gen and Mains sources are available (voltage and frequency measurement)
- Led is on = source available- Led is off = source missing
Retransfer Inhibit 1 yellow Led, linked to
retransfer inhibit pushbutton- Led is on = retransfer
inhibit feature is active- Led is off = retransfer
inhibit inactive- Led is blinking = retransfer
is blocked, waiting for a push on the retransfer inhibit pushbutton to allow retransfer
Switch state 2 green Leds to indicate if
the switch is opened or closed- Led is on = switch is closed- Led is off = switch is opened
1 Yellow led to indicate if both switches are in 0 position- Led is on = both switches opened- Led is off = Gen or Mains
switch closed
Error Led 1 red led to indicate a fault
- Led is on = switch errorAction from software not confirmed by an auxiliary contact. Reset after power off- Led blinks in case of lightning protection operation No reset required (blinking disappears once input is low)
Power Led 1 green led
- Blinks slowly as soon as the product is powered and software runs correctly
- Always on = Power OK and software error
- Always off = Power off or software error if another led is on and LCD is OK
Keyswitch Insert key to allow switch
operational mode modification Turn right to access automatic mode Turn left to access manual mode
Padlock Pull the yellow handle to allow padlock insertion Padlocking possible in position 0,1 or 2
but only in Manual mode (keyswitch position), handle out of housing.
Keypad
Switch Position Indications 0, 1 or 2 position display
Manual Operation Insert handle to manually
operate the switch. Manual operation only possible
in Manual mode (keyswitch), when not padlocked
Modes annunciation and Tests 1 Top yellow led for Manual Mode position linked
to the key position 1 green led for Automatic Mode position linked
to the key position 2 Bottom yellows leds for Test On and
Off Load position Linked to the test pushbutton pressSymbols are represented to make comprehension easier
LCD Larger LCD to display information.
Push button
: Home push button during programming
: Lamps test button
SOCOMEC - Rf. : 678 623 G GB 61
ENGL
ISH
METERING PRODUCT USE
GENERAL INTRODUCTIONThe product provides sources availabilitymonitoring, Automatic/Manual Retransfer,Manual / Automatic or Test operationmonitoring, voltage and frequency metering,and good operation or error information. Theproduct provides sources error information.Furthermore, the metering module allowscurrent and power metering on a large back-lited display.
The product requires at least one type ofnetwork configuration and a network nominalvoltage configuration to be input via thekeypad by the user.Other default values can be kept or modifiedaccording to hereafter programming guide-lines.
ELECTRONIC MODULE USAGE
The electronic module is directly mountedon the motorized block.
It integrates the following features:- Voltage and frequency metering- Automatic transfer controls
Following diagram introduces productfront panel.
Led indication is only active once theproduct is powered (power ledactivated).
Front Panel Introduction
Verify power applied on theelectronic module power inputsterminals 101-102 or 201-202before powering up the unit.
ATI
067
A
ATI
068
B
ATI
070
B
62 SOCOMEC - Rf. : 678 623 G GB
METERING PRODUCT USE (continued)
Software version is displayed on theunit after reset (powering up action after3 minutes power off to discharge theunit).
Software version
Product Programming is possible inAutomatic Mode in position 1 when theMains Source is available, or in Manualmode.
It is not accessible when a test or anautomatic sequence is activated.
Programming mode is accessible bypressing and holding the validation push-button for 5 seconds and then enteringthe code 1000:
Product ProgrammingBefore first product use,
access programming modeand verify product programming parameters.
PROGRAMMING ACCESS
To exit the Programming and comeback to visualisation mode, hold thevalidation pushbutton for 5 seconds.Parameters saved permanently once exit.
PROGRAMMING EXIT
Press for 5 seconds
Press once to display 1
Validate
Access to programming Menus
{ {
Version Number
ATI
069
B
SOCOMEC - Rf. : 678 623 G GB 63
ENGL
ISH
Default values areloaded as standard.
METERING PRODUCT USE (continued)
Setup: Network parametersVoltage levels: Voltage detection levelsFreq. levels: Frequency detection levelstimers: Automatic timer settingsCommunication: Communication parameters (Optional), communication
module must be plugged.
PROGRAMMING MENUS
Setup parameters must always be verified/modified in accordance to theapplication.
Architecture and navigation
The first menu to access is the Setup menu
The programming mode integrates 5 Menus
Option
ATI
071
B
ATI
072
B
64 SOCOMEC - Rf. : 678 623 G GB
METERING PRODUCT USE (continued)
The setup menu integrates 6 parame-ters described in the table hereunder.The table explains parameters definition,settings possibilities, and default values.
Press Down push button to access parameter required.
Press Up push button to come back to previous value, or press
or Home push button to come back to
SETUP MENU
NOM.VOLT: Phase-Phasenominal voltage.
From 200 to 480 V 400 V AC
NETWORK: Network configuration.Type of metering (1P or 3Pphases).Number of active wires (2L,3L or 4L) definition.
1P2L, 1P3L, 3P4L 3P4L3P3L, 1PAP
NOM.FREQ: Nominal frequency. 50 or 60 Hz 50 Hz
TRANS IHI: Retransfer inhibit feature:press on RTI buttonrequired to allow retransferfrom gen to main.
Yes or No No
CNT RST: Reset number of commuta-tion counter (from Main toGen).Displays no once reset.
Yes or No No
Definition Setting range Default value
Parameter Display
ATI
073
C
CT: winding ratio of current transformers50/5 to 1600/5
50/5 to 1600/5 500/5
ATI
075
B
ATI
076
B
ATI
074
B
SOCOMEC - Rf. : 678 623 G GB 65
ENGL
ISH
METERING PRODUCT USE (continued)
To return to Setup menu press home pushbutton or press down to continue.
Press to access the first digit (blinking)
Press twice to display 2 (blinking)
Press to access the second digit (blinking)
Press 3 times to display 3 (blinking)
Press to validate the value
Press to return to Setup menu Press to reach next parameter
Parameter modification
Display the required parameter formodification.Apply the same procedure describedhereunder for network voltage modifica-tion, to all other parameters. Possible
settings are described in the previoustable.Example:We want to modify network voltagefrom 400V to 230V.
ATI
077
B
66 SOCOMEC - Rf. : 678 623 G GB
METERING PRODUCT USE (continued)
To reach voltage menu from Setup menu press once .
The voltage menu integrates 8 parame-ters described in the table hereunder.The table explains parameters defini-tion, settings possibilities, and defaultvalues.Over and Under voltage conditions areverified on Mains and Generator side toallow operation as per the flow chart.Mains sensing is 3 phase and
Generator sensing single phase.Over and under voltage detection lev-els + hysteresis are defined as per-centage of nominal voltage.Hysteresis levels allow under and overvoltage conditions reset (voltage needsto pass hysteresis level to reset).
Press Down push button to access parameter required.
Press Up push button to come back to previous value
or Home push button to come back to
VOLTAGE MENU
OV U: Main Over voltage detection 102 - 120% 115%
OV U HYS: Main Over voltage hysteresisdetection
101 - 119% 110%
UND.U: Main Under voltage detection 80 - 98% 85%
UND.U HYS: Main Under voltage hys-teresis detection
81 - 99% 95%
OV U: Generator over voltage detection 102 - 120% 115%
OV U HYS: Generator over voltagehysteresis detection
101 - 119% 110%
UND.U: Generator under voltagedetection
80 - 98% 85%
UND.U HYS: Generator under voltagehysteresis detection
81 - 99% 95%
Definition Setting range Default value
Note:These values only need to bechanged if a value is required otherthan the default.
Parameter Display
SOCOMEC - Rf. : 678 623 G GB 67
ENGL
ISH
To reach frequency menu from voltage menu press once .
FREQUENCY MENU
METERING PRODUCT USE (continued)
Display the required parameter formodification.Apply the same procedure as describedin Setup Menu for network voltage mo-
dification. Possible settings are describedin the previous table.
The frequency menu integrates 8 parameters described in the table hereunder.
The table explains parameters definition,settings possibilities, and default values.Over and Under frequency conditions areverified on Mains and Generator side toallow operation following operational flowchart.
Over and under frequency detection levels+ hysterisis are defined as percentage ofnominal frequency.Hysteresis levels allow under and overfrequency conditions reset (frequencyneeds to pass hysteresis level to reset).
Press Down push button to access parameter required.
Press Up push button to come back to previous value
or Home push button to come back to.
Parameter modification
Parameter Display
OV F: Main over frequency detection 101 - 120% 105%
OV F HYS: Main over frequencyhysteresis
100.5 - 119.5% 103%
Definition Setting range Default value
UND.F: Main under frequency 80 - 99% 95%
UND.F HYS: Main Under frequencyhysteresis
80.5 - 99.5% 97%
OV F: Generetor over frequency 101 - 120% 105%
OV F HYS: Generator over frequencyhysteresis
100.5 - 119.5% 103%
UND.F: Generator under frequency 80.5 - 99.5% 95%
UND.F HYS: Generator under frequencyhysteresis
80 - 99% 97%
ATI
078
B
68 SOCOMEC - Rf. : 678 623 G GB
To reach timer menu from frequency menu press once .
TIMERS MENU
METERING PRODUCT USE (continued)
Display the required parameter formodification.Apply the same procedure as describedin the Setup Menu for network voltage
modification. Possible settings aredescribed in the previous table.
The timers menu integrates 5 para-meters described in the tablebelow.
The table explains parameters definition,settings possibilities, and default values.Timers operation is described in opera-tional flow chart page.
Press Down push button to access parameter required.
Press Up push button to come back to previous value
or Home push button to come back to .
Parameter modification
Parameter Display
2Mt: loss of mains validation timer. 0 to 60 sec. 5 sec.Once mains has disappeared, 2Mt is started. If Mains comes back before 2Mt ends, the commutation cycle is not started. (Delay on Gen start.)
At: Generator voltage and frequency 0 to 60 sec. 5 sec.stabilisation timer. Generator needs to be stable during AT to allow transfer from Mains.
1Mt: Mains Return validation timer. 0 to 30 min. 2 min.Once main is back 1Mt is started. If Mains disappears before 1Mt ends, the load is not switched back to the Mains.
dbt: Dead Band timer. This timer is 0 to 20 sec. 5 sec.counted down before transferring the load from the Mains source to the Generator or vice versa. It allows the load residual voltage to decrease under a non critical value before transfer (Necessary in case of rotating loads).
rot: Run on time timer. Once the 0 to 10 min. 4 min.load is switched back from the Generator to the Mains, ROT is started and the Generator will stop once ROT is finished (allows generator cool down).
Definition Setting range Default value
ATI
079
B
SOCOMEC - Rf. : 678 623 G GB 69
ENGL
ISH
To reach timer menu from frequency menu press once .
COMMUNICATION MENU (OPTIONAL)
METERING PRODUCT USE (continued)
Display the required parameter formodification.Apply the same procedure as describedin the Setup Menu for network voltage
modification. Possible settings aredescribed in the previous table.
The COMM menu integrates 4parameters described in the tablehereunder.The table explains parameters definition,settings possibilities, and default values.
Communication operation is described inparagraph 5.
Press Down push button to access parameter required.
Press Up push button to come back to previous value
or Home push button to come back to .
Parameter modification
Parameter Display
Slave Jbus/Modbus adress 001 to 247 005
Communication Speed 2400,4800,9600,(baud) 14400,19200,
28800, 38400 9600
Stop Bit 0,1,2 1
Parity No, Eve (Even), NoOdd
Definition Setting range Default value
This menu is only accessible when the optionhas been purchased and is present in the optional slots.Once plugged into the elec-tronic module, a 3 minutespower off action is requiredfor option identification bysoftware.
ATI
080
B
70 SOCOMEC - Rf. : 678 623 G GB
To access requested value press , , or .
METERING PRODUCT USE (continued)
Metering is active as soon as the unit ispowered.Commutation cycles have priority overVisualisation mode and display timerscount down as soon as they are active.Any value available in this mode canbe kept on the screen once displayed.excepted during commutation cycle;comes back to timer count down after5 s.
After commutation cycle, the displaycomes back to Mains voltage L1N (firstvariable of the mode).Visualisation mode architecture is asdescribed hereunder.
PRODUCT METERING
General comments
General commentsIf lightning protection
option is fitted, L.PROTECTmenu is available. cf option 4.
Option
ATI
081
B
SOCOMEC - Rf. : 678 623 G GB 71
ENGL
ISH
METERING PRODUCT USE (continued)
Mains and Generator sensing are 3 phases.
3P4LMain U1, U2, U3
U12, U23, U31Gen U1, U2, U3, U12, U23, U31
1P3LMain U12, U23, U31Gen U12, U23, U31
1P2LMain U31Gen U31
3P3LMain U12, U23, U31Gen U12, U23, U31
1PAPMain U1, U2, U3Gen U1, U2, U3
Values definition
All these values are notaccessible on all networks :
LIGHTNINGPROTECTION= option
Main Voltage L1-N, L2-N, L3-N
Main Voltage L1-L2, L2-L3, L3-L1
Main frequency
Generator Voltage L1-N, L2-N, L3-N
Generator Voltage L1-L2, L2-L3, L3-L1
Generator Frequency
Current I1, I2, I3
Current in the neutral
Loss of Mains validation Timer
Delay on transfer Timer
Mains return validation timer
Dead Band timer
Power factor (over all)
Total active power on 4 quadrants (+/-)
Run on timer (Generator cool down period)
Main -> Gen commutation Counter
Total reactive power on 4 quadrants (+/-)
Total apparent power
Lightning protection operation (0 or 1)
72 SOCOMEC - Rf. : 678 623 G GB
METERING PRODUCT USE (continued)
The functionality is similar to the basicproduct (see the manual mode of thebasic product paragraph).
The sequence is similar to the basicproduct.
MANUAL MODE
This sequence is started as soon as theunit is in automatic mode and in posi-tion 2.Position 2: Mains is not available Switch is in position 2 (Generator) Generator is off
Retransfer Inhibit Feature Once the Mains is back, it might be
preferable not to immediately transferthe load from the generator to themains.
If Retransfer inhibit feature has beenenabled in the programming mode,the RTI led is on (default value).
Once retransfer from the Generatorto the Mains is ready, RTI featureblocks the retransfer and the RTI ledis blinking.
A manual press on the RTI push but-ton is necessary to start retransfer.
MAINS RETURN AUTOMATIC SEQUENCE
Specific features
RTI LedRTI pushbutton
ATI
084
B G
B
ATI
086
B
SOCOMEC - Rf. : 678 623 G GB 73
ENGL
ISH
METERING PRODUCT USE (continued)Test Mode
Press and hold the test pushbutton for5 seconds to allow test modes access.
Enter code = 4000
Press during 5 sec
Press 4 times to display 4
Validate
TEST MODE EXIT
TEST MODE ACCES
Press and hold the test pushbutton for5 seconds to exit test mode and comeback to visualisation mode after testachievement.
Test on load and test off load facilitiesare similar to the basic product.
TEST
74 SOCOMEC - Rf. : 678 623 G GB
COMMUNICATIONThe JBUS/MODBUS used by the ATIinvolves a dialogue using a master-slave hierarchical structure. There aretwo possible dialogues: the master communicates with a
slave (ATI) and waits for its reply the master communicates with all the
slaves (ATI) without waiting for theirreply.
The mode of communication is theRTU (Remote Terminal Unit) usinghexadecimal characters of at least 8bits.
According to the JBUS / MODBUSprotocol, transmission time must beless than 3 silences, i.e. the emissiontime of 3 characters so that the mes-sage is processed by the ATI.
To correctly use information, thefollowing functions are important:
3 : to read n words (maximum 128).6 : to write one word.8 : to diagnose exchanges between
the master and the slave viameters 1, 3, 4, 5 and 6.
16 : to write n words (maximum 128).
LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)
Table of values on 2 words
The standard communications frameconsists of :
Slave address Function code Address Data CRC 16
NB:When selecting slave address 0, amessage is sent to all the instrumentspresent on the network (only for func-tions 6 and 16).
Comment:The maximum reply time is 250 ms.
Decimal Hexa Number Address Address of words Variable Units
768 300 2 I1 A/100770 302 2 I2 A/100772 304 2 I3 A/100774 306 2 In A/100776 308 2 U12Main V/100778 30A 2 U23Main V/100780 30C 2 U31Main V/100782 30E 2 V1Main V/100784 310 2 V2Main V/100786 312 2 V3Main V/100788 314 2 Freq.Main Hz/100790 316 2 Active power (total) kW/100792 318 2 Reactive power (total) kVar/100794 31A 2 Apparent power (total) kVA/100796 31C 2 Power factor 0,001880 370 2 U12 Gen V/100882 372 2 U23 Gen V/100884 374 2 U31Gen V/100886 376 2 V1Gen V/100888 378 2 V2Gen V/100890 37A 2 V3Gen V/100892 37C 2 FreqGen Hz/100894 37E 1 1MT V/100895 37F 1 2MT V/100896 380 1 AT s897 381 1 DBT s898 382 1 ROT s
Example:To read U31 gen = 228,89, thefollowing message should be sent:
SOCOMEC - Rf. : 678 623 G GB 75
ENGL
ISH
Table of values on 1 word
Decimal Hexa Number Address Address of words Variable Units
1792 700 1 U12 Main V/1001793 701 1 U23 Main V/1001794 702 1 U31 Main V/1001795 703 1 V1 Main V/1001796 704 1 V2 Main V/1001797 705 1 V3 Main V/1001798 706 1 Freq. Main Hz/1001799 707 1 U12 Gen V/1001800 708 1 U23. Gen V/1001801 709 1 U31 Gen V/1001802 70A 1 V1. Gen V/1001803 70B 1 V2. Gen V/1001804 70C 1 V3. Gen V/1001805 70D 1 Freq. Gen Hz/1001806 70E 1 1MT Timer s1807 70F 1 2MT Timer s1808 710 1 AT Timer s1809 711 1 DBT Timer s1810 712 1 ROT Timer s1813 715 1 I1 A/1001814 716 1 I2 A/1001815 717 1 I3 A/1001816 718 1 In A/1001817 719 1 Active power (total) kW1818 71A 1 Reactive power (total) kVar1819 71B 1 Apparent power (total) kVA1820 71C 1 Power factor 0,001
COMMUNICATION (continued)
LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3) (continued)
Slave
05
Function
03
High-orderaddress
03
Low-orderaddress
74
High-order word n
00
Low-order word n
02
CRC 16
85D1
ATI reply:
Decimal value = 89 x 256 + 105= 22889 (/100)
Slave
05
Function
03
Numberof bytes
04
Valuehigh-order
59
Valuelow-order
69
CRC 16
458DHex
Dec 89 105
76 SOCOMEC - Rf. : 678 623 G GB
COMMUNICATION (continued)
Example:Configuration of 233 V nominalvoltage for ATI n 5.
Hex
Slave
05
Function
10
High-orderaddress