AT E M M O D U L E 3 : C O N T R O L SA c c r e d i t e d T e x a s E n e r g y M a n a g e r

Page 2: ATEM MODULE 3: CONTROLS - TEMA COURSES

System Types

❯Manual

❯Programmable thermostats

❯Mechanical time clocks

❯Electronic time clocks

❯Pneumatic controls

❯Networked thermostats

❯Direct digital control (DDC)

A c c r e d i t e d T e x a s E n e r g y M a n a g e r

Page 3: ATEM MODULE 3: CONTROLS - TEMA COURSES

Pneumatic Control Systems

A c c r e d i t e d T e x a s E n e r g y M a n a g e r

❯Air compressor

❯Piping & tubing

❯Sensors

❯Actuators

Page 4: ATEM MODULE 3: CONTROLS - TEMA COURSES

DDC System Components

❯Desktop or laptop computer

-Operator workstation

-Programming

-Network interface

❯Controllers – executes control

logic based on inputs

-Building

-Local

❯Communications interfaces

❯Sensors

❯Data

-Analog – variable

-Digital – 0 or 1/on-off/open-closed

❯Network cabling

A c c r e d i t e d T e x a s E n e r g y M a n a g e r

Page 5: ATEM MODULE 3: CONTROLS - TEMA COURSES

e n e r g y m a n a g e m e n t p r o g r a m : f u n d a m e n t a l s a n d d e v e l o p m e n t

DDC System Architecture

BC

CC C

Internet

Page 6: ATEM MODULE 3: CONTROLS - TEMA COURSES

e n e r g y m a n a g e m e n t p r o g r a m : f u n d a m e n t a l s a n d d e v e l o p m e n t

DDC Inputs & Outputs

Controller

Co

ntr

ol O

utp

utsSen

sor In

pu

ts

Valve open/closeDamper open/closeMotor off/onIndicator lightAlarm

TemperaturePressure

FlowHumidity

Motor statusSwitch position

Page 7: ATEM MODULE 3: CONTROLS - TEMA COURSES

DDC System Functions

❯Scheduling

-Normal work days

-Events

-Weekends

-Holidays

❯Control strategies

-Optimum start & stop

-Demand limiting

-Temperature resets

❯Monitoring

❯Logging & trending

❯Diagnostics & troubleshooting

❯Alarming

A c c r e d i t e d T e x a s E n e r g y M a n a g e r

Page 8: ATEM MODULE 3: CONTROLS - TEMA COURSES

DDC Protocols

❯BACNet

-Open protocol

-Developed by ASHRAE

-Specifically for building equipment

control

❯LONTalk

-Proprietary protocol

-Developed by Echelon Corp.

-Special micro-compressor chip

required for communication

❯Tridium (Niagra)

-Proprietary built on open

standards

-Allows integration of diverse

systems

A c c r e d i t e d T e x a s E n e r g y M a n a g e r

Page 9: ATEM MODULE 3: CONTROLS - TEMA COURSES

Demand Control Ventilation

❯Utilize in area w/ high occupancy levels

❯Uses CO2 levels to estimate occupancy

❯Controls outside air flow w/ modulating dampers

-Closed at zero occupancy (low CO2 level)

-Full open at maximum occupancy (high CO2 level)

A c c r e d i t e d T e x a s E n e r g y M a n a g e r

Page 10: ATEM MODULE 3: CONTROLS - TEMA COURSES

Utilizing Economizers

❯Supplies 100% outside air for cooling

❯Compressors do not operate

❯Takes advantage of mild outdoor

conditions

❯Control types

-Dry bulb

› Less humid climates

› Temperature only

-Enthalpy

› More humid climates

› Temperature & humidity

A c c r e d i t e d T e x a s E n e r g y M a n a g e r

Page 11: ATEM MODULE 3: CONTROLS - TEMA COURSES

e n e r g y m a n a g e m e n t p r o g r a m : f u n d a m e n t a l s a n d d e v e l o p m e n t

Economizer Operation

Page 12: ATEM MODULE 3: CONTROLS - TEMA COURSES

Setpoints

A c c r e d i t e d T e x a s E n e r g y M a n a g e r

❯Occupied

-Occupant comfort

-Energy savings

-Cooling costs rise 1.5% for each degree below 72º

-Heating costs rise 1% for each degree above 68º

❯Unoccupied

-Energy savings

-Prevent building damage

-Use instead of turning systems off

Page 13: ATEM MODULE 3: CONTROLS - TEMA COURSES

Control Strategies

❯Demand limiting

-Demand limit setting

-Loads shed when setting reached

-Reduces peak demand & utility charges

❯Optimal startup

-Heating or cooling started before occupied time

-Setpoint reached at scheduled occupied time

❯Optimum stop

-Heating or cooling setback while facilities occupied

-Building allowed to “coast”

A c c r e d i t e d T e x a s E n e r g y M a n a g e r

Page 14: ATEM MODULE 3: CONTROLS - TEMA COURSES

More Control Strategies

❯Supply air temperature reset

-Based on return air or outside air temperature

-Reduces amount of reheat during cooling

❯Chilled water temperature reset

-Raise temperature of chilled water

-Based on outdoor temperature & humidity

-Caution not to raise temperature too much in humid conditions

❯Condenser water temperature reset

- Decrease temperature of water leaving cooling tower

- Increases chiller efficiency

- Reduces chiller capacity

A c c r e d i t e d T e x a s E n e r g y M a n a g e r

Page 15: ATEM MODULE 3: CONTROLS - TEMA COURSES

e n e r g y m a n a g e m e n t p r o g r a m : f u n d a m e n t a l s a n d d e v e l o p m e n t

Sample Display Screen

Page 16: ATEM MODULE 3: CONTROLS - TEMA COURSES

e n e r g y m a n a g e m e n t p r o g r a m : f u n d a m e n t a l s a n d d e v e l o p m e n t

Sample Display Screen

Page 17: ATEM MODULE 3: CONTROLS - TEMA COURSES

Ashley Williams, MCRP & ATEM

❯ Texas Energy Managers Association

❯ Director of Curriculum and Certification

[email protected]

questions

e n e r g y m a n a g e m e n t p r o g r a m : f u n d a m e n t a l s a n d d e v e l o p m e n t

Texas Energy Managers Association

❯ www.texasema.org

Page 18: ATEM MODULE 3: CONTROLS - TEMA COURSES