SECURITY IMPROVEMENTS
AT
THERESA MAHLEREARLY EDUCATION SCHOOL
990 CHURCH STREETSAN FRANCISCO, CA 94114
SFUSD Project No. 12064
CCTV SURVEILLANCE SYSTEM INSTALLATION
SCOPE OF WORK FOR THIS PROJECT IS NEW CAMERAS AND SECURITY MONITORING SYSTEM, ALONG WITH NEW VIDEO RECORDING NVR (1) AND ALL CABLING, CONDUIT, WIREWAY ,
POWER SUPPLIES AND NECESSARY INFRASTRUCTURE TO PROVIDE A WORKING AND OPERABLE SYSTEM PER PLANS AND SPECIFICATIONS.
NEW AIPHONE VIDEO ENTRY INTERCOM STATIONS , CONSISTING OF DOOR STATIONS, MASTER STATIONS AND CONTROLLER, POWER SUPPLIES AND CABLING, CONDUIT, BOXES, ETC.
SFUSD HAS SPECIFIC CCTV REQUIREMENTS, SEE SPECIFICATIONS FOR VENDORS, CAMERAS, DISPLAY SCREENS, CABLING, ETC.
(NOTE THAT ALL NEW HOLES, PENETRATIONS, DRILLING, ANCHORS, ETC. WILL NEED TO BE INSPECTED BY DISTRICT HAZ MAT CONSULTANT. ALL DISTRICT PROCEDURES MUST BE
FOLLOWED FOR ALL WALL AND FLOOR PENETRATIONS AND ATTACHMENTS.)
PROJECT SITE LOCATION
THERESA S MAHLER EES
990 CHURCH STREET
SAN FRANCISCO, CA 94114
TY-01
TITLE PAGE, SCOPE AND
DRAWING INDEX
SITE NO.
SCALE
DATECHECKED BY
S.F.U.S.D. PROJECT NO.
SHEETS
DRAFTER
OF
XXXX05/31/18 JSM -
12064
CONSTRUCTION
DESIGN &
FACILITIES
135 Van Ness Avenue
San Francisco, California 94102
Tel (415) 355-6979
Fax (415) 355-6988
Architect Engineer
School Name and Address
Project Name
Date No. Revisions
SHEET NO.
DRAWING TITLE
Approvals
AS NOTED
SFUSD SAN FRANCISCOPUBLIC SCHOOLS
Consultant Name and Address
05/15/2018 - BID ISSUE
G U T T M A N N B L A E V O E T
C O N S U L T I N G E N G I N E E R S
E
P F
THERESA MAHLER
EARLY EDUCATION SCHOOL
990 CHURCH STREET
SAN FRANCISCO, CA 94114
SFUSD PROJ. #12064
SECURITY
IMPROVEMENTS
TY- 01 TITLE PAGE, SCOPE AND DRAWING INDEX
TY- 02 WIRE LEGEND , SYMBOLS AND ABBREVIATIONS
TY- 03 GENERAL NOTES AND PROJECT NOTES
TY- 2.1 CCTV SURVEILLANCE AND VIDEO ENTRY INTERCOM PARTIAL FLOOR PLAN - MISSION CAMPUS
TY- 5.1 SECURITY SYSTEM BLOCK RISER DIAGRAM & CAMERA MATRIX SCHEDULE
TY - 7.1 SECURITY DETAILS
TY - 7.2 SECURITY DETAILS
TY - 7.3 SECURITY DETAILS
RATED WALL
ALL PENETRATIONS THROUGH RATED
WALLS MUST BE FIRE SEALED AND CAULKED
A AMPERES
ACAMS ACCESS CONTROL AND ALARM MONITORING SYSTEM
AFF ABOVE FINISHED FLOOR
AWG AMERICAN WIRE GAUGE
BAS BUILDING AUTOMATION SYSTEM
BDF BUILDING DISTRIBUTION FACILITY
C CONDUIT
CAT3 CATEGORY 3 TWISTED PAIR UTP CABLE
CAT5E CATEGORY 5E TWISTED PAIR UTP CABLE
CAT6 CATEGORY 6 TWISTED PAIR UTP CABLE
CATV COMMUNITY ANTENNA TELEVISION
CEC CCTV EQUIPMENT CABINET
DIV DIVISION
(E) EXISTING
EC ELECTRICAL CONTRACTOR
EMS ELECTRIC MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
(ER) EXISTING REPLACE
(F) FUTURE
FACP FIRE ALARM CONTROL PANEL
FATC FIRE ALARM TERMINAL CABINET
FO FIBER OPTIC
REX REQUEST TO EXIT
SAD SEE ARCHITECTURAL DRAWINGS
SEC SECURITY EQUIPMENT CABINET
SM SINGLEMODE OPTICAL FIBER
SCTP SCREENED TWISTED PAIR
STR STRAND(S) OF FIBER
STP SHEILDED TWISTED PAIR
TBB TELECOM BONDING BACKBONE
TBC TELECOM BONDING CONDUCTOR
TGB TELECOM GROUNDING BUSBAR
TMGB TELECOM MAIN GROUNDING BUSBAR
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
UTP UNSHEILDED TWISTED PAIR
V VOLTS
WP WEATHERPROOF
NOT ALL ABBREV. MAY BE
USED ON THIS PROJECT
GC GENERAL CONTRACTOR
IDF INTERMEDIATE DISTRIBUTION
FACILITY
JB JUNCTION BOX
LCP LIGHTING CONTROL PANEL
MDF MAIN DISTRIBUTION FACILITY
MH MAINTENANCE HOLE
MM MULTIMODE FIBER OPTIC CABLE
MPOE MINIMUM POINT OF ENTRY
MT EMPTY
N or (N) NEW
NC NORMALLY CLOSED
NO NORMALLY CLOSED
NTS NOT TO SCALE
OC ON CENTER
OSP OUTSIDE PLANT
PB PULL BOX
PNL PANEL
PR PAIR (OF COPPER CONDUCTORS)
PVC POLYVINYL CHLORIDE
TY-02
WIRE LEGEND , SYMBOLS
AND ABBREVIATIONS
SYMBOL DESPCRIPTION
SECURITY TERMINAL OR SYSTEMS CABINET
BOX
N/A
RING
N/A
MT. HT CONDUIT
3/4" MIN
NOTES
SEE KEYED NOTES, GENERAL NOTES AND
SPECIFICATIONS FOR SIZE AND TYPE
STC RSTC
SECURITY CAMERA - DOME TYPE FIXED FOCAL LENGTH
WP
SECURITY CAMERA - DOME TYPE FIXED FOCAL LENGTH
WEATHERPROOF
SECURITY AND ACCESS CONTROL SYMBOL LEGEND
WP
SECURITY CAMERA - DOME TYPE PTZ WEATHERPROOF
IC
M
IC
CA
SECURITY DOOR ENTRY SYSTEM CAMERA AND CALL STATION
SECURITY DOOR ENTRY VIDEO MONITOR STATION
MFR.
MFR.
MFR.
+102"
+120"
+120"
+72" TO
TOP
NVR
VSW
JOY
M24
M32
NETWORK VIDEO RECORDER, RACK MOUNTED
VIDEO SWITCHER, RACK MOUNTED
CAMERA POWER SUPPLY, WALL MOUNTED
DESK MOUNTED JOY STICK CONTROLLER AT PRINCIPALS OFFICE
24" VIDEO DISPLAY DESK MOUNTED AT PRINCIPALS OFFICE WITH WALL
MOUNT BRACKET/ARM
32" VIDEO WALL MOUNTED MONITOR FOR PUBLIC VIEW OF CAMERAS
WITH WALL MOUNT BRACKET/ARM
MFR.
MFR.
MFR.
N/A
N/A
N/A
N/A
N/A
+48 - +54"
RACK
RACK
+72" MAX
N/A
N/A
+96 MAX
+48 - +54"
N/A
N/A
N/A
N/A
N/A
40% FILL
3/4" MIN
40% FILL
3/4" MIN
40% FILL
3/4" MIN
40% FILL
3/4" MIN
40% FILL
3/4" MIN
40% FILL
PWR
SEC
DOOR POWER SUPPLY, WALL MOUNTED
PWR
DOOR
AIPHONE POWER SUPPLY, WALL MOUNTED
PWR
AIPH
PATCH PANEL FOR CAT 6 CABLES FROM CAMERAS
PP
TVM
TVM
XXCAMERA ID TAG CALLOUT
D
P1
VIDEO SYSTEM WIRE LEGEND INDEX
P2
T25
T100
V1
V2
MODEL
CONDUIT WIRE FILL CHART
SEE SPECS
SEE SPECS
SEE SPECS
SEE SPECS
SEE SPECS
SEE SPECS
SEE SPECS
SEE SPECS
SEE SPECS
SEE SPECS
SEE SPECS
SEE SPECS
SEE SPECS
SEE SPECS
SEE SPECS
SITE NO.
SCALE
DATE
CHECKED BY
S.F.U.S.D. PROJECT NO.
SHEETS
DRAFTER
OF
XXXX05/31/18 JSM -
12064
CONSTRUCTION
DESIGN &
FACILITIES
135 Van Ness Avenue
San Francisco, California 94102
Tel (415) 355-6979
Fax (415) 355-6988
Architect Engineer
School Name and Address
Project Name
Date No. Revisions
SHEET NO.
DRAWING TITLE
Approvals
AS NOTED
SFUSD SAN FRANCISCOPUBLIC SCHOOLS
Consultant Name and Address
05/15/2018 - BID ISSUE
G U T T M A N N B L A E V O E T
C O N S U L T I N G E N G I N E E R S
E
P F
THERESA MAHLER
EARLY EDUCATION SCHOOL
990 CHURCH STREET
SAN FRANCISCO, CA 94114
SFUSD PROJ. #12064
SECURITY
IMPROVEMENTS
Technical Reference
Conduit Capacity Chart
Conduit Size 1/2
I.D. Inches
Permissible Area*
Cable O.D
Inch
.100
.125
.150
.175
.200
.225
.250
.275
.300
.325
.350
.375
.400
.425
.450
.475
.500
.525
.550
.575
.600
.625
.650
.675
.700
.725
.750
.775
.800
.825
.850
.875
.900
.925
.950
.975
1.00
1.025
1.05
1.075
1.100
1.125
1.150
1.175
1.20
1.225
1.250
1.275
1.300
1.325
1.350
1.375
1.400
1.425
1.450
1.475
1.500
Cable Area
sq. Inch
.00785
.01227
.01767
.02405
.03142
.03976
.04909
.0594
.07069
.08296
.09621
.011045
.012566
.14186
.15904
.17721
.19635
.21648
.23758
.25967
.28274
.3068
.33183
.35785
.38484
.41282
.44179
.47173
.50265
.53456
.56745
.60132
.63617
.67201
.70882
.74662
.7854
0.825
0.866
0.908
0.950
0.994
1.039
1.084
1.131
1.179
1.227
1.277
1.327
1.379
1.431
1.485
1.539
1.595
1.651
1.709
1.767
15
10
7
5
4
3
2
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
27
17
12
9
6
5
4
3
3
2
1
1
1
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
44
28
19
14
11
8
7
6
5
4
3
3
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
WEST PENN WIRE
76
48
34
25
19
15
12
10
8
7
6
5
4
4
3
3
3
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
103
66
46
34
26
20
16
13
11
10
8
7
6
5
5
4
4
3
3
3
3
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
171
109
76
56
42
33
27
22
19
16
14
12
10
9
8
7
7
6
5
5
4
4
4
3
3
3
3
3
2
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
298
191
132
97
74
59
47
39
33
28
24
21
18
16
14
13
12
11
10
9
8
7
7
6
6
5
5
5
4
4
4
4
3
3
3
3
3
3
2
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
450
288
200
147
112
89
72
59
50
42
36
32
28
25
22
20
18
16
15
13
12
11
10
10
9
8
8
7
7
6
6
6
5
5
5
4
4
4
3
3
3
2
2
2
2
2
2
2
2
2
2
1
1
1
1
1
1
588
376
261
192
147
116
94
77
65
55
48
42
36
32
29
26
23
21
19
17
16
15
14
13
12
11
10
9
9
8
8
7
7
7
6
6
6
6
4
4
4
3
3
3
3
3
3
3
3
3
2
2
2
2
2
2
2
751
481
334
245
188
148
120
99
83
71
61
53
47
41
37
33
30
27
25
22
21
19
17
16
15
14
13
12
11
11
10
10
9
9
8
8
7
7
5
5
5
5
4
4
4
4
4
3
3
3
3
3
3
3
3
2
2
.622
0.12
3/4
.824
0.21
1
1.049
0.34
1 1/4
1.380
0.60
1 1/2
1.610
0.82
2
2.067
1.34
2 1/2
2.469
1.92
3
3.068
2.95
3 1/2
3.548
3.96
4
4.026
5.09
EXAMPLES:
Example A.
Sample Cable:
227- .260” O.D.
Example B.
Three different Cables:
227 - .260” sqd. = .0676
D434 - .411” sqd. = .1689
6350 - .275” sqd. = .0756
+
.3169
x .7854
.2489
CABLE WITH CONFIDENCE
On the Permissible Area-
equal to or greater. The
closest area is .034 Use a
1” Conduit
Go down the Cable O.D.
inch col-umn. Find the
number equal to or greater
than the cable O.D. Go
across to find the number
of cables in the appropriate
conduit size.
.269”- Closest .275”
13 in a 11/2” Conduit.
Important Note: This
conduit capacity chart is to
be used as a general
guideline. Because local
codes can vary from the
NEC. West Penn Wire
cannot be held responsible
for this information as it
pertains to your
installation. Proper
conduit fill is the sole
responsibility of the
installer and it is your
responsibility to see that
your installation will pass
local codes.
PTCH
1. THE PURPOSE OF THIS SHEET IS TO ILLUSTRATE AND DEFINE TYPICAL SYMBOLS, AND
SYSTEMS OF SYMBOLS, WHICH MAY OCCUR ON THE TELECOMMUNICATIONS
DRAWINGS. THE ILLUSTRATION OF A SYMBOL, OR SYSTEM OF SYMBOLS, ON THIS
SHEET DOES NOT NECESSARILY INDICATE THAT THE BUILDING ITEM OF THE
DESCRIBED SYSTEM BY THE SYMBOL IS USED AS PART OF THIS PROJECT. REFER TO
THE PLANS, ELEVATIONS, SECTIONS, SCHEDULES, DETAILS, AND SPECIFICATIONS TO
DETERMINE THE SCOPE OF THE WORK.
2. THE WORK - INCLUDING MATERIALS, METHODS, ASSEMBLIES, ETC - SHALL COMPLY
WITH THE MINIMUM REQUIREMENTS OF THE GOVERNING LAWS, ORDINANCES, AND
REGULATIONS OF ALL FEDERAL, STATE, AND LOCAL AUTHORITIES HAVING
JURISDICTION OVER THE PROJECT, AS WELL AS THOSE GREATER REQUIREMENTS
INDICATED BY THE CONTRACT DOCUMENTS. NO PART OF THE CONTRACT
DOCUMENTS MAY BE CONSTRUED TO REQUIRE OR PERMIT WORK CONTRARY TO A
GOVERNING LAW, ORDINANCE, OR REGULATION.
3. THE TELECOMMUNICATIONS DRAWINGS ARE PART OF THE OVERALL PROJECT
DRAWINGS WHICH, WHEN COMPLETE, CONSISTS OF DRAWINGS LISTED BY THE
"INDEX OF DRAWINGS". THE WORK DESCRIBED BY THE DRAWINGS OF ANY ONE
DISCIPLINE MAY BE AFFECTED BY THE WORK AND REQUIREMENTS DESCRIBED ON
DRAWINGS OF ANOTHER DISCIPLINE AND MAY REQUIRE REFERENCE TO THE
DRAWINGS OF ANOTHER DISCIPLINE. PARTIAL SETS OF DRAWINGS ARE INCOMPLETE
AND SHOULD NOT BE DISTRIBUTED OR UTILIZED BY THE CONTRACTOR. MANAGE,
SUPERVISE, REVIEW, AND COORDINATE THE WORK OF SUB-CONTRACTORS, TRADES,
AND SUPPLIERS WITH THE REQUIREMENTS OF THE CONTRACT DOCUMENTS BEFORE
COMMENCING CONSTRUCTION AND TO ASSURE THAT PARTIES ARE AWARE OF
REQUIREMENTS, REGARDLESS OF WHERE THE REQUIREMENTS OCCUR IN THE
CONTRACT DOCUMENTS, WHICH MAY AFFECT THE WORK OF THAT PARTY.
4. THE ARCHITECTURAL DRAWINGS ESTABLISH AND COORDINATE THE FINISHED
APPEARANCE AND EXACT LOCATION OF EXPOSED ELEMENTS OF THE WORK OF
TRADES, INCLUDING THAT WORK THAT IS ILLUSTRATED PRIMARILY ON THESE
DRAWINGS. LOCATIONS SHOWN ON THESE DRAWINGS ARE DIAGRAMMATIC. REFER
TO ARCHITECTURAL DRAWINGS FOR DIMENSIONED LOCATIONS.
5. MAINTAIN A COPY OF THE SPECIFICATIONS AND DRAWINGS AT THE JOB SITE.
PRESENT THE SPECIFICATIONS AND DRAWINGS UPON REQUEST. MAINTAIN DAILY
MARKUPS OF ACTUAL INSTALLATION AND PRESENT FOR REVIEW UPON REQUEST.
6. REFER TO WRITTEN SPECIFICATIONS FOR PROJECT SCOPE, GENERAL
REQUIREMENTS, PRODUCT SPECIFICATIONS, AND INSTALLATION REQUIREMENTS.
WHERE QUANTITY AND QUALITY DIFFER, THE HIGHER OF EACH SHALL PREVAIL.
7. PROVIDE NECESSARY EQUIPMENT AND ACCESSORIES FOR A FULLY FUNCTIONAL
SYSTEM THAT MEETS INTENDED DESIGN WHETHER EXPRESSLY SPECIFIED OR NOT
AND ALL INCIDENTALS PERTAINING TO THE INSTALLATION TO FORM A COMPLETE AND
WORKING SYSTEM.
8. PROVIDE MATERIALS AND EQUIPMENT LISTED BY UNDERWRITERS LABORATORIES
FOR THE PURPOSE USED AND BEARING THEIR LABEL.
9. PRIOR TO PERFORMING WORK, IMMEDIATELY NOTIFY THE OWNER, OR OWNER'S
REPRESENTATIVE, IN WRITING OF OBSERVATIONS OR CONDITIONS DISCOVERED
THAT WOULD PREVENT INSTALLATION ACCORDING TO DRAWINGS AND
SPECIFICATIONS.
10. BRING A SET OF MARKED UP PLANS TO WEEKLY CONSTRUCTION MEETINGS FOR
OWNER'S, OR OWNER'S REPRESENTATIVE'S, APPROVAL PRIOR TO PRODUCTION OF
AS-BUILT DRAWINGS FOR RECORD DOCUMENTATION.
11. REMOVE ABANDONED CABLING LEFT OVER CONDUIT, WIRE, SCRAPS, ETC. LEAVE
PREMISES CLEAN AND FREE OF TRASH OR DEBRIS RESULTING FROM WORK. AND
PROPERLY RECYCLE APPLICABLE MATERIAL ACCORDING TO ALL CODE
REQUIREMENTS FOR SUCH MATERIAL.
12. INSTALL EQUIPMENT, DEVICES, AND PATHWAYS, SUCH AS CABLE TRAY, RUNWAY,
CONDUITS, CABLE HANGERS, AND PULLBOXES, ETC., ACCORDING TO STATE
AND LOCAL CODES AND REGULATORY REQUIREMENTS FOR SEISMIC BRACING.
13. CONDUIT ROUTING, WHERE SHOWN ON DRAWINGS, IS DIAGRAMMATIC IN NATURE.
FIELD DETERMINE CONDUIT ROUTES TO SUIT FIELD CONDITIONS WHILE CONFORMING
TO SPECIFICATIONS. PREPARE SHOP DRAWINGS SHOWING EXACT CONDUIT ROUTES,
INDICATING PENETRATION TYPES (e.g., FRAMED WALL, CONCRETE WALL, ETC.).
COORDINATE REQUIREMENTS WITH OTHER TRADES.
14. INSTALL CONDUIT PATHWAYS PER TIA/EIA-568-B AND BICSI TDMM AND BEST
INDUSTRY STANDARDS AND PRACTICES.
15. ROUTE CONDUIT, CABLE TRAYS, J-HOOKS AND OTHER PATHWAYS PERPENDICULAR
OR PARALLEL TO BUILDING LINES, IN GENERAL. CABLING INSTALLED AT ANGLES AND
SKEWED ABOVE CEILINGS WILL NOT BE ALLOWED.
16. CONDUITS WITH LESS THEN 2" INSIDE DIAMETER WILL HAVE A BEND RADIUS OF NO
LESS THAN 6 TIMES THE INSIDE DIAMETER. CONDUITS WITH A 2" OR GREATER INSIDE
DIAMETER WILL HAVE A BEND RADIUS OF NO LESS THAN 10 TIMES THE INSIDE
DIAMETER.
17. CONDUIT RUNS SHALL NOT EXCEED 180 DEGREES OR TWO 90-DEGREE BENDS
WITHOUT AN APPROPRIATE NEMA RATED PULL BOX OR/AND INCREASE CONDUIT BY
ONE TRADE SIZE FOR EACH ADDITIONAL BEND OF UP TO 90 DEGREES, UNLESS LAST
BEND IS WITHIN 12 INCHES OF THE CONDUIT END.
18. WHEN ROUTING CONDUIT IN CONCRETE, MAINTAIN A GRADUATED BEND RADIUS TO
MAINTAIN CONDUIT CAPACITY. THE USE OF 90-DEGREE 'ELBOW' FITTINGS IS
EXPRESSLY PROHIBITED UNLESS PRIOR AUTHORIZATION IS RECEIVED FROM OWNER,
OR OWNER'S REPRESENTATIVE, IN WRITING.
19. PROPERLY FIRE SEAL CONDUIT AND RACEWAY PENETRATIONS THROUGH FIRE
RATED WALLS AND FLOORS TO MAINTAIN THE FIRE SEPARATION RATING. PROVIDE
FIRE SEALING ASSEMBLIES THAT ARE UL LISTED FOR THE APPLICATION.
COORDINATE REQUIREMENTS WITH LOCAL FIRE MARSHALL PRIOR TO INSTALLATION.
DO NOT MIX PRODUCTS BETWEEN MANUFACTURED ASSEMBLIES.
20. PROVIDE EXPANSION/DEFLECTION FITTINGS FOR CONDUITS AT STRUCTURAL
EXPANSION JOINT CROSSINGS.
21. PROVIDE PLASTIC BUSHINGS ON EXPOSED ENDS OF CONDUIT AND SLEEVES,
WHETHER VISIBLE OR NOT.
22. PROVIDE EMT 4" TRADE SIZE CONDUITS FOR BACKBONE PATHWAYS WITH 40"
MINIMUM BEND RADIUS FITTINGS, UON.
23. PROVIDE MINIMUM OF 1 INCH SIZE CONDUIT FOR HORIZONTAL DISTRIBUTION AND
TELECOMMUNICATIONS DEVICES. CONSOLIDATION OF CONDUITS IS ALLOWED WHEN
EQUAL OR GREATER CONSOLIDATED AREA IS PROVIDED.
24. PROVIDE DEDICATED CONDUIT STUB PER TELECOMMUNICATIONS DEVICE BOX.
DAISY-CHAINING DEVICE BOXES IS PROHIBITED UNLESS SPECIFICALLY NOTED ON
FLOOR PLANS.
25. CONDULET ("LB", ETC.) FITTINGS ARE EXPRESSLY PROHIBITED FOR
TELECOMMUNICATIONS SYSTEM PATHWAYS.
26. PROVIDE A PULL STRING OR PULL ROPE IN EMPTY/UNUSED DISTRIBUTION CONDUITS
AND CONDUITS SERVING TELECOMMUNICATIONS DEVICES SUITABLE FOR A 200 LB
PULL TENSION MINIMUM.
27. PROVIDE DEDICATED SUPPORTS (e.g., CLIPS & WIRES) FOR CABLE SUPPORT
HANGERS (OR SIMILAR PATHWAY COMPONENTS) INTENDED FOR
TELECOMMUNICATIONS CABLES.
28. ALL NEW TELECOM DEVICES FOR NEW CONSTRUCTION SHALL BE FLUSH MOUNTED
AND RECESSED IN WALLS, ALL CONDUITS, CABLING, ETC. SHALL BE CONCEALED IN
WALLS AND ABOVE SUSPENDED AND HARD LID CEILINGS.
29. PROVIDE SLEEVES AS REQUIRED WHERE CABLES PASS THROUGH RATED WALLS
30. SURFACE WIREWAY OR DEVICES SHALL BE ALLOWED AS SHOWN ON DRAWINGS,
U.O.N..
38. LABEL TELECOMMUNICATIONS CABLES ACCORDING TO SPECIFICATIONS.
PROVIDE LABELS AT BOTH ENDS, FACEPLATES, PATCH PANELS, ETC.
LABELING SCHEMA SHALL BE COORDINATED SO THAT ALL LABELING,
WHETHER ON FACEPLATE OR CABLE MATCHES CABLE DESCRIPTORS
END TO END. PROVIDE SAMPLE LABELS TO THE OWNER, OR OWNER'S
REPRESENTATIVE AND OBTAIN WRITTEN APPROVAL PRIOR TO LABELING
(VERIFY FORMAT AND REQUIRED FIELDS OF INFORMATION).
39. COMPONENTS NOT RELATED TO THE SUPPORT OF THE
TELECOMMUNICATIONS ROOM(S) FUNCTION (E.G.,PIPING, DUCTWORK,
PNEUMATIC TUBING, ETC.) SHALL NOT BE INSTALLED IN, PASS THROUGH,
OR ENTER THE TELECOMMUNICATIONS ROOM.
40. IT IS FORBIDDEN TO ROUTE ANY LIQUID CARRYING SYSTEMS, INCLUDING
VALVES OR RUBBER TUBING COMPONENTS CONTAINING LIQUID
THROUGH TELECOM ROOMS AND SPACES
41. OUTLET AND DEVICE LOCATIONS SHOWN ARE APPROXIMATE AND SHALL
BE COORDINATED IN THE FIELD WITH SFUSD. WIREWAY, CONDUITS,
OUTLETS, ETC. WILL REQUIRE ADJUSTMENT IN PATHWAYS, FOR BUILDING
FEATURES, ARCHITECTURAL FEATURES AND AVOIDING CONFLICT WITH
FURNITURE, SHELVING, DESKS, ETC. WIREWAYS,CONDUITS , ETC. SHALL
BE ROUTED IN A MANNER TO COORDINATE WITH ALL EXISTING
CONDITIONS ON SITE.
31. DO NOT SHARE SUPPORTS WITH OTHER TRADES/SYSTEMS, INCLUDING SECURITY
AND/OR AUDIOVISUAL SYSTEMS. PROVIDE WIRES, HANGERS, ETC. SEPARATE FROM
THE CEILING SUPPORT SYSTEM AND OTHER INSTALLED SYSTEMS, A DEDICATED
SUPPORT SYSTEM IS REQUIRED FOR TELECOMMUNICATIONS CABLING.
32. PROVIDE TELECOMMUNICATION CONDUITS FOR CABLING ROUTED THROUGH
NON-ACCESSIBLE CEILING SPACE (e.g., 'HARD LID' CEILING), UON. SIZE CONDUITS
TO MAINTAIN A FILL CAPACITY NO LESS THAN 40% PLUS 50% SPARE CAPACITY.
33. INSTALL TELECOMMUNICATIONS DEVICES AT HEIGHTS NOTED ON SYMBOLS LIST
OR DEVICE SCHEDULE, UNLESS OTHERWISE SHOWN ON THE DRAWINGS OR
STATED IN SPECIFICATIONS. MOUNTING HEIGHTS ARE FROM FINISHED FLOOR TO
THE CENTERLINE OF THE DEVICE. REFER TO ARCHITECTURAL ELEVATION
DRAWINGS FOR ADDITIONAL INFORMATION OR EXACT LOCATIONS OF
WALL/CEILING/FLOOR MOUNTED DEVICES. VERIFY HEIGHTS ARE THE SAME AS
ACCOMPANYING POWER RECEPTACLES AND NOTIFY OWNER, OR OWNER'S
REPRESENTATIVE OF ANY DISCREPANCY.
34. PROVIDE A 24" MINIMUM SEPARATION BETWEEN 'BACK-TO-BACK'
TELECOMMUNICATION POWER OR SIGNAL DEVICES IN FRAMED WALLS.
35. DO NOT TIE CABLES TO OTHER STRUCTURES NOT INTENDED FOR THIS SPECIFIC
USE. DO NOT TIE CABLES TO CABLE TRAY.
36. ROUTE TELECOMMUNICATIONS CABLES PERPENDICULAR OR PARALLEL TO
BUILDING LINES, IN GENERAL. ROUTE TELECOMMUNICATIONS CABLES NO LESS
THAN 6 INCHES FROM ANY POWER SOURCE OR FLORESCENT LIGHTING FIXTURE,
AND NO LESS THAN 4 FEET FROM ANY TRANSFORMER OR MOTOR.
37.. GROUP AND DRESS EXPOSED TELECOMMUNICATIONS CABLE GROUPS USING
VELCRO TIES, UON. GROUP NO MORE THAN 20 CABLES IN A NGLE BUNDLE AS
ESTABLISHED FOR PoE EQUIPMENT.
TY-03
GENERAL NOTES AND
PROJECT NOTES
1. DEVICES NOT ASSOCIATED WITH OR SHOWN ADJACENT TO
CABLE TRAY SHALL BE ROUTED IN CONDUIT TO CABLE TRAY
TO CABLE TRAY SYSTEM. CONDUIT RUNS FOR SAME SYSTEMS
MAY BE COMBINED BY SIZING TO THE NEXT TRADE SIZE
AND/OR ENSURING A MAXIMUM OF 40% FILL RATIO. A
MAXIMUM OF 2 RUNS FROM VOICE AND DATA SHALL BE
PERMITTED PER CONDUIT RUN.
2. CABLE TRAY SHALL BE FILLED TO A MAXIMUM OF 50% PER
THE CABLE TRAY FILL CHART.
3. DO NOT COMBINE CABLES FROM OTHER SYSTEMS INTO
COMMON CONDUIT RUNS. EACH SYSTEM SHALL HAVE A
SEPARATE CONDUIT RUN TO THE CABLE TRAY.
4. ALL CABLE TRAY IS TO BE INSTALLED TO MAKE EFFICIENT
USE OF THE SPACE ABOVE SUSPENDED CEILING SYSTEMS.
COORDINATE ALL TRAY LOCATIONS WITH ELECTRICAL AND
MECHANICAL SYSTEMS TRAVERSING HALLWAYS AND CORRIDORS,
ADJUST ROUTES AS NECESSARY. CABLE TRAY SHALL HAVE A
MINIMUM OF 9" WORKING CLEARANCE ABOVE TRAY.
5. REFER TO RISER DIAGRAMS FOR SYSTEMS INTERCONNECTION
AND CABLING REQUIREMENTS
6. COORDINATE VOICE AND DATA OUTLET LOCATIONS WITH
ELECTRICAL OUTLETS AND INSTALL A STUD BAY APART ALONG
COMMON USE WALLS.
7. COORDINATE ALL MOUNTING HEIGHTS OF DEVICES, OUTLETS,
ETC.., IN CASEWORK AND FURNITURE, SEE ARCHITECTURAL
ELEVATIONS FOR MOUNTING HEIGHTS OF OUTLETS AND
DEVICES.
8. CABLE TRAY THROUGH EXTENDED HARD LID AREAS SHALL BE
TRANSITIONED WITH SLEEVES AND FIRE STOPPING OR BY
PLACING MULTIPLE 4" CONDUITS BETWEEN ACCESSIBLE
CEILING SPACES, WHILE MAINTAINING CABLE TRAY CAPACITIES.
9. IT IS THE INTENT THAT ALL VOICE, DATA BE
INSTALLED IN THE COMMON CABLE TRAY SYSTEM ONLY.
OTHER SYSTEMS SUCH AS PAGING, SECURITY, ETC. SHALL BE
INSTALLED IN A J-HOOK SYSTEM, PARALLEL TO THE CABLE
TRAY. LIKE SYSTEMS CABLES SHALL BE INSTALLED ON
SEPARATED HOOKS IN THE J-HOOK PATHWAY AND BUNDLED
WITH VELCRO TYPE STRAPS, AND BY PLACING CABLES IN
ADJACENT J-HOOKS IN THE CABLE ROUTE. DRESS CABLING IN
COMMON GROUPS AND TYPES.
10. NEW CONDUITS, ETC..... ARE TO BE INSTALLED AROUND
BUILDING STRUCTURES, FEATURES, BEAMS, SUPPORTS ETC.....,
CONDUITS FEEDING DEVICES SHALL BE ROUTED DOWN TO THE
INSTALLATION HT. OF THE DEVICES AND STUBBED INTO
THE COMMON AREA TO CONNECT TO CABLE TRAYS.
PREPLANNING PATHWAYS AND ROUTES IS REQUIRED TO BE
FIELD COORDINATED PRIOR TO INSTALLATION. INCLUDE ALL
COSTS FOR ROUTES HORIZONTAL AND VERTICAL TO FACILITATE
DESIGN AND INTENT. PROVIDE NECESSARY BACKING OR
FURRING OF WIREWAY, CABLE TRAY, CONDUIT ETC.. TO
ROUTE AROUND MECHANICAL AND/OR ELECTRICAL SYSTEMS.
11. ALL CONDUIT CABLE RUNS TO CABLE TRAY SHALL BE
SLEEVED THRU WALLS WITH CONDUIT AND BUSHED WITH SNAP
ON BUSHINGS EACH END PRIOR TO CABLE INSTALLATION.
ROUTES WHICH PASS THRU RATED WALLS SHALL USE THE
APPROPRIATE SIZED FLAMESTOPPER OR U.L. ASSEMBLY,
SIMILAR TO IDF, SIZED FOR CABLE FILL. THIS APPLIES TO
ALL CABLES IN CEILING SPACE WITH PASS THRU GYP BOARD
WALLS IN ROUTE TO CABLE TRAY.
12. CONDUIT AND RATED SLEEVES FEEDING CABLE TRAYS SHALL
BE USED 100% OF CAPACITY PRIOR TO CABLING BEING
ADDED OR EXTENDED TO THE NEXT OPEN SLEEVE.
13. ALL CONDUITS SHALL HAVE PLASTIC SNAP ON BUSHINGS NOT
PRESS ON STYLE, INSTALLED PRIOR TO ANY CABLE
INSTALLATION.
14. REFER TO ARCHITECTURAL DRAWINGS (REFLECTED CEILING
PLANS, AND INTERIOR ELEVATIONS, ETC....) FOR
COORDINATION, WHICH INCLUDES LIGHTING FIXTURES,
SWITCHES, OUTLETS, SECURITY SYSTEMS, SMOKE DETECTORS,
MECHANICAL SYSTEMS ETC.... FOR DEVICE AND SYSTEM
COMPONENT LOCATIONS.
15. MAINTAIN FIRE RATING OF ALL FLOORS, CEILING AND
WALLS PENETRATED BY ELECTRIC WORK.
16. ALL DEVICES INDICATED MOUNTED BACK TO BACK
SHALL BE SEPARATED BY A WALL STUD. BOXES ARE
NOT TO BE MOUNTED IN SAME WALL CAVITY. PROVIDE
3M BRAND FIRE BARRIER MOLDABLE PUTTY MPP-1 AND
APPLY TO BOX MOUNTED IN FIRE RATED WALL PER
CONTRACT DOCUMENTS. IN FIRE RATED WALLS AND
PARTITIONS, OFFSET OUTLET BOXES A MINIMUM OF 24
INCHES HORIZONTALLY.
17. ALL ELECTRICAL EQUIPMENT SHALL BE BRACED OR ANCHORED
TO RESIST A HORIZONTAL FORCE ACTING IN
ANY DIRECTION PER THE FOLLOWING CRITERIA:
A. FIXED EQUIPMENT ON GRADE. 33% OF OPERATING
WEIGHT
B. FIXED EQUIPMENT ON STRUCTURE. 50% OF
OPERATING WEIGHT
C. COMMUNICATION SYSTEMS/CONDUIT/CABLE TRAY,
ETC.... ON GRADE: 50% OF OPERATING WEIGHT
D. COMMUNICATION SYSTEMS/CONDUIT/CABLE TRAY ON
STRUCTURE. 75% OF OPERATING WEIGHT
ALL CABLE TRAY AND SYSTEMS SHALL BE INSTALLED TO MEET
SEISMIC ZONE 4 REQUIREMENTS. PROVIDE ALL LATERAL
BRACING AND BUILDING ATTACHMENTS TO PRECLUDE
MOVEMENT OF CONDUITS, CABLE TRAYS, ETC.... WITHIN THE
HORIZONTAL AND VERTICAL PLANES.
18. SUPPORT AND SEISMIC BRACING OF ALL CONDUITS AND
CABLE TRAY SHALL BE IN ACCORDANCE WITH THE SMACNA
GUIDELINES FOR SEISMIC RESTRAINTS OF ELECTRICAL SYSTEMS
AND PRE-APPROVED ANCHORAGE DETAILS WHICH ARE PRE
APPROVAL, B-LINE BY OSHPD APPROVAL No. R0114
19. PROVIDE ANCHORS IN HARDENED CONCRETE (NORMAL OR
LIGHTWEIGHT). PROVIDE CAST-IN-PLACE ANCHORS IF
EXPANSION ANCHORS ARE USED.
20. DETAILS SHOWN ON THESE DRAWINGS ONLY SHOWS THE
INTENT OF THE DESIGN. ACTUAL EQUIPMENT ANCHORAGE
SHALL BE COORDINATED WITHIN THE STRUCTURAL BLDG..
REQUIREMENTS.
21. ALL DATA AND VOICE CABLES SHALL NOT BE PLACED WITHIN
THE BUILDING EXCEEDING 295', WHICH IS THE ESTABLISHED
MAXIMUM LENGTH LIMIT. CONTRACTOR TO COORDINATE
SHORTEST ROUTE AND PATHWAYS FROM INDIVIDUAL OUTLETS
TO EACH FLOORS TELECOM/IDF ROOM.
22. CABLE TRAY SHALL BE INSTALLED WITHOUT BARRIERS FOR
VOICE AND DATA CABLING IN THE HORIZONTAL TRAY
WITHIN CORRIDORS TO ALLOW FULL USE OF TRAY.
23. THE SECURITY SYSTEM SHALL NOT PREVENT EGRESS
THROUGH ANY CONTROLLED DOOR IN THE EVENT OF ANY
FIRE ALARM WITHIN THE BLDG.. OCCUPANTS SHALL HAVE FREE
EGRESS THROUGH ALL DOORS WHICH ARE PROVIDED WITH
DOOR PANIC HARDWARE. ALL EXIT DOORS ARE AND SHALL
BE OPERABLE WITHOUT SPECIAL KEYS OR HARDWARE, SPECIAL
KNOWLEDGE OR EFFORT.
24. WEATHERPROOF OR MOISTURE RESISTANT TYPE OUTLETS,
SWITCHES, ETC.. SHALL BE PROVIDED WITH A HINGED CAP OR
SCREW ON TYPE CAB ASSEMBLY OVER EACH ENTRANCE TO
THE CONNECTOR, RECEPTACLE OR DEVICES TO PRECLUDE
WATER DAMAGE.
25. COORDINATE ALL DOOR HARDWARE INTERFACE CONTROLS,
CONNECTIONS TO OTHER SYSTEMS, POWER SUPPLIES, ETC..
WITH OTHER TRADES. PROVIDE FULL LAYOUT AND
INTERCONNECT DETAILS WITHIN THE SHOP DRAWING PHASE
FOR ALL CARD ACCESS DOOR CONTROL ASSEMBLIES
26. COORDINATE ALL CABLE TRAY RUNS, CONDUITS, DEVICES,
OUTLETS, ETC.. INSTALLED ABOVE HARD LID OR T-GRID TYPE
CEILINGS WITH REFLECTED CEILINGS PLANS, ELECTRICAL
PLANS, MECHANICAL PLANS AND ARCHITECTURAL PLANS AND
DETAILS FOR FORM, FIT AND FUNCTION.
27. CONTRACTOR TO PROVIDE COORDINATED SHOP DRAWINGS FOR
TELECOM, VOICE, DATA AND SECURITY SYSTEM CABLING,
INFRASTRUCTURE, DEVICES, MOUNTING, ETC.. SEE
SPECIFICATIONS.
28. ALL WORK SHALL BE IN ACCORDANCE WIT H THE LATEST
EDITION OF THE CALIFORNIA ELECTRICAL CODE UNDER ARTICLES
720, 725 AND 800 AND THE NATIONAL ELECTRICAL CODE. THE
CONTRACTOR SHALL NOT INTERMIX ANY HIGH VOLTAGE POWER
WIRES (120VAC) WITH ANY LOW VOLTAGE SIGNAL OR CONTROL
WIRES IN ANY CONDUIT.
29. VERIFY ALL FIELD DIMENSIONS AND CONDITIONS, NOTIFY
ARCHITECT OF ANY DISCREPANCIES FOUND. VERIFY DIMENSIONS
OF ALL OWNER FURNISHED OPERATING EQUIPMENT TO ENSURE
PROPER COORDINATION WITH CONSTRUCTION
30. SCHEDULE ALL WORK INCLUDING CONSTRUCTION ACCESS AND
STORAGE WITH THE OWNER OR THOSE DESIGNATED BY THE
OWNER. THE CONSTRUCTION SCHEDULE SHALL BE APPROVED BY
THE OWNER PRIOR TO THE START OF CONSTRUCTION.
31. ALL UTILITIES REQUIRED FOR THE CONTINUOUS OPERATION OF
ALL EXISTING FACILITIES MUST BE MAINTAINED IN SERVICE AT
ALL TIMES (AS APPLICABLE).
32. CONTRACTOR SHALL PROVIDE DUST AND DEBRIS PROTECTION AS
NECESSARY TO CONTAIN DUST AND DEBRIS WITHIN THE
CONSTRUCTION AREA, BROOM CLEAN ALL AREAS DAILY.
33. COORDINATE WITH THE OWNER TO DETERMINE IF REMOVED DEMO
ITEMS (AS APPLICABLE) WILL BE RETAINED BY THE OWNER.
COORDINATE STORAGE AND INVENTORY OF DEMO DEVICES AND
DELIVER TO OWNER. DISPOSAL OF OLD EQUIPMENT, DEMO ITEMS
NOT RETAINED SHALL BE DONE IN ACCORDANCE WITH ALL
FEDERAL, STATE AND LOCAL CODES.
34. ALL WORK SHALL BE EXECUTED IN A CAREFUL AND ORDERLY
MANNER, WITH THE LEAST POSSIBLE DISTURBANCE TO THE
PUBLIC AND OCCUPANTS OF EXISTING BUILDINGS. NO
INTERRUPTION TO WORKING PERSONNEL WILL BE PERMITTED,
WORK IN AREAS SHALL BE DONE AFTER NORMAL WORKING
HOURS.
35. CONTRACTOR SHALL PROVIDE ALL BARRIERS, SIGNS, AREA
PROTECTION, SAFETY BARRIERS, ETC. TO KEEP PERSONNEL OUT
OF WORK AREA.
36. NO POWER SHALL BE SHUT DOWN DURING NORMAL WORKING
HOURS WITHOUT PRIOR CONSENT OF OWNER.
37. CONTRACTOR SHALL ASSUME SOLE RESPONSIBILITY FOR SAFETY
OF ALL PERSONS ON OR ABOUT THE CONSTRUCTION SITE IN
ACCORDANCE WITH APPLICABLE LAWS AND CODES. GUARD ALL
HAZARDS IN ACCORDANCE WITH SAFETY PROVISIONS OF THE
LATEST MANUAL OF ACCIDENT PREVENTION, PUBLISHED BY THE
ASSOCIATED GENERAL CONTRACTORS OF AMERICA.
38. COORDINATION WITH OTHER CONTRACTORS:
IF ANY PART OF THE CONTRACTORS WORK DEPENDS
UPON THE WORK OF ANOTHER CONTRACTOR OR TRADE,
THIS CONTRACTOR SHALL INSPECT SUCH WORK AND
PROMPTLY REPORT IN WRITING TO THE PROJECT
ARCHITECT ANY DEFECTS IN SUCH WORK THAT RENDER IT
UNSUITABLE TO RECEIVE THE WORK THIS THIS
CONTRACTOR. FAILURE TO INSPECT AND REPORT SHALL
CONSTITUTE AN ACCEPTANCE OF THE OTHER
CONTRACTORS OR TRADES WORK, EXCEPT AS TO DEFECTS
WHICH DEVELOP IN OTHER CONTRACTORS WORK AFTER
EXECUTION OF THIS CONTRACTORS WORK.
39. THE CONTRACTOR SHALL ALWAYS MAINTAIN AT THE JOB SITE AN
UPDATED "RECORD" SET OF DRAWINGS AND AS-BUILTS OR AS
INSTALLED DRAWINGS. THE DRAWINGS SHALL BE AVAILABLE TO
THE ARCHITECTS, ENGINEERS AND OR INSPECTORS UPON
REQUEST.
40. CABLE RUNS SHALL NOT BE SPLICED UNLESS TWO OR MORE
DEVICES ARE CONNECTED TO THE SAME CIRCUIT OR THE DEVICE
IS PROVIDED WITH FACTORY PIGTAIL WIRES. WHERE SPLICING IS
REQUIRED, THE SPLICE SHALL BE SOLDERED AND TAPED.
SPLICING SHALL BE DONE IN A TERMINAL BOX OR CABINET, OR
AT THE BACK BOX OF THE DEVICE OR TERMINAL LUGS. ALL
SPLICE BOXES MUST BE ACCESSIBLE AND CLEARLY MARKED ON
THE RECORD DRAWINGS (NOT APPLICABLE TO TELECOM OR
FIBER)
41. ALL WIRES AND CABLES SHALL BE COLOR CODED AND SHALL
BE CONNECTED IN A UNIFORM MANNER. TRANSPOSING OR
CHANGING OF COLOR CODES SHALL NOT BE PERMITTED. WIRE
AND CABLE SIZES, NUMBER OF CONDUCTORS, SHIELDING OR
OTHER ITEMS LISTED ON THESE DRAWINGS SHALL NOT BE
ALTERED OR CHANGED IN TYPE GAUGE OR ELECTRICAL CAPACITY.
42. ALL WIRING AND CABLING, INCLUDING SHIELDS MUST BE FREE
OF SHORTS, GROUNDS AND STRAY OR INDUCED VOLTAGES. ALL
UNDERGROUND OR BELOW GRADE CABLES AND WIRES MUST BE
RATED FOR WET LOCATIONS. ALL EXPOSED CABLE BELOW 12'
AFF SHALL BE IN CONDUIT U.O.N.
43. THE MAIN SECURITY CABLING CABLE TRAY, J-HOOK ROUTES
SHALL RUN PARALLEL AND PERPENDICULAR TO THE BUILDING
AND ADJACENT TO VOICE AND DATA CABLING SYSTEMS. EACH
CONTRACTOR AND SYSTEM SUPPLIER SHALL BE RESPONSIBLE
FOR PROVIDING ALL J-HOOK PATHWAYS AND ROUTES FOR
RESPECTIVE SYSTEMS BEYOND CABLE TRAYS, THIS INCLUDES ALL
CONDUITS, BOXES, FITTINGS ETC.
44. ALL CABLING WITHIN SYSTEMS SHALL BE INSTALLED WITH WRAP
AROUND IMPRINTED TYPE LABELING SYSTEM AS FOLLOWS:
A. CABLES WITHIN 6" UPON ENTRY TO ANY PANEL,
TERMINATION OR SPLICE BOX
B. ALL WIRE LEADS WITHIN 2" FROM ANY TERMINAL BLOCK
CONTRACTOR SHALL SUBMIT SAMPLES FOR APPROVAL OF
MARKING SYSTEM LABELS
ALL ELECTRICAL POWER SUPPLIED TO EQUIPMENT OR DEVICES
SHALL BE ON AN EMERGENCY SYSTEM (WHERE AVAILABLE). ALL
CONDUCTORS AND CIRCUIT BREAKERS SHALL BE SIZED IN
ACCORDANCE WITH THEIR CONNECTED LOADS (20 AMP
MINIMUM) ALL CIRCUITS SHALL BE DEDICATED. A GROUND
CONDUCTOR SHALL ALWAYS BE INSTALLED IN POWER WIRING
CONDUITS, ALL EQUIPMENT AND PANELS SHALL BE GROUNDED.
45. WHERE A CIRCUIT FOR SECURITY EQUIPMENT IS ORIGINATING
FROM A LOAD CENTER UTILIZED FOR OTHER ELECTRICAL
PURPOSES, THE BRANCH CIRCUIT BREAKER FOR SECURITY
EQUIPMENT SHALL BE THE LOCKABLE TYPE TO PREVENT ANY
ACCIDENTAL DISRUPTION AND POWER DISCONNECTION. ALL
SECURITY BRANCH CIRCUITS SHALL BE DEDICATED.
46. THE CONTRACTOR SHALL SEAL ALL CONDUIT OR SLEEVE
PENETRATIONS THROUGH ALL WALLS, FLOORS AND CEILING
USING U.L. APPROVED AND LISTED METHODS AND COMPOUNDS,
REGARDLESS OF RATINGS IN ACCORDANCE WITH APPLICABLE
BUILDING CODES. THIS PERTAINS TO ALL WALLS, FLOORS,
CEILINGS, ETC. WHETHER RATED OR NOT.
47. ALL ROUTING OF WIRING AND RELATED CONDUITS IF SHOWN ARE
DIAGRAMMATIC IN NATURE. CONTRACTOR SHALL FIELD VERIFY
EXACT ROUTING, FORM, FIT AND FUNCTION PRIOR TO
INSTALLATION.
48. CONTRACTOR SHALL PROVIDE PULL STRINGS, ROPES OR LINES
AS APPLICABLE FOR CONDUIT SIZE, SYSTEM AND FUNCTION.
49. ALL CONDUITS SHALL RUN PARALLEL OR PERPENDICULAR TO
WALLS, CEILINGS, FLOORS, ETC.. IF MORE THAN TWO 90 DEGREE
BENDS ARE TO BE INSTALLED IN A CONDUIT RUN, OR THE
CONDUIT IS LONGER THAN 100 FEET THE
CONTRACTOR SHALL PROVIDE THE NECESSARY PULL BOXES,
APPROPRIATELY SIZED AND FOR FUNCTION (NEMA1, 3R, ETC.).
CONDUITS SHALL BE SIZED AS SHOWN OR LARGER AS REQUIRED
TO COMPLY WITH CODE, MINIMUM CONDUIT SIZE 1" U.O.N.
50. CONTRACTOR SHALL CLEAN AND THOROUGHLY CHECK ALL
INSTALLED WORK PRIOR TO CONCEALING OF WORK. CLEAN ALL
EXPOSED SURFACES AND NEW EQUIPMENT UPON INSTALLATION
AND PRIOR TO PLACING INTO SERVICE. THE CONTRACTOR SHALL
REPAIR, CLEAN, ETC. ALL SOILED SURFACES, PAINTED SURFACES
OR DAMAGED ARCHITECTURAL BUILDING FINISHES TO MATCH THE
ADJACENT ERAS, WHERE REQUIRED PRIOR TO COMPLETION.
CLEANING, PATCHING, PAINTING TO RESTORE SURFACES TO
ORIGINAL FINISHES SHALL BE THE RESPONSIBILITY OF THIS
CONTRACTOR FOR SYSTEMS AND/OR DEVICES INSTALLED BY THIS
WORK SCOPE.
51. ALL EQUIPMENT AND DEVICES SHALL BE INSTALLED WITH
CONSIDERATION TO BARRIER FREE ACCESSIBILITY, AS DEFINED IN
CALIFORNIA TITLE 24.
52. WHERE CONCRETE FLOORS ARE TO BE CORED, AN X-RAY
SHALL BE TAKEN TO ENSURE THAT NO STRUCTURAL ELEMENTS
WILL BE DAMAGED DURING CORING.
53. SHOULD THE CONTRACTOR BE REQUIRED TO CHANGE ANY
DEVICE OR INSTALLATION TO SUIT THE ARCHITECTURAL FEATURES
OF THE BUILDING, THE WORK SHALL BE INCLUDED AS PART OF
THIS WORK SCOPE, ADJUSTED AND MODIFIED AS NECESSARY.
CHANGES AFFECTING BUILDING APPEARANCE SHALL BE BROUGHT
TO THE ATTENTION OF THE ARCHITECT PRIOR TO INSTALLATION.
54. COORDINATE ALL LOW VOLTAGE SYSTEMS WORK, INSTALLATION
AND CONNECTION WITH OTHER TRADES AND WITH OWNER
REQUIREMENTS.
55. THE CONTRACTOR SHALL UNDERTAKE THIS WORK IN ITS
ENTIRETY IN ACCORDANCE WITH DESIGN AND PURPOSE. ALL
WORK SHALL BE PERFORMED IN A PROFESSIONAL MANNER,
QUALITY, EFFICIENCY AND WORKMANSHIP.
56. THE CONTRACTOR SHALL INCLUDE ANY COORDINATION, RELAYS,
TIMERS, NETWORK CARDS, TERMINAL STRIPS, ETC. AS REQUIRED
FOR A COMPLETE AND OPERATIONALLY FUNCTIONING SYSTEM TO
INTERFACE WITH ELEVATOR CONTROLLERS, FIRE ALARM SYSTEMS,
DOOR HARDWARE AND AUTOMATIC DOOR OPENING DEVICES,
WHERE APPLICABLE.
57. ALL EXIT DOORS SHALL REMAIN FREE OPENING FROM EXIT SIDE
VIA PANIC HARDWARE, U.O.N.
58. PENETRATIONS THROUGH FIRE-RATED FLOORS, WALLS AND
CEILINGS SHALL BE PROTECTED IN ACCORDANCE WITH CBC
SECTION 709.6 AND 710.1. SYSTEMS SHALL BE INSTALLED IN
ACCORDANCE WITH MANUFACTURERS INSTALLATION INSTRUCTIONS
AND APPROVED LISTING. MANUFACTURERS INSTALLATION
INSTRUCTIONS AND APPROVED LISTINGS SHALL BE PROVIDED
FOR REVIEW UPON REQUEST. ANY SUBSTITUTIONS OF APPROVED
MATERIALS OR METHODS SHALL BE SUBMITTED FOR APPROVAL
PRIOR TO INSTALLATION
59. IN THE EVENT OF DISCREPANCIES BETWEEN THE SPECIFICATIONS
AND CONTRACT DRAWINGS, WHICHEVER IS THE MORE STRINGENT
REQUIREMENT OR MANDATES THE HIGHEST QUALITY OR QUANTITY,
SHALL PREVAIL.
61. NO PIPES OR CONDUITS SHALL BE PLACED OR ROUTED
THROUGH TELECOMMUNICATIONS OR SERVER ROOMS UNLESS
THEY ARE DEDICATED TO THE TELECOM OR SERVER ROOM. ALL
DEDICATED PIPES AND CONDUITS SHALL BE ROUTED AS HIGH AS
PRACTICABLE IN THE ROOM, TIGHT TIGHT TO CEILING TO
PRECLUDE INTERFERENCE WITH OTHER SYSTEMS, LIGHTING,
POWER ETC. FEEDING RACKS AND EQUIPMENT.
62. ALL HORIZONTAL FIBER OPTIC CABLES SHALL BE INSTALLED IN
CONTINUOUS INNER DUCT FROM SERVER ROOMS TO IDF ROOMS.
INNER DUCT SHALL BE SECURED TO CABLE TRAY BELOW
COPPER CABLES.
63. VELCRO TY-WRAPS ARE TO BE USED WITHIN THE TR'S ONLY
NO ELECTRICAL TAPE OR TY-WRAPS ARE TO BE USED WITHIN
THE CEILING SPACES.
64. CONTRACTOR SHALL NOTIFY A UCD COMMUNICATIONS RESOURCE
REPRESENTATIVE A MINIMUM OF 48 HOURS IN ADVANCE BEFORE
THEY TEST AND CABLING WITHIN THE BUILDING. NO TESTING
SHALL BE PERFORMED UNTIL A COMMUNICATION RESOURCES
REPRESENTATIVE APPROVES THE TEST EQUIPMENT, METHODS AND
TEST SETTINGS. ANY TESTING COMPLETED BEFORE CR
APPROVAL WILL BE NULL AND VOID AND SHALL BE RETESTED
AT NO ADDED COST TO UCD IN COMPLIANCE OF CR STANDARDS
AND THE ABOVE CRITERIA.
65. ALL VOICE CABLING AND CROSSCONNECTS SHALL TESTED WITH A
FIELD RECORDABLE DEVICE AND RECORDS PRESENTED UPON
COMPLETION. TESTING SHALL COMPLY WITH NOTE #64 ABOVE.
66. ALL FIBER TESTING AND CROSSCONNECTS SHALL BE TESTED
WITH A FIELD RECORDABLE DEVICE AND RECORDS PRESENTED
UPON COMPLETION. TESTING SHALL COMPLY WITH NOTE
#64 ABOVE.
SITE NO.
SCALE
DATECHECKED BY
S.F.U.S.D. PROJECT NO.
SHEETS
DRAFTER
OF
XXXX05/31/18 JSM -
12064
CONSTRUCTION
DESIGN &
FACILITIES
135 Van Ness Avenue
San Francisco, California 94102
Tel (415) 355-6979
Fax (415) 355-6988
Architect Engineer
School Name and Address
Project Name
Date No. Revisions
SHEET NO.
DRAWING TITLE
Approvals
AS NOTED
SFUSD SAN FRANCISCOPUBLIC SCHOOLS
Consultant Name and Address
05/15/2018 - BID ISSUE
G U T T M A N N B L A E V O E T
C O N S U L T I N G E N G I N E E R S
E
P F
THERESA MAHLER
EARLY EDUCATION SCHOOL
990 CHURCH STREET
SAN FRANCISCO, CA 94114
SFUSD PROJ. #12064
SECURITY
IMPROVEMENTS
FACULTY LOUNGE 104
STOR 102AOFFICE 111TOIL 109TOFFICE 108
TOILET 103ATOILET 103B
CLASSROOM 102
CORRIDOR 112
JANITOR J70
TOILET 102T
PANTRY 107
KITCHEN 106
TOILET 101T
STOR 101
STOR 101A
CLASSROOM 101
CLASSROOM 103
PORCH 114PORCH 113
CO
RR
ID
OR
1
05
TO
IL
1
10
T
1
1
1
1IC
W
M
IC
W
M
IC
W
M
IC
M
2
1
1
9
0
°
9
0
°
9
0
°
IC
CA
9
0
°
9
0
°
9
0
°
90°90°
+108-120"+108-120"
+108-120"
+108-120"
90°90°
+108-120"+108-120"
90°
+144"
9
0
°
9
0
°
M32
3
4
5
6
7
8
9
10
11
+108" -
+120"
+108" -
+120"
+108" -
+120"
+108" -
+120"
+108" -
+120"
J
J J J J J J J J J J J J J J J J J J J J J J J J J J J J J J J J J J J J
JJ
JJ
J J J J J J J J
JJ
JJ
JJ
JJ
JJ
JJ
JJ
12
13
14 14 14
15
1617
18
19
19
19
19
20
S
21
22
23
24
1
2
3
45
6
7
8
9
10
11
12
13
SITE NO.
SCALE
DATE
CHECKED BY
S.F.U.S.D. PROJECT NO.
SHEETS
DRAFTER
OF
XXXX05/31/18 JSM -
12064
CONSTRUCTION
DESIGN &
FACILITIES
135 Van Ness Avenue
San Francisco, California 94102
Tel (415) 355-6979
Fax (415) 355-6988
Architect Engineer
School Name and Address
Project Name
Date No. Revisions
SHEET NO.
DRAWING TITLE
Approvals
AS NOTED
SFUSD SAN FRANCISCOPUBLIC SCHOOLS
Consultant Name and Address
05/15/2018 - BID ISSUE
G U T T M A N N B L A E V O E T
C O N S U L T I N G E N G I N E E R S
E
P F
THERESA MAHLER
EARLY EDUCATION SCHOOL
990 CHURCH STREET
SAN FRANCISCO, CA 94114
SFUSD PROJ. #12064
SECURITY
IMPROVEMENTS
TY-2.1
CCTV AND ENTRY SYSTEM
SITE PLAN
THIS ROOM HAS ACCESSIBLE T-GRID CEILING
EXISTING RACK TO MOUNT NVR AND AIPHONE
CONTROLLER, MOVE RAILS OUT TO ACCOMMODATE
NEW EQUIPMENT DEPTH TO THAT DATA CABLES TO
NOT TOUCH FRONT DOOR.
NEW AIPHONE DOOR STATION. INSTALL WIREWAY ON
INTERIOR WALL FOR STATION AND PUNCH THRU TO
OUTSIDE STATION AT +48" FOR THIS UNIT. IF WALL CAN
BE FISHED OPEN CABLE TO ACCESSIBLE CEILING IS
PREFERRED.
TYPICAL NEW EXTERIOR CAMERA LOCATION , SEE
DETAILS
TYPICAL NEW AIPHONE MASTER STATION ON WALL AT
+48" AFF, FISH WIRE IN WALL OR ROUTE SURFACE
WIREMOLD TO STATION AT HIS LOCATION,
COORDINATE FINAL LOCATION WITH SITE STAFF
PRINCIPAL
NEW MASTER STATOIN ON WALL IN CLASSROOM BY
DOOR, WALL MOUNTED UNIT
NEW SECURITY MONITOR IN PASSABLE WAY, MOUNT
AT +1-8" ON SWING ARM OUT MOUNTING BRACKET AT
THIS LOCATION. EXTEND 120VAC POWER FROM
NEAREST OUTLET AT THIS LOCATION USING
WIREMOLD 500 OR 700 TO MATCH WALL COLOR AND
LOCATE BEHIND MONITOR FOR DUPLEX BOX
1
2
3
4
5
KEYED NOTES:
6
7
ROUTE NEW CABLES INTO EQUIPMENT RACK,
FOLLOWING SAME PATHWAYS INTO CABINET, MOUNT
UPS IN BOTTOM OF CABINET AND MOVE OTHER
NETWORK EQUIPMENT TO TOP AS NEEDED TO
FACILITATE INSTALLATION OF NEW SECURITY
EQUIPMENT, USE EXISTING POWER AT THIS LOCATION
NEW MASTER STATION ON WALL BY PHONE
COORDINATE FINAL LOCATION WITH SITE PRINCIPALS
AT THIS LOCATION, WALL MOUNTED UNIT.
NEW CAMERA MOUNTED ON FACIA OF OVERHANG SO
THAT IT LOOKS AT THE HIGH PLAY YARD AREA.
NEW CAMERA ON BUILDING LOOKING AT PLAY AREA
TYPICAL NEW
3
4
" CONDUIT ON BEAM AND SUPPORT OF
OVERHANG
NEW TRUNK CONDUIT ALONG BUILDING, TYPICALLY
3
4
"
AT THIS LOCATION
NEW TRUNK CONDUIT AT THIS LOCATION ALONG
BUILDING SIZE FOR CABLE COUNT - MINIMUM 1"
CONDUIT
NEW NEMA 3R BOX RECOMMEND 12 X 12 X 4 AT THIS
LOCATION ON BLDG AT +108-120"
NEW 2" CONDUIT FROM JUNCTION STUBBED INTO
ACCESSIBLE CEILING SPACE OF FACULTY LOUNGE
8
9
10
11
12
13
14
15
16
BUSH END OF CONDUIT STUB INTO BLDG.
NEW 2" CONDUIT FROM JUNCTION STUBBED INTO
ACCESSIBLE CEILING SPACE OF FACULTY LOUNGE
NEW J-HOOKS FOR AIPHONE CABLING THROUGH
BLDG.
NEW WALL MOUNTED MASTER STATION, FISH WALL AS
POSSIBLE, OR USE EXISTING DROP PATHWAYS TO
ESTABLISH NEW STATION FOR THE SECRETARIES
LOCATIONS
NEW SURFACE MOUNTED ELECTRIC STRIKE AT THIS
LOCATION , MOUNT TO VERTICAL COLUMN TRANSITION
FROM CONDUIT TO W/P BOX AND ARMORED CABLE TO
SERVICE.
NEW
3
4
" CONDUIT STUBBED INTO CEILING SPACE FOR
STRIKE CABLING.
STUB INTO ACCESSIBLE CEILING SPACE WITH
3
4
"
CONDUIT AND CONTINUE CABLE TO RACK FOR POWER,
INSTALL DOOR POWER SUPPLY BELOW RACK
INSTALL DOOR POWER SUPPLY ON WALL BELOW RACK
AN CONNECT TO POWER IN RACK
17
18
19
20
ALTERNATE WIRING APPROACH CAN USE J-HOOKS AND
ROUTE CCTV CAMERA AND POWER CABLES VIA CONDUIT
STUBS TO CAMERAS EXTERIOR TO BLDG. IN LIEU OF
CONDUIT AROUND THE BLDG., HOWEVER ADDITIONAL
HAZMAT COORDINATION SHALL BE REQUIRED FOR DRILLING
THROUGH STRUCTURE
21
22
23
24
ALL NEW CONDUITS, WIREWAYS, ETC. SHALL
BE PAINTED TO MATCH. USE COLOR
MATCHING TECHNOLOGY OR GET PAINT
NUMBERS FROM SFUSD BUILDINGS AND
GROUNDS DEPT.
TY5.1
SECURITY SYSTEM BLOCK
RISER DIAGRAM AND
CAMERA MATRIX
PWR
TO UPS
120VAC
CCTV CAMERA SURVEILLANCE RISER BLOCK DIAGRAM - MISSION SITE
SCALE: NONE-
1
PATCH PNL
NVR
POWER SUP.
93 4
LEVEL 1 / GROUND FLOOR
D, P1 (TYPICAL)
1 2 6 7 85
(N) (N) (N)(N)(N)(N)(N)(N)
SITE NO.
SCALE
DATECHECKED BY
S.F.U.S.D. PROJECT NO.
SHEETS
DRAFTER
OF
XXXX05/31/18 JSM -
12064
CONSTRUCTION
DESIGN &
FACILITIES
135 Van Ness Avenue
San Francisco, California 94102
Tel (415) 355-6979
Fax (415) 355-6988
Architect Engineer
School Name and Address
Project Name
Date No. Revisions
SHEET NO.
DRAWING TITLE
Approvals
AS NOTED
SFUSD SAN FRANCISCOPUBLIC SCHOOLS
Consultant Name and Address
05/15/2018 - BID ISSUE
G U T T M A N N B L A E V O E T
C O N S U L T I N G E N G I N E E R S
E
P F
THERESA MAHLER
EARLY EDUCATION SCHOOL
990 CHURCH STREET
SAN FRANCISCO, CA 94114
SFUSD PROJ. #12064
SECURITY
IMPROVEMENTS
(N)
M32
V2
MAIN OFFICE
TO DISTRICT
NETWORK SWITCH
WAN/LAN
PATCH
CAMERA RES. TYPE NEW OREXISTING SIGNAL CABLE POWER CABLE PATCH PANEL
PORT DVR PORT
1 1080HD FIXED (N) (N) (N) 1 DVR-1-1
2 1080HD FIXED (N) (N) (N) 2 DVR-1-2
3 1080HD FIXED (N) (N) (N) 3 DVR-1-3
4 1080HD FIXED (N) (N) (N) 4 DVR-1-4
5 1080HD FIXED (N) (N) (N) 5 DVR-1-5
6 1080HD FIXED (N) (N) (N) 6 DVR-1-6
7 1080HD FIXED (N) (N) (N) 7 DVR-1-7
8 1080HD FIXED (N) (N) (N) 8 DVR-1-8
9 1080HD FIXED (N) (N) (N) 9 DVR-1-9
CCTV CAMERA SURVEILLANCE MATRIX - MISSION SITE
SCALE: NONE-
2
10 DVR-1-10
11 DVR-1-1112 DVR-1-12
13 DVR-1-1314 DVR-1-14
15 DVR-1-15
16 DVR-1-16
1110
(N)(N)(N)(N)
12 13
10 1080HD FIXED (N) (N) (N)
11 1080HD FIXED (N) (N) (N)
12 1080HD FIXED (N) (N) (N)
13 1080HD FIXED (N) (N) (N)
SPARESPARESPARE
SECURITY DETAILS
TY-7.1
NOTE: ALL CONDUIT SHALL BE INSTALLED UNDER BUILDING EAVES AND/OR UNDERSIDE OF WALKWAY COVERS
INSTALL TIGHT TO ALL SURFACES
TO PREVENT FINGER ACCESS
ABOVE OR BEHIND.
STEEL COMPRESSION COUPLING (EMT ONLY)
2-HOLE STRAP (TYP)
(ROUTE MULTIPLE CONDUITS WITH UNISTRUT)
OR THREADED RIGID COUPLING
CONDUIT SIZE A B
3/4" TO 1" 6" 18"
1¼" TO 2" 12" 24"
2½" TO 4" 12" 48"
(ROUTE MULTIPLE CONDUITS WITH
UNISTRUT BRACING AND SUPPORT)
PACKING
WOOL, ETC.
BACKEROD,
MINERAL
MATERIAL
FSP PUTTY
NELSON
(OPTIONAL)
METAL SLEEVE
1/2" DEPTH
BOTH SIDES
STEEL SLEEVE
OF FSP PUTTY
CAULK OVER
1" MAX
METAL PIPE
OR CONDUIT
CONCRETE WALL
(SOLID OR BLOCK)
1" FOR 3 HOURS
1/2" FOR 1-2 HOURS
System No.
C-AJ-1004
I
S
A
S
R
L
C
I
F
D
E
F Rating 3 Hr. T Rating 1/2 or 3/4 Hr.
4" MAXIMUM
FIREPROOFING CONDUIT THROUGH CONCRETE WALL
_
1
SCALE: NONE
CONDUIT STRAPPING REQUIREMENTS
_
2
SCALE: NONE
MINERAL WOOL
PACKING
BLOCK WALL
OR UL CLASSIFIED
SOLID CONCRETE
OR CONDUIT
METAL PIPE
3M FIRE BARRRIER
CP 25WB+ CALUK
DRYWALL
STUD WALL
SINGLE CHANNEL
TWO CHANNEL
MULTI-CHANNEL
MINIMUM PENETRATION:1"
SIZE & TYPE AS
REQUIRED
FIRE RATED
GYPSUM
WOOD OR STEEL STUD
WALLBOARD
1 1/2" MIN.
1/4"MAX
1/2"1/2"
FS-195 WRAP-STRIP
METAL PIPE
OR CONDUIT
3M FIRE BARRIER
System No.
W-L-1006
F Rating 2 Hr. T Rating 0 Hr.
I
S
A
S
R
L
C
I
F
D
E
2" MAXIMUM
Nelson FSP Putty - Min 1-1/2" depth
in the annular space around the pipe.
Apply an additional 1/8" crown around
the pipe where it exits the wall on
both sides.
SCALE: NONE_
4
TYPICAL CONCRETE WALL PENETRATION DETAIL
_
3
SCALE: NONE
TYPICAL WIREWAY MOUNTING DETAIL
_
5
SCALE: NONE
TYPICAL FIRE PROOFING CONDUIT THROUGH
GYP/STUD WALL
NOTE: CONDUIT STRAPPING IS REQUIRED PER DETAILS IRREGARDLESS OF WHAT ELECTRICAL CODE REQUIRES
WIREWAY OR BOX
CONDUIT SLEEVE
W/ BUSHING
FIRE CAULK &
SEAL PENETRATION
SIZE PENETRATION
TO NEC FOR 40% FILL
CEILING
1" MIN PENATRATION INTO
OR BUILDING STUD
SCALE:-
7 TYPICAL STUB FROM WIREWAY TO DEVICE BOX/BOX TO BOX
NONE
FLOOR
+48" AFF MAX.
TO OPERABLE CONTROL
SCALE:-
6 TYIPCAL STATION MOUNTING HEIGHT
NONE
SITE NO.
SCALE
DATE
CHECKED BY
S.F.U.S.D. PROJECT NO.
SHEETS
DRAFTER
OF
XXXX05/31/18 JSM -
12064
CONSTRUCTION
DESIGN &
FACILITIES
135 Van Ness Avenue
San Francisco, California 94102
Tel (415) 355-6979
Fax (415) 355-6988
Architect Engineer
School Name and Address
Project Name
Date No. Revisions
SHEET NO.
DRAWING TITLE
Approvals
AS NOTED
SFUSD SAN FRANCISCOPUBLIC SCHOOLS
Consultant Name and Address
05/15/2018 - BID ISSUE
G U T T M A N N B L A E V O E T
C O N S U L T I N G E N G I N E E R S
E
P F
THERESA MAHLER
EARLY EDUCATION SCHOOL
990 CHURCH STREET
SAN FRANCISCO, CA 94114
SFUSD PROJ. #12064
SECURITY
IMPROVEMENTS
RIGHT FACING MOUNTINGLEFT FACING MOUNTING
BACK BOX FRONT STATION FRONT STATION SIDE VIEW
SCALE:-
8 MOUNTING LOCATION FOR CALL STATION
NONE
MINERAL WOOL
PACKING
BLOCK WALL
OR UL CLASSIFIED
SOLID CONCRETE
OR CONDUIT
METAL PIPE
3M FIRE BARRRIER
CP 25WB+ CALUK
OUTLINE OF CUSTOM SHIELD
OR SHROUD FOR WEATHER
PROTECTION, VIKING ELECTRONICS
OR SIMILAR MADE FROM STAINLESS
STEEL, SIMILAR TO AIPHONE SBX-ACE
AIPHONE STATOIN
SECURITY DETAILS
TY-7.2
Front View
Side View
Top View
8-1/4”
9” 1-3/4”
3/4”
-
1
SCALESCALE:
Mounting
Screw
Lockdown
Screw
(optional)
Set Screw
Location
Mounting
Screw
-
2
SCALESCALE:
C
L
Set Screw
Location
RUN
WIRING
IN
CENTER
COLUMN
-
3
NONESCALE:
C
L
SITE NO.
SCALE
DATECHECKED BY
S.F.U.S.D. PROJECT NO.
SHEETS
DRAFTER
OF
XXXX05/31/18 JSM -
12064
CONSTRUCTION
DESIGN &
FACILITIES
135 Van Ness Avenue
San Francisco, California 94102
Tel (415) 355-6979
Fax (415) 355-6988
Architect Engineer
School Name and Address
Project Name
Date No. Revisions
SHEET NO.
DRAWING TITLE
Approvals
AS NOTED
SFUSD SAN FRANCISCOPUBLIC SCHOOLS
Consultant Name and Address
05/15/2018 - BID ISSUE
G U T T M A N N B L A E V O E T
C O N S U L T I N G E N G I N E E R S
E
P F
THERESA MAHLER
EARLY EDUCATION SCHOOL
990 CHURCH STREET
SAN FRANCISCO, CA 94114
SFUSD PROJ. #12064
SECURITY
IMPROVEMENTS
HES 9600 ELECTRIC STRIKE INSTALL DETAIL
MULLION OR CENTER COLUMN -TYPICAL
HES 9600 ELECTRIC STRIKE DIMENSIONAL
DRAWING - TYPICAL
HES 9600 ELECTRIC STRIKE INSTALL DETAIL
-TYPICAL
EXISTING CLASSROOM CONDITION NEW INSTALL CLASSROOM CONDITION
SCALE:-
4 WALL PHONE MOUTING AND RELOCATION DETAIL FOR VIDEO INTERCOM
NONE
NEW VIDEO INTERCOM
ON WALL ABOVE PHONE
NEW SHALLOW PANCAKE BOX
ON WALL FOR NEW PHONE CABLING AND OUTLET
NEW VERTICAL WIREMOLD 500 OR 700
WHITE TO CONNECT TO STATION
NEW VERTICAL WIREMOLD 500 OR 700
WHITE TO CONNECT TO STATION
NEW SHALLOW PANCAKE BOX
ON WALL FOR NEW PHONE CABLING AND
OUTLET, THIS BOX IS ONLY FOR MOUNTING
EXISTING PHONE TO MAINTAIN PROPER SPACING
FOR NEW VIDEO INTERCOM UNIT
INSTALL NEW SHALLOW BOX ON WALL AND REINSTALL
FACEPLATE AND CABLE AND RECONNECT PHONE
CAT5E
TO POWER SUPPLIES
CAT5E
MOUNTED IN NEW RACK
FLOOR
+48" AFF
#14 OR #12 CABLE 2 CONDUCTOR OVER SIZE FOR DISTANCE
TO STRIKE AND POWER SUPPLY
MAX.
SCALE:-
5 AIPHONE ENTRY SYSTEM WIRING / BLOCK DIAGRAM (PROVIDE FOR DOOR & MASTER STATIONS)
NONE
SCALE:-
6 CAMERA DROPS FOR CONDUIT AND BACKBONE ALONG BUILDING
NONE
CONDUITS ALONG BLDGCONDUITS ALONG BLDG
CONDUITS ALONG BLDGCONDUITS ALONG BLDG
CAST
W/P BOX
CAST
W/P BOX
CONDUIT TO
CAMERA
CONDUIT SWEEPS TO
DUAL CAMERAS
ALTERNATE OR OPTIONAL
CONFIGURATION ON BLDG.
SECURITY DETAILS
TY-7.3
SITE NO.
SCALE
DATECHECKED BY
S.F.U.S.D. PROJECT NO.
SHEETS
DRAFTER
OF
XXXX05/31/18 JSM -
12064
CONSTRUCTION
DESIGN &
FACILITIES
135 Van Ness Avenue
San Francisco, California 94102
Tel (415) 355-6979
Fax (415) 355-6988
Architect Engineer
School Name and Address
Project Name
Date No. Revisions
SHEET NO.
DRAWING TITLE
Approvals
AS NOTED
SFUSD SAN FRANCISCOPUBLIC SCHOOLS
Consultant Name and Address
05/15/2018 - BID ISSUE
G U T T M A N N B L A E V O E T
C O N S U L T I N G E N G I N E E R S
E
P F
THERESA MAHLER
EARLY EDUCATION SCHOOL
990 CHURCH STREET
SAN FRANCISCO, CA 94114
SFUSD PROJ. #12064
SECURITY
IMPROVEMENTS
APPROX 8' 6" A.F.F.
EXTERIOR WALL
FINISHED SIDEWALK
INTERIOR WALL MOUNT FIXED CAMERA
SCALE: NONE-
1
APPROX 10' A.F.F.
3/4" C. TO SECURITY
PANELS/EQUIPMENT
FINISHED SIDEWALK
EXTERIOR WALL
EXTERIOR DUAL FIXED DOME DETAIL
SCALE: NONE-
2
APPROX 8' 6" ' A.F.F.
3/4" C. TO SECURITY
PANELS/EQUIPMENT
FINISHED FLOOR
INTERIOR WALL
INTERIOR DUAL FIXED DOME DETAIL - SIDE ENTRANCE
SCALE: NONE-
3
APPROX 8' 6" ' A.F.F.
3/4" C. TO
CHANNEL
FINISHED FLOOR
INTERIOR WALL
INTERIOR DUAL FIXED DOME DETAIL - TOP ENTRANCE WIREWAY
SCALE: NONE-
5
3/4" CONDUIT
OR CHASE
NIPPLE
WIREWAY CHANNEL
3/4" C. TO SECURITY
PANELS/EQUIPMENT
3/4" CONDUIT
OR CHASE
NIPPLE
APPROX 8' 6" ' A.F.F.
3/4" C.
FINISHED FLOOR
INTERIOR WALL
INTERIOR DUAL FIXED DOME DETAIL - TOP ENTRANCE
SCALE: NONE-
4
3/4" CONDUIT
OR CHASE
NIPPLE
APPROX 10' A.F.F.
EXTERIOR WALL
FINISHED SIDEWALK
EXTERIOR WALL MOUNT FIXED CAMERA
SCALE: NONE-
6
3/4" C. TO SECURITY
PANELS/EQUIPMENT
(NO FLEX ALLOWED)