Assurance Building Inspections, LLC Your Property Inspection Report Cover Page 630 S. SURREY CT, G.J., CO 81507 Inspection prepared for: YI LIU Real Estate Agent: JULIE PILAND - UNITED COUNTRYREAL QUEST REALTY Date of Inspection: 3/3/2017 Time: 1:00 PM Age of Home: 27 YRS Size: 3400 SQ FT Inspector: Lynn Bemis License # 460 East Scenic Drive, Grand Junction, CO 81507 Phone: 970-234-6457 Fax: 970-255-8192 Email: [email protected] assurancebuildinginspections.com

Assurance Building Inspections, LLChip-user-files.s3.amazonaws.com/lbemis/Liu_3-3-17-Report-292279.pdf · 3/3/2017  · Note that this report is a snapshot in time. We recommend

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Assurance Building Inspections, LLChip-user-files.s3.amazonaws.com/lbemis/Liu_3-3-17-Report-292279.pdf · 3/3/2017  · Note that this report is a snapshot in time. We recommend

Assurance Building Inspections, LLCYour Property Inspection Report

Cover Page

630 S. SURREY CT, G.J., CO 81507Inspection prepared for: YI LIU

Real Estate Agent: JULIE PILAND - UNITED COUNTRYREAL QUEST REALTY

Date of Inspection: 3/3/2017 Time: 1:00 PM Age of Home: 27 YRS Size: 3400 SQ FT

Inspector: Lynn BemisLicense #

460 East Scenic Drive, Grand Junction, CO 81507Phone: 970-234-6457 Fax: 970-255-8192

Email: [email protected]

Page 2: Assurance Building Inspections, LLChip-user-files.s3.amazonaws.com/lbemis/Liu_3-3-17-Report-292279.pdf · 3/3/2017  · Note that this report is a snapshot in time. We recommend

Assurance Building Inspections, LLC 630 S. SURREY CT, G.J., CO

Page 1 of 24

We appreciate the opportunity to conduct this inspection for you! Please carefully read your entireInspection Report. Call us after you have reviewed your report, so we can go over any questionsyou may have. Remember, when the inspection is completed and the report is delivered, we are stillavailable to you for any questions you may have, throughout the entire closing process.Properties being inspected do not "Pass" or "Fail.” - The following report is based on an inspectionof the visible portion of the structure; inspection may be limited by vegetation and possessions. Depending upon the age of the property, some items like GFCI outlets may not be installed; thisreport will focus on safety and function, not current code. This report identifies specific non-code,non-cosmetic concerns that the inspector feels may need further investigation or repair. For your safety and liability purposes, we recommend that licensed contractors evaluate and repairany critical concerns and defects. Note that this report is a snapshot in time. We recommendthat you or your representative carry out a final walk-through inspection immediately beforeclosing to check the condition of the property, using this report as a guide.

Page 3: Assurance Building Inspections, LLChip-user-files.s3.amazonaws.com/lbemis/Liu_3-3-17-Report-292279.pdf · 3/3/2017  · Note that this report is a snapshot in time. We recommend

Assurance Building Inspections, LLC 630 S. SURREY CT, G.J., CO

Page 2 of 24

Summary of Items of ConcernSummary of Items of Concern

On this page you will find, in RED, a brief summary of any CRITICAL concerns of the inspection, asthey relate to Safety and Function. Examples would be bare electrical wires, or active drain leaks.The complete list of items noted is found throughout the body of the report, including NormalMaintenance items. Be sure to read your entire report!For your safety and liability, we recommend that you hire only licensed contractors when having anywork done. If the living area has been remodeled or part of an addition, we recommend that youverify the permit and certificate of occupancy. This is important because our inspection does nottacitly approve, endorse, or guarantee the integrity of any work that was done without a permit, andlatent defects could exist. Depending upon your needs and those who will be on this property, items listed in the body of thereport may also be a concern for you; be sure to read your Inspection Report in its entirety.Note: If there are no comments in RED below, there were no CRITICAL system or safety concernswith this property at the time of inspection.Interior FeaturesPage 20 Item: 8 Interior Electric • Smoke detectors missing in bedrooms. Installation

recommended.• Receptacle in master bedroom has an open neutral.

Page 4: Assurance Building Inspections, LLChip-user-files.s3.amazonaws.com/lbemis/Liu_3-3-17-Report-292279.pdf · 3/3/2017  · Note that this report is a snapshot in time. We recommend

Assurance Building Inspections, LLC 630 S. SURREY CT, G.J., CO

Page 3 of 24

Exterior Areas This section describes the exterior wall coverings and trim. Inspectors are required to inspect theexterior wall coverings, flashing, trim, all exterior doors, the stoops, steps porches and theirassociated railings, any attached decks and balconies and eaves, soffits and fascias accessible fromground level.

1. RoofMaterials: Composition shinglesObservations:• No major system safety or function concerns noted at time of inspection.

good roof venting2. Chimney

3. Gutters & GradingInformation: Aluminum Gutters

Page 5: Assurance Building Inspections, LLChip-user-files.s3.amazonaws.com/lbemis/Liu_3-3-17-Report-292279.pdf · 3/3/2017  · Note that this report is a snapshot in time. We recommend

Assurance Building Inspections, LLC 630 S. SURREY CT, G.J., CO

Page 4 of 24

need to add permit extensions to downspouts

good extension valve boxes should be filled in with dirt to keepwater from running under steps

downspout wait not hooked up undermining patio

Page 6: Assurance Building Inspections, LLChip-user-files.s3.amazonaws.com/lbemis/Liu_3-3-17-Report-292279.pdf · 3/3/2017  · Note that this report is a snapshot in time. We recommend

Assurance Building Inspections, LLC 630 S. SURREY CT, G.J., CO

Page 5 of 24

4. Drives & WalksInformation: Concrete driveway, Concrete sidewalk.

some concrete spalling in driveway concrete spalling5. SidingInformation: Composition wood siding, wood frame construction.

water damage on siding NO ISSUE6. Vegetation

Page 7: Assurance Building Inspections, LLChip-user-files.s3.amazonaws.com/lbemis/Liu_3-3-17-Report-292279.pdf · 3/3/2017  · Note that this report is a snapshot in time. We recommend

Assurance Building Inspections, LLC 630 S. SURREY CT, G.J., CO

Page 6 of 24

recommend keeping water and plants away fromHouse

Good landscape border keeping water fromHouse.

7. Decks & StepsObservations:• No major system safety or function concerns noted at time of inspection.• Settlement crack at base of front steps. Monitor and repair as necessary.

minor cracking at front steps on sidewalk

Page 8: Assurance Building Inspections, LLChip-user-files.s3.amazonaws.com/lbemis/Liu_3-3-17-Report-292279.pdf · 3/3/2017  · Note that this report is a snapshot in time. We recommend

Assurance Building Inspections, LLC 630 S. SURREY CT, G.J., CO

Page 7 of 24

NO ISSUE balusters spacing too wide to meet today's code8. Electrical, Exterior

non-conforming electrical connection9. Doors

Page 9: Assurance Building Inspections, LLChip-user-files.s3.amazonaws.com/lbemis/Liu_3-3-17-Report-292279.pdf · 3/3/2017  · Note that this report is a snapshot in time. We recommend

Assurance Building Inspections, LLC 630 S. SURREY CT, G.J., CO

Page 8 of 24

sliding door missing screen door screen missing sliding door Southeast corner10. Window ConditionObservations:• Some window screens missing and some damaged.

left screen damage right one missing

Page 10: Assurance Building Inspections, LLChip-user-files.s3.amazonaws.com/lbemis/Liu_3-3-17-Report-292279.pdf · 3/3/2017  · Note that this report is a snapshot in time. We recommend

Assurance Building Inspections, LLC 630 S. SURREY CT, G.J., CO

Page 9 of 24

Garage, Basement & Attic Note that minor settlement or “hairline” cracks in garage or basement slabs are not noted in aninspection, as they are normal to properties of any age. They should, however, be monitored forexpansion and sealed as necessary. Residential inspections only include garages and carports thatare physically attached to the house. They are not considered habitable, and conditions are reportedaccordingly.Inspectors are not required to enter any crawlspace areas that are not readily accessible, less than36” clearance, wet (electrical shock hazard), or where entry could cause damage or pose a hazard tothe inspector.We recommend that all attic hatches have a batt of fiberglass insulation installed over them, and thatthe hatch be sealed shut with latex caulk. This will keep warm moist air from entering the attic, whichmay cause condensation or even mold. Note that every attic has mold; mold is everywhere. Someattics have some minor visible mold. This is often a result of the building process, when materials getwet during construction. If there is extensive mold, or mold that appears to have grown due to poormaintenance conditions, we will report it to you, the client. If the hatch is sealed shut when we go toinspect the attic, it can only be unsealed by the owner or their representative, as our insuranceprohibits us from performing any destructive testing or entry. In accordance with industry andinsurance standards, we will not attempt to enter an attic that has no permanently installed steps orpull-down stairs; less than thirty-six inches of headroom; does not have a standard floor designed fornormal walking; walking, in the inspector’s opinion, may compromise the ceiling below; is restrictedby ducts, or in which the insulation obscures the joists and thereby makes mobility hazardous, inwhich case we will inspect the attic as best we can from the access point, with no comments orevaluations of areas not readily viewed from the hatch area. 1. GarageObservations:• No major system safety or function concerns noted at time of inspection.

both Overhead Doors operated at inspection also sensors are correct2. Basement / CrawlspaceObservations:• No major system safety or function concerns noted at time of inspection.• Inspection Method: Traversed• Vapor barrier is missing or damaged. Recommend installing 6 mil polyethylene.

Page 11: Assurance Building Inspections, LLChip-user-files.s3.amazonaws.com/lbemis/Liu_3-3-17-Report-292279.pdf · 3/3/2017  · Note that this report is a snapshot in time. We recommend

Assurance Building Inspections, LLC 630 S. SURREY CT, G.J., CO

Page 10 of 24

crawl space access main water shut off valve no Vapor Barrier onground

3. AtticObservations:• No major system safety or function concerns noted at time of inspection.• Cellulose Insulation• Insulation averages about 8-10 inches in depth

no issue approximate 10-inch cellulose insulation

Page 12: Assurance Building Inspections, LLChip-user-files.s3.amazonaws.com/lbemis/Liu_3-3-17-Report-292279.pdf · 3/3/2017  · Note that this report is a snapshot in time. We recommend

Assurance Building Inspections, LLC 630 S. SURREY CT, G.J., CO

Page 11 of 24

attic access through master bedroom closet ceiling

Page 13: Assurance Building Inspections, LLChip-user-files.s3.amazonaws.com/lbemis/Liu_3-3-17-Report-292279.pdf · 3/3/2017  · Note that this report is a snapshot in time. We recommend

Assurance Building Inspections, LLC 630 S. SURREY CT, G.J., CO

Page 12 of 24

Electric, Heat, Water Heater Electric: Note that only actual GFCI outlets are tested and tripped. Some baths may have non-GFCI outlets which are protected by a GFCI outlet in a remote area (garage, another bath, etc.). Confirm with owner that apparent non-GFCI outlets within 6’ of wet areas are thus protected. Also,note that most electricians agree that smoke detectors are good for about 5 years, and the breakersin your panel box have an expected life of about 20 years. Therefore, if this home was built before1990, consider having the panel box and breakers evaluated by a licensed electrician, as anoverheated breaker can result in a structural fire. If your home does not have a carbon monoxidedetector (few do!), we recommend making that investment. Any home that has a Bulldog Pushmatic,Zinsco, Sylvania Zinsco or Federal Pacific Electric panel should have it evaluated by a licensedelectrician, as these older types of panels and breakers have been known to overheat and causehouse fires.Heat: The heating, ventilation, air conditioning and cooling system (often referred to as HVAC) is theclimate control system for the structure. The goal of these systems is to keep the occupants at acomfortable level while maintaining indoor air quality, ventilation while keeping maintenance costs ata minimum. The HVAC system is usually powered by electricity and natural gas, but can also bepowered by other sources such as butane, oil, propane, solar panels, or wood. The inspector willtest the heating and air conditioner using the thermostat or other controls. A more thoroughinvestigation of the system, including the heat (“firebox”) exchanger, should be conducted by alicensed HVAC service person every year. Failure to do so may result in carbon monoxide escapingthrough cracks in a heat exchanger or flue pipe, resulting in death.1. Electrical PanelMaterials: Underground Service, 200 Amp Service, Main Disconnect in panel box, GEObservations:• Panel cover screw(s) missing.

well labelled, screw missing to face, open wires incabinet should be wire nuted off.

Page 14: Assurance Building Inspections, LLChip-user-files.s3.amazonaws.com/lbemis/Liu_3-3-17-Report-292279.pdf · 3/3/2017  · Note that this report is a snapshot in time. We recommend

Assurance Building Inspections, LLC 630 S. SURREY CT, G.J., CO

Page 13 of 24

northeast corner of house irrigation clock, cable TV, telephone, electric panel2. HVAC UnitObservations:• No major system safety or function concerns noted at time of inspection.

two swamp coolers winterized and covered no issues

Page 15: Assurance Building Inspections, LLChip-user-files.s3.amazonaws.com/lbemis/Liu_3-3-17-Report-292279.pdf · 3/3/2017  · Note that this report is a snapshot in time. We recommend

Assurance Building Inspections, LLC 630 S. SURREY CT, G.J., CO

Page 14 of 24

pressures correct operating at inspection3. Water HeaterObservations:• No major system safety or function concerns noted at time of inspection.

H2O SHUT OFF & EXPANSION TANK 40 gallon reliance

Page 16: Assurance Building Inspections, LLChip-user-files.s3.amazonaws.com/lbemis/Liu_3-3-17-Report-292279.pdf · 3/3/2017  · Note that this report is a snapshot in time. We recommend

Assurance Building Inspections, LLC 630 S. SURREY CT, G.J., CO

Page 15 of 24

Interior Features This inspection does not include testing for radon, mold or other hazardous materials unlessspecifically requested.Plumbing is an important concern in any structure. Moisture in the air and leaks can cause mildew,wallpaper and paint to peel, and other problems. The home inspector will identify as many issues aspossible but some problems may be undetectable due to problems within the walls or under theflooring. Note that if in a rural location, sewer service and/or water service might be provided by private wastedisposal system and/or well. Inspection, testing, analysis, or opinion of condition and function ofprivate waste disposal systems and wells is not within the scope of a home inspection. Recommendconsulting with seller concerning private systems and inspection, if present, by appropriate licensedprofessional familiar with such private systems. If a Septic System is on the property, pumping isgenerally recommended prior to purchase, and then every three years. Interior areas consist of bedrooms, baths, kitchen, laundry, hallways, foyer, and other open areas. All exposed walls, ceilings and floors will be inspected. Doors and windows will also beinvestigated for damage and normal operation. Although excluded from inspection requirements, wewill inform you of obvious broken gas seals in windows. Please realize that they are not alwaysvisible, due to temperature, humidity, window coverings, light source, etc. Your inspection will reportvisible damage, wear and tear, and moisture problems if seen. Personal items in the structure mayprevent the inspector from viewing all areas, as the inspector will not move personal items.An inspection does not include the identification of, or research for, appliances and other items thatmay have been recalled or have had a consumer safety alert issued about it. Any comments made inthe report are regarding well known notices and are provided as a courtesy only. Product recalls andconsumer product safety alerts are added almost daily by the Consumer Product SafetyCommission. We recommend visiting the following Internet site if recalls are a concern to you:http://www.cpsc.gov.1. KitchenObservations:• GFCI TRIP TEST PASSED.

TESTED NO ISSUE

Page 17: Assurance Building Inspections, LLChip-user-files.s3.amazonaws.com/lbemis/Liu_3-3-17-Report-292279.pdf · 3/3/2017  · Note that this report is a snapshot in time. We recommend

Assurance Building Inspections, LLC 630 S. SURREY CT, G.J., CO

Page 16 of 24

GFCI test passed WASHER LOADED (NOT TESTED)

NO ISSUE NO ISSUE2. Master BathObservations:• LOCATION:• No major system safety or function concerns noted at time of inspection.• GFCI trip test passed.

Page 18: Assurance Building Inspections, LLChip-user-files.s3.amazonaws.com/lbemis/Liu_3-3-17-Report-292279.pdf · 3/3/2017  · Note that this report is a snapshot in time. We recommend

Assurance Building Inspections, LLC 630 S. SURREY CT, G.J., CO

Page 17 of 24

NO ISSUE NO ISSUE

NO ISSUE GOOD

GFCI test passed chip tub not tested switch could not be located

Page 19: Assurance Building Inspections, LLChip-user-files.s3.amazonaws.com/lbemis/Liu_3-3-17-Report-292279.pdf · 3/3/2017  · Note that this report is a snapshot in time. We recommend

Assurance Building Inspections, LLC 630 S. SURREY CT, G.J., CO

Page 18 of 24

3. BathObservations:• LOCATION: northcenter• GFCI TRIP TEST PASSED.

drains well no issue

NO ISSUE

Page 20: Assurance Building Inspections, LLChip-user-files.s3.amazonaws.com/lbemis/Liu_3-3-17-Report-292279.pdf · 3/3/2017  · Note that this report is a snapshot in time. We recommend

Assurance Building Inspections, LLC 630 S. SURREY CT, G.J., CO

Page 19 of 24

NO ISSUE NO ISSUE4. Bath #2Observations:• LOCATION: basement• No major system safety or function concerns noted at time of inspection.• GFCI trip tes tpassed.

GOOD GFCI test passed5. Bath (Guest)

6. Bath (Half)

7. Plumbing & Laundry

Page 21: Assurance Building Inspections, LLChip-user-files.s3.amazonaws.com/lbemis/Liu_3-3-17-Report-292279.pdf · 3/3/2017  · Note that this report is a snapshot in time. We recommend

Assurance Building Inspections, LLC 630 S. SURREY CT, G.J., CO

Page 20 of 24

no issues8. Interior ElectricObservations:• No major system safety or function concerns noted at time of inspection.• Smoke detectors missing in bedrooms. Installation recommended.• Receptacle in master bedroom has an open neutral.

receptacle master bedroom next to closet has open neutral9. Floors, Ceilings & WallsObservations:• Minor settlement cracks noted, which is normal for a house of this age.

Page 22: Assurance Building Inspections, LLChip-user-files.s3.amazonaws.com/lbemis/Liu_3-3-17-Report-292279.pdf · 3/3/2017  · Note that this report is a snapshot in time. We recommend

Assurance Building Inspections, LLC 630 S. SURREY CT, G.J., CO

Page 21 of 24

no issue minor drywall damage at Ridgeline

prior water damage minor

jet tub pump access

Page 23: Assurance Building Inspections, LLChip-user-files.s3.amazonaws.com/lbemis/Liu_3-3-17-Report-292279.pdf · 3/3/2017  · Note that this report is a snapshot in time. We recommend

Assurance Building Inspections, LLC 630 S. SURREY CT, G.J., CO

Page 22 of 24

10. DoorsObservations:• (2) sliding screen doors missing.

11. WindowsObservations:• Some window screens missing and some damaged.

12. Fireplaces & StovesObservations:• gas turned off to fireplace (have owner demonstrate)

fireplace not lit or operating have owner demonstrate13. StairwaysObservations:• No major system safety or function concerns noted at time of inspection.

no issue

Page 24: Assurance Building Inspections, LLChip-user-files.s3.amazonaws.com/lbemis/Liu_3-3-17-Report-292279.pdf · 3/3/2017  · Note that this report is a snapshot in time. We recommend

Assurance Building Inspections, LLC 630 S. SURREY CT, G.J., CO

Page 23 of 24

A Home Inspection is a non-invasive visual examination of a residential dwelling, performed for a fee,which is designed to identify observed material defects within specific components of said dwelling. Components may include any combination of mechanical, structural, electrical, plumbing, or otheressential systems or portions of the home, as identified and agreed to by the Client and Inspector,prior to the inspection process.A home inspection is intended to assist in evaluation of the overall condition of the dwelling. Theinspection is based on observation of the visible and apparent condition of the structure and itscomponents on the date of the inspection and not the prediction of future conditions.A home inspection will not reveal every concern that exists or ever could exist, but only thosematerial defects observed on the day of the inspection.A material defect is a condition with a residential real property or any portion of it that would have asignificant adverse impact on the value of the real property or that involves an unreasonable risk topeople on the property. The fact that a structural element, system or subsystem is near, at or beyondthe end of the normal useful life of such a structural element, system or subsystem is not by itself amaterial defect.An Inspection report shall describe and identify in written format the inspected systems, structures,and components of the dwelling and shall identify material defects observed. Inspection reports maycontain recommendations regarding conditions reported or recommendations for correction,monitoring or further evaluation by professionals, but this is not required.

Page 25: Assurance Building Inspections, LLChip-user-files.s3.amazonaws.com/lbemis/Liu_3-3-17-Report-292279.pdf · 3/3/2017  · Note that this report is a snapshot in time. We recommend

Assurance Building Inspections, LLC 630 S. SURREY CT, G.J., CO

Page 24 of 24

General Notes 1. General NotesObservations:

(1) TWO SLIDING SCREEN DOORS MISSING. SOME WINDOW SCREENS MISSING ORDETERIORATED. (2)MINOR CEILING DAMAGE AT LIVING ROOM & BASEMENT BY JET TUBPUMP ACCESS. (3)NO SMOKE DETECTORS IN BED ROOMS. (4)CORRECT DRAINAGE ATVALVE BOXES. (5)OPEN NEUTRAL RECEPTACLE MASTERBEDROOM. NON CONFORMINGELECTRICAL CONNECTION AT BAY AREA S.W. CORNER. (6)HAVE OWNER DEMONSTRATEFIRE PLACE OPERATION & JET TUB. SPRINKLER START UP AND OPERATION.