Asset Register – Mechanical Services North Herts Leisure Centre
Z:\3188\SBR\Asset Register Report\N.H.D.C
Asset Register and Conditions Schedule
for the
Mechanical Engineering Services
at
North Herts Leisure Centre
Rev Reason for Issue Date
A Preliminary Issue 13/05/2013B Asset Register Update 21/05/2013
Building Services Consultant Engineers
David Bedwell & PartnersManor House Yard,
Royston,Herts.
SG8 7BZ
(Tel: 01763 241556)(Fax: 01763 246487)
Email – [email protected]
Asset Register – Mechanical Services North Herts Leisure Centre
Z:\3188\SBR\Asset Register Report\N.H.D.C
Mechanical Services Specification
Table of Contents
Section Description
1.0 Introduction, Purpose and Format
2.0 Contractor’s Examinations, Checks and Tests
3.0 Exclusions / Clarification
Appendix A Asset Register : Conditions Schedule
Appendix B Summary Asset Register
Appendix C Excerpt from CIBSE Guide Volume M (2008) – Indicative LifeExpectancy for Building Services Plant, Equipment andSystems.
Appendix D Excerpts from B & S E (HVCA) SFG 20 (2012) – the StandardMaintenance Specification for Mechanical and ElectricalServices to Buildings
Asset Register – Mechanical Services North Herts Leisure Centre
Z:\3188\SBR\Asset Register Report\N.H.D.C
1.0 Introduction, Purpose and Format
1.1.0 Introduction
1.1.1 The maintenance philosophy adopted in this document relate to theexisting / installed mechanical equipment and plant and suchmaintenance regimes that shall be adopted in terms of PLANNEDPREVENTATIVE MAINTENANCE (PPM)
1.1.2 As its name implies PPM is a method of maintenance whichnecessitates well-defined maintenance routines for plant andequipment at regular pre-determined intervals. In contrast toRESPONSE MAINTENANCE which is effectively breakdownmaintenance; the philosophy underlying PPM is that plant andequipment is kept operating at or near its peak efficiency.
If PPM is organised and undertaken properly it will produce significantbenefits, the most important of these being the reduction of high repaircosts and energy costs and the elimination of lost revenue resultingfrom forced closure of facilities.
1.1.3 Initially the implementation of PPM is costly but in the long term will besubstantially less expensive than a response maintenance policy.
1.2.0 Purpose
1.2.1 The purpose of this document is identify all items of mechanicalservices equipment and plant currently installed at the Outdoor Pool,Letchworth, and subsequently the required PPM regime which shall bethe responsibility of the successful Contractor to perform.
1.2.0 Format
a) The PPM details included in this document are based upon performancerequirements as distinct from detailed schedules of the numerousspecific examinations, tests and checks that will be required of thesuccessful Contractor to achieve the standard of maintenance required.
b) In order to comply with the maintenance standards set out in theschedule the successful Contractor will therefore be required, not only tocomplete the stipulated tests, checks and examinations in accordancewith SFG20 (2012), but also to respond to any works necessary toachieve the standard of maintenance identified in the schedules.
c) The Contractor will be expected to complete all maintenancerequirements in accordance with the frequency intervals as specified inSFG20 (2012) and shall pay all costs relating to such works.
Asset Register – Mechanical Services North Herts Leisure Centre
Z:\3188\SBR\Asset Register Report\N.H.D.C
d) It should also be clearly understood, with regard to the period withinwhich corrective maintenance or repair is to be achieved, that where, inthe opinion of the Contract Administrator, failure to complete such worksmay give rise to potential injury to staff or users, the minimum statedresponse times will be applied. In certain circumstances it may on theother hand be the case that stated response times may be extended bythe Contract Administrator, when for example the subject building is notin use.
e) Much of the information appertaining to manufacturers, equipment / planttechnical data, current condition, etc as identified in Appendix’s A and Bis self-evident but for the avoidance of misunderstanding the followingadditional explanatory notes are provided:-
Condition Panel:
The intention of this panel is to indicate the condition of the item ofequipment at the date of tender invitation and is based on a scale of 1 to5. The classifications attributed to each point on the scale are asfollows:-
1 = In need of Repalacement2 = Poor Condition for Age, but still serviceable3 = Average Condition for Age4 = Good Condition for Age5 = As New (Excellent Condition)
Reference Appendix A the Asset Register : Conditions Schedule theassessed condition is identified by enlarged figures highlighted in boldtext.
Maintenance Schedule:
The Asset Register : Conditions Schedule includes reference toAppendix D, SFG20 (2012), the Standard Maintenance Specification forMechanical and Electrical Services to Buildings. Each Equipment / Plantdata sheet makes reference to the applicable maintenance clause thusidentifying the extent and frequency at which the required PPM shall beundertaken.
i.e. – Clause 05-23 of SFG20 (2012) refers to “05” Boilers/HeatGenerators and “23” LTHW Boilers.
Note: it is assumed that as competent M&E Maintenance Contractorsthat those tendering for this particular project will have access to theirown in house version of SFG20 (2012) and subsequently a copy of thisparticular document is not attached.
Asset Register – Mechanical Services North Herts Leisure Centre
Z:\3188\SBR\Asset Register Report\N.H.D.C
Economic Life:
As Appendix C, this the economic life expectancy obtained from CIBSEGuide Volume M (2008) – Indicative Life Expectancy for BuildingServices Plant, Equipment and Systems; and/or that which one wouldnormally expect to be achieved.
Predicted Future Life:
The predicted life is deemed to be the economic life less the number ofyears the item has been in operation or, where this is not known, thefuture anticipated life based upon its present condition, maintenancehistory and general state of repair.
It is acknowledged that although it is possible to keep many items ofmechanical plant operational for periods substantially in excess of theiranticipated life, the repair and maintenance costs of so doing may, aftera certain time, dictate that replacement is a more viable and costeffective option.
2.0 Contractors Examinations, Checks and Tests
It will be the responsibility of the successful Contractor to formulatedetailed inspection schedules and rotas to comply with the generalintention of the examinations, tests and checks stipulated within thisdocument and SFG 20 (2012).
3.0 Exclusions / Clarification
The Contractor’s attention is drawn to the fact that repair, maintenanceand inspection of the following items are expressly excluded from thiscontract:-
Shower thermostatic controls Chlorine alarms Trend heating and lighting control systems PA Systems Intruder Alarms Fire alarms
The testing of water systems in terms of the Control / Prevention ofLegionellae – NHDC will commission these specific works under aseparate contract.
Asset Register – Mechanical Services North Herts Leisure Centre
Z:\3188\SBR\Asset Register Report\N.H.D.C
APPENDIX A
- Asset Register: Conditions Schedule
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 01
Equipment / Plant Ref: Boiler No.1
Model Type: Hoval STP 650
No Off: 1 of 2
Location: Basement Plant Room
Manufacturer: Hoval Farrar LtdNorth Gate,Newark,Notts.NG24 1JN
Tel. No. 01636 672 711
Load/Duty: 518 kW Gas input: 198 kW min / 628 kW max
Voltage: 230V
Phase: 1
Hz / (CPS): 50 Hz
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: C333017 Date of Manufacture: 2004
Condition: 1 2 3 4 5
Comments: Top of casing slightly damaged
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 20 years Predicted Future Life: 11 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 05-23
Comments and Other Relevant Details:
Associated flue economiser – HOVAL TC-AF 400 Thermocondenser (120 litre capacity)
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 02
Equipment / Plant Ref: Burner No.1
Model Type: XGN1000-25 T3D 240 (spec: X60-028A)
No Off: 1 of 2
Location: Basement Plant Room
Manufacturer: Nuway Ltd (ENERTECH)PO Box 1Vines LaneDroitwichWorcesterhshire WR9 8NA
Tel No: 01905 794331
Load/Duty: 430-1090 Kw (nominal heat output)
Voltage: 415V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: 2.0 kW
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: SBO 2020400B/001 Date of Manufacture: 2004
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 12 years Predicted Future Life: 1 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 06-03
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 03
Equipment / Plant Ref: Boiler No.2
Model Type: Hoval STP 650
No Off: 2 of 2
Location: Basement Plant Room
Manufacturer: Hoval Farrar LtdNorth Gate,Newark,Notts.NG24 1JN
Tel. No. 0636 73532
Load/Duty: 518 kW Gas input: 198 kW min / 628 kW max
Voltage: 230V
Phase: 1
Hz / (CPS): 50 Hz
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: C333018 Date of Manufacture: 2004
Condition: 1 2 3 4 5
Comments: Top of casing slightly damaged
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 20 years Predicted Future Life: 11 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 05-23
Comments and Other Relevant Details:
Associated flue economiser – HOVAL TC-AF 400 Thermocondenser (120 litre capacity)
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 04
Equipment / Plant Ref: Burner No.2
Model Type: XGN1000-25 T3D 240 (spec: X60-028A)
No Off: 2 of 2
Location: Basement Plant Room
Manufacturer: Nuway Ltd (ENERTECH)PO Box 1Vines LaneDroitwichWorcesterhshire WR9 8NA
Tel No: 01905 794331
Load/Duty: 430-1090 Kw (nominal heat output)
Voltage: 415V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: 2.0 kW
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: SBO 2020400B/002 Date of Manufacture: 2004
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 12 years Predicted Future Life: 1 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 06-03
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 05
Equipment / Plant Ref: Twin Calorifier
Model Type: F42 Special ( 2 x F41 Modul Plus)
No Off: 1 of 1
Location: Basement Plant Room
Manufacturer: Hoval Farrar LtdNorth Gate,Newark,Notts.NG24 1JN
Tel. No. 01636 672 711
Load/Duty: 6 800 litres/hr @ 395Kw (combined) Capacity: 920 litres (combined)
Voltage: 230V
Phase: 1
Hz / (CPS): 50 Hz
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: could not be ascertained Date of Manufacture: 2004
Condition: 1 2 3 4 5
Comments: Top of casing slightly damaged
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 20 years Predicted Future Life: 9 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 32-09
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 06
Equipment / Plant Ref: HWSR Pump
Model Type: UPS 15-50 B 130
No Off: 1 of 1
Location: Basement Plant Room
Manufacturer: Grundfos Pumps LtdGrovebury RoadLeighton BuzzardBedsLU7 4TL
Tel. No. 01525 850 000
Load/Duty: 1.1l/s (max) & 50kPa (max)
Voltage: 230V
Phase: 1
Hz / (CPS): 50 Hz
HP / KW: 0.105 kW
R P M: 1900
Running Current: 0.42A
Starting Current: N/A
Serial Number: p/n: 96281429 Date of Manufacture: 2004
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 10 years Predicted Future Life: 1 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 45-06
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 07
Equipment / Plant Ref: Heating System Pressurisation Unit
Model Type: PRESSVAL FS 2X425/1.0-225 1R
No Off: 1 of 1
Location: Basement Plant Room
Manufacturer: Hoval Farrar LtdNorth Gate,Newark,Notts.NG24 1JN
Tel. No. 01636 672 711
Load/Duty: N/A
Voltage: 230V
Phase: 1
Hz / (CPS): 50 Hz
HP / KW: N/A
R P M: N/A
Running Current: 2.7A (max)
Starting Current: N/A
Serial Number: HFS 040204 Date of Manufacture: 2004
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 20 years Predicted Future Life: 11 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 45-04
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 08
Equipment / Plant Ref: Heating System Expansion Vessel 1
Model Type: Pressval FS425
No Off: 1 of 2
Location: Basement Plant Room
Manufacturer: Hoval Farrar LtdNorth Gate,Newark,Notts.NG24 1JN
Tel. No. 01636 672 711
Load/Duty: N/A Capacity: 425 litres
Voltage: N/A
Phase: N/A
Hz / (CPS): N/A
HP / KW: N/A
R P M: N/A
Running Current: N/A
Starting Current: N/A
Serial Number: K 64447 Date of Manufacture: 2004
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 6 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 32-12
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 09
Equipment / Plant Ref: Heating System Expansion Vessel 2
Model Type: Pressval FS425
No Off: 2 of 2
Location: Basement Plant Room
Manufacturer: Hoval Farrar LtdNorth Gate,Newark,Notts.NG24 1JN
Tel. No. 01636 672 711
Load/Duty: N/A Capacity: 425 litres
Voltage: N/A
Phase: N/A
Hz / (CPS): N/A
HP / KW: N/A
R P M: N/A
Running Current: N/A
Starting Current: N/A
Serial Number: K 64447 Date of Manufacture: 2004
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 6 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 32-12
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 010
Equipment / Plant Ref: Dirt Separator
Model Type: Spirovent Dirt Hi-Flow DN150
No Off: 1 of 1
Location: Basement Plant Room
Manufacturer: Spirotech UK LtdPO Box 818AltrinchamCheshireWA15 5GZ
T: 0208-451 3344
Load/Duty: N/A
Voltage: N/A
Phase: N/A
Hz / (CPS): N/A
HP / KW: N/A
R P M: N/A
Running Current: N/A
Starting Current: N/A
Serial Number: (g/n) 832894 Date of Manufacture: 2003
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 to 20 years Predicted Future Life: 5 to 10 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: No specific reference – use 40-01
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 011
Equipment / Plant Ref: Sports Hall Heating Pump
Model Type: Redline LX 653
No Off: 1 of 1
Location: Basement Plant Room
Manufacturer: Biral Pumps(Hamworthy Heating Ltd)Fleets CornerPooleDorset BH17 0HH
Tel. No. 01202 662 500
Load/Duty: could not be ascertained
Voltage: 415V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: 0.49 kW
R P M: 1250
Running Current: 0.9 A
Starting Current: N/A
Serial Number: 0402 Date of Manufacture: 2004
Condition: 1 2 3 4 5
Comments: Flanges showing signs of corrosion
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 6 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 45-02
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 012
Equipment / Plant Ref: Pool Hall Heating Pump
Model Type: Redline LX 803
No Off: 1 of 1
Location: Basement Plant Room
Manufacturer: Biral Pumps(Hamworthy Heating Ltd)Fleets CornerPooleDorset BH17 0HH
Tel. No 01202 662 500
Load/Duty: could not be ascertained
Voltage: 415V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: 1.1 kW
R P M: 1300
Running Current: 2.1 A
Starting Current: N/A
Serial Number: 0310 Date of Manufacture: 2004
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 6 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 45-02
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 013
Equipment / Plant Ref: Static Heating Pump
Model Type: UPS 40-120 F
No Off: 1 of 1
Location: Basement Plant Room
Manufacturer: Grundfos Pumps LtdGrovebury RoadLeighton BuzzardBedsLU7 4TL
Tel. No. 01525 850 000
Load/Duty: 5.6 l/s (max) & 90kPa (max)
Voltage: 230V
Phase: 1
Hz / (CPS): 50 Hz
HP / KW: 0.47 kW
R P M: N/A
Running Current: 2.3 A
Starting Current: N/A
Serial Number: (p/n) 96401942 Date of Manufacture: 2004
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 6 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 45-02
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 014
Equipment / Plant Ref: Wet Change Room HTG Pump
Model Type: Redline LX653
No Off: 1 of 1
Location: Basement Plant Room
Manufacturer: Biral Pumps(Hamworthy Heating Ltd)Fleets CornerPooleDorset BH17 0HH
Tel. No 01202 662 500
Load/Duty: could not be ascertained
Voltage: 415V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: 0.49 kW
R P M: 1250
Running Current: 0.9 A
Starting Current: N/A
Serial Number: 9912 Date of Manufacture: 2004
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 6 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 45-02
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 015
Equipment / Plant Ref: Header Pump
Model Type: UPS 15-50
No Off: 1 of 1
Location: Basement Plant Room
Manufacturer: Grundfos Pumps LtdGrovebury RoadLeighton BuzzardBedsLU7 4TL
Tel. No. 01525 850 000
Load/Duty: 1.1 l/s (max) & 50kPa (max)
Voltage: 230V
Phase: 1
Hz / (CPS): 50 Hz
HP / KW: 0.105 kW
R P M: 1900
Running Current: 0.42 A
Starting Current: N/A
Serial Number: U343 Date of Manufacture: 2004
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 10 years Predicted Future Life: 1 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 45-02
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 016
Equipment / Plant Ref: Café Heating Pump
Model Type: NBZ 50-3
No Off: 1 of 1
Location: Basement Plant Room
Manufacturer: Biral Pumps(Hamworthy Heating Ltd)Fleets CornerPooleDorset BH17 0HH
Tel. No. 01202 662 500
Load/Duty: could not be ascertained
Voltage: 230V
Phase: 1
Hz / (CPS): 50 Hz
HP / KW: (could not beascertained)
R P M: 1350
Running Current: 1.5 A
Starting Current: N/A
Serial Number: 860 Date of Manufacture: 2004 (TBC)
Condition: 1 2 3 4 5
Comments: Minor corrosion to pump flanges
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 6 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 45-02
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 017
Equipment / Plant Ref: Lounge Heating Pump
Model Type: NBZ 58-2
No Off: 1 of 1
Location: Basement Plant Room
Manufacturer: Biral Pumps(Hamworthy Heating Ltd)Fleets CornerPooleDorset BH17 0HH
Tel. No. 01202 662 500
Load/Duty: could not be ascertained
Voltage: 230V
Phase: 1
Hz / (CPS): 50 Hz
HP / KW: could not beascertained
R P M: 1350
Running Current: 3.0 A
Starting Current: N/A
Serial Number: 860 Date of Manufacture: 2004 (TBC)
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 6 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 45-02
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 018
Equipment / Plant Ref: Miscellaneous Expansion Vessel
Model Type: DRUKEPANSIEVAT
No Off: 1 of 1
Location: Basement Plant Room
Manufacturer: Flexcon
Load/Duty: N/A Capacity: 20 litre (approx.)
Voltage: N/A
Phase: N/A
Hz / (CPS): N/A
HP / KW: N/A
R P M: N/A
Running Current: N/A
Starting Current: N/A
Serial Number: could not be ascertained Date of Manufacture: 2004 (TBC)
Condition: 1 2 3 4 5
Comments: showing signs of corrosion externally
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 6 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 32-12
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 019
Equipment / Plant Ref: Waste Water Pumps
Model Type: TP40-90/2B A-F-Z-BUBE
No Off: 1 of 1
Location: Basement Plant Room
Manufacturer: Grundfos Pumps LtdGrovebury RoadLeighton BuzzardBedsLU7 4TL
Tel. No. 01525 850 000
Load/Duty: 8.0 m3/hr (max) @ 54 kPa (max)
Voltage: 230V
Phase: 1
Hz / (CPS): 50 Hz
HP / KW: 0.37 kW
R P M: 2830
Running Current: 2.8A
Starting Current: N/A
Serial Number: 96408494-P1-0327 Date of Manufacture: 2004 (TBC)
Condition: 1 2 3 4 5
Comments: Slight leak on 1No. pump head / corrosion to pump and flanges
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 6 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 45-03
Comments and Other Relevant Details:
2No. pumps installed in parallel
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 020 (not accessible)
Equipment / Plant Ref: Sump Pump 1
Model Type: DOMIA Robby 2
No Off: 1 of 2
Location: Basement Plant Room
Manufacturer: Lowara UK LtdMain OfficeMillwey Rise Industrial EstateAxminsterDevonEX13 5HU
Tel. No. 01279 630230
Load/Duty: 8m3/hr @ 2800 RPM
Voltage: 230V
Phase: 1
Hz / (CPS): 50Hz
HP / KW: N/A
R P M: 2800
Running Current: 1.8A
Starting Current: N/A
Serial Number: 86 Date of Manufacture: 2004 (TBC)
Condition: 1 2 3 4 5
Comments: Condition undefined – assumed average condition for age.
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 12 years Predicted Future Life: 3 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 45-07
Comments and Other Relevant Details:
Could not be fully accessed at the time of the survey – information extracted from previous asset register
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 021 (not accessible)
Equipment / Plant Ref: Sump Pump 2
Model Type: AMA Drainer C32 25P
No Off: 2 of 2
Location: Basement Plant Room
Manufacturer: KSB LTDWHARF ROADGRAVESENDKENT, DA12 2RZTEL. NO. 0474 321776
Load/Duty: Could not be ascertained
Voltage: N/A
Phase: N/A
Hz / (CPS): N/A
HP / KW: N/A
R P M: N/A
Running Current: N/A
Starting Current: N/A
Serial Number: 86 Date of Manufacture: 2004 (TBC)
Condition: 1 2 3 4 5
Comments: Condition undefined – assumed average condition for age.
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 12 years Predicted Future Life: 3 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 45-07
Comments and Other Relevant Details:
Could not be fully accessed at the time of the survey – information extracted from previous asset register
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 022
Equipment / Plant Ref: Primary Heating Pump 1
Model Type: Redline LX 504
No Off: 1 of 2
Location: Basement Plant Room
Manufacturer: Biral Pumps(Hamworthy Heating Ltd)Fleets CornerPooleDorset BH17 0HH
Tel. No. 01202 662 500
Load/Duty: could not be ascertained
Voltage: 415 V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: 0.35 kW
R P M: 1350
Running Current: 0.7 A
Starting Current: N/A
Serial Number: 0401 Date of Manufacture: 2004
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 6 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 45-02
Comments and Other Relevant Details:
Inaccessible location above boilers
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 023
Equipment / Plant Ref: Primary Heating Pump 2
Model Type: Redline LX 504
No Off: 2 of 2
Location: Basement Plant Room
Manufacturer: Biral Pumps(Hamworthy Heating Ltd)Fleets CornerPooleDorset BH17 0HH
Tel. No. 01202 662 500
Load/Duty: could not be ascertained
Voltage: 415 V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: 0.35 kW
R P M: 1350
Running Current: 0.7 A
Starting Current: N/A
Serial Number: 0402 Date of Manufacture: 2004
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 6 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 45-02
Comments and Other Relevant Details:
Inaccessible location above boilers
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 024
Equipment / Plant Ref: Pool Heating Pump 1
Model Type: Redline L 503
No Off: 1 of 2
Location: Basement Plant Room
Manufacturer: Biral Pumps(Hamworthy Heating Ltd)Fleets CornerPooleDorset BH17 0HH
Tel. No. 01202 662 500
Load/Duty: could not be ascertained
Voltage: 415 V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: 0.35 kW
R P M: 1350
Running Current: 1.2 A
Starting Current: N/A
Serial Number: 97 Date of Manufacture: 2004
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 6 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 45-02
Comments and Other Relevant Details:
Inaccessible location above pumps
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 025
Equipment / Plant Ref: Pool Heating Pump 2
Model Type: Redline LX 503
No Off: 2 of 2
Location: Basement Plant Room
Manufacturer: Biral Pumps(Hamworthy Heating Ltd)Fleets CornerPooleDorset BH17 0HH
Tel. No. 01202 662 500
Load/Duty: could not be ascertained
Voltage: 415 V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: 0.25 kW
R P M: 1350
Running Current: 0.6 A
Starting Current: N/A
Serial Number: 0702 Date of Manufacture: 2004
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 6 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 45-02
Comments and Other Relevant Details:
Inaccessible location above pumps
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 026
Equipment / Plant Ref: Water Meter
Model Type: PSM Class C
No Off: 1 of 1
Location: Basement Plant Room (CaretakersOffice)
Manufacturer: ABB LimitedHoward RoadEaton SoconSt NeotsCambridgeshire, PE19 8EU
Tel. No. 01480 475321
Load/Duty: N/A
Voltage: N/A
Phase: N/A
Hz / (CPS): N/A
HP / KW: N/A
R P M: N/A
Running Current: N/A
Starting Current: N/A
Serial Number: 00A822218 Date of Manufacture: 2000
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 20 years Predicted Future Life: 7 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: No specific reference – use 40-01
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 027
Equipment / Plant Ref: Air Handling Unit No.1 – Pool Hall Supply
Model Type: XPU20
No Off: 1
Location: Basement Plant
Manufacturer: Reycol SVC LtdDickinson SquareCroxley Green,Rickmansworth,Hertfordshire WD3 3ET
Tel. No. 01923 720900
Load/Duty: 11m³/Sec @ 600 Pa
Voltage: 415 V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: 7.5 kW (x2)
R P M: 1450
Full Load Current: 14.8 A (x2)
Serial Number: P/Code 6150/1 Date of Manufacture: 2004
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 20 years Predicted Future Life: 11 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 03-01
Comments and Other Relevant Details:
Twin Fan Unit
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 028
Equipment / Plant Ref: Air Handling Unit No.1 – Pool Hall Extract
Model Type: XPU20
No Off: 1
Location: Basement Plant
Manufacturer: Reycol SVC LtdDickinson SquareCroxley Green,Rickmansworth,Hertfordshire WD3 3ET
Tel. No. 01923 720900
Load/Duty: 11m³/Sec @ 300 Pa
Voltage: 415 V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: 7.5 kW (x2)
R P M: N A
Full Load Current: 14.8 A (x2)
Serial Number: P/Code 6150/6 Date of Manufacture: 2004
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 20 years Predicted Future Life: 11 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 03-01
Comments and Other Relevant Details:
Twin Fan Unit
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 029
Equipment / Plant Ref: Air Handling Unit No.2 – Café Supply
Model Type: MPU3
No Off: 1 of 1
Location: Basement Plant Room
Manufacturer: Reycol SVC LtdDickinson SquareCroxley Green,Rickmansworth,Hertfordshire WD3 3ET
Tel. No. 01923 720900
Load/Duty: 1.85 m3/s
Voltage: 415V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: 0.48 / 2.4 kW
R P M: 1500/1750
Running Current: 4.9A
Starting Current: N/A
Serial Number: 6150/2 Date of Manufacture: 2004
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 20 years Predicted Future Life: 11 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference:
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 030
Equipment / Plant Ref: Air Handling Unit No.2 – Café Extract
Model Type: MPU3
No Off: 1 of 1
Location: Basement Plant Room
Manufacturer: Reycol SVC LtdDickinson SquareCroxley Green,Rickmansworth,Hertfordshire WD3 3ET
Tel. No. 01923 720900
Load/Duty: 1.0 m3/s
Voltage: 415V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: 0.75 kW
R P M: 1410
Running Current: 1.9A
Starting Current: N/A
Serial Number: 6150/7 Date of Manufacture: 2004
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 20 years Predicted Future Life: 11 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 03-01
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 031
Equipment / Plant Ref: Air Handling Unit No.3 – Lounge Supply
Model Type: MPU3
No Off: 1 of 1
Location: Basement Plant Room
Manufacturer: Reycol SVC LtdDickinson SquareCroxley Green,Rickmansworth,Hertfordshire WD3 3ET
Tel. No. 01923 720900
Load/Duty: 2.3 m3/s
Voltage: 415V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: 2.5 / 3.7 kW
R P M: 1500/1000
Running Current: 6.5 A
Starting Current: N/A
Serial Number: 6150/3 Date of Manufacture: 2004
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 20 years Predicted Future Life: 11 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 03-01
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 032
Equipment / Plant Ref: Air Handling Unit No.3 – Lounge Extract
Model Type: XPU 12
No Off: 1 of 1
Location: Basement Plant Room
Manufacturer: Reycol SVC LtdDickinson SquareCroxley Green,Rickmansworth,Hertfordshire WD3 3ET
Tel. No. 01923 720900
Load/Duty: 1.7 m3/s
Voltage: 415V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: 1.5kW
R P M: 1420
Running Current: 3.5 A
Starting Current: N/A
Serial Number: 6150/8 Date of Manufacture: 2004
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 20 years Predicted Future Life: 11 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 03-01
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 033
Equipment / Plant Ref: Air Handling Unit No.4 – Changing Room Supply
Model Type: XPU 14
No Off: 1 of 1
Location: Basement Plant Room
Manufacturer: Reycol SVC LtdDickinson SquareCroxley Green,Rickmansworth,Hertfordshire WD3 3ET
Tel. No. 01923 720900
Load/Duty: 3.9 m3/s
Voltage: 415V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: 4 kW
R P M: 1440
Running Current: 8.3 A
Starting Current: N/A
Serial Number: 6150/4 Date of Manufacture: 2004
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 20 years Predicted Future Life: 11 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 03-01
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 034
Equipment / Plant Ref: Air Handling Unit No.4 – Changing Room Extract
Model Type: TZR-01-560
No Off: 1 of 1
Location: Basement Plant Room
Manufacturer: Reycol SVC LtdDickinson SquareCroxley Green,Rickmansworth,Hertfordshire WD3 3ET
Tel. No. 01923 720900
Load/Duty: 3.9 m3/s
Voltage: 415V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: 3 kW
R P M: (could not beascertained)
Running Current: 6.4 A
Starting Current: N/A
Serial Number: 6150/9 Date of Manufacture: 2004
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 20 years Predicted Future Life: 11 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 03-01
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 035
Equipment / Plant Ref: Air Handling Unit No.5 – Sauna Supply
Model Type: MPU 13
No Off: 1 of 1
Location: Basement Plant Room
Manufacturer: Reycol SVC LtdDickinson SquareCroxley Green,Rickmansworth,Hertfordshire WD3 3ET
Tel. No. 01923 720900
Load/Duty: 1 m3/s
Voltage: 415V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: 1.1 kW
R P M: (could not beascertained)
Running Current: 2.63A
Starting Current: N/A
Serial Number: 6150/5 Date of Manufacture: 2004
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 20 years Predicted Future Life: 11 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 03-01
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 077
Equipment / Plant Ref: Chiller
Model Type: Compact Ultima
No Off: 1 of 1
Location: Basement Level – External ChillerCompound
Manufacturer: AiredaleLeeds RoadRawdonLeedsLS19 6JY
Tel. No. 0113 239 1000
Load/Duty: Ultima compact range - 30-450kW
Voltage: 415V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: N/A
R P M: N/A
Running Current: N/A
Starting Current: N/A
Serial Number: Could not be ascertained Date of Manufacture: 2004 (TBC)
Condition: 1 2 3 4 5
Comments: Damaged fins – showing signs of corrosion
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 20 years Predicted Future Life: 11 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 09-02
Comments and Other Relevant Details:
Could not ascertain full technical information at time of survey
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 078
Equipment / Plant Ref: First Floor Toilet Fans
Model Type: Could not be ascertained
No Off: 2No.
Location: Kitchen Roof
Manufacturer: Fantech10048 Industrial BlvdLenexa,KS 66215USA
Load/Duty: Could not be ascertained
Voltage: N/A
Phase: N/A
Hz / (CPS): N/A
HP / KW: N/A
R P M: N/A
Running Current: N/A
Starting Current: N/A
Serial Number: (P/N) M01203 Date of Manufacture: 2004 (TBC)
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 6 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 20-04
Comments and Other Relevant Details:
Full technical information could not be ascertained
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 079 Not fully Accessible
Equipment / Plant Ref: Gas Fired Radiant Panels
Model Type: Could not be ascertained
No Off: 4No.
Location: Ground Floor Squash Courts
Manufacturer: Ambirad LtdFens Pool Avenue,Brierley Hill,West MidlandsDY5 1QA UK
Tel. No. 01384 489700
Load/Duty: Could not be ascertained
Voltage: 230 V
Phase: 1
Hz / (CPS): 50Hz
HP / KW: N/A
R P M: N/A
Running Current: N/A
Starting Current: N/A
Serial Number: Could not be ascertained Date of Manufacture: 2004 (TBC)
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 to 20 years Predicted Future Life: 2 to 7 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 28-03
Comments and Other Relevant Details:
Full technical information could not be ascertained at the time of the survey
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 080
Equipment / Plant Ref: Kitchen Extract Fan
Model Type: STRR5-L
No Off: 1 of 1.
Location: Kitchen Roof
Manufacturer: Elta Fans Ltd46 Third Avenue,Pensnett Trading Estate,Kingswinford,West Midlands,DY6 7US
Tel. No. 01384 275 808
Load/Duty:
Voltage: 230 V
Phase: 1
Hz / (CPS): 50 Hz
HP / KW: 0.96 kW
R P M: 1250
Running Current: 4.0 A
Starting Current: 12.6 A
Serial Number: Could not be ascertained Date of Manufacture: 2004 (TBC)
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 6 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 20-03
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 081
Equipment / Plant Ref: Kitchen Extract Hood Fan
Model Type: Could not be ascertained
No Off: 1 of 1
Location: Kitchen Roof
Manufacturer: Matthews and Yates Fans(Systemair)72 Cheston Road,Birmingham,B7 5EJ
Tel. No. 0121 322 0200
Load/Duty: Could not be ascertained
Voltage: N/A
Phase: N/A
Hz / (CPS): N/A
HP / KW: N/A
R P M: N/A
Running Current: N/A
Starting Current: N/A
Serial Number: Could not be ascertained Date of Manufacture: 2004 (TBC)
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 6 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 20-03
Comments and Other Relevant Details:
Full technical details could not be ascertained
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 082
Equipment / Plant Ref: Kitchen Gas Meter
Model Type: N/A
No Off: 1 of 1.
Location: First Floor Kitchen
Manufacturer: Parkinson Cowan MeasurementNow (Electrolux PLC)Preston RoadAycliffe Industrial ParkNewton AycliffeCounty Durham, DL5 6ED
Tel. No. 01325 302464
Load/Duty: N/A
Voltage: N/A
Phase: N/A
Hz / (CPS): N/A
HP / KW: N/A
R P M: N/A
Running Current: N/A
Starting Current: N/A
Serial Number: 012654 Date of Manufacture: 2004 (TBC)
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 20 years Predicted Future Life: 11 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: No specific reference – use 40-01
Comments and Other Relevant Details:
Exposed within kitchen – member of staff concerned re: exposed meter within kitchen
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 083
Equipment / Plant Ref: Sauna Plant Control Panel
Model Type: ST7
No Off: 1 of 1
Location: Ground Floor Sauna Plant Room
Manufacturer: DalesaunaGrimbald Crag CloseSt James Business ParkKnaresboroughNorth YorkshireHG5 8PJ
Tel. No. 01423 798630
Load/Duty: N/A
Voltage: 230 V
Phase: 1
Hz / (CPS): 50Hz
HP / KW: N/A
R P M: N/A
Running Current: N/A
Starting Current: N/A
Serial Number: 017011 Date of Manufacture: 2004 (TBC)
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 20 years Predicted Future Life: 11 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 14-01
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 084
Equipment / Plant Ref: Sauna Steam Generator
Model Type: AT 3000D-1534
No Off: 1 of 1
Location: Ground Floor Sauna Plant Room
Manufacturer: DalesaunaGrimbald Crag CloseSt James Business ParkKnaresboroughNorth Yorkshire, HG5 8PJ
Tel. No. 01423 798630
Load/Duty: 11.4 kW
Voltage: 415V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: 11.4 kW
R P M: N/A
Running Current: 15.9 A
Starting Current: N/A
Serial Number: 0607177 Date of Manufacture: 2004
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 25 years Predicted Future Life: 16 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 33-03
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 085 Not fully Accessible
Equipment / Plant Ref: Sports Hall Extract AHU
Model Type: Could not be ascertained
No Off: 2No.
Location: Ground Floor Sports Hall (HL)
Manufacturer: Elta Fans Ltd46 Third Avenue,Pensnett Trading Estate,Kingswinford,West Midlands,DY6 7US,
Tel. No. 01384 275 808
Load/Duty: Could not be ascertained
Voltage: N/A
Phase: N/A
Hz / (CPS): N/A
HP / KW: N/A
R P M: N/A
Running Current: N/A
Starting Current: N/A
Serial Number: Could not be ascertained Date of Manufacture: 2004 (TBC)
Condition: 1 2 3 4 5
Comments: Condition undefined – assumed average condition for age.
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 20 years Predicted Future Life: 11 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 03-01
Comments and Other Relevant Details:
Could not ascertain full technical information at time of survey – Note: this includes number of fans,ventilation configuration etc
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 086
Equipment / Plant Ref: Fire Ventilator
Model Type: 1m x 1.25m
No Off: 6No.
Location: Sports Hall Roof
Manufacturer: Colt InternationalNew LaneHavantHampshirePO9 2LY
Tel. No. 02392 451111
Load/Duty: N/A
Voltage: N/A
Phase: N/A
Hz / (CPS): N/A
HP / KW: N/A
R P M: N/A
Running Current: N/A
Starting Current: N/A
Serial Number: N/A Date of Manufacture: 1980 (TBC)
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 20 years Predicted Future Life: Expired
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 52-01
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 087 Not fully Accessible
Equipment / Plant Ref: Sports Hall Supply AHU
Model Type: Could not be ascertained
No Off: 2No.
Location: Ground Floor Sports Hall (HL)
Manufacturer: Elta Fans Ltd46 Third Avenue,Pensnett Trading Estate,Kingswinford,West Midlands, DY6 7US,
Tel. No. 01384 275 808
Load/Duty: Could not be ascertained
Voltage: N/A
Phase: N/A
Hz / (CPS): N/A
HP / KW: N/A
R P M: N/A
Running Current: N/A
Starting Current: N/A
Serial Number: Could not be ascertained Date of Manufacture: 2004 (TBC)
Condition: 1 2 3 4 5
Comments: Condition undefined – assumed average condition for age.
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 20 years Predicted Future Life: 11 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 03-01
Comments and Other Relevant Details:
Could not ascertain full technical information at time of survey – Note: this includes number of fans,ventilation configuration etc.
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 088
Equipment / Plant Ref: Wave Machine Fan 1
Model Type: M 225 S 60-4
No Off: 1 of 2
Location: Basement Wave Plant Room
Manufacturer: ASEA
Load/Duty: Could not be ascertained
Voltage: 415V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: 37 kW
R P M: 1460
Running Current: 67A
Starting Current: N/A
Serial Number: MK 223 048-AM Date of Manufacture: 1980 (TBC)
Condition: 1 2 3 4 5
Comments: Signs of corrosion
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 – 20 years Predicted Future Life: Expired
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 20-03
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 089
Equipment / Plant Ref: Wave Machine Fan 2
Model Type: M 225 S 60-4
No Off: 2 of 2
Location: Basement Wave Plant Room
Manufacturer: ASEA
Load/Duty: Could not be ascertained
Voltage: 415V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: 37 kW
R P M: 1460
Running Current: 67A
Starting Current: N/A
Serial Number: MK 223 048-AH Date of Manufacture: 1980 (TBC)
Condition: 1 2 3 4 5
Comments: Signs of corrosion
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 – 20 years Predicted Future Life: Expired
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 20-03
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 090
Equipment / Plant Ref: Wave Machine Compressor
Model Type: 56442-10/6
No Off: 1 of 1
Location: Basement Wave Plant Room
Manufacturer: Hydrovane (Gardner Denver Ltd.)Claybrook DriveWashford Industrial EstateRedditchWorcestershireB98 0DS
Tel. No. 01527 838200
Load/Duty: 10 Bar
Voltage: 415V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: 2.2 kW
R P M: 2850
Running Current: 5.2A
Starting Current: 9.0A
Serial Number: 502-000655 Date of Manufacture: 1998 (TBC)
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 20 years Predicted Future Life: 5 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 40-08
Comments and Other Relevant Details:
100l capacity vessel forms part of compressor package
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 091
Equipment / Plant Ref: Wave Plant Room Control Panel
Model Type: N/A
No Off: 1 of 1
Location: Basement Wave Plant Room
Manufacturer: Metzenauer and Jung
Load/Duty: N/A
Voltage: 415V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: ?
R P M: N/A
Running Current: ?
Starting Current: ?
Serial Number: N/A Date of Manufacture: 1980 (TBC)
Condition: 1 2 3 4 5
Comments: Condition – 2/3
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: Expired
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 14-01
Comments and Other Relevant Details:
100l capacity vessel forms part of compressor package
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 092
Equipment / Plant Ref: Wave Plant Ventilation Fan
Model Type: Ventilator VM-40-10-2
No Off: 1 of 1
Location: Basement Wave Plant Room
Manufacturer: DLK (LUFT KLIMATCHING Gmbh)D 7306DENKENDORFHEERWEG 15POSTFACH 1128
Tel No. 0711 344061
Load/Duty: Could not be ascertained
Voltage: N/A
Phase: N/A
Hz / (CPS): N/A
HP / KW: N/A
R P M: 2770 RPM
Running Current: N/A
Starting Current: N/A
Serial Number: 01845 Date of Manufacture: Could not beascertained
Condition: 1 2 3 4 5
Comments: Condition 2/3
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: Expired
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 20-04
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 37
Equipment / Plant Ref: Ener-G Combined Heat and Power Unit
Model Type: Ener-G 110
No Off: 1
Location: Basement Plant Room
Manufacturer: Ener-G Combined Power LtdEner-G House,Daniel Adamson Road,Manchester.M50 1DT
Tel. No. (0161 745 7450)
Load/Duty: 110 kW (e) Gas input: 28.32 m³/hour184 kW (t)
Voltage: N A
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Reference Number: 1062 Date of Manufacture: 2005
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: Estimated at 15 years Predicted Future Life: Estimated at 7 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: N A
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 38
Equipment / Plant Ref: CHP Primary Pump
Model Type: Grundfos UPS 50-120F Model C
No Off: 1
Location: CHP Unit - Basement Plant Room
Manufacturer: Grundfos Pumps LtdGrovebury Road,Leighton Buzzard,Beds.LU7 4TL
Tel. No. (01525 850 000)
Load/Duty: N A
Voltage: 230-240 V
Phase: 1
Hz / (CPS): 50 Hz
HP / KW: 0.76 kW (Max)
R P M: N A
Running Current: N A
Starting Current: N A
Product Number: 96402101 Date of Manufacture: Undefined(Assumed 2005)
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 7 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 45-02
Comments and Other Relevant Details:
Product Code: 0537
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 39
Equipment / Plant Ref: CHP Fan Unit
Model Type: Elta SC050K4-A10/20/BU
No Off: 1
Location: CHP Unit - Basement Plant Room
Manufacturer: Elta Fans Ltd46 Third Avenue,Pensnett Trading Estate,Kingswinford, West Midlands.DY6 7US
Tel. No. (01384 275 800)
Load/Duty: N A
Voltage: 230 V
Phase: 1
Hz / (CPS): 50 Hz
HP / KW: 0.55 kW
R P M: 1440
Full Load Current: 3.93 A
Serial Number: 158025 Date of Manufacture: Undefined(Assumed 2005)
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 7 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 20-04
Comments and Other Relevant Details:
Elta Fan Reference: 37252Client Reference: 9103396
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 40
Equipment / Plant Ref: Cold Water Booster Set – Control Panel
Model Type: Flow Mech FP-SVH804/60/DA
No Off: 1
Location: Cold Water Booster Set - BasementPlant Room
Manufacturer: Flow Mech Products LtdAbbey House,Charter Street,Leicestershire.LE1 3UD
Tel. No. (0116 242 5425)
Load/Duty: N A
Voltage: N A
Phase: N A
Hz / (CPS): N A
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: 14637 Date of Manufacture: 2004
Condition: 1 2 3 4 5
Comments: Top of casing slightly damaged
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 20 years Predicted Future Life: 11 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 14-
Comments and Other Relevant Details:
Associated Pumps and Expansion Vessel – Refer to AR41 and AR42
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 41
Equipment / Plant Ref: Cold Water Booster Set – Pumps
Model Type: Lowara SVH804R22T
No Off: 2
Location: Cold Water Booster Set - BasementPlant Room
Manufacturer: Lowara UK LtdMillwey Rise Industrial Estate,Axminster,Devon.EX13 5HU
Tel. No. (01297 630 230)
Load/Duty: 6-14 m³/hour at 50-26.5 m head
Voltage: N A
Phase: N A
Hz / (CPS): N A
HP / KW: 2.2 kW
R P M: 2900
Running Current: N A
Starting Current: N A
Serial Number: 2004031600036 – Pump 1Code Number: 102543643 – Pump 2
Date of Manufacture: 2004 – Pump 12012 – Pump 2
Condition: 1 2 3 4 5
Comments: Date Markings on Pump 2 suggests it was replaced in 2012
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 6 years – Pump 114 years – Pump 2
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 45-12
Comments and Other Relevant Details:
Associated Control Panel and Expansion Vessel – Refer to AR40 and AR42
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 42
Equipment / Plant Ref: Cold Water Booster Set – Expansion Vessel
Model Type: Flow Mech Expansion Vessel
No Off: 1
Location: Cold Water Booster Set - BasementPlant Room
Manufacturer: Flow Mech Products LtdAbbey House,Charter Street,Leicestershire.LE1 3UD
Tel. No. (0116 242 5425)
Capacity: 60 litres
Voltage: N A
Phase: N A
Hz / (CPS): N A
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: 14637/03/04 (serial number worn) Date of Manufacture: 2004
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 6 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 32-12
Comments and Other Relevant Details:
Maximum Working Pressure: 10 BarCommissioned Working Pressure: 3.7 BarMembrane Type: E.D.P.M/ButylAssociated Control Panel and Pumps – Refer to AR40 and AR41
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 43
Equipment / Plant Ref: Electronic Water Conditioner
Model Type: Liff Wrappa LW10
No Off: 1
Location: Basement Plant Room – Cold WaterPipework
Manufacturer: Culligan International LtdBay Hall, Miln Road,Huddersfield,West Yorkshire.HD1 5EJ
Tel. No. (01484 512 537)
Load/Duty: 2.5 litres/sec (max) on 76mm dia pipe
Voltage: 230V
Phase: 1
Hz / (CPS): 50 Hz
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Product Number: 05040251 Date of Manufacture: Undefined
Condition: 1 2 3 4 5
Comments: Cabling in poor condition only a few cables are still wrapped around the pipework
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 3-5 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 65-
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 44
Equipment / Plant Ref: Dosing Pot
Model Type: Environmental and Mechanical Services Ltd - Dosing Pot
No Off: 1
Location: Basement Plant Room
Manufacturer: Environmental and MechanicalServices LtdSentinal House,11 High Street, Long BuckbyNorthampton.NN6 7RE
Tel. No. (01327 844 848)
Load/Duty: 5 Litres
Voltage: N A
Phase: N A
Hz / (CPS): N A
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Batch Number: 4785 Date of Manufacture: 2004
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 6 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 65-10
Comments and Other Relevant Details:
UN: 3287
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 45
Equipment / Plant Ref: Chlorine Dosing System
Model Type: Dinotec DSC Compact 2000
No Off: 1
Location: Basement Plant Room
Manufacturer: Dinotec
UK Distributor: Gaffey Technical Services LtdUnit 3, Underbank Way,Haslingden, Rossendale,Lancashire.BB4 5HR
Tel. No. (01706 233 600)
Load/Duty: N A
Voltage: 230 V
Phase: 1
Hz / (CPS): 50 Hz
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: N A Date of Manufacture: Undefined
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 6 years approx.
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 65-
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 46
Equipment / Plant Ref: BMS Control Panel
Model Type: Canham Controls Ltd – BMS Panel
No Off: 1
Location: Basement Plant Room
Manufacturer: Canham Controls Ltd25 Fenlake Business Centre,Fengate,Peterborough.PE1 5BQ
Tel. No. (01733 894 489)
Load/Duty: N A
Voltage: N A
Phase: N A
Hz / (CPS): N A
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: N A Date of Manufacture: Undefined
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 20 years Predicted Future Life: 10 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 14-
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 47
Equipment / Plant Ref: Pump Inverters
Model Type: ABB Pump Inverters
No Off: 3
Location: Basement Plant Room
Manufacturer: ABB LtdDaresbury Park,Daresbury,Warrington.WA4 4BT
Tel. No. (01925 741 111)
Load/Duty: N A
Voltage: N A
Phase: N A
Hz / (CPS): N A
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: N A Date of Manufacture: Undefined
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 20 years Predicted Future Life: 10 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 14-
Comments and Other Relevant Details:
Inverters Control: Circulation Pump No.1 VSDCirculation Pump No.2 VSDCirculation Pump No.3 VSD
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 48
Equipment / Plant Ref: Pool Circulation Pumps No. 1-3
Model Type: 80 WJE 160
No Off: 3
Location: Basement Plant Room
Manufacturer: Ingersoll Dresser LtdChorley New Road,Horwich, Nr Bolton,Lancs.BL6 6JN
Tel. No. (01204 690 690)
Load/Duty: 300 m³/hour @ 16m head (total duty for both pumps)
Voltage: 415 V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: 11 kW
R P M: 2910
Current: 21.5 A
Serial Number: 175489, 175490, 175491 Date of Manufacture: 1997
Condition: 1 2 3 4 5
Comments: Signs of corrosion on pump No. 2
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 1-2 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 45-02
Comments and Other Relevant Details:
Pumps have reached the end of their economic life
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 49
Equipment / Plant Ref: Ultra Violet Unit
Model Type: Hanovia UV Ultra Violet Treatment Unit
No Off: 1
Location: Basement Plant Room
Manufacturer: Hanovia UV780 Buckingham AvenueSloughSL1 4LA
Tel. No. (01753 515 300)
Load/Duty: N A
Voltage: N A
Phase: N A
Hz / (CPS): N A
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: N A Date of Manufacture: Undefined
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years (Whole unit exc. UV Lamp) Predicted Future Life: 6 years approx.
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 65-08
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 50
Equipment / Plant Ref: Swimming Pool Filter Tanks
Model Type: Quartz/Sand Filter Tanks
No Off: 4
Location: Basement Plant Room
Manufacturer: N A
Load/Duty: N A
Voltage: N A
Phase: N A
Hz / (CPS): N A
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: N A Date of Manufacture: 1981
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 20-25 years Predicted Future Life: 5-10 years approx.
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 56-02 and 57-03
Comments and Other Relevant Details:
2mCASING H-2mTOTAL H-3.1mFilter No. 1 and 2 Refurbished 1994Filter No. 3 and 4 Refurbished 1998
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 51
Equipment / Plant Ref: Run-around Coil Dosing Pot
Model Type: Environmental and Mechanical Services Ltd - Dosing Pot
No Off: 1
Location: Run-Around Coil - Basement PlantRoom
Manufacturer: Environmental and MechanicalServices LtdSentinal House,11 High Street, Long BuckbyNorthampton.NN6 7RE
Tel. No. (01327 844 848)
Load/Duty: 25 Litres
Voltage: N A
Phase: N A
Hz / (CPS): N A
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Batch Number: 4874 Date of Manufacture: 2004
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 6 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 65-10
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 52
Equipment / Plant Ref: Run-Around Coil Circulation Pump
Model Type: Biral Redline HX 502
No Off: 1
Location: Run-Around Coil - Basement PlantRoom
Manufacturer: Biral Pumps LtdUK Distributor: Hamworthy Heating Ltd
Fleets Corner,Poole,Dorset.BH17 0HH
Tel. No. (01202 662 500)
Load/Duty: 3.85 litres/sec @ 90 kPa (With 25% Glycol mix)
Voltage: 230 V
Phase: 1
Hz / (CPS): 50 Hz
HP / KW: 0.1028 kW
R P M: N A
Current: 5.3 A
Serial Number: 0401 Date of Manufacture: 2004
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 6 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 45-02
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 53
Equipment / Plant Ref: Run-Around Coil Expansion Vessel
Model Type: N A
No Off: 1
Location: Run-Around Coil - Basement PlantRoom
Manufacturer: N A
Capacity: <10 litres
Voltage: N A
Phase: N A
Hz / (CPS): N A
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: N A Date of Manufacture: 2004 (assumed)
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 6 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 32-12
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 54
Equipment / Plant Ref: Gas Safety Valve
Model Type: AVCDO 6” Free Fall Fire Valve
No Off: 1
Location: Basement Plant Room
Manufacturer: Landon KingswayPatrick Gregory Road,Wolverhampton,West Midlands.WV11 3DZ
Tel. No. (01902 384 238)
Capacity: N A
Voltage: N A
Phase: N A
Hz / (CPS): N A
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: N A Date of Manufacture: 1992
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 20 years Predicted Future Life: 1-2 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 62-04
Comments and Other Relevant Details:
Safety valve has reached the end of its economic lifeTesting Required at 6 month intervals
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 55
Equipment / Plant Ref: Electric Hot Water Heater
Model Type: Redring WS7 Vented Water Heater
No Off: 1
Location: Basement Plant Room
Manufacturer: Redring Xpelair Group LtdNewcombe House,Newcombe Way,Orton Southgate,Peterborough.PE2 6SE
Tel. No. (0844 372 7761)
Capacity: 7 Litres
Voltage: N A
Phase: N A
Hz / (CPS): N A
HP / KW: 1 or 3 kW
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: 25 240831 Date of Manufacture: Undefined
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 10 years Predicted Future Life: 5 years approx.
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 32-
Comments and Other Relevant Details:
Model Number: 44-780001Inlet 0.34-6.8 BarMains Pressure
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 56
Equipment / Plant Ref: Flume Control Panel
Model Type: Edwards Modular Controls Control Panel
No Off: 1
Location: Basement Plant Room
Manufacturer: Edwards Modular Controls Ltd25 Freehold TerraceBrightonEast SussexBN2 4AB
Tel. No. (01273 688 285)
Load/Duty: N A
Voltage: N A
Phase: N A
Hz / (CPS): N A
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: N A Date of Manufacture: Undefined
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 20 years Predicted Future Life: 10 years approx.
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 14-
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 57
Equipment / Plant Ref: Miscellaneous Control Panel 1
Model Type: Pentagon Control System Control Panel
No Off: 1
Location: Basement Plant Room
Manufacturer: Pentagon Control Systems Ltd8 Burnet Road,Norwich,Norfolk.NR3 2BS
Tel. No. (01603 404 828)
Load/Duty: N A
Voltage: N A
Phase: N A
Hz / (CPS): N A
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: N A Date of Manufacture: 2006
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 20 years Predicted Future Life: 13 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 14-
Comments and Other Relevant Details:
Job Number: P16710/1
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 58
Equipment / Plant Ref: Miscellaneous Control Panel 2
Model Type: Pump Interface Panel
No Off: 1
Location: Basement Plant Room
Manufacturer: N A
Load/Duty: N A
Voltage: N A
Phase: N A
Hz / (CPS): N A
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: N A Date of Manufacture: Undefined
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 20 years Predicted Future Life: 10 years approx.
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 14-
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 59
Equipment / Plant Ref: Miscellaneous Control Panel 3
Model Type: Hanovia UV Control Panel
No Off: 1
Location: Basement Plant Room
Manufacturer: Hanovia UV780 Buckingham AvenueSloughSL1 4LA
Tel. No. (01753 515 300)
Load/Duty: N A
Voltage: N A
Phase: N A
Hz / (CPS): N A
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: N A Date of Manufacture: Undefined
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 20 years Predicted Future Life: 10 years approx.
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 14-
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 60
Equipment / Plant Ref: Pump Control Panel
Model Type: N A
No Off: 1
Location: Basement Plant Room
Manufacturer: N A
Load/Duty: N A
Voltage: N A
Phase: N A
Hz / (CPS): N A
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: N A Date of Manufacture: Undefined
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 20 years Predicted Future Life: 5 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 14-
Comments and Other Relevant Details:
Electrical Installation: Danbury MaintenanceHylands32D High StreetLangford, Beds.SG18 9RRTel: 01462 700910
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 61
Equipment / Plant Ref: External Condenser Unit
Model Type: Dakin RYN35CBMD7
No Off: 1
Location: Wall Mounted Near Ground FloorPlantroom
Manufacturer: Dakin Air Conditioning UK LtdThe Heights, Brooklands,Weybridge,Surrey.KT15 0NY
Tel. No. (0845 641 9000)
Load/Duty: N A Electrical input: 1.045kW (cooling) 1.055kW (heating)
Voltage: 230 V
Phase: 1
Hz / (CPS): 50 Hz
HP / KW: N A
R P M: N A
Total Current: 4.9 A
Maximum Current: 14 A
Serial Number: 4601701 Date of Manufacture: 2004
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 6 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 54-02
Comments and Other Relevant Details:
Refrigerant R410A / 1.01kg
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 62
Equipment / Plant Ref: External Condenser Unit – A3 Pembrook
Model Type: Dakin RZQSG100L7Y1B
No Off: 1 of 2
Location: Roof Mounted
Manufacturer: Dakin Air Conditioning UK LtdThe Heights, Brooklands,Weybridge,Surrey.KT15 0NY
Tel. No. (0845 641 9000)
Load/Duty: N A Electrical input: N A
Voltage: 380 – 415 V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: N A
R P M: N A
Total Current: 17.7 A
Maximum Current: 20 A
MFG Number: 3201108 Date of Manufacture: 2012
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 14 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 54-02
Comments and Other Relevant Details:
Refrigerant R410A / 2.9 kg
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 63
Equipment / Plant Ref: External Condenser Unit – A4 Pembrook
Model Type: Dakin RZQSG100L7Y1B
No Off: 2 of 2
Location: Roof Mounted
Manufacturer: Dakin Air Conditioning UK LtdThe Heights, Brooklands,Weybridge,Surrey.KT15 0NY
Tel. No. (0845 641 9000)
Load/Duty: N A Electrical input: N A
Voltage: 380 – 415 V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: N A
R P M: N A
Total Current: 17.7 A
Maximum Current: 20 A
MFG Number: 3201161 Date of Manufacture: 2012
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 14 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 54-02
Comments and Other Relevant Details:
Refrigerant R410A / 2.9 kg
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 64
Equipment / Plant Ref: External Condenser Unit – A5 Gym
Model Type: Dakin RZQSG125L7Y1B
No Off: 1 of 4
Location: Roof Mounted
Manufacturer: Dakin Air Conditioning UK LtdThe Heights, Brooklands,Weybridge,Surrey.KT15 0NY
Tel. No. (0845 641 9000)
Load/Duty: N A Electrical input: N A
Voltage: 380 – 415 V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: N A
R P M: N A
Total Current: 19.2 A
Maximum Current: 20 A
MFG Number: 3201168 Date of Manufacture: 2012
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 14 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 54-02
Comments and Other Relevant Details:
Refrigerant R410A / 2.9 kg
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 65
Equipment / Plant Ref: External Condenser Unit – A6 Gym
Model Type: Dakin RZQSG125L7Y1B
No Off: 2 of 4
Location: Roof Mounted
Manufacturer: Dakin Air Conditioning UK LtdThe Heights, Brooklands,Weybridge,Surrey.KT15 0NY
Tel. No. (0845 641 9000)
Load/Duty: N A Electrical input: N A
Voltage: 380 – 415 V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: N A
R P M: N A
Total Current: 19.2 A
Maximum Current: 20 A
MFG Number: 3201138 Date of Manufacture: 2012
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 14 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 54-02
Comments and Other Relevant Details:
Refrigerant R410A / 2.9 kg
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 66
Equipment / Plant Ref: External Condenser Unit – A7 Gym
Model Type: Dakin RZQSG125L7Y1B
No Off: 3 of 4
Location: Roof Mounted
Manufacturer: Dakin Air Conditioning UK LtdThe Heights, Brooklands,Weybridge,Surrey.KT15 0NY
Tel. No. (0845 641 9000)
Load/Duty: N A Electrical input: N A
Voltage: 380 – 415 V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: N A
R P M: N A
Total Current: 19.2 A
Maximum Current: 20 A
MFG Number: 3201137 Date of Manufacture: 2012
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 14 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 54-02
Comments and Other Relevant Details:
Refrigerant R410A / 2.9 kg
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 67
Equipment / Plant Ref: External Condenser Unit – A8 Gym
Model Type: Dakin RZQSG125L7Y1B
No Off: 4 of 4
Location: Roof Mounted
Manufacturer: Dakin Air Conditioning UK LtdThe Heights, Brooklands,Weybridge,Surrey.KT15 0NY
Tel. No. (0845 641 9000)
Load/Duty: N A Electrical input: N A
Voltage: 380 – 415 V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: N A
R P M: N A
Total Current: 19.2 A
Maximum Current: 20 A
MFG Number: 3201095 Date of Manufacture: 2012
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 14 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 54-02
Comments and Other Relevant Details:
Refrigerant R410A / 2.9 kg
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 68
Equipment / Plant Ref: External Condenser Unit – A9 Foyer
Model Type: Dakin RZQ100B8W1B
No Off: 1
Location: Roof Mounted
Manufacturer: Dakin Air Conditioning UK LtdThe Heights, Brooklands,Weybridge,Surrey.KT15 0NY
Tel. No. (0845 641 9000)
Load/Duty: N A Electrical input: N A
Voltage: 400 V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: N A
R P M: N A
Total Current: 15.3 A
Maximum Current: 20 A
MFG Number: 1601859 Date of Manufacture: 2006
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 8 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 54-02
Comments and Other Relevant Details:
Refrigerant R410A / 4.3 kg
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 69
Equipment / Plant Ref: External Condenser Unit – A10 Dance
Model Type: Dakin RZQSG100L7Y1B
No Off: 1 of 2
Location: Roof Mounted
Manufacturer: Dakin Air Conditioning UK LtdThe Heights, Brooklands,Weybridge,Surrey.KT15 0NY
Tel. No. (0845 641 9000)
Load/Duty: N A Electrical input: N A
Voltage: 380-415 V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: N A
R P M: N A
Total Current: 17.7 A
Maximum Current: 20 A
MFG Number: 3201109 Date of Manufacture: 2012
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 14 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 54-02
Comments and Other Relevant Details:
Refrigerant R410A / 2.9 kg
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 70
Equipment / Plant Ref: External Condenser Unit – A11 Dance
Model Type: Dakin RZQSG125L7Y1B
No Off: 2 of 2
Location: Roof Mounted
Manufacturer: Dakin Air Conditioning UK LtdThe Heights, Brooklands,Weybridge,Surrey.KT15 0NY
Tel. No. (0845 641 9000)
Load/Duty: N A Electrical input: N A
Voltage: 380-415 V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: N A
R P M: N A
Total Current: 19.2 A
Maximum Current: 20 A
MFG Number: 3201121 Date of Manufacture: 2012
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 14 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 54-02
Comments and Other Relevant Details:
Refrigerant R410A / 2.9 kg
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 71
Equipment / Plant Ref: External Condenser Unit
Model Type: Dakin RZQ100B8W1B
No Off: 1
Location: Roof Mounted
Manufacturer: Dakin Air Conditioning UK LtdThe Heights, Brooklands,Weybridge,Surrey.KT15 0NY
Tel. No. (0845 641 9000)
Load/Duty: N A Electrical input: N A
Voltage: 400 V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: N A
R P M: N A
Total Current: 15.3 A
Maximum Current: 20 A
MFG Number: 1601862 Date of Manufacture: 2006
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 8 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 54-02
Comments and Other Relevant Details:
Refrigerant R410A / 4.3 kg
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 72
Equipment / Plant Ref: External Condenser Unit
Model Type: Dakin RZQ100B8W1B
No Off: 1
Location: Roof Mounted
Manufacturer: Dakin Air Conditioning UK LtdThe Heights, Brooklands,Weybridge,Surrey.KT15 0NY
Tel. No. (0845 641 9000)
Load/Duty: N A Electrical input: N A
Voltage: 400 V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: N A
R P M: N A
Total Current: 15.3 A
Maximum Current: 20 A
MFG Number: 1601863 Date of Manufacture: 2006
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 8 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 54-02
Comments and Other Relevant Details:
Refrigerant R410A / 4.3 kg
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 73
Equipment / Plant Ref: External Condenser Unit – A1 Weights
Model Type: Dakin RZQ100B8W1B
No Off: 1 of 2
Location: Roof Mounted
Manufacturer: Dakin Air Conditioning UK LtdThe Heights, Brooklands,Weybridge,Surrey.KT15 0NY
Tel. No. (0845 641 9000)
Load/Duty: N A Electrical input: N A
Voltage: 400 V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: N A
R P M: N A
Total Current: 15.3 A
Maximum Current: 20 A
MFG Number: 1602056 Date of Manufacture: 2006
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 8 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 54-02
Comments and Other Relevant Details:
Refrigerant R410A / 4.3 kg
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 74
Equipment / Plant Ref: External Condenser Unit – A2 Weights
Model Type: Dakin RZQSG125L7Y1B
No Off: 2 of 2
Location: Roof Mounted
Manufacturer: Dakin Air Conditioning UK LtdThe Heights, Brooklands,Weybridge,Surrey.KT15 0NY
Tel. No. (0845 641 9000)
Load/Duty: N A Electrical input: N A
Voltage: 380-415 V
Phase: 3
Hz / (CPS): 50 Hz
HP / KW: N A
R P M: N A
Total Current: 19.2 A
Maximum Current: 20 A
MFG Number: 3201131 Date of Manufacture: 2012
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 14 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 54-02
Comments and Other Relevant Details:
Refrigerant R410A / 2.9 kg
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 75
Equipment / Plant Ref: Roof Mounted Fan – Squash Court Roof
Model Type: Elta
No Off: 6
Location: Roof Mounted
Manufacturer: Elta Fans Ltd46 Third Avenue,Pensnett Trading Estate,Kingswinford,West Midlands.DY6 7US
Tel. No. (01384 275 808)
Load/Duty: N A Electrical input: N A
Voltage: N A
Phase: N A
Hz / (CPS): N A
HP / KW: N A
R P M: N A
Total Current: N A
Maximum Current: N A
MFG Number: N A Date of Manufacture: N A
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 5 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 20-04
Comments and Other Relevant Details:
We were informed at the time of the survey that 2No. fans are no longer in use
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 76
Equipment / Plant Ref: Inline Extract Fan
Model Type: Euro Series
No Off: 1
Location: Roof Void
Manufacturer: Ziehl-AbeggUK Distributor: Roof Units Group
Peartree House,Peartree Lane, Dudley,West Midlands.DY2 0QU
Tel. No. (01384 418 600)
Load/Duty: N A Electrical input: N A
Voltage: 230/400 V
Phase: 1/3
Hz / (CPS): N A
HP / KW: 0.40 kW
R P M: 1380
Current: 1.36/0.78 A
Serial Number: N A Date of Manufacture: N A
Condition: 1 2 3 4 5
Comments:
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: 15 years Predicted Future Life: 5 years
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: 20-04
Comments and Other Relevant Details:
Additional Reference Codes: 104127, Z260822, FC045-4DF.4C.3
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 093
Equipment / Plant Ref: Sodium Hypochlorite Dosing Set
Model Type: N A
No Off: 1
Location: Plant Room
Manufacturer: N A
Load/Duty: N A
Voltage: 230 V
Phase: 1
Hz / (CPS): 50 Hz
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: N A Date of Manufacture: N A
Condition: 1 2 3 4 5
Comments: Condition 2/3
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: ? Predicted Future Life: ?
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: N A
Comments and Other Relevant Details:
Asset Register: Mechanical Services
Project: North Herts Leisure Centre
Date: May 2013
Ref: A R 094
Equipment / Plant Ref: Hydrochloric Acid Dosing Set
Model Type: N A
No Off: 1
Location: Plant Room
Manufacturer: N A
Load/Duty: N A
Voltage: 230 V
Phase: 1
Hz / (CPS): 50 Hz
HP / KW: N A
R P M: N A
Running Current: N A
Starting Current: N A
Serial Number: N A Date of Manufacture: N A
Condition: 1 2 3 4 5
Comments: Condition 2/3
Note: Enlarged bold figure denotes assessed condition.
5 = As new (Excellent Condition)4 = Good Condition for Age3 = Average Condition for Age2 = Poor Condition for Age, but still serviceable1 = In Need of Replacement.
Economic Life: ? Predicted Future Life: ?
B & S E (HVCA) SFG 20 (2012)Maintenance Schedule Reference: N A
Comments and Other Relevant Details:
Asset Register – Mechanical Services North Herts Leisure Centre
Z:\3188\SBR\Asset Register Report\N.H.D.C
APPENDIX B
- Summary Asset Register
Summary Asset Register: Mechanical Services
Project: Letchworth Leisure Centre
Date: May 2013
Ref:
Eq
uip
me
nt
/
Pla
nt
Re
f:
Lo
ca
tio
n
Mo
de
lT
yp
e
No
.O
ff.
Ma
nu
fac
ture
r
Lo
ad
/D
uty
Ele
ctr
ica
l
Su
pp
ly
Se
ria
lN
o.
Da
teo
f
Ma
nu
fac
ture
Co
nd
itio
n*
Ec
on
om
icL
ife
(Ye
ars
)
Pre
dic
ate
d
Fu
ture
Lif
e
(Ye
ars
)
Ma
inte
na
nc
e
Sc
he
du
leR
ef
Comments
A R 01 Boiler No 1Basement PlantRoom
Hoval STP 650 1 of 2 Hoval Farrar Ltd 518kW 230V C333017 2004 3 20 11 05-23
A R 02 Burner No 1Basement PlantRoom
XGN1000-25 T3D 240 1 of 2 Nuway Ltd (Enertech) 430-1090kW 415VSBO2020400B/001
2004 3 12 1 06-03
A R 03 Boiler No 2Basement PlantRoom
Hoval STP 650 2 of 2 Hoval Farrar Ltd 518kW 230V C333018 2004 3 05-23
A R 04 Burner No 2Basement PlantRoom
XGN1000-25 T3D 240(spec X60-028A)
2 of 2 Nuway Ltd (Enertech) 430-1090kW 415VSBO2020400B/002
2004 3 12 1 06-03
A R 05 Twin CalorifierBasement PlantRoom
F42 Special (2xF41Modul Plus)
1 of 1 Hoval Farrar Ltd
6 800 ltr/hr @395kW(combined) -Capacity920ltrs(combined)
230VCould not beascertainedduring survey
2004 3 20 9 32-09
A R 06 HWSR PumpBasement PlantRoom
UPS 15-50 B 130 1 of 1 Grundfos Pumps1.1l/s &50kPa (max)
230V P/N 96281429 2004 3 10 1 45-06
A R 07Heating System PressurisationUnit
Basement PlantRoom
PRESSVAL FS2X425/1.05-225 1R
1 of 1 Hoval Farrar Ltd N/A 230V HFS 040204 2004 3 20 11 45-04
A R 08Heating System ExpansionVessel 1
Basement PlantRoom
PRESSVAL FS425 1 of 2 Hoval Farrar Ltd 425ltr cap. N/A K 64447 2004 4 15 6 32-12
A R 09Heating System ExpansionVessel 2
Basement PlantRoom
PRESSVAL FS425 2 of 2 Hoval Farrar Ltd 425ltr cap. N/A K 64447 2004 4 15 6 32-12
A R 10 Dirt SeparatorBasement PlantRoom
Spirovent Dirt Hi-FlowDN150
1 of 1 Spirotech UK Ltd N/A N/A G/N 832894 2003 3 15 to 20 5 to 10 40-01
A R 11 Sports Hall Heating PumpBasement PlantRoom
Redline LX 653 1 of 1 BIRAL PumpsCould not beascertained
415V 0 402 2004 2 15 6 45-02
A R 12 Pool Hall Heating PumpBasement PlantRoom
Redline LX 803 1 of 1 BIRAL PumpsCould not beascertained
415V 0 310 2004 3 15 6 45-02
A R 13 Static Heating PumpBasement PlantRoom
Grundfos UPS 40-120 F 1 of 1 Grundfos Pumps5.6l/s (max) &90kPa (max)
230V P/N 96401942 2004 4 15 6 45-02
A R 14 Wet Change Room Htg PumpBasement PlantRoom
Redline LX653 1 of 1 BIRAL PumpsCould not beascertained
415V 9912 2004 3 15 6 45-02
A R 15 Header PumpBasement PlantRoom
UPS 15-50 1 of 1 Grundfos Pumps1.1l/s (max) &50kPa (max)
230V U343 2004 3 10 1 45-02
A R 16 Café Heating PumpBasement PlantRoom
NBZ 50-3 1 of 1 BIRAL PumpsCould not beascertained
230V 860 2004 3 15 6 45-02
A R 17 Lounge Heating PimpBasement PlantRoom
NBZ 58-2 1 of 1 BIRAL PumpsCould not beascertained
230V 860 2004 3 15 6 45-02
A R 18 Misc. Expansion VesselBasement PlantRoom
DRUKEPANSIEVAT 1 of 1 Flexcon20ltr cap.approx
N/ACould not beascertainedduring survey
2004 2 15 6 32-12
A R 19 Waste Water PumpsBasement PlantRoom
TP40-90/2B A-F-Z-BUBE
1 of 1 Grundfos Pumps8.0m3/hr @54kPa (max)
230V96408494-P1-0327
2004 2 15 6 45-032no. Pumpsinstalled parallel
* Condition Legend:
5 = As New (Excellent Condition) / 4 = Good Condition for Age / 3 = Average Condition for Age / 2 = Poor Condition for Age, but still servicable / 1 = In Need of Replacement
Summary Asset Register: Mechanical Services
Project: Letchworth Leisure Centre
Date: May 2013
A R 20 Sump PumpBasement PlantRoom
DOMIA ROBBY 2 1 of 2 Lowara UK Ltd8m3/hr @2800 rpm
230V 86 2004 (TBC) 3 12 3 45-07
Could not beFully accessedat time ofsurvey -informationextracted fromprevious assetregister
A R 21 Sump PumpBasement PlantRoom
AMA Drainer C32 25P 2 of 2 KSB LtdCould not beascertained
N/A 86 2004 (TBC) 3 12 3 45-07
Could not beFully accessedat time ofsurvey -informationextracted fromprevious assetregister
A R 022 Primary Heating PumpBasement PlantRoom
Redline LX 504 1 of 2 BIRAL PumpsCould not beascertained
415V 0 401 2004 3 15 6 45-02
A R 023 Primary Heating Pump 2Basement PlantRoom
Redline LX 504 2 of 2 BIRAL PumpsCould not beascertained
415V 0 402 2004 3 15 6 45-02
A R 024 Pool Heating PumpBasement PlantRoom
Redline LX 503 1 of 2 BIRAL PumpsCould not beascertained
415V 97 2004 3 15 6 45-02Inaccessiblelocation abovepumps
A R 025 Pool Heating Pump 2Basement PlantRoom
Redline LX 503 2 of 2 BIRAL PumpsCould not beascertained
415V 0702 2004 3 15 6 45-02Inaccessiblelocation abovepumps
A R 026 Water Meter
Basement PlantRoom(CaretakersOffice)
PSM Class C 1 of 1 ABB Ltd N/A N/A 00A822218 2000 3 20 7 40-01
A R 027Air Handling Unit No1 Pool HallSupply
Basement PlantRoom
XPU20 1 of 1 REYCOL SVC Ltd11m3/sec @600Pa
415V P/Code 6150/1 2004 3 20 11 03-01 Twin Fan Unit
A R 028Air Handling Unit No 1 - PoolHall Extract
Basement PlantRoom
XPU20 1 of 1 REYCOL SVC Ltd11m3/sec @300Pa
415V P/Code 6150/6 2004 3 20 11 03-01 Twin Fan Unit
A R 029Air Handling Unit No.2 CaféSupply
Basement PlantRoom
MPU3 1 of 1 REYCOL SVC Ltd 1.85m3/s 415V 6150/2 2004 3 20 11 03-01
A R 030Air Handling Unit No.2 CaféExtract
Basement PlantRoom
MPU3 1 of 1 REYCOL SVC Ltd 1.0m3/s 415V 6150/7 2004 3 20 11 03-01
A R 031Air Handling Unit No.3 LoungeSupply
Basement PlantRoom
MPU3 1 of 1 REYCOL SVC Ltd 2.3m3/s 415V 6150/3 2004 3 20 11 03-01
A R 032Air Handling Unit No.3 LoungeExtract
Basement PlantRoom
XPU 12 1 of 1 REYCOL SVC Ltd 1.7m3/s 415V 6150/8 2004 3 20 11 03-01
A R 033Air Handling Unit No.4Changing Room Supply
Basement PlantRoom
XPU 14 1 of 1 REYCOL SVC Ltd 3.9m3/s 415V 6150/4 2004 3 20 11 03-01
A R 034Air Handling Unit No.4Changing Room Extract
Basement PlantRoom
TZR-01-560 1 of 1 REYCOL SVC Ltd 3.9m3/s 415V 6150/9 2004 3 20 11 03-01
A R 035Air Handling Unit No.5 SaunaSupply
Basement PlantRoom
MPU13 1 of 1 REYCOL SVC Ltd 1m3/s 415V 6150/5 2004 3 20 11 03-01
A R 077 ChillerBasement LevelExternal ChillerCompound
Compact Ultima 1 of 1 Airedale30-450kW (inrange)
415VCould not beascertainedduring survey
2004 (TBC) 2 20 11 09-02
Could notascertaintechnicalinformation attime of survey
A R 078 1st Floor Toilet Fans Kitchen RoofCould not beascertained
2No. FantechCould not beascertained
N/A P/N M01203 2004 (TBC) 3 15 6 20-04Full technicaldetails Couldnot be obtained
* Condition Legend:
5 = As New (Excellent Condition) / 4 = Good Condition for Age / 3 = Average Condition for Age / 2 = Poor Condition for Age, but still servicable / 1 = In Need of Replacement
Summary Asset Register: Mechanical Services
Project: Letchworth Leisure Centre
Date: May 2013
A R 079 Gas Fired Radiant PanelsGF SquashCourts
Could not beascertained
4No AMBIRADCould not beascertained
230VCould not beascertainedduring survey
2004 (TBC) 3 15 to 20 2 to 7 28-03Full technicaldetails Couldnot be obtained
A R 080 Kitchen Extract Fan Kitchen Roof STRR5-L 1 of 1 Elta Fans LtdCould not beascertained
230VCould not beascertainedduring survey
2004 3 15 6 20-03
A R 081 Kitchen Extract Hood Fan Kitchen RoofCould not beascertained
1 of 1Matthews & YatesFans
Could not beascertained
N/ACould not beascertainedduring survey
2004 (TBC) 3 15 6 20-03Full technicaldetails Couldnot be obtained
A R 082 Kitchen Gas Meter 1st Floor Kitchen N/A 1 of 1Parkinson CowanMeasurement
N/A N/A 012654 2004 2
20 11 40-01
Exposed meterwithin kitchen
A R 083 Sauna Plant Control PanelGF Sauna PlantRoom
ST7 1 of 1 Dalesauna N/A 230V 17011 2004 320 11 14-01
A R 084 Sauna Steam GeneratorGF Sauna PlantRoom
AT 3000D-1534 1 of 1 Dalesauna 11.4 kW 415V 0 607177 2004 425 16 33-03
A R 085 Sports Hall Extract AHUGF Sports Hall(HL)
Could not beascertained
2No. Elta Fans LtdCould not beascertained
N/ACould not beascertained
2004 (TBC) 3 20 11 03-01
Could notascertaintechnicalinformation attime of survey -Note: thisincludesnumber of fans,ventilationconfigurationetc.
A R 086 Sports Hall Fire Ventilation Sports Hall Roof 1m x 1.25m 6No. Colt International N/A N/A N/A 1980 3 20 Expired 52-01
A R 087 Sports Hall Supply AHUGF Sports Hall(HL)
Could not beascertained
2No. Elta Fans LtdCould not beascertained
N/ACould not beascertained
2004 (TBC) 3 20 11 03-01
Could notascertaintechnicalinformation attime of survey -Note: thisincludesnumber of fans,ventilationconfigurationetc.
A R 088 Wave Machine Fan 1Basement WavePlant Room
M 225 S 60-4 1 of 2 ASEACould not beascertained
415VMK 223 048-AM
1980 2 15 to 20 Expired 20-03
A R 089 Wave Machine Fan 2Basement WavePlant Room
M 225 S 60-4 2 of 2 ASEACould not beascertained
415V MK 223 048-AH 1980 2 15 to 20 Expired 20-03
A R 090 Wave Machine CompressorBasement WavePlant Room
56442-10/6 1 of 1Hydrovane (GardnerDenver Ltd)
10 bar 415V 502-000655 1998 3 20 5 40-08
100ltr capacityvessel formspart forcompressorpackage
A R 091Wave Plant Room ControlPanel
Basement WavePlant Room
N/A 1 of 1 Metzenauer & Jung N/A 415V N/A 1980 2 15 Expired 14-01
100ltr capacityvessel formspart forcompressorpackage
* Condition Legend:
5 = As New (Excellent Condition) / 4 = Good Condition for Age / 3 = Average Condition for Age / 2 = Poor Condition for Age, but still servicable / 1 = In Need of Replacement
Summary Asset Register: Mechanical Services
Project: Letchworth Leisure Centre
Date: May 2013
A R 092 Wave Plant Ventilation FanBasement WavePlant Room
Ventilator VM-40-10-2 1 of 1DLK (LUFTKLIMATCHINGGmbh)
Could not beascertained
N/A 01845Could not beascertained
2/3 15 Expired 20-04
* Condition Legend:
5 = As New (Excellent Condition) / 4 = Good Condition for Age / 3 = Average Condition for Age / 2 = Poor Condition for Age, but still servicable / 1 = In Need of Replacement
Summary Asset Register: Mechanical Services
Project: Letchworth Leisure Centre
Date: April 2013
Re
f:
Eq
uip
me
nt
/
Pla
nt
Re
f:
Lo
ca
tio
n
Mo
de
lT
yp
e
No
.O
ff.
Ma
nu
fac
ture
r
Lo
ad
/D
uty
Ele
ctr
ica
l
Su
pp
ly
Se
ria
lN
o.
Da
teo
f
Ma
nu
fac
ture
Co
nd
itio
n*
Ec
on
om
icL
ife
(Ye
ars
)
Pre
dic
ate
d
Fu
ture
Lif
e
(Ye
ars
)
Ma
inte
na
nc
e
Sc
he
du
leR
ef
Comments
A R 37Ener-G Combined Heat &Power Unit
Basement PlantRoom
Ener-G 110 1 of 1Ener-G CombinedPower Ltd
110kW e184kW(t) GasInput
28.32m3/hr
N/A 1062 2005 4 15 7 N/A
A R 38 CHP Primary PumpCHP Unit -Basement PlantRoom
Grundfos UPS 50-120FModel C
1 of 1 Grundfos Pumps N/A 230-240V 96402101 2005 3 15 7 45-02Product Code0537
A R 39 CHP Fan UnitCHP Unit -Basement PlantRoom
Elta SC050K4-A10/20/BU
1 of 1 Elta Fans Ltd N/A 230V 158025 2005 3 15 7 20-04Elta Fan Ref:37252 ClientRef: 9103396
A R 40Cold Water Booster Set -Control Panel
Cold WaterBooster Set -Basement PlantRoom
Flow Mech FP-SVH804/60/DA
1 of 1Flow Mech ProductsLtd
N/A N/A 14637 2004 3 20 11 14-
AssociatedPumps &ExpansionVessel ref toAR41 & AR42
A R 41Cold Water Booster Set -Pumps
Cold WaterBooster Set -Basement PlantRoom
Lowara SVH804R22T 2 Lowara UK Ltd6-14m3/hr at50-26.5mhead
N/A
Pump 1 -2004031600036 Pump 2 -102543643
2004 pump1 2012pump 2
3 156 yr pump 1 14
yr pump 245-12
AssociatedControl Paneland ExpansionVessel Refer toAR40 & AR42
A R 42Cold Water Booster Set -Expansion Vessel
Cold WaterBooster Set -Basement PlantRoom
Flow Mech ExpansionVessel
1 of 1 Flow Mech Products Ltd60 litres N/A 14637/03/04? 2004 3 15 6 32-12
Max WorkingPressure 10 BarCommissionedWorkingPressure 3.7bar MembraneType E.D.PM/ButylAssociatedControl PanelPumps Refer toAR40 & AR41
A R 43 Electronic Water Conditioner
Cold WaterPipework -Basement PlantRoom
Liff Wrappa LW10 1 of 1Culligan InternationalLtd
2.5ltrs/sec(max) on76mm diapipe
230V 05040251 undefined 2 15 3 to 5 65-
A R 44 Dosing PotBasement PlantRoom
Enviromental & MechDosing Pot
1 of 1Enviromental &Mechanical ServicesLtd
5 litres N/A 4785 2004 2 15 6 65-10 UN: 3287
A R 45 Chlorine Dosing SystemBasement PlantRoom
Dinotec DSC Compact2000
1 of 1 Dinotec N/A 230V N/A undefined 3 15 6 65-
A R 46 BMS Control PanelBasement PlantRoom
Canham Controls Ltd -BMS Panel
3 Canham Controls N/A N/A N/A undefined 4 20 10 14-
A R 47 Pump InvertersBasement PlantRoom
ABB Pump Inverters 1 of 1 ABB Ltd N/A N/A N/A undefined 4 20 10 14-
Pump No 1VSD Pump No2 VSD PumpNo 3 VSD
* Condition Legend:
5 = As New (Excellent Condition) / 4 = Good Condition for Age / 3 = Average Condition for Age / 2 = Poor Condition for Age, but still servicable / 1 = In Need of Replacement
Summary Asset Register: Mechanical Services
Project: Letchworth Leisure Centre
Date: April 2013
A R 48 Pool Circulation PumpsBasement PlantRoom
80 WJE 160 3 off Ingersoll Dresser Ltd
300m3/hr @16m head(total duty forboth pumps
415V175489,175490,175491
1997 3 15 1 to 2 45-02
Pumps havereached the endof theireconomic life
A R 49 Ultra Violet UnitBasement PlantRoom
Hanovia UV UltraTreatment Unit
1 of 1 Hanovia UV N/A N/A N/A Undefined 315 (wholeunit exc.
UV Lamp)6 65-08
A R 50 Swimming Pool Filter TanksBasement PlantRoom
Quartz/Sand Filter Tanks 4 off N/A N/A N/A N/A 1981 3 20 to 25 5 to 1056-02 and 57-
03
Casing H-2MTotal H-3.1mFilter No1 & 2refurb 1994Filter No3 refurb1998
A R 51 Run-around Coil Dosing PotBasement PlantRoom
Enviromental & MechDosing Pot
1 of 1Enviromental &Mechanical ServicesLtd
25 litres N/A 4874 2004 3 15 6 65-10
A R 52Run-around Coil CirculationPump
Basement PlantRoom
Biral Redline HX 502 1 of 1 Biral Pumps Ltd
3.85ltrs/sec@ 90kPa(with 25%Glycol mix)
230V 0401 2004 3 15 6 45-02
A R 53Run-around Coil ExpansionVessel
Basement PlantRoom
N/A 1 of 1 N/A <10 litres N/A N/A 2004 3 15 6 32-12
A R 54 Gas Safety ValveBasement PlantRoom
AVCDO 6" Free Fall FireValve
1 of1 Landon Kingsway N/A N/A N/A 1992 1 20 1 to 2 62-04
Safety valvehas reached theend of itseconomic life.Testing requiredat 6 monthintervals
A R 55 Electric Hot Water HeaterBasement PlantRoom
Redring WS7 VentedWater Heater
1 of 1Redring XpelairGroup Ltd
7 ltires N/A 25 240831 undefined 3 10 5 32-
Model No 44-780001Inlet 0.34-6.8BarMains Pressure
A R 56 Flume Control PanelBasement PlantRoom
Edwards ModularControls Panel
1 of 1Edwards ModularControls Ltd
N/A N/A N/A undefined 2 20 10 14-
A R 57 Misc. Control Panel 1Basement PlantRoom
Pentagon ControlSystem Control Panel
1 of 1Pentagon ControlSystems Ltd
N/A N/A N/A 2006 3 20 13 14-Job NoP16710/1
A R 58 Misc. Control Panel 2Basement PlantRoom
Pump Interface Panel 1 of 1 N/A N/A N/A N/A undefined 3 20 10 14-
A R 59 Misc. Control Panel 3Basement PlantRoom
Hanovia UV ControlPanel
1 of 1 Hanovia UV N/A N/A N/A undefined 3 20 10 14-
A R 60 Pump Control PanelBasement PlantRoom
N/A 1 of 1 N/A N/A N/A N/A Undefined 3 20 5 14-Elec Install:Danbury Maint
A R 61 External Condenser UnitWall mountednear GF PlantRoom
Dakin RYN35CBMD7 1 of 1Dakin AirConditioning UK
N/A N/A 4601701 2004 3 15 6 54-02RefrigerantR410A/1.01kg
A R 62External Condenser Unit - A3Pembrook
Roof Mounted Dakin RZQSG100L7Y1B 1 of 2Dakin AirConditioning UK
N/A 380-415V 3201108 2012 3 15 14 54-02RefrigerantR410A/2.9kg
A R 63External Condenser Unit - A4Pembrook
Roof Mounted Dakin RZQSG100L7Y1B 1 of 1Dakin AirConditioning UK
N/A 380-415V 3201161 2012 3 15 14 54-02RefrigerantR410A/2.9kg
A R 64External Condenser Unit - A5Gym
Roof Mounted Dakin RZQSG125L7Y1B 1 of 4Dakin AirConditioning UK
N/A 380-415V 3201168 2012 3 15 14 54-02RefrigerantR410A/2.9kg
A R 65External Condenser Unit - A6Gym
Roof Mounted Dakin RZQSG125L7Y1B 2 of 4Dakin AirConditioning UK
N/A 380-415V 3201138 2012 3 15 14 54-02RefrigerantR410A/2.9kg
* Condition Legend:
5 = As New (Excellent Condition) / 4 = Good Condition for Age / 3 = Average Condition for Age / 2 = Poor Condition for Age, but still servicable / 1 = In Need of Replacement
Summary Asset Register: Mechanical Services
Project: Letchworth Leisure Centre
Date: April 2013
A R 66External Condenser Unit - A7Gym
Roof Mounted Dakin RZQSG125L7Y1B 3 of 4Dakin AirConditioning UK
N/A 380-415V 3201137 2012 3 15 14 54-02RefrigerantR410A/2.9kg
A R 67External Condenser Unit - A8Gym
Roof Mounted Dakin RZQSG125L7Y1B 4 of 4Dakin AirConditioning UK
N/A 380-415V 3201095 2012 3 15 14 54-02RefrigerantR410A/2.9kg
A R 68External Condenser Unit - A9Foyer
Roof Mounted Dakin RZQ100B8W1B 1 offDakin AirConditioning UK
N/A 400V 1601859 2006 3 15 8 54-02RefrigerantR410A/4.3kg
A R 69External Condenser Unit - A10Dance
Roof MountedDakingRZQSG100L7Y1B
1 of 2Dakin AirConditioning UK
N/A 380-415V 3201109 2012 3 15 14 54-02RefrigerantR410A/2.9kg
A R 70External Condenser Unit - A11Dance
Roof MountedDakingRZQSG125L7Y1B
2 of 2Dakin AirConditioning UK
N/A 380-415V 3201121 2012 3 15 14 54-02RefrigerantR410A/2.9kg
A R 71 External Condenser Unit Roof Mounted Daking RZQ100B8W1B 1 offDaking AirConditioning UK
N/A 400V 1601862 2006 3 15 8 54-02RefrigerantR410A/4.3kg
A R 72 External Condenser Unit Roof Mounted Daking RZQ100B8W1B 1 offDaking AirConditioning UK
N/A 400V 1601863 2006 3 15 8 54-02RefrigerantR410A/4.3kg
A R 73External Condenser Unit - A1Weights
Roof Mounted Daking RZQ100BW1B 1 of 2Daking AirConditioning UK
N/A 400V 1602056 2006 3 15 8 54-02RefrigerantR410A/4.3kg
A R 74External Condenser Unit - A2Weights
Roof MountedDakingRZQSG125L7Y1B
2 of 2Daking AirConditioning UK
N/A 380-415V 3201131 2012 3 15 14 54-02RefrigerantR410A/2.9kg
A R 75Roof Mounted Fan - SquashCourt Roof
Roof Mounted Elta 6 off Elta Fans Ltd N/A N/A N/A N/A 2 15 5 20-04
Time of surveyinformed 2no.Fans are nolonger in use
A R 76 Inline Extract Fan Roof Void Euro Series 1 of 1 Ziehl-Abegg N/A 230/400V N/A N/A 2 15 5 20-04
Additional refcodes 104127,Z260822,FC045-4DF.4C.3
A R 93Sodium Hyprochlorite DosingSet
Plant Room N/A 1 of 1 N/A N/A 230V N/A N/A 3 N/A N/A N/A
A R 94 Hydrochloric Acid Dosing Set Plant Room N/A 1 of 1 N/A N/A 230V N/A N/A 3 N/A N/A N/A
* Condition Legend:
5 = As New (Excellent Condition) / 4 = Good Condition for Age / 3 = Average Condition for Age / 2 = Poor Condition for Age, but still servicable / 1 = In Need of Replacement
Asset Register – Mechanical Services North Herts Leisure Centre
Z:\3188\SBR\Asset Register Report\N.H.D.C
APPENDIX C
- Excerpt from CIBSE Guide Volume M (2008)
Indicative Life Expectancy for Building Services Plant, Equipment and Systems
Ref: CIBSE Guide Volume M (2008)
Indicative Life Expectancy for Building Services Plant, Equipment and Systems – excerpt from CIBSE Guide Volume M (2008)
Equipment Item Indicative
Life (Years)
Remarks
Boiler Plant
Shell and tube boilers (steam and HTHW)
20 Water treatment is very important
Water tube boilers (steam and HTHW) 25 Water treatment is very important
Electrode/electric boilers (steam and HTHW)
25 Water treatment is very important
Shell and tube boilers (MTHW/LTHW) 20
Water tube boilers (MTHW/LTHW) 25
Electrode/electric boilers (MTHW/LTHW)
25
Cast iron sectional boilers (MTHW/LTHW)
25
Steel boilers (MTHW/LTHW) 15
Condensing boilers (MTHW/LTHW) 15
Refrigeration Plant - medium to large capacity
Centrifugal chiller 15 See note 1
Reciprocating chiller 20 See note 1
Screw chiller 20 See note 1
Absorption chiller 20
Refrigeration Plant - open type cooling towers
Plastic coated metal cooling tower of plastic coating
25 Consider thickness, bonding and quality
Galvanised metal cooling tower 12 Consider thickness and quality of galvanising
Timber constructed cooling tower which can extend life
10 Consider quality of timber preservation
Ceramic cooling tower 35
Plastic constructed cooling tower 20 Consider thickness and quality of plastic
Epoxy treated metal cooling tower 15
Stainless steel cooling tower 30 Consider quality and thickness of stainless steel
Refrigeration Plant - external heat rejection
Air cooled condensers 20
Evaporative condensers 20
Air blast dry air coolers - plastic coated metal of plastic coating
25 Consider thickness, bonding and quality
Air blast dry air coolers - galvanised metal 20 Consider thickness and quality of galvanising
Air blast dry air coolers — epoxy treated metal
20
Ref: CIBSE Guide Volume M (2008)
Equipment Item Indicative
Life (Years)
Remarks
Boiler Plant Auxiliaries
Oil storage tanks — external protection 20 Depends on thickness of metal and corrosion protection
Oil storage tanks — underground 15 Depends on thickness of metal and corrosion protection
Combustion controls 12
Boiler electrodes 8
Feed pumps 15
Water treatment 15
Atmospheric gas burners 15
Forced air gas burners 12
Oil burners 12
Solid fuel handling plant 15 Conveyor system up to 20 years
High temperature fans 15
Instrumentation 10
Oil distribution system for boiler plant 15
Gas distribution system for boiler plant 20
Mild steel flue 15 Depends on thickness of metal and corrosion protection
Stainless steel flue 20 Check quality of stainless steel
Brick or concrete chimney — external 40
Brick or concrete chimney — internal 50
Steel chimney — external 30 Depends on thickness of metal and corrosion protection
Water Tanks
Cast iron water cisterns 35
Mild steel (treated) water cisterns 15 Not for domestic or drinking water purposes
Plastic water cisterns 35 High quality structural support is necessary
Galvanised metal water cisterns 12
Ductwork - systems and components
Ductwork (galvanised) 30
Ductwork (plastic) need to be considered 20 Mechanical damage and expansion
Ductwork (flexible circular) 20 Mechanical damage needs to be considered also cleaning difficulties
Fans (heavy duty centrifugal) 25
Fans (centrifugal) 20
Fans (axial) 20
Fans (propeller) 15
Fans (roof mounted units) 15
Fire dampers: curtain type 12
Coils (copper fins) heating 25
Coils (copper fins) cooling 25 Consider operational duty — wet surfaces
Coils (aluminium fins) heating 15 Consider quality and thickness of aluminium fins and exposure to adverse external conditions
Coils (aluminium fins) cooling 15 Consider quality and thickness of aluminium fins and exposure to adverse and wet external conditions
Coils (galvanised) heating 12
Ref: CIBSE Guide Volume M (2008)
Equipment Item Indicative Life
(Years)
Remarks
Ductwork - systems and components (contd…)
Spray cooler coils (copper electro-tinned) and washers
15
Eliminators (galvanised) 10
Eliminators (plastic) 15
Eliminators (stainless steel) 20
Coils (electric) 10
Thermal wheels 15
Filters (automatic) — excluding media 15
Filters (panel) — excluding media 20
Filters (electrostatic) 15
Filters (activated carbon) — excluding media
15
Grilles and diffusers (anodised aluminium) 25
Grilles and diffusers (painted metal) 30
Plate recuperator 20
Dampers manual 20
Dampers automatic 15
Steam humidifier (direct) 10 Maintenance is very important
Steam humidifier (electric generated) 8 Maintenance is very important
Water spray humidifier 12 Early signs of corrosion must be dealt with
Pan type humidifier 10 Early signs of corrosion must be dealt with
Chemical dehumidifiers (excluding medium)
15
External louvres (anodised aluminium) 25 Regular cleaning is important to avoid possible breakdown of surface coating
External louvres (steel painted) 20 Early signs of corrosion must be dealt with
Attenuators 25 Consider type of lining, adhesive and fixing of acoustic material
Packaged air handling/conditioning units (internal)
20
Packaged air handling/conditioning units (external)
15 Consider type of corrosion protection
Air Conditioning Terminal Units
Fan coil units (heating and cooling) 15
Induction units 20
Terminal reheat units 20
VAV terminal units (bellows type) 15
VAV terminal units (box type) 15
Double duct terminal units 15
Chilled ceiling panels 25 Flexible water pipework connections - depending on type -10 years
Chilled beams 20 Flexible water pipework connections - depending on type -10 years
Ventilated ceilings 25
VRV units 10
VVT fan powered terminal units 15
Split systems 10
Ref: CIBSE Guide Volume M (2008)
Equipment Item Indicative
Life (Years)
Remarks
Heating Terminal Units
Radiators (cast iron) 25
Radiators (steel) 15 Water condition is important
Radiators (2mm thick steel) 20 Water condition is important
Radiators aluminium 20 Water condition is important and materials in system
Radiator painting 5 Use correct type of paint
Unit heaters (steam and hot water) 15
Unit heaters (gas and electric) 10
Radiant heaters (steam and hot water) 20
Radiant heaters (electric) 10
Fan coil units (heating only) 15
Natural convectors water 20
Natural convectors electric 10
Underfloor heating with concrete encased steel pipes
25 Suggest a long-term bonded warranty is obtained — corrosion prevention of steel pipes
Underfloor heating with concrete encased plastic pipes
30 Suggest a long-term bonded warranty is obtained — consider quality of plastic pipes
Underfloor electric heating 20
Ceiling heating (hot water) 25
Ceiling heating (electric) 15
Electric storage heaters 10
Pipework Systems and Components
Open pipework systems (steel) 25
Closed pipework systems (steel) 30
Open pipework systems (copper) 35 Consider tube thickness and quality of copper
Closed pipework systems (copper) 40 Consider tube thickness and quality of copper
Open pipework systems (steel galvanised) 25
Closed pipework systems (steel galvanized)
35
Refrigerant pipework systems 20 See note 1
Steam pipework system 25
Condensate pipework system 12 Consider type of material, wall thickness and water treatment
Condensate collecting vessel 12 Consider type of material, wall thickness and water treatment
Open expansion vessel 10
Closed expansion vessel with membrane 15
Water treatment plant 15
Water treatment control and measurement equipment
10
Pumps (base mounted) 20
Ref: CIBSE Guide Volume M (2008)
Equipment Item Indicative Life
(Years)
Remarks
Pipework Systems and Components (contd…)
Pumps (pipework mounted) 15
Pumps (glandless) 10
Pumps (sump and well) 12
Pumps (condensate) 10
Bellows flexible (steel) 10
Bellows flexible (rubber) 8
Bellows expansion (steel) 10
Valves (glandless) 20
Valves (glands) 15
Calorifiers 20
Heat exchangers (shell and tube) 25
Ductwork and vessel thermal insulation (blanket type)
30 Consider type of fixing and mechanical damage
Pipework and vessel thermal insulation (moulded type)
30 Consider fire and smoke rating
Drainage and Public Health
Internal waste, foul and rainwater drainage (cast iron)
35
Internal waste, foul and rainwater drainage (copper)
40
Internal waste, foul and rainwater drainage (plastic)
20 Consider mechanical damage & any expansion requirement
Below ground salt glazed drainage 40 Consider possibility of damage and structural movement
Below ground cast iron drainage 45 Consider possibility of ground and structural movement
Below ground plastic drainage 40 Consider mechanical damage
Above ground rainwater – plastic 25
Sanitary ware 25
Fire Fighting and Protection Systems
Alternate wet and dry sprinklers 20 Consider corrosion; see CIBSE Guide E(28)section 8.1.7.3
Wet sprinklers 25 Consider corrosion
Wet risers 20
Dry risers 25
Foam systems 15
Portable fire appliances 8
Fire hose reels 15
Fire hydrants 30
Fire alarms (electrical) 20
Battery support for fire alarm 10
Fire dampers (curtain type) 15
Computer room fire extinguishing system 15 Consider environmental impact and possible phasing out of fire extinguishing agent
Smoke and heat detectors 10
Ref: CIBSE Guide Volume M (2008)
Equipment Item Indicative
Life (Years)
Remarks
Electrical Distribution Network
Main supply switchgear and distribution equipment
30
Transformers (dry type) 30
Transformers (oil type) 30
Mains cables (permanent installations) 30
Electrical Installations in Buildings
Final circuits and outlets 20
Lighting installations (internal) 20 Low voltage decorative may be limited to 10 years
Lighting installations (external) 15
Emergency lighting 20
Electrical motors (general) 15 Smaller motors may have a shorter life — check with supplier
Motor speed control devices 10
Motor control centres 20
Electrical Generating Plant
Alternators 25
Continuously rated gas/oil engines (frequent use)
15
Continuously rated gas/oil engines (standby)
25
Continuously rated steam engines (frequent use)
25
Continuously rated steam turbines (frequent use)
25
Oil storage 30
Controls & instrumentation 20
Mains failure sensors 15
Battery support 10 Building Management and Controls - electrics and electronics
Personal computer 10 Alternative name — supervisor. Reference note 2.0
PC operating system 8 See note 2
BMS operating system 8
Autodial modem 8
Printer 5 With frequent use operating costs are important
Screened network (hardwiring) 25 Should be future proofed with additional cable wireways. See note 2
Network communication devices 10 Proprietary devices or gateways — may require support. See note 2
Damper actuators 10
Intelligent outstations 10 See note 2
Sensors 8 Periodic loop tuning and calibration should be considered
Control valves 15
Ref: CIBSE Guide Volume M (2008)
Equipment Item Indicative Life
(Years)
Remarks
Building Management and Controls- electrics and electronics (contd…)
Control dampers 15
Electronic/pneumatic interfaces 10
Utility metering 20
Pagers 5
Remote display panels 10 See note 2
Hardwiring between devices 25 Screened cables may be necessary
Controls General
Pneumatic controls 20
Electric controls 20
Electronic controls 15
Hydraulic valve actuators 10
Pneumatic valve actuators 15
Self-contained valve actuators 8
Miscellaneous Electrical Equipment and Plant
Lead acid batteries (sealed) 5
Nickel alkaline batteries (vented) 20
Battery chargers 20
Clock systems 15
Communication systems 20 Voice and data. See note 2
Public address systems 20
Intruder alarms and intercommunications 10
Uninterrupted power supply systems 20
Closed circuit television and video 10
Television and satellite systems 15 See note 2
Lightning protection 25
Lighting control and management system 15
Continuous flow electrical heaters 12
Electrical water heaters 12
Electrical storage heaters with ventilation 20
Electrical floor heating 25
Electrical heater (on peak) 8
Window unit air conditioner 8
Residential single or split package air conditioner
10
Commercial through the wall air conditioner 10
Water cooled air conditioner 15
Residential air to air heat pump 10
Commercial air to air heat pump 15
Commercial water to air heat pump 15
Miscellaneous Mechanical Equipment and Plant
Kitchen (cooking and support systems) 15
Laundries (equipment and support systems) 20
Water features 15 Water treatment is very important
Computer room air conditioning 15
Tea rooms (equipment and support systems) 15
Hand dryers 5
Drinking fountains 10
Vending machines 8
Sanitary towel disposal 10
Food/container waste disposal 5
Waste paper shredders/disposal 10
Stair/lobby ventilation 20
Fire protection (pipes and ducts) 20 Damage to fire protection should be examined at frequent intervals
Ref: CIBSE Guide Volume M (2008)
Equipment Item Indicative Life
(Years)
Remarks
Miscellaneous Mechanical Equipment and Plant (contd…)
Incinerators 15
Gas or oil fired furnaces 15 Selection of heat exchanger material is important
Domestic gas fired warm air heaters 15
Domestic gas fired boilers 10
Domestic gas fired combination boilers 10
Gas fired hot water (storage and continuous) 12
Gas fires 8
Vertical Transportation
Lifts 15
Escalators 15
Security
Access systems (door releases, card readers, key pads)
10
CCTV cameras 10
CCTV control systems & multiplexers 15
Infra red lighting 10
Intruder detection 15
Note 1 - The phasing out of CFCs and HCFCs may require replacement of equipment earlier than originally planned
Note 2 - Technology changes can influence early replacement
Note 3 - Ensure that all heat exchangers especially refrigerant cooling and heat pumps
systems are suitable for UK operating conditions