43
ASHRAE W ILL G IVE Y OU THE W ORLD This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee

ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

Embed Size (px)

Citation preview

Page 1: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

ASHRAE WILL GIVE YOU

THE WORLD

This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee

Page 2: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

2

Julian R. de Bullet

ASHRAE Distinguished Lecturer

President, deBullet Consulting

703-483-0179

[email protected]

PLEASE MUTE CELL PHONES

VARIABLE FLOW

CHILLER PLANT DESIGN

Page 3: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

Why Optimized Design?

• Buildings In The US Consume 39% Of Our Total Energy

• 70% Of Our Electricity Annually

• 5 Billion Gallons Potable Water Per Day For Toilets

• Typical Construction Generates 2.5 lbs. Of Solid Waste Per Square Foot

• High Performance Building Practices Can Reduce These Negative Environmental Impacts

Page 4: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

4

Page 5: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

5

Page 6: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

6

Chiller Basics

• Air, Water Or Evaporatively

Cooled

• Reciprocating, Scroll, Screw

Or Centrifugal Compressors

• DX or Flooded Evaporators

Page 7: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

7

Cooling Tower Basics

Induced Draft Tower

Forced Draft Tower

Page 8: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

8

Load Basics

• Chilled Water Coils

Transfer Heat From

Building Air To Chilled

Water

• Process Loads

– Cooling Jackets

Page 9: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

9

HVAC Controls

BACnetAS

H R

E

A ™

OPEN PROTOCOL IS A NORM!

Web-based?

Page 10: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

Constant Volume Chilled Water Flow Design

Chilled Water Pump

(constant speed)

3 Way valve

Page 11: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

Constant Volume Chilled Water Flow Design

Chilled Water Pump

(constant speed)

No valve

Commonly

called a “Wild

Coil”

Page 12: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

Constant Volume Chilled Water Flow Design

Chilled Water Pump

(constant speed)

3 Way valve

Temperature Differential on

the chilled water supply and

return

Capacity measurement

55f

45f

50f

Page 13: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

Constant Volume Chilled Water Flow Design

Constant chilled water flow required because of the three way bypass valves on

each air handler

Multiple chiller applications require the chillers to be in series for capacity reduction

Capacity measurement is with the chilled water temperature differential

Advantages to this design-

Ease of control

Disadvantages to this design-

Increased installation cost because of parallel piping required to allow for service

or isolation of one unit

Low fluid velocities

Chillers with different lift and mass flow capabilities

Matching or balancing the load of two chillers

Page 14: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

14

Full Load Vs. Annual Load

Design Performance

Chiller

58%

Tower

5%

Fans

24%Pumps

13%

Annual Energy Usage

Pumps

22%

Tower

2%

Chiller

33%Fans

43%

Page 15: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

15

• Variable Flow Required For Systems Over 10

HP (6.4.3.1)

– Modulate Down To 50%

• Exceptions

– Where Minimum Flow Is Less Than Flow Required

By Equipment And < 75HP

• Individual Variable Flow Pumps > 100 Feet And 50 hp Motor

– 30% Design Wattage At 50% Flow

– Controlled As A Function Of Flow Or Pressure

Differential

HVAC - Prescriptive Method (Section 6)

Hydronic Systems (6.3.4)!!!!!

Page 16: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

Primary/Secondary Chilled Water Flow Design

Constant Flow Primary

Chilled Water Pumps

Check Valve in the Bridge or

De-coupler Circuit

Variable Flow

Secondary Chilled

Water Pump

2 Way modulating

CHW valve

Page 17: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

Primary/Secondary Chilled Water Flow Design

Measurement devices required

for system capacity

Bridge or De-coupler temperature sensor

or bi-directional flow meter

Secondary Chilled

Water Supply

Temperature

Secondary Chilled

Water Return

Temperature

Secondary

Chilled

Water Flow

Meter

Pressure

differential

transmitter

Page 18: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

Primary/Secondary Chilled Water Flow Design

Example of 60% system load

with 40% bypass

40% flow

42 deg f

60% valve

position

48 deg f

52 deg f

42 deg f

60% of chilled

water flow

ON

ON

Page 19: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

19

Primary/Secondary Design

• Pros

• Variable Flow Through Secondary Loop

• Stable Constant Flow through Chillers

• Cons

• Complexity

• Low Delta T Syndrome

• Stepped Primary Flow

– (More Pump Work Than Variable Primary Flow)

Page 20: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

20

Low Delta T-Definition

A Condition Whereby a Low Chilled Water

Return Temperature Causes an Excessive

Amount of Chilled Water to Circulate to

Meet System Cooling Loads and Chillers

Receiving the Low Temperature CHR

CANNOT be Loaded to Their Design

Capacity

Page 21: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

21

Low Delta T Syndrome

Low Delta T Symptoms And Solutions

• 3 Way Valves

– Don’t Use Them

• Supply Air Set points Lowered Beyond Design

– Valves Go Wide Open - No Control

– Ensure Valves Are Tracking

• Valves Not Closed When Not Required

– Ensure Valves Close When AHU Not In Use

• All System Components Not Designed For Same

Delta T

Page 22: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

22

Low Delta T Syndrome

Low Delta T Symptoms And Solutions Cont’d

• Coils And Valves Not Properly Selected

– Select Correctly

• Coils Piped “Backwards”

– Coils Must Be Piped So Water Is Counterflow To Air

• Improper Tertiary Piping

– Ensure Tertiary Setpoint Is Above Chilled Water Setpoint

• Dirty Coils- Clean the Coils

Page 23: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

23

Low Delta T Syndrome

Low Delta T Retrofit Solutions Cont’d

• VFD Chillers

– Excellent Part Load Performance Allows Two Chillers To

Operate More Efficiently Even With Parasitic Losses

• Oversize Primary Pumps

– Oversized Primary Pumps With VFDs Can Over Pump

Chillers And Avoid Starting Additional Machines

• Variable Primary Flow

– Easily Accommodates Over Pumping Chillers

Page 24: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

24

Low Delta T Syndrome

Low Delta T Retrofit Solutions Cont’d

• Reduce Delta T On Primary Side

– Larger Pumps And Piping Will Increase Capital Cost

– Penalty At Full Load

• Add Flow Control Valves At Each Coil

– Ensures Terminal Device Doesn’t Exceed Design Flow

– Space Cooling Not Satisfied

– Increase System Pressure Drop

– Adds Cost

Page 25: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

25

Low Delta T Syndrome

• Check Valve Puts Pumps In Series

• Potentially Over-pump Chiller

• Can Starve Building

• Doesn’t Fix Real Problem

Low Delta T Retrofit Solutions ?

Check Valve In

Decoupler

Page 26: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

26

Variable Primary Flow Design

General

– Primary Pump Operates When Chilled Water

Required

– Condenser Pump And Tower Operate When

Chiller Operates

– 2 Way Valves

• Diversity To Flow

– Works With Single, Series And Parallel

Chillers

Page 27: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

Variable Primary Chilled Water Flow Design

Measurement devices required to

control the chillers

Minimum flow bypass

2 Way modulating

CHW valve

Pressure differential transmitter across each chiller

evaporator to operate the minimum flow bypass

Page 28: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

Variable Primary Chilled Water Flow Design

Measurement devices required to

control the chillers

Minimum flow bypass

2 Way modulating

CHW valve

Pressure differential transmitter across the

chilled water header to control the chilled

water pump speed

Page 29: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

Variable Primary Chilled Water Flow Design

Measurement devices required to

control the chillers

Minimum flow bypass

2 Way modulating

CHW valve

Chilled water flow meter to measure the total

chilled water flow

Page 30: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

Variable Primary Chilled Water Flow Design

Example of the system at full load

Minimum flow bypass

100% open

ON

ON

42 deg F 52 deg F

CHWP’s at

100% speed

42 deg F 52 deg F

0% Open

Page 31: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

Variable Primary Chilled Water Flow Design

Example of the system at 60% load

Minimum flow bypass

60% open

ON

ON

42 deg F 52 deg F

CHWP’s at

60% speed

42 deg F 52 deg F0% Open

Page 32: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

Variable Primary Chilled Water Flow Design

Example of the system at 20% load

Minimum flow bypass

OFF

ON

42 deg F 52 deg F

CHWP at

25% speed

42 deg F 52 deg F5%

20%

flow

Page 33: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

Flow Meter

Control Valve, sized for minimum chiller flow

Automatic Isolation Valves

Variable Speed Primary Pumps

Bypass

350 Ton

1,231 kW

1050 gpm

(66 l/s)

700 tons / 2 chillers = 350 tons (1,231 kW) per chiller

When building 100% loaded, entering condenser water = 85F (29.4 C)

350 Ton

1,231 kW

2 350 TON, VARIABLE PRIMARY

33

Building Load 100% (700 Tons, 2462 kW)

Page 34: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

34

Variable Primary Flow Design

• Design Flowrate Determined by Tube Velocity

– Minimum 1.5 FPS ( Based On A Reynolds # Of 7500)

– Maximum 12 FPS

• At Typical Conditions, 6-7 FPS

• Select Evaporator With More Passes & Higher

Pressure Drop

• Minimum Flow Typically 50% Or Less Of Design

• Bypass Must Be Sized To Maintain Minimum Flow

Rate Of Largest Chiller

Page 35: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

Benefits of a variable primary chilled water flow design

•Reduced first cost with the elimination of the secondary

chilled water pumps

•Reduced energy cost by the elimination of the constant

speed energy on the primary chilled water pumps

•Measurement of capacity with chilled water flow and

chilled water temperature differential

•Chillers do not operate in an unloaded condition to

generate enough chilled water flow to prevent negative

water flow through the de-coupler in a primary secondary

design

Page 36: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

36

When to consider VPF ?

When:

•System flow can be reduced by at least 30% of design.

•Design affords greater cost savings than a “de-coupled” system.

•Operators will understand how the system works and will run it properly.

•The system can tolerate a modest variation in supply water temperature.

•A single chiller is being replaced and the primary flow can be varied.

•Variable Flow can be applied to Parallel as well as Series Flow.

Page 37: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

CHILLER STAGING

37

Condenser piping not shown

Bypass piping, isolation valves not shownT2 T1T3

CH-1 Lead CH-2 Lag

CH-1 Programmed as lead chiller, CH-2 programmed as lag chiller.

CH-1 loads up until compressor speed indicates 2nd chiller appropriate

Based on compressor speed, CH-1 commands CH-2 to turn on.

Since chillers are in series, pump flows are already established.

CH-1 and CH-2 operate together to regulate T3 to set point.

At appropriate compressor speed, CH-1 commands CH-2 to turn off.

If CH-1 becomes disabled, the on board controls rotate CH-2 as the lead chiller.

CH-2 regulates to the leaving temperature T3 via the sensor.

No Human Intervention Required

Page 38: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

Increasing system reliability in a VPF System

Does the system have the instrumentation in

place to control a VPF system?

It is critical that the system have the necessary flow meters,

differential pressure sensors, and valves in the system for

proper operation.

In addition, these devices should be selected for the system

requirements. The accuracy of the instrumentation should be

factored into the recommended minimum/maximum water flow limits.

Page 39: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

39

VPF vs. Primary Secondary

0

50000

100000

150000

200000

250000

300000

350000

400000

450000

500000

Chillers Pumps Towers Fans

kW

h

Variable Primary Flow 2 Chiller Primary/Secondary Flow 2 Chiller Parallel Flow

Page 40: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

According to an ARTI study results, variable

primary-only chilled water systems reduced

the total annual plant energy by 3 to 8 percent,

first cost by 4 to 8 percent, and life cycle cost

by 3 to 5 percent relative to conventional

constant primary flow/variable secondary flow

chilled water systems.

40

More or Less?

Page 41: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

41

Future Goals

• Net- Zero Energy Buildings

– Combination of Rising Energy Prices

– Improving Technology

– Concerns about Climate Change

• Future Goal of Net-Zero Carbon Emissions

• ASHRAE Standard 189, Design of High Performance

Green Buildings

Page 42: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

Complete the Distinguished Lecturer

Event Summary Critique

CTTC needs your feedback to continue to improve the

DL Program

Distribute the DL Evaluation Form to all attendees

Collect at the end of the meeting

Compile the attendee rating on the Event Summary Critique

Send the completed Event Summary Critique to your CTTC RVC

and ASHRAE Headquarters

Forms are available at:

www.ashrae.org/distinguishedlecturers

Page 43: ASHRAE WILL GIVE YOU THE WORLD - Anthracite Chapteranthraciteashrae.weebly.com/uploads/2/2/8/5/22852420/ashrae... · HVAC Controls A t S H R E A ... Constant chilled water flow required

43