Ashrae Std 62 11

Embed Size (px)

Citation preview

  • 7/29/2019 Ashrae Std 62 11

    1/35

    Ventilation for AcceptableIndoor Air Quality

    62.1-2010

    Dave Kahn, P.E.Dave Kahn, P.E.

  • 7/29/2019 Ashrae Std 62 11

    2/35

    What Is ASHRAE Standard

    62.1?

    The Industries Ventilation StandardConsensus StandardStandard of Care

    Used in NFPA 5000 BuildingConstruction and Safety Code

    LEED Requirement

    2009 IMC Ventilation systemefficiency may be calculated byAppendix A (62.1-2004)

  • 7/29/2019 Ashrae Std 62 11

    3/35

    History of the Standard

    1905 Flugge 30 cfm

    1936 Yaglou 10 cfm 1973 First Issued office 15 cfm/p 1981 Lower Rates office 5 cfm/p 1989 Higher Rates office 20 cfm/p

    1999 Little Change

    office

    20 cfm/p

    2001 More Mandatory Language office 20 cfm/p

    2004 Key Changes

    office 17 cfm/p

    2007 Appendix H office 17 cfm/p 2010 Dropped Smoking office17 cfm/p

  • 7/29/2019 Ashrae Std 62 11

    4/35

    Acceptable Indoor Air Quality

    What Is It? Standard 62: Air in whichthere is no known

    contaminants at harmful

    concentrations as determinedby cognizant authorities and

    with which a substantial

    majority (80% or more) of thepeople exposed do not

    express dissatisfaction.

  • 7/29/2019 Ashrae Std 62 11

    5/35

    How Much Ventilation?

    Unknown Chamber studies

    Limited to body odor (olf)

    Medical evidence

    No evidence based

    studies

    Rule of thumb evidence

  • 7/29/2019 Ashrae Std 62 11

    6/35

    Chamber Body Odor StudiesImpact of ventilation rate on visitors

    From ASHRAEpresentation by

    Steve Taylor

  • 7/29/2019 Ashrae Std 62 11

    7/35

    Body Oder StudiesCain & Leaderer

    From ASHRAEpresentation by

    Steve Taylor

  • 7/29/2019 Ashrae Std 62 11

    8/35

    Cain & Leaderer

    1983 For nonsmoking occupancy, 47 combinationsof temperature, humidity, ventilation rate and

    occupancy density were examined. Odor

    level depended entirely on ventilation rate perperson irrespective of the number of personsin the chamber.

    For both smoking and nonsmokingconditions, a combination of hightemperature (78F) and humidity (r.h. > 70

    %) exacerbated the odor problem

  • 7/29/2019 Ashrae Std 62 11

    9/35

    Recent Studies

    Hillsborogh County Schools March 2011 Engineered Systems

    9th

    largest district in US

    7.5 cfm/student 2 California Studies ongoing Anticipate ventilation rate changes

  • 7/29/2019 Ashrae Std 62 11

    10/35

    62.1 New in 2010

    PM2.5 non-attainment areas require air cleaning Smoking spaces no longer covered by thestandard Air intake separation distances revised Deletes requirements for health care spaces Revises IAQ procedure to make it more robust Most natural ventilation systems now requiremechanical systems for when natural vent cannot

    be used (thermal comfort, noise, security)

  • 7/29/2019 Ashrae Std 62 11

    11/35

    Fun Facts

    Means to balance the system to achieve minimum

    airflow. Design documentation to state ventilation rate andair distribution assumptions. Controls to enable the fan to operate wheneverthe spaces served are occupied. VAV systems with fixed OA dampers must complyat minimum supply airflow.

    MERV 6 filters upstream of all coils or other

    devices with wetted surfaces.

  • 7/29/2019 Ashrae Std 62 11

    12/35

    Two paths to compliance

    Ventilation Rate Procedure

    Most commonly used method

    Lookup table (simple) or Appendix A (complex)

    Need zone air distribution effectiveness

    LEED requires this method

    Indoor Air Quality Procedure

    Design to maintain specific contaminant levels

    Mass Balance Analysis

    Methods used in similar buildings

    Validation by contaminant monitoring

    Single duct

    systems such

    as VAV

    reheat

    Multiple paths: Fan

    powered VAV and

    Dual duct

  • 7/29/2019 Ashrae Std 62 11

    13/35

    Ventilation Rate Procedure

  • 7/29/2019 Ashrae Std 62 11

    14/35

    Ventilation Rate Procedure

  • 7/29/2019 Ashrae Std 62 11

    15/35

    Ventilation Rate Procedure

  • 7/29/2019 Ashrae Std 62 11

    16/35

    Classroom ExampleSingle zone 2010

    High School classroom 35x35 30 people Vbz = Rp

    Pz

    + Ra

    Az Vbz

    = Breathing Zone OA

    10 cfm /person 10 * 30 = 300 cfm

    0.12 cfm/ft2 0.12 * 35 * 35 = 147 cfm

    300 + 147 = 447 cfm

    Zone outdoor airflow Voz =Vbz /Ez 447 /1 = 447 cfm or14.9 cfm/person

  • 7/29/2019 Ashrae Std 62 11

    17/35

    Short-Term Conditions

    Peak occupancy of short duration Ventilation interrupted for a short period oftime T = 3V/ Vbz V = Volume of ventilation zone

    + Zone outdoor air flow

  • 7/29/2019 Ashrae Std 62 11

    18/35

    Example Private Office

    230 Sq Ft, 9 ft ceiling Work station and 2guest chairs

    T= 3V/ Vbz = 9*230*9/(3*5 +230 *0.06) = 3.6hrs

    Assume guests present 1/3 of time

    Design occupancy = 1 + (2 * 1/3) = 1.7

  • 7/29/2019 Ashrae Std 62 11

    19/35

    Multiple-Zone Recirculating

    Systems

    For each zone: Vbz = Rp

    Pz

    + Ra

    Az Just like previous example

    Voz =Vbz /Ez Just like previous example

  • 7/29/2019 Ashrae Std 62 11

    20/35

    Multiple-Zone Recirculating

    Systems

    Primary outdoor air fraction Zp Zpz = Voz

    /Vpz (For each zone)

    Voz -

    zone outdoor airflow

    Vpz - minimum zone primary airflow(supply air)

  • 7/29/2019 Ashrae Std 62 11

    21/35

    Uncorrected Outdoor

    Air Intake

    Vou

    = Dall zones

    Rp

    Pz

    + all zones

    Ra

    Az Vou

    -

    uncorrected outdoor air intake

    D - occupant diversity = Ps / all zones Pz

    Ps

    -total population of area served

    by the system

    Pz

    - largest number of peoplein the zone

  • 7/29/2019 Ashrae Std 62 11

    22/35

    System Ventilation Efficiency

  • 7/29/2019 Ashrae Std 62 11

    23/35

    Outdoor Air Intake

    Vot = Vou /Ev Vot - design outdoor air intake flow

    Vou

    -

    uncorrected outdoor air intake

    Ev - ventilation efficiency from Table 6-3or Appendix A

  • 7/29/2019 Ashrae Std 62 11

    24/35

    62MZCalc

  • 7/29/2019 Ashrae Std 62 11

    25/35

    62MZCALC

  • 7/29/2019 Ashrae Std 62 11

    26/35

    62MZCALC

  • 7/29/2019 Ashrae Std 62 11

    27/35

    DYNAMIC RESET

    VRP procedure gives the peak rate based on

    worst case assumptions (design)

    Reset based on Occupancy: time of day Occupancy sensors

    Carbon dioxide

    Air distribution efficiency

    Multiple space equation solved

    dynamically Economizer reset of VAV minimums

  • 7/29/2019 Ashrae Std 62 11

    28/35

    Dynamic Reset

    Air Distribution Efficiency If min OA determined in heating mode, OA can bereduced during cooling due to a higher Ez

    Solve equations in appendix A dynamically based onzone and system flows to reset zone minimums andoutdoor airflow.

    OA economizer reset of VAV Box minimum

    Dont drop below the area outdoor air rate Ra . Economically limited to high-density occupancies.

  • 7/29/2019 Ashrae Std 62 11

    29/35

    Demand Controlled Ventilation

    CO2 .Time averaging to reduce zone population is notallowed

    Constant Volume with no air flow measurementAt CO2

    max, damper positioned to admit Vot design

    occupancy

    At ambient CO2

    levels set minimum to admit required

    air quantity with no occupants Vat

    Linear reset between CO2

    max and CO2

    ambient

  • 7/29/2019 Ashrae Std 62 11

    30/35

    Demand Controlled Ventilation

    CO2 sensor location: In the breathing zone

    Typically adjacent to the temp sensor

    44 AFF

    Return air sensing doesnt work

    Sensor type Infrared Accuracy +- 75 PPM

  • 7/29/2019 Ashrae Std 62 11

    31/35

    Constant Volume W/O air flow

    measurement

    Calculate Vot at design occupancy rate Calculate Vot with no occupants call it Vat

    Reset min OA damper position from Vat to

    Vot as CO2 varies from 400 (ambient) to 800(calculated or arbitrary setpoint)

    Damper positions set in conjunction withbalancer

  • 7/29/2019 Ashrae Std 62 11

    32/35

    Constant volume with air

    flow measurement Solve equations A-H dynamically to reset therequired min OA qty

    Cant reduce the number of occupants using

    time averaging Can reset zone effectiveness based onsupply air temperature

  • 7/29/2019 Ashrae Std 62 11

    33/35

    Multiple Zone Systems

    ASHRAE Research 1547TRP is working on it

    Old

    method in 2004 handbook

  • 7/29/2019 Ashrae Std 62 11

    34/35

    Learning More

    Read the standard

    2010 Handbook is available ASHRAE ALI courses

  • 7/29/2019 Ashrae Std 62 11

    35/35

    Questions