Upload
mark-ramnarine
View
34
Download
0
Tags:
Embed Size (px)
DESCRIPTION
Power Point for seismic considerations
Citation preview
ASCE 7-05 Seismic
Provisions
A Beginner’s Guide to ASCE 7-05
Dr. T. Bart Quimby, P.E., F.ASCE
Quimby & Associates
www.bgstructuralengineering.com
1 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Earthquake Protective Design
Philosophical Issues
High probability
of “Failure”
“Failure”
redefined to
permit behavior
(yielding) that
would be
considered
failure under
other loads.
High Uncertainty
Importance of
Details
“In dealing with earthquakes we must
contend with appreciable probabilities
that failure will occur in the near
future. Otherwise, all the wealth of
the world would prove insufficient…
We must also face uncertainty on a
large scale… In a way, earthquake
engineering is a cartoon…
Earthquakes systematically bring out
the mistakes made in design and
construction, even the minutest
mistakes.” Newmark & Rosenblueth 2 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Hazard Levels
Incipient Collapse
Life Safety
Immediate
Reoccupancy
Fully Operational
Occasional
50% in 50 years
Rare
10% in 50 years
Very Rare
5% in 50 years
Max Considered
2% in 50 years
Performance Levels
3 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Design Objective Defined
A specific performance level given a specific
earthquake hazard level
Stated basis of current codes:
Life safety (+some damage control) at 10% in
50 year event (nominally)
4 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Purpose of the Provisions
FEMA 302 Section 1.1
“The design earthquake ground motion levels specified herein
could result in both structural and nonstructural damage.
For most structures designed and constructed according to
these Provisions, structural damage from the design earthquake
ground motion would be repairable although perhaps not
economically so. For essential facilities, it is expected that the
damage from the design earthquake ground motion would not
be so severe as to preclude continued occupancy and function
of the facility.”
“For ground motions larger than the design levels, the intent of
these Provisions is that there be a low likelihood of
structural collapse.”
5 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Compare Wind and Seismic Design of Simple Building
120’
90’
62.5’
Earthquake:
Assume 0.4g NEHRP
Wind:
100 MPH Exposure C
Building Properties:
Moment Resisting Frames
density r = 8 pcf
Period T = 1.0 sec
Damping x = 5%
4.3
6 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Wind:
120’
90’
62.5’100 mph Fastest mile
Exposure C
Velocity pressure qs= 25.6 psf
Gust/Exposure factor Ce = 1.25
Pressure coefficient Cq = 1.3
Load Factor for Wind = 1.3
Total wind force on 120’ face:
VW120= 62.5*120*25.6*1.25*1.3*1.3/1000 = 406 kips
Total wind force on 90’ face:
VW90 = 62.5*90*25.6*1.25*1.3*1.3/1000 = 304 kips
4.4
7 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Earthquake:
120’
90’
62.5’Building Weight W=
120*90*62.5*8/1000 = 5400 kips
Total ELASTIC earthquake force (in each direction):
VEQ = 0.480*5400 = 2592 kips
CA S
TS
V
12 12 0 4 10
100 480
2 3 2 3
. . . .
..
/ /
V C WEQ S
This example uses an old version of both the NEHRP and the ASCE 7
Wind Load Criteria. It is used for illustrative purposes only.
8 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Comparison: Earthquake vs. Wind
V
V
EQ
W120
2952
4067 3 .
V
V
EQ
W 90
2952
3049 7 .
• ELASTIC Earthquake forces are 7 to 10 times wind!
• Virtually impossible to obtain economical design
4.6
9 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
How to Deal with Huge Earthquake Force?
• Isolate structure from ground (Base Isolation)
• Increase Damping (Passive Energy Dissipation)
• Allow Inelastic Response
Historically, Building Codes use Inelastic Response Procedure.
Inelastic response occurs though structural damage (yielding).
We must control the damage for the method to be successful.
4.7
10 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Interim Conclusion (The Good News)
The frame, designed for a wind force which is 15% of the
ELASTIC earthquake force, can survive the earthquake if:
It has the capability to undergo numerous cycles of
INELASIC deformation
It suffers no appreciable loss of strength
It has the capability to deform at least 5 to 6 times
the yield deformation
REQUIRES ADEQUATE DETAILING
4.12
11 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Interim Conclusion (The Bad News)
As a result of the large displacements associated with the
inelastic deformations, the structure will suffer considerable
structural and nonstructural damage.
This damage must be controlled by
adequate detailing and by limiting
structural deformations (drift)
4.13
12 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Elastic vs. Inelastic Response
The red line shows the force and displacement that would be reached if the structure responded elastically.
The green line shows the actual force vs. displacement response of the structure
The pink line indicates the minimum strength required to hold everything together during inelastic behavior
The blue line is the force level that we design for.
We rely on the ductility of the system to prevent collapse.
From 1997 NEHRP Provisions
13 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Historical Development of Seismic Codes
1755 - Lisbon: ground shaking waves
1906 - San Francisco: Fire, lateral force from wind
1911 - Messina, Italy: Static inertial force (10%), First recognition of F=ma
1923 - Tokyo: Prediction by seismic gap
1925 - Santa Barbara: USCGS instructed to develop strong motion seismographs.
1927 - U.B.C.: Inertial forces and soil effects in the U.S. (7.5% or 10% of D+L)
1933 - Long Beach: First instrumental records (flawed): reinforcement required for masonry; quality assurance; design review & construction inspection.
14 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Historical Development of Seismic Codes
1940 - El Centro: Earthquake ground motion record. Makes possible
the computation of structural response. Became the most used record.
1943 - City of Los Angles Building Code: Dynamic property of building
used in addition to mass (Number of stories relates to period and to
distribution of force)
1952 - San Francisco Joint Committee:
Modal analysis used as a basis for static forces and distribution.
Difference between design force and computed forces not resolved.
Distinction for soils types dropped
Overturning reductions
Torsion
1956 - World Conference on Earthquake Engineering
1957 - Mexico City: Success with design using dynamic analysis.
15 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Historical Development of Seismic Codes
1960 - SEAOC blue book
Design accel. Similar to 1943 LA and 1952 SF
Factor for performance of structural systems (K)
Effect of higher modes on vertical distribution
1961 - “Design of Multi-Story Reinforced Concrete Buildings for Earthquake Motions”, Blume, Newmark, and Corning
Inelastic response
Ductility in concrete
1964 Alaska Earthquake: Lack of instrumental data. Observations influenced thinking on torsional response, anchorage of cladding, and overall load path concepts.
1964 - Niigata, Japan: Liquefaction
1967 - Caracas Earthquake: Non structural infill and overturning.
16 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Historical Development of Seismic Codes
1974 Applied Technology Council Report ATC 2
Continued to use single design spectrum for buildings
1976 ATC 3
Probabilistic ground accelerations
Realistic response accelerations and explicit factors for inelastic action
Strength design
Ground motion attenuation
Nationwide applicability
Existing buildings
1977 National Earthquake Hazards Reduction Act: Federal support
and direction
1979 Building Seismic Safety Council: response to ATC 3 - extensive
review and trial designs
1985 - BSSC/NEHRP Recommended provisions: Son of ATC 3
17 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Historical Development of Seismic Codes
1985 - Mexico City Earthquake: Extreme site effects
1988 - New SEAOC (1987) and UBC requirements:
Allowable stress design and a single map.
1988 Armenia Earthquake: Structural details and site
effects
1989 Loma Prieta Earthquake: A performance test
for buildings & bridges.
1991 NEHRP Provisions into Model Codes
18 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Building Seismic Safety Council http://www.bssconline.org/
Private
Voluntary
National Forum
Issues:
Technical
Social
Economical
Members are
organizations
(ASCE, ACI, AISC,
AIA, ICBO, BOCA,
EERI, SEAOC,
etc…)
Consensus Process
19 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
ASCE 7-05 Seismic Provisions
20 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Seismic Ground Motion Values
Mapped Acceleration Parameters
Ss = Mapped 5% damped, spectral response
acceleration parameter at short periods
S1 = Mapped 5% damped spectral response
acceleration parameter at a period of 1 sec.
Can be found online at
http://earthquake.usgs.gov/research/hazmaps/
You need Java to run the downloadable
application.
See ASCE 7-05 11.4
21 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
SS
Use Map to find the
maximum
considered ground
motion for short
periods.
The contours are
irregularly spaced
Values are in % of g
See ASCE 7-05 22
22 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
S1
Use Map to find the
maximum
considered ground
motion for short
periods.
The contours are
irregularly spaced
Values are in % of g
See ASCE 7-05 22
23 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Site Classes
Site Classes are also labeled A-F
A is for hard rock, F for very soft soils
See definitions in ASCE 7-05 20
Choice of site class is based on soil stiffness which is measured in
different ways for different types of soil.
See ASCE 7-05 20 for procedure
If insufficient data is available, assume Site Class D unless there is a
probability of a Site Class F.
See ASCE 7-05 11.4.2, 20
24 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Compute SMS and SM1
SMS = FaSS
Fa from Table
11.4-1
SM1= FvS1
Fv from Table
11.4-2
See ASCE 7-05 11.4.3
25 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Spectral Response Accelerations
SDS and SD1
SDS is the design, 5% damped, spectral
response acceleration for short periods.
SD1 is the design, 5% damped, spectral
response acceleration at a period of 1 sec.
SDS and SD1 are used in selecting the Seismic
Design Category and in the analysis
methods.
See ASCE 7-05 11.4.4
SDS = 2*SMS/3 SD1 = 2*SM1/3
26 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Design Response Spectrum
Period Limiting Values
T0 = .2 SD1/SDS
TS = SD1/SDS
TL from ASCE 7-05 22
Sa, design spectral
response acceleration
Sa is a function of
structure period, T
Four regions, four
equations.
See ASCE 7-05 11.4.5
27 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Importance Factor, I
See ASCE 7-05 Table 11.5-1
Function of Occupancy Category
Requirement for structures adjacent to
occupancy category IV structures where
access is needed to get to the category IV
structure.
See ASCE 7-05 11.5
28 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Seismic Design Categories
To be determined for every structure
function of:
Occupancy Category
Spectral Response Accelerations SDS and SD1.
Used to determine analysis options, detailed
requirements, height limitations, and other
limits on usage.
Seismic Design Categories labeled A-F
See ASCE 7-05 11.6
29 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Seismic Design Categories
The most restrictive
value controls
SDC E:
OC I, II, III where
S1 > 0.75
SDC F:
OC IV where S1
> 0.75
30 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Seismic Design Category A
Very limited seismic exposure and risk
Lateral forces taken to equal 1% of structure
weight.
A complete load path must be in place.
See ASCE 7-05 11.7
31 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Soil Report Requirements
Limits on where you can place a structure
(SDC E or F)
SDC C – F:
specific evaluation of listed hazards.
SDC D-F:
Even more evaluation requirements.
See ASCE 7-05 11.8
32 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Seismic Load Analysis Procedures
Equivalent Lateral Force (ELF)
Static approximation.
May not be used on structures of Seismic Design
Categories E or F with particular irregularities. (ASCE
7-05 Table 12.6-1)
Modal Analysis
2D and 3D dynamic analysis
Required for buildings with particular irregularities
Site Specific Response Spectrum
Permitted for all structures
See ASCE 7-05 12.6
33 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Analysis Procedures
Category A: regular and irregular structures designed
for a minimum lateral force
Category B & C: regular and irregular structures
using any of the three methods
Category D, E, & F: Table 12.6-1 with some limits on
SDS and SD1
ELF for regular and some irregular
Modal for some irregular
Site specific required in Site Classes E or F
34 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Structure Configuration
(regular or irregular)
Plan Configuration
ASCE 7-05 12.3.2.1
Vertical Configuration
ASCE 7-05 12.3.2.2
35 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Plan Structural Irregularities
1a - Torsional Irregularity
1b - Extreme Torsional Irregularity
2 - Re-entrant Corners
3 - Diaphragm Discontinuity
4 - Out-of-plane Offsets
5 - Nonparallel Systems
36 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Type 1: Torsional Irregularities
1a - Torsional Irregularity
larger story drift more than 1.2
times average story drift
1b - Extreme Torsional Irregularity
larger story drift more than 1.4
times average story drift
Not permitted in Design
Categories E & F
Design forces for lateral force
connections to be increased 25% in
Design Categories D, E, & F.
37 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Type 2: Re-entrant Corners
Both projections
beyond the corner are
more than 15% of the
plan dimension of the
structure in the same
direction
38 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Type 3: Diaphragm
Discontinuities
Diaphragms with abrupt discontinuities or variations
in stiffness, including those having cutout or open
areas greater than 50% of the gross enclosed
diaphragm area, or changes in effective diaphragm
stiffness of more than 50% from one story to the next.
Design forces for lateral force connections to be
increased 25% in Design Categories D, E, & F.
39 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Type 4: Out-of-Plane Offsets
Discontinuities in a lateral
force resistance path, such
as out-of-plane offsets of
the vertical elements.
Design forces for lateral
force connections to be
increased 25% in Design
Categories D, E, & F.
40 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Type 5: Nonparallel Systems
The vertical lateral force-
resisting elements are not
parallel to or symmetric about
the major orthogonal axes of
the lateral force resisting
system.
Analyze for forces applied in
the direction that causes the
most critical load effect for
Design Categories C - F.
41 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Vertical Irregularities
1a - Stiffness Irregularity -Soft Story
1b - Stiffness Irregularity - Extreme Soft Story
2 - Weight (Mass) Irregularity
3 - Vertical Geometry Irregularity
4 - In-plane Discontinuity in Vertical Lateral Force
Resisting Elements
5 - Discontinuity in Capacity - Weak Story
42 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Type 1: Stiffness Irregularities
1a - Soft Story
the lateral stiffness is less than
70% of that in the story above
or less than 80% of the average
stiffness of the three stories
above.
1b - Extreme Soft Story
the lateral stiffness is less than
60% of that in the story above
or less than 70% of the average
stiffness of the three stories
above.
Not permitted in Design
Categories E & F 43 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Type 2: Weight (Mass) Irregularity
Mass irregularity shall be considered to exist where the effective mass of any story is more than 150% of the effective mass of an adjacent story. A roof that is lighter than the floor below need not be considered.
44 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Type 3: Vertical Geometry
Irregularity
Vertical geometry
irregularity shall be
considered to exist where
the horizontal dimension of
the lateral force-resisting
system in any story is
more than 130% of that in
an adjacent story.
45 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Type 4: In-Plane Discontinuity in Vertical
Lateral Force Resisting Elements
An in-plane offset of the lateral force-resisting elements greater than the length of those elements or a reduction in stiffness in the resisting element in the story below.
Design forces for lateral force connections to be increased 25% in Design Categories D, E, & F.
46 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Type 5: Discontinuity in
Capacity - Soft Story
A weak story is one in which the
story lateral strength is less than
80% of that in the story above. The
story strength is the total strength of
all seismic-resisting elements
sharing the story shear for the
direction under consideration.
Do not confuse STIFFNESS with
STRENGTH.
Not permitted in Design Categories
E & F.
47 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Equivalent Force Method (ASCE 7-05 12.8)
48 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Base Shear Determination
Base Shear, V = CsW
Where:
Cs = seismic response coefficient
W = the effective seismic weight, including
applicable portions of other storage and snow
loads (See ASCE 7-05 12.7.2)
See ASCE 7-05 12.8.1
49 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Seismic Weight, W
W is to include:
all dead load (all permanent components of the
building, including permanent equipment)
25% of any design storage floor live loads except
for floor live load in public garages and open
parking structures.
If partition loads are considered in floor design, at
least 10 psf is to be included.
A portion of the snow load (20% pf minimum) in
regions where the flat roof snow load exceeds 30
psf.
See ASCE 7-05 12.7.2
50 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Seismic Response Coefficient, Cs
Cs = SDS /(R/I)
Cs need not exceed
SD1/(T(R/I)) for T < TL
SD1TL/(T2(R/I)) for T > TL
Cs shall not be taken less than
Max[0.044SDSI, 0.01] for S1 < 0.6g
0.5S1/(R/I) for S1 > 0.6g
See ASCE 7-05 12.8.1.1
See also ASCE 7-05 Supplement No. 2 51 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Response Modification
Coefficient, R
The response modification factor, R, accounts for the dynamic
characteristics, lateral force resistance, and energy dissipation capacity
of the structural system.
Can be different for different directions.
See ASCE 7-05 12.2
52 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Fundamental Period, T
May be computed by analytical means
May be computed by approximate means, Ta
Where analysis is used to compute T:
T < Cu Ta
May also use Ta in place of actual T
53 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Approximate Fundamental
Period, Ta
An approximate means may be used.
Ta = CThnx
Where:
CT = Building period coefficient.
hn = height above the base to the highest level of the
building
for moment frames not exceeding 12 stories and having a
minimum story height of 10 ft, Ta may be taken as 0.1N, where
N = number of stories.
For masonry or concrete shear wall buildings use eq 12.8-9
Ta may be different in each direction.
See ASCE 7-05 12.8.2
54 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Building Period Coefficient, CT
See ASCE 7-05 12.8.2
55 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Base Shear Summary
V = CsW
W = Building Seismic Weight
Max[0.044SDSI,0.01] or 0.5S1/(R/I) < SDS/(R/I) < SD1/(T(R/I)) or TLSD1/(T2(R/I))
From Design Spectrum
From map
R from Table 12.2-1 based
on the Basic Seismic-Force-
Resisting System
Numerical Analysis or Ta
= CThnx or Ta = 0.1N
CT = 0.028, 0.016, 0.030, or
0.020
hn = building height
N = number of storys
I from Table 11.5-1 based on
Occupancy Category
Vertical Distribution of Base Shear
For short period buildings the vertical
distribution follows generally follows the
first mode of vibration in which the force
increases linearly with height for evenly
distributed mass.
For long period buildings the force is
shifted upwards to account for the
whipping action associated with
increased flexibility
See ASCE 7-05 12.8.3
57 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Story Force, Fx
Fx = CvxV
Where Cvx = Vertical Distribution Factor
Wx = Weight at level x
hx = elevation of level x above the base
k = exponent related to structure period
When T < 0.5 s, k =1, When T > 2.5 s, k =2,
Linearly interpolate when 0.5 < T < 2.5 s
Cvx
Wx
hx
k
1
n
i
Wi
hi
k
=
58 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Story Shear, Vx
Story shear, Vx, is the shear force at a given story
level
Vx is the sum of all the forces above that level.
59 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Horizontal Distribution
Being an inertial force, the Story Force, Fx, is
distributed in accordance with the distribution
of the mass at each level.
The Story Shear, Vx, is distributed to the
vertical lateral force resisting elements based
on the relative lateral stiffnesses of the
vertical resisting elements and the
diaphragm.
See ASCE 7-05 12.8.4
60 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Torsion
The analysis must take into account any torsional effects
resulting from the location of the masses relative to the
centers of resistance.
In addition to the predicted torsion, accidental torsion must
be applied for structures with rigid diaphragms by assuming
the center of mass at each level is moved from its actual
location a distance equal to 5% the building dimension
perpendicular to the direction of motion.
Buildings of Seismic Design Categories C, D, E, and F with
torsional irregularities are to have torsional moments
magnified.
See ASCE 7-05 12.8.4.1-3
61 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Using the results of the Seismic
Analysis
“The effects on the structure and its
components due to gravity loads and seismic
forces shall be combined in accordance with
the factored load combinations as presented
in ASCE 7 except that the effect of seismic
loads, E, shall be as defined herein.”
62 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Overturning
The effects of overturning must be considered.
The overturning moment at any level is the sum of the
moments at that level created by the Story Forces at each
level above it.
See ASCE 7-05 12.8.5
63 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
ASCE 7 Load Combinations which
include Seismic Effects
LRFD
5: 1.2D + 1.0E + L + 0.2S
7: 0.9D + 1.0E
ASD
5: D + (W or 0.7E)
6: D + 0.75(W or 0.7E) + 0.75L + 0.75(Lr or S or R)
8: 0.6D + 0.7E
See ASCE 7-05 2.3 & 2.4
64 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
Definition of E
When Seismic effects and Dead Load effects
are additive:
E = Eh + Ev = DQE + 0.2SDSD
When Seismic effects and Dead Load effects
counteract:
E = Eh - Ev = DQE - 0.2SDSD
QE = Effect of horizontal seismic forces
D = the reliability factor
See ASCE 7-05 12.4
65 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05
The Reliability Factor, D
The reliability factor is intended to account for redundancy in the
structure.
The factor, D, may be taken as 1.0 for eight cases listed in
ASCE 7-05 12.3.4.1, including Seismic Design Categories A-C.
For structures of Seismic Design Categories D-F:
D = 1.3
With listed exceptions (ASCE 7-05 12.3.4.2)
See ASCE 7-05 12.3.4
66 ASCE 7-05 Seismic Provisions - A Beginner's
Guide to ASCE 7-05