12
Owner’s Manual 1111 W. 35th Street, Chicago, IL 60609 USA www.tripplite.com/support Important Safety Instructions 2 Installation 3 Basic Operation 6 Battery Replacement 11 Storage and Service 11 Audio/Video Pure Sine Wave UPS Systems • Intelligent, True On-Line Operation • Pure Sine-Wave Output • Zero Transfer Time • 1000VA - 2200VA Capacities • Extended-Run Options Warranty Registration 12 Copyright ©2009 Tripp Lite. All rights reserved. Troubleshooting 10 Warranty Registration: register online today for a chance to win a FREE Tripp Lite product— www.tripplite.com/warranty Not suitable for mobile applications. 200907169 93-2615.indd 1 8/11/2009 10:14:56 AM

arranty chance anty Owner’s Manual - Tripp Liteonly Tripp Lite-recommended battery packs of the correct voltage and type. Do not connect or disconnect battery packs when the UPS

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: arranty chance anty Owner’s Manual - Tripp Liteonly Tripp Lite-recommended battery packs of the correct voltage and type. Do not connect or disconnect battery packs when the UPS

Owner’s Manual

1111 W. 35th Street, Chicago, IL 60609 USA www.tripplite.com/support

Important Safety Instructions 2

Installation 3

Basic Operation 6

Battery Replacement 11

Storage and Service 11

Audio/Video Pure Sine Wave UPS Systems

• Intelligent, True On-Line Operation• Pure Sine-Wave Output

• Zero Transfer Time• 1000VA - 2200VA Capacities

• Extended-Run Options

Warranty Registration 12

Copyright ©2009 Tripp Lite. All rights reserved.

Troubleshooting 10

Warranty

Registratio

n:

re

gister o

nline today f

or a ch

ance

to win a FREE Tr

ipp Lite product—

www.tri

pplite.co

m/warranty

Not suitable for mobile applications.

200907169 93-2615.indd 1 8/11/2009 10:14:56 AM

Page 2: arranty chance anty Owner’s Manual - Tripp Liteonly Tripp Lite-recommended battery packs of the correct voltage and type. Do not connect or disconnect battery packs when the UPS

UPS Location Warnings• InstallyourUPSindoors,awayfromexcessmoistureorheat,conductivecontaminants,dustordirect

sunlight.

• Forbestperformance,keeptheindoortemperaturebetween32ºFand104ºF(0ºCand40ºC).

• LeaveadequatespacearoundallsidesoftheUPSforproperventilation.

• Donotmountunitwithitsfrontorrearpanelfacingdown(atanyangle).Mountinginthismannerwill seriouslyinhibittheunit’sinternalcooling,eventuallycausingproductdamagenotcoveredunderwarranty.

UPS Connection Warnings• ConnectyourUPSdirectlytoaproperlygroundedACpoweroutlet.DonotplugtheUPSintoitself;

thiswilldamagetheUPS.

• DonotmodifytheUPS'splug,anddonotuseanadapterthatwouldeliminatetheUPS’sgroundonnection.

• DonotuseextensioncordstoconnecttheUPStoanACoutlet.YourwarrantywillbevoidedifanythingotherthanTrippLitesurgesuppressorsareusedtoconnectyourUPStoanoutlet.

• IftheUPSreceivespowerfromamotor-poweredACgenerator,thegeneratormustprovideclean,filteredoutput.

Equipment Connection Warnings• Useofthisequipmentinlifesupportapplicationswherefailureofthisequipmentcanreasonablybe

expectedtocausethefailureofthelifesupportequipmentortosignificantlyaffectitssafetyor effectivenessisnotrecommended.Donotusethisequipmentinthepresenceofaflammable anestheticmixturewithair,oxygenornitrousoxide.

• DonotconnectsurgesuppressorstotheoutputofyourUPS.ThismightdamagetheUPSandwillvoidthesurgesuppressorandUPSwarranties.However,TrippLitehasapprovedtheconnectionofextensioncordsand/orourHT3100PCPowerConditioningCenterattheoutputofthisUPSforgreateraccessibilityandtoincreasethenumberofbatterybackupsupportedoutlets.*Theuseofextensioncordsisapprovedforremotepowerneeds,aslongastheextensioncordissizedproperly(byusingproperlygaugedwire)andproperlyconnected(byhavinga3-pronggroundedplugononeendanda3-prongreceptacleontheotherendofthiscord).TheUPSitselfmustbedirectlyconnectedtoaproperlygroundedwalloutlet.* The total number of components connected should not exceed the UPS capacity. This will overload your UPS system.

Battery Warnings• Batteriescanpresentariskofelectricalshockandburnfromhighshort-circuitcurrent.Observe

properprecautions.Donotdisposeofthebatteriesinafire.DonotopentheUPSorbatteries.Donotshortorbridgethebatteryterminalswithanyobject.UnplugandturnofftheUPSbeforeperformingbatteryreplacement.Usetoolswithinsulatedhandles.Therearenouser-serviceablepartsinsidetheUPS.Batteryreplacementshouldbeperformedonlybyauthorizedservicepersonnelusingthesamenumberandtypeofbatteries(sealedLead-Acid).Thebatteriesarerecyclable.RefertoyourlocalcodesfordisposalrequirementsorintheUSAonlycall1-800-SAV-LEADor1-800-8-BATTERY(1-800-822-8837)orvisitwww.rbrc.comforrecyclinginformation.TrippLiteoffersacompletelineofUPSSystemReplacementBatteryCartridges(R.B.C.).VisitTrippLiteontheWebatwww.tripplite.com/support/battery/index.cfmtolocatethespecificreplacementbatteryforyourUPS.

• Duringhot-swapbatteryreplacement,theUPSwillnotprovidebackuppowerintheeventofablackoutorotherpowerinterruptions.

• DonotoperateUPSwithoutbatteries.

• Whenaddingexternalbatterypackstoselectmodelswithexternalbatterypackconnectors,connectonlyTrippLite-recommendedbatterypacksofthecorrectvoltageandtype.DonotconnectordisconnectbatterypackswhentheUPSisoperatingonbatterypower.

SAVE THESE INSTRUCTIONSThismanualcontainsinstructionsandwarningsthatshouldbefollowedduringtheinstallation,operationandstorageofallTrippLiteUPSSystems.Failuretoheedthesewarningswillvoidyourwarranty.

2

Important Safety Instructions

200907169 93-2615.indd 2 8/11/2009 10:14:56 AM

Page 3: arranty chance anty Owner’s Manual - Tripp Liteonly Tripp Lite-recommended battery packs of the correct voltage and type. Do not connect or disconnect battery packs when the UPS

Mountyourequipmentineithera4-postor2-postrackorrackenclosure.Theusermustdeterminethefitnessofhardwareandproceduresbeforemounting.Ifhardwareandproceduresarenotsuitableforyourapplication, contact the manufacturer of your rack or rack enclosure.The procedures described in thismanualareforcommonrackandrackenclosuretypesandmaynotbeappropriateforallapplications.

4-Post Mounting

AllUPSmodelsincludehardwarerequiredtomountina 4-post rack. Select models include an adjustablerackmount shelf kit to provide additional support. If your UPS model does not include an adjustable rackmount shelf kit, skip steps 1 and 2.

Connectthetwosegmentsofeachshelf A usingtheincluded screws and nuts B . Leave the screwsslightlyloosesothattheshelvescanbeadjustedinthenextstep.

Adjusteachshelftofityourrack,thenmountthemin the lowestavailablespaceofyourrackwith thescrews,nutsandwashersprovided C .Notethatthesupport ledges should face inward. Tighten thescrewsthatconnecttheshelfsegments B .

Attachmountingears D tothefrontmountingholesofyourequipment E usingthescrewsprovided F

.Theearsshouldfaceforward.

Usinganassistantifnecessary,liftyourequipmentandslideitontothemountingshelves.Attachyourequipment to the rack by using the appropriatehardware G throughitsmountingearsandintotherackrails.

2-Post Mounting

Ifyoumount theUPSina2-postrack, it requires theadditionofaTrippLite2-PostRackmountInstallationKit (model:2POSTRMKITWM, sold separately).SeeInstallationKitowner’smanualfor2-postrackmountingprocedures.

Your UPS can be mounted in an upright towerpositionwithoptionalbasestandssoldseparatelybyTrippLite(Model#2-9USTAND).WhenmountingtheUPSonadjustablebase stands,make sure thatthecontrolpanelistowardthetop.Thecontrolpanelmay be rotated to make it easier to read. Insert asmall screwdriver or similar tool in the slots oneithersideofthepanel,popitout,rotateit,andpopitbackintoplaceasshown.

WARNING!All UPS systems are extremely heavy. Use caution when lifting and mounting. User must properly stabilize the UPS when lifting and mounting.

Rack Mounting

3

Installation

A

B

C

B

E

D F

G

1

2

3

4

1

2

3

4

5

5

Tower Mounting

200907169 93-2615.indd 3 8/11/2009 10:14:58 AM

Page 4: arranty chance anty Owner’s Manual - Tripp Liteonly Tripp Lite-recommended battery packs of the correct voltage and type. Do not connect or disconnect battery packs when the UPS

Important Safety InstructionsConnection and Start-Up

Plug your UPS’s line cord into an electrical outlet.Your UPS must be connected to a dedicated circuit ofsufficient amperage.Note,however, that theselectmodelsmaybe fittedwithdifferentplug types.Refer to the“OPRating/ Plug Rating” chart printed on the top of yourUPS.

Once your UPS is plugged in, the fan and all IndicatorLights will turn ON. The “LINE” and “LOAD ACTIVEMETER”LEDswillilluminate andtheUPSwillemitabeeptoindicatenormaloperation.However,powerisnotsuppliedto yourUPS’sACoutletsuntiltheUPSisturnedon.

Plug your equipment into your UPS.YourUPSisdesignedtosupportaudio/videosystemsandtheirassociatedservers,MediaCenterPCs,andaTrippLiteHT3100PCorHT7300PCPowerConditioningCenteronly.The total number of components connected should notexceedUPScapacity.ThiswilloverloadyourUPSsystem.YouwillalsooverloadyourUPSifyouconnecthouseholdappliancestotheUPS'soutlets.

Turn your UPS ON:• Pressthe“ON/TEST”Button

• Holditforseveralsecondsuntilyouhearabeep

• Releaseit

Your UPS will begin providing AC power to its outlets. The “ON LINE” LED will illuminate.

Note: The UPS system will function properly upon initial startup, however, maximum runtime for the unit’s battery will only be accessible after it has been charged for 24 hours.

YourUPSwillfunctionproperlywithouttheseconnections.

Phone/Network Line Surge Suppression (Select Models)TheseRJ-45jacksprotectconnectedequipmentfromsurges onaphoneornetworkline.*Usingappropriatenetwork cords,connectyourwalljacktotheUPSjackmarkedIN andyourequipmenttotheUPSjackmarkedOUT.Make surethattheequipmentyouconnecttotheRJ-45jacksisalsoprotectedontheACpowerline.* Not compatible with PoE (Power Over Ethernet) applications.

CAUTIONRisk of electric shockSee top of unit for cautionary markings

WARNINGCONNECT 48 VDC

BATTERY SYSTEMS ONLYCONNECTING OTHERSYSTEMS WILL VOID

WARRANTY

30A

Your model may differ.1

1

2

3

2

3

Your model may differ.

Installation (continued)

4

Optional Connections

1

CAUTIONRisk of electric shockSee top of unit for cautionary markings

WARNINGCONNECT 48 VDC

BATTERY SYSTEMS ONLYCONNECTING OTHERSYSTEMS WILL VOID

WARRANTY

30A

1

200907169 93-2615.indd 4 8/11/2009 10:14:59 AM

Page 5: arranty chance anty Owner’s Manual - Tripp Liteonly Tripp Lite-recommended battery packs of the correct voltage and type. Do not connect or disconnect battery packs when the UPS

5

Optional Connections (continued)

USB and RS-232 Serial CommunicationsUse the includedUSBcable (see 2a )and/orDB9serialcable(see 2b )toconnecttheUPStoaMediaCenter PC, home automation system or server.InstalltheTrippLitePowerAlertSoftwareappropriateto your equipment's operating system. Your UPSmayfeaturetwocommunicationports;theadditionalport can be used to connect the UPS to a secondhomeentertainmentorhomeautomationPCthathasPowerAlertSoftwareinstalled.Formoreinformation,consultyourPowerAlertsmanual.

EPO Port Connection (Select Models)This optional feature is only for those applicationsthatrequireconnectiontoahomeautomation/homesecurityEmergencyPowerOff(EPO)circuit.Whenthe UPS is connected to this circuit, it enablesemergency shutdown of the UPS's inverter. Usingthe cable provided, connect the EPO port of yourUPS(see 3a )toauser-suppliednormallyclosedornormally open switch according to the circuitdiagram (see 3b ).The EPO port is not a phone line surge suppressor; do not connect a phone line to this port.

External Battery Connection Check to ensure that the external batteries you areconnecting match the voltage listed on your UPS'sbattery connector. All UPS models come with arobust internal battery system; all models featureconnectors that accept optional external batterypacks (sold separately from Tripp Lite) to provideadditional runtime. Adding external batteries willincrease recharge time as well as runtime. See thebatterypackowner'smanualforcompleteinstallationinstructions.Makesurecablesarefullyinsertedintotheir connectors. Small sparks may result duringbatteryconnection;thisisnormal.Donotconnectordisconnect battery packs when the UPS is runningonbatterypower.

2

3

CAUTIONRisk of electric shockSee top of unit for cautionary markings

WARNINGCONNECT 48 VDC

BATTERY SYSTEMS ONLYCONNECTING OTHERSYSTEMS WILL VOID

WARRANTY

30A

48V/26A

2b

4

Your model may differ.

Your model may differ.

Installation (continued)

4

CAUTIONRisk of electric shockSee top of unit for cautionary markings

WARNINGCONNECT 48 VDC

BATTERY SYSTEMS ONLYCONNECTING OTHERSYSTEMS WILL VOID

WARRANTY

30A

2a Your model may differ.

CAUTIONRisk of electric shockSee top of unit for cautionary markings

WARNINGCONNECT 48 VDC

BATTERY SYSTEMS ONLYCONNECTING OTHERSYSTEMS WILL VOID

WARRANTY

30A

3a Your model may differ.

4-5

3b

200907169 93-2615.indd 5 8/11/2009 10:15:01 AM

Page 6: arranty chance anty Owner’s Manual - Tripp Liteonly Tripp Lite-recommended battery packs of the correct voltage and type. Do not connect or disconnect battery packs when the UPS

Front Panel Switches

“ON/TEST” Button:ThisswitchcontrolsfourseparateUPSfunctions:

UPS Power ON

ToturntheUPSon,pressthisbutton,holditforseveralsecondsuntilyouhearabeep,thenreleaseit.The“ONLINE”LEDwillilluminate.

UPS Self-Test

Duringnormalon-lineoperation,pressthisbuttonandholdituntilyouhearabeep.Thisinitiatesa10-secondself-testofthebattery.TheUPSwillshifttobatterypower(allLEDswillilluminate)fortenseconds.

Alarm Silence

TosilencetheUPS“on-battery”alarm,pressthisbuttonandholdituntilyouhearabeep.

UPS Cold Start

TouseyourUPSasastand-alonepowersourcewhenACpowerisunavailable(i.e.duringablackout),pressthisbuttonandholdituntilyouhearabeep.TheUPSwillthenprovidebatterypowertoitsoutlets.*

* The “ON BATT” Indicator Light will be illuminated since your UPS will be operating from battery power.

“OFF” Button:ThisbuttonturnspowerOFFattheUPSreceptacles.Pressthis switch, hold it until you hear a beep, then release it. The UPS willcontinuechargingandthefanwillcontinuetocoolinternalcomponentsevenafter you turn the UPS receptacles off. To turn the UPS OFF completely,including the charger, disconnect the UPS’s power cord after pressing the“OFF”switch.

“ON LINE” LED:ThisgreenlightwillilluminateconstantlytoindicatetheUPS is performing normal on-line operation (filtering and resynthesizingincomingAClinevoltagetoprovidepuresinewaveoutput).Whenthislightis illuminated, you canmonitor the load level ofyourUPSon the “LOADACTIVEMETER”LEDs.

“LINE” LED: This green light will illuminate constantly to indicate theutilitysuppliedAClinevoltageatyourwalloutletisnominal.Itwillflashifthelinevoltageisoutsidethenominalrange(eithertoolowortwohigh).NoactionisrequiredonyourpartwhentheLEDflashes;theUPScontinuouslyandautomaticallyfiltersAClinepowertoprovideyourequipmentwithpuresinewaveACpower,regardlessofbrownoutorovervoltageconditions.Ifthislightisoff,thenAClinevoltageisnotpresent(blackout)orisatanextremelyhighvoltage,andtheUPSwillprovideconnectedequipmentwithpowerfrombattery.

Front Panel Indicator Lights

Basic Operation

6

200907169 93-2615.indd 6 8/11/2009 10:15:01 AM

Page 7: arranty chance anty Owner’s Manual - Tripp Liteonly Tripp Lite-recommended battery packs of the correct voltage and type. Do not connect or disconnect battery packs when the UPS

7

Front Panel Indicator Lights continued

“BYPASS” LED:ThisyellowlightwillflashtoindicatethattheUPS’sDC/AC inverter is deactivated and the UPS is in the “Bypass” mode. DuringnormaloperationthisLEDwilllightbrieflywhentheunitispluggedin,butifaninternalfaultoroverloadoccursthislightwillflashconstantlytoshowthatconnectedequipmentwillreceivefilteredACmainspower,butwillnotreceivebatterypowerduringablackout.Inthiscase,contactTrippLiteforservice.

“FAULT” LED (select models only):ThisredlightwillflashwhenyourUPSdetectsaninternalfault(overheating,overvoltages,etc.)orwhenitdetectsawiringfault inyourwalloutlet (reversedphases,missingground,etc.) TheUPSwillonlydetectwiringfaultswhenitispluggedintoautilityoutletbutnot turned ON. If the light persists after restarting the UPS, contact anelectriciantochecktheACline.YourUPSwillidentifythepresenceofmost(butnotall)wiringfaults.

“LOAD ACTIVE METER” LED:ThisgreenlightwillilluminatewhenyourUPSisreceivingACpowertoindicatethatthesetoffourdual-functionLEDsisdisplayingtheloadlevelofyourUPS.

“BATT ACTIVE METER” LED:ThisgreenlightwillilluminatewhenyourUPS is operating from battery power to indicate that the set of four dual-functionLEDsisdisplayingthebatterychargelevelofyourUPS.Note: the“ONBATT”LEDwillalsobeilluminated.

“OVERLOAD” LED:ThisredlightwillilluminateconstantlytoindicatethatyourUPS’scapacityhasbeenexceededwhileit is inon-lineoperation.TheUPSalarmwillbeepcontinuously. Immediately removeoverloaduntil lightandalarmgoesoff.Ifyoudonotimmediatelyremovetheoverload,theUPSwilltransferfromon-linetobypassoperation.

“BATT LOW” LED: This yellow light will illuminate when your UPS’sbatterychargelevel is low.TheUPSalarmwillbeepuntileither thebatterychargeisdepletedorthebatteriesareadequatelyrecharged.

“ON BATT” LED:ThisgreenlightwillilluminateconstantlytoindicatethatAClinevoltageisnotpresentandyourUPSisprovidingyourequipmentwithbatterypower.TheUPSwillalsobeepeverytwoseconds,unlesssilencedbythe“ON/TEST”Button.Whenthislightis illuminated,youcanmonitorthebatterychargelevelofyourUPSonthe“BATTACTIVEMETER”LEDs.

Basic Operation (continued)

200907169 93-2615.indd 7 8/11/2009 10:15:03 AM

Page 8: arranty chance anty Owner’s Manual - Tripp Liteonly Tripp Lite-recommended battery packs of the correct voltage and type. Do not connect or disconnect battery packs when the UPS

Rear Panel

“REPLACE BATT” LED:ThisredlightwillilluminateconstantlyandtheUPSalarmwillbeepevery2secondsifyourUPS’smicroprocessordetectsabatteryfaultorifyourUPSfailstheautomaticself-test(afteryouturnyourUPSON)andtheUPSbatteryislessthanfullycharged.LettheUPSsystemcharge for at least 12 hours and perform a self test using the “ON/TESTButton”asdescribedonpage6.Ifthelightcontinuestostayon,contactTrippLiteforservice. Accessory Slot:Removethesmallcoverpanelfromthisslottouseoptionalaccessories to remotely monitor and control your UPS. Contact Tripp LiteCustomerSupportat(773)869-1234formoreinformation,includingalistofavailableSNMP,networkmanagementandconnectivityproducts.

External Battery Pack Connector (configuration varies by model):Usetoconnect optional Tripp Lite Battery Packs for additional runtime. ContactTrippLiteCustomerSupportat(773)869-1234fortheappropriateTrippLitebatterypacktoconnect.RefertoinstructionsavailablewiththeBatteryPackforcompleteconnectioninformationandsafetywarnings.

Fan:ThefancoolstheUPS’sinternalcomponents.Itisalwaysonwhenlinepowerispresent.

Input Circuit Breaker Switch:This resettablebreakerpreventshigh inputcurrent from damaging the UPS or the attached load. If this breaker trips,makesureyourUPSisconnectedtoACpowerofthepropervoltagebeforeresettingthecircuitbreakerbypushingthebreakerswitchin.

Ground Screw: Use this to connect any equipment that requires a chassisground.

Output Circuit Breakers Switches (HTR22-3U): These resettable circuitbreakersprotectyourUPSfromoutputoverload.Ifoneorbothbreakerstrip,removesomeoftheloadonthecircuit(s)andallowtheUPStocoolbeforepressingthebreakerswitch(es)intoreset.

Input Cord:ThispermanentlyattachedpowercordconnectsyourUPStoapoweroutlet.

Front Panel Indicator Lights continued

Basic Operation (continued)

8

200907169 93-2615.indd 8 8/11/2009 10:15:04 AM

Page 9: arranty chance anty Owner’s Manual - Tripp Liteonly Tripp Lite-recommended battery packs of the correct voltage and type. Do not connect or disconnect battery packs when the UPS

9

Rear Panel continued

AC Receptacles (Varied by Model): These15-,20-and30-ampreceptaclesprovideyourconnectedequipmentwithpuresine-waveACoutput fromtheAClineduringnormaloperationandfrombatterypowerduringblackoutsandsevere brownouts. Power provided at these outlets is filtered to protectconnectedequipmentagainstdamagingsurgesandlinenoise.Thereceptaclesare divided into numbered load banks, as labelled on the unit. UsingPowerAlertsoftwareandcabling,loadbanksoneandtwomaybeindividuallyturned off and on from a remote location, allowing users to reset or rebootconnectedequipment.

Phone/Network Line Surge Suppression Jacks: If your UPS is equippedwiththesejacks,theywillprotectconnectedequipmentagainstsurgesoveraphoneornetworkline.Connectingyourequipmenttothesejacksisoptional;your UPS will work properly without this connection. For connectioninstructions, see “Optional Connections” in the Installation section. Not compatible with PoE (Power Over Ethernet) applications.

USB or DB9 Communication Port (select models only):These ports canconnect your UPS to any computer for automatic file saves and unattendedshutdown in theeventofapower failure.UsewithTrippLite’sPowerAlertSoftwareandappropriateUSBorDB9cable.APowerAlertCDandUSBorDB9cablemaybeincludedwithyourUPS;ifso,inserttheCDintotheCDtrayofyourcomputerandfollowtheinstallationinstructions.IfPowerAlertSoftware and the appropriate cable did not come with your UPS, you canobtain the software FREE via the Web at www.tripplite.com. Any user-suppliedDB9pass-throughorUSBcablemaythenbeusedtoconnectyourUPStoyourcomputer.NOTE: This connection is optional. The UPS will work properly without this connection.

TheDB9portcanbeusedtomonitorandcontrolyourUPSusingeitherRS-232ordrycontactprotocols.

RS-232communicationsarecomplexbuteasytoimplementbyusingaDB9cabletoconnecttheUPStoacomputerwithTrippLitePowerAlertSoftwareinstalled.

Drycontactcommunicationsaresimple,butsomeknowledgeofelectronicsisnecessarytoconfigurethem.TheDB9port'spinassignmentsareshowninthediagramattheleft.

Units with both USB and DB9 ports: If the UPS battery is low, the UPSsendsasignalbybridgingpins1and5.Ifutilitypowerfails,theUPSsendsasignalbybridgingpins8 and5.To shut theUPSdown remotely, short pin3~pin9foratleast3.8seconds.

Units with DB9 ports only: IftheUPSbatteryislow,theUPSsendsasignalby bridging pins 1 and 5. If utility power fails, the UPS sends a signal bybridgingpins8and5.ToshuttheUPSdownremotely,senda5Vto12Vsignalonpin3(usingpin5asthenegativeground)foratleast3.8seconds.

EPO (Emergency Power Off) Port: Selectmodels featureaEPOport thatmay be used to connect the UPS to a contact closure switch to enableemergencyinvertershutdown.SeeOptionalInstallation.

NEMA 5-15ROther outlet types not shown

Communications

Basic Operation (continued)

USB Port (Select Models)

DB9 Port

200907169 93-2615.indd 9 8/11/2009 10:15:05 AM

Page 10: arranty chance anty Owner’s Manual - Tripp Liteonly Tripp Lite-recommended battery packs of the correct voltage and type. Do not connect or disconnect battery packs when the UPS

TheUPS’scontrolpanellightswillturnoninthesequencesbelowtosignalthattheUPSishavingoperationaldifficulties.

Lights (On/Flashing) and Condition Solution

On: REPLACE BATT Let the UPS system charge for at least 12 hours Condition: Replace Battery and perform a self test using the "ON/Test Switch" as described on page 6. If the light continues to stay on, contact Tripp Lite for service.

On: BATT LOW, ON BATT Prepare for imminent UPS shutdown. Condition: Battery Low

On: BYPASS, LINE, LOAD, OVERLOAD Reduce the load the UPS supports. Condition: On Bypass due to Overload

Flashing: OVERLOAD Remove the cause of the short circuit Condition: Short Circuit from the UPS output.

On: FAULT Check the utility line for wiring problems such as Condition: Wiring Fault reversed line and neutral or a missing ground.

On: FAULT, 100% Restart the UPS. If the problem persists, Condition: Battery Voltage too High contact Tripp Lite for repairs.

On: FAULT, BYPASS, LINE, 50% Restart the UPS. If the problem persists, Condition: On Bypass due to contact Tripp Lite for repairs. High Output Voltage

On: FAULT, BYPASS, LINE Restart the UPS. If the problem persists, Flashing: 50% contact Tripp Lite for repairs. Condition: On Bypass due to Low Output Voltage

On: FAULT, BYPASS, LINE, 25% Restart the UPS. If the problem persists, Condition: On Bypass due to High contact Tripp Lite for repairs. Bus Voltage

On: FAULT, BYPASS, LINE Restart the UPS. If the problem persists, Flashing: 25% contact Tripp Lite for repairs. Condition: On Bypass due to Low Bus Voltage

On: BYPASS, LINE Check the UPS to be sure that there is Flashing: FAULT adequate space for air to circulate near Condition: On Bypass due to High the vents and that the fan is working Internal Temperature properly. Restart the UPS.

Flashing: LINE This indicates that utility power is too high or low Condition: Input Abnormal for the UPS to operate in BYPASS mode, so if an inverter failure occurs, the UPS will deliver no output.

On: FAULT, 50% Restart the UPS. If the problem persists, Flashing: LINE contact Tripp Lite for repairs. Condition: No Output due to High Output Voltage and Abnormal Input

On: FAULT Restart the UPS. If the problem persists, Flashing: LINE, 50% contact Tripp Lite for repairs. Condition: No Output due to Low Output Voltage and Abnormal Input

On: FAULT, 25% Restart the UPS. If the problem persists, Flashing: LINE contact Tripp Lite for repairs. Condition: No Output due to High Bus Voltage and Abnormal Input

On: FAULT Restart the UPS. If the problem persists, Flashing: LINE, 25% contact Tripp Lite for repairs. Condition: No Output due to Low Bus Voltage and Abnormal Input

Flashing: LINE, FAULT Check the UPS to be sure that there is adequate Condition: No Output due to High space for air to circulate near the vents and that Internal Temperature and Abnormal the fan is working properly. Restart the UPS. Input If the problem persists, contact Tripp Lite for repairs.

Troubleshooting

10

200907169 93-2615.indd 10 8/11/2009 10:15:05 AM

Page 11: arranty chance anty Owner’s Manual - Tripp Liteonly Tripp Lite-recommended battery packs of the correct voltage and type. Do not connect or disconnect battery packs when the UPS

11

Battery Replacement

Under normal conditions, theoriginal battery in yourUPSwill last several years.Battery replacementshould be performed only by qualified service personnel. Refer to “Battery Warnings” in the Safetysection.ShouldyourUPSrequirebatteryreplacement,visitTrippLiteontheWebatwww.tripplite.com/support/battery/index.cfmtolocatethespecificreplacementbatteryforyourUPS.

1 Remove Front Panel

2 Disconnect Batteries

3 Remove/Dispose of Batteries

4 Add Batteries

5 Connect Batteries Attachconnectors:black-to-blackandred-to-red.

6 Replace Front Panel

1 6

2 5

3 4

Procedure

Storage and Service

FirstturnyourUPSOFF:pressthe“OFF”switchtoturnpoweroffattheUPSoutlets,thendisconnectthepowercord from thewalloutlet.Next,disconnect all equipment toavoidbatterydrain. IfyouplanonstoringyourUPSforanextendedperiodoftime,fullyrechargetheUPSbatteriesonceeverythreemonthsbypluggingtheUPSintoaliveACoutletandlettingtheUPSchargefor4-6hours.IfyouleaveyourUPSbatteriesdischargedforanextendedperiodoftime,theymaysufferpermanentlossofcapacity.

YourTrippLiteA/VUPSSystemiscoveredbythe2-yearwarrantyperioddescribedbelow.AvarietyofExtendedWarrantyandOn-SiteServiceProgramsarealsoavailablefromTrippLite.Formoreinformationonservice,visitwww.tripplite.com/support.BeforereturningyourUPSforservice,followthesesteps:

1.Reviewtheinstallationandoperationproceduresinthismanualtoinsurethattheserviceproblemdoesnotoriginatefromamisreadingoftheinstructions.

Storage

Service

200907169 93-2615.indd 11 8/11/2009 10:15:06 AM

Page 12: arranty chance anty Owner’s Manual - Tripp Liteonly Tripp Lite-recommended battery packs of the correct voltage and type. Do not connect or disconnect battery packs when the UPS

2-YEAR LIMITED WARRANTYSeller warrants this product, if used in accordance with all applicable instructions, to be free from original defects in material and workmanship for a period of 2 years (except internal UPS System batteries outside USA and Canada, 1 year) from the date of initial purchase. If the product should prove defective in material or workmanship within that period, Seller will repair or replace the product, in its sole discretion. Service under this Warranty can only be obtained by your delivering or shipping the product (with all shipping or delivery charges prepaid) to: Tripp Lite; 1111 W. 35th Street; Chicago IL 60609; USA. Seller will pay return shipping charges.

Visit www.tripplite.com/support before sending any equipment back for repair.

THIS WARRANTY DOES NOT APPLY TO NORMAL WEAR OR TO DAMAGE RESULTING FROM ACCIDENT, MISUSE, ABUSE OR NEGLECT. SELLER MAKES NO EXPRESS WARRANTIES OTHER THAN THE WARRANTY EXPRESSLY SET FORTH HEREIN. EXCEPT TO THE EXTENT PROHIBITED BY APPLICABLE LAW, ALL IMPLIED WARRANTIES, INCLUDING ALL WARRANTIES OF MERCHANTABILITY OR FITNESS, ARE LIMITED IN DURATION TO THE WARRANTY PERIOD SET FORTH ABOVE; AND THIS WARRANTY EXPRESSLY EXCLUDES ALL INCIDENTAL AND CONSEQUENTIAL DAMAGES. (Some states do not allow limitations on how long an implied warranty lasts, and some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations or exclusions may not apply to you. This Warranty gives you specific legal rights, and you may have other rights which vary from jurisdiction to jurisdiction).

Tripp Lite; 1111 W. 35th Street; Chicago IL 60609; USA

WARNING: The individual user should take care to determine prior to use whether this device is suitable, adequate or safe for the use intended. Since individual applications are subject to great variation, the manufacturer makes no representation or warranty as to the suitability or fitness of these devices for any specific application.

Visit www.tripplite.com/warranty today to register the warranty for your new Tripp Lite product. You'll be automatically entered into a drawing for a chance to win a FREE Tripp Lite product!* * No purchase necessary. Void where prohibited. Some restrictions apply. See website for details.

Regulatory Compliance Identification Numbers: For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been assigned a unique series number. The series number can be found on the product nameplate label, along with all required approval markings and information. When requesting compliance information for this product, always refer to the series number. The series number should not be confused with the marking name or model number of the product.

FCC Specifications for Models with FCC Approval: This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. The user must use shielded cables and connectors with this product. Any changes or modifications to this product not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.

FCC Part 68 Notice (United States Only): If your Modem/Fax Protection causes harm to the telephone network, the telephone company may temporarily discontinue your service. If possible, they will notify you in advance. If advance notice isn't practical, you will be notified as soon as possible. You will be advised of your right to file a complaint with the FCC. Your telephone company may make changes in its facilities, equipment, operations or procedures that could affect the proper operation of your equipment. If it does, you will be given advance notice to give you an opportunity to maintain uninterrupted service. If you experience trouble with this equipment's Modem/Fax Protection, please call Tripp Lite Technical Support at (773) 869-1234 for repair/warranty information. The telephone company may ask you to disconnect this equipment from the network until the problem has been corrected or you are sure the equipment is not malfunctioning. There are no repairs that can be made by the customer to the Modem/Fax Protection. This equipment may not be used on coin service provided by the telephone company. Connection to party lines is subject to state tariffs. (Contact your state public utility commission or corporation commission for information.)

The policy of Tripp Lite is one of continuous improvement. Specifications are subject to change without notice.

Storage and Service (continued)

Warranty Registration

1111 W. 35th Street, Chicago, IL 60609 USA www.tripplite.com/support

200907169 • 932615-EN

2.Iftheproblemcontinues,donotcontactorreturntheUPStothedealer. Instead,visitwww.tripplite.com/support

3.Iftheproblemrequiresservice,visitwww.tripplite.com/supportandclicktheProductReturnslink.FromhereyoucanrequestaReturnedMaterialAuthorization(RMA)number,whichisrequiredforservice.Thissimpleon-lineformwillaskforyourunit’smodelandserialnumbers,alongwithothergeneralpurchaserinformation.TheRMAnumber,alongwithshippinginstructionswillbeemailedtoyou.Anydamages(direct,indirect,specialorconsequential)totheUPSincurredduringshipmenttoTrippLiteoranauthorizedTrippLiteservicecenterisnotcoveredunderwarranty.UPSsystemsshippedtoTrippLiteor an authorizedTrippLite service centermust have transportation chargesprepaid.Mark theRMAnumberontheoutsideofthepackage.IftheUPSsystemiswithinthe2-yearwarrantyperiod,encloseacopyofyoursalesreceipt.ReturntheUPSforserviceusinganinsuredcarriertotheaddressgiventoyouwhenyourequesttheRMA.

200907169 93-2615.indd 12 8/11/2009 10:15:06 AM