Arico v-series Temperature Controllers

Embed Size (px)

Citation preview

  • 8/11/2019 Arico v-series Temperature Controllers

    1/4

    V Series Temperature Controllers

    User's manual

    (21)Specifications

    1 100240VAC10H, 50/60HZ

    2. 2 * 4

    3. 4

    4. 0.5% 25J )

    5. TC: J BK@@@ @@@RTD: Pt100

    6. G@ @@

    @ 250V NO:7A / NC:5A@@ @@@@Digital. DC24V/20mA

    @ 010VA05VA15V

    @ 020mAA420mA

    Alarm1/2 & Aux.outputlG

    RelayG250V NO:7A / NC:5A

    Digital VoltageGDC24V/20mA

    (* V Series output for aux. and alarm1/2 : 250V/5A)

    7.

    8. ON/OFF, PID

    9.

    10. 055J (32K130K)

    @@@@@ 10%80%

    . Power SupplyG

    DisplayG digits

    KeyG machinery keys

    AccuracyG full scale (

    Main InputG

    OutputGMain output

    RelayGVoltageG

    Analog volt.G

    Analog currentG

    FunctionGHeating and cooling

    Control ModeG

    Alarm ModeG10

    AmbientGTemperatureG

    HumidityG (non-condensing)

    (22)Wiring

    Thank you for purchasing model V Series PID

    Temperature Controller.

    Before installing, connecting or using the instrument,

    please go through this instruction manual

    carefully and use the unit in proper manner.

    VNA0000006

    ARICO Technology Co., Ltd. reserves the right to

    make any kind of design or functional modification

    at any moment without prior notice.

    Website:www.arico.com.tw E-mail:infoI arico.com.twVer.:1.0.8

    V V3

    V2 BV5

    V4

  • 8/11/2019 Arico v-series Temperature Controllers

    2/4

    (11)Faceplate (12)Key Operation

    Level Key

    Set Key

    Increment Key

    Decrement Key

    (23)PID Control

    1BEntry into level select mode and select level, and press intoparameter mode.

    2BIn parameter mode, press level key leave parameter mode to

    3BIn setting mode, press level key for saving parameter and return to

    mode.parameter

    Press for 2 sec to return to normal mode.

    1BPress set key enable set value.

    2BIn parameter mode, press set key for enable to set parameter.

    3BIn setting mode, press set key for saving parameter or settingreturn to parameter mode.digit, and

    1BIn level select mode, key to entry parameter modepress increment

    2BIn parameter mode, key for selecting parameter.press increment

    3BIn setting mode, key to increase the setting valueuntil high limit.

    press increment

    1BIn level select mode, press decrement key to entry parameter mode

    2BIn parameter mode, key for selecting parameter.press decrement

    3BIn setting mode, key to decrease the setting valueuntil low limit,,

    press decrement

    Press + at the same time for 2 sec to start or stop self-tuning.

    Press decrement key for 2 sec to start or stop control output.

    Press increment key for 2 sec to start or stop manual output.

    Press set key for 8 sec to set the pass word "0044" automatically

    Press to return to the head of level in parameter mode.

    1. Output control mode

    Main : PID Aux. : PID

    Main : on/off Aux. : on/off

    Main : on/off Aux. : PID

    Main : PID Aux. : on/off

    2. Output heating &cooling control mode

    Main :heating Aux. :cooling

    Main :cooling Aux. :heating

    Auxiliary output function assists main output function in avoiding

    the temperature out of control. They have opposite modes to

    control.

    3. Alarm Hysteresis band :

    The output cycle time is one of important factor in control.It's

    necessary to evaluate the heating and cooling system effici-

    ency to set the output cycle time.suggest that the output

    cycle time >20sec in relay output. If the output cycle time=0,

    it will be analog output mode for that the higher temperature

    stability system is desired,and the time=1~19 are for voltage

    output mode and lower stability system.

    4. Proportional Band : P

    Range=1~100 or and it 's avalible to set by user.

    5. Integral Time : I

    The time is fluctuation.I

    6. Differential Tim e : D

    Range=0~250 units,1unit=0.1sec and 0 for disable.It's

    avalible to set by user.

    7. What is the "PID" Control?

    "P" is proportional band and unit = or .It can describe

    with the following equation:

    P = [ ( SV - PV ) * 100 ] / proportional band

    "D" is differential time and unit=0.1sec. If "D"=10,10*0.1=1

    sec, it means that differential action will be executed once

    per sec. The setting is smaller and the time is shorter and

    the output percentage is fewer.

    8. PID Value Self Tuning :

    PID value self tuning has three types: The first is disable

    for self tuning,the second is only once ,and the other is

    every times after power on.

    But it only will be executed by the following situations:

    The setting value of heating system should be higher than

    the present temperature for 45 or 85 .Or the setting

    value of cooling system should be lower than the present

    tem perature for 45 or 85 .If this function was executed

    is desired,it's necessary to start this one, to set value,and

    to comfirm that the temperature range is enough to execute it, then turn off the power supply and restart the instrument,

    we will see the PID value and the flashing of decimal point

    in the right-down horn.It will be shuted after changing value

    during self tuning.

    PVGNorm al modeGPres ent temp. Value

    Level select modeGParameter level 1~4

    Parameter modeGParameter name

    SVGNormal modeGSetting valueBManual output percentage

    Parameter modeGParameter value

    OUT1GMain o utput indic ator

    OUT2GAux. output indicator

    AL1GAlarm 1 output indicator

    AL2GAlarm 2 output indicator

    Level select mode.

  • 8/11/2019 Arico v-series Temperature Controllers

    3/4

    (41)Other Parameter Function (42)Error Messages

    (32)Alarm Function (33)ON/OFF Control

    Thermocouple

    breaking

    (43)Special Function

    (44)Order Code

    In ON/OFF control type, we can

    set ON/OFF hysteresis band to

    control temperature in desired range.

    (34)Manual Control Type

    The user can force to set output percentage.

    (35)Output Function

    ON/OFF hysteresis band

    Alarm Range :

    It's avalible to set alarm

    0 to 99 in unit

    Alarm Hysteresis band :

    range from or

    It's avalible to set alarmhysteresis band from 0 to 10in unit orAnd avoid temperature tounstable and fast change incritical point.

    Alarm rang e Alarm rang e

    Alarm rang e Alarm range

    1. Relay Output :

    It's better to set output cycle time >20sec in relay output. The setting

    time is larger and the duration of relay is longer.

    2. Digital voltage Output :

    It's available to set output cycle time from 1 to 60 sec as user's

    need in digital voltage output (24V).

    3. Analog Output :

    It's available to set the high and low limits of analog output after

    the value of output cycle time equal 0. The range of analog

    output are 0~20mA or 0~10V.

    1. Password

    Password has 4 digits.The units digit controls the using ofparameter level 1~4, the tens digit controls the setting of

    Parameter level 1~4, and the other digits should be set by 0. The example is the following :

    Password = 0023The parameter level 1~3 can be used and the level 1~2 canbe set.

    *DP:Decimal point

    2. Thermocouple type

    3. Unit

    The unit : or

    4. Temperature Offset

    The tem

    perature offest range :

    -99~+99 /

    5. Main Output Percentage High Lim it :

    This function can magnify and minifyof PID control.the output percentage

    The related equation as the following: Output percentage after tuning = ( output percentage before

    it ) / 100 tuning * output percentage high lim

    6. Aux. Output Percentage High Lim it :

    This function can magnify and minify the output percentageof PID control. The related equation as the following:

    Output percentage after tuning = ( output percentage before

    7. Restore The Default :

    tuning * output percentage high limit ) / 100

    This function will restore the default from the user's settings.

    1.PID Self Tuning :The condition for starting : Present value should be lower than

    setting for 45 . Present value will flash during executingself-tuning.

    2.Manual Output Control : Under manual output control,setting value is manual output

    percentage and setting output key to tuning output percentagedirectly.

    (31)Dimension

    TC type

    Open

    Short

    JP1

    JP2

    PT type

    Short

    Open

    J0 TYPE

    J1 TYPE

    K0 TYPE

    K1 TYPE

    PT0 TYPE

    PT1 TYPE

    No alarm

    Low limit

    High limit

    Lo/Hi limit

    Low limit standby

    Lo/Hi limit standby

    Reverse Lo/Hi limit

    Absolute

    Reverse Lo limit

    Reverse Hi limit

    Reverse Absolute

    Unit: mm

    J TYPE without DP,Range: 0~900 XC / 32 1200

    J TYPE with DP, Range: 0.0~900.0 XC / 32.0~999.9 XF

    K TYPE without DP,Range: 0~1200 XC / 32~1500 XF

    K TYPE with DP, Range: 0.0~999.9 XC / 32.0~999.9 XF

    PT TYPE without DP,Range: -200~500 XC / -328~900 XF

    PT TYPE with DP, Range: -199.9~500.0 XC / -199.9~900.0 XF

    ~ XF

    Model

    1GMode

    V100G48 48 mm

    V200G48 96 mm

    V300G72 72 mm

    V400G96 96 mm

    V500G96 48 mm

    2 3GMain Output / Aux. Output

    OGNone

    RGRelay ( * )

    VGDigital volt. Output 24V/20mA

    IGAnalog current output 0~20mA, 4~20mA

    LGAnalog volt. output 0~10V, 0~5V, 1~5V

    /

    4 / 5GAlarm 1 / 2

    OGNone

    RGRelay ( * )

    VGDigital volt. output 24V/20mA

    1 2 3 4 5

  • 8/11/2019 Arico v-series Temperature Controllers

    4/4

    (36)Parameter Configuration Flow Chart

    PV

    SV:default=50C

    Level 1 Level 2 Level 3

    Main outputPercentageRange=0~100%

    Aux. outputpercentageRange=0~100%

    Alarm 1 Hi value

    Range=0~99 J /K

    Alarm 2 value

    Range=0~99J /K

    PID auto tuning:none

    :Execute once :execute every

    times

    Control mode

    See Table 1

    Main & Aux. O/PHeating/coolingModeSee Table 2

    Main O/P cycletimeRange=0~60sec

    Aux. O/P cycletimeRange=0~60sec

    Main O/P propor-Tional bandRange=0~100C/F

    Aux. O/P propor-tional bandRange=0~100C/F

    Main O/P different-ial timeRange=0~250/0.1s

    Aux. O/P D time

    Range=0~250/0.1s

    Level 4

    Alarm 1 mode

    See Table 3

    Manual O/P mode:enable

    :disable

    Alarm 1 deadbandRange=0~10 J /K

    Alarm 2 mode

    See Table 3

    Alarm 2 dead

    bandRange=0~10 J /K

    Analog O/P lowlimitRange=0~200

    Analog O/P highlimitRange=0~200

    Password

    Range=0000~9999

    Thermocoupletype

    See Table 4

    Unit= orJ K

    Input temp.offsetRange=-99~+99J/K

    Main O/P propor-tional high limitRange=0~200

    Aux. O/P propor-tional high limitRange=0~200

    Restore default:usable

    :disable

    Main output hyst-eresis bandRange:1~100J /KDisplay in on/offcontrol mode

    Aux. output hyst-eresis bandRange:1~100J/KDisplay in on/offcontrol mode

    Main output I timeRangeG0~250/0.1sec

    Aux. output I timeRangeG0~250/0.1sec

    SV low limit

    Range:Thermocouple

    Low limit ~

    (J /K)

    SV high limit:Range: ~Thermocouple high limit

    (J /K)

    ake 5 Main O/P control model

    use self tuning

    control model

    use auto tuning

    control model

    matters needing attention:

    When use At control model.

    Will have the excess temperature

    henomenon in at calculation process.

    inished until the calculation.

    he calculation period PV right

    ottom decimal point will glitter.

    Level 2

    Main & aux. output heating & cooling mode:Set the control modes of main & aux. heat-ing & cooling

    Main output cycle time : Set the cycle timeof main output.

    Aux. output cycle time : Set the cycle time

    of aux. output.

    Main output proportional band : Set thevalue P of main output proportional band.

    Main output differential time : Set the valueD of main output differential time.

    Aux. output differential time : Set the valueD of aux. output differential time.

    Aux. output proportional band : Set thevalue P of aux. output proportional band.

    Main output hysteresis band : Set thevalue of main output hysteresis bandDisplay and adjust in on/off control mode

    Aux. output hysteresis band : Set thevalue of aux. output hysteresis bandDisplay and adjust in on/off control mode

    Aux. output integral time : Set thevalue of aux. output integral time

    Main output integral time : Set thevalue of main output integral time

    SV high limit : Set the S V high limit fromSV low limit to the thermocouple highlimit

    SV low limit : Set the SV low limit fromthe thermocouple low range to SV highlimit

    Cooling delay : Set the range of PV exceedSV, the system will execute the cooling

    Control mode : Set the control modes ofmain and aux. output.

    Table 1 Output control mode

    Main : PID Aux. : PID

    Main : on/off Aux. : on/off

    Main : on/off Aux. : PID

    Main : PID Aux. : on/off

    Table 2 Output heating &cooling control mode

    Main :heating Aux. :cooling

    Main :cooling Aux. :heating

    Table 3 Alarm mode

    Table 4 Input thermocouple type

    *DP:Decimal point

    Parameter description

    Level 1

    Level 3

    Level 4

    Main output percentage : Display the perc-entage of main output, and it was controledby PID control function.

    Alarm 2 value : Set the range of alarm 2

    Aux. output percentage : Display thePercentage of aux. output.

    PID auto tuning : Execute the PID valueautomatically.

    Manual output mode : Switch usable & dis-able for manual output.

    Alarm 1 mode : Set the alarm 1 action mode

    Alarm 1 hysteresis band : Set the value ofalarm 1 hysteresis band.

    Alarm 2 mode : Set the alarm 2 action mode

    Alarm 2 hysteresis band : Set the value ofalarm 2 hysteresis band.

    Analog output low limit : Output the low limitwhen analog output

    Analog output high limit : Output the highlimit when analog output

    Password : Set the password to change theparameter using and setting.

    Thermocouple type : Set the thermocoupletype.

    Unit : or are selectable

    Input temperature offset : Set offset value toincrease or decrease the present tempera-ture.

    Main output percentage high limit : Set thepercentage high limit of main output

    Aux. output percentage high limit : Set thepercentage high limit of aux. output

    Default value : Restore default from theuser settings.

    Range=0~99 J /K

    Alarm 1 Low value

    auto tuning switch

    Yes:start AT tuning

    NO:stop AT tuning

    Main O/P

    control model

    Set Take 5

    Cooling delayRangeG0~30J /K

    Alarm 1 value : Set the low alarm range of

    alarm 1

    Alarm 1 value : Set the Hi alarm range of

    alarm 1

    Auto tuning model switch

    Main output control model:Set the Auto tuning or Self tuning

    J0 TYPE

    J1 TYPE

    K0 TYPE

    K1 TYPE

    PT0 TYPE

    PT1 TYPE

    (Take 6)

    (Take 6)

    (Take 6)

    Soft start outputtime rangeG0~60min

    Soft start output

    Percent rangeG0~100%

    Soft start output time : Heater dehumidifyTime

    Soft start output percent : Heater dehumidifyOutput percent

    (Take 6)

    No alarm

    Low limit

    High limit

    Lo/Hi limit

    Low limit standby

    Lo/Hi limit standby

    Reverse Lo/Hi limit

    Absolute

    Reverse Lo limit

    Reverse Hi limit

    Reverse Absolute

    ake 6 :the Main O/P control

    model( ) set to mode

    he PID parameter shows:

    J TYPE without DP,Range: 0~900C/32 1200F

    J TYPE with DP, Range: 0.0~900.0C/32.0~999.9F

    K TYPE without DP,Range: 0~1200C/32~1500F

    K TYPE with DP, Range: 0.0~999.9C/32.0~999.9F

    PT TYPE without DP,Range: -200~500C/-328~900F

    PT TYPE with DP, Range: -199.9~500.0C/-199.9~900.0F

    ~

    Present value

    digital filter time

    0~60 sec