Layer 2: Layer 1: Viracon VNE163 (e=0.032*, #2) SS-D: Viracon ExtremeEdge Spacer Pilkington Energy Advantage (e=0.154*, #4) 1/4" 0.56" 1/4" NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT Rendered to: TUBELITE, INC. SERIES/MODEL: TU24000 HP Thermal Storefront 90% Argon* Unit Size: 78-7/8" x 79-3/8" (2003 mm x 2016 mm) (Non-Standard Size) TYPE: Glazed Wall Systems (Site-built) 0.28 Reference must be made to Report No. C5868.01-116-46, dated 05/07/13 for complete test specimen description and data. Summary of Results Standardized Thermal Transmittance (U-Factor) Gap 1: Architectural Testing 130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax: 717-764-4129 www.archtest.com

Architectural Testing - Tubelite · SS-D: Viracon ExtremeEdge Spacer Pilkington Energy Advantage (e=0.154*, #4) 1/4" 0.56" 1/4" ... Metering Room Maximum Relative Humidity % 6

  • Upload
    ngokhue

  • View
    213

  • Download
    1

Embed Size (px)

Citation preview

Page 1: Architectural Testing - Tubelite · SS-D: Viracon ExtremeEdge Spacer Pilkington Energy Advantage (e=0.154*, #4) 1/4" 0.56" 1/4" ... Metering Room Maximum Relative Humidity % 6

Layer 2:

Layer 1: Viracon VNE163 (e=0.032*, #2)SS-D: Viracon ExtremeEdge SpacerPilkington Energy Advantage (e=0.154*, #4)

1/4"0.56"1/4"

NFRC 102-2010 THERMAL PERFORMANCETEST REPORT

Rendered to:

TUBELITE, INC.

SERIES/MODEL: TU24000 HP Thermal Storefront

90% Argon*

Unit Size: 78-7/8" x 79-3/8" (2003 mm x 2016 mm) (Non-Standard Size)

TYPE: Glazed Wall Systems (Site-built)

0.28

Reference must be made to Report No. C5868.01-116-46, dated 05/07/13 for complete testspecimen description and data.

Summary of ResultsStandardized Thermal Transmittance (U-Factor)

Gap 1:

Architectural Testing

130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax: 717-764-4129 www.archtest.com

Page 2: Architectural Testing - Tubelite · SS-D: Viracon ExtremeEdge Spacer Pilkington Energy Advantage (e=0.154*, #4) 1/4" 0.56" 1/4" ... Metering Room Maximum Relative Humidity % 6

Report Number:Test Date:

Report Date:

78-7/8" x 79-3/8" (2003 mm x 2016 mm) (Non-Standard Size)

Btu/hr·ft2·F (CTS Method)Standardized U-factor (Ust):

4878 Mackinaw Trail

Series/Model:

Overall Size:

Test Sample Identification:

Glazed Wall Systems (Site-built)Type:

C5868.01-116-46

TU24000 HP Thermal Storefront

Test Results Summary:

Client

0.28

Test Procedure: U-factor tests were performed in a Guarded Hot Box in accordance withNFRC 102-2010, Procedure for Measuring the Steady-State Thermal Transmittance ofFenestration Systems .

78.7" x 78.7" (2000 mm wide x 2000 mm high)NFRC Standard Size:

Test Sample Submitted by:

Test Sample Submitted for: Validation for Initial Certification (Production Line Unit) & Plant Qualification

Reed City, Michigan 49677

NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT

05/07/1304/16/13

Rendered to:

TUBELITE, INC.

Architectural Testing

130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax: 717-764-4129 www.archtest.com

Page 3: Architectural Testing - Tubelite · SS-D: Viracon ExtremeEdge Spacer Pilkington Energy Advantage (e=0.154*, #4) 1/4" 0.56" 1/4" ... Metering Room Maximum Relative Humidity % 6

Test Sample Description:

*Stated per Client/Manufacturer N/A Non-Applicable

Exterior Finish: Anodized

0.56"1/4"

90% Argon*

Single-Probe Method*

Gap 1:1/4"

Corner Joinery:

Gas Fill Method:

Viracon VNE163 (e=0.032*, #2)

C5868.01-116-46

Material:

Page 2 of 8

78-7/8" x 79-3/8" (Non-Standard Size)

Frame:AT (0.28"): Aluminum with Thermal Breaks - All Members

Daylight Opening:GrayGray

ExteriorGlazing Method:Exterior Color:Interior Color: Interior Finish:

SS-D: Viracon ExtremeEdge SpacerPilkington Energy Advantage (e=0.154*, #4)

Anodized

36-3/8" x 74-3/4" (x2)

Square Cut / Screws / Unsealed

Size:

Layer 1:Glazing Information:

Layer 2:

Architectural Testing

Page 4: Architectural Testing - Tubelite · SS-D: Viracon ExtremeEdge Spacer Pilkington Energy Advantage (e=0.154*, #4) 1/4" 0.56" 1/4" ... Metering Room Maximum Relative Humidity % 6

Test Sample Description: (Continued)

Weatherstripping:

Hardware:

Drainage:Size

(3.38" x 0.63") Wood block

Aluminum glazing bead

Vinyl fin

Quantity LocationDrainage Method

Page 3 of 8

Sill flashing

Two per lite frame at sill4

2

AT (0.28") Sill flashing

0.63" x 0.19" 2Weepslot

Sill

Description

2 Exterior sill

1

Jambs

Quantity Location

Description Quantity

EPDM glazing gasket

C5868.01-116-46

1 row

Location

Interior and exterior glazing perimeter

Architectural Testing

Page 5: Architectural Testing - Tubelite · SS-D: Viracon ExtremeEdge Spacer Pilkington Energy Advantage (e=0.154*, #4) 1/4" 0.56" 1/4" ... Metering Room Maximum Relative Humidity % 6

Measured Test Data

Heat Flows1. Total Measured Input into Metering Box (Qtotal) Btu/hr 2. Surround Panel Heat Flow (Qsp) Btu/hr 3. inches4.5. Metering Box Wall Heat Flow (Qmb) Btu/hr 6. EMF vs Heat Flow Equation (equivalent information) 0.0115*EMF + -0.0177. Flanking Loss Heat Flow (Qfl) Btu/hr 8. Net Specimen Heat Loss (Qs) Btu/hr

Areas1. Test Specimen Projected Area (As) ft2

2. Test Specimen Interior Total (3-D) Surface Area (Ah) ft2

3. Test Specimen Exterior Total (3-D) Surface Area (Ac) ft2

4. Metering Box Opening Area (Amb) ft2

5. Metering Box Baffle Area (Ab1) ft2

6. Surround Panel Interior Exposed Area (Asp) ft2

Test Conditions1. Average Metering Room Air Temperature (th) F2. Average Cold Side Air Temperature (tc) F3. Average Guard/Environmental Air Temperature F4. Metering Room Average Relative Humidity %5. Metering Room Maximum Relative Humidity %6. Metering Room Minimum Relative Humidity %7. Measured Cold Side Wind Velocity (Perpendicular Flow) mph8. Measured Warm Side Wind Velocity (Parallel Flow) mph9. Measured Static Pressure Difference Across Test Specimen 0.00" ± 0.04"H2O

Average Surface Temperatures1. Metering Room Surround Panel F2. Cold Side Surround Panel F

Results

55.11

Thermal Transmittance (U-factor)

929.82

Btu/hr·ft2·F0.0226

7.59

75.1170.84

9.74

69.79

31.63

8.52

-0.37

1. Thermal Transmittance of Test Specimen (Us)

NA

0.28

67.00

874.59

43.4854.98

Surround Panel Thickness48.268.00

-0.62

Surround Panel Conductance

C5868.01-116-46

Standardized Thermal Transmittance of Test Specimen (Ust) Btu/hr·ft2·F

Page 4 of 8

-0.43

7.64

71.26

12.66

2.Btu/hr·ft2·F0.29

Architectural Testing

Page 6: Architectural Testing - Tubelite · SS-D: Viracon ExtremeEdge Spacer Pilkington Energy Advantage (e=0.154*, #4) 1/4" 0.56" 1/4" ... Metering Room Maximum Relative Humidity % 6

Calculated Test Data

CTS Method1. Warm Side Emittance of Glass (e1)2. Cold Side Emittance of Glass3. Warm Side Frame Emittance*4. Cold Side Frame Emittance*5. Warm Side Sash/Panel/Vent Emittance*6. Cold Side Sash/Panel/Vent Emittance*7. Warm Side Baffle Emittance (eb1)8. Cold Side Baffle Emittance (eb2)9. Equivalent Warm Side Surface Temperature F

10. Equivalent Cold Side Surface Temperature F11. Warm Side Baffle Surface Temperature F12. Cold Side Baffle Surface Temperature F13. Measured Warm Side Surface Conductance (hh)14. Measured Cold Side Surface Conductance (hc)15. Test Specimen Thermal Conductance (Cs)16. Convection Coefficient (Kc) Btu/(hr·ft2·F1.25)17. Radiative Test Specimen Heat Flow (Qr1) Btu/hr18. Conductive Test Specimen Heat Flow (Qc1) Btu/hr19. Radiative Heat Flux of Test Specimen (qr1)20. Convective Heat Flux of Test Specimen (qc1)21. Standardized Warm Side Surface Conductance (hsth)22. Standardized Cold Side Surface Conductance (hstc)23. Standardized Thermal Transmittance (Ust)

Test Duration1.2.

*Stated per NFRC 101

9.2910.82

Btu/hr·ft2·F

N/A

3.48

The thermal performance test results were derived from 11:50 hours, 04/16/13 to 15:50hours, 04/16/13.

Btu/hr·ft2·F5.220.39

403.99

Btu/hr·ft2·F

0.92

55.00

N/A

0.28

0.84

The environmental systems were started at 06:55 hours, 04/15/13.

Btu/hr·ft2·FBtu/hr·ft2·F

5.28

The test parameters were considered stable for two consecutive four hour test periodsfrom 07:50 hours, 04/16/13 to 15:50 hours, 04/16/13.

1.19 Btu/hr·ft2·F

69.21

470.60

0.800.80

1.36

The reported Standardized Thermal Transmittance (Ust) was determined using CTS Method,per Section 8.2(A) of NFRC 102.

3.

Btu/hr·ft2·F

Btu/hr·ft2·F

C5868.01-116-46

0.84

Thermal Transmittance (U-factor)

Page 5 of 8

N/AN/A

0.32

Architectural Testing

Page 7: Architectural Testing - Tubelite · SS-D: Viracon ExtremeEdge Spacer Pilkington Energy Advantage (e=0.154*, #4) 1/4" 0.56" 1/4" ... Metering Room Maximum Relative Humidity % 6

Glass collapse determined using a digital glass and air space meter

ANSI/NCSL Z540-2-1997 type B uncertainty for this test was 1.58%.

The test sample was installed in a vertical orientation, the exterior of the specimen was exposedto the cold side. The direction of heat transfer was from the interior (warm side) to the exterior(cold side) of the specimen. The ratings were rounded in accordance to NFRC 601, NFRC Unitand Measurement Policy. The data acquisition frequency is 5 minutes.

“This test method does not include procedures to determine the heat flow due to either airmovement through the specimen or solar radiation effects. As a consequence, the thermaltransmittance results obtained do not reflect performances which are expected from fieldinstallations due to not accounting for solar radiation, air leakage effects, and the thermal bridgeeffects that have the potential to occur due to the specific design and construction of thefenestration system opening. The latter can only be determined by in-situ measurements.Therefore, it is important to recognize that the thermal transmittance results obtained from thistest method are for ideal laboratory conditions and should only be used for fenestration productcomparisons and as input to thermal performance analyses which also include solar, air leakageand thermal bridge effects.”

0.50"0.47"

Page 6 of 8

Glazing Deflection:

C5868.01-116-46

Left Glazing

Center gap width at laboratory ambientconditions on day of testing

The sample was inspected for the formation of frost or condensation, which may influence thesurface temperature measurements. The sample showed no evidence of condensation/frost atthe conclusion of the test.

Right Glazing

Estimated center gap width upon receipt ofspecimen in laboratory (after stabilization)

Edge Gap Width

0.50"

0.56" 0.56"

0.47"

0.41" 0.41"Center gap width at test conditions

Required annual calibrations for the Architectural Testing Inc. 'thermal test chamber' (ICN000001) in York, Pennsylvania were last conducted in May 2012 in accordance withArchitectural Testing Inc. calibration procedure. A CTS Calibration verification was performedJune 2012. A Metering Box Wall Transducer and Surround Panel Flanking LossCharacterization was performed December 2012.

Architectural Testing

Page 8: Architectural Testing - Tubelite · SS-D: Viracon ExtremeEdge Spacer Pilkington Energy Advantage (e=0.154*, #4) 1/4" 0.56" 1/4" ... Metering Room Maximum Relative Humidity % 6

For ARCHITECTURAL TESTING, INC.

Tested By: Reviewed By:

Ryan P. Moser Shon W. EinsigTechnician Senior Technician

Individual-In-Responsible-Charge

RPM:amgC5868.01-116-46

Attachments (pages): This report is complete only when all attachments listed are included.

Submittal Form and Drawings (13)Baffle Wiring Diagram (1)

C5868.01-116-46

"Ratings included in this report are for submittal to an NFRC licensed IA for certificationpurposes and are not meant to be used for labeling purposes. Only those values identified on avalid Certification Authorization Report (CAR) are to be used for labeling purposes."

Page 7 of 8

Architectural Testing, Inc. will service this report for the entire test record retention period. Testrecords that are retained such as detailed drawings, datasheets, representative samples of testspecimens, or other pertinent project documentation will be retained by Architectural Testing,Inc. for the entire test record retention period. The test record retention end date for this reportis April 16, 2017.

Appendix-A: Appendix-B:

Architectural Testing, Inc. is accredited by the International Accreditation Service (IAS) under thespecific test methods listed under lab code TL-144, in accordance with the recognizedInternational Standard ISO/IEC 17025:2005. The laboratory’s accreditation or test report in noway constitutes or implies product certification, approval, or endorsement by IAS.

CTS Calibration Data (1)

This report does not constitute certification of this product nor an opinion or endorsement bythis laboratory. It is the exclusive property of the client so named herein and relates only to thespecimen tested. This report may not be reproduced, except in full, without the writtenapproval of Architectural Testing, Inc.

Appendix-D: Appendix-C:

Surround Panel Wiring Diagram (1)

Architectural Testing

Page 9: Architectural Testing - Tubelite · SS-D: Viracon ExtremeEdge Spacer Pilkington Energy Advantage (e=0.154*, #4) 1/4" 0.56" 1/4" ... Metering Room Maximum Relative Humidity % 6

Revision(s)

Revision Log

Page(s)

Original Report Issue. Work requested byPiet Visser of Tubelite, Inc.

DateRev. #

C5868.01-116-46Page 8 of 8

.01R0 05/07/13 All

This report produced from controlled document template ATI 00025(a), revised 03/14/2013.

Architectural Testing

Page 10: Architectural Testing - Tubelite · SS-D: Viracon ExtremeEdge Spacer Pilkington Energy Advantage (e=0.154*, #4) 1/4" 0.56" 1/4" ... Metering Room Maximum Relative Humidity % 6

CTS Test DateCTS Size ft2

CTS Glass/Core ConductanceWarm Side Air Temperature FCold Side Air Temperature FWarm Side Average Surface Temperature FCold Side Average Surface Temperature FConvection Coefficient (Kc)Measured Cold Side Surface Conductance (hc)Measured Thermal Transmittance

4.

1.2. 43.06

06/05/12

69.813. 0.40

C5868.01-116-46Appendix A: CTS Calibration Data

Btu/hr·ft2·F

8. 0.32

5. -0.406. 54.59

Btu/hr·ft2·F

3.52

9. 5.2210. 0.30 Btu/hr·ft2·F

7.Btu/(hr·ft2·F1.25)

Page 11: Architectural Testing - Tubelite · SS-D: Viracon ExtremeEdge Spacer Pilkington Energy Advantage (e=0.154*, #4) 1/4" 0.56" 1/4" ... Metering Room Maximum Relative Humidity % 6

+1 +2 +3

+4 +5

+6 +7 +8

C5868.01-116-46Appendix B: Surround Panel Wiring Diagram

Page 12: Architectural Testing - Tubelite · SS-D: Viracon ExtremeEdge Spacer Pilkington Energy Advantage (e=0.154*, #4) 1/4" 0.56" 1/4" ... Metering Room Maximum Relative Humidity % 6

+1 +2 +3 +4 +5 +6 +7 +8 +9 +10 +11 +12 +13 +14 +15 +16 +17 +18 +19 +20 +21 +22 +23 +24 +25 +26 +27 +28 +29 +30

Appendix C: Baffle Wiring DiagramC5868.01-116-46

Page 13: Architectural Testing - Tubelite · SS-D: Viracon ExtremeEdge Spacer Pilkington Energy Advantage (e=0.154*, #4) 1/4" 0.56" 1/4" ... Metering Room Maximum Relative Humidity % 6

Appendix D: Submittal Form and DrawingsC5868.01-116-46

Page 14: Architectural Testing - Tubelite · SS-D: Viracon ExtremeEdge Spacer Pilkington Energy Advantage (e=0.154*, #4) 1/4" 0.56" 1/4" ... Metering Room Maximum Relative Humidity % 6
Page 15: Architectural Testing - Tubelite · SS-D: Viracon ExtremeEdge Spacer Pilkington Energy Advantage (e=0.154*, #4) 1/4" 0.56" 1/4" ... Metering Room Maximum Relative Humidity % 6
Page 16: Architectural Testing - Tubelite · SS-D: Viracon ExtremeEdge Spacer Pilkington Energy Advantage (e=0.154*, #4) 1/4" 0.56" 1/4" ... Metering Room Maximum Relative Humidity % 6
Page 17: Architectural Testing - Tubelite · SS-D: Viracon ExtremeEdge Spacer Pilkington Energy Advantage (e=0.154*, #4) 1/4" 0.56" 1/4" ... Metering Room Maximum Relative Humidity % 6
Page 18: Architectural Testing - Tubelite · SS-D: Viracon ExtremeEdge Spacer Pilkington Energy Advantage (e=0.154*, #4) 1/4" 0.56" 1/4" ... Metering Room Maximum Relative Humidity % 6
Page 19: Architectural Testing - Tubelite · SS-D: Viracon ExtremeEdge Spacer Pilkington Energy Advantage (e=0.154*, #4) 1/4" 0.56" 1/4" ... Metering Room Maximum Relative Humidity % 6
Page 20: Architectural Testing - Tubelite · SS-D: Viracon ExtremeEdge Spacer Pilkington Energy Advantage (e=0.154*, #4) 1/4" 0.56" 1/4" ... Metering Room Maximum Relative Humidity % 6
Page 21: Architectural Testing - Tubelite · SS-D: Viracon ExtremeEdge Spacer Pilkington Energy Advantage (e=0.154*, #4) 1/4" 0.56" 1/4" ... Metering Room Maximum Relative Humidity % 6
Page 22: Architectural Testing - Tubelite · SS-D: Viracon ExtremeEdge Spacer Pilkington Energy Advantage (e=0.154*, #4) 1/4" 0.56" 1/4" ... Metering Room Maximum Relative Humidity % 6
Page 23: Architectural Testing - Tubelite · SS-D: Viracon ExtremeEdge Spacer Pilkington Energy Advantage (e=0.154*, #4) 1/4" 0.56" 1/4" ... Metering Room Maximum Relative Humidity % 6
Page 24: Architectural Testing - Tubelite · SS-D: Viracon ExtremeEdge Spacer Pilkington Energy Advantage (e=0.154*, #4) 1/4" 0.56" 1/4" ... Metering Room Maximum Relative Humidity % 6
Page 25: Architectural Testing - Tubelite · SS-D: Viracon ExtremeEdge Spacer Pilkington Energy Advantage (e=0.154*, #4) 1/4" 0.56" 1/4" ... Metering Room Maximum Relative Humidity % 6
Page 26: Architectural Testing - Tubelite · SS-D: Viracon ExtremeEdge Spacer Pilkington Energy Advantage (e=0.154*, #4) 1/4" 0.56" 1/4" ... Metering Room Maximum Relative Humidity % 6