AQUABOXES To enable a pressure system to operate, the aquabox must be set up correctly. The pre-charge air pressure must be less than the cut-in pressure of the pump. For normal domestic type installation, the pre-charge should be approximately 3 psi, less than the cut-in pressure. When working with systems at higher pressures or with the larger horizontal aquaboxes, this difference may need to be 5, 10 or even 15 psi. The pre-charge must always be measured with the aquabox drained of water and should be check every six months. PRESSURE SYSTEMS When installing any pump in an automatic pressure system it is essential to fit a check valve (non return valve) on the suction. In addition it is always advisable to include the following in the system. 1. Isolation valve on suction. (Only necessary for flooded suction installations). 2. Isolation valve on discharge. 3. Drain cock on discharge. These valves allow maintenance to be done on the pump without the need to drain the whole system. Also during commissioning or adjusting the pressure switches, the valves allow the running of the pump to be controlled at the pump. does increase as the pressure is set higher. Empty Charging Discharging PRESSURE SWITCHES Whilst there are several different pressure switches used on INTERDAB equipment their operation is essentially the same. All have a range or main adjustment and some also have a differential adjustment. On switches with the two adjustments the range is set by the screw with the heavier or longer spring and the differential by the lighter or shorter spring. When setting a pressure switch, the range should always be set first. Turning the nut or screw clockwise will increase the pressure setting, anti-clockwise will decrease. Altering this setting will not normally change the difference between the cut-in and cut-out pressures. On some of the higher range switches the differential The differential, as the name implies, affects the difference between the cut-in and cut-out pressures. On some switches this alters the cut-in without affecting the cut-out (eg Telemechanique XMP2) whilst on others it affects the cut-out without affecting the cut-in. In either case turning the screw or nut clockwise will increase the differential whilst anti-clockwise will reduce. Thainstone Business Park, Inverurie, Aberdeenshire AB51 5GT Tel 01467 623010 Fax 01467 623011 Email [email protected]

Aquaboxes, pressure systems and pressure switches 150515

Embed Size (px)

DESCRIPTION

 

Citation preview

Page 1: Aquaboxes, pressure systems and pressure switches 150515

AQUABOXES

To enable a pressure system to operate, the aquaboxmust be set up correctly. The pre-charge air pressuremust be less than the cut-in pressure of the pump. Fornormal domestic type installation, the pre-chargeshould be approximately 3 psi, less than the cut-inpressure. When working with systems at higherpressures or with the larger horizontal aquaboxes, thisdifference may need to be 5, 10 or even 15 psi. Thepre-charge must always be measured with theaquabox drained of water and should be check everysix months.

PRESSURE SYSTEMS

When installing any pump in an automatic pressure system it is essential to fit a check valve (non return valve) on the suction. Inaddition it is always advisable to include the following in the system.

1. Isolation valve on suction. (Only necessary for flooded suction installations).2. Isolation valve on discharge.3. Drain cock on discharge.

These valves allow maintenance to be done on the pump without the need to drain the whole system. Also during commissioning oradjusting the pressure switches, the valves allow the running of the pump to be controlled at the pump.does increase as the pressure is set higher.

Empty Charging Discharging

PRESSURE SWITCHES

Whilst there are several different pressure switches used on INTERDABequipment their operation is essentially the same. All have a range ormain adjustment and some also have a differential adjustment. Onswitches with the two adjustments the range is set by the screw with theheavier or longer spring and the differential by the lighter or shorterspring.

When setting a pressure switch, the range should always be set first.Turning the nut or screw clockwise will increase the pressure setting,anti-clockwise will decrease. Altering this setting will not normallychange the difference between the cut-in and cut-out pressures. Onsome of the higher range switches the differential The differential, as thename implies, affects the difference between the cut-in and cut-outpressures. On some switches this alters the cut-in without affecting thecut-out (eg Telemechanique XMP2) whilst on others it affects the cut-outwithout affecting the cut-in. In either case turning the screw or nutclockwise will increase the differential whilst anti-clockwise will reduce.