  • —RELION® 615 SERIES

    Voltage Protection and ControlREU615Application Manual

  • Document ID: 1MRS758128Issued: 2019-04-30

    Revision: BProduct version: 5.0 FP1

    © Copyright 2019 ABB. All rights reserved

  • Copyright

    This document and parts thereof must not be reproduced or copied without writtenpermission from ABB, and the contents thereof must not be imparted to a third party,nor used for any unauthorized purpose.

    The software or hardware described in this document is furnished under a license andmay be used, copied, or disclosed only in accordance with the terms of such license.

    TrademarksABB and Relion are registered trademarks of the ABB Group. All other brand orproduct names mentioned in this document may be trademarks or registeredtrademarks of their respective holders.

    WarrantyPlease inquire about the terms of warranty from your nearest ABB representative.

    www.abb.com/relion

    http://www.abb.com/relion

  • Disclaimer

    The data, examples and diagrams in this manual are included solely for the concept orproduct description and are not to be deemed as a statement of guaranteed properties.All persons responsible for applying the equipment addressed in this manual mustsatisfy themselves that each intended application is suitable and acceptable, includingthat any applicable safety or other operational requirements are complied with. Inparticular, any risks in applications where a system failure and/or product failurewould create a risk for harm to property or persons (including but not limited topersonal injuries or death) shall be the sole responsibility of the person or entityapplying the equipment, and those so responsible are hereby requested to ensure thatall measures are taken to exclude or mitigate such risks.

    This product has been designed to be connected and communicate data andinformation via a network interface which should be connected to a secure network.It is the sole responsibility of the person or entity responsible for networkadministration to ensure a secure connection to the network and to take the necessarymeasures (such as, but not limited to, installation of firewalls, application ofauthentication measures, encryption of data, installation of anti virus programs, etc.)to protect the product and the network, its system and interface included, against anykind of security breaches, unauthorized access, interference, intrusion, leakage and/ortheft of data or information. ABB is not liable for any such damages and/or losses.

    This document has been carefully checked by ABB but deviations cannot becompletely ruled out. In case any errors are detected, the reader is kindly requested tonotify the manufacturer. Other than under explicit contractual commitments, in noevent shall ABB be responsible or liable for any loss or damage resulting from the useof this manual or the application of the equipment.

  • Conformity

    This product complies with the directive of the Council of the European Communitieson the approximation of the laws of the Member States relating to electromagneticcompatibility (EMC Directive 2014/30/EU) and concerning electrical equipment foruse within specified voltage limits (Low-voltage directive 2014/35/EU). Thisconformity is the result of tests conducted by the third party testing laboratory Intertekin accordance with the product standard EN 60255-26 for the EMC directive, and withthe product standards EN 60255-1 and EN 60255-27 for the low voltage directive. Theproduct is designed in accordance with the international standards of the IEC 60255series.

  • Table of contents

    Section 1 Introduction.......................................................................5This manual........................................................................................ 5Intended audience.............................................................................. 5Product documentation.......................................................................6

    Product documentation set............................................................6Document revision history............................................................. 6Related documentation..................................................................7

    Symbols and conventions...................................................................7Symbols.........................................................................................7Document conventions..................................................................8

    Section 2 REU615 overview.............................................................9Overview.............................................................................................9

    Product version history..................................................................9PCM600 and relay connectivity package version........................10

    Operation functionality......................................................................10Optional functions........................................................................10

    Physical hardware............................................................................ 11Local HMI......................................................................................... 12

    Display.........................................................................................13LEDs............................................................................................14Keypad........................................................................................ 14

    Web HMI...........................................................................................14Authorization.....................................................................................16

    Audit trail......................................................................................16Communication.................................................................................18

    Self-healing Ethernet ring............................................................19Ethernet redundancy................................................................... 20Process bus.................................................................................22Secure communication................................................................24

    Section 3 REU615 standard configurations................................... 25Standard configurations....................................................................25

    Addition of control functions for primary devices and the useof binary inputs and outputs........................................................ 27

    Connection diagrams........................................................................28Standard configuration A.................................................................. 30

    Applications................................................................................. 30Functions.....................................................................................31

    Default I/O connections.......................................................... 31

    Table of contents

    REU615 1Application Manual

  • Default disturbance recorder settings.....................................33Functional diagrams.................................................................... 36

    Functional diagrams for protection......................................... 36Functional diagrams for disturbance recorder........................45Functional diagrams for control and interlocking....................45Functional diagrams for measurement functions................... 46Functional diagrams for I/O and alarm LEDs......................... 48Other functions....................................................................... 51

    Standard configuration B.................................................................. 51Applications................................................................................. 51Functions.....................................................................................53

    Default I/O connections.......................................................... 53Default disturbance recorder settings.....................................55

    Functional diagrams.................................................................... 58Functional diagrams for protection......................................... 58Functional diagrams for disturbance recorder........................62Functional diagrams for condition monitoring.........................62Functional diagrams for control and interlocking....................63Functional diagrams for measurement functions................... 67Functional diagrams for IO and alarm LEDs.......................... 69Functional diagrams for other timer logics............................. 72Other functions....................................................................... 72

    Section 4 Requirements for measurement transformers................73Current transformers........................................................................ 73

    Current transformer requirements for overcurrent protection...... 73Current transformer accuracy class and accuracy limitfactor...................................................................................... 73Non-directional overcurrent protection................................... 74Example for non-directional overcurrent protection................75

    Section 5 Protection relay's physical connections..........................77Inputs................................................................................................77

    Energizing inputs.........................................................................77Phase currents....................................................................... 77Residual current..................................................................... 77Phase voltages.......................................................................77Residual voltage.....................................................................78

    Auxiliary supply voltage input...................................................... 78Binary inputs................................................................................78RTD/mA inputs............................................................................ 80

    Outputs............................................................................................. 81Outputs for tripping and controlling..............................................81Outputs for signalling...................................................................82

    Table of contents

    2 REU615Application Manual

  • IRF...............................................................................................83

    Section 6 Glossary......................................................................... 85

    Table of contents

    REU615 3Application Manual

  • 4

  • Section 1 Introduction

    1.1 This manual

    The application manual contains application descriptions and setting guidelinessorted per function. The manual can be used to find out when and for what purpose atypical protection function can be used. The manual can also be used when calculatingsettings.

    1.2 Intended audience

    This manual addresses the protection and control engineer responsible for planning,pre-engineering and engineering.

    The protection and control engineer must be experienced in electrical powerengineering and have knowledge of related technology, such as protection schemesand principles.

    1MRS758128 B Section 1Introduction

    REU615 5Application Manual

  • 1.3 Product documentation

    1.3.1 Product documentation set

    Pla

    nnin

    g &

    pu

    rcha

    se

    Eng

    inee

    ring

    Inst

    alla

    tion

    Com

    mis

    sion

    ing

    Ope

    ratio

    n

    Mai

    nten

    ance

    Dec

    omm

    issi

    onin

    g,

    dein

    stal

    latio

    n &

    dis

    posa

    l

    Quick start guideQuick installation guideBrochureProduct guideOperation manualInstallation manualConnection diagramEngineering manualTechnical manualApplication manualCommunication protocol manualIEC 61850 engineering guidePoint list manualCyber security deployment guideline

    GUID-12DC16B2-2DC1-48DF-8734-0C8B7116124C V2 EN

    Figure 1: The intended use of documents during the product life cycle

    Product series- and product-specific manuals can be downloadedfrom the ABB Web site http://www.abb.com/relion.

    1.3.2 Document revision historyDocument revision/date Product version HistoryA/2014-05-14 4.1 First release

    B/2019-04-30 5.0 FP1 Content updated

    Download the latest documents from the ABB Web sitehttp://www.abb.com/substationautomation.

    Section 1 1MRS758128 BIntroduction

    6 REU615Application Manual

    http://www.abb.com/relionHTTP://WWW.ABB.COM/SUBSTATIONAUTOMATION

  • 1.3.3 Related documentationName of the document Document IDModbus Communication Protocol Manual 1MRS759002

    IEC 60870-5-103 Communication Protocol Manual 1MRS759001

    IEC 61850 Engineering Guide 1MRS759000

    Engineering Manual 1MRS758999

    Installation Manual 1MRS758997

    Operation Manual 1MRS758998

    Technical Manual 1YHT530004D05

    1.4 Symbols and conventions

    1.4.1 Symbols

    The electrical warning icon indicates the presence of a hazard whichcould result in electrical shock.

    The warning icon indicates the presence of a hazard which couldresult in personal injury.

    The caution icon indicates important information or warning relatedto the concept discussed in the text. It might indicate the presence ofa hazard which could result in corruption of software or damage toequipment or property.

    The information icon alerts the reader of important facts andconditions.

    The tip icon indicates advice on, for example, how to design yourproject or how to use a certain function.

    Although warning hazards are related to personal injury, it is necessary to understandthat under certain operational conditions, operation of damaged equipment may resultin degraded process performance leading to personal injury or death. Therefore,comply fully with all warning and caution notices.

    1MRS758128 B Section 1Introduction

    REU615 7Application Manual

  • 1.4.2 Document conventions

    A particular convention may not be used in this manual.

    • Abbreviations and acronyms are spelled out in the glossary. The glossary alsocontains definitions of important terms.

    • Push button navigation in the LHMI menu structure is presented by using thepush button icons.To navigate between the options, use and .

    • Menu paths are presented in bold.Select Main menu/Settings.

    • LHMI messages are shown in Courier font.To save the changes in nonvolatile memory, select Yes and press .

    • Parameter names are shown in italics.The function can be enabled and disabled with the Operation setting.

    • Parameter values are indicated with quotation marks.The corresponding parameter values are "On" and "Off".

    • Input/output messages and monitored data names are shown in Courier font.When the function starts, the START output is set to TRUE.

    • This document assumes that the parameter setting visibility is "Advanced".

    Section 1 1MRS758128 BIntroduction

    8 REU615Application Manual

  • Section 2 REU615 overview

    2.1 Overview

    The voltage protection and control relay REU615 is available in two standardconfigurations, denoted A and B. Configuration A is preadapted for voltage andfrequency-based protection schemes in utility and industrial power systems anddistribution systems including networks with distributed power generation. The Bconfiguration is designed for automatic voltage regulation of power transformersequipped with an on-load tap changer. Both configurations also feature additional CBcontrol, measuring and supervising functions. REU615 is a member of ABB’sRelion® product family and part of its 615 protection and control product series. The615 series relays are characterized by their compactness and withdrawable-unitdesign.

    Re-engineered from the ground up, the 615 series has been designed to unleash the fullpotential of the IEC 61850 standard for communication and interoperability betweensubstation automation devices. Once the standard configuration relay has been giventhe application-specific settings, it can directly be put into service.

    The 615 series relays support a range of communication protocols including IEC61850 with Edition 2 support, process bus according to IEC 61850-9-2 LE, IEC60870-5-103 and Modbus®. Profibus DPV1 communication protocol is supported byusing the protocol converter SPA-ZC 302.

    2.1.1 Product version historyProduct version Product history4.1 Product released

    5.0 FP1 • New layout in Application Configuration for all configurations• Support for IEC 61850-9-2 LE• IEEE 1588 v2 time synchronization• New controllable tap changer object available for SLD• Load profile recorder• High-speed binary outputs• Optional RTD/mA inputs for configurations A, B and Z• Profibus adapter support• Support for multiple SLD pages• Import/export of settings via WHMI• Setting usability improvements• HMI event filtering tool• IEC 61850 Edition 2• Currents sending support with IEC 61850-9-2 LE• Support for synchronism and energizing check with IEC 61850-9-2 LE• Software closable Ethernet ports• Report summary via WHMI• Additional timer, set-reset and analog value scaling functions

    1MRS758128 B Section 2REU615 overview

    REU615 9Application Manual

  • 2.1.2 PCM600 and relay connectivity package version

    • Protection and Control IED Manager PCM600 2.9 Hotfix 1 or later• REU615 Connectivity Package Ver.5.1 or later

    • Parameter Setting• Signal Monitoring• Event Viewer• Disturbance Handling• Application Configuration• Signal Matrix• Graphical Display Editor• Communication Management• IED User Management• IED Compare• Firmware Update• Fault Record tool• Load Record Profile• Lifecycle Traceability• Configuration Wizard• AR Sequence Visualizer• Label Printing• IEC 61850 Configuration

    Download connectivity packages from the ABB Web sitehttp://www.abb.com/substationautomation or directly with UpdateManager in PCM600.

    2.2 Operation functionality

    2.2.1 Optional functions

    • Arc protection (configuration A only)• Modbus TCP/IP or RTU/ASCII• IEC 60870-5-103• RTD/mA measurements and multipurpose protection (configuration B only)• IEC 61850-9-2 LE• IEEE 1588 v2 time synchronization

    Section 2 1MRS758128 BREU615 overview

    10 REU615Application Manual

    HTTP://WWW.ABB.COM/SUBSTATIONAUTOMATION

  • 2.3 Physical hardware

    The protection relay consists of two main parts: plug-in unit and case. The contentdepends on the ordered functionality.

    Table 1: Plug-in unit and case

    Main Slot ID Content optionsPlug-inunit

    - HMI Small (5 lines, 20 characters)Large (10 lines, 20 characters) with SLD

    Small Chinese (3 lines, 8 or more characters)Large Chinese (7 lines, 8 or more characters) withSLD

    X100 Auxiliary power/BOmodule

    48-250 V DC/100-240 V AC; or 24-60 V DC2 normally-open PO contacts1 change-over SO contact1 normally open SO contact2 double-pole PO contacts with TCS1 dedicated internal fault output contact

    X110 BIO module 8 binary inputs4 SO contacts

    Optional for configuration A:8 binary inputs3 HSO contacts

    X120 AI/BI module Only with configuration B:3 phase current inputs (1/5 A)1 residual current input (1/5 A)3 phase voltage inputs (60-210 V)

    Case X130 AI/BI module Only with configuration A:3 phase voltage inputs (60-210 V)1 residual voltage input (60-210 V)1 reference voltage input for SECRSYN1 (60-210 V)4 binary inputs

    Optional RTD/mA module Optional for configuration B:2 generic mA inputs6 RTD sensor inputs

    Optional BIO module Optional for configuration B:6 binary inputs3 SO contacts

    X000 Optional communicationmodule

    See the technical manual for details about differenttypes of communication modules.

    Rated values of the current and voltage inputs are basic setting parameters of theprotection relay. The binary input thresholds are selectable within the range 16…176V DC by adjusting the binary input setting parameters.

    The connection diagrams of different hardware modules are presented in this manual.

    See the installation manual for more information about the case andthe plug-in unit.

    1MRS758128 B Section 2REU615 overview

    REU615 11Application Manual

  • Table 2: Input/output overview

    Std. conf. Order code digit Analog channels Binary channels 5-6 7-8 CT VT BI BO RTD mA

    A EA

    AD - 5 12 4 PO + 6SO- -

    FE- 5 12 4 PO + 2

    SO + 3HSO

    - -

    BCA BB 4 3 14 4 PO + 9SO

    - -

    CC AH 4 3 8 4 PO + 6SO6 2

    2.4 Local HMI

    The LHMI is used for setting, monitoring and controlling the protection relay. TheLHMI comprises the display, buttons, LED indicators and communication port.

    REF615

    Overcurrent

    Dir. earth-fault

    Voltage protection

    Phase unbalance

    Thermal overload

    Breaker failure

    Disturb. rec. Triggered

    CB condition monitoring

    Supervision

    Arc detected

    Autoreclose shot in progr.

    A070704 V4 EN

    Figure 2: Example of the LHMI

    Section 2 1MRS758128 BREU615 overview

    12 REU615Application Manual

  • 2.4.1 Display

    The LHMI includes a graphical display that supports two character sizes. Thecharacter size depends on the selected language. The amount of characters and rowsfitting the view depends on the character size.

    Table 3: Small display

    Character size1) Rows in the view Characters per row

    Small, mono-spaced (6 × 12 pixels) 5 20

    Large, variable width (13 × 14 pixels) 3 8 or more

    1) Depending on the selected language

    Table 4: Large display

    Character size1) Rows in the view Characters per row

    Small, mono-spaced (6 × 12 pixels) 10 20

    Large, variable width (13 × 14 pixels) 7 8 or more

    1) Depending on the selected language

    The display view is divided into four basic areas.

    1 2

    3 4A070705 V3 EN

    Figure 3: Display layout

    1 Header

    2 Icon

    3 Content

    4 Scroll bar (displayed when needed)

    1MRS758128 B Section 2REU615 overview

    REU615 13Application Manual

  • 2.4.2 LEDs

    The LHMI includes three protection indicators above the display: Ready, Start andTrip.

    There are 11 matrix programmable LEDs on front of the LHMI. The LEDs can beconfigured with PCM600 and the operation mode can be selected with the LHMI,WHMI or PCM600.

    2.4.3 Keypad

    The LHMI keypad contains push buttons which are used to navigate in different viewsor menus. With the push buttons you can give open or close commands to objects inthe primary circuit, for example, a circuit breaker, a contactor or a disconnector. Thepush buttons are also used to acknowledge alarms, reset indications, provide help andswitch between local and remote control mode.

    A071176 V1 EN

    Figure 4: LHMI keypad with object control, navigation and command pushbuttons and RJ-45 communication port

    2.5 Web HMI

    The WHMI allows secure access to the protection relay via a Web browser. When theSecure Communication parameter in the protection relay is activated, the Web serveris forced to take a secured (HTTPS) connection to WHMI using TLS encryption.TheWHMI is verified with Internet Explorer 8.0, 9.0, 10.0 and 11.0.

    WHMI is disabled by default.

    WHMI offers several functions.

    Section 2 1MRS758128 BREU615 overview

    14 REU615Application Manual

  • • Programmable LEDs and event lists• System supervision• Parameter settings• Measurement display• Disturbance records• Fault records• Load profile record• Phasor diagram• Single-line diagram• Importing/Exporting parameters• Report summary

    The menu tree structure on the WHMI is almost identical to the one on the LHMI.

    GUID-38AF6905-4903-4C61-B22C-8509D99398E0 V1 EN

    Figure 5: Example view of the WHMI

    The WHMI can be accessed locally and remotely.

    • Locally by connecting the laptop to the protection relay via the frontcommunication port.

    • Remotely over LAN/WAN.

    1MRS758128 B Section 2REU615 overview

    REU615 15Application Manual

  • 2.6 Authorization

    Four user categories have been predefined for the LHMI and the WHMI, each withdifferent rights and default passwords.

    The default passwords in the protection relay delivered from the factory can bechanged with Administrator user rights.

    User authorization is disabled by default for LHMI but WHMI alwaysuses authorization.

    Table 5: Predefined user categories

    Username User rightsVIEWER Read only access

    OPERATOR • Selecting remote or local state with (only locally)• Changing setting groups• Controlling• Clearing indications

    ENGINEER • Changing settings• Clearing event list• Clearing disturbance records• Changing system settings such as IP address, serial baud rate or

    disturbance recorder settings• Setting the protection relay to test mode• Selecting language

    ADMINISTRATOR • All listed above• Changing password• Factory default activation

    For user authorization for PCM600, see PCM600 documentation.

    2.6.1 Audit trail

    The protection relay offers a large set of event-logging functions. Critical system andprotection relay security-related events are logged to a separate nonvolatile audit trailfor the administrator.

    Audit trail is a chronological record of system activities that allows the reconstructionand examination of the sequence of system and security-related events and changes inthe protection relay. Both audit trail events and process related events can beexamined and analyzed in a consistent method with the help of Event List in LHMIand WHMI and Event Viewer in PCM600.

    Section 2 1MRS758128 BREU615 overview

    16 REU615Application Manual

  • The protection relay stores 2048 audit trail events to the nonvolatile audit trail.Additionally, 1024 process events are stored in a nonvolatile event list. Both the audittrail and event list work according to the FIFO principle. Nonvolatile memory is basedon a memory type which does not need battery backup nor regular component changeto maintain the memory storage.

    Audit trail events related to user authorization (login, logout, violation remote andviolation local) are defined according to the selected set of requirements from IEEE1686. The logging is based on predefined user names or user categories. The user audittrail events are accessible with IEC 61850-8-1, PCM600, LHMI and WHMI.

    Table 6: Audit trail events

    Audit trail event DescriptionConfiguration change Configuration files changed

    Firmware change Firmware changed

    Firmware change fail Firmware change failed

    Attached to retrofit test case Unit has been attached to retrofit case

    Removed from retrofit test case Removed from retrofit test case

    Setting group remote User changed setting group remotely

    Setting group local User changed setting group locally

    Control remote DPC object control remote

    Control local DPC object control local

    Test on Test mode on

    Test off Test mode off

    Reset trips Reset latched trips (TRPPTRC*)

    Setting commit Settings have been changed

    Time change Time changed directly by the user. Note that this is not usedwhen the protection relay is synchronised properly by theappropriate protocol (SNTP, IRIG-B, IEEE 1588 v2).

    View audit log Administrator accessed audit trail

    Login Successful login from IEC 61850-8-1 (MMS), WHMI, FTP orLHMI.

    Logout Successful logout from IEC 61850-8-1 (MMS), WHMI, FTP orLHMI.

    Password change Password changed

    Firmware reset Reset issued by user or tool

    Audit overflow Too many audit events in the time period

    Violation remote Unsuccessful login attempt from IEC 61850-8-1 (MMS),WHMI, FTP or LHMI.

    Violation local Unsuccessful login attempt from IEC 61850-8-1 (MMS),WHMI, FTP or LHMI.

    PCM600 Event Viewer can be used to view the audit trail events and process relatedevents. Audit trail events are visible through dedicated Security events view. Sinceonly the administrator has the right to read audit trail, authorization must be used in

    1MRS758128 B Section 2REU615 overview

    REU615 17Application Manual

  • PCM600. The audit trail cannot be reset, but PCM600 Event Viewer can filter data.Audit trail events can be configured to be visible also in LHMI/WHMI Event listtogether with process related events.

    To expose the audit trail events through Event list, define theAuthority logging level parameter via Configuration/Authorization/Security. This exposes audit trail events to all users.

    Table 7: Comparison of authority logging levels

    Audit trail event Authority logging level

    NoneConfiguration change

    Settinggroup

    Settinggroup,control

    Settingsedit

    All

    Configuration change ● ● ● ● ●

    Firmware change ● ● ● ● ●

    Firmware change fail ● ● ● ● ●

    Attached to retrofit testcase

    ● ● ● ● ●

    Removed from retrofittest case

    ● ● ● ● ●

    Setting group remote ● ● ● ●

    Setting group local ● ● ● ●

    Control remote ● ● ●

    Control local ● ● ●

    Test on ● ● ●

    Test off ● ● ●

    Reset trips ● ● ●

    Setting commit ● ●

    Time change ●

    View audit log ●

    Login ●

    Logout ●

    Password change ●

    Firmware reset ●

    Violation local ●

    Violation remote ●

    2.7 Communication

    The protection relay supports a range of communication protocols including IEC61850, IEC 61850-9-2 LE, IEC 60870-5-103 and Modbus®. Profibus DPV1

    Section 2 1MRS758128 BREU615 overview

    18 REU615Application Manual

  • communication protocol is supported by using the protocol converter SPA-ZC 302.Operational information and controls are available through these protocols. However,some communication functionality, for example, horizontal communication betweenthe protection relays, is only enabled by the IEC 61850 communication protocol.

    The IEC 61850 communication implementation supports all monitoring and controlfunctions. Additionally, parameter settings, disturbance recordings and fault recordscan be accessed using the IEC 61850 protocol. Disturbance recordings are availableto any Ethernet-based application in the IEC 60255-24 standard COMTRADE fileformat. The protection relay can send and receive binary signals from other devices(so-called horizontal communication) using the IEC 61850-8-1 GOOSE profile,where the highest performance class with a total transmission time of 3 ms issupported. Furthermore, the protection relay supports sending and receiving of analogvalues using GOOSE messaging. The protection relay meets the GOOSEperformance requirements for tripping applications in distribution substations, asdefined by the IEC 61850 standard.

    The protection relay can support five simultaneous clients. If PCM600 reserves oneclient connection, only four client connections are left, for example, for IEC 61850and Modbus.

    All communication connectors, except for the front port connector, are placed onintegrated optional communication modules. The protection relay can be connected toEthernet-based communication systems via the RJ-45 connector (100Base-TX) or thefiber-optic LC connector (100Base-FX).

    2.7.1 Self-healing Ethernet ring

    For the correct operation of self-healing loop topology, it is essential that the externalswitches in the network support the RSTP protocol and that it is enabled in theswitches. Otherwise, connecting the loop topology can cause problems to thenetwork. The protection relay itself does not support link-down detection or RSTP.The ring recovery process is based on the aging of the MAC addresses, and the link-up/link-down events can cause temporary breaks in communication. For a betterperformance of the self-healing loop, it is recommended that the external switchfurthest from the protection relay loop is assigned as the root switch (bridge priority= 0) and the bridge priority increases towards the protection relay loop. The end linksof the protection relay loop can be attached to the same external switch or to twoadjacent external switches. A self-healing Ethernet ring requires a communicationmodule with at least two Ethernet interfaces for all protection relays.

    1MRS758128 B Section 2REU615 overview

    REU615 19Application Manual

  • Managed Ethernet switchwith RSTP support

    Managed Ethernet switchwith RSTP support

    Client BClient A

    Network ANetwork B

    GUID-283597AF-9F38-4FC7-B87A-73BFDA272D0F V3 EN

    Figure 6: Self-healing Ethernet ring solution

    The Ethernet ring solution supports the connection of up to 30protection relays. If more than 30 protection relays are to beconnected, it is recommended that the network is split into severalrings with no more than 30 protection relays per ring. Each protectionrelay has a 50-μs store-and-forward delay, and to fulfil theperformance requirements for fast horizontal communication, thering size is limited to 30 protection relays.

    2.7.2 Ethernet redundancy

    IEC 61850 specifies a network redundancy scheme that improves the systemavailability for substation communication. It is based on two complementaryprotocols defined in the IEC 62439-3:2012 standard: parallel redundancy protocolPRP and high-availability seamless redundancy HSR protocol. Both protocols rely onthe duplication of all transmitted information via two Ethernet ports for one logicalnetwork connection. Therefore, both are able to overcome the failure of a link orswitch with a zero-switchover time, thus fulfilling the stringent real-timerequirements for the substation automation horizontal communication and timesynchronization.

    PRP specifies that each device is connected in parallel to two local area networks.HSR applies the PRP principle to rings and to the rings of rings to achieve cost-effective redundancy. Thus, each device incorporates a switch element that forwardsframes from port to port. The HSR/PRP option is available for all 615 series protectionrelays. However, RED615 supports this option only over fiber optics.

    Section 2 1MRS758128 BREU615 overview

    20 REU615Application Manual

  • IEC 62439-3:2012 cancels and replaces the first edition published in2010. These standard versions are also referred to as IEC 62439-3Edition 1 and IEC 62439-3 Edition 2. The protection relay supportsIEC 62439-3:2012 and it is not compatible with IEC 62439-3:2010.

    PRPEach PRP node, called a double attached node with PRP (DAN), is attached to twoindependent LANs operated in parallel. These parallel networks in PRP are calledLAN A and LAN B. The networks are completely separated to ensure failureindependence, and they can have different topologies. Both networks operate inparallel, thus providing zero-time recovery and continuous checking of redundancy toavoid communication failures. Non-PRP nodes, called single attached nodes (SANs),are either attached to one network only (and can therefore communicate only withDANs and SANs attached to the same network), or are attached through a redundancybox, a device that behaves like a DAN.

    Ethernet switchIEC 61850 PRPEthernet switch

    SCADACOM600

    GUID-334D26B1-C3BD-47B6-BD9D-2301190A5E9D V2 EN

    Figure 7: PRP solution

    In case a laptop or a PC workstation is connected as a non-PRP node to one of the PRPnetworks, LAN A or LAN B, it is recommended to use a redundancy box device or anEthernet switch with similar functionality between the PRP network and SAN toremove additional PRP information from the Ethernet frames. In some cases, defaultPC workstation adapters are not able to handle the maximum-length Ethernet frameswith the PRP trailer.

    There are different alternative ways to connect a laptop or a workstation as SAN to aPRP network.

    1MRS758128 B Section 2REU615 overview

    REU615 21Application Manual

  • • Via an external redundancy box (RedBox) or a switch capable of connecting toPRP and normal networks

    • By connecting the node directly to LAN A or LAN B as SAN• By connecting the node to the protection relay's interlink port

    HSRHSR applies the PRP principle of parallel operation to a single ring, treating the twodirections as two virtual LANs. For each frame sent, a node, DAN, sends two frames,one over each port. Both frames circulate in opposite directions over the ring and eachnode forwards the frames it receives, from one port to the other. When the originatingnode receives a frame sent to itself, it discards that to avoid loops; therefore, no ringprotocol is needed. Individually attached nodes, SANs, such as laptops and printers,must be attached through a “redundancy box” that acts as a ring element. For example,a 615 or 620 series protection relay with HSR support can be used as a redundancybox.

    GUID-207430A7-3AEC-42B2-BC4D-3083B3225990 V2 EN

    Figure 8: HSR solution

    2.7.3 Process bus

    Process bus IEC 61850-9-2 defines the transmission of Sampled Measured Valueswithin the substation automation system. International Users Group created aguideline IEC 61850-9-2 LE that defines an application profile of IEC 61850-9-2 tofacilitate implementation and enable interoperability. Process bus is used fordistributing process data from the primary circuit to all process bus compatibledevices in the local network in a real-time manner. The data can then be processed byany protection relay to perform different protection, automation and control functions.

    Section 2 1MRS758128 BREU615 overview

    22 REU615Application Manual

  • UniGear Digital switchgear concept relies on the process bus together with currentand voltage sensors. The process bus enables several advantages for the UniGearDigital like simplicity with reduced wiring, flexibility with data availability to alldevices, improved diagnostics and longer maintenance cycles.

    With process bus the galvanic interpanel wiring for sharing busbar voltage value canbe replaced with Ethernet communication. Transmitting measurement samples overprocess bus brings also higher error detection because the signal transmission isautomatically supervised. Additional contribution to the higher availability is thepossibility to use redundant Ethernet network for transmitting SMV signals.

    Common EthernetStation bus (IEC 61850-8-1), process bus (IEC 61850-9-2 LE) and IEEE 1588 v2 time synchronization

    GO

    OS

    E

    SM

    V

    GO

    OS

    E

    SM

    V

    SM

    V

    GO

    OS

    E

    GO

    OS

    E

    SM

    V

    GO

    OS

    E

    SM

    V

    SM

    V

    GO

    OS

    E

    SM

    V

    GO

    OS

    E

    GUID-2371EFA7-4369-4F1A-A23F-CF0CE2D474D3 V5 EN

    Figure 9: Process bus application of voltage sharing and synchrocheck

    The 615 series supports IEC 61850 process bus with sampled values of analogcurrents and voltages. The measured values are transferred as sampled values usingthe IEC 61850-9-2 LE protocol which uses the same physical Ethernet network as theIEC 61850-8-1 station bus. The intended application for sampled values is sharing themeasured voltages from one 615 series protection relay to other devices with phasevoltage based functions and 9-2 support.

    The 615 series protection relays with process bus based applications use IEEE 1588 v2Precision Time Protocol (PTP) according to IEEE C37.238-2011 Power Profile forhigh accuracy time synchronization. With IEEE 1588 v2, the cabling infrastructurerequirement is reduced by allowing time synchronization information to betransported over the same Ethernet network as the data communications.

    1MRS758128 B Section 2REU615 overview

    REU615 23Application Manual

  • IEC 61850

    HSR

    SMV

    tra

    ffic

    Backup 1588

    master clock

    Managed HSR

    Ethernet

    switch

    Primary

    IEEE 1588 v2

    master clock

    Secondary

    IEEE 1588 v2

    master clock

    (optional)

    Managed HSR

    Ethernet

    switch

    GUID-7C56BC1F-F1B2-4E74-AB8E-05001A88D53D V5 EN

    Figure 10: Example network topology with process bus, redundancy and IEEE1588 v2 time synchronization

    The process bus option is available for all 615 series protection relays equipped withphase voltage inputs. Another requirement is a communication card with IEEE 1588v2 support (COM0031...COM0037). However, RED615 supports this option onlywith the communication card variant having fiber optic station bus ports. See the IEC61850 engineering guide for detailed system requirements and configuration details.

    2.7.4 Secure communication

    The protection relay supports secure communication for WHMI and file transferprotocol. If the Secure Communication parameter is activated, protocols require TLSbased encryption method support from the clients. In this case WHMI must beconnected from a Web browser using the HTTPS protocol and in case of file transferthe client must use FTPS.

    Section 2 1MRS758128 BREU615 overview

    24 REU615Application Manual

  • Section 3 REU615 standard configurations

    3.1 Standard configurations

    REU615 is available with two standard configurations. The standard signalconfiguration can be altered by means of the signal matrix or the graphical applicationfunctionality of the Protection and Control IED Manager PCM600. Further, theapplication configuration functionality of PCM600 supports the creation of multi-layer logic functions using various logical elements, including timers and flip-flops.By combining protection functions with logic function blocks, the relay configurationcan be adapted to user-specific application requirements.

    The relay is delivered from the factory with default connections described in thefunctional diagrams for binary inputs, binary outputs, function-to-functionconnections and alarm LEDs. Some of the supported functions in REU615 must beadded with the Application Configuration tool to be available in the Signal Matrix tooland in the relay. The positive measuring direction of directional protection functionsis towards the outgoing feeder.

    Table 8: Standard configurations

    Description Std.conf.Voltage and frequency protection, synchro-check and load-shedding A

    Automatic voltage regulator B

    Table 9: Supported functions

    Function IEC 61850 A BProtection

    Three-phase non-directional overcurrent protection, low stage PHLPTOC 1

    Three-phase non-directional overcurrent protection, high stage PHHPTOC 1

    Three-phase non-directional overcurrent protection, instantaneous stage PHIPTOC 1

    Residual overvoltage protection ROVPTOV 3

    Three-phase undervoltage protection PHPTUV 3 3

    Three-phase overvoltage protection PHPTOV 3 3

    Positive-sequence undervoltage protection PSPTUV 2

    Negative-sequence overvoltage protection NSPTOV 2

    Frequency protection FRPFRQ 6

    Three-phase thermal overload protection, two time constants T2PTTR 1

    Master trip TRPPTRC 2 2

    Arc protection ARCSARC (3)1)

    Table continues on next page

    1MRS758128 B Section 3REU615 standard configurations

    REU615 25Application Manual

  • Function IEC 61850 A B

    Multipurpose protection2) MAPGAPC 18 18

    Load-shedding and restoration LSHDPFRQ 5

    Control

    Circuit-breaker control CBXCBR 1 1

    Disconnector control DCXSWI 2 2

    Earthing switch control ESXSWI 1 1

    Disconnector position indication DCSXSWI 3 3

    Earthing switch indication ESSXSWI 2 2

    Tap changer position indication TPOSYLTC 1

    Tap changer control with voltage regulator OLATCC 1

    Synchronism and energizing check SECRSYN 1

    Condition monitoring

    Trip circuit supervision TCSSCBR 2 2

    Current circuit supervision CCSPVC 1

    Fuse failure supervision SEQSPVC 1

    Runtime counter for machines and devices MDSOPT 1 1

    Measurement

    Disturbance recorder RDRE 1 1

    Load profile record LDPRLRC 1 1

    Fault record FLTRFRC 1 1

    Three-phase current measurement CMMXU 1

    Sequence current measurement CSMSQI 1

    Three-phase voltage measurement VMMXU 2 1

    Residual voltage measurement RESVMMXU 1

    Sequence voltage measurement VSMSQI 1 1

    Three-phase power and energy measurement PEMMXU 1

    RTD/mA measurement XRGGIO130 (1)

    Frequency measurement FMMXU 1

    IEC 61850-9-2 LE sampled value sending3) SMVSENDER (1) (1)

    IEC 61850-9-2 LE sampled value receiving (voltage sharing)3) SMVRECEIVER (1) (1)

    Other

    Minimum pulse timer (2 pcs) TPGAPC 4 4

    Minimum pulse timer (2 pcs, second resolution) TPSGAPC 1 1

    Minimum pulse timer (2 pcs, minute resolution) TPMGAPC 1 1

    Pulse timer (8 pcs) PTGAPC 2 2

    Time delay off (8 pcs) TOFGAPC 4 4

    Time delay on (8 pcs) TONGAPC 4 4

    Set-reset (8 pcs) SRGAPC 4 4

    Move (8 pcs) MVGAPC 2 2

    Table continues on next page

    Section 3 1MRS758128 BREU615 standard configurations

    26 REU615Application Manual

  • Function IEC 61850 A BGeneric control point (16 pcs) SPCGAPC 2 2

    Analog value scaling SCA4GAPC 4 4

    Integer value move MVI4GAPC 1 1

    1, 2, ... = Number of included instances. The instances of a protection function represent the number of identical protection function blocksavailable in the standard configuration.() = optional

    1) Light only2) Used for RTD/mA based protection or analog GOOSE, for example3) Available only with COM0031...0037

    3.1.1 Addition of control functions for primary devices and the useof binary inputs and outputs

    If extra control functions intended for controllable primary devices are added to theconfiguration, additional binary inputs and/or outputs are needed to complement thestandard configuration.

    If the number of inputs and/or outputs in a standard configuration is not sufficient, itis possible either to modify the chosen standard configuration in order to release somebinary inputs or binary outputs which have originally been configured for otherpurposes, or to integrate an external input/output module, for example RIO600, to theprotection relay.

    The external I/O module’s binary inputs and outputs can be used for the less time-critical binary signals of the application. The integration enables releasing someinitially reserved binary inputs and outputs of the protection relay’s standardconfiguration.

    The suitability of the protection relay’s binary outputs which have been selected forprimary device control should be carefully verified, for example make and carry andbreaking capacity. If the requirements for the primary device control circuit are notmet, using external auxiliary relays should be considered.

    1MRS758128 B Section 3REU615 standard configurations

    REU615 27Application Manual

  • 3.2 Connection diagrams

    REU615

    X13Light sensor input 1 1)

    X14Light sensor input 2 1)

    X15Light sensor input 3 1)

    16

    17

    1918

    X100

    67

    89

    10

    111213

    15

    14

    2

    1

    3

    45

    22

    212324

    SO2

    TCS2

    PO4

    SO1

    TCS1

    PO3

    PO2

    PO1

    IRF

    Uaux

    20

    L1L2L3

    da dn

    X110

    34

    56

    7

    89

    10BI 6

    BI 5

    BI 4

    BI 3

    BI 2

    BI 8

    BI 712

    13

    11

    BI 112

    X110

    16

    14

    15

    19

    17

    18

    22

    20

    21

    SO3

    SO2

    SO1

    23SO4

    24

    a

    nN

    A

    A N n a

    X13012

    34

    56

    BI 4

    BI 3

    BI 2

    BI 1

    87

    9101112

    U12B

    1314

    U1

    1516

    U2

    1718

    U3

    UoN

    N

    N

    N

    60 -

    N

    210V

    60 -210V

    60 -210V

    60 -210V

    60 -210V

    GUID-DFFD1465-B99C-4E83-832A-073E84404E68 V1 EN

    Figure 11: Connection diagram for the A configuration

    Section 3 1MRS758128 BREU615 standard configurations

    28 REU615Application Manual

  • REU615

    X13Light sensor input 1 1)

    X14Light sensor input 2 1)

    X15Light sensor input 3 1)

    16

    17

    1918

    X100

    67

    8910

    111213

    15

    14

    2

    1

    3

    45

    22

    212324

    SO2

    TCS2

    PO4

    SO1

    TCS1

    PO3

    PO2

    PO1

    IRF

    Uaux

    20

    X13012

    3

    45

    6BI 4

    BI 3

    BI 2

    BI 1

    BI 6

    BI 58

    9

    7

    X130

    12

    10

    11

    15

    13

    14

    18

    16

    17

    SO3

    SO2

    SO1

    3)

    3)

    X110

    34

    56

    7

    89

    10BI 6

    BI 5

    BI 4

    BI 3

    BI 2

    BI 8

    BI 712

    13

    11

    BI 112

    X110

    16

    14

    15

    19

    17

    18

    22

    20

    21

    SO3

    SO2

    SO1

    23SO4

    24

    2)

    1) Optional2) The IED features an automatic short-circuit mechanism in the CT connector when plug-in unit is detached3) Optional BIO module

    NA an

    L1L2L3

    S1

    S2

    P1

    P2

    L1L2L3

    S1

    S2

    P1

    P2

    Protectioncore

    CT Supervisionreference current

    PositiveCurrentDirection

    X120

    1

    23

    4

    567

    89

    1011

    1213

    14Io

    IL1

    IL2

    U3

    IL3

    1/5A

    N1/5A

    N1/5A

    N1/5A

    N

    N

    U2N

    U160 -

    N

    210V

    60 -210V

    60 -210V

    GUID-E087BFB3-0CB1-4C94-9D29-AA4A54911CC2 V1 EN

    Figure 12: Connection diagram for the B configuration

    1MRS758128 B Section 3REU615 standard configurations

    REU615 29Application Manual

  • 3.3 Standard configuration A

    3.3.1 Applications

    The standard configuration is intended for voltage protection and synchronism checkin the medium voltage networks. The configuration handles fault conditionsoriginating from abnormal voltages in the power system. The synchronism andenergizing check can be handled for two galvanically interconnected networks.

    The protection relay with a standard configuration is delivered from the factory withdefault settings and parameters. The end-user flexibility for incoming, outgoing andinternal signal designation within the protection relay enables this configuration to befurther adapted to different primary circuit layouts and the related functionality needsby modifying the internal functionality using PCM600.

    Section 3 1MRS758128 BREU615 standard configurations

    30 REU615Application Manual

  • 3.3.2 Functions

    -

    5

    CONDITION MONITORING AND SUPERVISION

    ORAND

    CONTROL AND INDICATION 1) MEASUREMENT

    PROTECTION LOCAL HMI

    Object Ctrl 2) Ind 3)

    CB

    DC

    ES1) Check availability of binary inputs/outputs

    from technical documentation2) Control and indication function for

    primary object3) Status indication function for primary object

    1 -

    2 3

    1 2

    STANDARD CONFIGURATION

    RL

    ClearESCI

    O

    Configuration ASystemHMITimeAuthorization

    RL

    ClearESCI

    O

    U12 0. 0 kVP 0.00 kWQ 0.00 kVAr

    IL2 0 A

    A

    COMMUNICATION

    Protocols: IEC 61850-8-1/9-2LE Modbus®

    IEC 60870-5-103 Interfaces: Ethernet: TX (RJ45), FX (LC) Serial: Serial glass fiber (ST), RS-485, RS-232Redundant protocols: HSR PRP RSTP

    REU615 A

    - U, Uo, f- Symmetrical components- Limit value supervision- Load profile record

    Analog interface types 1)

    Current transformer

    Voltage transformer1) Conventional transformer inputs

    ALSO AVAILABLE

    - Disturbance and fault recorders- Event log and recorded data- High-Speed Output module (optional)- Local/Remote push button on LHMI- Self-supervision - Time synchronization: IEEE 1588 v2,

    SNTP, IRIG-B- User management- Web HMI

    REMARKS

    Optionalfunction

    No. ofinstances

    Alternative function to be defined when ordering

    OR

    Io/Uo

    Calculatedvalue

    2×TCSTCM

    SYNC25

    3×ARC

    50L/50NL

    3×3U<27

    2×U2>47O-

    2×U1<

    47U+

    3×3U>59

    3×Uo>59G

    6×f>/f

  • Table 10: Default connections for analog inputs

    Analog input Description Connector pinsIL1 Phase A current X120:7-8

    IL2 Phase B current X120:9-10

    IL3 Phase C current X120:11-12

    Io Residual current X120:13-14

    U12B U_SYN X130:9-10

    U1 Phase voltage U1 X130:11-12

    U2 Phase voltage U2 X130:13-14

    U3 Phase voltage U3 X130:15-16

    Uo Residual voltage X130:17-18

    Table 11: Default connections for binary inputs

    Binary input Description Connector pinsBIO0005 BIO0007

    X110-BI1 Setting group change X110:1-2 X110:1,5

    X110-BI2 Manual restore group 1 X110:3-4 X110:2,5

    X110-BI3 Manual restore group 2 X110:5-6 X110:3,5

    X110-BI4 - X110:7-6 X110:4-5

    X110-BI5 Voltage transformer truck in indication X110:8-9 X110:6,10

    X110-BI6 Voltage transformer truck out indication X110:10-9 X110:7,10

    X110-BI7 Earthing switch closed indication X110:11-12 X110:8,10

    X110-BI8 Earthing switch open indication X110:13-12 X110:9-10

    X130-BI1 Blown primary fuse indication X130:1-2

    X130-BI2 Line voltage transformer MCB open X130:3-4

    X130-BI3 Bus voltage transformer MCB open X130:5-6

    X130-BI4 Lockout reset X130:7-8

    Table 12: Default connections for binary outputs

    Binary output Description Connector pinsX100-PO1 - X100:6-7

    X100-PO2 In synchronism for close X100:8-9

    X100-SO1 General start indication X100:10-11,(12)

    X100-SO2 General operate indication X100:13-14

    X100-PO3 Open circuit breaker/trip coil 1 X100:15-19

    X100-PO4 Open circuit breaker/trip coil 2 X100:20-24

    X110-SO1 Load-shedding group 1 X110:14-16

    X110-SO2 Load-shedding group 2 X110:17-19

    X110-SO3 Load restore group 1 X110:20-22

    X110-SO4 Load restore group 2 X110:23-24

    Table continues on next page

    Section 3 1MRS758128 BREU615 standard configurations

    32 REU615Application Manual

  • Binary output Description Connector pinsX110-HSO1 Arc protection instance 1 operate activated X110:15-16

    X110-HSO1 Arc protection instance 2 operate activated X110:19-20

    X110-HSO1 Arc protection instance 3 operate activated X110:23-24

    Table 13: Default connections for LEDs

    LED Description1 Overvoltage protection operate

    2 Undervoltage protection operate

    3 Residual voltage operate

    4 Sequence voltage protection operate

    5 Frequency protection operate

    6 Load-shedding operate

    7 Disturbance recorder triggered

    8 Systems synchronized

    9 Voltage transformer secondary MCB open

    10 Arc protection operate

    11 Primary voltage transformer fuse blown

    3.3.2.2 Default disturbance recorder settings

    Table 14: Default disturbance recorder analog channels

    Channel Description1 Uo

    2 U1

    3 U2

    4 U3

    5 U1B

    6 -

    7 -

    8 -

    9 -

    10 -

    11 -

    12 -

    1MRS758128 B Section 3REU615 standard configurations

    REU615 33Application Manual

  • Table 15: Default disturbance recorder binary channels

    Channel ID text Level trigger mode1 FRPFRQ1 - start Positive or Rising

    2 FRPFRQ2 - start Positive or Rising

    3 FRPFRQ3 - start Positive or Rising

    4 FRPFRQ4 - start Positive or Rising

    5 FRPFRQ5 - start Positive or Rising

    6 FRPFRQ6 - start Positive or Rising

    7 LSHDPFRQ1 - start Positive or Rising

    8 LSHDPFRQ2- start Positive or Rising

    9 LSHDPFRQ3 - start Positive or Rising

    10 LSHDPFRQ4 - start Positive or Rising

    11 LSHDPFRQ5 - start Positive or Rising

    12 NSPTOV1 - start Positive or Rising

    13 NSPTOV2 - start Positive or Rising

    14 PSPTUV1 - start Positive or Rising

    15 PSPTUV2 - start Positive or Rising

    16 PHPTOV1 - start Positive or Rising

    17 PHPTOV2 - start Positive or Rising

    18 PHPTOV3 - start Positive or Rising

    19 PHPTUV1 - start Positive or Rising

    20 PHPTUV2 - start Positive or Rising

    21 PHPTUV3 - start Positive or Rising

    22 ROVPTOV1 - start Positive or Rising

    23 ROVPTOV2 - start Positive or Rising

    24 ROVPTOV3 - start Positive or Rising

    25 FRPFRQ1 - operate Level trigger off

    FRPFRQ2 - operate

    FRPFRQ3 - operate

    FRPFRQ4 - operate

    FRPFRQ5 - operate

    FRPFRQ6 - operate

    26 LSHDPFRQ1 - operate Level trigger off

    LSHDPFRQ2 - operate

    LSHDPFRQ3 - operate

    LSHDPFRQ4 - operate

    LSHDPFRQ5 - operate

    LSHDPFRQ6 - operate

    Table continues on next page

    Section 3 1MRS758128 BREU615 standard configurations

    34 REU615Application Manual

  • Channel ID text Level trigger mode27 PHPTOV1 - operate Level trigger off

    PHPTOV2 - operate

    PHPTOV3 - operate

    28 PHPTUV1 - operate Level trigger off

    PHPTUV2 - operate

    PHPTUV3 - operate

    29 NSPTOV1 - operate Level trigger off

    NSPTOV2 - operate

    PSPTUV1 - operate

    PSPTUV2 - operate

    30 ROVPTOV1 - operate Level trigger off

    31 LSHDPFRQ1 - restore Level trigger off

    32 X130BI2 - line VT MCB open Level trigger off

    33 X130BI3 - bus VT MCB open Level trigger off

    34 SECRSYN1 - sync inpro Level trigger off

    35 SECRSYN1 - sync ok Level trigger off

    36 ARCSARC1 - arc flt det Level trigger off

    37 ARCSARC2 - arc flt det Level trigger off

    38 ARCSARC3 - arc flt det Level trigger off

    39 - -

    40 - -

    41 - -

    42 - -

    43 - -

    44 - -

    45 - -

    46 - -

    47 - -

    48 - -

    49 - -

    50 - -

    51 - -

    52 - -

    53 - -

    54 - -

    55 - -

    56 - -

    57 - -

    58 - -

    Table continues on next page

    1MRS758128 B Section 3REU615 standard configurations

    REU615 35Application Manual

  • Channel ID text Level trigger mode59 - -

    60 - -

    61 - -

    62 - -

    63 - -

    64 - -

    3.3.3 Functional diagrams

    The functional diagrams describe the default input, output, alarm LED and function-to-function connections. The default connections can be viewed and changed withPCM600 according to the application requirements.

    The analog channels have fixed connections to the different function blocks inside theprotection relay’s standard configuration. However, the 12 analog channels availablefor the disturbance recorder function are freely selectable as a part of the disturbancerecorder’s parameter settings.

    The phase and bus voltages to the protection relay are fed from voltage transformer.The residual voltage to the protection relay is fed from either residually connectedVTs or an open delta connected VT or internally calculated.

    The protection relay offers six different setting groups which can be set based onindividual needs. Each group can be activated or deactivated using the setting groupsettings available in the protection relay.

    Depending on the communication protocol the required function block needs to beinstantiated in the configuration.

    3.3.3.1 Functional diagrams for protection

    The functional diagrams describe the protection relay's protection functionality indetail and according to the factory set default connections.

    Three overvoltage and undervoltage protection stages PHPTOV and PHPTUV offerprotection against abnormal phase voltage conditions. The undervoltage protectionstage is blocked, if fuse failure is detected in voltage transformer. The information isavailable through the binary input X130:BI1.

    Section 3 1MRS758128 BREU615 standard configurations

    36 REU615Application Manual

  • PHPTOV1BLOCK OPERATE

    START

    PHPTOV2BLOCK OPERATE

    START

    PHPTOV3BLOCK OPERATE

    START

    OR6B1B2B3B4B5B6

    O

    PHPTOV1_OPERATE

    PHPTOV1_OPERATE

    PHPTOV2_OPERATE

    PHPTOV2_OPERATE

    PHPTOV3_OPERATE

    PHPTOV3_OPERATE

    PHPTOV1_START

    PHPTOV2_START

    PHPTOV3_START

    PHPTOV_OPERATE

    GUID-81B61B9F-7976-4345-A2C9-2D24F425A8EB V1 EN

    Figure 14: Overvoltage protection function

    PHPTUV1BLOCK OPERATE

    START

    PHPTUV2BLOCK OPERATE

    START

    PHPTUV3BLOCK OPERATE

    START

    OR6B1B2B3B4B5B6

    O

    X130_BI1_PRIMARY_VT_FUSE_BLOWN

    X130_BI1_PRIMARY_VT_FUSE_BLOWN

    X130_BI1_PRIMARY_VT_FUSE_BLOWN

    PHPTUV1_OPERATE

    PHPTUV1_OPERATE

    PHPTUV2_OPERATE

    PHPTUV2_OPERATE

    PHPTUV3_OPERATE

    PHPTUV3_OPERATE

    PHPTUV1_START

    PHPTUV2_START

    PHPTUV3_START

    PHPTUV_OPERATE

    GUID-DAF89708-AABD-4D0E-B07B-1097F3D78495 V1 EN

    Figure 15: Undervoltage protection function

    1MRS758128 B Section 3REU615 standard configurations

    REU615 37Application Manual

  • Four unbalance voltage protection functions are available, two stages of positive-sequence undervoltage protection PSPTUV and two stages of negative-sequenceovervoltage protection NSPTOV. The unbalance protection stages are blocked, if fusefailure is detected in voltage transformer.

    NSPTOV1BLOCK OPERATE

    START

    PSPTUV1BLOCK OPERATE

    START

    NSPTOV2BLOCK OPERATE

    START

    PSPTUV2BLOCK OPERATE

    START

    OR6B1B2B3B4B5B6

    O

    X130_BI1_PRIMARY_VT_FUSE_BLOWN

    X130_BI1_PRIMARY_VT_FUSE_BLOWN

    X130_BI1_PRIMARY_VT_FUSE_BLOWN

    X130_BI1_PRIMARY_VT_FUSE_BLOWN

    NSPTOV1_OPERATE

    NSPTOV1_OPERATE

    NSPTOV2_OPERATE

    NSPTOV2_OPERATE

    PSPTUV1_OPERATE

    PSPTUV1_OPERATE

    PSPTUV2_OPERATE

    PSPTUV2_OPERATE

    NSPTOV1_START

    NSPTOV2_START

    PSPTUV1_START

    PSPTUV2_START

    SEQUENCE_VOLTAGE_OPERATE

    GUID-1D04E3BD-C662-4657-9AF2-F61A354A7369 V1 EN

    Figure 16: Sequence voltage protection function

    The residual overvoltage protection ROVPTOV provides earth-fault protection bydetecting abnormal level of residual voltage. The residual overvoltage protectionstages are blocked, if fuse failure is detected in voltage transformer.

    Section 3 1MRS758128 BREU615 standard configurations

    38 REU615Application Manual

  • ROVPTOV1BLOCK OPERATE

    START

    ROVPTOV2BLOCK OPERATE

    START

    ROVPTOV3BLOCK OPERATE

    START

    OR6B1B2B3B4B5B6

    O

    X130_BI1_PRIMARY_VT_FUSE_BLOWN

    X130_BI1_PRIMARY_VT_FUSE_BLOWN

    X130_BI1_PRIMARY_VT_FUSE_BLOWN

    ROVPTOV1_OPERATE

    ROVPTOV1_OPERATE

    ROVPTOV2_OPERATE

    ROVPTOV2_OPERATE

    ROVPTOV3_OPERATE

    ROVPTOV3_OPERATE

    ROVPTOV1_START

    ROVPTOV2_START

    ROVPTOV3_START

    ROVPTOV_OPERATE

    GUID-7FD1A83F-E64A-4274-AF52-22AAD26875C4 V1 EN

    Figure 17: Residual voltage protection function

    The selectable underfrequency or overfrequency protection FRPFRQ preventsdamage to network components under unwanted frequency conditions. The functionalso contains a selectable rate of change of the frequency (gradient) protection todetect an increase or decrease in the fast power system frequency at an early stage.This can be used as an early indication of a disturbance in the system.

    1MRS758128 B Section 3REU615 standard configurations

    REU615 39Application Manual

  • OR6B1B2B3B4B5B6

    OFRPFRQ1_OPERATEFRPFRQ2_OPERATEFRPFRQ3_OPERATEFRPFRQ4_OPERATEFRPFRQ5_OPERATEFRPFRQ6_OPERATE

    FREQUENCY_OPERATE

    FRPFRQ2BLOCK OPERATE

    OPR_OFRQOPR_UFRQ

    OPR_FRGSTART

    ST_OFRQST_UFRQ

    ST_FRG

    FRPFRQ4BLOCK OPERATE

    OPR_OFRQOPR_UFRQ

    OPR_FRGSTART

    ST_OFRQST_UFRQ

    ST_FRG

    FRPFRQ6BLOCK OPERATE

    OPR_OFRQOPR_UFRQ

    OPR_FRGSTART

    ST_OFRQST_UFRQ

    ST_FRG

    FRPFRQ2_OPERATE

    FRPFRQ4_OPERATE

    FRPFRQ6_OPERATE

    FRPFRQ2_START

    FRPFRQ4_START

    FRPFRQ6_START

    FRPFRQ1BLOCK OPERATE

    OPR_OFRQOPR_UFRQ

    OPR_FRGSTART

    ST_OFRQST_UFRQ

    ST_FRG

    FRPFRQ3BLOCK OPERATE

    OPR_OFRQOPR_UFRQ

    OPR_FRGSTART

    ST_OFRQST_UFRQ

    ST_FRG

    FRPFRQ5BLOCK OPERATE

    OPR_OFRQOPR_UFRQ

    OPR_FRGSTART

    ST_OFRQST_UFRQ

    ST_FRG

    FRPFRQ1_OPERATE

    FRPFRQ3_OPERATE

    FRPFRQ5_OPERATE

    FRPFRQ1_START

    FRPFRQ3_START

    FRPFRQ5_START

    GUID-C35E450A-7391-454F-8AE8-31A97FC8DE7E V1 EN

    Figure 18: Frequency protection function

    Five load-shedding and restoration stages are offered in the standard configuration.The load-shedding and restoration function LSHDPFRQ is capable of shedding loadbased on underfrequency and rate of change of frequency. The load that is shed duringthe frequency disturbance can be restored once the frequency is stabilized to thenormal level. The manual restore commands can be given through the binary inputs.In the configuration, two restore stages are implemented with manual restorecommand. Depending on application needs, it is possible to take other stages into use.

    Section 3 1MRS758128 BREU615 standard configurations

    40 REU615Application Manual

  • LSHDPFRQ5BLOCKBLK_RESTMAN_RESTORE

    OPERATEOPR_FRQOPR_FRG

    STARTST_FRQST_FRG

    RESTOREST_REST

    LSHDPFRQ5_OPERATE

    LSHDPFRQ5_RESTORE

    LSHDPFRQ5_START

    LSHDPFRQ3BLOCKBLK_RESTMAN_RESTORE

    OPERATEOPR_FRQOPR_FRG

    STARTST_FRQST_FRG

    RESTOREST_REST

    LSHDPFRQ3_OPERATE

    LSHDPFRQ3_RESTORE

    LSHDPFRQ3_START

    LSHDPFRQ1BLOCKBLK_RESTMAN_RESTORE

    OPERATEOPR_FRQOPR_FRG

    STARTST_FRQST_FRG

    RESTOREST_REST

    LSHDPFRQ1_OPERATE

    LSHDPFRQ1_RESTORE

    X110_BI2_MANUAL_RESTORE_GR1LSHDPFRQ1_START

    LSHDPFRQ2BLOCKBLK_RESTMAN_RESTORE

    OPERATEOPR_FRQOPR_FRG

    STARTST_FRQST_FRG

    RESTOREST_REST

    LSHDPFRQ2_RESTORE

    LSHDPFRQ2_OPERATE

    X110_BI3_MANUAL_RESTORE_GR2LSHDPFRQ2_START

    LSHDPFRQ4BLOCKBLK_RESTMAN_RESTORE

    OPERATEOPR_FRQOPR_FRG

    STARTST_FRQST_FRG

    RESTOREST_REST

    LSHDPFRQ4_OPERATE

    LSHDPFRQ4_RESTORE

    LSHDPFRQ4_START

    OR6B1B2B3B4B5B6

    OLSHDPFRQ1_OPERATELSHDPFRQ2_OPERATELSHDPFRQ3_OPERATELSHDPFRQ4_OPERATELSHDPFRQ5_OPERATE

    LOAD_SHEDDING_OPERATE

    GUID-1FEA38DF-1E65-4888-89E9-187CCCF71A7C V1 EN

    Figure 19: Load-shedding and restoration function

    Three arc protection stages ARCSARC1...3 are included as optional functions. Thearc protection offers individual function blocks for three arc sensors that can beconnected to the protection relay. The arc protection in this standard configurationdetects an arc flash and supplies the information for the operating arc protection unit,which de-energizes the faulty area by opening the circuit breaker. For example, fastGOOSE communication is used to route the detected information to the circuitbreaker.

    If the protection relay is ordered with high speed binary outputs, individual arcdetection from ARCSARC1...3 are connected to the dedicated high speed outputsX110:HSO1, X110:HSO2 and X110:HSO3.

    1MRS758128 B Section 3REU615 standard configurations

    REU615 41Application Manual

  • OR6B1B2B3B4B5B6

    O

    ARCSARC1BLOCK ARC_FLT_DET

    ARCSARC2BLOCK ARC_FLT_DET

    ARCSARC3BLOCK ARC_FLT_DET

    ARCSARC1_ARC_FLT_DET

    ARCSARC1_ARC_FLT_DET

    ARCSARC2_ARC_FLT_DET

    ARCSARC2_ARC_FLT_DET

    ARCSARC3_ARC_FLT_DET

    ARCSARC3_ARC_FLT_DET

    ARC_FAULT_DETECTED

    GUID-D27CE92B-3A0B-4155-9DA8-E05BB9B7D4EB V1 EN

    Figure 20: Arc protection with dedicated HSO

    General start and operate from all the functions are connected to the minimum pulsetimer TPGAPC1 for setting the minimum pulse length for the outputs. The outputfrom TPGAPC1 is connected to the binary outputs.

    Section 3 1MRS758128 BREU615 standard configurations

    42 REU615Application Manual

  • OR6B1B2B3B4B5B6

    O

    TPGAPC1IN1IN2

    OUT1OUT2

    OR6B1B2B3B4B5B6

    O

    OR6B1B2B3B4B5B6

    O

    OR6B1B2B3B4B5B6

    O

    OR6B1B2B3B4B5B6

    O

    OR6B1B2B3B4B5B6

    O

    OR6B1B2B3B4B5B6

    O

    OR6B1B2B3B4B5B6

    O

    OR6B1B2B3B4B5B6

    O

    OR6B1B2B3B4B5B6

    O

    GENERAL_START_PULSEGENERAL_OPERATE_PULSE

    FRPFRQ1_OPERATEFRPFRQ2_OPERATEFRPFRQ3_OPERATEFRPFRQ4_OPERATEFRPFRQ5_OPERATEFRPFRQ6_OPERATE

    PHPTOV1_OPERATEPHPTOV2_OPERATEPHPTOV3_OPERATEPHPTUV1_OPERATEPHPTUV2_OPERATEPHPTUV3_OPERATE

    NSPTOV1_OPERATENSPTOV2_OPERATEPSPTUV1_OPERATEPSPTUV2_OPERATE

    ROVPTOV1_OPERATEROVPTOV2_OPERATEROVPTOV3_OPERATE

    FRPFRQ1_STARTFRPFRQ2_STARTFRPFRQ3_STARTFRPFRQ4_STARTFRPFRQ5_STARTFRPFRQ6_START

    PHPTOV1_STARTPHPTOV2_STARTPHPTOV3_STARTPHPTUV1_STARTPHPTUV2_STARTPHPTUV3_START

    NSPTOV1_STARTNSPTOV2_STARTPSPTUV1_STARTPSPTUV2_START

    ROVPTOV1_STARTROVPTOV2_STARTROVPTOV3_START

    GUID-1D22AD17-55D6-4FB1-9EC8-249B1F2F8EE3 V1 EN

    Figure 21: General start and operate signals

    The operate signals from the protection functions are connected to the two trip logicsTRPPTRC1 and TRPPTRC2. The output of these trip logic functions is available atbinary output X100:PO3 and X100:PO4. The trip logic functions are provided with alockout and latching function, event generation and the trip signal duration setting. Ifthe lockout operation mode is selected, binary input X120:BI4 has been assigned tothe RST_LKOUT input of both the trip logic to enable external reset with a pushbutton.

    Three other trip logics TRPPTRC3...4 are also available if the protection relay isordered with high speed binary outputs options.

    1MRS758128 B Section 3REU615 standard configurations

    REU615 43Application Manual

  • TRPPTRC1BLOCKOPERATERST_LKOUT

    TRIPCL_LKOUT

    OR6B1B2B3B4B5B6

    O

    OR6B1B2B3B4B5B6

    O

    OR6B1B2B3B4B5B6

    O

    OR6B1B2B3B4B5B6

    O

    OR6B1B2B3B4B5B6

    O

    TRPPTRC1_TRIPFRPFRQ1_OPERATEFRPFRQ2_OPERATEFRPFRQ3_OPERATEFRPFRQ4_OPERATEFRPFRQ5_OPERATEFRPFRQ6_OPERATE

    PHPTOV1_OPERATEPHPTOV2_OPERATEPHPTOV3_OPERATEPHPTUV1_OPERATEPHPTUV2_OPERATEPHPTUV3_OPERATE

    NSPTOV1_OPERATENSPTOV2_OPERATEPSPTUV1_OPERATEPSPTUV2_OPERATE

    ROVPTOV1_OPERATEROVPTOV2_OPERATEROVPTOV3_OPERATE

    X130_BI4_LOCKOUT_RESET

    GUID-A2FFA630-DE41-472B-8275-93C1D1C0ED00 V1 EN

    Figure 22: Trip logic TRPPTRC1

    OR6B1B2B3B4B5B6

    O

    OR6B1B2B3B4B5B6

    O

    OR6B1B2B3B4B5B6

    O

    OR6B1B2B3B4B5B6

    O

    OR6B1B2B3B4B5B6

    O

    TRPPTRC2BLOCKOPERATERST_LKOUT

    TRIPCL_LKOUT

    TRPPTRC2_TRIPFRPFRQ1_OPERATEFRPFRQ2_OPERATEFRPFRQ3_OPERATEFRPFRQ4_OPERATEFRPFRQ5_OPERATEFRPFRQ6_OPERATE

    PHPTOV1_OPERATEPHPTOV2_OPERATEPHPTOV3_OPERATEPHPTUV1_OPERATEPHPTUV2_OPERATEPHPTUV3_OPERATE

    NSPTOV1_OPERATENSPTOV2_OPERATEPSPTUV1_OPERATEPSPTUV2_OPERATE

    ROVPTOV1_OPERATEROVPTOV2_OPERATEROVPTOV3_OPERATE

    X130_BI4_LOCKOUT_RESET

    GUID-5691FC6D-136E-4BE0-9000-69E1EDB8CCEC V1 EN

    Figure 23: Trip logic TRPPTRC2

    Section 3 1MRS758128 BREU615 standard configurations

    44 REU615Application Manual

  • 3.3.3.2 Functional diagrams for disturbance recorder

    The START and the OPERATE outputs from the protection stages are routed to triggerthe disturbance recorder or, alternatively, only to be recorded by the disturbancerecorder depending on the parameter settings. Additionally, the selected signals fromdifferent functions and the few binary inputs are also connected to the disturbancerecorder.

    RDRE1C1C2C3C4C5C6C7C8C9C10C11C12C13C14C15C16C17C18C19C20C21C22C23C24C25C26C27C28C29C30C31C32C33C34C35C36C37C38C39C40C41C42C43C44C45C46C47C48C49C50C51C52C53C54C55C56C57C58C59C60C61C62C63C64

    TRIGGERED

    OR6B1B2B3B4B5B6

    O

    OR6B1B2B3B4B5B6

    O

    OR6B1B2B3B4B5B6

    O

    OR6B1B2B3B4B5B6

    O

    OR6B1B2B3B4B5B6

    O

    OR6B1B2B3B4B5B6

    O

    OR6B1B2B3B4B5B6

    O

    LSHDPFRQ1_OPERATE

    LSHDPFRQ1_RESTORELSHDPFRQ2_RESTORE

    LSHDPFRQ2_OPERATE

    ARCSARC1_ARC_FLT_DETARCSARC2_ARC_FLT_DETARCSARC3_ARC_FLT_DET

    SECRSYN1_SYNC_OK

    X130_BI2_LINE_VT_MCB_OPENX130_BI3_BUS_VT_MCB_OPEN

    FRPFRQ1_OPERATEFRPFRQ2_OPERATEFRPFRQ3_OPERATEFRPFRQ4_OPERATEFRPFRQ5_OPERATEFRPFRQ6_OPERATE

    PHPTOV1_OPERATEPHPTOV2_OPERATEPHPTOV3_OPERATE

    PHPTUV1_OPERATEPHPTUV2_OPERATEPHPTUV3_OPERATE

    NSPTOV1_OPERATENSPTOV2_OPERATEPSPTUV1_OPERATEPSPTUV2_OPERATE

    ROVPTOV1_OPERATEROVPTOV2_OPERATEROVPTOV3_OPERATE

    FRPFRQ1_STARTFRPFRQ2_STARTFRPFRQ3_STARTFRPFRQ4_STARTFRPFRQ5_STARTFRPFRQ6_START

    PHPTOV1_STARTPHPTOV2_STARTPHPTOV3_STARTPHPTUV1_STARTPHPTUV2_STARTPHPTUV3_START

    NSPTOV1_STARTNSPTOV2_STARTPSPTUV1_STARTPSPTUV2_START

    ROVPTOV1_STARTROVPTOV2_STARTROVPTOV3_START

    LSHDPFRQ3_OPERATELSHDPFRQ4_OPERATELSHDPFRQ5_OPERATE

    LSHDPFRQ3_RESTORELSHDPFRQ4_RESTORELSHDPFRQ5_RESTORE

    SECRSYN1_SYNC_INPRO

    LSHDPFRQ1_STARTLSHDPFRQ2_STARTLSHDPFRQ3_STARTLSHDPFRQ4_STARTLSHDPFRQ5_START

    DISTURB_RECORD_TRIGGERED

    GUID-311D3D6F-EF61-41FF-8098-E9506DEFA85D V1 EN

    Figure 24: Disturbance recorder

    3.3.3.3 Functional diagrams for control and interlocking

    The main purpose of the synchronism and energizing check SECRSYN1 is to providecontrol over the closing of the circuit breakers in power networks to prevent the

    1MRS758128 B Section 3REU615 standard configurations

    REU615 45Application Manual

  • closing if the conditions for synchronism are not detected. The energizing functionallows closing, for example, when one side of the circuit breaker is dead.

    SECRSYN1 measures the bus and line voltages and compares them to set conditions.When all the measured quantities are within set limits, the output SYNC_OK isactivated. The SYNC_OK output signal of SECRSYN is connected to the binaryoutput X100:PO2. The function is blocked, in case line side or bus side MCB is open.

    SECRSYN1BLOCKCL_COMMANDBYPASS

    SYNC_INPROSYNC_OK

    CL_FAIL_ALCMD_FAIL_AL

    LLDBLLLBDLLBDLDB

    SECRSYN1_SYNC_OKBLOCK_SECRSYN1 SECRSYN1_SYNC_INPRO

    OR6B1B2B3B4B5B6

    O BLOCK_SECRSYN1X130_BI1_PRIMARY_VT_FUSE_BLOWNX130_BI2_LINE_VT_MCB_OPENX130_BI3_BUS_VT_MCB_OPEN

    GUID-9CCE0F59-600A-412B-AA0A-4E4D57CB4CCC V1 EN

    Figure 25: Synchrocheck function

    Two types of disconnector and earthing switch function blocks are available.DCSXSWI1...3 and ESSXSWI1...2 are status only type, and DCXSWI1...2 andESXSWI1 are controllable type. By default, the status only blocks are connected instandard configuration. The disconnector (CB truck) is connected to DCSXSWI1 andline side earthing switch status information is connected to ESSXSI1.

    ESSXSWI1POSOPENPOSCLOSE

    OPENPOSCLOSEPOS

    OKPOS

    X110_BI8_ES1_OPENEDX110_BI7_ES1_CLOSED

    DCSXSWI1POSOPENPOSCLOSE

    OPENPOSCLOSEPOS

    OKPOS

    X110_BI6_VT_DC1_OPENEDX110_BI5_VT_DC1_CLOSED

    GUID-F7D07794-69E5-45BE-983E-672D9417213C V1 EN

    Figure 26: Disconnector and earth-switch control logic

    3.3.3.4 Functional diagrams for measurement functions

    The three-phase bus side phase voltage and single-phase line side phase voltage inputsto the protection relay are measured by the three-phase voltage measurementVMMXU1 and VMMXU2. The voltage input is connected to the X130 card in theback panel. The sequence voltage measurement VSMSQI1 measures the sequencevoltage.

    The measurements can be seen in the LHMI and they are available under themeasurement option in the menu selection. Based on the settings, function blocks can

    Section 3 1MRS758128 BREU615 standard configurations

    46 REU615Application Manual

  • generate low alarm or warning and high alarm or warning signals for the measuredcurrent values.

    The frequency measurement FMMXU1 of the power system is available. The loadprofile record LDPRLRC1 is included in the measurements sheet. LDPRLRC1 offersthe ability to observe the loading history of the corresponding feeder.

    VMMXU1BLOCK HIGH_ALARM

    HIGH_WARNLOW_WARN

    LOW_ALARM

    GUID-6B7DC952-6857-4183-A474-D01CDC1BFB9A V1 EN

    Figure 27: Voltage measurement: Three-phase voltage measurement

    VSMSQI1

    GUID-3569EF4C-561C-42B3-B259-7C53DC402B67 V1 EN

    Figure 28: Voltage measurement: Sequence voltage measurement

    RESVMMXU1BLOCK HIGH_ALARM

    HIGH_WARN

    GUID-357F2289-1823-4D2D-A6F2-A9CD25F50CA2 V1 EN

    Figure 29: Voltage measurement: Residual voltage measurement

    VMMXU2BLOCK HIGH_ALARM

    HIGH_WARNLOW_WARN

    LOW_ALARM

    GUID-2954D877-B9C2-4977-8131-AB1BFDFF875A V1 EN

    Figure 30: Voltage measurement: Three-phase voltage measurement

    FMMXU1

    GUID-3A350A86-323A-4AA7-86DC-BC0263AA2B11 V1 EN

    Figure 31: Other measurement: Frequency measurement

    FLTRFRC1BLOCKCB_CLRD

    GUID-99FC75A8-659E-420C-958D-0829CF9A4152 V2 EN

    Figure 32: Other measurement: Data monitoring

    1MRS758128 B Section 3REU615 standard configurations

    REU615 47Application Manual

  • LDPRLRC1RSTMEM MEM_WARN

    MEM_ALARM

    GUID-27DA4FD3-9AB2-4F0A-B7ED-FD43B8437170 V2 EN

    Figure 33: Other measurement: Load profile record

    3.3.3.5 Functional diagrams for I/O and alarm LEDs

    ORB1B2

    O

    ORB1B2

    O

    ORB1B2

    O

    ORB1B2

    O

    ORB1B2

    O

    ORB1B2

    O

    ORB1B2

    O

    X110_BI1_SG_CHANGE

    X110_BI6_VT_DC1_OPENED

    X110_BI5_VT_DC1_CLOSED

    X110_BI8_ES1_OPENED

    X110_BI7_ES1_CLOSED

    X110_BI2_MANUAL_RESTORE_GR1

    X110_BI3_MANUAL_RESTORE_GR2X110 (BIO).X110-Input 3

    X110 (BIO-H).X110-Input 5

    X110 (BIO).X110-Input 1

    X110 (BIO-H).X110-Input 6

    X110 (BIO).X110-Input 5

    X110 (BIO-H).X110-Input 8

    X110 (BIO).X110-Input 6

    X110 (BIO).X110-Input 8

    X110 (BIO-H).X110-Input 3

    X110 (BIO-H).X110-Input 1

    X110 (BIO).X110-Input 7

    X110 (BIO-H).X110-Input 2

    X110 (BIO).X110-Input 2

    X110 (BIO-H).X110-Input 7

    GUID-7673B764-A100-40BB-97B1-F351022BAA59 V1 EN

    Figure 34: Default binary inputs - X110

    Section 3 1MRS758128 BREU615 standard configurations

    48 REU615Application Manual

  • X130_BI1_PRIMARY_VT_FUSE_BLOWN

    X130_BI2_LINE_VT_MCB_OPEN

    X130_BI3_BUS_VT_MCB_OPEN

    X130_BI4_LOCKOUT_RESET

    X130 (AIM).X130-Input 1

    X130 (AIM).X130-Input 2

    X130 (AIM).X130-Input 3

    X130 (AIM).X130-Input 4GUID-2A98DEBA-77CD-4C56-8752-E71F5C81C665 V1 EN

    Figure 35: Default binary inputs - X130

    LSHDPFRQ1_OPERATE

    LSHDPFRQ1_RESTORE

    LSHDPFRQ2_RESTORE

    LSHDPFRQ2_OPERATE

    ARCSARC1_ARC_FLT_DET

    ARCSARC2_ARC_FLT_DET

    ARCSARC3_ARC_FLT_DET

    X110 (BIO).X110-SO1

    X110 (BIO).X110-SO2

    X110 (BIO).X110-SO3

    X110 (BIO).X110-SO4

    X110 (BIO-H).X110-HSO1

    X110 (BIO-H).X110-HSO2

    X110 (BIO-H).X110-HSO3

    GUID-06520671-4C0E-4A42-B368-E1298EAAF9CD V1 EN

    Figure 36: Default binary outputs - X110

    SECRSYN1_SYNC_OK

    GENERAL_START_PULSE

    GENERAL_OPERATE_PULSE

    TRPPTRC1_TRIP

    TRPPTRC2_TRIP

    FALSE

    X100 (PSM).X100-PO2

    X100 (PSM).X100-SO1

    X100 (PSM).X100-SO2

    X100 (PSM).X100-PO3

    X100 (PSM).X100-PO4

    X100 (PSM).X100-PO1

    GUID-42D5E662-A59C-4505-9441-6E80E1F134FD V1 EN

    Figure 37: Default binary outputs - X100

    1MRS758128 B Section 3REU615 standard configurations

    REU615 49Application Manual

  • LED1

    O:77|T:2.5|I:1

    OKALARMRESET

    LED2

    O:97|T:2.5|I:2

    OKALARMRESET

    LED3

    O:75|T:2.5|I:3

    OKALARMRESET

    LED4

    O:79|T:2.5|I:4

    OKALARMRESET

    LED5

    O:86|T:2.5|I:5

    OKALARMRESET

    PHPTOV_OPERATE

    PHPTUV_OPERATE

    ROVPTOV_OPERATE

    SEQUENCE_VOLTAGE_OPERATE

    FREQUENCY_OPERATE

    GUID-44B1C7FE-4A35-4D45-BBF8-56E360B58016 V1 EN

    Section 3 1MRS758128 BREU615 standard configurations

    50 REU615Application Manual

  • LED6

    O:83|T:2.5|I:6

    OKALARMRESET

    LED7

    O:73|T:2.5|I:7

    OKALARMRESET

    LED8

    O:84|T:2.5|I:8

    OKALARMRESET

    LED9

    O:93|T:2.5|I:9

    OKALARMRESET

    LED10

    O:81|T:2.5|I:10

    OKALARMRESET

    LED11

    O:116|T:2.5|I:11

    OKALARMRESET

    OR

    O:92|T:2.5|I:7

    B1B2

    O

    SECRSYN1_SYNC_OK

    X130_BI1_PRIMARY_VT_FUSE_BLOWN

    X130_BI2_LINE_VT_MCB_OPENX130_BI3_BUS_VT_MCB_OPEN

    DISTURB_RECORD_TRIGGERED

    ARC_FAULT_DETECTED

    LOAD_SHEDDING_OPERATE

    GUID-3F5FEAE6-4F62-4B0D-B032-422CA41C5993 V1 EN

    Figure 38: Default LED connections

    3.3.3.6 Other functions

    The configuration includes few instances of multipurpose protection functionMAPGAPC, runtime counter for machines and devices MDSOPT, trip circuitsupervision, different types of timers and control functions. These functions are notincluded in application configuration but they can be added based on the systemrequirements.

    3.4 Standard configuration B

    3.4.1 Applications

    The standard configuration is intended for automatic voltage regulator of powertransformers equipped with a on-load tap changer. It also features three-stage three-

    1MRS758128 B Section 3REU615 standard configurations

    REU615 51Application Manual

  • phase non-directional overcurrent protection, three-phase under- and overvoltageprotection. The configuration also incorporates a thermal overload protectionfunction, which supervises the thermal stress of the transformer windings to preventpremature aging of the winding’s insulation.

    The RTD/mA input module is optional in the configuration. While using the RTD/mAinput module, it is possible to have the tap changer position indication as an mA signal.Ambient temperature of the power transformer can be used in thermal protection andthe multi-purpose protection functions are also available. The multi-purposeprotection function enables protection based on analog values from the IEDsRTD/mA input module or from other IEDs using analog horizontal GOOSEmessaging.

    The protection relay with a standard configuration is delivered from the factory withdefault settings and parameters. The end-user flexibility for incoming, outgoing andinternal signal designation within the protection relay enables this configuration to befurther adapted to different primary circuit layouts and the related functionality needsby modifying the internal functionality using PCM600.

    Section 3 1MRS758128 BREU615 standard configurations

    52 REU615Application Manual

  • 3.4.2 Functions

    CONDITION MONITORING AND SUPERVISION

    ORAND

    CONTROL AND INDICATION 1) MEASUREMENT

    PROTECTION LOCAL HMI

    Object Ctrl 2) Ind 3)

    CB

    DC

    ES1) Check availability of binary inputs/outputs

    from technical documentation2) Control and indication function for

    primary object3) Status indication function for primary object

    1 -

    2 3

    1 2

    STANDARD CONFIGURATION

    RL

    ClearESCI

    O

    Configuration ASystemHMITimeAuthorization

    RL

    ClearESCI

    O

    U12 0. 0 kVP 0.00 kWQ 0.00 kVAr

    IL2 0 A

    A

    COMMUNICATION

    Protocols: IEC 61850-8-1/9-2LE Modbus®

    IEC 60870-5-103 Interfaces: Ethernet: TX (RJ45), FX (LC) Serial: Serial glass fiber (ST), RS-485, RS-232Redundant protocols: HSR PRP RSTP

    REU615

    - I, U, P, Q, E, pf- Symmetrical components- Limit value supervision- Load profile record- RTD/mA measurement (optional)

    4

    3

    B

    OR

    REMARKS

    Optionalfunction

    No. ofinstances

    Alternative function to be defined when ordering

    Io/Uo

    Calculatedvalue

    Sum of phase currents

    I∑

    Analog interface types 1)

    Current transformer

    Voltage transformer1) Conventional transformer inputs

    ALSO AVAILABLE

    - Disturbance and fault recorders- Event log and recorded data- Local/Remote push button on LHMI- Self-supervision - Time synchronization: IEEE 1588 v2,

    SNTP, IRIG-B- User management- Web HMI

    VOLTAGE PROTECTION AND CONTROL RELAYAutomatic voltage regulator

    2×TCSTCM

    2×Master Trip

    Lockout relay94/86

    3×3U<27

    3×3U>59

    FUSEF60

    MCS 3IMCS 3I

    TPOSM84M

    COLTC90V

    3I>>>50P/51P

    3I>51P-1

    3I>>51P-2

    18×MAPMAP

    OPTSOPTM

    UL1UL2UL3

    3I

    3I

    I∑

    6xRTD2xmA

    3Ith>T/G/C49T/G/C

    GUID-B0EC6C7D-3A58-4A5B-9A52-2D20D98AAD02 V1 EN

    Figure 39: Functionality overview for standard configuration B

    3.4.2.1 Default I/O connections

    Connector pins for each input and output are presented in the Protection relay'sphysical connections section.

    1MRS758128 B Section 3REU615 standard configurations

    REU615 53Application Manual

  • Table 16: Default connections for analog inputs

    Analog input Description Connector pinsIL1 Phase A current X120:7-8

    IL2 Phase B current X120:9-10

    IL3 Phase C current X120:11-12

    Io Residual current X120:13-14

    U1 Phase voltage U1 X120:1-2

    U2 Phase voltage U2 X120:3-4

    U3 Phase voltage U3 X120:5-6

    AI1 Tap change position X130:1-2

    AI2 - X130:3-4

    AI3 Ambient temperature X130:5-6

    AI4 - X130:7-8

    AI5 - X130:9-10

    AI6 - X130:13-14

    AI7 - X130:15-16

    AI8 - X130:17-18

    Table 17: Default connections for binary inputs

    Binary input Description Connector pinsX110-BI1 Tap changer operate X110:1-2

    X110-BI2 Voltage transformer secondary MCB open X110:3-4

    X110-BI3 Lower local request X110:5-6

    X110-BI4 Raise local request X110:7-6

    X110-BI5 - X110:8-9

    X110-BI6 - X110:10-9

    X110-BI7 Circuit breaker closed position indication X110:11-12

    X110-BI8 Circuit breaker open position indication X110:13-12

    X130-BI1 BCD sign bit (tap changer position) X130:1-2

    X130-BI2 BCD bit 0 (LSB) X130:3-2

    X130-BI3 BCD bit 1 X130:4-5

    X130-BI4 BCD bit 2 X130:6-5

    X130-BI5 BCD bit 3 X130:7-8

    X130-BI6 BCD Bit 4 (MSB) X130:9-8

    Section 3 1MRS758128 BREU615 standard configurations

    54 REU615Application Manual

  • Table 18: Default connections for binary outputs

    Binary output Description Connector pinsX100-PO1 Lower own command X100:6-7

    X100-PO2 Raise own command X100:8-9

    X100-SO1 General start indication X100:10-11,(12)

    X100-SO2 General operate indication X100:13-14

    X100-PO3 Master trip X100:15-19

    X100-PO4 Close circuit beaker X100:20-24

    X110-SO1 Tap changer control alarm X110:14-16

    X110-SO2 Overcurrent operate alarm X110:17-19

    X110-SO3 Voltage protection operate alarm X110:20-22

    X110-SO4 Overload protection operate alarm X110:23-24

    Table 19: Default connections for LEDs

    LED Description1 Overcurrent protection operate

    2 Overvoltage protection operate

    3 Undervoltage protection operate

    4 Thermal overload protection operate

    5 Raise own

    6 Lower own

    7 Disturbance recorder triggered

    8 Tap changer control alarm

    9 Supervision

    10 Tap changer operates

    11 -

    3.4.2.2 De