20
Effective August 2016 Application Data AD013001EN Time Current Curves Series NRX NF and RF Circuit Breakers PXR 20/25 Trip Units Contents Description Page Revision notes 2 PXR catalog number convention 3 PXR 20 trip units 4 PXR 25 trip units 5 Curves Long Delay I 2 t and Short Delay Flat Response: TC013001E 6 Long Delay I 2 t and Short Delay I 2 t Response TC013002E 7 Long Delay I 05 t and Short Delay Flat Response: TC013003E 8 Long Delay I 05 t and Short Delay I 2 t Response: TC013004E 9 Long Delay I 1 t and Short Delay Flat Response: TC013005E 10 Long Delay I 1 t and Short Delay I 2 t Response: TC013006E 11 Long Delay I 4 t and Short Delay Flat Response: TC013007E 12 Long Delay I 4 t and Short Delay I 2 t Response: TC013008E 13 Ground (Earth) Flat Response: TC013009E 14 Ground (Earth) I 2 t Response: TC013010E 15 Instantaneous Response: TC013011E 16 High Instantaneous Response: TC013012E 17 Maintenance Mode Protection Response: TC013013E 18

Application Data AD013001EN Time Current Curves Series ......2 Application Data AD013001EN Effective August 2016 Time Current Curves Series NRX NF and RF Circuit Breakers PXR 20/25

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Application Data AD013001EN Time Current Curves Series ......2 Application Data AD013001EN Effective August 2016 Time Current Curves Series NRX NF and RF Circuit Breakers PXR 20/25

Effective August 2016Application Data AD013001EN

Time Current CurvesSeries NRX NF and RF Circuit BreakersPXR 20/25 Trip Units

ContentsDescription Page

Revision notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2PXR catalog number convention . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3PXR 20 trip units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4PXR 25 trip units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Curves

Long Delay I2t and Short Delay Flat Response: . . . . . . . . . . . . . . . . . . . . . . . . . . . . TC013001E . . . . . . . . 6Long Delay I2t and Short Delay I2t Response . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TC013002E . . . . . . . . 7Long Delay I0 .5t and Short Delay Flat Response: . . . . . . . . . . . . . . . . . . . . . . . . . . . TC013003E . . . . . . . . . 8Long Delay I0 .5t and Short Delay I2t Response: . . . . . . . . . . . . . . . . . . . . . . . . . . . . TC013004E . . . . . . . . 9Long Delay I1t and Short Delay Flat Response: . . . . . . . . . . . . . . . . . . . . . . . . . . . . TC013005E . . . . . . . 10Long Delay I1t and Short Delay I2t Response: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TC013006E . . . . . . . 11Long Delay I4t and Short Delay Flat Response: . . . . . . . . . . . . . . . . . . . . . . . . . . . . TC013007E . . . . . . . 12Long Delay I4t and Short Delay I2t Response: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TC013008E . . . . . . . 13Ground (Earth) Flat Response: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TC013009E . . . . . . . 14Ground (Earth) I2t Response: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TC013010E . . . . . . . 15Instantaneous Response: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TC013011E . . . . . . . 16High Instantaneous Response: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TC013012E . . . . . . . 17Maintenance Mode Protection Response: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TC013013E . . . . . . . 18

Page 2: Application Data AD013001EN Time Current Curves Series ......2 Application Data AD013001EN Effective August 2016 Time Current Curves Series NRX NF and RF Circuit Breakers PXR 20/25

2

Application Data AD013001ENEffective August 2016

Time Current Curves Series NRX NF and RF Circuit Breakers

PXR 20/25 Trip Units

EATON www.eaton.com

Revision notes

ote:N Unless noted below, all curves remain unchanged from their prior revision .

Page 3: Application Data AD013001EN Time Current Curves Series ......2 Application Data AD013001EN Effective August 2016 Time Current Curves Series NRX NF and RF Circuit Breakers PXR 20/25

3

Application Data AD013001ENEffective August 2016

Time Current Curves Series NRX NF and RF Circuit Breakers PXR 20/25 Trip Units

EATON www.eaton.com

PXR catalog number convention

Table 1. Breakdown of the PXR Trip Unit Catalog Numbering Convention.

General curve notes:

1 . These curves apply to 50Hz and 60Hz applications .

2 . These curves are comprehensive for Series NRX NF/RF (IZMX 16/40) style circuit breakers including all frame sizes, ratings and con-structions . The total clearing times shown include the response time for the trip unit, the breaker opening and the interruption of the current . The bottom of the time band is the minimum commit to trip time .

3 . These curves apply to an ambient of -20°C to +50°C . Trip Unit temperature above 85°C will cause an over-temperature trip and light the Long cause of trip LED .

4 . The end of the curve is determined by the application or the interrupting rating of the circuit breaker .

Page 4: Application Data AD013001EN Time Current Curves Series ......2 Application Data AD013001EN Effective August 2016 Time Current Curves Series NRX NF and RF Circuit Breakers PXR 20/25

4

Application Data AD013001ENEffective August 2016

Time Current Curves Series NRX NF and RF Circuit Breakers

PXR 20/25 Trip Units

EATON www.eaton.com

PXR 20 trip units

Figure 1. PXR 20 Trip Units .

LSI W/Maintenance Mode

LSI LSIG W/Maintenance Mode

LSIG

Page 5: Application Data AD013001EN Time Current Curves Series ......2 Application Data AD013001EN Effective August 2016 Time Current Curves Series NRX NF and RF Circuit Breakers PXR 20/25

5

Application Data AD013001ENEffective August 2016

Time Current Curves Series NRX NF and RF Circuit Breakers PXR 20/25 Trip Units

EATON www.eaton.com

PXR 25 trip units

Figure 2. PXR 25 Trip Units .

LSI W/Maintenance Mode

LSI LSIG W/Maintenance Mode

LSIG

Page 6: Application Data AD013001EN Time Current Curves Series ......2 Application Data AD013001EN Effective August 2016 Time Current Curves Series NRX NF and RF Circuit Breakers PXR 20/25

6

Application Data AD013001ENEffective August 2016

Time Current Curves Series NRX NF and RF Circuit Breakers

PXR 20/25 Trip Units

EATON www.eaton.com

Curves

Figure 3. PXR 20/25 Long Delay I2t and Short Delay Flat Response Curve Number: TC013001E August 2016 .

Power Xpert Release - PXR 20 / PXR 25

Time Current Curves

Series NRX NF and RF Frame Circuit Breakers

Long Delay I2t and Short Delay Flat Curves

Notes:

1 . Long Delay pickup is 110% of the Ir setting (0 .4, 0 .5, 0 .6, 0 .7, 0 .75, 0 .8, 0 .9, 0 .95, 1 .0) with ±5% tolerance .

2 . Long Delay Time Settings 0 .5s to 24s have +0%/-30% tolerance .

3 . If Thermal Memory is enabled, trip times may be shorter than indicated in this curve .

4 . Short Delay pickup settings have ±10% tolerance .

5 . If the Long Delay time is projected to be faster than the Short Delay time, the Long Delay trip time will go no faster than the Short Delay time value .

6 . With ZSI enabled, tripping times for 3-phase faults, no aux . power will be a maximum of 75ms for 60Hz and 80ms for 50Hz .

Page 7: Application Data AD013001EN Time Current Curves Series ......2 Application Data AD013001EN Effective August 2016 Time Current Curves Series NRX NF and RF Circuit Breakers PXR 20/25

7

Application Data AD013001ENEffective August 2016

Time Current Curves Series NRX NF and RF Circuit Breakers PXR 20/25 Trip Units

EATON www.eaton.com

Figure 4. PXR 20/25 Long Delay I2t and Short Delay I2t Response Curve Number: TC013002E August 2016.

Power Xpert Release - PXR 20 / PXR 25

Time Current Curves

Series NRX NF and RF Frame Circuit Breakers

Long Delay I2t and Short Delay I2t Curves

Notes:

1 . Long Delay pickup is 110% of the Ir setting (0 .4, 0 .5, 0 .6, 0 .7, 0 .75, 0 .8, 0 .9, 0 .95, 1 .0) with ± 5% tolerance .

2 . Long Delay Time Settings 0 .5s to 24s have +0% /-30% tolerance .

3 . If Thermal Memory is enabled, trip times may be shorter than indicated in this curve .

4 . Short Delay pickup settings have ±10% tolerance .

5 . Short Time delay (0 .5, 0 .4, 0 .3) I2t slopes have a +0%/-30% tolerance, 0 .1s slope has a +0%/-40% tolerance .

6 . If the Long Delay time is projected to be faster than the Short Delay time, the Long Delay trip time will go no faster than the Short Delay time value .

7 . With ZSI enabled, tripping times for 3-phase faults, no aux . power will be a maximum of 75ms for 60Hz and 80ms for 50Hz .

Page 8: Application Data AD013001EN Time Current Curves Series ......2 Application Data AD013001EN Effective August 2016 Time Current Curves Series NRX NF and RF Circuit Breakers PXR 20/25

8

Application Data AD013001ENEffective August 2016

Time Current Curves Series NRX NF and RF Circuit Breakers

PXR 20/25 Trip Units

EATON www.eaton.com

Figure 5. PXR 20/25 Long Delay I0.5t and Short Delay Flat Response Curve Number: TC013003E August 2016.

Power Xpert Release - PXR 20 / PXR 25

Time Current Curves

Series NRX NF and RF Frame Circuit Breakers

Long Delay I0.5t and Short Delay Flat Curves

Notes:

1 . Long Delay pickup is 110% of the Ir setting (0 .4, 0 .5, 0 .6, 0 .7, 0 .75, 0 .8, 0 .9, 0 .95, 1 .0) with ±5% tolerance .

2 . Long Delay Time Settings 0.5, 1, 2, 4, 7, 10, 12, 15, 20, 24s (not all shown) have +0%/-30% toler-ance.

3 . If Thermal Memory is enabled, trip times may be shorter than indicated in this curve.

4 . Short Delay pickup settings of 1.5, 2, 2.5, 3, 4, 5, 6, 7, 8, 10 (not all shown) have ±10% tolerance.

5 . If the Long Delay time is projected to be faster than the Short Delay time, the Long Delay trip time will go no faster than the Short Delay time value.

6 . With ZSI enabled, tripping times for 3-phase faults, no aux. power will be a maximum of 75ms for 60Hz and 80ms for 50Hz.

Page 9: Application Data AD013001EN Time Current Curves Series ......2 Application Data AD013001EN Effective August 2016 Time Current Curves Series NRX NF and RF Circuit Breakers PXR 20/25

9

Application Data AD013001ENEffective August 2016

Time Current Curves Series NRX NF and RF Circuit Breakers PXR 20/25 Trip Units

EATON www.eaton.com

Figure 6. PXR 20/25 Long Delay I0.5t and Short Delay I2t Response Curve Number: TC013004E August 2016.

Power Xpert Release - PXR 20 / PXR 25

Time Current Curves

Series NRX NF and RF Frame Circuit Breakers

Long Delay I0.5t and Short Delay I2t Curves

Notes:

1 . Long Delay pickup is 110% of the Ir setting (0 .4, 0 .5, 0 .6, 0 .7, 0 .75, 0 .8, 0 .9, 0 .95, 1 .0) with ± 5% tolerance .

2 . Long Delay Time Settings 0 .5, 1, 2, 4, 7, 10, 12, 15, 20, 24s (not all shown) have +0%/-30% tolerance .

3 . If Thermal Memory is enabled, trip times may be shorter than indicated in this curve .

4 . Short Delay pickup settings of 1 .5, 2, 2 .5, 3, 4, 5, 6, 7, 8, 10 (not all shown) have ±10% tolerance .

5 . Short Time delay (0 .5, 0 .4, 0 .3) I2t slopes have a +0%/-30% tolerance, 0 .1s slope has a +0%/-40% tolerance .

6 . If the Long Delay time is projected to be faster than the Short Delay time, the Long Delay trip time will go no faster than the Short Delay time value .

7 . With ZSI enabled, tripping times for 3-phase faults, no aux . power will be a maximum of 75ms for 60Hz and 80ms for 50Hz .

Page 10: Application Data AD013001EN Time Current Curves Series ......2 Application Data AD013001EN Effective August 2016 Time Current Curves Series NRX NF and RF Circuit Breakers PXR 20/25

10

Application Data AD013001ENEffective August 2016

Time Current Curves Series NRX NF and RF Circuit Breakers

PXR 20/25 Trip Units

EATON www.eaton.com

Figure 7. PXR 20/25 Long Delay I1t and Short Delay Flat Response Curve Number: TC013005E August 2016.

Power Xpert Release - PXR 20 / PXR 25

Time Current Curves

Series NRX NF and RF Frame Circuit Breakers

Long Delay I1t and Short Delay Flat Curves

Notes:

1 . Long Delay pickup is 110% of the Ir setting (0 .4, 0 .5, 0 .6, 0 .7, 0 .75, 0 .8, 0 .9, 0 .95, 1 .0) with ±5% tolerance .

2 . Long Delay Time Settings 0 .5, 1, 2, 4, 7, 10, 12, 15, 20, 24s (not all shown) have +0%/-30% tolerance .

3 . If Thermal Memory is enabled, trip times may be shorter than indicated in this curve .

4 . Short Delay pickup settings have of 1 .5, 2, 2 .5, 3, 4, 5, 6, 7, 8, 10 (not all shown) ±10% tolerance .

5 . If the Long Delay time is projected to be faster than the Short Delay time, the Long Delay trip time will go no faster than the Short Delay time value .

6 . With ZSI enabled, tripping times for 3-phase faults, no aux . power will be a maximum of 75ms for 60Hz and 80ms for 50Hz .

Page 11: Application Data AD013001EN Time Current Curves Series ......2 Application Data AD013001EN Effective August 2016 Time Current Curves Series NRX NF and RF Circuit Breakers PXR 20/25

11

Application Data AD013001ENEffective August 2016

Time Current Curves Series NRX NF and RF Circuit Breakers PXR 20/25 Trip Units

EATON www.eaton.com

Figure 8. PXR 20/25 Long Delay I1t and Short Delay I2t Response Curve Number: TC013006E August 2016.

Power Xpert Release - PXR 20 / PXR 25

Time Current Curves

Series NRX NF and RF Frame Circuit Breakers

Long Delay I1t and Short Delay I2t Curves

Notes:

1 . Long Delay pickup is 110% of the Ir setting (0 .4, 0 .5, 0 .6, 0 .7, 0 .75, 0 .8, 0 .9, 0 .95, 1 .0) with ±5% tolerance .

2 . Long Delay Time Settings 0 .5, 1, 2, 4, 7, 10, 12, 15, 20, 24s (not all shown) have +0%/-30% tolerance .

3 . If Thermal Memory is enabled, trip times may be shorter than indicated in this curve .

4 . Short Delay pickup settings of 1 .5, 2, 2 .5, 3, 4, 5, 6, 7, 8, 10 (not all shown) have ±10% tolerance .

5 . Short Time delay (0 .5, 0 .4, 0 .3) I2t slopes have a +0%/-30% tolerance, 0 .1s slope has a +0%/-40% tolerance .

6 . If the Long Delay time is projected to be faster than the Short Delay time, the Long Delay trip time will go no faster than the Short Delay time value .

7 . With ZSI enabled, tripping times for 3-phase faults, no aux . power will be a maximum of 75ms for 60Hz and 80ms for 50Hz .

Page 12: Application Data AD013001EN Time Current Curves Series ......2 Application Data AD013001EN Effective August 2016 Time Current Curves Series NRX NF and RF Circuit Breakers PXR 20/25

12

Application Data AD013001ENEffective August 2016

Time Current Curves Series NRX NF and RF Circuit Breakers

PXR 20/25 Trip Units

EATON www.eaton.com

Figure 9. PXR 20/25 Long Delay I4t and Short Delay Flat Response Curve Number: TC013007E August 2016.

Power Xpert Release - PXR 20 / PXR 25

Time Current Curves

Series NRX NF and RF Frame Circuit Breakers

Long Delay I4t and Short Delay Flat Curves

Notes:

1 . Long Delay pickup is 110% of the Ir setting (0 .4, 0 .5, 0 .6, 0 .7, 0 .75, 0 .8, 0 .9, 0 .95, 1 .0) with ±5% tolerance .

2 . Long Delay Time Settings 0 .5s to 7s have +0%/-30% tolerance .

3 . If Thermal Memory is enabled, trip times may be shorter than indicated in this curve .

4 . Short Delay pickup settings of 1 .5, 2, 2 .5, 3, 4, 5, 6, 7, 8, 10 (not all shown) have ±10% tolerance .

5 . If the Long Delay time is projected to be faster than the Short Delay time, the Long Delay trip time will go no faster than the Short Delay time value .

6 . With ZSI enabled, tripping times for 3-phase faults, no aux . power will be a maximum of 75ms for 60Hz and 80ms for 50Hz .

7 . For the Long Time I4t slope only, all settings above 7 seconds will default to a maximum allowable 7 second time delay band .

Page 13: Application Data AD013001EN Time Current Curves Series ......2 Application Data AD013001EN Effective August 2016 Time Current Curves Series NRX NF and RF Circuit Breakers PXR 20/25

13

Application Data AD013001ENEffective August 2016

Time Current Curves Series NRX NF and RF Circuit Breakers PXR 20/25 Trip Units

EATON www.eaton.com

Figure 10. PXR 20/25 Long Delay I4t and Short Delay I2t Response Curve Number: TC013008E August 2016.

Power Xpert Release - PXR 20 / PXR 25

Time Current Curves

Series NRX NF and RF Frame Circuit Breakers

Long Delay I4t and Short Delay I2t Curves

Notes:

1 . Long Delay pickup is 110% of the Ir setting (0 .4, 0 .5, 0 .6, 0 .7, 0 .75, 0 .8, 0 .9, 0 .95, 1 .0) with ±5% tolerance .

2 . Long Delay Time Settings 0 .5s to 7s have +0%/-30% tolerance .

3 . If Thermal Memory is enabled, trip times may be shorter than indicated in this curve .

4 . Short Delay pickup settings of 1 .5, 2, 2 .5, 3, 4, 5, 6, 7, 8, 10 (not all shown) have ±10% tolerance .

5 . Short Time delay (0 .5, 0 .4, 0 .3) I2t slopes have a +0%/-30% tolerance, 0 .1s slope has a +0%/-40% tolerance .

6 . If the Long Delay time is projected to be faster than the Short Delay time, the Long Delay trip time will go no faster than the Short Delay time value .

7 . With ZSI enabled, tripping times for 3-phase faults, no aux . power will be a maximum of 75ms for 60Hz and 80ms for 50Hz .

8 . For the Long Time I4t slope only, all settings above 7 seconds will default to a maximum allowable 7 second time delay band .

Page 14: Application Data AD013001EN Time Current Curves Series ......2 Application Data AD013001EN Effective August 2016 Time Current Curves Series NRX NF and RF Circuit Breakers PXR 20/25

14

Application Data AD013001ENEffective August 2016

Time Current Curves Series NRX NF and RF Circuit Breakers

PXR 20/25 Trip Units

EATON www.eaton.com

Figure 11. PXR 20/25 Ground (Earth) Flat Response Curve Number: TC013009E August 2016.

Power Xpert Release - PXR 20 / PXR 25

Time Current Curves

Series NRX NF and RF Frame Circuit Breakers

Ground (Earth) Flat Curves

Notes:

1 . Ground Pickup settings shown are for Residual sensing with a tolerance of ± 10% . Pick up settings for Source Ground/Zero Sequence sensing have a tolerance of ± 15% .

2 . Ground slope Flat, trip time tolerance is +0ms/-80ms for all settings except 0 .1s setting is +0ms/-40ms

3 . If Thermal Memory is enabled, trip times may be shorter than indicated in this curve .

4 . With ZSI enabled, tripping times for 3-phase faults, no aux . power will be a maximum of 75ms for 60Hz and 80ms for 50Hz .

Page 15: Application Data AD013001EN Time Current Curves Series ......2 Application Data AD013001EN Effective August 2016 Time Current Curves Series NRX NF and RF Circuit Breakers PXR 20/25

15

Application Data AD013001ENEffective August 2016

Time Current Curves Series NRX NF and RF Circuit Breakers PXR 20/25 Trip Units

EATON www.eaton.com

Figure 12. PXR 20/25 Ground (Earth) I2t Response Curve Number: TC013010E August 2016.

Power Xpert Release - PXR 20 / PXR 25

Time Current Curves

Series NRX NF and RF Frame Circuit Breakers

Ground (Earth) I2t Curves

Notes:

1 . Ground Pickup settings shown are for Residual sensing with a tolerance of ± 10% . Pick up settings for Source Ground/Zero Sequence sensing have a tolerance of ± 15% .

2 . If Thermal Memory is enabled, trip times may be shorter than indicated in this curve .

3 . Break point is at 0 .625 x In from I2t to flat .

4 . Ground slope: I2t, tolerance is: 0 .1s, 0 .2s: +0%/-40% 0 .3s, 0 .4s, 0 .5s: +0%/-30%

5 . With ZSI enabled, tripping times for 3-phase faults, no aux . power will be a maximum of 75ms for 60Hz and 80ms for 50Hz .

Page 16: Application Data AD013001EN Time Current Curves Series ......2 Application Data AD013001EN Effective August 2016 Time Current Curves Series NRX NF and RF Circuit Breakers PXR 20/25

16

Application Data AD013001ENEffective August 2016

Time Current Curves Series NRX NF and RF Circuit Breakers

PXR 20/25 Trip Units

EATON www.eaton.com

Figure 13. PXR 20/25 Instantaneous Response Curve Number: TC013011E August 2016.

Power Xpert Release - PXR 20 / PXR 25

Time Current Curves

Series NRX NF and RF Frame Circuit Breakers

Instantaneous Curves

Notes:

1 . The Instantaneous pickup settings have a ±10% tolerance .

Page 17: Application Data AD013001EN Time Current Curves Series ......2 Application Data AD013001EN Effective August 2016 Time Current Curves Series NRX NF and RF Circuit Breakers PXR 20/25

17

Application Data AD013001ENEffective August 2016

Time Current Curves Series NRX NF and RF Circuit Breakers PXR 20/25 Trip Units

EATON www.eaton.com

Figure 14. PXR 20/25 High Instantaneous Response Curve Number: TC013012E August 2016.

Power Xpert Release - PXR 20 / PXR 25

Time Current Curves

Series NRX NF and RF Frame Circuit Breakers

High Instantaneous Curves

Notes:

1 . The 90kA peak curve applies to IEC and UL 489 Selective NF (IZMX16) frame Series NRX breakers

2 . The 167 kA peak curve applies to RF (IZM40) frame Series NRX breakers with an (Icu) interrupt-ing rating of 100kA and above .

3 . The 138 kA peak curve applies to UL 489 Selective Series NRX RF frame series with an (Icu) interrupting rating of 85kA and above .

4 . The 18-6 7kA peak curves apply to UL 489 Switchboard Protective Series NRX breakers with the instantaneous asymmetrical peak value of 22 .5 times the frame current rating .

5 . The Instantaneous pickup settings have a ±10% tolerance .

6 . This protection is functional even when the Instantaneous is set to the OFF position .

7 . The PXR trip unit will light the Instantaneous LED for a High Instantaneous trip .

8 . The total High Instantaneous clearing times shown are conservative and consider the maxi-mum response times of the trip unit, the circuit breaker opening, and the interruption of the current under factors that contribute to worst case conditions, such as: maximum rated volt-ages, single phase interruption, and minimum power factor . Faster clearing times are possible depending on the specific system conditions .

Page 18: Application Data AD013001EN Time Current Curves Series ......2 Application Data AD013001EN Effective August 2016 Time Current Curves Series NRX NF and RF Circuit Breakers PXR 20/25

18

Application Data AD013001ENEffective August 2016

Time Current Curves Series NRX NF and RF Circuit Breakers

PXR 20/25 Trip Units

EATON www.eaton.com

Figure 15. PXR 20/25 Maintenance Mode Protection Response Curve Number: TC013013E August 2016.

Power Xpert Release - PXR 20 / PXR 25

Time Current Curves

Series NRX NF and RF Frame Circuit Breakers

Maintenance Mode Curves

Notes:

1 . Reduction Pickup settings have a ±20% tolerance .

2 . The trip unit will light the Instantaneous LED for a Maintenance Mode protective trip .

Page 19: Application Data AD013001EN Time Current Curves Series ......2 Application Data AD013001EN Effective August 2016 Time Current Curves Series NRX NF and RF Circuit Breakers PXR 20/25

19

Application Data AD013001ENEffective August 2016

Time Current Curves Series NRX NF and RF Circuit Breakers PXR 20/25 Trip Units

EATON www.eaton.com

Notes:

Page 20: Application Data AD013001EN Time Current Curves Series ......2 Application Data AD013001EN Effective August 2016 Time Current Curves Series NRX NF and RF Circuit Breakers PXR 20/25

Eaton Electrical Sector1000 Eaton BoulevardCleveland, OH 44122United States877-ETN-CARE (877-386-2273)Eaton.com

© 2016 Eaton All Rights ReservedPrinted in USAPublication No. AD013001EN / TBG001334August 2016

Eaton is a registered trademark.

All other trademarks are property of their respective owners.

Application Data AD013001ENEffective August 2016

Time Current Curves Series NRX NF and RF Circuit Breakers

PXR 20/25 Trip Units

At Eaton, we’re energized by the challenge of powering a world that demands more . With over 100 years’ experience in electrical power management, we have the expertise to see beyond today . From groundbreaking products to turnkey design and engineering services, critical industries around the globe count on Eaton .

We power businesses with reliable, efficient and safe electri-cal power management solutions . Combined with our personal service, support and bold thinking, we are answering tomorrow’s needs today . Follow the charge with Eaton . Visit eaton .com/elec-trical .