10
LIT-1900691 Release 11.0 2020-10-22 Application and Data Server (ADS) Lite-A System Catalog Page MS-ADSLA5U-0, MS-ADSLA5U-6 ADS-Lite-A Overview The ADS Lite-A manages the collection and presentation of large amounts of trend data, event messages, operator transactions, and system configuration data. As Site Director, the ADS-Lite-A provides secure communication to a maximum of four network of engines from the following models: the NAE45-Lite, SNE110L and NIE29/NIE39/NIE49. The ADS-Lite-A supports robust features and capabilities that continue to position the Metasys system as the leading building automation system in the industry, including: Fault detection: identifies and lists building system- related faults in order of severity to help operators quickly fix issues and avoid equipment issues, energy waste, and comfort complaints. Fault triage: is an add-on to fault detection that provides fault duration, occurrence information, and corrective action recommendations to improve fault prioritization that assists less experienced building operators with problem solving. Building Network tree allows for faster delivery of the Metasys User Interface (UI) by enabling its deployment prior to the spaces and equipment configuration process. It also provides a familiar navigation experience for Metasys operators who have previous experience using the All Items tree of the Site Management Portal.

Application and Data Server (ADS) Lite-A System Catalog Page

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Application and Data Server (ADS) Lite-A System Catalog Page

LIT-1900691 Release 11.02020-10-22

Application and Data Server (ADS)Lite-A System Catalog Page

MS-ADSLA5U-0, MS-ADSLA5U-6

ADS-Lite-A OverviewThe ADS Lite-A manages the collection and presentationof large amounts of trend data, event messages,operator transactions, and system configurationdata. As Site Director, the ADS-Lite-A provides securecommunication to a maximum of four network ofengines from the following models: the NAE45-Lite,SNE110L and NIE29/NIE39/NIE49.The ADS-Lite-A supports robust features and capabilitiesthat continue to position the Metasys system as theleading building automation system in the industry,including:• Fault detection: identifies and lists building system-

related faults in order of severity to help operatorsquickly fix issues and avoid equipment issues, energywaste, and comfort complaints.

• Fault triage: is an add-on to fault detection thatprovides fault duration, occurrence information, andcorrective action recommendations to improve faultprioritization that assists less experienced buildingoperators with problem solving.

• Building Network tree allows for faster deliveryof the Metasys User Interface (UI) by enabling itsdeployment prior to the spaces and equipmentconfiguration process. It also provides a familiarnavigation experience for Metasys operators whohave previous experience using the All Items tree ofthe Site Management Portal.

Page 2: Application and Data Server (ADS) Lite-A System Catalog Page

• Advanced Search and Reporting in the MetasysUI allows Metasys operators to find and reporton operational data and make bulk commands torestore order more quickly. The Advanced Searchand Reporting feature provides Metasys usersthe ability to quickly search Metasys objects byBuilding Network, equipment, equipment type, orspace.

• Custom Dashboards for the Metasys UserInterface. Custom dashboards enable Metasys UIdesigners to create dashboards that provide themost relevant and critical information to Metasysoperators for enhanced productivity and createsan experience that mimics users operationalstyles for ease of use.

• Graphics Custom Behaviors provide Metasys UIdesigners the flexibility to use custom symbolsthat are required for their individual building orcampus needs or their local standards.

• Trend widget updates allow users to identifypatterns including outliers, using an intuitivecandlestick chart that displays min, max, andaverages.

• Cyber Health Dashboard provides a Metasysadministrator with a centralized view of potentialsecurity-related issues or system issues which aredetectable by an ADS-LiteADS/ADXOAS, but whichmay not surface as part of general system alarms.

• User Management facilitates the creation andmanagement of users and their roles, category-based permissions, and privileges directly inMetasys UI Online, without the need to installsoftware on client machines.

• Historical data management, including an ODBC-compliant database package for storage of trenddata, event messages, operator transactions, andsystem configuration data.

• RESTful APIs: the Metasys API provides easyaccess for you to pull raw data from the serverinto your processing and analytic mechanisms,such as PowerBI® and Tableau®, and supportsboth historical data fetching and gatheringinformation about the site and all of its childelements. Additionally, the new MetasysMonitoring and Commanding API enablesreading, writing, and commanding of one ormore Metasys objects and properties to providea secure and cost-effective way to bi-directionallyintegrate with third party applications

Figure 1: ADS-Lite-A Site Management UI

Figure 2: Metasys UI

Note: In this document, the term enginerefers to NAE45-Lite, SNE110L, and NIEs, unlessotherwise noted.

Features and Benefits of the ADS-Lite-A with an SNE110LCommunication using commonly accepted ITstandards

Allows you to install a system on your existing ITinfrastructure within a building or enterprise anduse standard IT communication services over thecompany intranet, WAN, or public Internet withfirewall protection.

2 Application and Data Server (ADS) Lite-A System Catalog Page

Page 3: Application and Data Server (ADS) Lite-A System Catalog Page

Secure, encrypted communication

Protects the system from unauthorized users andcomputer hackers with the implementation ofthe Hypertext Transfer Protocol Secure (HTTPS)application protocol and Transport Layer Security(TLS 1.2) to encrypt communications between theADS-Lite-A, network engines, and clients.

Web-based user interface

Allows you to access system data from anysupported web browser device connected to thenetwork, including remote users connected by anInternet Service Provider (ISP).

UI support for five users

Allows up to five users to access the ADS-Lite-A UI atone time.

Support for up to four engines

Enables flexibility and scalability on your network.

Support for MS/TP Bus, BACnet Protocol, andThird-Party Communication

Allows you to leverage standard communicationformats on your network: MS/TP and BACnet/IPcommunication to third-party devices, and third-party communication with the SNE110L and NIE29/NIE39/NIE49.

Support for the Language Installation Program(LIP)

Installs language resources and makes the neededconfiguration changes so that the ADS-Lite-A systemsupports one or more locales.

ADS-Lite-A Ordering InformationTable 1: ADS-Lite-ACodeNumber Description

MS-ADSLA5U-0

ADS-Lite-A New project software: for upto five users, on new sites

MS-ADSLA5U-6

ADS-Lite-A Upgrade project software:for up to five users, on sites witha previous version of the Metasyssoftware

SNE110L Ordering InformationTable 2: SNE110LCodenumber Description

M4-SNE110L0-0

M4-SNE110L1-0

Supports one field bus deviceintegration with a maximum of 100devices on the trunk. This model isintended for use with Metasys ServerLite (ADS-Lite-A) software in selectregions of Australia, China, HongKong, India, Indonesia, Japan, Korea,Malaysia, New Zealand, Philippines,Singapore, Taiwan, Thailand, Vietnam,and select branches.

Note: This model does notsupport the N2 Bus or LonWorksnetwork interface, but doessupport up to 10 IP deviceintegrations.

3 Application and Data Server (ADS) Lite-A System Catalog Page

Page 4: Application and Data Server (ADS) Lite-A System Catalog Page

Table 3: Optional feature add-on licensesCode number Description

M4-APIMOCMD-0

License enablingthe Monitoring andCommanding API fornew site.

M4-FAULT-0

License enabling FaultDetection feature forone Metasys server(ADS, ADS-Lite, ADX, orOAS series). 11

M4-TRIAGE-0

License enabling FaultTriage feature for oneMetasys server (ADS,ADS-Lite, ADX, or OASseries).22

Note: M4-FAULT-0is also required as aprerequisite.

M4-ADFS-0

License enabling ActiveDirectory FederationServices (ADFS) featurefor one Metasys server(ADS, ADS-Lite, ADX orOAS series).

M4-FIPS-0

License enablingFederal InformationProcessing Standard140-2 (FIPS 140-2 Level1 compliance) forone Metasys server(ADS, ADS-Lite, ADX,or OAS series), or forone software networkengine (NAE85 or LCS85series).

1 The OAS must meet minimum requirements.2 The OAS must meet minimum requirements.

AccessoriesSee Table 4 for accessories available for theSNE110L.

Table 4: NAE45-Lite Accessories OrderingInformationProductCodeNumber

Description

AS-XFR100-1

Power transformer (Class 2, 24 VAC, 92VA maximum output), with enclosure

AS-XFR010-1

Power transformer (Class 2, 24 VAC, 92VA maximum output), no enclosure

4 Application and Data Server (ADS) Lite-A System Catalog Page

Page 5: Application and Data Server (ADS) Lite-A System Catalog Page

Application and Data Server-Litesystem requirementsTable 5: Application and Data Server-Lite systemrequirementsRecommendedComputerPlatform11

Intel i7 processor latest version with at least 6cores or better

2 x 500 GB hard disk (RAID 1) 22 with 40 GBfree space after installation of all prerequisitesoftware and before installation of ADS-Litesoftware. Configure RAID 1 (mirroring) withdisk write-caching turned on.

Note: Prerequisite software includesthe supported operating system,database software, .NET Framework,and any other software or service packsrequired for your ADS configuration.

Graphics adapter (1 GB RAM, ATI®Technologies or NVIDIA® Corporation, 64-bit compatible [for 64-bit operating systems],Small Form Factor [SFF] if required)

RequiredMinimumMemory 33

8 GB minimum, 16 GB recommendedFor VM hosts, allocate a minimum of 8 GB ofRAM

Table 5: Application and Data Server-Lite systemrequirements

Windows® 10 Pro and Windows 10 EnterpriseEditions versions 1903, 1909, and 2004 (64-bit). For all future Windows 10 updates afterversion 2004, we will evaluate and certify thatMetasys software can support the updatesbefore we provide guidance on support.Supports:

• SQL Server® 2019 Express (64-bit)Note: SQL Server 2019 may causethe configuration service cachethat builds stored procedures totime out. This causes the user'slog in to Metasys UI to fail. Toresolve this issue, set SQL Server2019 to run in 2018 compatibilitymode. For more information,refer to docs.microsoft.com

• SQL Server® 2017 Express with CU17(64-bit)

• SQL Server® 2016 Express with SP2CU10 (64-bit)

• SQL Server® 2014 Express with SP3 CU4(64-bit)

SupportedOperatingSystems andDatabaseSoftware 44

Windows® 8.1 Pro and Windows 8.1Enterprise Editions with Update (KB2919355)(64-bit)Supports:

• SQL Server® 2017 Express with CU17(64-bit)

• SQL Server® 2016 Express with SP2CU10 (64-bit)

• SQL Server® 2014 Express with SP3 CU4(64-bit)

SupportedVirtualEnvironments

Microsoft Hyper-V™VMware®

Supported UserInterfaces

Site Management Portal (SMP)Metasys UI

5 Application and Data Server (ADS) Lite-A System Catalog Page

Page 6: Application and Data Server (ADS) Lite-A System Catalog Page

Table 5: Application and Data Server-Lite systemrequirementsAdditionalSoftwareIncluded withthe ADS-LiteSoftwareDownload

Microsoft .NET Framework 4.7.2Launcher Software

OptionalHardware

Any network or local printer supported by thequalified Windows operating system

OptionalSoftware

Graphic Generation ToolCCT SoftwareSCT SoftwareMetasys Device ManagerMetasys Export Utility

1 Our computer platform and memory recommendationsare not meant to imply that older or slower machines arenot usable. Refer to the Network and IT Guidance TechnicalBulletin (LIT-12011279)1 for more information regardingcomputer/server recommendations.

2 For best performance, use Serial Attached SCSI (SAS) harddrives, not Small Computer System Interface (SCSI) harddrives.

3 It is recommended to use RAM that the computer supports.4 Refer to the Network and IT Guidance Technical Bulletin

(LIT-12011279) for specific Microsoft Windows operatingsystem settings that may be required for your Metasyssystem configuration.

SNE110L Technical Specifications

Table 6: SNE110L network engines

PowerRequirement

Dedicated nominal 24 VAC, Class 2 power supply (North America), SELV power supply(Europe), at 50/60 Hz (20 VAC minimum to 30 VAC maximum)

Alternate: Dedicated nominal 24 VDC, Class II power supply input; North America:ACC-PWRKIT-1A24; Europe: ACC-PWRKIT-1E24

PowerConsumption 38 W maximum

AmbientTemperatureConditions

Operating: 0°C to 50°C (32°F to 122°F)

Operating Survival: -30°C to 60°C (-22°F to 140°F)

Non-Operating: -40°C to 70°C (-40°F to 158°F)

Ambient HumidityConditions

Storage: 5% to 95% RH, 30°C (86°F) maximum dew point conditions

Operating: 10% to 90% RH, 30°C (86°F) maximum dew point conditions

Processor NXP i.MX6 DualLite processor, dual core Cortex-A9 processor at 1.0 GHz with 512 KBof L2 cache

Memory

16 GB flash nonvolatile memory for operating system, configuration data, andoperations data storage and backup

2 GB SDRAM for operations data dynamic memory

Operating System Wind River® Linux LTS 17 (LTS=long-term support)

6 Application and Data Server (ADS) Lite-A System Catalog Page

Page 7: Application and Data Server (ADS) Lite-A System Catalog Page

Table 6: SNE110L network engines

TransmissionSpeeds

Optically isolated, Serial Communication (FC Bus): 9600, 19,200, 38,400, or 76,800bps

Ethernet Communication: 1000, 100, or 10 Mbps

Network and SerialInterfaces

One Ethernet port; 1000/100/10 Mbps; 8-pin RJ45 connector

One FC port (RJ12 6-pin port; connects with 1.5 m [4.9 ft] RJ-12 field bus cable, and oneScrew terminal plug, 4-pin)

Three USB ports (one Micro-B port, and two USB A ports). All support USB 2.0 andOpen Host Controller Interface [Open HCI] specification; Micro-USB port currentlyinactive

SupportedIntegrations BACnet/IP, BACnet MS/TP, Modbus, M-Bus, KNX, and OPC UA.

Housing Black Polycarbonate and Acrylonitrile butadiene styrene (ABS) blend

Mounting On flat surface with screws on three mounting clips or a single 35 mm DIN rail

Dimensions(Height x Width xDepth)

190 mm x 125 mm x 45.5 mm (7.48 in. x 4.92 in. x 1.75 in.)

Weight 0.387 kg (0.852 lbs)

United States: UL Listed, File E107041, CCN PAZX, UL 916, Energy ManagementEquipment; FCC Compliant to CFR47, Part 15, Subpart B, Class A

Canada: UL Listed, File E107041, CCN PAZX7, CAN/CSA C22.2 No. 205, SignalEquipment; Industry Canada Compliant, ICES-003

Europe: CE Mark – Johnson Controls, Inc. declares that this product is in compliancewith the essential requirements and other relevant provisions of the EMC Directive.

Australia and New Zealand: RCM Mark, Australia/NZ Emissions Compliant

Compliance

BACnet International: BTL 135-2016 Listed B-BC/B-RTR/B-BBMD, Protocol Revision18.

NAE45-Lite SpecificationsTable 7: NAE45-Lite Specifications

Power Requirement

Dedicated nominal 24VAC, Class 2 Power Supply(North America), SafetyExtra-Low Voltage (SELV)power supply (Europe), at50/60 Hz (20 VAC minimumto 30 VAC maximum)

Table 7: NAE45-Lite SpecificationsPower Consumption 25 VA maximum

Ambient OperatingConditions

0 to 50°C (32 to 122°F);10 to 90% RH, 30°C (86°F)maximum dew point

Ambient StorageConditions

-40 to 70°C (-40 to 158°F);5 to 95% RH, 30°C (86°F)maximum dew point

7 Application and Data Server (ADS) Lite-A System Catalog Page

Page 8: Application and Data Server (ADS) Lite-A System Catalog Page

Table 7: NAE45-Lite Specifications

Data ProtectionBattery

Supports data protectionon power failure.

Rechargeable NiMHbattery: 3.6 VDC 500 mAh,with a typical life of 5 to 7years at 21°C (70°F)

Product Code Number: MS-BAT1020-0

Processor 192 MHz Renesas® SH47760 RISC processor

Memory

128 MB flash nonvolatilememory for operatingsystem, configurationdata, and operations datastorage and backup

128 MB SynchronousDynamic Random AccessMemory (DRAM) foroperations data dynamicmemory

Operating System

Metasys 9.0 or earlier:

Microsoft® Windows® CEembedded

Metasys 9.0.7 or later:

Linux® Buildroot 2017.08.2

Table 7: NAE45-Lite Specifications

Network and SerialInterfaces

One Ethernet port;10/100 Mbps; 8-pin RJ-45connector

One optically isolatedRS-485 port; 9600, 19.2k,38.4k, or 76.8k baud(depending on protocol);with a pluggable and keyed4-position terminal block

One RS-232-C serial portwith standard 9-pin sub-D connector that supportsstandard baud rates.

A second serial port, onmodels without an internalmodem, that supports anoptional, user-suppliedexternal modem.

One USB serial port withstandard USB connectorthat supports an optional,user-supplied externalmodem.

Housing

Plastic housing material:ABS + polycarbonateUL94-5VB

Protection: IP20 (IEC 60529)

MountingOn flat surface with screwson three mounting clips ora single 35 mm DIN rail

Dimensions

(Height x Width xDepth)

131 x 270 x 62 mm (5.2 x10.6 x 2.5 in.)

Minimum space formounting NAE45-Lite:

210 x 350 x 110 mm (8.3 x13.8 x 4.3 in.)

Shipping Weight 1.2 kg (2.7 lb)

8 Application and Data Server (ADS) Lite-A System Catalog Page

Page 9: Application and Data Server (ADS) Lite-A System Catalog Page

Table 7: NAE45-Lite SpecificationsUnited States: UL Listed,File E107041, CCN PAZX, UL916, Energy ManagementEquipment, FCC Compliantto CFR47, Part 15, SubpartB, Class A

Canada: UL Listed, FileE107041, CCN PAZX7,CAN/CSA C22.2 No. 205,Signal Equipment; IndustryCanada Compliant,ICES-003

Europe: CE Mark - JohnsonControls declares thatthe NAE45-Lite is incompliance with theessential requirements andother relevant provisions ofthe EMC Directive.

Compliance

Australia and NewZealand: RCM Mark,Australia/NZ EmissionsCompliant

The performance specifications are nominal andconform to acceptable industry standard. Forapplication at conditions beyond these specifications,consult the local Johnson Controls office. JohnsonControls shall not be liable for damages resulting frommisapplication or misuse of its products.

EuropeanSingle Point ofContact:

NA/SA SinglePoint ofContact:

APAC SinglePoint ofContact:

JOHNSONCONTROLS

WESTENDHOF 3

45143 ESSEN

GERMANY

JOHNSONCONTROLS

507 EMICHIGAN ST

MILWAUKEE WI53202

USA

JOHNSONCONTROLS

C/O CONTROLSPRODUCTMANAGEMENT

NO. 22 BLOCK DNEW DISTRICT

WUXI JIANGSUPROVINCE214142

CHINA

Product warrantyThis product is covered by a limited warranty, details of which can be found at www.johnsoncontrols.com/buildingswarranty.

Software termsUse of the software that is in (or constitutes) this product, or access to the cloud, or hosted servicesapplicable to this product, if any, is subject to applicable end-user license, open-source softwareinformation, and other terms set forth at www.johnsoncontrols.com/techterms. Your use of thisproduct constitutes an agreement to such terms.

PatentsPatents: https://jcipat.com

Contact informationContact your local branch office:www.johnsoncontrols.com/locationsContact Johnson Controls:www.johnsoncontrols.com/contact-us

9 Application and Data Server (ADS) Lite-A System Catalog Page

Page 10: Application and Data Server (ADS) Lite-A System Catalog Page

© 2020 Johnson Controls. All rights reserved. All specifications and other information shown werecurrent as of document revision and are subject to change without notice.www.johnsoncontrols.com