August 30, 2018 J.N.: 2693.00

Mr. Joshua Haskins 740 E. La Palma, LLC 2390 E. Orangewood Ave., Suite 510 Anaheim, CA 92806

Subject: Response to Geotechnical Review Comments, City of Anaheim OTH 2018-01084, Proposed Residential Development, 740 East La Palma Avenue, City of Anaheim California.

References: Review of Geotechnical Due-Diligence and Percolation Study Report on Behalf of City of Anaheim, Proposed Residential Development, 740 East La Palma Avenue, Anaheim, California, prepared by Leighton and Associates, Inc., dated August 14, 2018 (Leighton Project No. 11702.016)

Geotechnical Due-Diligence Investigation and Percolation Study, Proposed Residential Development, 740 East La Palma Avenue, Anaheim, California, prepared by Albus-Keefe & Associates, Inc., dated January 15, 2018 (J.N.: 2693.00)

Dear Mr. Haskins,

Albus-Keefe & Associates, Inc. is pleased to present to you our response to the referenced review document prepared by Leighton and Associates, Inc. dated August 14, 2018. A copy of the review comments is attached.

Comment #1

The consultant should provide seismic design parameters for use in the structural design in addition to what is presented in Section 4.1.

Response #1

Our referenced report dated January 15, 2018 was prepared to determine feasibility of future site development from a geotechnical perspective as part of the owner’s due-diligence assessment. Specific design parameters, including CBC seismic parameters, are not deemed necessary to address geotechnical feasibility of the proposed site development. If the project advances to development of construction documents, a comprehensive design-level geotechnical report should be prepared and specific recommendations provided at that time, including seismic design parameters. However, to address the reviewer’s comment, the following is presented on a preliminary basis.

Page 3: Appendix D Geotechnical Due-Diligence Investigation and

740 E. La Palma, LLC August 30, 2018 J.N.: 2693.00

ALBUS-KEEFE & ASSOCIATES, INC.

For design of the project in accordance with Chapter 16 of the 2016 CBC, the table below presents the seismic design factors. The values presented below may require revision depending on applicable CBC requirements at the time a design-level geotechnical report is prepared for the subject development.

CBC 2016 SEISMIC DESIGN PARAMETERS

Parameter Value Site Class D Mapped MCE Spectral Response Acceleration, short periods, SS 1.530 Mapped MCE Spectral Response Acceleration, at 1-sec. period, S1 0.590 Site Coefficient, Fa 1.0 Site Coefficient, Fv 1.5 Adjusted MCE Spectral Response Acceleration, short periods, SMS 1.530 Adjusted MCE Spectral Response Acceleration, at 1-sec. period, SM1 0.885 Design Spectral Response Acceleration, short periods, SDS 1.020 Design Spectral Response Acceleration, at 1-sec. period, SD1 0.590

MCE = Maximum Considered Earthquake

Closing

We appreciate this opportunity to be of service to you. If you have any questions regarding the contents of this report, please do not hesitate to call.

Sincerely,

ALBUS-KEEFE & ASSOCIATES, INC.

David E. Albus Principal Engineer GE 2455

Enclosures:

Review Letter by Leighton and Associates, Inc., dated August 14, 2018

Page 4: Appendix D Geotechnical Due-Diligence Investigation and
Page 5: Appendix D Geotechnical Due-Diligence Investigation and
Page 6: Appendix D Geotechnical Due-Diligence Investigation and
Page 7: Appendix D Geotechnical Due-Diligence Investigation and
Page 8: Appendix D Geotechnical Due-Diligence Investigation and

January 15, 2018 J.N.: 2693.00

Mr. Joshua Haskins 740 E. La Palma, LLC 2390 E. Orangewood Ave., Suite 510 Anaheim, CA 92806 Subject: Geotechnical Due-Diligence Investigation and Percolation Study, Proposed

Residential Development, 740 East La Palma Avenue, Anaheim, California. Dear Mr. Haskins, Albus-Keefe & Associates, Inc. is pleased to present to you our geotechnical due-diligence report for the proposed residential development at the subject site. This report presents the results of our review of historical photographs, subsurface exploration, laboratory testing, and engineering analyses. Conclusions relevant to the feasibility of the proposed site development are also presented in this report based on the findings of our work. We appreciate this opportunity to be of service to you. If you have any questions regarding the contents of this report, please do not hesitate to call. Sincerely, ALBUS-KEEFE & ASSOCIATES, INC. Patrick M. Keefe Principal Engineering Geologist CEG 2022

Page 9: Appendix D Geotechnical Due-Diligence Investigation and

740 E. La Palma, LLC January 15, 2018 J.N.: 2693.00

Page i TABLE OF CONTENTS

REPORT

ALBUS-KEEFE & ASSOCIATES, INC.

1.0 INTRODUCTION..................................................................................................................... 1 1.1 PURPOSE AND SCOPE......................................................................................................... 1 1.2 SITE LOCATION AND DESCRIPTION ............................................................................... 1 1.3 PROPOSED DEVELOPMENT .............................................................................................. 3

2.0 INVESTIGATION .................................................................................................................... 3 2.1 RESEARCH ............................................................................................................................ 3 2.2 SUBSURFACE EXPLORATION .......................................................................................... 3 2.3 LABORATORY TESTING .................................................................................................... 4

3.0 SUBSURFACE CONDITIONS ............................................................................................... 4 3.1 SOIL CONDITIONS ............................................................................................................... 4 3.2 GROUNDWATER .................................................................................................................. 4 3.3 FAULTING ............................................................................................................................. 5

4.0 ANALYSES ............................................................................................................................... 5 4.1 SEISMICITY ........................................................................................................................... 5 4.2 SETTLEMENT ....................................................................................................................... 5

5.0 CONCLUSIONS ....................................................................................................................... 6 5.1 FEASIBILITY OF PROPOSED DEVELOPMENT ............................................................... 6 5.2 GEOLOGIC HAZARDS ......................................................................................................... 6

5.2.1 Ground Rupture ................................................................................................................ 6 5.2.2 Ground Shaking ................................................................................................................ 6 5.2.3 Landsliding ....................................................................................................................... 6 5.2.4 Liquefaction ...................................................................................................................... 6

5.3 STATIC SETTLEMENT ........................................................................................................ 7 5.4 EXCAVATION AND MATERIAL CHARACTERISTICS .................................................. 7 5.5 SHRINGKAGE AND BULKAGE ......................................................................................... 8 5.6 SOIL EXPANSION ................................................................................................................. 8 5.7 FOUNDATIONS ..................................................................................................................... 8 5.8 CONCRETE MIX DESIGN .................................................................................................... 8 5.9 CORROSION POTENTIAL ................................................................................................... 9 5.10 PAVEMENT SECTIONS .................................................................................................... 9 5.11 PERCOLATION CHARACTERISTICS ............................................................................. 9

6.0 LIMITATIONS ......................................................................................................................... 9 REFERENCES .................................................................................................................................. 11

FIGURES AND PLATES Figure 1 - Site Location Map Plate 1 - Geotechnical Map

APPENDICES APPENDIX A - Exploration Logs Plates A-1 through A-7 - Boring Logs APPENDIX B - Laboratory Test Program Table B - Summary of Laboratory Test Results

Plate B-1 – Grain Size Distribution Plot Plate B-2 - Direct Shear Plot

Page 10: Appendix D Geotechnical Due-Diligence Investigation and

740 E. La Palma, LLC January 15, 2018 J.N.: 2693.00

Page 1

ALBUS-KEEFE & ASSOCIATES, INC.

1.0 INTRODUCTION

1.1 PURPOSE AND SCOPE The purpose of our work was to evaluate the feasibility of proposed site development in order to assist you in your land acquisition evaluation and due-diligence review. The scope of our work for this investigation was focused primarily on the geotechnical issues that we expect could have significant fiscal impacts on future site development. While this report is comprehensive for the intended purpose, it is not intended for final design purposes. As such, additional geotechnical studies may be warranted based on our review of future rough grading plans and foundation plans. The scope of our geotechnical due-diligence work included the following:

• Review of published geologic and seismic data for the site and surrounding area

• Review of historical photos for the surrounding area

• Exploratory drilling and sampling

• Engineering analyses of data from the exploration and laboratory testing • Evaluation of site seismicity, liquefaction potential, and settlement potential • Preparation of this report

1.2 SITE LOCATION AND DESCRIPTION The site is located at 740 E. La Palma Avenue in the city of Anaheim, California. The site is bordered by E. La Palma Avenue and an adjoining parcel of the Anaheim Fullerton Storage facility to the north, an alleyway followed by single-family residences to the west, an unimproved lot used for storage to the south, and a railroad easement to the east. The location of the site and its relationship to the surrounding areas is shown on the Site Location Map, Figure 1. The property is about 850 feet long by 100 feet wide and comprises approximately 1.7 acres of land. The site is asphalt-paved and is currently utilized by Anaheim Fullerton Storage for storage of automobiles, recreational vehicles (RV’s), and boats. On-site improvements include various underground utilities, iron-clad fencing, chain-link fencing, and/or masonry block walls along the east, west, and south property lines. The subject site is relatively level with an elevation of approximately 167 feet above mean sea level (MSL). Drainage at the site appears to be directed as sheet flow to the north and west towards the adjacent alleyway and streets. Vegetation on site is sparse and primarily consists of wall-shrubs and vines around the perimeter of the site.

Page 11: Appendix D Geotechnical Due-Diligence Investigation and

740 E. La Palma, LLC January 15, 2018 J.N.: 2693.00

Page 2

ALBUS-KEEFE & ASSOCIATES, INC.

© 2017 Google

N

SITE LOCATION MAP 740 E La Palma, LLC

Proposed Residential Development 740 East La Palma Avenue

Anaheim, California

NOT TO SCALE

FIGURE 1

SITE

Page 12: Appendix D Geotechnical Due-Diligence Investigation and

740 E. La Palma, LLC January 15, 2018 J.N.: 2693.00

Page 3

ALBUS-KEEFE & ASSOCIATES, INC.

1.3 PROPOSED DEVELOPMENT Based on our review of the referenced conceptual site plan, the proposed site development will consist of 3 multi-family residential buildings including 31 townhome units. We understand that all proposed structures will be constructed on grade with no subterranean elements. Associated interior driveways, perimeter/retaining walls, storm water infiltration system, and underground utilities are also planned. No grading or structural plans were available in preparation of this report. However, we anticipate that minor rough grading of the site will be required to achieve future surface configuration and we expect the proposed residential dwellings will be 3-story; wood-framed structures with concrete slabs on grade yielding relatively light foundation loads.

2.0 INVESTIGATION

2.1 RESEARCH We have reviewed the referenced geologic publications and maps for the site and vicinity. Data from these sources were utilized to develop some of our findings and conclusions presented in this report. We have also reviewed the referenced aerial photographs from our in-house library. The earliest available aerial photograph taken circa 1952 shows that the site was included within a wider railroad easement that included rail tracks running through the subject site. The site appears to have been relatively unchanged from 1952 to the early 1990’s. Sometime in the early 1990’s the rail road tracks within the property were abandoned and/or removed. Sometime between 1997 and 1999, the site was developed into the asphalt-paved lot. By 2003 the site was utilized for RV and automobile storage.

2.2 SUBSURFACE EXPLORATION Subsurface exploration for this investigation was conducted at the site on December 21, 2017, and consisted of drilling three (3) exploratory borings and two (2) percolation test wells. The borings were drilled to maximum depths of approximately 51.5 feet below the existing ground surface utilizing a truck-mounted, hollow-stem-auger drill rig. A representative of Albus-Keefe & Associates, Inc. logged the exploratory excavations. Visual and tactile identifications were made of the materials encountered, and their descriptions are presented on the Exploration Logs in Appendix A. The approximate locations of the exploratory excavations completed by this firm are shown on the enclosed Geotechnical Map, Plate 1. Bulk, relatively undisturbed and Standard Penetration Test (SPT) samples were obtained at selected depths within the exploratory borings for subsequent laboratory testing. Relatively undisturbed samples were obtained using a 3-inch O.D., 2.5-inch I.D., California split-spoon soil sampler lined with brass rings. SPT samples were obtained from the borings using a standard, unlined SPT soil sampler. During each sampling interval, the sampler was driven 18 inches with successive drops of a 140-pound automatic hammer falling 30 inches. The number of blows required to advance the

Page 13: Appendix D Geotechnical Due-Diligence Investigation and

740 E. La Palma, LLC January 15, 2018 J.N.: 2693.00

Page 4

ALBUS-KEEFE & ASSOCIATES, INC.

sampler was recorded for each six inches of advancement. The total blow count for the lower 12 inches of advancement per soil sample is recorded on the exploration log. Samples were placed in sealed containers or plastic bags and transported to our laboratory for analyses. All borings were backfilled with auger cuttings and capped with cold-patch asphaltic-concrete upon completion of sampling and percolation testing. Upon completion of drilling, two percolation tests were conducted at boring P-1 drilled within the vicinity of boring B-1 in the middle of the site and at boring B-3 toward the north side of the site. The tests were conducted using 2-inch diameter casings installed in the boreholes after completion of drilling and sampling. Details of percolation testing are not included in this report, however, a brief discussion of our test results and recommended BMP systems are summarized in Section 5.11.

2.3 LABORATORY TESTING Selected samples of representative earth materials from the borings were tested in our laboratory. Tests consisted of in-situ moisture and dry density, maximum dry density and optimum moisture content, expansion index, soluble sulfate content, direct shear strength, corrosivity (pH, minimum resistivity, chloride content), and grain size analysis. Descriptions of laboratory testing and a summary of the test results are presented in Appendix B and on the exploration log in Appendix A.

3.0 SUBSURFACE CONDITIONS

3.1 SOIL CONDITIONS Earth materials encountered at the site consist of native alluvial deposits mantled by artificial fills. The artificial fill materials are generally comprised of brown and dark brown clayey sand, silty sand and sandy clay. These materials were typically damp to moist and loose to medium dense. The thickness of the artificial fill encountered ranged from 3.0 to 5.5 feet below the existing ground surface. Artificial fills of greater thickness may also locally be present beneath the site. The native alluvial deposits are predominately comprised of brown and light gray to gray, silty sand, sand with silt, and sand that are dry to moist and medium dense to very dense. A brown, moist, very stiff clay layer was also encountered in boring B-1 at approximately 51.0 feet below the existing ground surface. A more detailed description of the interpreted soil profile at each of the boring locations, based upon the borehole cuttings and soil samples, are presented in Appendix A. The stratigraphic descriptions in the logs represent the predominant materials encountered and relatively thin, often discontinuous layers of different material may occur within the major divisions.

3.2 GROUNDWATER Groundwater was not encountered during this firm’s subsurface exploration to the maximum depth explored, approximately 51.5 feet below the existing ground surface. A review of the CDMG Seismic Hazard Zone Report 003 indicates that historical high groundwater levels for the general site

Page 14: Appendix D Geotechnical Due-Diligence Investigation and

740 E. La Palma, LLC January 15, 2018 J.N.: 2693.00

Page 5

ALBUS-KEEFE & ASSOCIATES, INC.

area are greater than 50 feet below the existing ground surface. Research of groundwater data in the vicinity of the site indicates groundwater levels in excess of 80 feet below the existing ground surface.

3.3 FAULTING Geologic literature and field exploration do not indicate the presence of active faulting within the site. The site does not lie within an "Earthquake Fault Zone" as defined by the State of California in the Alquist-Priolo Earthquake Fault Zoning Act. Table 3.1 presents a summary of all the known seismically active faults within 10 miles of the site based on the 2008 National Seismic Hazards Maps.

TABLE 3.1 Summary of Faults

Name Distance (miles)

Slip Rate

(mm/yr.)

Preferred Dip

(degrees)

Slip Sense

Rupture Top (km)

Fault Length (km)

Puente Hills (Coyote Hills) 1.96 0.7 26 thrust 2.8 17 Elsinore; W+GI 6.59 n/a 81 strike slip 0 83 Elsinore; W+GI+T+J+CM 6.59 n/a 84 strike slip 0 241 Elsinore; W 6.59 2.5 75 strike slip 0 46 Elsinore; W+GI+T 6.59 n/a 84 strike slip 0 124 Elsinore; W+GI+T+J 6.59 n/a 84 strike slip 0 199 Puente Hills (Santa Fe Springs) 8.65 0.7 29 thrust 2.8 11

4.0 ANALYSES

4.1 SEISMICITY We have performed probabilistic seismic analyses utilizing the U.S. Seismic Design Maps web application by the U.S. Geological Survey (USGS). From our analyses, we obtain a PGA of 0.579 in accordance with Figure 22-7 of ASCE 7-10. The FPGA factor for site class D is 1.0. Therefore, the PGAM = 1.0 x 0.579 = 0.58g. The mean event associated with a probability of exceedance equal to 2% over 50 years has a moment magnitude of 6.64 and the mean distance to the seismic source is 8.3 miles.

4.2 SETTLEMENT Based on the anticipated relatively light foundation loads and provided the upper 4 to 6 feet (which includes all existing artificial fill and the weathered/disturbed near-surface alluvium) of existing soils are removed and replaced as engineered compacted fill, the total and differential static settlements

Page 15: Appendix D Geotechnical Due-Diligence Investigation and

740 E. La Palma, LLC January 15, 2018 J.N.: 2693.00

Page 6

ALBUS-KEEFE & ASSOCIATES, INC.

are not anticipated to exceed 1 inch and ½-inch over 30 feet, respectively, for the proposed residential structures.

5.0 CONCLUSIONS

5.1 FEASIBILITY OF PROPOSED DEVELOPMENT From a geotechnical point of view, the proposed site development is considered feasible provided appropriate geotechnical recommendations are incorporated into the design and construction of the project. Key issues that could have significant fiscal impacts on the geotechnical aspects of the proposed site development are discussed in the following sections of this report.

5.2 GEOLOGIC HAZARDS

5.2.1 Ground Rupture No known active faults are known to project through the site nor does the site lie within the boundaries of an “Earthquake Fault Zone” as defined by the State of California in the Alquist-Priolo Earthquake Fault Zoning Act. Therefore, the potential for ground rupture due to an earthquake beneath the site is considered low. The nearest zoned fault is the Puente Hills (Coyote Hills) fault located approximately 1.96 miles to the north.

5.2.2 Ground Shaking The site is situated in a seismically active area that has historically been affected by generally moderate to occasionally high levels of ground motion. The site lies in relative close proximity to several seismically active faults; therefore, during the life of the proposed structures, the property will probably experience similar moderate to occasionally high ground shaking from these fault zones, as well as some background shaking from other seismically active areas of the Southern California region. Potential ground accelerations have been estimated for the site and are presented in Section 4.1 of this report. Design and construction in accordance with the current California Building Code (C.B.C.) requirements is anticipated to adequately address potential ground shaking. 5.2.3 Landsliding Geologic hazards associated with landsliding are not anticipated at the site. Furthermore, the site is not located within an area identified by the California Geologic Survey (CGS) as having potential for seismic slope instability.

5.2.4 Liquefaction Engineering research of soil liquefaction potential (Youd, et al., 2001) indicates that generally three basic factors must exist concurrently in order for liquefaction to occur. These factors include:

• A source of ground shaking, such as an earthquake, capable of generating soil mass distortions.

• A relatively loose silty and/or sandy soil.

Page 16: Appendix D Geotechnical Due-Diligence Investigation and

740 E. La Palma, LLC January 15, 2018 J.N.: 2693.00

Page 7

ALBUS-KEEFE & ASSOCIATES, INC.

• A relative shallow groundwater table (within approximately 50 feet below ground surface) or completely saturated soil conditions that will allow positive pore pressure generation.

The liquefaction susceptibility of the onsite subsurface soils was evaluated by analyzing the potential concurrent occurrence of the above-mentioned three basic factors. The liquefaction evaluation for this site was completed under the guidance of Special Publication 117A: Guidelines for Evaluating and Mitigating Seismic Hazards in California (CDMG, 2008). Groundwater was not encountered during this firm’s subsurface exploration. Moreover, historical high groundwater has been documented at a depth greater than 50 feet below the site. In addition, the site is not located within a mapped liquefaction hazard zone by the California Geologic Survey and Anaheim Safety Element. Therefore, the potential for liquefaction at the site is not considered as a seismic hazard.

5.3 STATIC SETTLEMENT Provided all undocumented artificial fill and weathered alluvium is removed (generally the upper 4 to 6 feet) and replaced as engineered compacted fill and based on the anticipated relatively light foundation loads, total and differential static settlements are not anticipated to exceed 1 inch and ½-inch over 30 feet, respectively, for the proposed residential structures.

5.4 EXCAVATION AND MATERIAL CHARACTERISTICS In general, all existing artificial fills and the upper weathered/disturbed near-surface alluvium are considered unsuitable in their existing condition to support proposed structural fills and site improvements. Based on our subsurface exploration, we anticipate these materials to range from 4 to 6 feet in thickness across the site. These materials should be removed from below future building sites, retaining walls, screen walls, pavement, and any other “structural” areas, and replaced as engineered compacted fill. The actual depth of removal should be determined by the geotechnical consultant during grading. Removals should extend laterally beyond the limits of the proposed structure no less than 5 feet or distance equal to the depth of removal (i.e. 1:1 projection) if the removals are greater than 5 feet. Off-site improvements exist near and along the property lines. The presence of the existing offsite improvements will limit removals of unsuitable materials adjacent the property lines. As such, future grading along the margins of the site will need to be performed in such a manner as to not adversely impact adjacent existing improvements. Where removals for future residential improvements are limited by existing improvements or property lines, special grading techniques such as slot cutting, shoring or other acceptable design criteria may be required. Under such conditions, specific recommendations should be provided by this firm during review of final grading plan. Construction of perimeter site walls will likely require deepened footings or caissons and grade beams where removals are restricted by property boundaries. Following removals, the exposed grade should first be scarified to a depth of 6 inches; moisture conditioned to at least 110 percent of the optimum moisture content, and then compacted to at least 90 percent of the laboratory determined maximum dry density.

Page 17: Appendix D Geotechnical Due-Diligence Investigation and

740 E. La Palma, LLC January 15, 2018 J.N.: 2693.00

Page 8

ALBUS-KEEFE & ASSOCIATES, INC.

Temporary construction slopes and trench excavations can likely be cut vertically up to a height of 4 feet within the onsite materials provided that no surcharging of the excavations is present. Temporary excavations greater than 4 feet in height but no greater than 10 feet will likely need to be laid back to 1.5:1 (H:V) or flatter. Site materials may be prone to sloughing and possible caving if allowed to dry. Demolition of the existing site improvements will generate a considerable amount of asphaltic concrete debris. Significant portions of concrete and asphaltic concrete debris can likely be reduced in size to less than 4 inches and incorporated within fill soils during earthwork operations. Onsite disposal systems, clarifiers and other underground improvements may be present on site. If encountered during future rough grading, these improvements will require proper abandonment or removal. Subsurface soils are anticipated to be relatively easy to excavate with conventional heavy earthmoving equipment.

5.5 SHRINGKAGE AND BULKAGE Volumetric changes in earth quantities will occur when excavated onsite soil materials are replaced as properly compacted fill. We estimate the existing upper 4 to 6 feet of earth materials will shrink 5 to 10 percent. Subsidence of removal bottoms is considered to be negligible. The estimates of shrinkage and bulkage are intended as an aid for project engineers in determining earthwork quantities. However, these estimates should be used with some caution since they are not absolute values. Contingencies should be made for balancing earthwork quantities based on actual swelling and bulkage that occurs during the grading process.

5.6 SOIL EXPANSION Based on our laboratory test results and the USCS visual manual classification, the near-surface soils within the site are generally anticipated to possess a Low expansion potential. Additional testing for soil expansion may be required subsequent to rough grading and prior to construction of foundations and other concrete work to confirm these conditions.

5.7 FOUNDATIONS Conventional shallow spread and continuous footings may be utilized to support the proposed residential buildings and wall structures at the site. Considering the Low expansion potential, the foundations for the proposed structures and other site improvements, such as retaining walls, screen walls, and flatwork, will likely require nominal reinforcement and depths.

5.8 CONCRETE MIX DESIGN Laboratory testing of onsite soil indicates Negligible soluble sulfate content. Concrete designed to follow the procedures provided in ACI 318, Section 4.3, Table 4.3.1 for negligible sulfate exposure are anticipated to be adequate for mitigation of sulfate attack on concrete. Upon completion of

Page 18: Appendix D Geotechnical Due-Diligence Investigation and

740 E. La Palma, LLC January 15, 2018 J.N.: 2693.00

Page 9

ALBUS-KEEFE & ASSOCIATES, INC.

rough grading, an evaluation of as-graded conditions and further laboratory testing will be required for the site to confirm or modify the conclusions provided in this section.

5.9 CORROSION POTENTIAL Laboratory testing of onsite soil indicates indicate a minimum resistivity of approximately 1,100 ohm-cm, pH of 7.9, and a soluble chloride content of 18 ppm. Based on laboratory test results, site soils are Corrosive to metals. Structures fabricated from metals should have appropriate corrosion protection if they will be in direct contact with site soils. Under such conditions, a corrosion specialist should provide specific recommendations.

5.10 PAVEMENT SECTIONS Existing near-surface soils are anticipated to have a moderate R-value. Based on the assumed R-value of 10 and a traffic index of 5.5, a preliminary pavement structural section of 3 inches asphaltic concrete over 12 inches of aggregate base may be used for planning and estimating purpose. R-value testing will be required subsequent to rough grading and prior to construction of interior driveways to confirm these conditions.

5.11 PERCOLATION CHARACTERISTICS Most of the site soils include coarse-grained soil starting at about 6 feet below the ground surface and extending at to at least 50 feet below the ground surface. Therefore, shallow infiltration chamber systems and/or deeper dry wells systems are considered feasible options to satisfy infiltration requirements for WQMP purposes. Specific design criteria can be provided upon review of future grading plans.

6.0 LIMITATIONS

This report is based on the proposed development and geotechnical data as described herein. The materials described herein and in other literature are believed representative of the total project area, and the conclusions contained in this report are presented on that basis. However, soil materials can vary in characteristics between points of exploration, both laterally and vertically, and those variations could affect the conclusions and recommendations contained herein. As such, observation and testing by a geotechnical consultant prior to and during the grading and construction phases of the project are essential to confirming the basis of this report. This report summarizes several geotechnical topics that should be beneficial for project planning and budgetary evaluations. The information presented herein is intended only for a preliminary feasibility evaluation and is not intended to satisfy the requirements of a site specific and detailed geotechnical investigation required for further planning and permitting. This report has been prepared consistent with that level of care being provided by other professionals providing similar services at the same locale and time period. The contents of this report are professional opinions and as such, are not to be considered a guaranty or warranty.

Page 19: Appendix D Geotechnical Due-Diligence Investigation and

740 E. La Palma, LLC January 15, 2018 J.N.: 2693.00

Page 10

ALBUS-KEEFE & ASSOCIATES, INC.

This report should be reviewed and updated after a period of one year or if the site ownership or project concept changes from that described herein.

This report has been prepared for the exclusive use of 740 E. La Palma, LLC to assist the project consultants in determining the feasibility of the proposed development. This report has not been prepared for use by parties or projects other than those named or described herein. This report may not contain sufficient information for other parties or other purposes.

Respectfully submitted,

ALBUS-KEEFE & ASSOCIATES, INC

Mark Principe David E. AlbusStaff Engineer Principal Engineer

GE 2455

Page 20: Appendix D Geotechnical Due-Diligence Investigation and

740 E. La Palma, LLC January 15, 2018 J.N.: 2693.00

Page 11

ALBUS-KEEFE & ASSOCIATES, INC.

REFERENCES Publications

California Department of Conservation, Division of Mines and Geology, Seismic Hazard Report 03, “Seismic Hazard Zone Report for the Anaheim and Newport Beach 7.5-Minute Quadrangles, Orange County, California”, 1997.

California Department of Conservation, Division of Mines and Geology, Special Publication 117A “Guidelines for Evaluating and Mitigating Seismic Hazards in California”, 2008.

City of Anaheim, “General Plan, Safety Element”, p. S-21-29, May, 2004.

Southern California Earthquake Center (SCEC), University of Southern California, “Recommended Procedures for Implementation of DMG Special Publication 117 Guidelines for Analyzing and Mitigating Liquefaction Hazards in California,” March, 1999.

Youd, T.L., Idriss, I.M., Andrus, R.D., Arango, I., Castro, G., Christian, J., Dobry, R., Finn, W.D.L., Harder, L.F., Hynes, M.E., Ishihara, K., Koester, J.P., Liao, S.S.C., Marcuson, W.F., Martin, G.R., Mitchell, J.K., Moriwaki, Y., Power, M.S., Robertson, P.K., Seed, R.B., and Stokoe, K.H., “Liquefaction Resistance of Soils: Summary Report from the 1996 NCEER and 1998 NCEER/NSF Workshops on Evaluation of Liquefaction Resistance of Soils”, Journal of Geotechnical and Geoenvironmental Engineering, October, 2001.

Plans

D33 Design & Planning Inc., Conceptual Site Plan, La Palma Townhomes, Anaheim, California, dated August 24, 2017 (Project No. 20170064).

Aerial Photographs

Photo Source Date Flown Flight No. Photo No. Continental Aerial Photo, Inc. 05-30-53 AXK-6K 20 Continental Aerial Photo, Inc. 05-01-67 3 209 Continental Aerial Photo, Inc. 01-13-75 157-6 12 Continental Aerial Photo, Inc. 06-09-93 C93-14 133 Continental Aerial Photo, Inc. 10-16-97 C118-34 105 Continental Aerial Photo, Inc. 02-24-99 C134-34 22 GoogleEarth 04-03

Page 21: Appendix D Geotechnical Due-Diligence Investigation and

P-1

B-1

B-2

B-3/P-2

E. N

OR

TH

S

TR

EE

T

N. PAULINE ST.

PROJECT

LIMIT

N. MAVIS ST.

E. N

OR

TH

S

TR

EE

T

E. W

ILH

ELM

IN

A S

TR

EE

T

E. W

ILH

ELM

IN

A S

TR

EE

T

E

. L

A

P

A

L

M

A

A

V

E

.

RAILROAD EASEMENT

ALBUS-KEEFE & ASSOCIATES, INC.GEOTECHNICAL CONSULTANTS

GEOTECHNICAL MAP

Job No.:

Date: Plate: 1

© Google 2018

EXPLANATION

(Locations Approximate)

- Exploratory Boring

B-3

- Percolation Test Boring

P-1

ALBUS-KEEFE & ASSOCIATES, INC.GEOTECHNICAL CONSULTANTS

GEOTECHNICAL MAP

2693.00Job No.:

Date: Plate: 101/15/18

B-3/P-2

- Exploratory & Percolation Test Boring

0 50 100 200

APPROX. SCALE : 1" = 100'

Page 22: Appendix D Geotechnical Due-Diligence Investigation and

ALBUS-KEEFE & ASSOCIATES, INC.

APPENDIX A

EXPLORATION LOGS

Page 23: Appendix D Geotechnical Due-Diligence Investigation and

Project:

Address:

Job Number:

Drill Method:

Client:

Driving Weight:

Location:

Elevation:

Date:

Logged By:

Depth

(feet)

Lith-

ology

Blows

Per

Foot

Moisture

Content

(%)

Dry

Density

(pcf)

Other

Lab

Tests

Laboratory TestsSamples

Material Description

E X P L O R A T I O N L O G

Wate

r

Core

Bu

lk

5

10

15

20

EXPLANATION

Solid lines separate geologic units and/or material types.

Dashed lines indicate unknown depth of geologic unit change or material type change.

Solid black rectangle in Core column represents California Split Spoon sampler (2.5in ID, 3in OD).

Double triangle in core column represents SPT sampler.

Solid black rectangle in Bulk column respresents large bag sample.

Other Laboratory Tests:

Max = Maximum Dry Density/Optimum Moisture Content

EI = Expansion Index

SO4 = Soluble Sulfate Content

DSR = Direct Shear, Remolded

DS = Direct Shear, Undisturbed

SA = Sieve Analysis (1" through #200 sieve)

Hydro = Particle Size Analysis (SA with Hydrometer)

200 = Percent Passing #200 Sieve

Consol = Consolidation

SE = Sand Equivalent

Rval = R-Value

ATT = Atterberg Limits

Albus-Keefe & Associates, Inc. Plate A-1

Page 24: Appendix D Geotechnical Due-Diligence Investigation and

Project:

Address:

Job Number:

Drill Method:

Client:

Driving Weight:

Location:

Elevation:

Date:

Logged By:

Depth

(feet)

Lith-

ology

Blows

Per

Foot

Moisture

Content

(%)

Dry

Density

(pcf)

Other

Lab

Tests

Laboratory TestsSamples

Material Description

E X P L O R A T I O N L O G

751-775 E La Palma Ave, Anaheim, CA 92801

2693.00 12/21/2017

RMHollow-Stem Auger

740 E. La Palma, LLC

B-1

166.5

Wate

r

Core

Bu

lk

140 lbs / 30 in

5

10

15

20

Asphalt Concrete (AC): 4 inches

Crushed Aggregate Base (CAB): 2 inches

ARTIFICIAL FILL (Af)Clayey Sand/Sandy Clay (SC/CL): Brown, damp to moist, medium dense, fine grained sand, trace gravel

@ 4 ft, loose, intermixed silty sand

ALLUVIUM (Qal)Sand with Silt (SP-SM): Gray, dry, medium dense, fine to coarse grained sand

Sand (SP): Light gray, dry to damp, medium dense, fine to medium grained sand

@ 15 ft, damp

14 N.R.

18

16

19

12

28

16

11.1

1.9

107.7

113.7

Dist.

Max EI

SO4 DS pH Resist

Ch

SA Hydro

Albus-Keefe & Associates, Inc. Plate A-2

Page 25: Appendix D Geotechnical Due-Diligence Investigation and

Project:

Address:

Job Number:

Drill Method:

Client:

Driving Weight:

Location:

Elevation:

Date:

Logged By:

Depth

(feet)

Lith-

ology

Blows

Per

Foot

Moisture

Content

(%)

Dry

Density

(pcf)

Other

Lab

Tests

Laboratory TestsSamples

Material Description

E X P L O R A T I O N L O G

751-775 E La Palma Ave, Anaheim, CA 92801

2693.00 12/21/2017

RMHollow-Stem Auger

740 E. La Palma, LLC

B-1

166.5

Wate

r

Core

Bu

lk

140 lbs / 30 in

30

35

40

45

@ 25 ft, dense

Sand with Silt (SP-SM): Light brown, damp to moist, dense, fine grained sand

Sand (SP): Light gray, damp, dense, fine to medium grained sand

@ 45 ft, very dense

30

28

21

27

33

Albus-Keefe & Associates, Inc. Plate A-3

Page 26: Appendix D Geotechnical Due-Diligence Investigation and

Project:

Address:

Job Number:

Drill Method:

Client:

Driving Weight:

Location:

Elevation:

Date:

Logged By:

Depth

(feet)

Lith-

ology

Blows

Per

Foot

Moisture

Content

(%)

Dry

Density

(pcf)

Other

Lab

Tests

Laboratory TestsSamples

Material Description

E X P L O R A T I O N L O G

751-775 E La Palma Ave, Anaheim, CA 92801

2693.00 12/21/2017

RMHollow-Stem Auger

740 E. La Palma, LLC

B-1

166.5

Wate

r

Core

Bu

lk

140 lbs / 30 in

Clay (CL): Brown, moist, very stiff, laminated, with silt

End of boring at 51.5 feet. No groundwater encountered. Installed percolation test well (P-1) offset approx. 50 feet south ofboring.Backfilled with soil cuttings and capped with asphalt cold patch.

10

Albus-Keefe & Associates, Inc. Plate A-4

Page 27: Appendix D Geotechnical Due-Diligence Investigation and

Project:

Address:

Job Number:

Drill Method:

Client:

Driving Weight:

Location:

Elevation:

Date:

Logged By:

Depth

(feet)

Lith-

ology

Blows

Per

Foot

Moisture

Content

(%)

Dry

Density

(pcf)

Other

Lab

Tests

Laboratory TestsSamples

Material Description

E X P L O R A T I O N L O G

751-775 E La Palma Ave, Anaheim, CA 92801

2693.00 12/21/2017

RMHollow-Stem Auger

740 E. La Palma, LLC

B-2

168.1

Wate

r

Core

Bu

lk

140 lbs / 30 in

5

10

15

20

Asphalt Concrete (AC): 3 inches

ARTIFICIAL FILL (Af)Silty Sand (SM): Brown, moist, loose, fine grained sand, gravel up to 2 inches, trace charcoal, with clay

Silty Sand (SM): Brown to dark brown, moist, medium dense, fine grained sand, trace gravel, trace glass debris

ALLUVIUM (Qal)Sand (SP): Light gray, dry to damp, medium dense, fine to medium grained sand

@ 15 ft, damp

@ 20 ft, dense

10

16

8

26

13

14

3.6

14.3

14.3

1.6

93.3

110.3

105.1

Dist.

SA Hydro

Albus-Keefe & Associates, Inc. Plate A-5

Page 28: Appendix D Geotechnical Due-Diligence Investigation and

Project:

Address:

Job Number:

Drill Method:

Client:

Driving Weight:

Location:

Elevation:

Date:

Logged By:

Depth

(feet)

Lith-

ology

Blows

Per

Foot

Moisture

Content

(%)

Dry

Density

(pcf)

Other

Lab

Tests

Laboratory TestsSamples

Material Description

E X P L O R A T I O N L O G

751-775 E La Palma Ave, Anaheim, CA 92801

2693.00 12/21/2017

RMHollow-Stem Auger

740 E. La Palma, LLC

B-2

168.1

Wate

r

Core

Bu

lk

140 lbs / 30 in

30

@ 25 ft, damp to moist

@ 30 ft, moist

End of boring at 31.5 feet. No groundwater encountered. Backfilled with soil cuttings and capped with asphalt cold patch.

26

27

Albus-Keefe & Associates, Inc. Plate A-6

Page 29: Appendix D Geotechnical Due-Diligence Investigation and

Project:

Address:

Job Number:

Drill Method:

Client:

Driving Weight:

Location:

Elevation:

Date:

Logged By:

Depth

(feet)

Lith-

ology

Blows

Per

Foot

Moisture

Content

(%)

Dry

Density

(pcf)

Other

Lab

Tests

Laboratory TestsSamples

Material Description

E X P L O R A T I O N L O G

751-775 E La Palma Ave, Anaheim, CA 92801

2693.00 12/21/2017

RMHollow-Stem Auger

740 E. La Palma, LLC

B-3

168.6

Wate

r

Core

Bu

lk

140 lbs / 30 in

5

10

15

Asphalt Concrete (AC): 4 inches

ALLUVIUM (Qal)Silty Sand (SM): Light brown, dry, medium dense, fine to medium grained sand, trace gravel up to 2 inches, weathered

Sand (SP): Light gray, dry, medium dense, fine to medium grained sand, trace gravel

@ 10 ft, damp

End of boring at 15 feet. No groundwater encountered. Installed percolation test well (P-2) within boring. Backfilled with soil cuttings and capped with asphalt cold patch upon completion of testing.

16

18

17

19 N.R.

14 N.R.

1.8

2

102

111.3

SA Hydro

Albus-Keefe & Associates, Inc. Plate A-7

Page 30: Appendix D Geotechnical Due-Diligence Investigation and

ALBUS-KEEFE & ASSOCIATES, INC.

APPENDIX B

LABORATORY TEST PROGRAM

Page 31: Appendix D Geotechnical Due-Diligence Investigation and

740 E. La Palma, LLC January 15, 2018 J.N.: 2693.00

ALBUS-KEEFE & ASSOCIATES, INC.

LABORATORY TESTING PROGRAM Soil Classification Soils encountered within the exploratory borings were initially classified in the field in general accordance with the visual-manual procedures of the Unified Soil Classification System (ASTM D 2487). The samples were re-examined in the laboratory and classifications reviewed and then revised where appropriate. The assigned group symbols are presented on the Exploration Logs provided in Appendix A. In-Situ Moisture Content and Dry Density Moisture content and dry density of in-place soil materials were determined in representative strata. Test data are presented on the Exploration Logs provided in Appendix A. Laboratory Maximum Dry Density Maximum dry density and optimum moisture content of onsite soils were determined for selected samples in general accordance with Method A of ASTM D 1557. Pertinent test values are given on Table B-1. Direct Shear The Coulomb shear strength parameters, angle of internal friction and cohesion, were determined for a bulk sample obtained from one our borings. The tests were performed in general conformance with Test Method ASTM D 3080. The sample was remolded to 90 percent of maximum dry density and at the optimum moisture content. Three specimens were prepared for each test, artificially saturated, and then sheared under varied loads at an appropriate constant rate of strain. Results are graphically presented on Plate B-4. Soluble Sulfate Content Chemical analysis was performed on selected samples to determine soluble sulfate content. The tests were performed in accordance with California Test Method No. 417. The test results are included on Table B-1. Expansion Potential An Expansion Index test was performed on a selected sample in accordance with ASTM D 4829. The test result and expansion potential are presented on Table B-1. Corrosion Select samples were tested for minimum resistivity, chloride, and pH in accordance with California Test Method 643. Results of these tests are provided in Table B-1. Particle-Size Analyses Particle-size analyses were performed on selected samples in accordance with ASTM D 422-63. The results are presented graphically on the attached Plates B-1.

Page 32: Appendix D Geotechnical Due-Diligence Investigation and

740 E. La Palma, LLC January 15, 2018 J.N.: 2693.00

ALBUS-KEEFE & ASSOCIATES, INC.

Hydrometer Hydrometer analyses were performed on representative samples of site materials in accordance with ASTM D 7928. The results are presented graphically on the attached Plate B-1.

TABLE B-1

SUMMARY OF LABORATORY TEST RESULTS

Boring No.

Sample Depth

(ft.) Soil Description Test Results

B-1 0-4 Clayey

Sand/Sandy Clay (SC/CL)

Maximum Dry Density: Optimum Moisture Content:

Expansion Index: Expansion Potential:

pH: Resistivity:

Chloride Content: Soluble Sulfate Content:

Sulfate Exposure:

129.5 pcf 9.0%

31 Low 7.9

1,100 ohm-cm 18 ppm 0.002%

Negligible Note: Additional laboratory test results are provided on the boring logs in Appendix A.

Page 33: Appendix D Geotechnical Due-Diligence Investigation and

6" 3" 1.5" 3/4" 3/8" 4 10 20 40 60 100 200U.S. STANDARD SIEVE SIZES

2345678923456789234567892345678923456789234567892

Plate No: B

-1

Job No:

GR

AIN

SIZE

DIST

RIB

UT

ION

GRAVEL SAND SILT AND CLAYCOARSE FINE MEDIUM

UNIFIED SOIL CLASSIFICATION

COARSE FINECOBBLES

CLASSIFICATIONPILLSYMBOLSAMPLELOCATION

0.00010.0010.010.1110100

GRAIN SIZE IN MILLIMETERS

100

90

80

70

60

50

40

30

20

10

0

PERCENT RETAINED

0

10

20

30

40

50

60

70

80

90

100

PER

CE

NT

PA

SSIN

G

10 feet Sand (SP)

Page 34: Appendix D Geotechnical Due-Diligence Investigation and

Job No:

Plate No: B-2DIRECT SHEAR

SAMPLE LOCATION SAMPLE TYPE SAMPLE DESCRIPTIONB-1 @ 0-4 feet 90% of 129.5 pcf @ 9% Clayey Sand/Sandy Clay (SC/CL)

Strain Rate (in/min) 0.01Initial Moisture Content (%) 9 9 9Initial Dry Density (pcf) 116.5 116.5 116.5Ultimate Displacement (in) 0.25 0.25 0.25Ultimate Shear Stress (ksf) 0.648 1.248 2.196Peak Displacement (in) 0.005 0.002 0.013Peak Shear Stress (ksf) 0.84 1.296 2.232Normal Stress (ksf) 1 2 4

1 2 3Specimen No.

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0NORMAL STRESS (ksf)

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

SHEA

R S

TRES

S (k

sf)

0 2 4 6 8 10Axial Strain (%)

0.0

1.0

2.0

3.0

She

ar S

tress

(ksf

)0 2 4 6 8 10

Axial Strain (%)

-0.025

0.000

0.025

Ver

tical

Dis

plac

emen

t (in

.)

124

Strain Legend

Peak

Strength Legend

Ultimate