77
Appendix B – Owner Provided Equipment Appendix B

Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

Appendix B – Owner Provided Equipment

Appendix B

Page 2: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

APPENDIX B

OWNER PROVIDED EQUIPMENT

PART 1 OWNER-FURNISHED PRODUCTS

1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480

A. All Owner-supplied precast items are as indicated below in the procurement table. The vaults will be used for flow meters, process equipment and other services, as well as catch basins.

Table 1 – Owner Supplied Precast Vault/Catch Basin Schedule

Vault Description Quantity Options 5’-0” x 5’-0”x 7’-6” deep Precast Concrete Mag Meter Vault 1

5’-0” x 5’-0” (Clear Opening) AL Double Access Hatch, Spring Assisted, H-20 Rated. Access Ladder with Ladder-up Option

5’-0” x 5’-0”x 7’-0” deep Precast Concrete Mag Meter Vault 3

5’-0” x 5’-0” (Clear Opening) AL Double Access Hatch, Spring Assisted, H-20 Rated. Access Ladder with Ladder-up Option

6’-0” x 6’-0” x 10’-6” deep Precast Concrete Bladder Surge Tank Vault

2

6’-0” x 6’-0” (Clear Opening) AL Double Access Hatch, Spring Assisted, 300 PSF Rated. Provide a minimum of (1) 12 inch grade rings for height adjustment. Access Ladder with Ladder-up Option and Fall Protection

8’-0” x 6’-0” x 7’-8” deep Precast Concrete Booster Pump Control Valve Vault

3 6’-0” x 6’-0” (Clear Opening) AL Double Access Hatch Spring Assisted, H-20 Rated. Access Ladder with Ladder-up Option

4’-0” x 4’-0”x 7’-0” deep Precast Concrete Pressure Relief Valve Vault

2 4’-0” x 4’-0” (Clear Opening) AL Single Access Hatch, Spring Assisted, H-20 Rated. Access Ladder with Ladder-up Option

48” square x 48” deep Precast Concrete Drop Inlet 1 48” Square (Clear Opening) with

Galvanized Steel Grating. 16” square x 24” deep Precast Concrete Drop Inlet 1

16” Square (Clear Opening) with Galvanized Steel Grating.

6’-6” x 4’-0”x 8’-0” deep Precast Concrete PRV & Pressure Relief Valve (Welcome Way)

1 6’-6” x 4’-0” (Clear Opening) AL Double Access Hatch, Spring Assisted, H-20 Rated. Access Ladder with Ladder-up Option

36” square x 42” deep Precast Concrete Drop Inlet. 1 36” Square (Clear Opening) with

Galvanized Steel Grating Please Note: Minimum access hatch size and style are shown on the drawings (nominal clear opening shown, provide additional length/width as necessary to form a complete frame).

Owner Provided Equipment Appendix B-1

Page 3: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

B. Estimated Delivery Date

1. October 9th, 2015

1.2 SUBMERSIBLE TURBINE PUMPS - SPECIFICATION SECTION 11300 (SEE ATTACHED)

A. All Owner-supplied submersible turbine pumps and motors are indicated below:

1. Zolezzi Booster Pump Station Site:

a. 2 Goulds 10RJLC Vertical Submersible Turbine

b. Design Conditions 900 GPM at 460 FT TDH

c. Centripro, 150 HP Motor, 460V/3Ph/60 Hz, 3600 RPM

2. ArrowCreek 1 Booster Pump Station Site:

a. 2 Goulds 10RJLC Vertical Submersible Turbine

b. Design Conditions 900 GPM at 350 FT TDH

c. Centripro, 100 HP Motor, 460V/3Ph/60 Hz, 3600 RPM

3. Copper Cloud Booster Pump Station Site:

a. 2 Goulds 10RJLC Vertical Submersible Turbine

b. Design Conditions 900 GPM at 340 FT TDH

c. Centripro, 100 HP Motor, 460V/3Ph/60 Hz, 3600 RPM

B. Estimated Delivery Date

1. October 7th, 2015

1.3 BOOSTER CAN UNIT STATION - SPECIFICATION SECTION 11302 (SEE ATTACHED)

A. The Owner-furnished booster station can units at the following three existing locations:

1. Zolezzi Booster Pump Station Site:

a. Two (2) - MAASS Midwest Model Number: MB,HD, B-16,18,10,FL-8, NPT-WT-4.33-HDH-LOB-(5) 1.25 SWC-10-FL,12.

2. ArrowCreek 1 Booster Pump Station Site:

a. Two (2) - MAASS Midwest Model Number: MB,HD, B-16,18,10,FL-8, NPT-WT-4.33-HDH-LOB-(5) 1.25 SWC-10-FL,12.

3. Copper Cloud Booster Pump Station Site:

a. Two (2) - MAASS Midwest Model Number: MB,HD, B-16,18,10,FL-8, NPT-WT-4.33-HDH-LOB-(5) 1.25 SWC-10-FL,12.

Owner Provided Equipment Appendix B-2

Page 4: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

B. Estimated Delivery Date

1. October 7th, 2015

1.4 BLADDER – TYPE HYDROPNEUMATIC TANKS - SPECIFICATION SECTION 11650 (SEE ATTACHED)

A. The Owner has pre-purchased two bladder-type surge control tanks for this project. The following sites each have one bladder-type hydropneumatic tank:

1. Zolezzi Booster Pump Station Site:

a. 250 minimum nominal capacity gallons (model number to be provided later), ANSI 300 pound flange.

2. ArrowCreek 1 Booster Pump Station Site:

b. 250 minimum nominal capacity gallons (suction side) (model number to be provided later), ANSI 150 pound flange.

B. Estimated Delivery Date

1. October 23rd, 2015

1.5 OWNER PROVIDED ELECTRICAL / INSTRUMENTATION ITEMS (SEE ATTACHED)

A. The Owner has pre-purchased and will provide the following electrical / Instrumentation items at each site:

1. Zolezzi Booster Pump Station Site:

a. Main Switch Board - (see attached)

b. PLC and RTU - (model number to be provided later)

c. Chart Recorder - (model number to be provided later)

d. All CAT 5 Cables

e. All Pressure Transducers - (model number to be provided later)

f. All Pressure Switches - (model number to be provided later)

g. Float Switch for installation in pump can - (model number to be provided later)

h. Thermal Couples - (model number to be provided later)

2. ArrowCreek 1 Booster Pump Station Site:

a. Main Switch Board - (see attached)

b. PLC and RTU - (model number to be provided later)

c. Chart Recorder - (model number to be provided later)

Owner Provided Equipment Appendix B-3

Page 5: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

d. All CAT 5 Cables

e. All Pressure Transducers - (model number to be provided later)

f. Switches - (model number to be provided later)

g. Float Switch for installation in pump can - (model number to be provided later)

h. Thermal Couples - (model number to be provided later)

3. Copper Cloud Booster Pump Station Site:

a. Main Switch Board - (see attached)

b. PLC and RTU - (model number to be provided later)

c. All CAT 5 Cables

d. All Pressure Transducers - (model number to be provided later)

e. Switches - (model number to be provided later)

f. Float Switch for installation in pump can- (model number to be provided later)

g. Thermocouples - (model number to be provided later)

B. Estimated Delivery Date

1. TBD

1.6 ITEMS NOT SUPPLIED BY OWNER:

The following is a partial list of items not being supplied by the Owner, and is provided for the Contractor’s reference only.

1. Magnetic flow meters

2. Sump pumps and integral float switches

3. Equipment pads

4. All conduits and wiring

5. Cla-Val control and relief valves

6. Lighting fixtures

Owner Provided Equipment Appendix B-4

Page 6: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

Submittal Review FormProject Name: TMWA ArrowCreek Drought Response Design Proj

Routing Sequence Date Received

Checked By Date Sent

Contract No: 205300179

Spec. No: 11300, 11302

Submittal No: 1

Contractor/Subcontractor

CH Spencer

Submittal Title: Booster Pump Submittal Package

Bid Item No.:

Orig. Mfg.Lit.SamplesPrints

Number of Copies

cc:

Resubmittal Received

We have verified that the material or equipment contained in this submittal meets all the requirements specified or shown (no exceptions).

We have verified that the material or equipment contained in this submittal meets all the requirements specified or shown, except for the following deviations (list deviations, attach separate sheet if necessary)

Submittal StatusSubmittal Compliance

A - NO EXCEPTION NOTED (Confirm)

B - NOTE MARKINGS (Confirm)

C - NOTE MARKINGS (Resubmit)

D - REJECTED (Resubmit)

Engineer Remarks

See attached Comments.Contractor Remarks

GC Representative: Designer: David Diegle

CH Spencer Danny Beck 7/29/2015

TMWA 7/29/2015 Ray Kruth 8/3/2015

8/3/2015 David Diegle 8/3/2015

TMWA

CH Spencer

8/3/2015 Scott Estes

Stantec Consulting Ltd.

E - UNREVIEWED / INFORMATION ON

Stantec Consulting Services Inc. Stantec Consulting Services Inc.©

Page 7: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

Submittal Review CommentsProject Name: TMWA ArrowCreek Drought Response Design Project

Submittal Title: Booster Pump Submittal Package

Specification No: 11300, 11302

Submittal No: 1

Date Received: 7/29/2015

Resubmittal No.:

Remarks

1.Pump bowls to be provided with exterior fusion epoxy coating per Spec. Section 2.2.A, rather than the Tnemec coating proposed.

2.Pumps to be provided with stainless steel intake screen (strainer marked as “none” on submittal).

3.Provide additional motor lead length if necessary so that splicing of the motor cable is not required within the pump can per spec. paragraph 2.4. Standard motor lead length is listed as 200”, which may not be sufficient to extend beyond the pump can to a pull box.

4.Please submit written certification that proposed Tnemec 140 meets the NSF 372 requirement for low lead. If not, provide alternative coating.

5.Maass Midwest pump can to extend 24” above finish grade, not 18” as shown.

6.Maass Can suction side flange shall be ANSI Class 150, not Class 300 as show.

7.Maass Can shop drawing should indicate design test pressures.

8.Pump can wetted surfaces to be factory coated with NSF 61 and NSF 372 certified coating. No coating is listed for the pump can.

Contract No.: 205300179

Review EngineerDavid Diegle/Ray Kruth

Stantec Consulting Services Inc. Stantec Consulting Services Inc.©

Page 8: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

C.H. Spencer & Company 95 Isidor Court Sparks, Nevada 775-825-8882

TRUCKEE MEADOWS WATER AUTHORITY (Pumps, Motors, & Pitless Adapters for Arrowcreek Drought Response- Bid # 2016-001)

Page 9: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

Page 1 of 3

C.H. Spencer & Company 1075 South Pioneer Road Salt Lake City, UT 84104 Phone: 801-975-0300 x.110 Fax: 801-972-5216

To: Truckee Meadows Water Authority Attn: Scott Estes Date: July 28, 2015 Reference: TMWA Project No. 2016-001 Bid Date: July 23, 2015

Scott:

Please see attached Submittal Package for the Booster Pump on the TMWA Pumps, Motors and Pitless Adapters for Arrowcreek Drought Response Project

Section 11300 Zolezzi Booster Pump Station (Qty 2) Goulds 10RJLC Vertical Submersible Turbine

- Design Conditions 900 GPM at 460 FT TDH - Centripro, 150 HP Motor, 460V/3Ph/60 Hz, 3600 RPM - Bronze Impellers -416 SS Collets - Tnemic 8 mills OD Coating - N/W Factory Testing -Spare Parts

Section 11300 Arrow Creek Booster Pump Station (Qty 2) Goulds 10RJLC Vertical Submersible Turbine

- Design Conditions 900 GPM at 350 FT TDH - Centripro, 100 HP Motor, 460V/3Ph/60 Hz, 3600 RPM - Bronze Impellers -416 SS Collets - Tnemic 8 mills OD Coating - N/W Factory Testing -Spare Parts

Section 11300 Copper Cloud Booster Pump Station (Qty 2) Goulds 10RJLC Vertical Submersible Turbine

- Design Conditions 900 GPM at 340 FT TDH - Centripro, 100 HP Motor, 460V/3Ph/60 Hz, 3600 RPM - Bronze Impellers -416 SS Collets - Tnemic 8 mills OD Coating - N/W Factory Testing -Spare Parts

Let me know if you have any questions.

Thanks Daniel Beck C.H. Spencer Sales Engineer

Page 10: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

C.H. Spencer & Company 95 Isidor Court Sparks, Nevada 775-825-8882

TABLE OF CONTENTS

TAB # GENERAL PUMP DATA 1 SPECIFIC PUMP DATA 2 SPECIFIC MOTOR DATA 3 PUMP CANS & ACCESSORIES 4 WARRANTY 5

Page 11: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

C.H. Spencer & Company 95 Isidor Court Sparks, Nevada 775-825-8882

GENERAL PUMP DATA

Page 12: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

BTURBINE

Lineshaft and Submersible Turbine Pumps

Page 13: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

TURBINE PUMP PRODUCTION

Page 14: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

You not only get the latest in pump design and technology from Goulds Water Technology, you get more than 100 years of pump manufacturing know-how that includes most of the major innovations in pump engineer-ing and materials. All our prod-ucts reflect the engineering design advances for top efficien-cy and head generation.

Our engineers are specialists, using computer assisted design and extensive test and research facilities. They develop the specifications that guide our in-house pattern shop technicians in the development of preci-sion turbine pattern equipment. The result is consistent casting accuracy, close tolerances and the quality needed to maintain water passage shape and pump efficiencies.

Goulds Water Technology fur-ther controls the quality of its products in its own foundries. Here the molding, core work and Vitra-Glass enameling are closely supervised for tight qual-ity standards.

Our modern manufacturing facilities assure dimensionally consistent, high quality, fully machined parts, produced on a volume basis to bring down costs. Every impeller is precision balanced on a micro processor balance analyzer. Goulds Water Technology is one of the larg-est manufacturers in the turbine industry.

From design to pattern shop to foundry to manufacturing to warehousing — Goulds Water Technology is a completely inte-grated producer. Our network of turbine warehouses brings pumps and same day service to you. We offer full service on new units. Rebowling, rebuild-ing and repair on turbine pumps and submersible and centrifugal pumps.

We are committed to service. We offer ready availability of complete pumps, repair parts and service. We are continually improving and expanding our turbine products warehouse net-work with locations in key areas.

PAGE 3

Page 15: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

150

100908070

50

60

40

30

25

20

0.2 0.3 0.4 0.6 0.8 1 1.5 2 3 4 5 6 7 8 9 10 15 20 25 30 40 50 60 70 80 100

15

10987

200

HEA

D P

ER S

TAG

E (F

T.)

FLOW (100 U.S. GPM)

1770 RPM60 Hz

250

20EH

18HM

18DH

18DM

20BH18CH18BH

18BL16DM 16DHH

18LH

16F

16RGH

15F

16DHL

16BHC16BLC

14F

14RHH

14RHM

14RJH

14RJM

14DHL

12FRH

12DHH

14RJL

13CH

13CM

12CHC

12RJH12RJM

12DHL

10LH

10DHH

13RAH

12WAH12WAM 11CH11CM

11CL

11WAH11RAH9BM 9RCH

10RJ

9TH9TL

9RCL

10WAL

10RAH

10RJL

8DHH

9WAH9WAL8IH

8RJH

8DIL7TH

7CL

8RJL

7CH

8IL

7WAH7W

AL

8RAH

7TL

8RAL

6CH

6DHH6DHL

5TH5TL

6CL5CH

5CL

7RAH7RAL6RAH

5WAH

5WAL

2

60

50

40

30

25

20

15

10987

6

5

3 4 6 7 10 15 20 30 40 50 60 80 100 150 200 300

HEA

D P

ER S

TAG

E (m

)

FLOW (10 Cu. M/Hr)

259851.51.8.6

1470 RPM50 Hz

708090

100

24EH24EL

20GH20GL

20CH20CL

20EH

20BH18CH

18DH

18HM

18DM

18BH18BL

16DM 16DHH

16GL

16GH

15F

16DHL

14F

16BHC16BLC

14RHH

14RJH

14RHM

12RAH

14DHL

12FRH

18LH

12DHH

14RJL

13CH

13CL

13CHC

12RJH

13WAH11CH

12RJM

12DHL

10LH

13WAM11WAH

11CL

11CM11RAH9BN 9RCH

10RJ10DHH9TH

9TL

9RCL

10WAH

10RAH

10RJL

8DHH

9WAH9WAL 8IH

8RJH8DHL7TH

7CH

8IL7WAH

7CL 8RJL

7WAL

6CH

8RAH8RAL7RAH7RAL

14RJM

PAGE 8

LINESHAFT

Page 16: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

ApplicationsGoulds Water Technology combines the hydraulic engineer-ing of turbine pumps matched to the hi-tech design of elec-tric submersible motors.

Features1 Discharge Pipe Properly sized for optimum water velocities to insure peak hydraulic performance.

2 Discharge Bowl Several discharge sizes available for NPT or flanged pipe.

3 Discharge Bearing Extra long top protected bronze bearing insures positive shaft alignment and stabilization for extended life.

4 Intermediate Bowl Close grained Class 30 cast iron. Water passage glassed for maximum efficiency and abrasion resistance.

5 Impellers Designed for maximum efficiency with wide range hydraulic coverage. Precision balanced for smooth operation.

6 Upthrust Collar Designed for extra margin of safety against possible momentary upthrust occurring at startup.

7 Intermediate Bowl Bearings Reliable long life bronze or rubber bearing.

8 Lock Collets Accurately machined to insure positive locking of impeller to pump shaft.

9 Pump Shaft 100,000 PSI high tensile stainless steel provides strength and excellent corrosion resistance. Ground and polished for smooth bearing surface.

10 Suction Inlet Contoured for smooth flow entrance. Protected by an oversized stainless steel strainer to prevent entrance of damaging solids.

11 Suction Adapter Ductile iron provides for increased strength and positive motor alignment. Open area permits easy access to pump/motor coupling.

12 Pump/Motor Coupling Large stainless steel coupling accurately machined for perfect alignment, balance and power transmission. Submersible pumps and motors provide an extensive list of options versus other deep well pumping equipment systems. Advanced engineering designs and experience now assure units for long term pumping service. Water well applications provide the perfect opportunity to evaluate features and benefits of submersible equipment.

1

2

3

4

5

6

7

8

9

12

10

11

PAGE 10

SUBMERSIBLE

Page 17: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

Hermetically Sealed TypeA Hermetically Sealed Type motor utilizes windings of standard construction and insulation thickness. The windings are encased and Hermetically Sealed within the external shell casing on the outside and an internal tube or liner inside the bore. The Hermetically Sealed enclosure elimi-nates the possibility of water leakage into the winding the liquid medium circulates between the rotor and stator liner providing lubrication and cooling to the bearings.

Wet Winding TypeA Wet Winding Type motor is one in which the motor windings are in direct contact with a liquid medium. The medium is clean, clear water. A pressure balancing system prevents exchange of the motor liquid medium and well water due to thermal expansion and contraction when the motor is operating. The liquid medium fills the inside of the motor and surrounds both the stator windings and the rotor. A completely water proof insulation is used on the mag-net wire used for the stator windings. The liquid medium inside the motor air gap and coils acts as a heat transfer device by circu-lating through the windings and transferring heat to the external casing. Dissipation of this heat occurs as the well water flows at a required velocity over the external case. As is the case in all submersible type motors, the internal liquid medium is also used for bearing lubrication.

Submersible OptionsGoulds Water Technology can provide sev-eral options in pump and motor combina-tions to meet the exacting conditions of your applications:

• High temperature wells• High horsepower, limited well diameters• Motor sensing devices• Water level indicators• Special materials• Special voltage motors

Consult Goulds Water Technology Turbine Customer Service Department for details.

Submersible Accessories:Valves— Check Valves — Gate Valves— Flow Control — Ball Valves

Electrical Panels— Furnas Panels — V.F.D. Drivers

Pitless Adapters

Wire— 12 to 0000

Heat Shrinks

Splice Kits

Tanks

Well Heads— Submersible Discharge Head

Torque Arrestors

Gauges

Motor Shrouds

PAGE 11

Page 18: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

HEA

D P

ER S

TAG

E (F

T.)

FLOW (100 U.S. GPM)

150

100908070

50

60

40

30

25

.4 .6 .8 1 1.5 32 4 5 6 7 8 9 10

250

200

300

400

3450 RPM60 Hz

.220

.3 15 20 25 30 40

13RAH13RAL

11CL

11RAH

9RCH

9BM

9TH

9TL

9RCL10RJL

10WAL

10RAH

8DHH

9WAH9WAL8IH8IL

7CH 8RJH

8DHL7TH7TL

8RJL7CL

7WAH

7WAL

6CL6CH

6DHH

6DHL

5TH

5TL

5CL

5CH

8RAH

8RAL7RAH

7RAL6RAH5WAH

5WAL

HEA

D P

ER S

TAG

E (m

)

FLOW (10 Cu. M/Hr)

8070

50

60

40

30

25

20

.8.6 1.0 1.5 2.0 3 4 5 6 7 8 9 10 15 20 25 30 40 50

15

10987

2850 RPM50 Hz

90100

60 70.4

13RAH12WAH11WAH11RAH 12CH

11CH

11CL9BM

9RCH

9TH9TL

9RCL

10WAL

10WAL

10RJL

8DHH

9WAH9WAL8IH8IL

7CH 8RJH

8DHL7TH7TL

8RJL

7WAH

7WAL 7CL

6CH6CL

5CH

8RAH8RAL

7RAH

7RAL

5CL 5TH5TL

6DHH6DHL

8RAH

5WAH5WAL

PAGE 12

SUBMERSIBLE

Daniel
Line
Page 19: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

Hydraulic PerformanceThe system requirements can be met with a choice of pump sizes and selections for the best hydraulic performance. The choice of pump and motor diameters, voltage and specs for varying well conditions provides additional opportunity to match the unit to all the requirements of the system.

The availability of accessory items, cable and controls enables you to rely on Goulds Water Technology for units that provide top service.

Submersibles for 1800 RPM through 20” are also available.

PAGE 13

Page 20: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

Parts List Standard Materials of Construction No. Description Material

GWT No. Description

1 Discharge Head 1003 C.I. ASTM A48,CL 30B

2 Head Shaft Water Lube 2227 Stainless — ASTM A582, Type 416 Oil Lube 2205 Steel — AISI C1045 3 Adjusting Nut 2130 Brass ASTM B16M C360 4 Gib Key 2242 Mild Steel — ASTM A108, Gr. 1018 5 Tension Nut Oil Lube Only 1187 Brass ASTM B584 C844 6 Tension Plate Oil Lube Only 1003 Cast Iron — ASTM A48, CL 30B 7 Oiler Body Oil Lube Only 1425 Aluminum — SAE 329 or Steel 8 Stuffing Box Water Lube 1003 Cast Iron — ASTM A48, CL 30B 9 Stuffing Box Busing Water Lube 1109 Bronze — ASTM B584 C89835 Federalloy III 10 Stuffing Box Stud Water Lube 2229 Stainless — ASTM A276 Type 316 11 Stuffing Box Stud Nut Water Lube 2229 Stainless — ASTM A276 Type 316 12 Stuffing Box Gasket Water Lube 5136 Garlock Brand Blue Guard 13 Stuffing Box Split Gland Water Lube 1193 Aluminum Bronze — ASTM B148HT 14 Stuffing Box Slinger Water Lube 5121 Rubber 15 Packing 5026 Graphited Acrylic Yarn 16 Column Nipple 6501 Pipe — ASTM A53 17 Lock Ring 1018 Ductile — ASTM A536, Gr. 65-45-12 18 Reducer-Bushing 1003 Cast Iron — ASTM A48, CL 30B 19 Companion Flange 1003 Cast Iron — ASTM A48, CL 30B 20 Companion Flange Gasket 5136 Garlock Brand Blue Guard 21 Nameplate 3211 Stainless — ASTM A240, Type 316 22 Sole Plate 3201 Steel Plate — ASTM A36 23 Column Pipe 6501 Pipe — ASTM A53 24 Column Coupling 6501 Pipe — ASTM A53 25 Tube Nipple 6518 Pipe — Steel SCH80 ASTM A120 Gr. B

26 Enclosing Tube Bronze Construction 6518 Steel — SCH80, ASTM A120, Gr. B Wood-Lined Construction 6518 Steel — SCH80, ASTM A120, Gr. B 27 Oil Tube Coupling Wood-Lined Only 6518 Steel — SCH80, ASTM A120, Gr. B 28 Lineshaft Bearing Bronze Construction 1109 Bronze — ASTM B584 C903 Wood-Lined Construction Clear Heart Redwood — Grade A W/L — Sleeved 2205 Steel — AISI C1045 with Type 304SS Sleeve 29 Lineshaft W/L — Stainless 2227 Stainless — ASTM A582, Type 416 Oil Lube 2205 Steel — AISI C1045

30 Lineshaft Coupling Water Lube 2242 Mild Steel — ASTM A108, Gr. 1018 Stainless 2218 Stainless — ASTM A582, Type 416

31 Water Lube Retainer Retainer 1102 Silicon Bronze — ASTM B584 C876 Insert 5121 Rubber 32 Tube Centering Spider 5121 Rubber 33 Discharge Bowl 1003 Cast Iron — ASTM A48, CL 30B 34 Discharge Bushing Water Lube 1109 Bronze — ASTM B584 C89835 Federalloy III 35 Throttle Bushing Oil Lube 1109 Bronze — ASTM B584 C89835 Federalloy III 36 Intermediate Bowl 6911 Cast Iron — ASTM A48, CL 30B, Enameled 37 Top Inter Bowl 6911 Cast Iron — ASTM A48, CL 30B, Enameled

38 Inter Bowl Bushing Bronze 1109 Bronze — ASTM B584 C89835 Federalloy III Rubber 5121 Rubber

39 Wear Rings — Optional Inter Bowl 1117 AL Bronze ASTM B148 C954 Impeller 1117 AL Bronze ASTM B148 C954 40 Impeller 1102 Silicon Bronze — ASTM B584 C876 41 Taper Lock 2242 Mild Steel — ASTM A108, Gr. 1018 42 Suction Bowl 1003 Cast Iron — ASTM A48, CL 30B 43 Suction Bushing 1109 Bronze — ASTM B584 C89835 Federalloy III 44 Sand Collar 1109 Bronze — ASTM B584 C89835 Federalloy III 45 Suction Strainer 6952 Galvanized — ASTM A123 46 Plug 1046 Steel — ASTM A197 Mall. Iron

47 Screw Bearing Bronze Construction 1109 Bronze — ASTM B584 C89835 Federalloy III Wood-Lined Construction 2242 Mild Steel — ASTM A108, Gr. 1018 48 Bowl Shaft 2227 Stainless — ASTM A582, Type 416 49 Hex Bolt 2298 Steel — SAEJ 429, Gr. 8 50 Lock Washer 2242 Steel — ASTM A108, Gr. 10180

51 Suction Adapter Submersible Only 1018 Ductile Iron — Astm A536, Gr. 65-45-12 52 Adapter Plate Submersible Only (Optional) 1018 Ductile Iron — ASTM A536, Gr. 65-45-12 53 Motor Coupling Submersible Only 2218 Stainless Steel — ASTM A582, Type 416 54 Motor Mounting Bolts Submersible Only 2229/2228 Stainless — ASTM A276, Type 316/304SS 55 Suction Screen Submersible Only 3215 AISI 304 Stainless 56 Cable Guard Submersible Only 3215/6266 AISI 304 Stainless or Polyethylene (UHMW) 57 Discharge Bearing Submersible Only 1109 Bronze — ASTM B584 C89835 Federalloy III 58 Discharge Bearing Plug Submersible Only 1046 Steel — ASTM A197 Mall. Iron 59 Upthrust Washer Submersible Only 6266 Polyethylene (UHMW)

PAGE 14

LINESHAFT/SUBMERSIBLES

Page 21: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

• Municipal• Wastewater Plants• Commercial/Industrial• Golf Courses/

Turf Irrigation• Agricultural Irrigation

• Dewatering• Mining• Cooling Tower• Water Parks• Snowmaking• Flood Control

Services

PAGE 15

Page 22: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

Turbine Distribution Centers: Phone FaxLUBBOCK P.O. Box 5487, Lubbock, TX 79408 1-806-763-7867 1-806-743-5730

MEMPHIS 1085 Stateline Road East, Suite 107, Southaven, MS 38671 1-662-393-5853 1-800-453-4745

ORLANDO 1150 Emma Oaks Trail, Suite 150, Lake Mary, FL 32746 1-407-829-7724 1-407-829-7725

FRESNO 3878 S. Willow Ave., #104, Fresno, CA 93725 1-559-265-4730 1-800-453-7523 1-559-265-4740

Specifications & Special Projects:LUBBOCK CUSTOMER SERVICE CENTER 1-806-763-7867 1-806-743-5730

Mexico

CanadaUSA

Venezuela

BelgiumFrance

Portugal

UK

NetherlandsGermanyItaly

China

Philippines

Singapore

Australia

Lubbock, TX

Goulds is a registered trademark of Goulds Pumps, Inc. and is used under license. © 2012 Xylem Inc. BTURBINE January 2012

Xylem Inc.

P.O. Box 5487 Lubbock, TX 79408 www.xyleminc.com/brands/gouldswatertechnology

Goulds Water Technology, headquartered in Seneca Falls, New York, designs, manufactures and services pumps, motors and accessories for industrial, agricul-tural, municipal, commercial and residential markets. Our sales offices and manufacturing facilities are located worldwide.

Goulds Water Technology is a brand of Xylem, Inc., the world's largest and premier pump manufacturer, and offers the most complete range of pumps available.

Page 23: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

C.H. Spencer & Company 95 Isidor Court Sparks, Nevada 775-825-8882

SPECIFIC PUMP DATA

Page 24: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

Pump Data Sheet - Submersible 60 Hz

Company: CH Spencer & CompanyName: ZolezziDate: 7/8/2015

TMWA

Pump:Size: 10RJLC (4 stage)Type: Submersible Speed: 3450 rpmSynch speed: 3600 rpm Dia: 6.0625 inCurve: 3010 Impeller:Specific Speeds: Ns: 2760

Nss: ---Dimensions: Suction: ---

Discharge: ---Vertical Turbine: Bowl size: 9.5 in

Max lateral: 0.75 inThrust K factor: 7 lb/ft

Pump Limits:Temperature: 120 °F Power: ---Pressure: 430 psi g Eye area: ---Sphere size: 0.68 in

Search Criteria:Flow: 900 US gpm Head: 460 ft

Fluid:Water Temperature: 68 °FDensity: 62.32 lb/ft³ Vapor pressure: 0.3391 psi aViscosity: 0.9946 cP Atm pressure: 14.7 psi aNPSHa: ---

Motor:Size: 150 hpSpeed: 3600Frame: 8 inch

Standard: NEMAEnclosure: SUB

Sizing criteria: Max Power on Design Curve

PUMP-FLO 10.6.2.0 Selected from catalog: Goulds Sub 60Hz Vers: 3.36

---- Data Point ----Flow: 900 US gpmHead: 461 ftEff: 82.8%Power: 126 hpNPSHr: 34.5 ft

---- Design Curve ----Shutoff head: 682 ftShutoff dP: 295 psiMin flow: ---BEP: 83.2% @ 942 US gpmNOL power:

128 hp @ 1008 US gpm

-- Max Curve --Max power:

168 hp @ 1139 US gpm

Discharge Sizes-6",8". Curves are certified for water at 60°F only. Consult factory for performance with any other fluid.US gpm

Pow

er -

hp

16001400120010008006004000 200

100

200

NPS

Hr -

ft

16001400120010008006004000 200

50

100

Hea

d - f

t

16001400120010000 800

200

600

400

400

600

200

800

83.2

6.0625 in

6.62 in

5.25 in

40

40

50

50

60

60

70

7070

70

74

7474

74

77

77

77

77

79

79

79

79

81

81

8282

Performance Evaluation:Flow Speed Head Efficiency Power NPSHrUS gpm rpm ft % hp ft1080 3450 377 81.2 126 44.1900 3450 461 82.8 126 34.5720 3450 523 77.8 122 28.2540 3450 568 67.5 114 27360 3450 605 51.3 107 27

Page 25: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

CH Spencer & Company DIMENSIONAL OUTLINEVIS-T

4 Stage 8x10RJLCPump Data

AD:AG: Size: 10RJLC

Stages: 4BL: 51.35

CD: BowlShaft: 1.50"CL: N/ACOL: 0.00" LineShaft: N/ADD: LineShaft Type: N/A

Column: StandardDH: Column: 8" ThreadedG: Bearing Spacing: N/AH: Section Length: N/AHH: Head: NoneJ: Disch. NPT: N/AR: 10.00 Suct.:ML: 70.10

Seal: N/ATPL: N/A" Strainer: NoneUG: N/A SubBase: N/AV:W: Motor Diameter: 8"X:SD:Y:Z:

Hydraulic Data Miscellaneous Motor DataFlow (gpm): 900 Thrust At Design (lb): 3269 Model: 8M1504Pump Head (ft): 460.4 Thrust At Shutoff (lb): 4817 Make: CentriProTDH (ft): 461.0 Pumping Level(in): 0 HP: 150Speed (rpm): 3450 RPM: 3600Fluid: Water Weight Type: SUBTemperature (F): 68 Pump (lb): 367 Efficiency: 85.6Viscosity: 0.9946 Motor (lb): 683 Nominal Dia: 8"Spec.Grav: 1.00012 Total (lb): 1050 Voltage: 460

Version: 4.16P Date: 07-08-2015Customer:

Page 26: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

CH Spencer & Company HYDRAULIC ANALYSISVIS-T

4 Stage 8x10RJLCOverall Pump Parameters

Size and Model: 10RJLC Pump Operating Speed, RPM: 3450Capacity, GPM: 900 Total Dynamic Head, Ft.: 461.0Total Pump Length, In.: 121.4 Impeller Trim, In.: 6.1Pump Type: Submersible Head Type: NonePump K-Factor: 7 Number of Stages: 4

Pumping Level, In.: 0.0 Bowl Data

Total Bowl Length, In.: 51.35 Bowl Diameter, In.: 9.5Bowl Shaft Dia, In.: 1.50 Bowl Shaft Limit, HP: 498

Bowl Shaft Material: 416SS Column Data

Column Diameter, In.: 8 Column Load, Lb.: 4467.1Wall Thickness, In: Column Elongation, In.: 0.00

Shutoff Column Elongation, In.: 0.00 HorsePower Data

Thrust Load Loss, Hp.: 0.00Bowl HP At Design, Hp.: 126 Motor HorsePower, Hp.: 150

Other Data

Hydraulic Thrust, Lb.: 3227.4 Thrust at Design, Lb.: 3269.4Thrust at Shutoff, Lb.: 4817 Actual Head above Grade, Ft.: 460.35Suction Pressure, psi: 0.0 Shutoff Disc Pressure, psi: 295.3Column Loss, Ft.: 0.00 NPSHa, Ft.:Head Loss, Ft.: 0.65 NPSHr, Ft.: 34.50Total Loss, Ft.: 0.65 NPSH margin, Ft.:

Efficiency Data (Efficiencies estimated not guaranteed)Bowl Efficiency: 82.80 Pump Efficiency: 82.68Motor Efficiency: 85.60 Overall Efficiency: 70.78

KWH/1000 gallons: 2.05 Component Weights

Bowl Weight, Lbs.: 367 Column Weight,Lbs.: 0Head Weight, Lbs.: 0 Can Weight,Lbs.: 0Motor Weight, Lbs.: 683 Total Pump Weight,Lbs.: 1050

Version: 4.16P Date: 07-08-2015Customer:

Page 27: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

CH Spencer & Company SECTIONALVIS-T

4 Stage 8x10RJLC

DISCHARGE HEAD ASSEMBLYITEM NAME Code MATERIAL ASTM

COLUMN AND LINESHAFT ASSEMBLY

BOWL ASSEMBLY614 COUPLING -- SUB MOTOR 2218 SST 416 A582M-95b660 SHAFT- BOWL 2227 SST 416 A582M-95b661 BOWL- DISCHARGE 8536 TNEMEC 140 ON IRON A48670 BOWL- INTERMEDIATE 8536 TNEMEC 140 ON IRON A48671 SUBADAPTER 1018 DUCTILE IRON 65-45-12 A536-84(1999)e1672 BEARING- INT BOWL 1109 FEDERALLOY BISMUTH BRZ B584-00673 IMPELLER 1102 SILICON BRONZE C87600 B584-00677 COLLET- IMPELLER 2242 CARBON STEEL 1018 A108-99680 WEAR RING- BOWL 1128 BRONZE, AL C95400 B148-97e1681 WEAR RING- IMPELLER 1128 BRONZE, AL C95400 B148-97e1690 BEARING- SUCTION 1109 FEDERALLOY BISMUTH BRZ B584-00715 GUARD- CABLE 3215 SST 304 A240M-00758 CAPSCREW- HEX (MOTOR)2228 SST 304 A276760 CAPSCREW- HEX 2298 STEEL BOLTING GR 8 J429-99781 SCREEN- SUCTION 3215 SST 304 A240M-00789 WASHER- UPTHRUST 6266 TIVAR 1000 x

Version: 4.16P Date: 07-08-2015Customer:

Page 28: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

CH Spencer & Company ADDERSVIS-T

4 Stage 8x10RJLC

ADDITIONAL PUMP COMPONENTS

The following is a list of the additional components you ordered.Consult factory for any other components or services.

Component

Motor Adaptation Bronze 416 SS Collets Performance TestBowl Coating (type 3)

Tnemec 140 8 mil

Version: 4.16P Date: 07-08-2015Customer:

Page 29: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

Pump Data Sheet - Submersible 60 Hz

Company: CH Spencer & CompanyName: Aarow CreekDate: 7/8/2015

TMWA

Pump:Size: 10RJLC (3 stage)Type: Submersible Speed: 3450 rpmSynch speed: 3600 rpm Dia: 6.125 inCurve: 3010 Impeller:Specific Speeds: Ns: 2760

Nss: ---Dimensions: Suction: ---

Discharge: ---Vertical Turbine: Bowl size: 9.5 in

Max lateral: 0.75 inThrust K factor: 7 lb/ft

Pump Limits:Temperature: 120 °F Power: ---Pressure: 430 psi g Eye area: ---Sphere size: 0.68 in

Search Criteria:Flow: 900 US gpm Head: 350 ft

Fluid:Water Temperature: 68 °FDensity: 62.32 lb/ft³ Vapor pressure: 0.3391 psi aViscosity: 0.9946 cP Atm pressure: 14.7 psi aNPSHa: ---

Motor:Size: 100 hpSpeed: 3600Frame: 8 inch

Standard: NEMAEnclosure: SUB

Sizing criteria: Max Power on Design Curve

PUMP-FLO 10.6.2.0 Selected from catalog: Goulds Sub 60Hz Vers: 3.36

---- Data Point ----Flow: 900 US gpmHead: 356 ftEff: 82.6%Power: 97.5 hpNPSHr: 34.6 ft

---- Design Curve ----Shutoff head: 522 ftShutoff dP: 226 psiMin flow: ---BEP: 83.2% @ 949 US gpmNOL power:

99.3 hp @ 1015 US gpm

-- Max Curve --Max power:

126 hp @ 1139 US gpm

Discharge Sizes-6",8". Curves are certified for water at 60°F only. Consult factory for performance with any other fluid.US gpm

Pow

er -

hp

16001400120010008006004000 200

50

100

150

NPS

Hr -

ft

16001400120010008006004000 200

50

100

Hea

d - f

t

1600140012001000100 800

200

600

300

400

400

500

200

600

83.2

6.125 in

6.62 in

5.25 in

40

40

50

50

60

60

70

7070

70

74

74 74

74

77

77

77

77

79

79

79

79

81

81

82

82

Performance Evaluation:Flow Speed Head Efficiency Power NPSHrUS gpm rpm ft % hp ft1080 3450 293 81.3 98.1 44.1900 3450 356 82.6 97.5 34.6720 3450 402 77.6 94.1 28.3540 3450 436 67.3 87.9 27360 3450 464 51.3 82.1 27

Page 30: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

CH Spencer & Company DIMENSIONAL OUTLINEAarow Creek VIS-T

4 Stage 8x10RJLCPump Data

AD: 0.00AG: Size: 10RJLC

Stages: 4BL: 53.23

CD: BowlShaft: 1.50"CL: N/ACOL: 0.00" LineShaft: N/ADD: LineShaft Type: N/A

Column: StandardDH: Column: 8" ThreadedG: Bearing Spacing: N/AH: Section Length: N/AHH: Head: NoneJ: Disch. NPT: N/AR: 10.00 Suct.:ML: 58.30

Seal: N/ATPL: 111.53 Strainer: NoneUG: N/A SubBase: N/AV:W: Motor Diameter: 8"X:SD:Y:Z:

Hydraulic Data Miscellaneous Motor DataFlow (gpm): 900 Thrust At Design (lb): 2534 Model: 8M1004Pump Head (ft): 355.4 Thrust At Shutoff (lb): 4817 Make: CentriProTDH (ft): 356.0 Pumping Level(in): 0 HP: 100Speed (rpm): 3450 RPM: 3600Fluid: Water Weight Type: SUBTemperature (F): 68 Pump (lb): 367 Efficiency: 86.2Viscosity: 0.9946 Motor (lb): 683 Nominal Dia: 8"Spec.Grav: 1.00012 Total (lb): 1050 Voltage: 460

Version: 4.16P Date: 07-08-2015TMWA

Page 31: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

CH Spencer & Company HYDRAULIC ANALYSISAarow Creek VIS-T

4 Stage 8x10RJLCOverall Pump Parameters

Size and Model: 10RJLC Pump Operating Speed, RPM: 3450Capacity, GPM: 900 Total Dynamic Head, Ft.: 356.0Total Pump Length, In.: 107.9 Impeller Trim, In.: 6.1Pump Type: Submersible Head Type: NonePump K-Factor: 7 Number of Stages: 4

Pumping Level, In.: 0.0 Bowl Data

Total Bowl Length, In.: 53.23 Bowl Diameter, In.: 9.5Bowl Shaft Dia, In.: 1.50 Bowl Shaft Limit, HP: 499

Bowl Shaft Material: 416SS Column Data

Column Diameter, In.: 8 Column Load, Lb.: 4467.1Wall Thickness, In: Column Elongation, In.: 0.00

Shutoff Column Elongation, In.: 0.00 HorsePower Data

Thrust Load Loss, Hp.: 0.00Bowl HP At Design, Hp.: 97.5 Motor HorsePower, Hp.: 150

Other Data

Hydraulic Thrust, Lb.: 2492.3 Thrust at Design, Lb.: 2534.3Thrust at Shutoff, Lb.: 4817 Actual Head above Grade, Ft.: 355.35Suction Pressure, psi: 0.0 Shutoff Disc Pressure, psi: 295.3Column Loss, Ft.: 0.00 NPSHa, Ft.:Head Loss, Ft.: 0.65 NPSHr, Ft.: 34.50Total Loss, Ft.: 0.65 NPSH margin, Ft.:

Efficiency Data (Efficiencies estimated not guaranteed)Bowl Efficiency: 82.60 Pump Efficiency: 82.45Motor Efficiency: 85.60 Overall Efficiency: 70.58

KWH/1000 gallons: 1.58 Component Weights

Bowl Weight, Lbs.: 367 Column Weight,Lbs.: 0Head Weight, Lbs.: 0 Can Weight,Lbs.: 0Motor Weight, Lbs.: 683 Total Pump Weight,Lbs.: 1050

Version: 4.16P Date: 07-08-2015TMWA

Page 32: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

CH Spencer & Company SECTIONALAarow Creek VIS-T

4 Stage 8x10RJLC

DISCHARGE HEAD ASSEMBLYITEM NAME Code MATERIAL ASTM

COLUMN AND LINESHAFT ASSEMBLY

BOWL ASSEMBLY614 COUPLING -- SUB MOTOR 2218 SST 416 A582M-95b660 SHAFT- BOWL 2227 SST 416 A582M-95b661 BOWL- DISCHARGE 8536 TNEMEC 140 ON IRON A48670 BOWL- INTERMEDIATE 8536 TNEMEC 140 ON IRON A48671 SUBADAPTER 1018 DUCTILE IRON 65-45-12 A536-84(1999)e1672 BEARING- INT BOWL 1109 FEDERALLOY BISMUTH BRZ B584-00673 IMPELLER 1102 SILICON BRONZE C87600 B584-00677 COLLET- IMPELLER 2242 CARBON STEEL 1018 A108-99680 WEAR RING- BOWL 1128 BRONZE, AL C95400 B148-97e1681 WEAR RING- IMPELLER 1128 BRONZE, AL C95400 B148-97e1690 BEARING- SUCTION 1109 FEDERALLOY BISMUTH BRZ B584-00715 GUARD- CABLE 3215 SST 304 A240M-00758 CAPSCREW- HEX (MOTOR)2228 SST 304 A276760 CAPSCREW- HEX 2298 STEEL BOLTING GR 8 J429-99781 SCREEN- SUCTION 3215 SST 304 A240M-00789 WASHER- UPTHRUST 6266 TIVAR 1000 x

Version: 4.16P Date: 07-08-2015TMWA

Page 33: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

CH Spencer & Company ADDERSAarow Creek VIS-T

4 Stage 8x10RJLC

ADDITIONAL PUMP COMPONENTS

The following is a list of the additional components you ordered.Consult factory for any other components or services.

Component

416 SS Collets Performance TestBowl Coating (type 3)

Tnemec 140 8 mil

Version: 4.16P Date: 07-08-2015TMWA

Page 34: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

Pump Data Sheet - Submersible 60 Hz

Company: CH Spencer & CompanyName: Cooper CloudDate: 7/8/2015

TMWA

Pump:Size: 10RJLC (3 stage)Type: Submersible Speed: 3450 rpmSynch speed: 3600 rpm Dia: 6.0625 inCurve: 3010 Impeller:Specific Speeds: Ns: 2760

Nss: ---Dimensions: Suction: ---

Discharge: ---Vertical Turbine: Bowl size: 9.5 in

Max lateral: 0.75 inThrust K factor: 7 lb/ft

Pump Limits:Temperature: 120 °F Power: ---Pressure: 430 psi g Eye area: ---Sphere size: 0.68 in

Search Criteria:Flow: 900 US gpm Head: 340 ft

Fluid:Water Temperature: 68 °FDensity: 62.32 lb/ft³ Vapor pressure: 0.3391 psi aViscosity: 0.9946 cP Atm pressure: 14.7 psi aNPSHa: ---

Motor:Size: 100 hpSpeed: 3600Frame: 8 inch

Standard: NEMAEnclosure: SUB

Sizing criteria: Max Power on Design Curve

PUMP-FLO 10.6.2.0 Selected from catalog: Goulds Sub 60Hz Vers: 3.36

---- Data Point ----Flow: 900 US gpmHead: 345 ftEff: 82.8%Power: 94.6 hpNPSHr: 34.5 ft

---- Design Curve ----Shutoff head: 511 ftShutoff dP: 221 psiMin flow: ---BEP: 83.2% @ 942 US gpmNOL power:

96.2 hp @ 1008 US gpm

-- Max Curve --Max power:

126 hp @ 1139 US gpm

Discharge Sizes-6",8". Curves are certified for water at 60°F only. Consult factory for performance with any other fluid.US gpm

Pow

er -

hp

16001400120010008006004000 200

50

100

150

NPS

Hr -

ft

16001400120010008006004000 200

50

100

Hea

d - f

t

1600140012001000100 800

200

600

300

400

400

500

200

600

83.2

6.0625 in

6.62 in

5.25 in

40

40

50

50

60

60

70

7070

70

74

74 74

74

77

77

77

77

79

79

79

79

81

81

82

82

Performance Evaluation:Flow Speed Head Efficiency Power NPSHrUS gpm rpm ft % hp ft1080 3450 283 81.2 94.8 44.1900 3450 345 82.8 94.6 34.5720 3450 392 77.8 91.6 28.2540 3450 426 67.5 85.7 27360 3450 454 51.3 80.3 27

Page 35: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

CH Spencer & Company DIMENSIONAL OUTLINECooper Cloud VIS-T

3 Stage 8x10RJLCPump Data

AD: 0.00AG: Size: 10RJLC

Stages: 3BL: 42.95

CD: BowlShaft: 1.50"CL: N/ACOL: 0.00" LineShaft: N/ADD: LineShaft Type: N/A

Column: StandardDH: Column: 8" ThreadedG: Bearing Spacing: N/AH: Section Length: N/AHH: Head: NoneJ: Disch. NPT: N/AR: 10.00 Suct.:ML: 58.30

Seal: N/ATPL: 101.25 Strainer: NoneUG: N/A SubBase: N/AV:W: Motor Diameter: 8"X:SD:Y:Z:

Hydraulic Data Miscellaneous Motor DataFlow (gpm): 900 Thrust At Design (lb): 2447 Model: 8M1004Pump Head (ft): 344.4 Thrust At Shutoff (lb): 3609 Make: CentriProTDH (ft): 345.0 Pumping Level(in): 0 HP: 100Speed (rpm): 3450 RPM: 3600Fluid: Water Weight Type: SUBTemperature (F): 68 Pump (lb): 307 Efficiency: 86.2Viscosity: 0.9946 Motor (lb): 595 Nominal Dia: 8"Spec.Grav: 1.00012 Total (lb): 902 Voltage: 460

Version: 4.16P Date: 07-08-2015TMWA

Page 36: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

CH Spencer & Company HYDRAULIC ANALYSISCooper Cloud VIS-T

3 Stage 8x10RJLCOverall Pump Parameters

Size and Model: 10RJLC Pump Operating Speed, RPM: 3450Capacity, GPM: 900 Total Dynamic Head, Ft.: 345.0Total Pump Length, In.: 101.2 Impeller Trim, In.: 6.1Pump Type: Submersible Head Type: NonePump K-Factor: 7 Number of Stages: 3

Pumping Level, In.: 0.0 Bowl Data

Total Bowl Length, In.: 42.95 Bowl Diameter, In.: 9.5Bowl Shaft Dia, In.: 1.50 Bowl Shaft Limit, HP: 499

Bowl Shaft Material: 416SS Column Data

Column Diameter, In.: 8 Column Load, Lb.: 3301.8Wall Thickness, In: Column Elongation, In.: 0.00

Shutoff Column Elongation, In.: 0.00 HorsePower Data

Thrust Load Loss, Hp.: 0.00Bowl HP At Design, Hp.: 94.6 Motor HorsePower, Hp.: 100

Other Data

Hydraulic Thrust, Lb.: 2415.3 Thrust at Design, Lb.: 2446.8Thrust at Shutoff, Lb.: 3609 Actual Head above Grade, Ft.: 344.35Suction Pressure, psi: 0.0 Shutoff Disc Pressure, psi: 221.2Column Loss, Ft.: 0.00 NPSHa, Ft.:Head Loss, Ft.: 0.65 NPSHr, Ft.: 34.50Total Loss, Ft.: 0.65 NPSH margin, Ft.:

Efficiency Data (Efficiencies estimated not guaranteed)Bowl Efficiency: 82.80 Pump Efficiency: 82.64Motor Efficiency: 86.20 Overall Efficiency: 71.24

KWH/1000 gallons: 1.52 Component Weights

Bowl Weight, Lbs.: 307 Column Weight,Lbs.: 0Head Weight, Lbs.: 0 Can Weight,Lbs.: 0Motor Weight, Lbs.: 595 Total Pump Weight,Lbs.: 902

Version: 4.16P Date: 07-08-2015TMWA

Page 37: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

CH Spencer & Company SECTIONALCooper Cloud VIS-T

3 Stage 8x10RJLC

DISCHARGE HEAD ASSEMBLYITEM NAME Code MATERIAL ASTM

COLUMN AND LINESHAFT ASSEMBLY

BOWL ASSEMBLY614 COUPLING -- SUB MOTOR 2218 SST 416 A582M-95b660 SHAFT- BOWL 2227 SST 416 A582M-95b661 BOWL- DISCHARGE 8536 TNEMEC 140 ON IRON A48670 BOWL- INTERMEDIATE 8536 TNEMEC 140 ON IRON A48671 SUBADAPTER 1018 DUCTILE IRON 65-45-12 A536-84(1999)e1672 BEARING- INT BOWL 1109 FEDERALLOY BISMUTH BRZ B584-00673 IMPELLER 1102 SILICON BRONZE C87600 B584-00677 COLLET- IMPELLER 2242 CARBON STEEL 1018 A108-99680 WEAR RING- BOWL 1128 BRONZE, AL C95400 B148-97e1681 WEAR RING- IMPELLER 1128 BRONZE, AL C95400 B148-97e1690 BEARING- SUCTION 1109 FEDERALLOY BISMUTH BRZ B584-00715 GUARD- CABLE 3215 SST 304 A240M-00758 CAPSCREW- HEX (MOTOR)2228 SST 304 A276760 CAPSCREW- HEX 2298 STEEL BOLTING GR 8 J429-99781 SCREEN- SUCTION 3215 SST 304 A240M-00789 WASHER- UPTHRUST 6266 TIVAR 1000 x

Version: 4.16P Date: 07-08-2015TMWA

Page 38: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

CH Spencer & Company ADDERSCooper Cloud VIS-T

3 Stage 8x10RJLC

ADDITIONAL PUMP COMPONENTS

The following is a list of the additional components you ordered.Consult factory for any other components or services.

Component

Motor Adaptation Bronze 416 SS Collets Performance TestBowl Coating (type 3)

Tnemec 140 8 mil

Version: 4.16P Date: 07-08-2015TMWA

Page 39: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

C.H. Spencer & Company 95 Isidor Court Sparks, Nevada 775-825-8882

SPECIFIC MOTOR DATA

Page 40: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

BRCP6SM

6-10" Submersible MotorsFOR 6" AND LARGER DEEP WELL PUMPS

Daniel
Line
Page 41: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

PAGE 4

Commercial, Irrigation and Agricultural WaterCentriPro

6" Canned Design Motor Features• Replaceable Plug-in Motor Lead – All 6” motor leads

are stranded copper for flexibility and strength. Leads are 150” long and field replaceable.

• Insulation – The canned motor’s stator coil is mounted in a stainless steel frame and is completely sealed in a stainless steel cylinder. The coil wire features moisture resistant insulation which is completely water-proofed for long life.

• Heat Resistant – The space between the stator's stain-less steel protective can and its frame is filled with a specially formulated patented resin that protects the motor against thermal fluctuation and internal stress.

• 95º F (35º C) Water Temperature (CANNED TYPE: 6", 5 – 50 HP) – The motors operate with a minimum flow rate of 0.5 ft./sec. (0.15 m/sec) in water temperature up to 95º F (35º C) without any derating of horsepower. This 95º F (35º C) temperature is 18º F (10º C) higher than NEMA standards.

8-10" Rewindable Water-Tight Motor Features• Insulation Wire – The coil conductor insulation mate-

rial is a specially developed denatured polypropylene, which offers excellent leak-resistant characteristics. Three barriers are applied to the copper conductors to provide complete insulation against the motor’s cool-ing fluid. This design is the result of extensive research and is of superior quality. It insures that CentriPro mo-tors will have an extremely long service life.

Motor Features - Both Designs• Sand Resistant Slinger and Lip Seals – CentriPro sub-

mersible motors feature double-row, grease packed, lip seals to prevent sand from entering the motor. A carbon steel slinger with a baked on epoxy coating pre-vents sand from entering the lip seal area. Additional protection against sand intrusion is provided by the close tolerance slinger guide with a .02” fit. This design

is field-proven in West Texas wells which are consid-ered to be some of the worst sandy well applications. Best of all, these features are standard for a CentriPro motor, so there is no need to stock one motor for clean wells and another more expensive motor for the more abrasive, sandy jobs.

• High Torque Characteristics – The stator laminations are constructed of high quality, electrical grade, silicon steel which provide high torque even when the motor is subjected to nominal voltage variations.

• Balancing – The rotor balance rings (one on each end of the rotor) allow for excellent dynamic balance for the rotating element of the motor.

• Carbon Sleeve Bearings – Two carbon, water-lubri-cated, guide bearings are used to properly align the shaft. The bearings have a large surface area to better support the shaft, reducing whipping, while acting as a steady bushing.

• Water-Filled Design – The internal cooling water is mixed with antifreeze and antirust liquid to allow the motor to be stored at –22º F (–30º C). Two water plugs are provided for filling or draining the anti-freeze fluid during maintenance. These plugs are also used to top off and to check the water level.

• Complete Corrosion and Water-Tight Protection – All main motor components are made of stainless steel: in-cluding the can housing (water tight type motors have baked epoxy coated carbon steel housings), shaft and bolts. All other motor parts are finished with the baked epoxy coating.

• Baked Epoxy Coating – All external and internal cast iron parts are coated with a baked epoxy resin that pro-vides excellent resistance to water and corrosion.

• Quality Control – All CentriPro submersible motors are manufactured and tested under the most stringent quality control procedures, providing long service life and trouble-free operation.

TYPE 6" CANNED DESIGN 8-10" REWINDABLE WATER-TIGHT DESIGN

Construction

Slot Insulation

GENERAL FEATURES OF CANNED AND REWINDABLE WATER-TIGHT MOTORS

CONSTRUCTION AND INSULATION DETAILS

Daniel
Line
Page 42: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

PAGE 5

Commercial, Irrigation and Agricultural WaterCentriPro

THREE PHASE, 5-30 HP, 230 AND 460V DUAL VOLTAGE MOTORS

With DUAL VOLTAGE SUBMERSIBLE MOTORS IN YOUR STOCK, you no longer have to worry about inventory balance between 230V and 460V.

DUAL VOLTAGE SUBMERSIBLE MOTORS have all the same specifications of canned type motors plus the unique feature of dual voltage.

Motor voltage can be changed from 460V to 230V or from 230V to 460V on three-phase, 5 through 30 HP motors by changing voltage plugs.

Voltage plugs are clearly and permanently marked as 230V or 460V. Each plug is usable on all 5 through 30 HP motors.

Voltage Plug Order Numbers:PLUG-230VPLUG-460V

5 – 30 HP (3.7kW – 22kW), 3Ø

STANDARD SPECIFICATIONSCable Connection : Plug-In Type Water EnvironmentCable Length : 150 inch (3.8 m) Flow Rate : 0.5 ft./sec. minimum

Shaft : NEMA Splined pH Level : 6.5 – 8

Flange : NEMA Standard Maximum Temperature : 95º F (35º C)Speed : 2P 3600/3000 RPM (60/50 Hz) Service Factor 1.15 : at 230, 460V/60Hz

1.00 : at 208, 380V/60 Hz and 380, 400, 415V/50 Hz

6" CANNED DESIGN

Page 43: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

PAGE 7

Commercial, Irrigation and Agricultural WaterCentriPro

8-10" REWINDABLE WATER-TIGHT MOTORS

2 POLE 3600/3000 RPM

➀ 8-10" motors do not have a factory installed ground lead.

*See dimensional data for correct variations.

40-200 HP (30 kW - 150 kW) 3Ø2P 3,600/3,000 RPM (60/50 Hz)

DESCRIPTION OF WATER TIGHT INSULATION WIRE

The reliability of submersible motors depends on their insulation characteristics. CentriPro 8-10” motors are the result of years of con-tinuous research and development. Our re-windable water-tight motors feature excellent insulation characteristics thanks to their new patented, water-tight, insulated magnet wire.

The insulation material is a specially developed denatured polypropylene applied over a spe-cial enamel layer. An external nylon sheath is applied over this polypropylene layer for extra mechanical protection. These three barriers are applied to copper conductors for complete insulation from the motor’s cooling fluid. This insures that CentriPro motors will have an ex-tremely long service life.

STANDARD SPECIFICATIONS

Cable Connection Direct to StatorCable Length 200 inch (5 m)

Shaft 2P Splined 40-150 HP (30-110 kW) Keyed 200 HP (150 kW)Flange NEMA Standard

Speed 60 Hz 2P 3600 RPM 50 Hz 2P 3000 RPM

Water EnvironmentMinimum Flow Rate 0.5 ft./sec. (0.15 m/sec.)pH Level 6.5 – 8Maximum Temperature 77º F (25º C)

Service Factor Service Factor 1.15 1.0 Motor 40-200 HP 460V / 60 Hz 380, 400, 2P 415V / 50 Hz

Daniel
Line
Page 44: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

FEATURESSINGLE PHASE:

Single Phase, 6” motors available in 5 – 15 HP, 230 volt models.

Require CentriPro Control Boxes as shown on Order Number chart.

THREE PHASE:

Three Phase, 6”, 5 – 30 HP, 230 and 460 volt models have an exclusive voltage change plug feature. Stock one model and a different voltage plug to reduce inventory cost.

Change Plug Order Numbers are:

• PLUG-230V • PLUG-460V

6 – 10” Three Phase available from 5 – 200 HP, see charts for available voltages.

NOTE: See color brochure (BRCP6SM) for more information and cutaway views.

6" Single Phase Motors 6-10" Three Phase Motors

TECHNICAL BROCHUREBCP6-10MTR R2

NSF/ANSI STANDARD 61Drinking Water System Components - Health EffectsNSF®

Page 45: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

PAGE 2

Commercial, Irrigation and Agricultural WaterCentriPro

6-10" THREE PHASE MOTORS Motor

HP kW Volts Phase Motor Dia. S.F.

Rated Input Service Factor L.R. Order No. vs Flange Dia. Amps Watts Amps Watts Amps 6M058 5 3.7 200 17.5 4910 19.5 5610 124

6M052 5 3.7 230 15.0 4857 17.0 5520 110

6M054 5 3.7 460 7.5 4857 8.5 5520 55

6M078 7.5 5.5 200 25.4 7180 28.5 8230 158

6M072 7.5 5.5 230 22.0 7127 26.0 8140 144

6M074 7.5 5.5 460 11.0 7127 13.0 8140 72

6M108 10 7.5 200 33.3 9360 37.2 10700 236

6M102 10 7.5 230 29.0 9407 33.0 10730 208

6M104 10 7.5 460 14.5 9407 16.5 10730 104

6M158 15 11 200 47.4 13700 53.5 15710 347

6M152 15 11 230 3 6" x 6" 1.15 42.0 13700 46.0 15800 320

6M154 15 11 460 21.0 13700 23.0 15800 160

6M208 20 15 200 61.2 18040 69.5 20820 431

6M202 20 15 230 54.0 17930 60.0 20650 392

6M204 20 15 460 27.0 17930 30.0 20650 196

6M258 25 18.5 200 77.3 22740 87.5 26190 578

6M252 25 18.5 230 68.0 22470 76.0 25800 530

6M254 25 18.5 460 34.0 22470 37.0 25800 265

6M308 30 22 200 91.8 27000 104.0 31120 674

6M302 30 22 230 82.0 27130 94.0 31160 610

6M304 30 22 460 41.0 27130 47.0 31160 305

6M404 40 30 460 6" x 6"

53.0 35530 60.0 41100 340

66M504 50 37 460 70.0 45210 79.0 52380 465

86M504 50 37 460 8" x 6"

66.1 44501 74.1 50891 518

86M604 60 45 460 76.8 51866 86.8 59576 562

8M754 75 55 460 3 1.15 96.0 65900 109.0 76100 650

8M1004 100 75 460 8" x 8"

127.0 87600 145.0 101300 795

8M1254 125 90 460 160.0 110800 180.0 126000 980

8M1504 150 110 460 195.0 130700 220.0 152000 1060

10M2004 200 150 460 10 "x 10" 235.0 171100 270.0 198600 1260

5-30 HP, 3 Phase 230 and 460 Motors have adjustable voltage feature, change voltage plugs to convert from 230V to 460V operation. Spare Change Plug Order No's are: PLUG-230V or PLUG-460V.

6" SINGLE PHASE MOTORS AND REQUIRED CONTROL BOXES Motor

HP kW Volts Phase Motor Dia. S.F.

Rated Input Service Factor L.R. Control Box Order No. vs Flange Dia. Amps Watts Amps Watts Amps Order No.➀

6M051 5 3.7 24 4987 27.5 5735 124 CB05MC3R

6M071 7.5 5.5 230 1 6” x 6” 1.15

36 7675 41 8950 167 CB07MC3R

6M101 10 7.5 50 10135 58 11830 202 CB10MC3R

6M151 15 11 72 15180 85 18050 275 CB15MC3R➀ NEMA 3R control boxes will be replacing the current models.

Daniel
Line
Daniel
Typewritten Text
Zolezzi -Will be provided with a 150 HP Motor model # 8M1504 Aarow Creek- Will be provided with a 100 HP Motor model # 8M1004 Cooper Cloud- Will be provided with a 100 HP Motor model # 8M1004
Daniel
Rectangle
Daniel
Line
Daniel
Line
Page 46: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

PAGE 3

Commercial, Irrigation and Agricultural WaterCentriPro

6" SINGLE PHASE MOTORS

Motor HP kW Volts Phase

F.L. KVA Resistance - Ohms Order No. Efficiency % Code R - Y B - Y R - B 6M051 5 3.7 74.8 G 2.172 0.512 2.627

6M071 7.5 5.5 230 1

72.9 F 1.401 0.400 1.774

6M101 10 7.5 73.6 E 1.052 0.316 1.310

6M151 15 11 73.7 D 0.678 0.230 0.850

6-10" THREE PHASE MOTORS

Motor HP kW Volts Phase

F.L. KVA Line - Line Time Delay Fuse Order No. Efficiency % Code Resistance Standard Dual Element 6M058 5 3.7 200 75.9 K 0.618 50 25

6M052 5 3.7 230 76.8 K 0.806 45 20

6M054 5 3.7 460 76.8 K 3.050 25 10

6M078 7.5 5.5 200 77.9 J 0.504 80 40

6M072 7.5 5.5 230 78.5 J 0.651 70 30

6M074 7.5 5.5 460 78.5 J 2.430 35 15

6M108 10 7.5 200 79.7 K 0.315 100 50

6M102 10 7.5 230 79.3 K 0.448 90 40

6M104 10 7.5 460 79.3 K 1.619 45 20

6M158 15 11 200 81.7 K 0.213 175 70

6M152 15 11 230 81.7 K 0.312 150 60

6M154 15 11 460 81.7 K 1.074 70 30

6M208 20 15 200 82.7 J 0.189 200 90

6M202 20 15 230 83.2 J 0.258 175 70

6M204 20 15 460 3

83.2 J 0.861 90 35

6M258 25 18.5 200 82.0 K 0.146 250 110

6M252 25 18.5 230 83.0 K 0.210 225 90

6M254 25 18.5 460 83.0 K 0.666 110 45

6M308 30 22 200 82.9 J 0.119 300 125

6M302 30 22 230 82.5 K 0.166 250 100

6M304 30 22 460 82.5 K 0.554 125 50

6M404 40 30 460 84.0 H 0.446 175 70

66M504 50 37 460 82.5 J 0.388 225 90

86M504 50 37 460 83.8 K 0.331 225 125

86M604 60 45 460 86.3 J 0.278 250 150

8M754 75 55 460 84.9 H 0.218 300 125

8M1004 100 75 460 85.2 H 0.164 400 175

8M1254 125 90 460 84.2 G 0.132 500 225

8M1504 150 110 460 85.6 G 0.115 600 250

10M2004 200 150 460 87.2 F 0.0929 800 350

Daniel
Line
Daniel
Line
Daniel
Line
Page 47: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

PAGE 4

Commercial, Irrigation and Agricultural WaterCentriPro

GENERAL FEATURES OF CANNED AND REWINDABLE WATER-TIGHT MOTORS

6" AND 8"X6" CANNED DESIGN MOTOR FEATURES

• Replaceable Plug-in Motor Lead – All 6” motor leads are stranded copper for flexibility and strength. Leads are 150” long and field replaceable.

• Insulation – The canned motor’s stator coil is mounted in a stainless steel frame and is completely sealed in a stainless steel cylinder. The coil wire features moisture resistant insulation which is completely water-proofed for long life.

• Heat Resistant – The space between the stator's stainless steel protective can and its frame is filled with a spe-cially formulated patented resin that protects the motor against thermal fluctuation and internal stress.

8-10" REWINDABLE WATER-TIGHT MOTOR FEATURES

• Insulation Wire – The coil conductor insulation mate-rial is a specially developed denatured polypropylene, which offers excellent leak-resistant characteristics. Three barriers are applied to the copper conductors to provide complete insulation against the motor’s cooling fluid. This design is the result of extensive research and is of superior quality. It insures that CentriPro motors will have an extremely long service life.

MOTOR FEATURES - BOTH DESIGNS

• Sand Resistant Slinger and Lip Seals – CentriPro sub-mersible motors feature double-row, grease packed, lip seals to prevent sand from entering the motor. A carbon steel slinger with a baked on epoxy coating prevents sand from entering the lip seal area. Additional

protection against sand intrusion is provided by the close tolerance slinger guide with a .02” fit. This design is field-proven in West Texas wells which are considered to be some of the worst sandy well applications. Best of all, these features are standard for a CentriPro motor, so there is no need to stock one motor for clean wells and another more expensive motor for the more abrasive, sandy jobs.

• High Torque Characteristics – The stator laminations are constructed of high quality, electrical grade, silicon steel which provide high torque even when the motor is subjected to nominal voltage variations.

• Balancing – The rotor balance rings (one on each end of the rotor) allow for excellent dynamic balance for the rotating element of the motor.

• Carbon Sleeve Bearings – Two carbon, water-lubricated, guide bearings are used to properly align the shaft. The bearings have a large surface area to better support the shaft, reducing whipping, while acting as a steady bushing.

• Water-Filled Design – The internal cooling water is mixed with antifreeze and antirust liquid to allow the motor to be stored at –22º F (–30º C). Two water plugs are provided for filling or draining the anti-freeze fluid during maintenance. These plugs are also used to top off and to check the water level.

• Complete Corrosion and Water-Tight Protection – All main motor components are made of stainless steel: including the can housing (water tight type motors have baked epoxy coated carbon steel housings), shaft and bolts. All other motor parts are finished with the baked epoxy coating.

• Baked Epoxy Coating – All external and internal cast iron parts are coated with a baked epoxy resin that provides excellent resistance to water and corrosion.

• Quality Control – All CentriPro submersible motors are manufactured and tested under the most stringent qual-ity control procedures, providing long service life and trouble-free operation.

CONSTRUCTION AND INSULATION DETAILS

TYPE 6" and 8"x6" CANNED DESIGN 8-10" REWINDABLE WATER-TIGHT DESIGN

Construction

Slot Insulation

Maximum Water Temperature 6, 8 & 10" Motors

Size HP Temperature Range

Minimum Flow Rate Ph Range

6" 5 - 40 95º F (35º C) .5 Ft/sec. 6.5 - 8.0

8x6" 50 - 60 77º F (25º C) .5 Ft/sec. 6.5 - 8.0

8" 75 - 150 77º F (25º C) .5 Ft/sec. 6.5 - 8.0

10" 200 77º F (25º C) .5 Ft/sec. 6.5 - 8.0

Daniel
Line
Page 48: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

PAGE 5

Commercial, Irrigation and Agricultural WaterCentriPro

SPECIAL TECHNOLOGYHIGH PERFORMANCE THRUST BEARING

APPLICATION

Motor Output Bearing Number Size HP kW Type of Shoes 6" 5 – 30 3.7 – 22 A 3 6" 40 – 50 30 – 45 B 6 8 – 10" 40 – 150 30 – 110 C 6 10" 200 150 C 8

The field proven KINGSBURY design thrust bearing creates a wedge of water between the pivot shoe and carbon disc. Our innovative design permits high thrust loads to be placed on the bearings while showing no measurable wear after several years of severe duty operation. This allows for long pumping life, virtual trouble free operation and low maintenance. For all 6" motors, the 300 lbs. maximum continuous up thrust is absorbed between the upper carbon sleeve bearing and the rotor balance ring. For all 8" – 10" motors, the 1000 lbs. maximum continuous up thrust is carried between the upper slide plate and the separate up thrust carbon bearing.

Number Part Name 1 Pivot Shoe

2 Bearing Frame

3 Carbon Disc

4 Metal Support

5 Metal Frame

6 Thrust Plate

7 Slide Plate

8 Up Thrust Bearing

Motor

2P

Size Down Thrust Up Thrust

lbs. kg lbs. kg

6" 3,500 1,590 300 136 5-30 HP *(450) *(200)

6" 5,000 2,270 300 136 40-50 HP *(450) *(200)

8x6" 6,000 2,721 300 136 50-60 HP *(450) *(200)

10,000 4,540 1,000 450 8" ** ** ** ** (5,000) (2,270) (1,500) (680)

10" 10,000 4,540 1,000 450

Note:1. Thrust ratings showed are continuous except for values marked *.2. * Momentary rating (3 minutes maximum).3. ** 8" motor - 6" Flange when using standard stainless steel bolts

(B&M), has a thrust value of 5,000 lbs. A thrust value of 10,000 lbs. can be obtained by using high tensile stainless steel bolts (ASTM F593G).

Daniel
Line
Daniel
Line
Page 49: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

PAGE 8

Commercial, Irrigation and Agricultural WaterCentriPro

REWINDABLE WATER-TIGHT DESIGN MOTORS

SIZE AND WEIGHT - 2 POLE 3600 RPM 60 Hz — 3000 RPM 50 Hz

Motor Output D L Net Weight Size HP kW inch (mm) inch mm lbs. kg 75 55 53.15 1350 463 210

8" 100 75 7.52 58.27 1480 518 235

125 90 (191) 66.14 1680 595 270 150 110 70.08 1780 661 300

10" 200 150 8.52 (216.5) 69.68 1770 816 370

(*) 6 inch flange. **Gross Weight: See page 12.

CABLE SIZE AND TYPE - 2 POLE 3600 RPM 60 Hz — 3000 RPM 50 Hz

200 inch (5 m) – Lead Wire Standard Length (Round 1 Stranded Conductor)

Output 460V, 415V, 400V, 380V Motor Size HP kW Lead Wire Size Cable Diameter mm2 AWG inch mm

75 30-55 8 #8 0.362 9.2

8" 100-125 75-90 14 #6 0.433 11.0

150 110 22 #4 0.531 13.5

10" 200 150 30 #2 0.591 15.0

Type of Lead Wire – 600V ClassEthylene Propylene rubber insulated chloroprene cabtyre cable.

L

D

Daniel
Rectangle
Daniel
Rectangle
Daniel
Line
Daniel
Line
Daniel
Rectangle
Daniel
Rectangle
Daniel
Line
Daniel
Line
Page 50: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

PAGE 10

Commercial, Irrigation and Agricultural WaterCentriPro

DIMENSIONAL DATA

8", 3600 RPM, 2 POLE (6" FLANGE) 8", 3600 RPM, 2 POLE (8" FLANGE)

SizeOutput

PhaseC L

HP kW inch mm inch mm

8"x8"

50 37

3

48.15 1223 45.28 115060 45 50.91 1293 48.03 122075 55 57.13 1451 53.15 1350

100 75 62.24 1581 58.27 1480125 90 70.12 1781 66.14 1680150 110 74.06 1881 70.08 1780

8"x6"50 37

44.48 1130 41.61 105760 45

Daniel
Line
Daniel
Line
Daniel
Line
Page 51: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

C.H. Spencer & Company 95 Isidor Court Sparks, Nevada 775-825-8882

PUMPS/ CANS & ACCESSORIES

Page 52: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied
Page 53: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

C.H. Spencer & Company 95 Isidor Court Sparks, Nevada 775-825-8882

THE FOLLOWING ACCESSORIES WILL BE PROVIDED Spare Parts: -Each Model of Pump will be provided with one set of bearings and all gaskets/O-Rings. Pump Can Testing: Each Pump can will be hydrostatically tested, test results will be supplied prior to shipment to the design engineer. Pump Bowl Assembly Each Bowl Assembly will have a N/W Factory Performance Test Supplied, pumps will not ship from the manufactures facility without engineers prior approval.

Page 54: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

C.H. Spencer & Company 95 Isidor Court Sparks, Nevada 775-825-8882

WARRANTY

Page 55: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

Terms & Conditions General Provisions

Page 2 of 2

WARRANTY - Company warrants title to the product(s) and, except as noted with respect to items not of Company’s manufacturer, also warrants the product(s) on date of shipment to Purchaser, to be of the kind and quality described herein, and free of defects in workmanship and material. THIS WARRANTY IS EXPRESSLY IN LIEU OF ALL OTHER WARRANTIES, INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS, AND CONSTITUTES THE ONLY WARRANTY OF COMPANY WITH RESPECT TO THE PRODUCT(S). If within one year from date of initial operation, but not more than eighteen months from date of shipment by Company of any item of product(s), Purchaser discovers that such item was not as warranted above and promptly notifies Company in writing thereof, Company shall remedy such nonconformance by, at Company’s option, adjustment or repair or replacement of the item and any affected part of the product(s). Purchaser shall assume all responsibility and expense for removal, reinstallation, and freight in connection with the foregoing remedies. The same obligations and conditions shall extend to replacement parts furnished by Company hereunder. Company shall have the right of disposal of parts replaced by it. Purchaser agrees to notify Company, in writing, of any apparent defects in design, material or workmanship, prior to performing any corrective action back chargeable to the Company. Purchaser shall provide a detailed estimate of the material, labor costs associated with proposed remedy for expeditious review and approval by the Company. ANY SEPARATELY LISTED ITEM OF THE PRODUCT(S) WHICH IS NOT MANUFACTURED BY THE COMPANY IS NOT WARRANTED BY COMPANY and shall be covered only by the express warranty, if any, of the manufacturer thereof. THIS STATES PURCHASER’S EXCLUSIVE REMEDY AGAINST COMPANY AND ITS SUPPLIERS RELATING TO THE PRODUCT(S) WHETHER IN CONTRACT OR IN TORT OR UNDER ANY OTHER LEGAL THEORY, AND WHETHER ARISING OUT OF WARRANTIES, REPRESENTATIONS, INSTRUCTIONS, INSTALLATIONS OR DEFECTS FROM ANY CAUSE. Company and its suppliers shall have no obligation as to any product which has been improperly stored or handled, or which has not been operated or maintained according to instructions in Company or supplier furnished manuals. PATENTS - Company shall pay costs and damages finally awarded in any suit against Purchaser or its vendees to the extent based upon a finding that the design or construction of the product(s) as furnished infringes a United States patent (except infringement occurring as a result of incorporating a design or modification at Purchaser’s request) provided that Purchaser promptly notifies Company of any change of such infringement, and Company is given the right at its expense to settle such charge and to defend or control the defense of any suit based upon such charge. THIS PARAGRAPH SETS FORTH COMPANY’S EXCLUSIVE LIABILITY WITH RESPECT TO PATENTS. BUYER DATA - Timely performance is contingent upon the Purchaser supplying to the Company, when needed, all required technical information, including drawing approval, and all required commercial documentation. NUCLEAR - Purchaser represents and warrants that the product(s) covered by this contract shall not be used in or in connection with a nuclear facility or application. NONCANCELLATION - Purchaser may not cancel or terminate for convenience, or direct suspension of manufacture, except on mutually acceptable terms. DELAYS - If Company suffers delay in performance due to any cause beyond its control, including but not limited to act of God, war, act or failure to act of government, act or omission of Purchaser, fire flood, strike or labor troubles, sabotage, or delay in obtaining from others suitable services, materials, components, equipment or transportation, the time of performance shall be extended a period of time equal to the period of the delay and its consequences. Company will give to Purchaser notice in writing within a reasonable time after Company becomes aware of any such delay. STORAGE - Any item of the product(s) on which manufacture or shipment is delayed by causes within Purchaser’s control, or by causes which affect Purchaser’s ability to receive the product(s), may be placed in storage by Company for Purchaser’s account and risk. SHIPMENT - The term “shipment” means delivery to the initial carrier in accordance with the delivery terms of this order. Company may make partial shipments. Company shall select method of transportation and route, unless terms are f.o.b. point of shipment and Purchaser specifies the method and route and is to pay the freight costs in addition to the price. When terms are f.o.b. destination or freight allowed to destination, “destination” means common carrier delivery point (within the continental United States, excluding Alaska) nearest the destination. For movement outside the United States, Company shall arrange for inland carriage to port of exit and shall cooperate with Purchaser’s agents in making necessary arrangements for overseas carriage and preparing necessary documents. SPECIAL SHIPPING DEVICES - On shipments to a destination in the continental United States or Canada, Company has the right to add to the invoice, as a separate item, the value of any special shipping device (barrel, reel, tarpaulin, cradle, crib and the like) used to contain or protect the product(s) invoiced, while in transit. Full credit will be given on the return to Company of the device in a reusable condition, f.o.b. destination, freight prepaid. TITLE AND INSURANCE - Title to the product(s) and risk of loss or damage shall pass to Purchaser at the f.o.b. point, except that a security interest in the product(s) and proceeds and any replacement shall remain in Company, regardless of mode of attachment to realty or other property, until the full price has been paid in cash. Purchaser agrees to do all acts necessary to perfect and maintain said security interest, and to protect Company's interest by adequately insuring the product(s) against loss or damage from any external cause with Company named as insured or co-insured. TERMS OF PAYMENT - Unless otherwise stated all payments shall be Net Thirty (30) Days and in United States dollars, and a pro rata payment shall become due as each shipment is

made. If shipment is delayed by Purchaser, date of readiness for shipment shall be deemed to be date of shipment for payment purposes. If at any time in Company’s judgment Purchaser may be or may become unable or unwilling to meet the terms specified, Company may require satisfactory assurances or full or partial payment as a condition to commencing or continuing manufacture or making shipment; and may, if shipment has been made, recover the product(s) from the carrier, pending receipt of such assurances. TAXES - Any applicable duties or sales, use, excise, value added or similar taxes will be added to the price and invoiced separately (unless acceptable exemption certificate is furnished). LIMITATION OF LIABILITY - Neither Company nor its suppliers shall be liable, whether in contract or in tort or under any other legal theory, for loss of use, revenue or profit, or for cost of capital or of substitute use or performance, or for incidental, indirect, or special or consequential damages, or for any other loss or cost of similar type, or for claims by Purchaser for damages of Purchaser’s customers. Likewise, Company shall not, under any circumstances, be liable for the fault, negligence, or wrongful acts of Purchaser or Purchaser’s employees, or Purchaser’s other contractors of suppliers. IN NO EVENT SHALL COMPANY BE LIABLE IN EXCESS OF THE SALES PRICE OF THE PART(S) OR PRODUCT FOUND DEFECTIVE. GENERAL - (a) Company will comply with all laws applicable to Company. Compliance with OSHA or similar federal, state or local laws during any operation or use of the product(s) is the sole responsibility of Purchaser. (b) The laws of the State of New York shall govern the validity, interpretation and enforcement of any contract of which these provisions are a part, without giving effect to any rules governing the conflict of laws. (c) This document and any other documents specifically referred to as being a part hereof, constitute the entire contract on the subject matter, and it shall not be modified except in writing signed by both parties. Unless otherwise specified, any reference to Purchaser’s order is for identification only. Assignment may be made only with written consent of both parties. ACCEPTANCE - The determination of compliance with performance guarantees will be based on results of factory tests under controlled conditions with calibrated instruments and tested per standards of the Hydraulic Institute. INSPECTIONS/EXPEDITING - The Company wishes to clarify that it will have to restrict access to agreed upon reasonable times and only for the purpose of conducting those inspections agreed upon. We request 72 hours notice prior to each visit. We request notification prior to visits to our subcontractors. PRICES - The prices stated herein will remain firm for the period up to the stated date of shipment providing the shipment is not delayed by the customer. If shipment is delayed by the customer beyond the shipment date quoted herein, the prices will be based on the prices in effect at time of shipment, including storage and material handling costs. In no event shall the adjusted price be less than the original order price, including change orders. Prices are F.O.B. Shipping Point, unless otherwise specified. When price includes transportation and other charges pertaining to the shipment of goods, any increase in transportation rates and other charges will be for the account of the Purchaser. There will be an extra charge for any test other than that which may be normally run by the Company, or for any test performed to suit the convenience of the Purchaser. CONTROLLING PROVISIONS - These terms and conditions shall control with respect to any purchase order or sale of the Company’s products. No waiver, alteration or modification of these terms and conditions whether on Purchaser’s purchase order or otherwise shall be valid unless the waiver, alteration or modification is specifically accepted in writing and signed by an authorized representative of the Company. If this transaction involves EXPORT, the following additional terms and conditions shall apply: PACKING - Equipment will be packed, boxed or crated in accordance with the Company’s standard commercial practice, for underdeck export shipment, unless otherwise agreed. LETTER OF CREDIT - Unless otherwise specified in writing, payment shall be made by irrevocable letter of credit in form acceptable to Company, confirmed by a major USA bank, acceptable to the Company and providing for payment in full in United States dollars against presentation of United States inland shipping documents and invoices, such letter of credit to be established prior to Company’s acceptance of the order. The letter of credit shall also provide that in the event Company is, for any reason beyond its control, prevented from making shipment from Company’s factory or delivery at the port of embarkation, a certificate of manufacture of the whole or any part of the goods shall constitute delivery of such whole or any part of the goods and payment in full of any and all drafts drawn against the letter of credit for the goods so “delivered” shall be made upon presentation of such certificates of manufacture in lieu of United States inland shipping documents. In the event that Company is prevented by law, or otherwise, from making shipment from Company’s factory or delivery at port of embarkation of the goods or any part thereof, on completion of manufacture, Company reserves the right to place the goods in storage for the Purchaser’s account and risk. Any charges incurred in this connection will be for the account of the Purchaser at cost and will be payable upon demand. COMPANY AS AGENT - If Company makes or arranges for ocean shipment, Company shall act as agent for the Purchaser and reserves the right to procure full insurance coverage, including war risk insurance, at the expense of the Purchaser. All expenses incurred in this connection will be payable upon demand to the Company. If Company as agent applies for or secures manufacturing, financing, exporting or other licenses required by the United States Government, or any department thereof, Company shall make such applications or secure such licenses solely as agent for the Purchaser, and assumes no responsibility therefore

Page 56: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

Submittal Review FormProject Name: TMWA ArrowCreek Drought Response Design Proj

Routing Sequence Date Received

Checked By Date Sent

Contract No: 205300179

Spec. No: 11300, 11302

Submittal No: 1-R1

Contractor/Subcontractor

CH Spencer

Submittal Title: Booster Pump Submittal Package

Bid Item No.:

Orig. Mfg.Lit.SamplesPrints

Number of Copies

cc: File, Ray

Resubmittal Received

We have verified that the material or equipment contained in this submittal meets all the requirements specified or shown (no exceptions).

We have verified that the material or equipment contained in this submittal meets all the requirements specified or shown, except for the following deviations (list deviations, attach separate sheet if necessary)

Submittal StatusSubmittal Compliance

A - NO EXCEPTION NOTED (Confirm)

B - NOTE MARKINGS (Confirm)

C - NOTE MARKINGS (Resubmit)

D - REJECTED (Resubmit)

Engineer Remarks

1. Pump Discharge to the control valve will be tested to 400 PSI, please make sure the pump pitless can will handle this pressure.

Contractor Remarks

GC Representative: Danny Beck Designer: David Diegle

CH Spencer 8/7/2015 Danny Beck 8/7/2015

TMWA 8/7/2015 Scott Estes 8/7/2015

8/7/2015 David Diegle 8/7/2015

TMWA

CH Spencer

8/7/2015 Scott Estes

Stantec Consulting Ltd.

E - UNREVIEWED / INFORMATION ON

Stantec Consulting Services Inc. Stantec Consulting Services Inc.©

Page 57: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

Page 1 of 3

C.H. Spencer & Company 1075 South Pioneer Road Salt Lake City, UT 84104 Phone: 801-975-0300 x.110 Fax: 801-972-5216

To: Truckee Meadows Water Authority Attn: Scott Estes Date: August 7, 2015 Reference: TMWA Project No. 2016-001 Bid Date: July 23, 2015

Scott:

Please see attached Submittal Package B for the Booster Pump on the TMWA Pumps, Motors and Pitless Adapters for Arrowcreek Drought Response Project

ENGINEERS COMMENTS:

1) Pump Bowls were quoted with and will be supplied with coating per Section 2.2A2) Pumps will be provided with SS Suction Screens3) Motors will be provided with standard cable length, there should be roughly an additional 3-4 spare ft at the top of the adapter.4) Pump Bowls were quoted with and will be supplied with coating per 2.2A.5) Revised drawing attached showing 24” dimensions.6) Revised drawing attached showing 150 lb suction flange.7) Revised drawing showing testing that will be performed at the factory per Section 11032 3.1:A.8) Pump Can will be coated per Section 11032 1.1:B, see attached data sheet and drawing.

Let me know if you have any questions.

Thanks Daniel Beck C.H. Spencer Sales Engineer

Page 58: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied
Page 59: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

RustNotHEAVY INDUSTRIALCOATING PROTECTION

Excellent Chemical Resistance to a Broad Range of Chemicals

RUSTNOT™ TankLine™ 253i PW

Page 60: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

- RustNot™ TankLine™ 253i PW

PRODUCT DESCRIPTION

HD5120-01 White HD5120-02 Beige HD5125 Hardener

A two-component, high solids epoxy phenolic novolac system formulated as an internal tank lining for potable water applications and as a coating for resistance to a wide range of chemicals and solvents. Offers excellent adhesion and corrosion resistance. VOC compliant (less than 190 g/L). Also suitable for secondary containment uses and for highly corrosive applications.

FEATURES

• High solids, low VOC • Excellent adhesion to metal and concrete • Excellent corrosion resistance • Excellent solvent resistance

RECOMMENDED USES

• Internal lining for chemical tanks, petroleum tanks and drill-ing water tanks

• Potable water tank lining • Marine • Secondary containment

PRODUCT DATA

Description ResultsVehicle Type ........................................Epoxy / Phenolic Novolac Color .....................................................White and BeigeVOC (mixed w/HD5125) .......................<230 g/L (1.89 lbs/gal) Weight/Gallon .......................................12.14 pounds Solids by Volume (mixed) .....................77+/-2% Packaging .............................................5 Gallon Kits

APPLICATION DATA

Description ResultsApplication ............................................Spray, Brush or RollMix Ratio ..............................................1 unit of Part B to 5gl pail

of Part A.

Hardener ..............................................HD5125 Recommended Thickness ....................6-8 mils/coat (dry) 8-10 mils/coat (wet) Number of Coats ...................................1 or 2 (Use a stripe coat

on difficult to paint areas, such as welds, pits, edges, cutouts, brackets, etc.)

Theoretical Coverage ............................1,235 sf/gal at 1 mil DFT Pot Life @ 77°F ....................................6 hours

Cure to Immersion Service 77°F and 50% R.H. ...............................14 days Dry Time @

77°F and 50% R.H. Touch Dry ........................................4 hoursRecoat .............................................10 hours Max. Recoat ....................................5 days

Mixing ....................................................Power stir the base and hardener, then add hardener to the base and stir 5 - 10 minutes.

Induction Time.......................................15 minutes

The above product and application data for this technical data sheet are based on product HD5120-01 White.

EQUIPMENT RECOMMENDATIONS

Listed below are general equipment guidelines for the application of this product. Job site conditions may require modifications to these guidelines to achieve the desired results. Ensure brush and roller is well loaded to avoid air entrapment. Multiple coats may be needed to achieve adequate film build.

BRUSH: Use a good quality solvent resistant, natural or synthetic.

ROLLER: Use a good quality natural or synthetic 3/8” short-nap roller cover with phenolic core.

Page 61: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

- RustNot™ TankLine™ 253i PW

SPRAY APPLICATION (General): The following spray equipment has been found suitable and is available from manufacturers such as Binks, DeVilbiss and Graco.

AIR ATOMIZED SPRAY:Model Air Cap Fluid Head Fluid Delivery Atomizing

PressureBinks 18 68 PB 68 20 oz/min 65 - 75 psiDeVilbiss MBC-510

MB-4039-62HD AV-650-AC 20 oz/min 65 - 75 psi

AIRLESS SPRAY:Model Pump Ratio Fluid Tip Fluid Pressure Filter MeshGraco 30:1 or Larger 0.018 - 0.020 1,800 - 2,400 60 mesh

GENERAL SURFACE PREPARATION

All surfaces must be sound, dry, clean and free of oil, dirt, grease, wax, mildew, loose or flaking paint and other surface contaminants.

Remove loose, peeling, flaking or scaling paint by scraping, sanding or wire brush.

Area should be sheltered from airborne particulates and pollutants. Avoid combustion gases or other sources of carbon dioxide that may promote amine blush. Ensure good ventilation during application and curing. Provide shelter to prevent wind from affecting spray patterns. For tank lining, dehumidification equipment is recommended.

Surface temperature must remain at least 5°F above dew point temperature.

For good results, an SSPC-SP 5 (NACE No. 1) white metal blast or SSPC-SP 10 (NACE No. 2) near-white metal blast is recommended. For moderate exposure (non-immersion), an SSPC-SP 6 (NACE No. 3) commercial blast should be used.

DIRECTIONS FOR USE

TINTING: Do not tint.

THINNING:• Brush or Roll - None needed • Spray - Not recommended

Note: Always know local VOC restrictions for coatings applications in your area before thinning this product. Thinning recommendations meet Federal VOC restrictions for architectural coatings. This product and other referenced products may not meet VOC restrictions for your application and may not be available in your area. Carefully read and observe warning thinner labels.

Page 62: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

- RustNot™ TankLine™ 253i PW

JONES-BLAIR®/NEOGARD®

APPLICATION: Apply by spray, brush or roller. APPLY ONLY when air and surface temperatures are between 50 - 122°F and the surface temperature is at least 5°F above the dew point temperature.

DRYING TIME: Under normal conditions, dries to touch in 4 hours and to recoat in 8 hours. Low temperature, high humidity, poor ventilation and thick films will retard drying.

CLEAN UP: Clean up skin, clothing, paint tools or spills immediately with recommended thinner, carefully observing cautions on paint and thinner labels. Dried paint may be removed by scraping. Clean Up with 21064 or 21092 Thinner, MEK or Xylene

HEALTH AND SAFETY

Read the Material Safety Data Sheet (MSDS) and container labels for detailed health and safety information. This product is intended for industrial use by properly trained professional applicators only.

DISCLAIMERManufacturer warrants that the physical properties of the product reported above will meet the standards and deviations of the associated ASTM test method. MANUFACTURER HEREBY EXPRESSLY DISCLAIMS ANY AND ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING, WITHOUT LIMITATION, ANY IMPLIED WARRANTY OF MERCHANTABILITY AND/OR IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. Buyer must make its own determination of the suitability of any product for its use, whether such product is used alone or in combination with other materials. To the extent this or any of Manufacturer’s products is proven to be defective, Buyer’s sole remedy shall be limited to the replacement of such defective product, exclusive of any costs of labor. MANUFACTURER SHALL NOT BE LIABLE OR OBLIGATED FOR ANY LOSS OR CONSEQUENTIAL OR OTHER DAMAGE INCURRED DIRECTLY OR INDIRECTLY BY BUYER OR ANY OTHER PERSON OR ENTITY THAT ARISES IN ANY WAY IN RELATION TO THIS OR ANY OF MANUFACTURER’S OTHER PRODUCTS. Nothing contained herein shall be construed to constitute inducement or recom-mendation to practice any invention covered by any patent without authority of the owner of the patent. No Applicator is or should be viewed as an employee or agent of Manufacturer.

Robert Claybaker832-349-5172 Cellwww.jones-blair.com/rustnot

Page 63: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

Terms & Conditions General Provisions

Page 2 of 2

WARRANTY - Company warrants title to the product(s) and, except as noted with respect to items not of Company’s manufacturer, also warrants the product(s) on date of shipment to Purchaser, to be of the kind and quality described herein, and free of defects in workmanship and material. THIS WARRANTY IS EXPRESSLY IN LIEU OF ALL OTHER WARRANTIES, INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS, AND CONSTITUTES THE ONLY WARRANTY OF COMPANY WITH RESPECT TO THE PRODUCT(S). If within one year from date of initial operation, but not more than eighteen months from date of shipment by Company of any item of product(s), Purchaser discovers that such item was not as warranted above and promptly notifies Company in writing thereof, Company shall remedy such nonconformance by, at Company’s option, adjustment or repair or replacement of the item and any affected part of the product(s). Purchaser shall assume all responsibility and expense for removal, reinstallation, and freight in connection with the foregoing remedies. The same obligations and conditions shall extend to replacement parts furnished by Company hereunder. Company shall have the right of disposal of parts replaced by it. Purchaser agrees to notify Company, in writing, of any apparent defects in design, material or workmanship, prior to performing any corrective action back chargeable to the Company. Purchaser shall provide a detailed estimate of the material, labor costs associated with proposed remedy for expeditious review and approval by the Company. ANY SEPARATELY LISTED ITEM OF THE PRODUCT(S) WHICH IS NOT MANUFACTURED BY THE COMPANY IS NOT WARRANTED BY COMPANY and shall be covered only by the express warranty, if any, of the manufacturer thereof. THIS STATES PURCHASER’S EXCLUSIVE REMEDY AGAINST COMPANY AND ITS SUPPLIERS RELATING TO THE PRODUCT(S) WHETHER IN CONTRACT OR IN TORT OR UNDER ANY OTHER LEGAL THEORY, AND WHETHER ARISING OUT OF WARRANTIES, REPRESENTATIONS, INSTRUCTIONS, INSTALLATIONS OR DEFECTS FROM ANY CAUSE. Company and its suppliers shall have no obligation as to any product which has been improperly stored or handled, or which has not been operated or maintained according to instructions in Company or supplier furnished manuals. PATENTS - Company shall pay costs and damages finally awarded in any suit against Purchaser or its vendees to the extent based upon a finding that the design or construction of the product(s) as furnished infringes a United States patent (except infringement occurring as a result of incorporating a design or modification at Purchaser’s request) provided that Purchaser promptly notifies Company of any change of such infringement, and Company is given the right at its expense to settle such charge and to defend or control the defense of any suit based upon such charge. THIS PARAGRAPH SETS FORTH COMPANY’S EXCLUSIVE LIABILITY WITH RESPECT TO PATENTS. BUYER DATA - Timely performance is contingent upon the Purchaser supplying to the Company, when needed, all required technical information, including drawing approval, and all required commercial documentation. NUCLEAR - Purchaser represents and warrants that the product(s) covered by this contract shall not be used in or in connection with a nuclear facility or application. NONCANCELLATION - Purchaser may not cancel or terminate for convenience, or direct suspension of manufacture, except on mutually acceptable terms. DELAYS - If Company suffers delay in performance due to any cause beyond its control, including but not limited to act of God, war, act or failure to act of government, act or omission of Purchaser, fire flood, strike or labor troubles, sabotage, or delay in obtaining from others suitable services, materials, components, equipment or transportation, the time of performance shall be extended a period of time equal to the period of the delay and its consequences. Company will give to Purchaser notice in writing within a reasonable time after Company becomes aware of any such delay. STORAGE - Any item of the product(s) on which manufacture or shipment is delayed by causes within Purchaser’s control, or by causes which affect Purchaser’s ability to receive the product(s), may be placed in storage by Company for Purchaser’s account and risk. SHIPMENT - The term “shipment” means delivery to the initial carrier in accordance with the delivery terms of this order. Company may make partial shipments. Company shall select method of transportation and route, unless terms are f.o.b. point of shipment and Purchaser specifies the method and route and is to pay the freight costs in addition to the price. When terms are f.o.b. destination or freight allowed to destination, “destination” means common carrier delivery point (within the continental United States, excluding Alaska) nearest the destination. For movement outside the United States, Company shall arrange for inland carriage to port of exit and shall cooperate with Purchaser’s agents in making necessary arrangements for overseas carriage and preparing necessary documents. SPECIAL SHIPPING DEVICES - On shipments to a destination in the continental United States or Canada, Company has the right to add to the invoice, as a separate item, the value of any special shipping device (barrel, reel, tarpaulin, cradle, crib and the like) used to contain or protect the product(s) invoiced, while in transit. Full credit will be given on the return to Company of the device in a reusable condition, f.o.b. destination, freight prepaid. TITLE AND INSURANCE - Title to the product(s) and risk of loss or damage shall pass to Purchaser at the f.o.b. point, except that a security interest in the product(s) and proceeds and any replacement shall remain in Company, regardless of mode of attachment to realty or other property, until the full price has been paid in cash. Purchaser agrees to do all acts necessary to perfect and maintain said security interest, and to protect Company's interest by adequately insuring the product(s) against loss or damage from any external cause with Company named as insured or co-insured. TERMS OF PAYMENT - Unless otherwise stated all payments shall be Net Thirty (30) Days and in United States dollars, and a pro rata payment shall become due as each shipment is

made. If shipment is delayed by Purchaser, date of readiness for shipment shall be deemed to be date of shipment for payment purposes. If at any time in Company’s judgment Purchaser may be or may become unable or unwilling to meet the terms specified, Company may require satisfactory assurances or full or partial payment as a condition to commencing or continuing manufacture or making shipment; and may, if shipment has been made, recover the product(s) from the carrier, pending receipt of such assurances. TAXES - Any applicable duties or sales, use, excise, value added or similar taxes will be added to the price and invoiced separately (unless acceptable exemption certificate is furnished). LIMITATION OF LIABILITY - Neither Company nor its suppliers shall be liable, whether in contract or in tort or under any other legal theory, for loss of use, revenue or profit, or for cost of capital or of substitute use or performance, or for incidental, indirect, or special or consequential damages, or for any other loss or cost of similar type, or for claims by Purchaser for damages of Purchaser’s customers. Likewise, Company shall not, under any circumstances, be liable for the fault, negligence, or wrongful acts of Purchaser or Purchaser’s employees, or Purchaser’s other contractors of suppliers. IN NO EVENT SHALL COMPANY BE LIABLE IN EXCESS OF THE SALES PRICE OF THE PART(S) OR PRODUCT FOUND DEFECTIVE. GENERAL - (a) Company will comply with all laws applicable to Company. Compliance with OSHA or similar federal, state or local laws during any operation or use of the product(s) is the sole responsibility of Purchaser. (b) The laws of the State of New York shall govern the validity, interpretation and enforcement of any contract of which these provisions are a part, without giving effect to any rules governing the conflict of laws. (c) This document and any other documents specifically referred to as being a part hereof, constitute the entire contract on the subject matter, and it shall not be modified except in writing signed by both parties. Unless otherwise specified, any reference to Purchaser’s order is for identification only. Assignment may be made only with written consent of both parties. ACCEPTANCE - The determination of compliance with performance guarantees will be based on results of factory tests under controlled conditions with calibrated instruments and tested per standards of the Hydraulic Institute. INSPECTIONS/EXPEDITING - The Company wishes to clarify that it will have to restrict access to agreed upon reasonable times and only for the purpose of conducting those inspections agreed upon. We request 72 hours notice prior to each visit. We request notification prior to visits to our subcontractors. PRICES - The prices stated herein will remain firm for the period up to the stated date of shipment providing the shipment is not delayed by the customer. If shipment is delayed by the customer beyond the shipment date quoted herein, the prices will be based on the prices in effect at time of shipment, including storage and material handling costs. In no event shall the adjusted price be less than the original order price, including change orders. Prices are F.O.B. Shipping Point, unless otherwise specified. When price includes transportation and other charges pertaining to the shipment of goods, any increase in transportation rates and other charges will be for the account of the Purchaser. There will be an extra charge for any test other than that which may be normally run by the Company, or for any test performed to suit the convenience of the Purchaser. CONTROLLING PROVISIONS - These terms and conditions shall control with respect to any purchase order or sale of the Company’s products. No waiver, alteration or modification of these terms and conditions whether on Purchaser’s purchase order or otherwise shall be valid unless the waiver, alteration or modification is specifically accepted in writing and signed by an authorized representative of the Company. If this transaction involves EXPORT, the following additional terms and conditions shall apply: PACKING - Equipment will be packed, boxed or crated in accordance with the Company’s standard commercial practice, for underdeck export shipment, unless otherwise agreed. LETTER OF CREDIT - Unless otherwise specified in writing, payment shall be made by irrevocable letter of credit in form acceptable to Company, confirmed by a major USA bank, acceptable to the Company and providing for payment in full in United States dollars against presentation of United States inland shipping documents and invoices, such letter of credit to be established prior to Company’s acceptance of the order. The letter of credit shall also provide that in the event Company is, for any reason beyond its control, prevented from making shipment from Company’s factory or delivery at the port of embarkation, a certificate of manufacture of the whole or any part of the goods shall constitute delivery of such whole or any part of the goods and payment in full of any and all drafts drawn against the letter of credit for the goods so “delivered” shall be made upon presentation of such certificates of manufacture in lieu of United States inland shipping documents. In the event that Company is prevented by law, or otherwise, from making shipment from Company’s factory or delivery at port of embarkation of the goods or any part thereof, on completion of manufacture, Company reserves the right to place the goods in storage for the Purchaser’s account and risk. Any charges incurred in this connection will be for the account of the Purchaser at cost and will be payable upon demand. COMPANY AS AGENT - If Company makes or arranges for ocean shipment, Company shall act as agent for the Purchaser and reserves the right to procure full insurance coverage, including war risk insurance, at the expense of the Purchaser. All expenses incurred in this connection will be payable upon demand to the Company. If Company as agent applies for or secures manufacturing, financing, exporting or other licenses required by the United States Government, or any department thereof, Company shall make such applications or secure such licenses solely as agent for the Purchaser, and assumes no responsibility therefore

Page 64: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

Page 1 of 3

C.H. Spencer & Company 1075 South Pioneer Road Salt Lake City, UT 84104 Phone: 801-975-0300 x.110 Fax: 801-972-5216 To: TMWA Attn: Scott Estes Date: August 25, 2015 Reference: Bladder –Type Hydro Pneumatic Tanks for the Arrow Creek Drought Response Project. Bid Date: Enter Date Scott: Below is a Submittal Package for the Hydro Pneumatic Tanks for the Arrow Creek Drought Response Project. I: EQUIPMENT DESCRIPTION: Zolezzi Booster Pump Station Quantity (1) SSA-636-250 Hydro -Pressure Rating of 350 PSI -ID Coating with NSF 61 and 372 Certified Coating. -Seismic Cals stamped by a NV Engineer Arrow Creek Booster Pump Station Quantity (1) SSA-636-250 Hydro -Pressure Rating of 250 PSI -ID Coating with NSF 61 and 372 Certified Coating. -Seismic Calcs stamped by a NV Engineer Accessories that will be provided loose: - (2) ½ inch ball valves rated for 600 psi, NSF 61 compliant. - (2) ½” Safety Relief Valves *Please note that the seismic calculations will be provided 2-4 weeks after engineer’s approval. As Built Drawings will be provided 2-4 weeks after engineer’s approval. Very truly yours, Daniel Beck Sales Engineer C.H. Spencer & Company

Page 65: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

CAPACITY DIA HT SYS

MODEL (GAL.) (IN.) (IN.) (IN.) 275 PSI 500 PSI

SSA 636-250 250 36 85 8 1043 1939

SUBMITTAL

TYPE: ASME SHOCK ARRESTORS

MODELS: SSA 636-250 Submittal Sheet No. B-3806 Date: 4-03

JOB AAtanks Representative _____________

_________________________________

_________________________________

Unit Tag No. ________________________ Order No. _____________ Date _______

Engineer ___________________________ Submitted By __________ Date _______

Contractor __________________________ Approved By ___________ Date _______

DESCRIPTION AAtanks Type SSA Tank is an ASME replaceable bladder type pre-charge hydro-pneumatic tanks for commercial and industrial, municipal, and well water systems, to effectively control water hammer shock, and pump start-up/shut-down water surge. The vessel is fabricated to 275 psi rating with large water system connection designed to accept potentially harmful water surge pressures quickly, with minimal pressure drop.

CONSTRUCTION Shell: Carbon Steel Bladder: Heavy Duty Butyl External Finish: Red Epoxy Primer 2-3 mills Internal Finish: NSF 61 /NSF 372 Coating System

PERFORMANCE LIMITATIONS Maximum Design Temperature: 240ºF Maximum Design Pressure: 275 PSI Factory pre-charge: 10 PSI (Field Adjustable)

TYPICAL SPECIFICATION Furnish and install on the plans a 250 gallon 36” diameter X 85” (high) pre-charged steel hydro-pneumatic tank with 8” diameter system connection and replaceable heavy-duty butyl bladder. The interior shall be properly prepared sand blasted to white metal prior and shall be epoxy-lined with a NSF 372/NSF 61 coating. The tank shall have a bottom flanged system connection, a ¼” pressure gauge tapping, and a .302”-32 charging valve connection (standard tire valve) to facilitate the on-site charging of the tank to meet system requirements. The tank shall be fitted with lifting rings and a floor mounting legs for vertical installation. The tank must be constructed in accordance with Section VIII of the ASME Boiler and Pressure Vessel Code and stamped ________ PSI working pressure.

24356 Sherwood ● Center Line, MI 48015 ● (586) 427-7700 ● (586) 427-7895 FAX ● www.aatanks.com

AAtanks

WEIGHT

C.H. SPENCER & COMPANY

STANTEC ENGINEERING

TRUCKEE MEADOWSDaniel Beck 08/26/15

250

Aarow Creek Pump Station

Daniel
Rectangle
Daniel
Typewritten Text
8 inch 300 # Suction/Discharge Flange. 16 inch Top Flange Seismic Analysis Report (To be provided 2-4 weeks after engineers approval) Specific Dimensional Drawings will be provided 2-4 weeks after engineers approval.
Page 66: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

CAPACITY DIA HT SYS

MODEL (GAL.) (IN.) (IN.) (IN.) 275 PSI 500 PSI

SSA 636-250 250 36 85 8 1043 1939

SUBMITTAL

TYPE: ASME SHOCK ARRESTORS

MODELS: SSA 636-250 Submittal Sheet No. B-3806 Date: 4-03

JOB AAtanks Representative _____________

_________________________________

_________________________________

Unit Tag No. ________________________ Order No. _____________ Date _______

Engineer ___________________________ Submitted By __________ Date _______

Contractor __________________________ Approved By ___________ Date _______

DESCRIPTION AAtanks Type SSA Tank is an ASME replaceable bladder type pre-charge hydro-pneumatic tanks for commercial and industrial, municipal, and well water systems, to effectively control water hammer shock, and pump start-up/shut-down water surge. The vessel is fabricated to 500 PSI rating with large water system connection designed to accept potentially harmful water surge pressures quickly, with minimal pressure drop.

CONSTRUCTION Shell: Carbon Steel Bladder: Heavy Duty Butyl External Finish: Red Epoxy Primer 2-3 millsInternal Finish: NSF 61/ NSF 372 CoatingSystem

PERFORMANCE LIMITATIONS Maximum Design Temperature: 240ºF Maximum Design Pressure: 500 PSI Factory pre-charge: 10 PSI (Field Adjustable)

TYPICAL SPECIFICATION Furnish and install on the plans a 250 gallon 36” diameter X 85” (high) pre-charged steel hydro-pneumatic tank with 8” diameter system connection and replaceable heavy-duty butyl bladder. The interior shall be properly prepared sand blasted to white metal prior and shall be epoxy-lined with a Tnemec™ Plastite #7156 two-part epoxy coating. The tank shall have a bottom flanged system connection, a ¼” pressure gauge tapping, and a .302”-32 charging valve connection (standard tire valve) to facilitate the on-site charging of the tank to meet system requirements. The tank shall be fitted with lifting rings and a floor mounting legs for vertical installation. The tank must be constructed in accordance with Section VIII of the ASME Boiler and Pressure Vessel Code and stamped ________ PSI working pressure.

24356 Sherwood ● Center Line, MI 48015 ● (586) 427-7700 ● (586) 427-7895 FAX ● www.aatanks.com

AAtanks

WEIGHT

Zolezzi Booster Pump Statoion

STANTEC ENGINEERINGTRUCKEE MEADOWS

C.H. SPENCER & COMPANY

Daniel Beck 08/26/15

8 inch 300 # Suction/Discharge Flange.16 inch Top FlangeSeismic Analysis Report (To be provided 2-4 weeks after engineers approval)Specific Dimensional Drawings will be provided 2-4 weeks after engineers approval.

Daniel
Rectangle
Daniel
Rectangle
Daniel
Typewritten Text
350
Page 67: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

������

������ ����� �

� �������������������������������

� ������������� �������

� �������� ��� ���

� !�����"����# �������$��������%�&

� $���������$'� ���������������

!��(�� ������ �� ����$�)����$�����*�����

������

���������'���� ����� ��

�����

���

�� ��

���������������������������������������

��������� �!

"�

��

Page 68: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

�������������� �����������

�����������

� ����������������� �������� ���

� �!"#�$%������ ����������

�����

���

�� ��

���������������������������������������

��������� �!"�

��

�� � � ��

�� � � ��� �� � �� ����

���� �� ��� ��� ��� ��������� �

���������

����� !"

��!#�!$�%� �"���&'(

���#$%�������&'$(��#�)*+����,�-�,.�����+$��/�,�,."��.�0��� ��)%/�,�,.��0.�����

��������

���������������� ���������� �

�-0"��+(12�1�� (13�

#�)4231���5����)(1$�)�)6)������#�

�+$��/�����,��.�-.�,-�)%/���������,��.�-.�����

�+�41��672� �2)�8�2���

�9.�����$4)���:��);2)���5��&1�<�(�)�6�

�+$��/�����.��.-�.��.����)%/���������.��.-�.��.���

=�������9�����.>���������(1���6�1�����

�'�*1?1*)�1$�2�2;@A�*���$�*+)�8��&1�+$;���$�1*� &&&*�).3)�*$4�)��*+������*�,� ���

�����������&�'

-''"!.�(� �����"������!"�)������!�/#����01"��2$�-341� ��&���"�#

�����'��

()*����+**����$���

Daniel
Rectangle
Page 69: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

Water Quality Association 10/08/2014

CERTIFIED LEAD FREE PRODUCTS

NSF/ANSI 372: Drinking Water System Components - Lead Content

Certification to NSF/ANSI 372 (Previously, WQA's Other Recognized Document (ORD),

ORD0902), was established by WQA to compile the minimum requirements for the evaluation of

lead content in drinking water products, material, and components for compliance to laws,

regulations, or other restrictions for lead content. NSF/ANSI 372 combines the lead content

calculations from NSF/ANSI 61 - Annex G and the testing protocol established by the California

Department of Toxic Substances. Certification to NSF/ANSI 372 demonstrates compliance to the

following: • California Health and Safety Code Section 116875 definition of “lead free” (A.K.A.

NSF/ANSI 61 – Annex G, AB 1953), and • Vermont’s lead in consumer products law, 9 V.S.A.,

Chapter 63, Subchapter 1C, and • Any other law, regulation, or restriction on lead content that

may use the same calculations and testing protocol to demonstrate “lead free” compliance.

CLA-VAL1701 Placentia Ave

Costa Mesa, CA 92627-4475

Phone: (949)722-4969

http://www.cla-val.com

Product Type: Component

Brand Name Model

100-YY models 1

12X-YY/62X-YY models 2

131-YY/631-YY models 3

133-YY/633-YY models 4

136-YY/636-YY models 5

210-YY/610-YY models 6

4X-YY/64X-YY models 7

5X-YY/65X-YY models 8

6X-YY/66X-YY models 9

7XX-YY models 10

81-YY/681-YY models 11

9X-YY/69X-YY models 12

Page 1 of 3WQA Goldseal Certified Products

10/8/2014http://12.2.248.199/goldseal/detail.cfm?tableDefID=29&companyID=6333

Daniel
Rectangle
Page 70: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

Air and Vacuum Valve (1/2" to 20") Series 35, 37, TD

Air Release Valve (1/2" to 6") Series 34

Arrestor Check (3" to 16") Series AC

Combination Air Valve (1" to 8") Series 36

Flex-Check Valve (2" to 42") Series 584 (Optional RFA)

Silent Globe Check Valve (2.5" to 42") Series 581

Silent Wafer Check Valve (2" to 10") Series 580

Swing Check Valve (2" - 48") Series 585 (LW, AC, LS)

Tite Seal Foot Valve (2" to 36") Series 583

Two-Door Check Valve (2" to 66") Series 582, 582G, 582L, 582W

Vacuum Breaker (3" to 16') Series 38VB

1: 100-YY includes models 100-01,100-02,100-03,100-20 and 100-30

2: 12X-YY includes models 124-01, 124-02 and 129-01; 62X-YY includes 624-01, 624-02 and 629-01; 428-01 /628-01 also

fall in this family

3: 131-YY Include 131-01, 131-02, 131-04, 131-05, 131-06,131-08, 131-09 and 131-73; 631-YY Include 631-01, 631-02,

631-04, 631-05, 631-06, 631-08, 631-09 and 631-73

4: 133-YY includes 133-01 and 133-11; 633-YY includes 633-01 and 633-11

5: 136-YY Include 136-01 and 136-03; 636-YY Include 636-01 and 636-03

6: 210-YY Include 210-01, 210-02 , 210-03 and 210-16; 610-YY Include 610-01, 610-02 , 610-03 and 610-16

7: 4X-YY includes models 40-01, 43-01 and 49-01; 64X-YY includes 640-01, 643-01 and 649-01

8: 5X-YY Include models 50-01, 52-03 and 58-01; 65X -YY includes models 650-01, 652-03 and 658-01; 250-01 and 605/01

also fall in this family; the CRL and the 55 F are Controls and are part of the 50 series

9: 6X-YY include 60-11, 60-19, 60-73 and 61-02; 66X-YY include 660-11, 660-19, 660-73 and 661-02

10: 7XX-YY include 736-01, 750-01, 790-01, 792-01 and 792-07

11: 81-YY includes 81-01 and 81-02; 681-YY includes 681-01 and 681-02

12: 9X-YY includes 90-01, 90-48, 92-01, 93-01 and 90-11; 69X-YY includes 690-01, 690-48, 692-01, 693-01 and 690-11;

790-11 also falls in this family

Disclaimer: The information in the Water Quality Association product listings directory is made

available by WQA for users of this website and shows currently certified products.

Every effort has been made to verify the accuracy of all listings in this directory. The

association can assume no liability for errors or omissions.

Water Quality Association: Back

Wed, Oct 8, 2014

Copyright 2014 by the Water Quality Association – All rights reserved.Water Quality Association

International Headquarters & Laboratory4151 Naperville Road

Lisle, IL 60532-3696USA

630 505 0160, Fax 630 505 [email protected], www.wqa.org

Page 2 of 3WQA Goldseal Certified Products

10/8/2014http://12.2.248.199/goldseal/detail.cfm?tableDefID=29&companyID=6333

Mikes
Highlight
Page 71: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

USA 800-766-0076Fax 323-890-4456

www.smithcooper.comLos Angeles, CA

Chicago, ILAtlanta, GA

Vancouver, WAHouston, TX

• 1000# CWP, 150# WSP• Full Port• Blow-Out Proof Stem• Vacuum Service to 29” Hg• Locking Handle• ISO 9001:2008 Manufacturer• MSS SP-10• Lead Free

2-Piece 316 Stainless Ball Valve

Series SC201

12001000800600400200

0 100 200 300 400 500TEMPERATURE

PRESSURE PSI

PRESSURE - TEMPERATURERATING

No. Part Material1 Handle Sleeve Plastic2 Body ASTM A351 GR CF8M ( SS316)3 Seat RTFE 15%4 Ball ASTM A351 GR CF8M ( SS316)5 End Cap CF8M Stainless Steel (316)6 Body Seal PTFE7 Thrust Washer PTFE8 Stem Packing PTFE9 Packing Nut 304 Stainless Steel10 Handle Washer 304 Stainless Steel11 Handle Nut 304 Stainless Steel12 Stem ASTM A276 T-31613 Locking Device 304 Stainless Steel14 Handle 304 Stainless Steel

Size Part Number Weight d L H EIN LB IN IN IN IN1/4 SC201C 0.46 0.46 1.91 1.89 3.943/8 SC201E 0.46 0.50 1.91 1.89 3.941/2 SC201G 0.60 0.59 2.24 2.28 4.333/4 SC201I 0.87 0.79 2.68 2.40 4.921 SC201K 1.45 0.98 3.15 3.03 5.71

1-1/4 SC201L 2.13 1.26 3.58 3.19 6.301-1/2 SC201M 3.30 1.50 4.06 3.54 7.092 SC201N 5.70 1.97 4.88 4.25 7.09

2-1/2 SC201P 11.59 2.56 6.18 5.12 9.063 SC201Q 17.10 2.99 7.09 5.59 9.06

E

Rev.9/16/13

Daniel
Rectangle
Daniel
Rectangle
Page 72: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

August 18, 2015 Quote S1208498 Truckee Meadows Water Authority Scott Estes P.O. Box 30013 Reno, NV 89520 Dear Scott: Per your request please see below our proposal for the electrical equipment for the Arrowcreek project. If you have any questions or require any additional information, please don’t hesitate to ask. Thank you for considering the George T. Hall Company.

Zolezzi Lane BPS 1200A SWBD UL891 Nema 3R (White Finish) 1200A 480/277V 3Ø 4W 65Kaic 1,000SQ-Inch COPPER 1 1200A U.G/CT Compt (Utility) 1 1200A Main/Gen Compt. 1 1000A/3P MCCB TM trip (Main) 1 Rotary Door Handle 1 400A/3P MCCB TM trip (Gen.) 1 Rotary Door Handle 2 Key Interlock 1 Phase monitoring relay 1 Power Monitor 3 CT's 1200:5A 3 PT's 480-120V 1 SPD 320kA 1 60A/3P MCCB TM trip (SPD) 1 225A MLO panelboard "LP" -20/208V 3P4W AL 10kAIC UL 67 NEMA 1 12 20A/1P TM branch breaker 1 XMFR 30KVA 480-120/208V 1 50A/3P MCCB TM trip (XFMR) 1 400A/3P MCCB TM trip (Pump Station) 1 Booster Pump A sect 1 250A/3P MCCB TM trip (Pump-A) 1 SSRV/Contactors 100HP 1 HOA Switch 2 Pilot Lights 2 Control Relay 1 CPT 150VA 1 Push Button 1 Power Monitor (By others) 3 CT's 250:5A 3 PT's 480-120V 1 EMT 1 Delay relay 1 Power Fail Relay 1 Booster Pump B sect 1 250A/3P MCCB TM trip (Pump-B) 1 SSRV/Contactors 100HP 1 HOA Switch 2 Pilot Lights 2 Control Relay 1 CPT 150VA 1 Push Button 1 Power Monitor 3 CT's 250:5A 3 PT's 480-120V 1 EMT 1 Delay relay 1 Power Fail Relay MISC. 3 Door Switch 1 Receptacle 1 Mech Timer 3 LED light 3 Space Heater 1 Thermostat 1 Spare Fuses-Lights 3 Sunshield White finish 1 Pressure type lugs

Page 73: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

Arrowcreek BPS 1200A SWBD UL891 Nema 3R (White Finish) 1200A 480/277V 3Ø 4W 65Kaic 1,000SQ-Inch COPPER 1 1200A U.G/CT Compt (Utility) 1 1200A Main/Gen Compt. 1 800A/3P MCCB TM trip (Main) 1 Rotary Door Handle 1 400A/3P MCCB TM trip (Gen.) 1 Rotary Door Handle 2 Key Interlock 1 Phase monitoring relay 1 Power Monitor 3 CT's 1200:5A 3 PT's 480-120V 1 SPD 320kA 1 60A/3P MCCB TM trip (SPD) 1 225A MLO panelboard "LP" -20/208V 3P4W AL 10kAIC UL 67 NEMA 1 12 20A/1P TM branch breaker 1 XMFR 30KVA 480-120/208V 1 50A/3P MCCB TM trip (XFMR) 1 400A/3P MCCB TM trip (Pump Station) 1 Booster Pump A sect 1 175A/3P MCCB TM trip (Pump-A) 1 SSRV/Contactors 100HP 1 HOA Switch 2 Pilot Lights 2 Control Relay 1 CPT 150VA 1 Push Button 1 Power Monitor (By others) 3 CT's 250:5A 3 PT's 480-120V 1 EMT 1 Delay relay 1 Power Fail Relay 1 Booster Pump B sect 1 175A/3P MCCB TM trip (Pump-B) 1 SSRV/Contactors 100HP 1 HOA Switch 2 Pilot Lights 2 Control Relay 1 CPT 150VA 1 Push Button 1 Power Monitor 3 CT's 250:5A 3 PT's 480-120V 1 EMT 1 Delay relay 1 Power Fail Relay MISC. 3 Door Switch 1 Receptacle 1 Mech Timer 3 LED light 3 Space Heater 1 Thermostat 1 Spare Fuses-Lights 3 Sunshield White finish 1 Pressure type lugs

Page 74: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

400A SWBD UL891 Nema 3R (White Finish) 400A 480/277V 3Ø 4W 65Kaic 1,000SQ-Inch COPPER 1 400A U.G/CT Compt (Utility) 1 400A Main/Gen Compt. 1 400A/3P MCCB TM trip (Main) 1 Rotary Door Handle 1 400A/3P MCCB TM trip (Gen.) 1 Rotary Door Handle 2 Key Interlock 1 Phase monitoring relay 1 Power Monitor 3 CT's 1200:5A 3 PT's 480-120V 1 SPD 320kA 1 60A/3P MCCB TM trip (SPD) 1 225A MLO panelboard "LP" -20/208V 3P4W AL 10kAIC UL 67 NEMA 1 12 20A/1P TM branch breaker 1 XMFR 30KVA 480-120/208V 1 50A/3P MCCB TM trip (XFMR) 1 Booster Pump A sect 1 175A/3P MCCB TM trip (Pump-A) 1 SSRV/Contactors 1 HOA Switch 2 Pilot Lights 2 Control Relay 1 CPT 150VA 1 Push Button 1 Power Monitor (By others) 3 CT's 250:5A 3 80 120 PT's 480-120V 1 EMT 1 Delay relay 1 Power Fail Relay 1 Booster Pump B sect 1 175A/3P MCCB TM trip (Pump-B) 1 SSRV/Contactors 1 HOA Switch 2 Pilot Lights 2 Control Relay 1 CPT 150VA 1 Push Button 1 Power Monitor 3 CT's 250:5A 3 PT's 480-120V 1 EMT 1 Delay relay 1 Power Fail Relay 1 Control Section. Backpan MISC. 4 Door Switch 1 Receptacle 1 Mech Timer 4 LED light 4 Space Heater 1 Thermostat 1 Spare Fuses-Lights 4 Sunshield White finish

Page 75: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

NOTES Gear shall be manufactured by RSE-Sierra, a Myers Power Products Company. Seismic certification, if required, shall be furnished by others. Engineered drawings shall be furnished in the time frame quoted. Short circuit/coordination and arc flash studies shall be furnished by others. Field Testing shall be furnished by others. Allowance for field service covers no more than 8 hours per day, between 7 am and 6 pm Monday through Friday, holidays excepted. Transportation, lodging and per diem, if appropriate, will be added to the invoice. Startup services shall be furnished by others. Utility CT-meter compartments include provisions for CTs and for meters. CTs and meters not listed elsewhere in this BOM shall be furnished by others. - System Inergrator not part of scope (by others.) - Seismic Calculation is not included. Myers complies with Seismic Zone 4. -Vibration isolators not included - Quoting UL891 certified Switchboard. - Quoting control components per schematic drawing E005. - RTU/PLC not part of scope (By others.) - Exception to the AM-Meter per spec. Single line does not show the AM-Meter. - Per note 6 dwg, Power Monitor is provided by TMWA. Quoting only provisions. (By others.) -Section A-3: Across the line start FVNR is not included in this proposal. The control diagram does not show an across the line start, E0005.. However a Shorting contactor is internal to the ATS22. Quote is based on single line, E005 Energy Saver: Feature is not available in RVSS technology. It is used in VFDs. Please allow 2-3 weeks for submittals, then 10-12 weeks for delivery after approval to release CLARIFICATIONS Freight included, FOB Shipping Point (Ontario, CA). Lift gate, restricted access destination, or wait time >1 hr will incur additional charge. Lead time estimate is based on material availability at time of quote and begins upon release of order. Good faith efforts will be made to deliver in the time frame quoted; in the case of unanticipated delays. Payment terms: Progress Payments per following schedule 20% Upon Submittal of Drawings for Review / Approval 30% Release for Fabrication 30% Manufacturing Complete 10% Ready for test 10% Shipment This quotation is valid until 2/30/2016 Sales tax is not included. Liftgate truck additional $75.00 Submittals and O&M Manuals shall be furnished in PDF format. Hard copies may be purchased for $250 per volume. Receipt of a purchase order serves as explicit confirmation that customer has reviewed this quote for accuracy and completeness prior to acceptance and constitutes acceptance of the quote BOM without revision. No additions or modifications may be made to this BOM after the order is accepted without commensurate price adjustment. Any deviation in quantities or part numbers listed above will be subject to a new quotation.

Total for above products & services: $220,500.00

Page 76: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

Notes: Sincerely,

Michael Smith George T. Hall Company [email protected]

Page 77: Appendix B – Owner Provided Equipment...APPENDIX B OWNER PROVIDED EQUIPMENT PART 1 OWNER-FURNISHED PRODUCTS 1.1 PRECAST VAULTS - SPECIFICATION SECTION 03480 A. All Owner-supplied

STANDARD TERMS AND CONDITIONS

1. This Quotation becomes void after 30 days unless otherwise noted in the body of the quotation. 2. Price does not include any applicable Sales tax. 3. Price does not include Shipping, unless otherwise noted. 4. Product Lead times are estimates only. GTH relies heavily on the word of manufacturers and package carriers for these delivery dates.

This bid does not include electrical or mechanical installation. For example: Running conduit, pulling wire, mounting hardware and or instrumentation, unless otherwise stated above.

5. Fieldwork not included in the contract will be billed at standard rates. Unless otherwise stated above, fieldwork including start-up, instrumentation calibration, service, etceteras, will be billed at $125.00 per hour plus travel time, mileage, and expenses during normal business hours (8:00 a.m. – 5:00 p.m.). Over-Time rates are billed at $187.50 per hour plus travel time, mileage, and expenses. Holiday rates are billed at $250.00 per hour plus travel time, mileage, and expenses. Any exceptions must be stated and accepted in writing.

6. Acceptance of this quotation shall be in the form of a Purchase Order or signed contract, and shall not be modified without a written change order request.

7. Acceptance of this quotation acknowledges your acceptance of these terms in their entirety, regardless of other contract documents and their implied terms.

8. The terms of this quotation are Net 30 days from the date of invoice unless otherwise noted. Interest and late charges shall accrue at 1.5% per month on any unpaid balances.

9. Progress billing will be invoiced per an attached schedule if applicable. Typically this includes an invoice for 10% of the contract amount upon receipt of approved submittals, for engineering services.

10. Please note that GTH requires a complete set of customer supplied Project Specifications. 11. Please be advised that it is GTH’s standard practice to Lien all Jobs/Projects in excess of $5,000.00. A $100.00 filing fee may apply. 12. Start-Up assistance, Commissioning, and or Field Work may be suspended if invoices are past due. 13. GTH may not be able to respond to Warranty calls if invoices are past due. 14. Unit Price Breakouts are provided as estimates only. Prices for Change Order Additions or Subtractions may vary, and require a separate

quotation. 15. Returns, exchanges and/or cancellation may be subject to 25% fees. 16. On-site Training Terms: 50% at booking and 50% Net 30 days from the date of invoice. Please note a 50% fee will be assessed for

cancellations made within 1 week of date of training. 17. Any Custom Order, or Special Order made to your unique specifications, must be accompanied by a written and signed Purchase Order,

and cannot be cancelled once an acknowledgment has been issued. In addition, we cannot accept returns of Custom or Special Order items.

18. Warranty: Components are warranted by the manufacturer to be free of defects in materials and workmanship and are inspected prior to shipment to insure that they comply with the manufacturer’s stated specifications. Terms of the warranty are for a period of one (1) year from the date of shipment. Any component failing to meet specifications will be repaired or replaced, at our option, free of charge, provided the following conditions are met:

A. Notification of the nature of the defect is submitted within one (1) year of invoice date. B. Authorization to return the defective component is received. C. The component is returned freight charges prepaid to our Anaheim, CA. facility. The replacement component will be shipped freight

allowed. Correction of such defects by repair or replacement shall constitute the fulfillment of our obligations. We cannot be liable for consequential damages, direct or indirect, resulting from defect or delay. There is no provision for a labor allowance to cover the trouble- shooting, removal and reinstallation of any component that failed during the warranty period. Under no circumstances will claims be honored for repairs or rework of components without prior written approval of the manufacturer. Components damaged from improper installation, handling, storage, or operation, are specifically excluded from the warranty. The above warranty will pass through to the end user from the manufacturer.