AIR PREHEATERS

Page 2: APH

Typical savings from Heat Rate Improvement ( Rs /

Year)   Pit Head Station Rail Fed Station

210 MW 500 MW 210 MW 500 MW

       

1% Overall Heat Rate Improvement ( from 2500 kcal / kWh)

55.18 Lacs 131.4 Lacs 147 Lacs 350 Lacs

         

1 Deg C change in APH Exit Gas Temperature

2.64 Lacs 6.30 Lacs 7.06 Lacs 16.82 Lacs

Page 3: APH

TYPES OF AIR PREHEATERS

RECUPERATIVE AIR PREHEATERS TUBULAR APH PLATE TYPE APH STEAM APH

REGENERATIVE AIR PREHEATERS

Page 4: APH
Page 5: APH

REGENERATIVE APH

IT ABSORBS HEAT FROM FG AND TRANSFERS THIS HEAT TO INCOMING

COLD AIR BY MEANS OF CONTINUOUSLY ROTATING HEAT

TRANSFER ELEMENTS OF SPECIALLY FORMED METAL SHEETS.

Page 6: APH
Page 7: APH
Page 8: APH

Arrangement of Baskets

Page 9: APH

Arrangement of Baskets

Page 10: APH

Pin-rack assembly

Page 11: APH
Page 12: APH
Page 13: APH
Page 14: APH

Types of Seals

RADIAL SECTOR & AXIAL SEALING PLATE

RADIAL, CIRCUMFRENCIAL & AXIAL SEALS

ROTOR POST SEALS

INBOARD & OUTBOARD STATIC SEALS

Page 15: APH

TYPES OF SEALS

Page 16: APH

APH DEFORMATION

Page 17: APH

Factors affecting the performance of APHs

Condition of heating elements Condition of seals /seal setting Condition of sector plates / axial

seal plates Condition of Diaphragm plates Condition of Casing / enclosure Condition of Insulation

Page 18: APH

APH Performance Factors

Gas side Efficiency

Air side Efficiency

APH Seal Leakage

X-Ratio

Air / Gas side DP

Page 19: APH

Gas Side Efficiency

Ratio of Gas Temperature drop across the air heater, corrected for no leakage, to the temperature head.

= (Temp drop / Temperature head) * 100

where Temp drop = Tgas in -Tgas out (no leakage) Temp head = Tgasin - T air in

Page 20: APH

Air Heater Leakage (%)

Weight of air passing from air side to gas side

This leakage is assumed to occur entirely between air inlet and gas outlet

• Direct - Hot End / Cold End (60% through radial seals + 30% through Circumferential bypass)

• Entrained Leakage

Page 21: APH

X – Ratio

Ratio of heat capacity of air passing through the air heater to the heat capacity of flue gas passing through the air heater.

= Tgas in - Tgas out (no leakage) Tair out - Tair in

Say AH leakage – 17.1%, Gas In Temp – 333.5 C, Gas Out Temp – 133.8 C , Air In Temp – 36.1 C, Air Out Temp – 288 C

X ratio = (333.5 – 150.5) / (288 –36.1) = 0.73

Page 22: APH

Soot Blowers

Soot blower travel to be set to ensure full coverage of all the heating element

Thermal drain at soot blowing steam line.

Operation at rated steam pressure and temperature

Page 23: APH

THANK YOU

Page 24: APH

Reasons for rotor stopping

Foreign material jammed in between rotor and sector plate

Failure of Main drive

Failure of Auxiliary drive

Failure of service beam due to erosion