J OSLYN Manufacturing Co. Arresters Distribution Arresters Durability Riser Pole and Heavy Duty Distribution Class arresters have been called upon to serve in the most demanding of applications. Typically unshielded, overhead lines can produce some of the most severe lightning surges on the power system. Joslyn distribution arresters are designed to meet the demands of protecting underground and overhead equipment, respectively. Tested in accordance with the latest industry standard, ANSI/IEEE C62.11-1999 for Heavy Duty metal oxide arresters, Joslyn distribution arresters withstand the following minimum design tests: High Current-Short Duration: 2 current surges of 100kA magnitude and 4/10 microsecond duration. Low Current-Long Duration: 20 current surges with 2000 micro-second duration and 400 amperes magnitude discharged through ‘ZRP’ and 250 amperes magnitude discharged through ‘ZHP’. Duty Cycle: 20 discharges with a current surge of 10kA magnitude and 8/20 microsecond wave shape followed by 2 discharges with a current surge of 40kA magnitude. Following each of these tests, the arresters remain thermally stable and the discharge voltage change at the classifying current is less than 10%. For more details on procedures and results, request the product specific Certified Design Test Report. Insulating Bracket Joslyn’s polymer housed arresters are assembled complete with a molded glass reinforced polyester insulating bracket with greatly increased strength. This polyester bracket provides insulation between the arrester and ground after the ground lead disconnect has operated in the unlikely event of arrester failure. This bracket will accommodate a 1/2 inch carriage bolt on the crossarm bracket. Joslyn recommends that no more than 40 foot-pounds of torque be applied when installing the arrester on the crossarm mounting bolt. The bracket also uses a contamination deterrent crest down the centerline of the body of the bracket. This crest facilitates self-washing of contamination with rainwater. This feature reduces the risk of any contaminant build up on the top of the bracket between the skirts. ©2004 Joslyn Manufacturing Co. • 9200 W. Fullerton Avenue • Franklin Park, IL 60131 • www.joslynmfg.com Phone: 800-4-JOSLYN (800-456-7596) or 773-625-1500 • Fax 800-443-7380 or 773-625-0090 AR-13

Apartarryos Joslyn

  • Upload
    cleyvas

  • View
    80

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Apartarryos Joslyn

JOSLYNManufacturing Co. Arresters

Distribution Arresters

DurabilityRiser Pole and Heavy Duty Distribution Class arresters have beencalled upon to serve in the most demanding of applications.Typically unshielded, overhead lines can produce some of themost severe lightning surges on the power system. Joslyndistribution arresters are designed to meet the demands ofprotecting underground and overhead equipment, respectively.Tested in accordance with the latest industry standard,ANSI/IEEE C62.11-1999 for Heavy Duty metal oxide arresters,Joslyn distribution arresters withstand the following minimumdesign tests:

• High Current-Short Duration: 2 current surges of 100kAmagnitude and 4/10 microsecond duration.

• Low Current-Long Duration: 20 current surges with 2000micro-second duration and 400 amperes magnitude discharged through ‘ZRP’ and 250 amperes magnitudedischarged through ‘ZHP’.

• Duty Cycle: 20 discharges with a current surge of 10kAmagnitude and 8/20 microsecond wave shape followed by 2 discharges with a current surge of 40kA magnitude.

• Following each of these tests, the arresters remain thermallystable and the discharge voltage change at the classifyingcurrent is less than 10%. For more details on procedures andresults, request the product specific Certified Design TestReport.

Insulating BracketJoslyn’s polymer housed arresters are assembled complete with a molded glass reinforced polyester insulating bracket withgreatly increased strength. This polyester bracket providesinsulation between the arrester and ground after the ground lead disconnect has operated in the unlikely event of arresterfailure.

This bracket will accommodate a 1/2 inch carriage bolt on the crossarm bracket. Joslyn recommends that no more than 40 foot-pounds of torque be applied when installing the arresteron the crossarm mounting bolt.

The bracket also uses a contamination deterrent crest down the centerline of the body of the bracket. This crest facilitatesself-washing of contamination with rainwater. This featurereduces the risk of any contaminant build up on the top of thebracket between the skirts.

©2004 Joslyn Manufacturing Co. • 9200 W. Fullerton Avenue • Franklin Park, IL 60131 • www.joslynmfg.comPhone: 800-4-JOSLYN (800-456-7596) or 773-625-1500 • Fax 800-443-7380 or 773-625-0090 AR-13

Page 2: Apartarryos Joslyn

Distribution Arresters (continued)

Arresters JOSLYNManufacturing Co.

©2004 Joslyn Manufacturing Co. • 9200 W. Fullerton Avenue • Franklin Park, IL 60131 • www.joslynmfg.comPhone: 800-4-JOSLYN (800-456-7596) or 773-625-1500 • Fax 800-443-7380 or 773-625-0090AR-14

Terminal ConnectionsDistribution arrester line terminals utilize a stainless steelfour cornered “Star Clamp” for maximum conductor rangeand speed of installation. The ground terminals utilize astainless steel “U clamp”. Both connectors securely clampaluminum or copper conductors from No. 10 solid through2/0 stranded. Joslyn specifies that no more than 20 foot-pounds of torque be applied to the line and groundterminals.

Transformer ProtectionThe level of protection an arrester can provide will decreasewhen utilizing long connecting leads (line and ground side).This is due to the inductive voltage drop which is added tothe discharge voltage of the arrester. Mounting an arresterdirectly to the transformer will yield excellent protectivemargins from a combination of controlled lead length andlow discharge voltages.

Available OptionsFor options, see Catalog Selection Guides (page AR-19 thru22) and Accessories (page AR-26 and 27).

Fault-Current Withstand TestsFault-current testing, also known as short circuit testing,demonstrates an arrester failure based on the most probablefailure modes over a range of fault currents. Two failuremodes are tested: 1) a fuse wire runs along the side of theinternal valve elements to simulate and internal flashover(moisture or collar failure), 2) overvoltage the arrester untilthe resistive elements fail to simulate a system overvoltageexceeding the unit’s TOV capability.

ANSI/IEEE C62.11 1999, specifies the test procedures andacceptance criteria for fault-current tests on distributionsurge arresters. Joslyn’s arresters passed the fuse wire andovervoltage fault-current testing at the current levels anddurations listed in the applicable Fault-Current Data Tables.Conformance was shown by oscillograph recordings ofcurrent magnitude and duration conducted through thearresters. All units passed the acceptance criteria.

Initial venting and arcing. Continued arcing. Following the severe fault, the arrester remainedintact.

Page 3: Apartarryos Joslyn

JOSLYNManufacturing Co. Arresters

Distribution Arresters (continued)

Zforce™ ‘ZNP’, ‘ZHP’ and ‘ZRP’ ArrestersPatent No. 5,923,518

‘ZNP’ (5kA Normal Duty Polymer, Rated 9, 10 & 18kV)‘ZHP’ (10kA Heavy Duty Polymer, Rated 3kV-36kV)‘ZRP’ (10kA Riser Pole Polymer, Rated 3kV-36kV)

Fault Current Withstand TestsFault current testing, also known as short circuit testing,demonstrates an arrester failure based on the most probablefailure modes over a range of fault currents. Two failure modesare tested:

• A fuse wire runs along the side of the internal and valveelements to simulate an internal flashover (moisture orcollar failure).

©2004 Joslyn Manufacturing Co. • 9200 W. Fullerton Avenue • Franklin Park, IL 60131 • www.joslynmfg.comPhone: 800-4-JOSLYN (800-456-7596) or 773-625-1500 • Fax 800-443-7380 or 773-625-0090 AR-15

‘ZNP’ Fault Current Data ‘ZHP’ & ‘ZRP’ Fault Current Data

Fault Circuit Fault Duration Fault Circuit Fault DurationTest Type (kA rms) (SEC) Test Type (kA rms) (SEC)

Fuse Wire 10.1 0.202 Fuse Wire 20.0 0.2110.1 0.212 20.0 0.21

Overvoltage 10.1 0.21 Overvoltage 20.0 0.20910.1 0.206 20.0 0.2095.27 0.207 10.1 0.2095.27 0.207 10.1 0.2110.608 1.009 0.708 1.0120.608 1.011 0.708 1.014

• Overvoltage the arrester until the resistive elements fail tosimulate a system overvoltage exceeding the units TOVcapability.

ANSI/IEEE C62.11-1999, specifies the test procedures andacceptance criteria for fault current tests on distributionsurge arresters. Joslyn’s Zforce™ arresters passed the fusewire and overvoltage fault-current testing at the currentlevels and durations listed in the applicable Fault-CurrentData Tables. Conformance was shown by oscillographrecordings of current magnitude and duration conductedthrough the arresters. All units passed the acceptancecriteria.

Page 4: Apartarryos Joslyn

Distribution Arresters (continued)

ZFORCE ZNP™ (5kA Normal Duty Polymer)

Physical Data

Creepage1 Strike A B C D Weight2

kV Inch mm Inch mm Inch mm Inch mm Inch mm Inch mm Lbs. kg Std. Pkg.9 15.04 382 7.69 195 8.83 224 4.00 102 7.71 195 3.93 100 2.9 1.32 5

10 17.41 442 8.00 203 9.14 232 4.00 102 8.02 204 3.93 100 3.0 1.36 518 26.59 675 11.23 285 12.23 311 4.00 102 11.16 283 5.43 138 4.8 2.18 5

Protective Characteristics

Voltage MCOV Max. Equiv. Max. Switch. Max. Discharge Voltage (kV Crest) Using an 8/20 µs Current ImpulseRating (Ur) (Uc)3 FOW4 Surge6 1.5 2.5 3.0 5.0 10 20 40

(kVrms) (kVrms) (kV Crest) (kV Crest) kA kA kA kA kA kA kA9 7.65 29.9 23.7 25.4 26.2 26.6 28.2 30.5 33.8 39.9

10 8.4 32.9 26.3 28.1 29.2 29.6 31.3 33.9 37.4 43.918 15.3 59.7 47.4 50.7 52.3 53.1 56.4 61.0 67.5 79.7

Arresters JOSLYNManufacturing Co.

©2004 Joslyn Manufacturing Co. • 9200 W. Fullerton Avenue • Franklin Park, IL 60131 • www.joslynmfg.comPhone: 800-4-JOSLYN (800-456-7596) or 773-625-1500 • Fax 800-443-7380 or 773-625-0090AR-16

INSULATED BRACKET DATAArrester Creepage E F G (Radius)Rating Skirts(kV) inch mm inch mm inch mm inch mm

3–15 4.6 117 3 1.875 47.62 2.70 66.58 1.312 33.3418–36 9.16 232 6 2.13 54.10 2.95 74.93 1.656 42.06

OPTIONAL BIRDGUARD

Page 5: Apartarryos Joslyn

JOSLYNManufacturing Co. Arresters

Distribution Arresters (continued)

ZFORCE ZHP™ (10kA Heavy Duty Polymer)

Physical Data

Creepage1 Strike A B C D Weight2

kV Inch mm Inch mm Inch mm Inch mm Inch mm Inch mm Lbs. kg Std. Pkg.3 7.96 202 5.47 139 6.52 166 4.30 109 5.40 137 3.93 100 2.3 1.05 56 11.94 303 6.02 153 7.66 195 4.30 109 6.54 166 3.93 100 3.0 1.37 59 15.92 404 7.76 197 8.80 224 4.30 109 7.68 195 3.93 100 3.6 1.64 5

10 18.28 464 8.21 209 9.14 232 4.30 109 8.02 204 3.93 100 3.7 1.68 512 19.90 506 8.91 226 9.94 253 4.30 109 8.82 224 3.93 100 4.2 1.91 515 23.84 606 10.01 254 11.09 282 4.30 109 10.02 254 3.93 100 4.9 2.23 518 27.87 708 11.40 290 12.23 311 4.30 109 11.16 283 5.43 138 5.9 2.68 521 31.85 809 12.54 319 13.37 340 4.30 109 12.30 312 5.43 138 6.5 2.96 524 35.83 910 13.69 348 14.51 369 4.30 109 13.44 341 5.43 138 7.1 3.23 527 39.92 1014 14.52 369 15.66 398 4.30 109 14.59 371 5.43 138 7.8 3.52 530 43.90 1115 15.51 394 16.78 426 4.30 109 15.71 399 5.43 138 8.4 3.80 1*36 51.95 1320 17.79 452 19.13 486 4.30 109 18.06 459 5.43 138 9.6 4.38 1*

Protective Characteristics

Voltage MCOV Max. Equiv. Max. Switch. Max. Discharge Voltage (kV Crest) Using an 8/20 µs Current ImpulseRating (Ur) (Uc)3 FOW5 Surge6 1.5 2.5 3.0 5.0 10 20 40

(kVrms) (kVrms) (kV Crest) (kV Crest) kA kA kA kA kA kA kA3 2.55 10.4 7.8 8.5 8.8 8.9 9.3 9.9 10.9 12.46 5.1 20.7 15.5 16.9 17.5 17.7 18.6 19.8 21.8 24.79 7.65 31.0 23.3 25.4 26.2 26.6 27.9 29.7 32.7 37.0

10 8.4 34.5 25.9 28.2 29.1 29.5 31.0 33.0 36.3 41.112 10.2 41.3 31.0 33.8 34.9 35.4 37.2 39.6 43.5 49.315 12.7 51.7 38.8 42.2 43.6 44.2 46.5 49.5 54.4 61.618 15.3 62.0 46.5 50.7 52.3 53.1 55.8 59.4 65.3 73.921 17.0 72.3 54.3 59.1 61.0 61.9 65.1 69.3 76.2 86.224 19.5 82.6 62.1 67.6 69.7 70.7 74.4 79.2 87.0 98.527 22.0 92.9 69.9 76.0 78.4 79.6 83.7 89.1 97.9 110.830 24.4 103.3 77.6 84.4 87.1 88.4 93.0 99.0 108.8 123.136 29.0 124.0 93.1 101.3 104.5 106.1 111.5 118.8 130.5 147.7

ZFORCE ZRP™ (10kA Riser Pole Polymer)

Physical Data

Creepage1 Strike A B C D Weight2

kV Inch mm Inch mm Inch mm Inch mm Inch mm Inch mm Lbs. kg Std. Pkg.3 7.96 202 5.47 139 6.52 166 4.30 109 5.40 137 3.93 100 2.3 1.05 56 11.94 303 6.02 153 7.66 195 4.30 109 6.54 166 3.93 100 3.0 1.37 59 15.92 404 7.76 197 8.80 224 4.30 109 7.68 195 3.93 100 3.6 1.64 5

10 18.28 464 8.21 209 9.14 232 4.30 109 8.02 204 3.93 100 3.7 1.68 512 19.90 506 8.91 226 9.94 253 4.30 109 8.82 224 3.93 100 4.2 1.91 515 23.84 606 10.01 254 11.09 282 4.30 109 10.02 254 3.93 100 4.9 2.23 518 27.87 708 11.40 290 12.23 311 4.30 109 11.16 283 5.43 138 5.9 2.68 521 31.85 809 12.54 319 13.37 340 4.30 109 12.30 312 5.43 138 6.5 2.96 524 35.83 910 13.69 348 14.51 369 4.30 109 13.44 341 5.43 138 7.1 3.23 527 39.92 1014 14.52 369 15.66 398 4.30 109 14.59 371 5.43 138 7.8 3.52 530 43.90 1115 15.51 394 16.78 426 4.30 109 15.71 399 5.43 138 8.4 3.80 1*36 51.95 1320 17.79 452 19.13 486 4.30 109 18.06 459 5.43 138 9.6 4.38 1*

©2004 Joslyn Manufacturing Co. • 9200 W. Fullerton Avenue • Franklin Park, IL 60131 • www.joslynmfg.comPhone: 800-4-JOSLYN (800-456-7596) or 773-625-1500 • Fax 800-443-7380 or 773-625-0090 AR-17

Page 6: Apartarryos Joslyn

ZFORCE ZRP™ (10kA Riser Pole Polymer)

Protective Characteristics

Voltage MCOV Max. Equiv. Max. Switch. Max. Discharge Voltage (kV Crest) Using an 8/20 µs Current ImpulseRating (Ur) (Uc)3 FOW5 Surge6 1.5 2.5 3.0 5.0 10 20 40

(kVrms) (kVrms) (kV Crest) (kV Crest) kA kA kA kA kA kA kA3 2.55 8.6 6.2 6.8 7.1 7.2 7.5 8.2 9.0 10.36 5.1 17.1 12.4 13.6 14.1 14.3 15.1 16.3 18.1 20.69 7.65 25.7 18.6 20.3 21.2 21.5 22.6 24.5 27.1 30.9

10 8.4 28.5 20.7 22.6 23.5 23.9 25.1 27.2 30.1 34.312 10.2 34.2 24.8 27.1 28.2 28.7 30.1 32.6 36.1 41.215 12.7 42.8 31.1 33.9 35.3 35.9 37.7 40.8 45.2 51.518 15.3 51.3 37.3 40.7 42.3 43.0 45.2 49.0 54.2 61.721 17.0 59.9 43.5 47.5 49.4 50.2 52.7 57.1 63.2 72.024 19.5 68.4 49.7 54.2 56.4 57.4 60.2 65.3 72.2 82.327 22.0 77.0 55.9 61.0 63.5 64.5 67.8 73.4 81.3 92.630 24.4 85.5 62.1 67.8 70.5 71.7 75.3 81.6 90.3 102.936 29.0 102.6 74.5 81.4 84.6 86.0 90.4 97.9 108.4 123.5

1. Reduce creepage by 1.45 inches (36.8mm) when ordering without insulating bracket.

2. Does not include metal mounting bracket hardware.

3. MCOV = Maximum Continuous Operating Voltage that may be applied continuously between the terminals of the arrester.

4. The equivalent Front-of-Wave is the maximum discharge voltage for a 5 kA impulse current wave which produces a voltage wave cresting in 0.5 µs.

5. The equivalent Front-of-Wave is the maximum discharge voltage for a 10 kA impulse current wave which produces a voltage wave cresting in 0.5 µs.

6. Based on a switching surge current impulse of 45x90 µs, 500 amperes.

* Single pack modifier required for 30 kV and 36 kV ratings.

Temporary Overvoltage—’ZNP’, ‘ZHP’ and ‘ZRP’ Arresters

Arresters JOSLYNManufacturing Co.

©2004 Joslyn Manufacturing Co. • 9200 W. Fullerton Avenue • Franklin Park, IL 60131 • www.joslynmfg.comPhone: 800-4-JOSLYN (800-456-7596) or 773-625-1500 • Fax 800-443-7380 or 773-625-0090AR-18

Distribution Arresters (continued)

Ove

rvol

tage

per

Uni

t of

Arr

este

r M

CO

V (

Uc)

Duration ZNP ZHP ZRP(seconds) Voltage P.U. of MCOV (Uc)

0.02 1.77 1.80 1.540.10 1.70 1.73 1.481.00 1.61 1.63 1.4010 1.52 1.54 1.31100 1.47 1.47 1.261000 1.42 1.43 1.22

Page 7: Apartarryos Joslyn

JOSLYNManufacturing Co. Arresters

©2004 Joslyn Manufacturing Co. • 9200 W. Fullerton Avenue • Franklin Park, IL 60131 • www.joslynmfg.comPhone: 800-4-JOSLYN (800-456-7596) or 773-625-1500 • Fax 800-443-7380 or 773-625-0090 AR-19

Distribution Arresters (continued)

#S - Single Pack Modifier (Requiredfor 30kV and 36kV ratings.)Standard package is 5 unless otherwise specified.

#P - OEM Bulk Packaging

* Top/Bottom Terminal: Fits wire ranges for aluminum or copper conductors from No. 10 solid (3.0mm dia.) through 2/0 stranded (11.0mm dia.)

Page 8: Apartarryos Joslyn

JOSLYNManufacturing Co. Arresters

©2004 Joslyn Manufacturing Co. • 9200 W. Fullerton Avenue • Franklin Park, IL 60131 • www.joslynmfg.comPhone: 800-4-JOSLYN (800-456-7596) or 773-625-1500 • Fax 800-443-7380 or 773-625-0090 AR-23

Flipper Fuse KitThe AD524-Z fuse kit includes a stationary terminal for mounting on the transformer bushing. Its spring arm subjects the fuselink to moderate tension during steady-state operation and provides a positive whip action to quickly separate the link during fault conditions. An insulating cap for the transformer bushing and an insulating sleeve for the spring arm are included for wildlife protection.

Optional Bagging Assemblies (Lug-H and Boss-B)

Transformer mounting hardware is available upon request. To specify, add suffix “-B” for Boss mounting hardware, or “-H” for Lug mounting hardware to catalog number. (See specific Catalog Number Selection Guides for details.)

MOUNTING BRACKETS

Accessories

AD1137-B

‘C’ Bracket7106A0025

‘A’ Bracket7106A0013

Page 9: Apartarryos Joslyn

Arresters JOSLYNManufacturing Co.

©2004 Joslyn Manufacturing Co. • 9200 W. Fullerton Avenue • Franklin Park, IL 60131 • www.joslynmfg.comPhone: 800-4-JOSLYN (800-456-7596) or 773-625-1500 • Fax 800-443-7380 or 773-625-0090AR-24

Accessories (continued)

‘N’ Bracket7106A0015

‘W’ Bracket7106A0047

‘E’ BracketJ24515

‘Z’ Bracket7106A0028