141
ANNUAL WATER QUALITY MONITORING REPORT OLALLA WATER SYSTEM 2014 Regional District of Okanagan-Similkameen April, 2015

ANNUAL WATER QUALITY MONITORING REPORT … · 2014 ANNUAL WATER QUALITY MONITORING REPORT ... (Operator-in-Training) 0 Water Treatment ... (PLC) along with the addition of a SCADA

Embed Size (px)

Citation preview

ANNUAL WATER QUALITY MONITORING REPORT

OLALLA WATER SYSTEM

2014

Regional District of Okanagan-Similkameen

April, 2015

2014 ANNUAL WATER QUALITY MONITORING REPORT

OLALLA WATER SYSTEM

OLALLA, B.C.

Copy Prepared for:

INTERIOR HEALTH AUTHORITY (IHA)

740 Carmi Ave.

Penticton, B.C.

V2A 8P9

Attention: Tristan Wilson

Environmental Health Officer

Prepared by:

Regional District of Okanagan-Similkameen

101 Martin St.

Penticton, B.C.

V2A 5J9

Author: Rob Palmer

Environmental Technician

Regional District of Okanagan Similkameen Olalla Annual Water Quality Report – 2014

i

Table of Contents 1. Introduction ....................................................................................................................................... 1

2. System Description ......................................................................................................................... 1

3. System Classification and Operator Certifications ................................................................. 2

3.1. System Classification ............................................................................................................. 2

3.2. Operator Certification ............................................................................................................. 2

4. Annual Water Usage ........................................................................................................................ 3

4.1. Consumption Records ............................................................................................................ 3

4.2. Water Conservation Program ............................................................................................... 3

5. Source and Distribution Water Quality....................................................................................... 4

5.1. Water Quality Complaints ...................................................................................................... 4

5.2. Potable Water Test Results ................................................................................................... 5

5.3. Bacteriological Results .......................................................................................................... 5

6. Water System Notifications ........................................................................................................... 6

6.1. Boil Water Notices (BWN) ...................................................................................................... 6

6.2. Water Quality Advisories (WQA) .......................................................................................... 6

6.3. Do Not Use Orders ................................................................................................................... 6

7. Program Updates and Status ........................................................................................................ 6

7.1. Water Quality Monitoring Program ...................................................................................... 6

7.2. Emergency Response Plan ................................................................................................... 6

7.3. Cross Connection Control Program ................................................................................... 6

7.4. System Maintenance/Upgrades............................................................................................ 6

7.5. Capital Works ............................................................................................................................ 6

7.6. Future System Upgrades ....................................................................................................... 6

8. Budget ................................................................................................................................................. 7

9. Summary ............................................................................................................................................ 7

Regional District of Okanagan Similkameen Olalla Annual Water Quality Report – 2014

ii

TABLES

Table 1: RDOS Operator Certifications 2014 ........................................................................................ 2

Table 2: Annual Water Usage for 2014 .................................................................................................. 3

Table 3: Source and Distribution Water Bacteriological Testing Summary for 2014 ....................... 5

FIGURES

No table of figures entries found.

APPENDICES

Appendix A - Bacteriological Results and Data

Appendix B – Water Sampling Field Data

Appendix C – Potability (Schedule A) Results and Data

Appendix D – Annual Budget

Regional District of Okanagan Similkameen Olalla Annual Water Quality Report – 2014

1

1. Introduction

As the owner and operator of the Olalla water system, the Regional District of Okanagan-

Similkameen is responsible for the following annual report summarizing the results of the

2014 Water Quality Monitoring Program. The report is a conditional requirement of the

Permit to Operate issued by the Interior Health Authority (IHA).

2. System Description

The Olalla water system is supplied by a single deep source groundwater well. Water is

pumped from the well into the distribution system and to an elevated storage reservoir.

There is no treatment of the groundwater supplying the system.

Regional District of Okanagan Similkameen Olalla Annual Water Quality Report – 2014

2

3. System Classification and Operator Certifications

3.1. System Classification

The British Columbia Environmental Operators Certification Program (BC EOCP) is

responsible for classifying potable water systems in BC.

The Olalla water system remained classified as a Small Water System in 2014.

3.2. Operator Certification

The British Columbia Environmental Operators Certification Program (BC EOCP) is

responsible for certification of all potable water system operators in BC.

All Regional District of Okanagan-Similkameen Operators are certified through the BC

EOCP.

All operators annually continue to work on maintaining and furthering levels of

certification.

Certification Level Number of Operators Holding Certification

Water Distribution (WD) IV 1

Water Distribution (WD) III 1

Water Distribution (WD) II 2

Water Distribution (WD) I 1

Water Distribution OIT (Operator-in-Training)

0

Water Treatment (WT) I 0

Water Treatment (WT) II 3

Chlorine Handlers 5

Table 1: RDOS Operator Certifications 2014

Regional District of Okanagan Similkameen Olalla Annual Water Quality Report – 2014

3

4. Annual Water Usage

4.1. Consumption Records

Cubic Meters (m3) US Gallons

Annual Total Usage 235,664 62,255,970 Date

Minimum Daily Flow 340 89,820 Jan 28/14

Maximum Daily Flow 1,404 370,824 Jul 13/14

Table 2: Annual Water Usage for 2014

4.2. Water Conservation Program

Annual water restrictions were in effect from April 1st to October 31st. Residential

watering was restricted to odd/even calendar days according to the property address.

Lawn watering was permitted before 9:00am and after 6:00pm on the designated

watering day. The Water Ambassador (WA) and Public Works Dept. provided a

newsletter update mailed to residents discussing water conservation and the current

state of their water system. The WA also conducted door-to-door canvassing to

distribute water conservation materials and discuss water issues with residents. Water

sprinkling audits were also conducted in the community on a random basis.

The Water Ambassador Program funds provided by the OBWB covers all the area that

lies within the Okanagan Basin and additional grants are sought to round out the whole

region; as programs can be overlaid outside the Basin for places such as Olalla,

Princeton, Hedly, Twin Lakes and Keremeos. During the months of March and April,

together with Solid Waste Coordinator Cameron Baughen, the WA provided 14

additional information sessions throughout the region from Osoyoos to Summerland,

Princeton to Naramata on water conservation. The Farmer’s Market in Penticton is a

region-wide draw and was the focus of booth displays and promotions during the

summer.

Regional District of Okanagan Similkameen Olalla Annual Water Quality Report – 2014

4

5. Source and Distribution Water Quality

All distribution system water quality parameters are compared to the British Columbia

Drinking Water Protection Act and Regulation (DWPA) and the Guidelines for Canadian

Drinking Water Quality (GCDWQ) unless otherwise noted, which could be indicated as an

operational guideline (OG). The DWPA and GCDWQ define these parameters and set

aesthetic objectives (AO) and maximum allowable concentrations (MAC).

For more information on specific water quality parameters please contact the RDOS or visit

the Province of BC’s Ministry of Healthy Living and Sport website to find the Drinking Water

Protection Act and Regulation http://www.health.gov.bc.ca/protect/dw_index.html or the

Health Canada website to find the Guidelines for Canadian Drinking Water Quality.

http://www.hc-sc.gc.ca/ewh-semt/pubs/water-eau/index-eng.php#tech_doc

All accredited laboratory tests for 2014 were performed by Caro Environmental (Kelowna,

B.C.).

5.1. Water Quality Complaints

In October the owner of a mobile home park on 1st St. called saying that the water had a metallic taste, an odour and was warm. Members of her family were no longer drinking the water and they purchased bottled water for drinking. The owner of the property was informed that the watermain on 1st St. is their property and responsibility however the RDOS did flush the main for the owner. A bacteriological sample was drawn at 2637 1st St. after flushing the main and the results were negative for both Total Coliforms and Escherichia coli.

Regional District of Okanagan Similkameen Olalla Annual Water Quality Report – 2014

5

5.2. Potable Water Test Results

A comprehensive water analysis (Schedule A) was performed on the untreated

groundwater from the Olalla well on August 26, 2014. None of the tested parameters

exceeded the GCDWQ.

No significant changes were noted in the tested parameters for 2014.

5.3. Bacteriological Results

The following in a summary of the bacteriological testing results from the Olalla water

system.

# of Positives

# of

Samples

Total

Coliforms

Escherichia

coli

Accredited Bacteriological Samples

(Caro Environmental, Kelowna B.C.) 54 1 0

Colilert © Bacteriological Samples

(RDOS In-house testing) 0 0 0

Table 3: Source and Distribution Water Bacteriological Testing Summary for 2014

Regional District of Okanagan Similkameen Olalla Annual Water Quality Report – 2014

6

6. Water System Notifications

6.1. Boil Water Notices (BWN)

None issued for 2014.

6.2. Water Quality Advisories (WQA)

None issued for 2014.

6.3. Do Not Use Orders

None issued for 2014.

7. Program Updates and Status

7.1. Water Quality Monitoring Program

The Water Quality Monitoring Program was updated in November, 2013.

7.2. Emergency Response Plan

The Emergency Response Plan was revised in November, 2013.

7.3. Cross Connection Control Program

The RDOS continued work in 2014 towards implementing an official Cross Connection

Control program. The Public Works Department does address specific cross

connection control issues with the current water system bylaws as they arise.

7.4. System Maintenance/Upgrades

In November the road crossing on 8th St. was completed to connect 8th St. to the new

water supply main.

7.5. Capital Works

No capital works were completed in 2014.

7.6. Future System Upgrades

The RDOS will be looking into upgrading the Programmable Logic Controller (PLC)

along with the addition of a SCADA system for the Olalla system in 2015.

Regional District of Okanagan Similkameen Olalla Annual Water Quality Report – 2014

7

8. Budget

The total operational expenses for the Olalla water system in 2014 were $67,652 (Total

Expenses less Depreciation, Debt Interest, Debt Principal, Transfer Interest to Reserve and

Transfer to Reserve) with $125,365 budgeted (Total Budgeted less Depreciation, Debt

Interest, Debt Principal, Transfer Interest to Reserve and Transfer to Reserves). A copy of

the 2014 budget is provided in Appendix D.

9. Summary

All tested water quality parameters for the Olalla water system met the Guidelines for

Canadian Drinking Water Quality in 2014 with the exception one routine bacteriological

sample which resulted in low level counts for Total Coliforms. The RDOS continues to work

on reviewing and upgrading the various programs that support facilitating the highest quality

of water possible.

APPENDIX A

REPORTED TO Regional District of Okanagan Similkameen

101 Martin Street

Penticton, BC V2A 5J9

TEL

FAX

1-250-490-4106

(250) 492-0063

ATTENTION Rob Palmer WORK ORDER

General Comments:

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate

regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing

methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition

document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage

resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis .

Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Issued By: Jennifer Shanko, AScT

Administration Coordinator

#110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue

Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7

Tel: 604-279-1499 Fax: 604-279-1599 Tel: 250-765-9646 Fax: 250-765-3893 Tel: 780-489-9100 Fax: 780-489-9700

www.caro.ca

Locations:

4010555

Work Order Comments:

Custody Seal Intact when Rec'd at CARO.

Please contact CARO if more information is needed or to provide feedback on our services.

CERTIFICATE OF ANALYSIS

PO NUMBER RECEIVED / TEMP Jan-14-14 08:30 / 5°C

PROJECT Olalla Water System REPORTED Jan-16-14

PROJECT INFO COC NUMBER 09018

Page 1 of 3CARO Analytical ServicesRev 12/10/13

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water SystemWORK ORDER

REPORTED

4010555

Jan-16-14

ANALYSIS INFORMATION

Method Reference (* = modified from)

Preparation AnalysisAnalysis Description Location

KelownaAPHA 9222 *E. coli (by CCA) N/A

KelownaAPHA 9222 *Total Coliforms (by CCA) N/A

Note: The numbers in brackets represent the year that the method was published/approved

Method Reference Descriptions:

APHA Standard Methods for the Examination of Water and Wastewater , American Public Health

Association

Glossary of Terms:

MRL Method Reporting Limit

< Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to

various factors such as dilutions, limited sample volume, high moisture, or interferences

AO Aesthetic objective

MAC Maximum acceptable concentration (health-related guideline)

Colony Forming Units per 100 mLCFU/100mL

Page 2 of 3CARO Analytical ServicesRev 12/10/13

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water SystemWORK ORDER

REPORTED

4010555

Jan-16-14

SAMPLE ANALYTICAL DATA

AnalyteResult /

Recovery

MRL /

Limit Units Prepared Notes

Canadian

DWQ

Guideline

Analyzed

Microbiological Parameters

Sample ID: Pump House (4010555-01) [Water] Sampled: Jan-13-14 08:05

Jan-15-14CFU/100mLColiforms, Total < 1 1MAC < 1 Jan-14-14

CFU/100mL< 1E. coli Jan-15-141MAC < 1 Jan-14-14

Sample ID: 12th St. (4010555-02) [Water] Sampled: Jan-13-14 08:18

Jan-15-14CFU/100mLColiforms, Total < 1 1MAC < 1 Jan-14-14

CFU/100mL< 1E. coli Jan-15-141MAC < 1 Jan-14-14

Page 3 of 3CARO Analytical ServicesRev 12/10/13

REPORTED TO Regional District of Okanagan Similkameen

101 Martin Street

Penticton, BC V2A 5J9

TEL

FAX

1-250-490-4106

(250) 492-0063

ATTENTION Rob Palmer WORK ORDER

General Comments:

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate

regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing

methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition

document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage

resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis .

Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Issued By: Jennifer Shanko, AScT

Administration Coordinator

#110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue

Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7

Tel: 604-279-1499 Fax: 604-279-1599 Tel: 250-765-9646 Fax: 250-765-3893 Tel: 780-489-9100 Fax: 780-489-9700

www.caro.ca

Locations:

4011339

Work Order Comments:

Custody Seals intact when received at Caro!

Please contact CARO if more information is needed or to provide feedback on our services.

CERTIFICATE OF ANALYSIS

PO NUMBER RECEIVED / TEMP Jan-29-14 09:45 / 3°C

PROJECT Olalla Water System REPORTED Jan-31-14

PROJECT INFO COC NUMBER B 01387

Page 1 of 3CARO Analytical ServicesRev 12/10/13

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water SystemWORK ORDER

REPORTED

4011339

Jan-31-14

ANALYSIS INFORMATION

Method Reference (* = modified from)

Preparation AnalysisAnalysis Description Location

KelownaAPHA 9222 *E. coli (by CCA) N/A

KelownaAPHA 9222 *Total Coliforms (by CCA) N/A

Note: The numbers in brackets represent the year that the method was published/approved

Method Reference Descriptions:

APHA Standard Methods for the Examination of Water and Wastewater , American Public Health

Association

Glossary of Terms:

MRL Method Reporting Limit

< Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to

various factors such as dilutions, limited sample volume, high moisture, or interferences

AO Aesthetic objective

MAC Maximum acceptable concentration (health-related guideline)

Colony Forming Units per 100 mLCFU/100mL

Page 2 of 3CARO Analytical ServicesRev 12/10/13

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water SystemWORK ORDER

REPORTED

4011339

Jan-31-14

SAMPLE ANALYTICAL DATA

AnalyteResult /

Recovery

MRL /

Limit Units Prepared Notes

Canadian

DWQ

Guideline

Analyzed

Microbiological Parameters

Sample ID: Pump House (4011339-01) [Water] Sampled: Jan-28-14 08:10

Jan-30-14CFU/100mLColiforms, Total < 1 1MAC < 1 Jan-29-14

CFU/100mL< 1E. coli Jan-30-141MAC < 1 Jan-29-14

Sample ID: N Main (4011339-02) [Water] Sampled: Jan-28-14 08:20

Jan-30-14CFU/100mLColiforms, Total < 1 1MAC < 1 Jan-29-14

CFU/100mL< 1E. coli Jan-30-141MAC < 1 Jan-29-14

Page 3 of 3CARO Analytical ServicesRev 12/10/13

REPORTED TO Regional District of Okanagan Similkameen

101 Martin Street

Penticton, BC V2A 5J9

TEL

FAX

1-250-490-4106

(250) 492-0063

ATTENTION Rob Palmer WORK ORDER

General Comments:

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate

regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing

methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition

document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage

resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis .

Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Issued By: Jennifer Shanko, AScT

Administration Coordinator

#110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue

Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7

Tel: 604-279-1499 Fax: 604-279-1599 Tel: 250-765-9646 Fax: 250-765-3893 Tel: 780-489-9100 Fax: 780-489-9700

www.caro.ca

Locations:

4020502

Work Order Comments:

Custody Seals intact when received at Caro!

Please contact CARO if more information is needed or to provide feedback on our services.

CERTIFICATE OF ANALYSIS

PO NUMBER RECEIVED / TEMP Feb-12-14 08:45 / 3°C

PROJECT Olalla Water System REPORTED Feb-14-14

PROJECT INFO COC NUMBER B 09871

Page 1 of 3CARO Analytical ServicesRev 12/10/13 Page 1 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water System

WORK ORDER

REPORTED

4020502

Feb-14-14

ANALYSIS INFORMATION

Method Reference (* = modified from)

Preparation AnalysisAnalysis Description Location

KelownaAPHA 9222 *E. coli (by CCA) N/A

KelownaAPHA 9222 *Total Coliforms (by CCA) N/A

Note: The numbers in brackets represent the year that the method was published/approved

Method Reference Descriptions:

APHA Standard Methods for the Examination of Water and Wastewater , American Public Health

Association

Glossary of Terms:

MRL Method Reporting Limit

< Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to

various factors such as dilutions, limited sample volume, high moisture, or interferences

AO Aesthetic objective

MAC Maximum acceptable concentration (health-related guideline)

Colony Forming Units per 100 mLCFU/100mL

Page 2 of 3CARO Analytical ServicesRev 12/10/13 Page 2 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water System

WORK ORDER

REPORTED

4020502

Feb-14-14

SAMPLE ANALYTICAL DATA

AnalyteResult /

Recovery

MRL /

Limit Units Prepared Notes

Canadian

DWQ

Guideline

Analyzed

Microbiological Parameters

Sample ID: Pump House (4020502-01) [Water] Sampled: Feb-11-14 08:08

Feb-13-14CFU/100mLColiforms, Total < 1 1MAC < 1 Feb-12-14

CFU/100mL< 1E. coli Feb-13-141MAC < 1 Feb-12-14

Sample ID: N Main (4020502-02) [Water] Sampled: Feb-11-14 09:35

Feb-13-14CFU/100mLColiforms, Total 2 1MAC < 1 Feb-12-14

CFU/100mL< 1E. coli Feb-13-141MAC < 1 Feb-12-14

Page 3 of 3CARO Analytical ServicesRev 12/10/13 Page 3 of 3

REPORTED TO Regional District of Okanagan Similkameen

101 Martin Street

Penticton, BC V2A 5J9

TEL

FAX

1-250-490-4106

(250) 492-0063

ATTENTION Rob Palmer WORK ORDER

General Comments:

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate

regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing

methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition

document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage

resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis .

Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Issued By: Jennifer Shanko, AScT

Administration Coordinator

#110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue

Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7

Tel: 604-279-1499 Fax: 604-279-1599 Tel: 250-765-9646 Fax: 250-765-3893 Tel: 780-489-9100 Fax: 780-489-9700

www.caro.ca

Locations:

4020715

Please contact CARO if more information is needed or to provide feedback on our services.

CERTIFICATE OF ANALYSIS

PO NUMBER RECEIVED / TEMP Feb-14-14 16:37 / 8°C

PROJECT Olalla Water System REPORTED Feb-17-14

PROJECT INFO COC NUMBER B05259

Page 1 of 3CARO Analytical ServicesRev 12/10/13 Page 1 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water System

WORK ORDER

REPORTED

4020715

Feb-17-14

ANALYSIS INFORMATION

Method Reference (* = modified from)

Preparation AnalysisAnalysis Description Location

KelownaAPHA 9222 *E. coli (by CCA) N/A

KelownaAPHA 9222 *Total Coliforms (by CCA) N/A

Note: The numbers in brackets represent the year that the method was published/approved

Method Reference Descriptions:

APHA Standard Methods for the Examination of Water and Wastewater , American Public Health

Association

Glossary of Terms:

MRL Method Reporting Limit

< Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to

various factors such as dilutions, limited sample volume, high moisture, or interferences

AO Aesthetic objective

MAC Maximum acceptable concentration (health-related guideline)

Colony Forming Units per 100 mLCFU/100mL

Page 2 of 3CARO Analytical ServicesRev 12/10/13 Page 2 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water System

WORK ORDER

REPORTED

4020715

Feb-17-14

SAMPLE ANALYTICAL DATA

AnalyteResult /

Recovery

MRL /

Limit Units Prepared Notes

Canadian

DWQ

Guideline

Analyzed

Microbiological Parameters

Sample ID: N Main St. (Resample) (4020715-01) [Water] Sampled: Feb-14-14 08:28

Feb-15-14CFU/100mLColiforms, Total < 1 1MAC < 1 Feb-14-14

CFU/100mL< 1E. coli Feb-15-141MAC < 1 Feb-14-14

Page 3 of 3CARO Analytical ServicesRev 12/10/13 Page 3 of 3

REPORTED TO Regional District of Okanagan Similkameen

101 Martin Street

Penticton, BC V2A 5J9

TEL

FAX

1-250-490-4106

(250) 492-0063

ATTENTION Rob Palmer WORK ORDER

General Comments:

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate

regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing

methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition

document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage

resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis .

Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Issued By: Jennifer Shanko, AScT

Administration Coordinator

#110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue

Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7

Tel: 604-279-1499 Fax: 604-279-1599 Tel: 250-765-9646 Fax: 250-765-3893 Tel: 780-489-9100 Fax: 780-489-9700

www.caro.ca

Locations:

4021268

Work Order Comments:

Custody Seal intact when received at Caro

Please contact CARO if more information is needed or to provide feedback on our services.

CERTIFICATE OF ANALYSIS

PO NUMBER RECEIVED / TEMP Feb-26-14 09:20 / 4°C

PROJECT Olalla Water System REPORTED Feb-27-14

PROJECT INFO COC NUMBER B 10225

Page 1 of 3CARO Analytical ServicesRev 12/10/13 Page 1 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water System

WORK ORDER

REPORTED

4021268

Feb-27-14

ANALYSIS INFORMATION

Method Reference (* = modified from)

Preparation AnalysisAnalysis Description Location

KelownaAPHA 9222 *E. coli (by CCA) N/A

KelownaAPHA 9222 *Total Coliforms (by CCA) N/A

Note: The numbers in brackets represent the year that the method was published/approved

Method Reference Descriptions:

APHA Standard Methods for the Examination of Water and Wastewater , American Public Health

Association

Glossary of Terms:

MRL Method Reporting Limit

< Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to

various factors such as dilutions, limited sample volume, high moisture, or interferences

AO Aesthetic objective

MAC Maximum acceptable concentration (health-related guideline)

Colony Forming Units per 100 mLCFU/100mL

Page 2 of 3CARO Analytical ServicesRev 12/10/13 Page 2 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water System

WORK ORDER

REPORTED

4021268

Feb-27-14

SAMPLE ANALYTICAL DATA

AnalyteResult /

Recovery

MRL /

Limit Units Prepared Notes

Canadian

DWQ

Guideline

Analyzed

Microbiological Parameters

Sample ID: Pump House (4021268-01) [Water] Sampled: Feb-25-14 10:38

Feb-27-14CFU/100mLColiforms, Total < 1 1MAC < 1 Feb-26-14

CFU/100mL< 1E. coli Feb-27-141MAC < 1 Feb-26-14

Sample ID: 12th St. (4021268-02) [Water] Sampled: Feb-25-14 10:54

Feb-27-14CFU/100mLColiforms, Total < 1 1MAC < 1 Feb-26-14

CFU/100mL< 1E. coli Feb-27-141MAC < 1 Feb-26-14

Sample ID: N Main St. (4021268-03) [Water] Sampled: Feb-25-14 11:07

Feb-27-14CFU/100mLColiforms, Total < 1 1MAC < 1 Feb-26-14

CFU/100mL< 1E. coli Feb-27-141MAC < 1 Feb-26-14

Page 3 of 3CARO Analytical ServicesRev 12/10/13 Page 3 of 3

REPORTED TO Regional District of Okanagan Similkameen

101 Martin Street

Penticton, BC V2A 5J9

TEL

FAX

1-250-490-4106

(250) 492-0063

ATTENTION Rob Palmer WORK ORDER

General Comments:

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate

regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing

methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition

document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage

resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis .

Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Issued By: Jennifer Shanko, AScT

Administration Coordinator

#110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue

Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7

Tel: 604-279-1499 Fax: 604-279-1599 Tel: 250-765-9646 Fax: 250-765-3893 Tel: 780-489-9100 Fax: 780-489-9700

www.caro.ca

Locations:

4030479

Work Order Comments:

Custody Seal Intact when received by CARO.

Please contact CARO if more information is needed or to provide feedback on our services.

CERTIFICATE OF ANALYSIS

PO NUMBER RECEIVED / TEMP Mar-11-14 09:50 / 3°C

PROJECT Olalla Water System REPORTED Mar-13-14

PROJECT INFO COC NUMBER B10447

Page 1 of 3CARO Analytical ServicesRev 12/10/13 Page 1 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water System

WORK ORDER

REPORTED

4030479

Mar-13-14

ANALYSIS INFORMATION

Method Reference (* = modified from)

Preparation AnalysisAnalysis Description Location

KelownaAPHA 9222 *E. coli (by CCA) N/A

KelownaAPHA 9222 *Total Coliforms (by CCA) N/A

Note: The numbers in brackets represent the year that the method was published/approved

Method Reference Descriptions:

APHA Standard Methods for the Examination of Water and Wastewater , American Public Health

Association

Glossary of Terms:

MRL Method Reporting Limit

< Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to

various factors such as dilutions, limited sample volume, high moisture, or interferences

AO Aesthetic objective

MAC Maximum acceptable concentration (health-related guideline)

Colony Forming Units per 100 mLCFU/100mL

Page 2 of 3CARO Analytical ServicesRev 12/10/13 Page 2 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water System

WORK ORDER

REPORTED

4030479

Mar-13-14

SAMPLE ANALYTICAL DATA

AnalyteResult /

Recovery

MRL /

Limit Units Prepared Notes

Canadian

DWQ

Guideline

Analyzed

Microbiological Parameters

Sample ID: Pump House (4030479-01) [Water] Sampled: Mar-10-14 08:12

Mar-12-14CFU/100mLColiforms, Total < 1 1MAC < 1 Mar-11-14

CFU/100mL< 1E. coli Mar-12-141MAC < 1 Mar-11-14

Sample ID: N Main St. (4030479-02) [Water] Sampled: Mar-10-14 08:41

Mar-12-14CFU/100mLColiforms, Total < 1 1MAC < 1 Mar-11-14

CFU/100mL< 1E. coli Mar-12-141MAC < 1 Mar-11-14

Page 3 of 3CARO Analytical ServicesRev 12/10/13 Page 3 of 3

REPORTED TO Regional District of Okanagan Similkameen

101 Martin Street

Penticton, BC V2A 5J9

TEL

FAX

1-250-490-4106

(250) 492-0063

ATTENTION Rob Palmer WORK ORDER

General Comments:

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate

regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing

methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition

document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage

resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis .

Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Issued By: Sara Gulenchyn For Jennifer Shanko, AScT

Administration Coordinator

#110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue

Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7

Tel: 604-279-1499 Fax: 604-279-1599 Tel: 250-765-9646 Fax: 250-765-3893 Tel: 780-489-9100 Fax: 780-489-9700

www.caro.ca

Locations:

4031351

Work Order Comments:

Custody Seal Intact When Received at CARO.

Please contact CARO if more information is needed or to provide feedback on our services.

CERTIFICATE OF ANALYSIS

PO NUMBER RECEIVED / TEMP Mar-26-14 08:40 / 7°C

PROJECT Olalla Water System REPORTED Mar-28-14

PROJECT INFO COC NUMBER 09869

Page 1 of 3CARO Analytical ServicesRev 03/14/14 Page 1 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water System

WORK ORDER

REPORTED

4031351

Mar-28-14

ANALYSIS INFORMATION

Method Reference (* = modified from)

Preparation AnalysisAnalysis Description Location

KelownaAPHA 9222 *E. coli (by CCA) N/A

KelownaAPHA 9222 *Total Coliforms (by CCA) N/A

Note: The numbers in brackets represent the year that the method was published/approved

Method Reference Descriptions:

APHA Standard Methods for the Examination of Water and Wastewater , American Public Health

Association

Glossary of Terms:

MRL Method Reporting Limit

< Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to

various factors such as dilutions, limited sample volume, high moisture, or interferences

AO Aesthetic objective

MAC Maximum acceptable concentration (health-related guideline)

Colony Forming Units per 100 mLCFU/100mL

Page 2 of 3CARO Analytical ServicesRev 03/14/14 Page 2 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water System

WORK ORDER

REPORTED

4031351

Mar-28-14

SAMPLE ANALYTICAL DATA

AnalyteResult /

Recovery

MRL /

Limit Units Prepared Notes

Canadian

DWQ

Guideline

Analyzed

Microbiological Parameters

Sample ID: Pump House (4031351-01) [Water] Sampled: Mar-25-14 08:20

Mar-27-14CFU/100mLColiforms, Total < 1 1MAC < 1 Mar-26-14

CFU/100mL< 1E. coli Mar-27-141MAC < 1 Mar-26-14

Sample ID: 12th St. (4031351-02) [Water] Sampled: Mar-25-14 08:25

Mar-27-14CFU/100mLColiforms, Total < 1 1MAC < 1 Mar-26-14

CFU/100mL< 1E. coli Mar-27-141MAC < 1 Mar-26-14

Page 3 of 3CARO Analytical ServicesRev 03/14/14 Page 3 of 3

REPORTED TO Regional District of Okanagan Similkameen

101 Martin Street

Penticton, BC V2A 5J9

TEL

FAX

1-250-490-4106

(250) 492-0063

ATTENTION Rob Palmer WORK ORDER

General Comments:

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate

regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing

methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition

document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage

resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis .

Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Issued By: Jennifer Shanko, AScT

Administration Coordinator

#110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue

Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7

Tel: 604-279-1499 Fax: 604-279-1599 Tel: 250-765-9646 Fax: 250-765-3893 Tel: 780-489-9100 Fax: 780-489-9700

www.caro.ca

Locations:

4040638

Work Order Comments:

Custody Seal Intact When Received at CARO.

Please contact CARO if more information is needed or to provide feedback on our services.

CERTIFICATE OF ANALYSIS

PO NUMBER RECEIVED / TEMP Apr-10-14 08:50 / 8°C

PROJECT Olalla Water System REPORTED Apr-14-14

PROJECT INFO COC NUMBER 10441

Page 1 of 3CARO Analytical ServicesRev 03/14/14 Page 1 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water System

WORK ORDER

REPORTED

4040638

Apr-14-14

ANALYSIS INFORMATION

Method Reference (* = modified from)

Preparation AnalysisAnalysis Description Location

KelownaAPHA 9222 *E. coli (by CCA) N/A

KelownaAPHA 9222 *Total Coliforms (by CCA) N/A

Note: The numbers in brackets represent the year that the method was published/approved

Method Reference Descriptions:

APHA Standard Methods for the Examination of Water and Wastewater , American Public Health

Association

Glossary of Terms:

MRL Method Reporting Limit

< Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to

various factors such as dilutions, limited sample volume, high moisture, or interferences

AO Aesthetic objective

MAC Maximum acceptable concentration (health-related guideline)

Colony Forming Units per 100 mLCFU/100mL

Page 2 of 3CARO Analytical ServicesRev 03/14/14 Page 2 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water System

WORK ORDER

REPORTED

4040638

Apr-14-14

SAMPLE ANALYTICAL DATA

AnalyteResult /

Recovery

MRL /

Limit Units Prepared Notes

Canadian

DWQ

Guideline

Analyzed

Microbiological Parameters

Sample ID: Pump House (4040638-01) [Water] Sampled: Apr-09-14 07:10

Apr-11-14CFU/100mLColiforms, Total < 1 1MAC < 1 Apr-10-14

CFU/100mL< 1E. coli Apr-11-141MAC < 1 Apr-10-14

Sample ID: N Main (4040638-02) [Water] Sampled: Apr-09-14 07:20

Apr-11-14CFU/100mLColiforms, Total < 1 1MAC < 1 Apr-10-14

CFU/100mL< 1E. coli Apr-11-141MAC < 1 Apr-10-14

Page 3 of 3CARO Analytical ServicesRev 03/14/14 Page 3 of 3

REPORTED TO Regional District of Okanagan Similkameen

101 Martin Street

Penticton, BC V2A 5J9

TEL

FAX

1-250-490-4106

(250) 492-0063

ATTENTION Rob Palmer WORK ORDER

General Comments:

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate

regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing

methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition

document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage

resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis .

Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Issued By: Jennifer Shanko, AScT

Administration Coordinator

#110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue

Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7

Tel: 604-279-1499 Fax: 604-279-1599 Tel: 250-765-9646 Fax: 250-765-3893 Tel: 780-489-9100 Fax: 780-489-9700

www.caro.ca

Locations:

4041373

Work Order Comments:

Custody Seal Intact When Received at CARO.

Please contact CARO if more information is needed or to provide feedback on our services.

CERTIFICATE OF ANALYSIS

PO NUMBER RECEIVED / TEMP Apr-24-14 09:00 / 7°C

PROJECT Olalla Water System REPORTED Apr-28-14

PROJECT INFO COC NUMBER 10437

Page 1 of 3CARO Analytical ServicesRev 03/14/14 Page 1 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water System

WORK ORDER

REPORTED

4041373

Apr-28-14

ANALYSIS INFORMATION

Method Reference (* = modified from)

Preparation AnalysisAnalysis Description Location

KelownaAPHA 9222 *E. coli (by CCA) N/A

KelownaAPHA 9222 *Total Coliforms (by CCA) N/A

Note: The numbers in brackets represent the year that the method was published/approved

Method Reference Descriptions:

APHA Standard Methods for the Examination of Water and Wastewater , American Public Health

Association

Glossary of Terms:

MRL Method Reporting Limit

< Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to

various factors such as dilutions, limited sample volume, high moisture, or interferences

AO Aesthetic objective

MAC Maximum acceptable concentration (health-related guideline)

Colony Forming Units per 100 mLCFU/100mL

Page 2 of 3CARO Analytical ServicesRev 03/14/14 Page 2 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water System

WORK ORDER

REPORTED

4041373

Apr-28-14

SAMPLE ANALYTICAL DATA

AnalyteResult /

Recovery

MRL /

Limit Units Prepared Notes

Canadian

DWQ

Guideline

Analyzed

Microbiological Parameters

Sample ID: Pump House (4041373-01) [Water] Sampled: Apr-23-14 08:07

Apr-25-14CFU/100mLColiforms, Total < 1 1MAC < 1 Apr-24-14

CFU/100mL< 1E. coli Apr-25-141MAC < 1 Apr-24-14

Sample ID: 12th St. (4041373-02) [Water] Sampled: Apr-23-14 08:22

Apr-25-14CFU/100mLColiforms, Total < 1 1MAC < 1 Apr-24-14

CFU/100mL< 1E. coli Apr-25-141MAC < 1 Apr-24-14

Page 3 of 3CARO Analytical ServicesRev 03/14/14 Page 3 of 3

REPORTED TO Regional District of Okanagan Similkameen

101 Martin Street

Penticton, BC V2A 5J9

TEL

FAX

1-250-490-4106

(250) 492-0063

ATTENTION Rob Palmer WORK ORDER

General Comments:

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate

regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing

methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition

document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage

resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis .

Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Issued By: Jennifer Shanko, AScT

Administration Coordinator

#110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue

Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7

Tel: 604-279-1499 Fax: 604-279-1599 Tel: 250-765-9646 Fax: 250-765-3893 Tel: 780-489-9100 Fax: 780-489-9700

www.caro.ca

Locations:

4050317

Work Order Comments:

Custody Seal Intact when received by CARO

Please contact CARO if more information is needed or to provide feedback on our services.

CERTIFICATE OF ANALYSIS

PO NUMBER RECEIVED / TEMP May-07-14 07:45 / 12°C

PROJECT Olalla Water System REPORTED May-09-14

PROJECT INFO COC NUMBER B20333

Page 1 of 3CARO Analytical ServicesRev 04/29/14 Page 1 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water System

WORK ORDER

REPORTED

4050317

May-09-14

ANALYSIS INFORMATION

Method Reference (* = modified from)

Preparation AnalysisAnalysis Description Location

KelownaAPHA 9222 *E. coli (by CCA) N/A

KelownaAPHA 9222 *Total Coliforms (by CCA) N/A

Note: The numbers in brackets represent the year that the method was published/approved

Method Reference Descriptions:

APHA Standard Methods for the Examination of Water and Wastewater , American Public Health

Association

Glossary of Terms:

MRL Method Reporting Limit

< Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to

various factors such as dilutions, limited sample volume, high moisture, or interferences

AO Aesthetic objective

MAC Maximum acceptable concentration (health-related guideline)

Colony Forming Units per 100 mLCFU/100mL

Page 2 of 3CARO Analytical ServicesRev 04/29/14 Page 2 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water System

WORK ORDER

REPORTED

4050317

May-09-14

SAMPLE ANALYTICAL DATA

AnalyteResult /

Recovery

MRL /

Limit Units Prepared Notes

Canadian

DWQ

Guideline

Analyzed

Microbiological Parameters

Sample ID: Pump House (4050317-01) [Water] Sampled: May-06-14 07:45

May-08-14CFU/100mLColiforms, Total < 1 1MAC < 1 May-07-14

CFU/100mL< 1E. coli May-08-141MAC < 1 May-07-14

Sample ID: N Main (4050317-02) [Water] Sampled: May-06-14 07:55

May-08-14CFU/100mLColiforms, Total < 1 1MAC < 1 May-07-14

CFU/100mL< 1E. coli May-08-141MAC < 1 May-07-14

Page 3 of 3CARO Analytical ServicesRev 04/29/14 Page 3 of 3

REPORTED TO Regional District of Okanagan Similkameen

101 Martin Street

Penticton, BC V2A 5J9

TEL

FAX

1-250-490-4106

(250) 492-0063

ATTENTION Rob Palmer WORK ORDER

General Comments:

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate

regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing

methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition

document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage

resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis .

Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Issued By: Jennifer Shanko, AScT

Administration Coordinator

#110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue

Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7

Tel: 604-279-1499 Fax: 604-279-1599 Tel: 250-765-9646 Fax: 250-765-3893 Tel: 780-489-9100 Fax: 780-489-9700

www.caro.ca

Locations:

4051121

Work Order Comments:

Custody Seal Intact when received by CARO.

Please contact CARO if more information is needed or to provide feedback on our services.

CERTIFICATE OF ANALYSIS

PO NUMBER RECEIVED / TEMP May-21-14 08:30 / 11°C

PROJECT Olalla Water System REPORTED May-23-14

PROJECT INFO COC NUMBER B10507

Page 1 of 3CARO Analytical ServicesRev 04/29/14 Page 1 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water System

WORK ORDER

REPORTED

4051121

May-23-14

ANALYSIS INFORMATION

Method Reference (* = modified from)

Preparation AnalysisAnalysis Description Location

KelownaAPHA 9222 *E. coli (by CCA) N/A

KelownaAPHA 9222 *Total Coliforms (by CCA) N/A

Note: The numbers in brackets represent the year that the method was published/approved

Method Reference Descriptions:

APHA Standard Methods for the Examination of Water and Wastewater , American Public Health

Association

Glossary of Terms:

MRL Method Reporting Limit

< Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to

various factors such as dilutions, limited sample volume, high moisture, or interferences

AO Aesthetic objective

MAC Maximum acceptable concentration (health-related guideline)

Colony Forming Units per 100 mLCFU/100mL

Page 2 of 3CARO Analytical ServicesRev 04/29/14 Page 2 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water System

WORK ORDER

REPORTED

4051121

May-23-14

SAMPLE ANALYTICAL DATA

AnalyteResult /

Recovery

MRL /

Limit Units Prepared Notes

Canadian

DWQ

Guideline

Analyzed

Microbiological Parameters

Sample ID: Pump House (4051121-01) [Water] Sampled: May-20-14 07:30

May-22-14CFU/100mLColiforms, Total < 1 1MAC < 1 May-21-14

CFU/100mL< 1E. coli May-22-141MAC < 1 May-21-14

Sample ID: 12th St. (4051121-02) [Water] Sampled: May-20-14 07:40

May-22-14CFU/100mLColiforms, Total < 1 1MAC < 1 May-21-14

CFU/100mL< 1E. coli May-22-141MAC < 1 May-21-14

Page 3 of 3CARO Analytical ServicesRev 04/29/14 Page 3 of 3

REPORTED TO Regional District of Okanagan Similkameen

101 Martin Street

Penticton, BC V2A 5J9

TEL

FAX

1-250-490-4106

(250) 492-0063

ATTENTION Rob Palmer WORK ORDER

General Comments:

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate

regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing

methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition

document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage

resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis .

Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Issued By: Jennifer Shanko, AScT

Administration Coordinator

#110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue

Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7

Tel: 604-279-1499 Fax: 604-279-1599 Tel: 250-765-9646 Fax: 250-765-3893 Tel: 780-489-9100 Fax: 780-489-9700

www.caro.ca

Locations:

4060101

Work Order Comments:

Custody Seal Intact When Received at CARO.

Please contact CARO if more information is needed or to provide feedback on our services.

CERTIFICATE OF ANALYSIS

PO NUMBER RECEIVED / TEMP Jun-03-14 10:10 / 8°C

PROJECT Olalla Water System REPORTED Jun-05-14

PROJECT INFO COC NUMBER 10426

Page 1 of 3CARO Analytical ServicesRev 04/29/14 Page 1 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water System

WORK ORDER

REPORTED

4060101

Jun-05-14

ANALYSIS INFORMATION

Method Reference (* = modified from)

Preparation AnalysisAnalysis Description Location

KelownaAPHA 9222 *E. coli (by CCA) N/A

KelownaAPHA 9222 *Total Coliforms (by CCA) N/A

Note: The numbers in brackets represent the year that the method was published/approved

Method Reference Descriptions:

APHA Standard Methods for the Examination of Water and Wastewater , American Public Health

Association

Glossary of Terms:

MRL Method Reporting Limit

< Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to

various factors such as dilutions, limited sample volume, high moisture, or interferences

AO Aesthetic objective

MAC Maximum acceptable concentration (health-related guideline)

Colony Forming Units per 100 mLCFU/100mL

Page 2 of 3CARO Analytical ServicesRev 04/29/14 Page 2 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water System

WORK ORDER

REPORTED

4060101

Jun-05-14

SAMPLE ANALYTICAL DATA

AnalyteResult /

Recovery

MRL /

Limit Units Prepared Notes

Canadian

DWQ

Guideline

Analyzed

Microbiological Parameters

Sample ID: Pump House (4060101-01) [Water] Sampled: Jun-02-14 07:20

Jun-04-14CFU/100mLColiforms, Total < 1 1MAC < 1 Jun-03-14

CFU/100mL< 1E. coli Jun-04-141MAC < 1 Jun-03-14

Sample ID: N Main St. (4060101-02) [Water] Sampled: Jun-02-14 07:32

Jun-04-14CFU/100mLColiforms, Total < 1 1MAC < 1 Jun-03-14

CFU/100mL< 1E. coli Jun-04-141MAC < 1 Jun-03-14

Page 3 of 3CARO Analytical ServicesRev 04/29/14 Page 3 of 3

REPORTED TO Regional District of Okanagan Similkameen

101 Martin Street

Penticton, BC V2A 5J9

TEL

FAX

1-250-490-4106

(250) 492-0063

ATTENTION Rob Palmer WORK ORDER

General Comments:

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate

regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing

methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition

document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage

resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis .

Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Issued By: Jennifer Shanko, AScT

Administration Coordinator

#110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue

Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7

Tel: 604-279-1499 Fax: 604-279-1599 Tel: 250-765-9646 Fax: 250-765-3893 Tel: 780-489-9100 Fax: 780-489-9700

www.caro.ca

Locations:

4061031

Work Order Comments:

Custody Seals intact when received at Caro

Please contact CARO if more information is needed or to provide feedback on our services.

CERTIFICATE OF ANALYSIS

PO NUMBER RECEIVED / TEMP Jun-17-14 09:20 / 7°C

PROJECT Olalla Water System REPORTED Jun-19-14

PROJECT INFO COC NUMBER B 10657

Page 1 of 3CARO Analytical ServicesRev 04/29/14 Page 1 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water System

WORK ORDER

REPORTED

4061031

Jun-19-14

ANALYSIS INFORMATION

Method Reference (* = modified from)

Preparation AnalysisAnalysis Description Location

KelownaAPHA 9222 *E. coli (by CCA) N/A

KelownaAPHA 9222 *Total Coliforms (by CCA) N/A

Note: The numbers in brackets represent the year that the method was published/approved

Method Reference Descriptions:

APHA Standard Methods for the Examination of Water and Wastewater , American Public Health

Association

Glossary of Terms:

MRL Method Reporting Limit

< Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to

various factors such as dilutions, limited sample volume, high moisture, or interferences

AO Aesthetic objective

MAC Maximum acceptable concentration (health-related guideline)

Colony Forming Units per 100 mLCFU/100mL

Page 2 of 3CARO Analytical ServicesRev 04/29/14 Page 2 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water System

WORK ORDER

REPORTED

4061031

Jun-19-14

SAMPLE ANALYTICAL DATA

AnalyteResult /

Recovery

MRL /

Limit Units Prepared Notes

Canadian

DWQ

Guideline

Analyzed

Microbiological Parameters

Sample ID: Pump House (4061031-01) [Water] Sampled: Jun-16-14 07:10

Jun-18-14CFU/100mLColiforms, Total < 1 1MAC < 1 Jun-17-14

CFU/100mL< 1E. coli Jun-18-141MAC < 1 Jun-17-14

Sample ID: 12th St. (4061031-02) [Water] Sampled: Jun-16-14 07:23

Jun-18-14CFU/100mLColiforms, Total < 1 1MAC < 1 Jun-17-14

CFU/100mL< 1E. coli Jun-18-141MAC < 1 Jun-17-14

Page 3 of 3CARO Analytical ServicesRev 04/29/14 Page 3 of 3

REPORTED TO Regional District of Okanagan Similkameen

101 Martin Street

Penticton, BC V2A 5J9

TEL

FAX

1-250-490-4106

(250) 492-0063

ATTENTION Rob Palmer WORK ORDER

General Comments:

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate

regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing

methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition

document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage

resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis .

Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Issued By: Karin Miyazaki For Jennifer Shanko, AScT

Administration Coordinator

#110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue

Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7

Tel: 604-279-1499 Fax: 604-279-1599 Tel: 250-765-9646 Fax: 250-765-3893 Tel: 780-489-9100 Fax: 780-489-9700

www.caro.ca

Locations:

4070146

Work Order Comments:

Custody Seals intact when received at Caro

Please contact CARO if more information is needed or to provide feedback on our services.

CERTIFICATE OF ANALYSIS

PO NUMBER RECEIVED / TEMP Jul-03-14 09:45 / 4°C

PROJECT Olalla Water System REPORTED Jul-07-14

PROJECT INFO COC NUMBER B 23560

Page 1 of 3CARO Analytical ServicesRev 04/29/14 Page 1 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water System

WORK ORDER

REPORTED

4070146

Jul-07-14

ANALYSIS INFORMATION

Method Reference (* = modified from)

Preparation AnalysisAnalysis Description Location

KelownaAPHA 9222 *E. coli (by CCA) N/A

KelownaAPHA 9222 *Total Coliforms (by CCA) N/A

Note: The numbers in brackets represent the year that the method was published/approved

Method Reference Descriptions:

APHA Standard Methods for the Examination of Water and Wastewater , American Public Health

Association

Glossary of Terms:

MRL Method Reporting Limit

< Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to

various factors such as dilutions, limited sample volume, high moisture, or interferences

AO Aesthetic objective

MAC Maximum acceptable concentration (health-related guideline)

Colony Forming Units per 100 mLCFU/100mL

Page 2 of 3CARO Analytical ServicesRev 04/29/14 Page 2 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water System

WORK ORDER

REPORTED

4070146

Jul-07-14

SAMPLE ANALYTICAL DATA

AnalyteResult /

Recovery

MRL /

Limit Units Prepared Notes

Canadian

DWQ

Guideline

Analyzed

Microbiological Parameters

Sample ID: Pump House (4070146-01) [Water] Sampled: Jul-02-14 07:11

Jul-04-14CFU/100mLColiforms, Total < 1 1MAC < 1 Jul-03-14

CFU/100mL< 1E. coli Jul-04-141MAC < 1 Jul-03-14

Sample ID: N Main St. (4070146-02) [Water] Sampled: Jul-02-14 07:33

Jul-04-14CFU/100mLColiforms, Total < 1 1MAC < 1 Jul-03-14

CFU/100mL< 1E. coli Jul-04-141MAC < 1 Jul-03-14

Page 3 of 3CARO Analytical ServicesRev 04/29/14 Page 3 of 3

REPORTED TO Regional District of Okanagan Similkameen

101 Martin Street

Penticton, BC V2A 5J9

TEL

FAX

1-250-490-4106

(250) 492-0063

ATTENTION Rob Palmer WORK ORDER

General Comments:

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate

regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing

methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition

document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage

resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis .

Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Issued By: Jennifer Shanko, AScT

Administration Coordinator

#110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue

Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7

Tel: 604-279-1499 Fax: 604-279-1599 Tel: 250-765-9646 Fax: 250-765-3893 Tel: 780-489-9100 Fax: 780-489-9700

www.caro.ca

Locations:

4070941

Work Order Comments:

Custody seal intact when received by CARO.

Please contact CARO if more information is needed or to provide feedback on our services.

CERTIFICATE OF ANALYSIS

PO NUMBER RECEIVED / TEMP Jul-15-14 10:00 / 8°C

PROJECT Olalla Water System REPORTED Jul-17-14

PROJECT INFO COC NUMBER 05793

Page 1 of 3CARO Analytical ServicesRev 04/29/14 Page 1 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water System

WORK ORDER

REPORTED

4070941

Jul-17-14

ANALYSIS INFORMATION

Method Reference (* = modified from)

Preparation AnalysisAnalysis Description Location

KelownaAPHA 9222 *E. coli (by CCA) N/A

KelownaAPHA 9222 *Total Coliforms (by CCA) N/A

Note: The numbers in brackets represent the year that the method was published/approved

Method Reference Descriptions:

APHA Standard Methods for the Examination of Water and Wastewater , American Public Health

Association

Glossary of Terms:

MRL Method Reporting Limit

< Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to

various factors such as dilutions, limited sample volume, high moisture, or interferences

AO Aesthetic objective

MAC Maximum acceptable concentration (health-related guideline)

Colony Forming Units per 100 mLCFU/100mL

Page 2 of 3CARO Analytical ServicesRev 04/29/14 Page 2 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water System

WORK ORDER

REPORTED

4070941

Jul-17-14

SAMPLE ANALYTICAL DATA

AnalyteResult /

Recovery

MRL /

Limit Units Prepared Notes

Canadian

DWQ

Guideline

Analyzed

Microbiological Parameters

Sample ID: 12th St. (4070941-01) [Water] Sampled: Jul-14-14 08:10

Jul-16-14CFU/100mLColiforms, Total < 1 1MAC < 1 Jul-15-14

CFU/100mL< 1E. coli Jul-16-141MAC < 1 Jul-15-14

Sample ID: Pump House (4070941-02) [Water] Sampled: Jul-14-14 08:00

Jul-16-14CFU/100mLColiforms, Total < 1 1MAC < 1 Jul-15-14

CFU/100mL< 1E. coli Jul-16-141MAC < 1 Jul-15-14

Page 3 of 3CARO Analytical ServicesRev 04/29/14 Page 3 of 3

REPORTED TO Regional District of Okanagan Similkameen

101 Martin Street

Penticton, BC V2A 5J9

TEL

FAX

1-250-490-4106

(250) 492-0063

ATTENTION Rob Palmer WORK ORDER

General Comments:

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate

regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing

methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition

document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage

resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis .

Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Issued By: Jennifer Shanko, AScT

Administration Coordinator

#110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue

Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7

Tel: 604-279-1499 Fax: 604-279-1599 Tel: 250-765-9646 Fax: 250-765-3893 Tel: 780-489-9100 Fax: 780-489-9700

www.caro.ca

Locations:

4071868

Work Order Comments:

Custody Seal Intact When Received at CARO.

Please contact CARO if more information is needed or to provide feedback on our services.

CERTIFICATE OF ANALYSIS

PO NUMBER RECEIVED / TEMP Jul-29-14 09:50 / 7°C

PROJECT Olalla Water System REPORTED Jul-31-14

PROJECT INFO COC NUMBER B 20843

Page 1 of 3CARO Analytical ServicesRev 04/29/14 Page 1 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water System

WORK ORDER

REPORTED

4071868

Jul-31-14

ANALYSIS INFORMATION

Method Reference (* = modified from)

Preparation AnalysisAnalysis Description Location

KelownaAPHA 9222 *E. coli (by CCA) N/A

KelownaAPHA 9222 *Total Coliforms (by CCA) N/A

Note: The numbers in brackets represent the year that the method was published/approved

Method Reference Descriptions:

APHA Standard Methods for the Examination of Water and Wastewater , American Public Health

Association

Glossary of Terms:

MRL Method Reporting Limit

< Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to

various factors such as dilutions, limited sample volume, high moisture, or interferences

AO Aesthetic objective

MAC Maximum acceptable concentration (health-related guideline)

Colony Forming Units per 100 mLCFU/100mL

Page 2 of 3CARO Analytical ServicesRev 04/29/14 Page 2 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water System

WORK ORDER

REPORTED

4071868

Jul-31-14

SAMPLE ANALYTICAL DATA

AnalyteResult /

Recovery

MRL /

Limit Units Prepared Notes

Canadian

DWQ

Guideline

Analyzed

Microbiological Parameters

Sample ID: Pump House (4071868-01) [Water] Sampled: Jul-28-14 07:25

Jul-30-14CFU/100mLColiforms, Total < 1 1MAC < 1 Jul-29-14

CFU/100mL< 1E. coli Jul-30-141MAC < 1 Jul-29-14

Sample ID: N Main (4071868-02) [Water] Sampled: Jul-28-14 07:40

Jul-30-14CFU/100mLColiforms, Total < 1 1MAC < 1 Jul-29-14

CFU/100mL< 1E. coli Jul-30-141MAC < 1 Jul-29-14

Page 3 of 3CARO Analytical ServicesRev 04/29/14 Page 3 of 3

REPORTED TO Regional District of Okanagan Similkameen

101 Martin Street

Penticton, BC V2A 5J9

TEL

FAX

1-250-490-4106

(250) 492-0063

ATTENTION Rob Palmer WORK ORDER

General Comments:

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate

regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing

methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition

document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage

resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis .

Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Issued By: Jennifer Shanko, AScT

Administration Coordinator

#110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue

Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7

Tel: 604-279-1499 Fax: 604-279-1599 Tel: 250-765-9646 Fax: 250-765-3893 Tel: 780-489-9100 Fax: 780-489-9700

www.caro.ca

Locations:

4080634

Work Order Comments:

Custody Seal Intact When Received at CARO.

Please contact CARO if more information is needed or to provide feedback on our services.

CERTIFICATE OF ANALYSIS

PO NUMBER RECEIVED / TEMP Aug-12-14 10:00 / 7°C

PROJECT Olalla Water System REPORTED Aug-14-14

PROJECT INFO COC NUMBER B 23689

Page 1 of 3CARO Analytical ServicesRev 04/29/14 Page 1 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water System

WORK ORDER

REPORTED

4080634

Aug-14-14

ANALYSIS INFORMATION

Method Reference (* = modified from)

Preparation AnalysisAnalysis Description Location

KelownaAPHA 9222 *E. coli (by CCA) N/A

KelownaAPHA 9222 *Total Coliforms (by CCA) N/A

Note: The numbers in brackets represent the year that the method was published/approved

Method Reference Descriptions:

APHA Standard Methods for the Examination of Water and Wastewater , American Public Health

Association

Glossary of Terms:

MRL Method Reporting Limit

< Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to

various factors such as dilutions, limited sample volume, high moisture, or interferences

AO Aesthetic objective

MAC Maximum acceptable concentration (health-related guideline)

Colony Forming Units per 100 mLCFU/100mL

Page 2 of 3CARO Analytical ServicesRev 04/29/14 Page 2 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water System

WORK ORDER

REPORTED

4080634

Aug-14-14

SAMPLE ANALYTICAL DATA

AnalyteResult /

Recovery

MRL /

Limit Units Prepared Notes

Canadian

DWQ

Guideline

Analyzed

Microbiological Parameters

Sample ID: Pump House (4080634-01) [Water] Sampled: Aug-11-14 07:05

HTAug-13-14CFU/100mLColiforms, Total < 1 1MAC < 1 Aug-12-14

CFU/100mL< 1 HTE. coli Aug-13-141MAC < 1 Aug-12-14

Sample ID: 12th St. (4080634-02) [Water] Sampled: Aug-11-14 07:23

HTAug-13-14CFU/100mLColiforms, Total < 1 1MAC < 1 Aug-12-14

CFU/100mL< 1 HTE. coli Aug-13-141MAC < 1 Aug-12-14

Sample / Analysis Qualifiers:

HT The sample was prepared / analyzed past the recommended holding time.

Page 3 of 3CARO Analytical ServicesRev 04/29/14 Page 3 of 3

REPORTED TO Regional District of Okanagan Similkameen

101 Martin Street

Penticton, BC V2A 5J9

TEL

FAX

1-250-490-4106

(250) 492-0063

ATTENTION Rob Palmer WORK ORDER

General Comments:

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate

regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing

methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition

document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage

resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis .

Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Issued By: Karin Miyazaki For Jennifer Shanko, AScT

Administration Coordinator

#110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue

Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7

Tel: 604-279-1499 Fax: 604-279-1599 Tel: 250-765-9646 Fax: 250-765-3893 Tel: 780-489-9100 Fax: 780-489-9700

www.caro.ca

Locations:

4081676

Work Order Comments:

Custody Seal Intact when received by CARO.

Please contact CARO if more information is needed or to provide feedback on our services.

CERTIFICATE OF ANALYSIS

PO NUMBER RECEIVED / TEMP Aug-27-14 09:48 / 9°C

PROJECT Olalla Water System REPORTED Aug-29-14

PROJECT INFO COC NUMBER B11099

Page 1 of 3CARO Analytical ServicesRev 04/29/14 Page 1 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water System

WORK ORDER

REPORTED

4081676

Aug-29-14

ANALYSIS INFORMATION

Method Reference (* = modified from)

Preparation AnalysisAnalysis Description Location

KelownaAPHA 9222 *E. coli (CCA) N/A

KelownaAPHA 9222 *Total Coliforms (CCA) N/A

Note: The numbers in brackets represent the year that the method was published/approved

Method Reference Descriptions:

APHA Standard Methods for the Examination of Water and Wastewater , American Public Health

Association

Glossary of Terms:

MRL Method Reporting Limit

Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to

various factors such as dilutions, limited sample volume, high moisture, or interferences

<

AO Aesthetic objective

MAC Maximum acceptable concentration (health-related guideline)

Colony Forming Units per 100 mLCFU/100mL

Page 2 of 3CARO Analytical ServicesRev 04/29/14 Page 2 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water System

WORK ORDER

REPORTED

4081676

Aug-29-14

SAMPLE ANALYTICAL DATA

AnalyteResult /

Recovery

Canadian

DWQ

Guideline

MRL /

Limit Units Prepared Analyzed Notes

Sample ID: N Main St. (4081676-01) [Water] Sampled: Aug-26-14 08:50

Microbiological Parameters

CFU/100mL< 1Coliforms, Total Aug-28-141 Aug-27-14MAC < 1

CFU/100mL< 1E. coli Aug-28-141 Aug-27-14MAC < 1

Page 3 of 3CARO Analytical ServicesRev 04/29/14 Page 3 of 3

REPORTED TO Regional District of Okanagan Similkameen

101 Martin Street

Penticton, BC V2A 5J9

TEL

FAX

1-250-490-4106

(250) 492-0063

ATTENTION Rob Palmer WORK ORDER

General Comments:

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate

regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing

methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition

document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage

resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis .

Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Issued By: Karin Miyazaki For Jennifer Shanko, AScT

Administration Coordinator

#110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue

Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7

Tel: 604-279-1499 Fax: 604-279-1599 Tel: 250-765-9646 Fax: 250-765-3893 Tel: 780-489-9100 Fax: 780-489-9700

www.caro.ca

Locations:

4081679

Work Order Comments:

Custody Seal Intact when received by CARO.

Please contact CARO if more information is needed or to provide feedback on our services.

CERTIFICATE OF ANALYSIS

PO NUMBER RECEIVED / TEMP Aug-27-14 09:48 / 9°C

PROJECT Olalla Water System REPORTED Aug-29-14

PROJECT INFO COC NUMBER B11099

Page 1 of 3CARO Analytical ServicesRev 04/29/14 Page 1 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water System

WORK ORDER

REPORTED

4081679

Aug-29-14

ANALYSIS INFORMATION

Method Reference (* = modified from)

Preparation AnalysisAnalysis Description Location

KelownaAPHA 9222 *E. coli (CCA) N/A

KelownaAPHA 9222 *Total Coliforms (CCA) N/A

Note: The numbers in brackets represent the year that the method was published/approved

Method Reference Descriptions:

APHA Standard Methods for the Examination of Water and Wastewater , American Public Health

Association

Glossary of Terms:

MRL Method Reporting Limit

Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to

various factors such as dilutions, limited sample volume, high moisture, or interferences

<

AO Aesthetic objective

MAC Maximum acceptable concentration (health-related guideline)

Colony Forming Units per 100 mLCFU/100mL

Page 2 of 3CARO Analytical ServicesRev 04/29/14 Page 2 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen

Olalla Water System

WORK ORDER

REPORTED

4081679

Aug-29-14

SAMPLE ANALYTICAL DATA

AnalyteResult /

Recovery

Canadian

DWQ

Guideline

MRL /

Limit Units Prepared Analyzed Notes

Sample ID: Pump House (4081679-01) [Water] Sampled: Aug-26-14 08:05

Microbiological Parameters

CFU/100mL< 1Coliforms, Total Aug-28-141 Aug-27-14MAC < 1

CFU/100mL< 1E. coli Aug-28-141 Aug-27-14MAC < 1

Page 3 of 3CARO Analytical ServicesRev 04/29/14 Page 3 of 3

REPORTED TO Regional District of Okanagan Similkameen

Penticton, BC V2A 5J9

TEL

FAX

ATTENTION WORK ORDER

General Comments:

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate

regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing

methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition

document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage

resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis .

Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Issued By:

#110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue

Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7

Tel: 604-279-1499 Fax: 604-279-1599 Tel: 250-765-9646 Fax: 250-765-3893 Tel: 780-489-9100 Fax: 780-489-9700

www.caro.ca

Locations:

4090566

Please contact CARO if more information is needed or to provide feedback on our services.

CERTIFICATE OF ANALYSIS

PO NUMBER RECEIVED / TEMP Sep-09-14 09:55 / 6°C

PROJECT REPORTED Sep-11-14

PROJECT INFO COC NUMBER B 09263

101 Martin Street 1-250-490-4106

(250) 492-0063

Rob Palmer

Olalla Water System

Administration Coordinator

Jennifer Shanko, AScT

Work Order Comments:

Custody seals intact when received at Caro!

Page 1 of 3CARO Analytical ServicesRev 08/19/14 Page 1 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen WORK ORDER

REPORTED Sep-11-14

ANALYSIS INFORMATION

Olalla Water System

4090566

Technique LocationAnalysis Description Method Reference

E. coli (CCA) APHA 9222 * Membrane Filtration Kelowna

Total Coliforms (CCA) APHA 9222 * Membrane Filtration Kelowna

Note: An asterisk in the Method Reference indicates that the CARO method has been modified from the reference method

Method Reference Descriptions:

APHA Standard Methods for the Examination of Water and Wastewater, 22nd Edition, American Public Health

Association/American Water Works Association/Water Environment Federation

Glossary of Terms:

MRL Method Reporting Limit

Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to various factors such

as dilutions, limited sample volume, high moisture, or interferences

<

AO Aesthetic objective

MAC Maximum acceptable concentration (health based)

OG Operational guideline (treated water)

Colony Forming Units per 100 millilitresCFU/100mL

Standards / Guidelines Referenced in this Report:

Guidelines for Canadian Drinking Water Quality (2012)

Website: http://www.hc-sc.gc.ca/ewh-semt/pubs/water-eau/2012-sum_guide-res_recom/index-eng.php

Note: In some cases, the values displayed on the report represent the lowest guideline and are to be verified by the end user

Page 2 of 3CARO Analytical ServicesRev 08/19/14 Page 2 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen WORK ORDER

REPORTED Sep-11-14

SAMPLE ANALYTICAL DATA

Olalla Water System

4090566

Analyte Result /

Recovery

Standard /

Guideline

MRL /

Limits

Units Prepared Analyzed Notes

Sample ID: Pump House (4090566-01) [Water] Sampled: Sep-08-14 08:34

Microbiological Parameters

CFU/100mL< 1Coliforms, Total Sep-10-141 Sep-09-14MAC = None

Detected

CFU/100mL< 1E. coli Sep-10-141 Sep-09-14MAC = None

Detected

Sample ID: 12th St. (4090566-02) [Water] Sampled: Sep-08-14 08:45

Microbiological Parameters

CFU/100mL< 1Coliforms, Total Sep-10-141 Sep-09-14MAC = None

Detected

CFU/100mL< 1E. coli Sep-10-141 Sep-09-14MAC = None

Detected

Page 3 of 3CARO Analytical ServicesRev 08/19/14 Page 3 of 3

REPORTED TO Regional District of Okanagan Similkameen

Penticton, BC V2A 5J9

TEL

FAX

ATTENTION WORK ORDER

General Comments:

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate

regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing

methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition

document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage

resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis .

Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Issued By:

#110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue

Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7

Tel: 604-279-1499 Fax: 604-279-1599 Tel: 250-765-9646 Fax: 250-765-3893 Tel: 780-489-9100 Fax: 780-489-9700

www.caro.ca

Locations:

4091823

Please contact CARO if more information is needed or to provide feedback on our services.

CERTIFICATE OF ANALYSIS

PO NUMBER RECEIVED / TEMP Sep-25-14 09:40 / 5°C

PROJECT REPORTED Sep-29-14

PROJECT INFO COC NUMBER B 23681

101 Martin Street 1-250-490-4106

(250) 492-0063

Rob Palmer

Olalla Water System

Administration Coordinator

Jennifer Shanko, AScT

Work Order Comments:

Custody Seal Intact When Received at CARO.

Page 1 of 3CARO Analytical ServicesRev 09/15/14 Page 1 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen WORK ORDER

REPORTED Sep-29-14

ANALYSIS INFORMATION

Olalla Water System

4091823

Technique LocationAnalysis Description Method Reference

E. coli (CCA) APHA 9222 * Membrane Filtration Kelowna

Total Coliforms (CCA) APHA 9222 * Membrane Filtration Kelowna

Note: An asterisk in the Method Reference indicates that the CARO method has been modified from the reference method

Method Reference Descriptions:

APHA Standard Methods for the Examination of Water and Wastewater, 22nd Edition, American Public Health

Association/American Water Works Association/Water Environment Federation

Glossary of Terms:

MRL Method Reporting Limit

Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to various factors such

as dilutions, limited sample volume, high moisture, or interferences

<

AO Aesthetic objective

MAC Maximum acceptable concentration (health based)

OG Operational guideline (treated water)

Colony Forming Units per 100 millilitresCFU/100mL

Standards / Guidelines Referenced in this Report:

Guidelines for Canadian Drinking Water Quality (2012)

Website: http://www.hc-sc.gc.ca/ewh-semt/pubs/water-eau/2012-sum_guide-res_recom/index-eng.php

Note: In some cases, the values displayed on the report represent the lowest guideline and are to be verified by the end user

Page 2 of 3CARO Analytical ServicesRev 09/15/14 Page 2 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen WORK ORDER

REPORTED Sep-29-14

SAMPLE ANALYTICAL DATA

Olalla Water System

4091823

Analyte Result /

Recovery

Standard /

Guideline

MRL /

Limits

Units Prepared Analyzed Notes

Sample ID: Pump House (4091823-01) [Water] Sampled: Sep-24-14 14:00

Microbiological Parameters

CFU/100mL< 1Coliforms, Total Sep-26-141 Sep-25-14MAC = None

Detected

CFU/100mL< 1E. coli Sep-26-141 Sep-25-14MAC = None

Detected

Sample ID: 12th St. Sample Stn (4091823-02) [Water] Sampled: Sep-24-14 13:48

Microbiological Parameters

CFU/100mL< 1Coliforms, Total Sep-26-141 Sep-25-14MAC = None

Detected

CFU/100mL< 1E. coli Sep-26-141 Sep-25-14MAC = None

Detected

Page 3 of 3CARO Analytical ServicesRev 09/15/14 Page 3 of 3

REPORTED TO Regional District of Okanagan Similkameen

Penticton, BC V2A 5J9

TEL

FAX

ATTENTION WORK ORDER

General Comments:

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate

regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing

methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition

document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage

resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis .

Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Issued By:

#110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue

Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7

Tel: 604-279-1499 Fax: 604-279-1599 Tel: 250-765-9646 Fax: 250-765-3893 Tel: 780-489-9100 Fax: 780-489-9700

www.caro.ca

Locations:

4100489

Please contact CARO if more information is needed or to provide feedback on our services.

CERTIFICATE OF ANALYSIS

PO NUMBER RECEIVED / TEMP Oct-08-14 09:40 / 5°C

PROJECT REPORTED Oct-10-14

PROJECT INFO COC NUMBER B 23690

101 Martin Street 1-250-490-4106

(250) 492-0063

Rob Palmer

Olalla Water System

Administration Coordinator

Jennifer Shanko, AScT

Work Order Comments:

Custody Seal Intact When Received at CARO.

Page 1 of 3CARO Analytical ServicesRev 09/15/14 Page 1 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen WORK ORDER

REPORTED Oct-10-14

ANALYSIS INFORMATION

Olalla Water System

4100489

Technique LocationAnalysis Description Method Reference

E. coli (CCA) APHA 9222 * Membrane Filtration Kelowna

Total Coliforms (CCA) APHA 9222 * Membrane Filtration Kelowna

Note: An asterisk in the Method Reference indicates that the CARO method has been modified from the reference method

Method Reference Descriptions:

APHA Standard Methods for the Examination of Water and Wastewater, 22nd Edition, American Public Health

Association/American Water Works Association/Water Environment Federation

Glossary of Terms:

MRL Method Reporting Limit

Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to various factors such

as dilutions, limited sample volume, high moisture, or interferences

<

AO Aesthetic objective

MAC Maximum acceptable concentration (health based)

OG Operational guideline (treated water)

Colony Forming Units per 100 millilitresCFU/100 mL

Standards / Guidelines Referenced in this Report:

Guidelines for Canadian Drinking Water Quality (2012)

Website: http://www.hc-sc.gc.ca/ewh-semt/pubs/water-eau/2012-sum_guide-res_recom/index-eng.php

Note: In some cases, the values displayed on the report represent the lowest guideline and are to be verified by the end user

Page 2 of 3CARO Analytical ServicesRev 09/15/14 Page 2 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen WORK ORDER

REPORTED Oct-10-14

SAMPLE ANALYTICAL DATA

Olalla Water System

4100489

Analyte Result /

Recovery

Standard /

Guideline

MRL /

Limits

Units Prepared Analyzed Notes

Sample ID: Pump House (4100489-01) [Water] Sampled: Oct-07-14 08:00

Microbiological Parameters

CFU/100 mL< 1Coliforms, Total Oct-09-141 Oct-08-14MAC = None

Detected

CFU/100 mL< 1E. coli Oct-09-141 Oct-08-14MAC = None

Detected

Sample ID: N Main St. (4100489-02) [Water] Sampled: Oct-07-14 08:25

Microbiological Parameters

CFU/100 mL< 1Coliforms, Total Oct-09-141 Oct-08-14MAC = None

Detected

CFU/100 mL< 1E. coli Oct-09-141 Oct-08-14MAC = None

Detected

Page 3 of 3CARO Analytical ServicesRev 09/15/14 Page 3 of 3

REPORTED TO Regional District of Okanagan Similkameen

Penticton, BC V2A 5J9

TEL

FAX

ATTENTION WORK ORDER

General Comments:

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate

regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing

methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition

document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage

resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis .

Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Issued By:

#110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue

Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7

Tel: 604-279-1499 Fax: 604-279-1599 Tel: 250-765-9646 Fax: 250-765-3893 Tel: 780-489-9100 Fax: 780-489-9700

www.caro.ca

Locations:

4101250

Please contact CARO if more information is needed or to provide feedback on our services.

CERTIFICATE OF ANALYSIS

PO NUMBER RECEIVED / TEMP Oct-21-14 09:30 / 6°C

PROJECT REPORTED Oct-23-14

PROJECT INFO COC NUMBER B 15250

101 Martin Street 1-250-490-4106

(250) 492-0063

Rob Palmer

Olalla Water System

Administration Coordinator

Karin Miyazaki For Jennifer Shanko, AScT

Work Order Comments:

Custody Seal Intact When Received at CARO.

Page 1 of 3CARO Analytical ServicesRev 09/15/14 Page 1 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen WORK ORDER

REPORTED Oct-23-14

ANALYSIS INFORMATION

Olalla Water System

4101250

Technique LocationAnalysis Description Method Reference

E. coli (CCA) APHA 9222 * Membrane Filtration Kelowna

Total Coliforms (CCA) APHA 9222 * Membrane Filtration Kelowna

Note: An asterisk in the Method Reference indicates that the CARO method has been modified from the reference method

Method Reference Descriptions:

APHA Standard Methods for the Examination of Water and Wastewater, 22nd Edition, American Public Health

Association/American Water Works Association/Water Environment Federation

Glossary of Terms:

MRL Method Reporting Limit

Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to various factors such

as dilutions, limited sample volume, high moisture, or interferences

<

AO Aesthetic objective

MAC Maximum acceptable concentration (health based)

OG Operational guideline (treated water)

Colony Forming Units per 100 millilitresCFU/100 mL

Standards / Guidelines Referenced in this Report:

Guidelines for Canadian Drinking Water Quality (2012)

Website: http://www.hc-sc.gc.ca/ewh-semt/pubs/water-eau/2012-sum_guide-res_recom/index-eng.php

Note: In some cases, the values displayed on the report represent the lowest guideline and are to be verified by the end user

Page 2 of 3CARO Analytical ServicesRev 09/15/14 Page 2 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen WORK ORDER

REPORTED Oct-23-14

SAMPLE ANALYTICAL DATA

Olalla Water System

4101250

Analyte Result /

Recovery

Standard /

Guideline

MRL /

Limits

Units Prepared Analyzed Notes

Sample ID: Pump House (4101250-01) [Water] Sampled: Oct-20-14 08:10

Microbiological Parameters

CFU/100 mL< 1Coliforms, Total Oct-22-141 Oct-21-14MAC = None

Detected

CFU/100 mL< 1E. coli Oct-22-141 Oct-21-14MAC = None

Detected

Sample ID: 12th St. (4101250-02) [Water] Sampled: Oct-20-14 08:20

Microbiological Parameters

CFU/100 mL< 1Coliforms, Total Oct-22-141 Oct-21-14MAC = None

Detected

CFU/100 mL< 1E. coli Oct-22-141 Oct-21-14MAC = None

Detected

Page 3 of 3CARO Analytical ServicesRev 09/15/14 Page 3 of 3

REPORTED TO Regional District of Okanagan Similkameen

Penticton, BC V2A 5J9

TEL

FAX

ATTENTION WORK ORDER

General Comments:

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate

regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing

methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition

document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage

resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis .

Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Issued By:

#110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue

Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7

Tel: 604-279-1499 Fax: 604-279-1599 Tel: 250-765-9646 Fax: 250-765-3893 Tel: 780-489-9100 Fax: 780-489-9700

www.caro.ca

Locations:

4101387

Please contact CARO if more information is needed or to provide feedback on our services.

CERTIFICATE OF ANALYSIS

PO NUMBER RECEIVED / TEMP Oct-22-14 09:30 / 7°C

PROJECT REPORTED Oct-23-14

PROJECT INFO COC NUMBER B 22939

101 Martin Street 1-250-490-4106

(250) 492-0063

Rob Palmer

Olalla Water System

Administration Coordinator

Karin Miyazaki For Jennifer Shanko, AScT

Work Order Comments:

Custody Seal Intact When Received at CARO.

Page 1 of 3CARO Analytical ServicesRev 09/15/14 Page 1 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen WORK ORDER

REPORTED Oct-23-14

ANALYSIS INFORMATION

Olalla Water System

4101387

Technique LocationAnalysis Description Method Reference

E. coli (CCA) APHA 9222 * Membrane Filtration Kelowna

Total Coliforms (CCA) APHA 9222 * Membrane Filtration Kelowna

Note: An asterisk in the Method Reference indicates that the CARO method has been modified from the reference method

Method Reference Descriptions:

APHA Standard Methods for the Examination of Water and Wastewater, 22nd Edition, American Public Health

Association/American Water Works Association/Water Environment Federation

Glossary of Terms:

MRL Method Reporting Limit

Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to various factors such

as dilutions, limited sample volume, high moisture, or interferences

<

AO Aesthetic objective

MAC Maximum acceptable concentration (health based)

OG Operational guideline (treated water)

Colony Forming Units per 100 millilitresCFU/100 mL

Standards / Guidelines Referenced in this Report:

Guidelines for Canadian Drinking Water Quality (2012)

Website: http://www.hc-sc.gc.ca/ewh-semt/pubs/water-eau/2012-sum_guide-res_recom/index-eng.php

Note: In some cases, the values displayed on the report represent the lowest guideline and are to be verified by the end user

Page 2 of 3CARO Analytical ServicesRev 09/15/14 Page 2 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen WORK ORDER

REPORTED Oct-23-14

SAMPLE ANALYTICAL DATA

Olalla Water System

4101387

Analyte Result /

Recovery

Standard /

Guideline

MRL /

Limits

Units Prepared Analyzed Notes

Sample ID: 2637 1st St. (4101387-01) [Water] Sampled: Oct-21-14 08:30

Microbiological Parameters

CFU/100 mL< 1Coliforms, Total Oct-23-141 Oct-22-14MAC = None

Detected

CFU/100 mL< 1E. coli Oct-23-141 Oct-22-14MAC = None

Detected

Page 3 of 3CARO Analytical ServicesRev 09/15/14 Page 3 of 3

REPORTED TO Regional District of Okanagan Similkameen

Penticton, BC V2A 5J9

TEL

FAX

ATTENTION WORK ORDER

General Comments:

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate

regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing

methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition

document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage

resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis .

Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Issued By:

#110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue

Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7

Tel: 604-279-1499 Fax: 604-279-1599 Tel: 250-765-9646 Fax: 250-765-3893 Tel: 780-489-9100 Fax: 780-489-9700

www.caro.ca

Locations:

4110102

Please contact CARO if more information is needed or to provide feedback on our services.

CERTIFICATE OF ANALYSIS

PO NUMBER RECEIVED / TEMP Nov-04-14 10:05 / 4°C

PROJECT REPORTED Nov-06-14

PROJECT INFO COC NUMBER B 22938

101 Martin Street 1-250-490-4106

(250) 492-0063

Rob Palmer

Olalla Water System

Administration Coordinator

Jennifer Shanko, AScT

Work Order Comments:

Custody seals intact when received at Caro!

Page 1 of 3CARO Analytical ServicesRev 09/15/14 Page 1 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen WORK ORDER

REPORTED Nov-06-14

ANALYSIS INFORMATION

Olalla Water System

4110102

Technique LocationAnalysis Description Method Reference

E. coli (CCA) APHA 9222 * Membrane Filtration Kelowna

Total Coliforms (CCA) APHA 9222 * Membrane Filtration Kelowna

Note: An asterisk in the Method Reference indicates that the CARO method has been modified from the reference method

Method Reference Descriptions:

APHA Standard Methods for the Examination of Water and Wastewater, 22nd Edition, American Public Health

Association/American Water Works Association/Water Environment Federation

Glossary of Terms:

MRL Method Reporting Limit

Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to various factors such

as dilutions, limited sample volume, high moisture, or interferences

<

AO Aesthetic objective

MAC Maximum acceptable concentration (health based)

OG Operational guideline (treated water)

Colony Forming Units per 100 millilitresCFU/100 mL

Standards / Guidelines Referenced in this Report:

Guidelines for Canadian Drinking Water Quality (Oct 2014)

Website: http://www.hc-sc.gc.ca/ewh-semt/pubs/water-eau/2012-sum_guide-res_recom/index-eng.php

Note: In some cases, the values displayed on the report represent the lowest guideline and are to be verified by the end user

Page 2 of 3CARO Analytical ServicesRev 09/15/14 Page 2 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen WORK ORDER

REPORTED Nov-06-14

SAMPLE ANALYTICAL DATA

Olalla Water System

4110102

Analyte Result /

Recovery

Standard /

Guideline

MRL /

Limits

Units Prepared Analyzed Notes

Sample ID: Pump House (4110102-01) [Water] Sampled: Nov-03-14 08:10

Microbiological Parameters

CFU/100 mL< 1Coliforms, Total Nov-05-141 Nov-04-14MAC = None

Detected

CFU/100 mL< 1E. coli Nov-05-141 Nov-04-14MAC = None

Detected

Sample ID: N Main (4110102-02) [Water] Sampled: Nov-03-14 08:20

Microbiological Parameters

CFU/100 mL< 1Coliforms, Total Nov-05-141 Nov-04-14MAC = None

Detected

CFU/100 mL< 1E. coli Nov-05-141 Nov-04-14MAC = None

Detected

Page 3 of 3CARO Analytical ServicesRev 09/15/14 Page 3 of 3

REPORTED TO Regional District of Okanagan Similkameen

Penticton, BC V2A 5J9

TEL

FAX

ATTENTION WORK ORDER

General Comments:

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate

regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing

methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition

document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage

resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis .

Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Issued By:

#110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue

Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7

Tel: 604-279-1499 Fax: 604-279-1599 Tel: 250-765-9646 Fax: 250-765-3893 Tel: 780-489-9100 Fax: 780-489-9700

www.caro.ca

Locations:

4111010

Please contact CARO if more information is needed or to provide feedback on our services.

CERTIFICATE OF ANALYSIS

PO NUMBER RECEIVED / TEMP Nov-19-14 09:30 / 3°C

PROJECT REPORTED Nov-21-14

PROJECT INFO COC NUMBER B 22935

101 Martin Street 1-250-490-4106

(250) 492-0063

Rob Palmer

Olalla Water System

Administration Coordinator

Jennifer Shanko, AScT

Work Order Comments:

Custody Seals intact when received at Caro!

Page 1 of 3CARO Analytical ServicesRev 09/15/14 Page 1 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen WORK ORDER

REPORTED Nov-21-14

ANALYSIS INFORMATION

Olalla Water System

4111010

Technique LocationAnalysis Description Method Reference

E. coli (CCA) APHA 9222 * Membrane Filtration Kelowna

Total Coliforms (CCA) APHA 9222 * Membrane Filtration Kelowna

Note: An asterisk in the Method Reference indicates that the CARO method has been modified from the reference method

Method Reference Descriptions:

APHA Standard Methods for the Examination of Water and Wastewater, 22nd Edition, American Public Health

Association/American Water Works Association/Water Environment Federation

Glossary of Terms:

MRL Method Reporting Limit

Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to various factors such

as dilutions, limited sample volume, high moisture, or interferences

<

AO Aesthetic objective

MAC Maximum acceptable concentration (health based)

OG Operational guideline (treated water)

Colony Forming Units per 100 millilitresCFU/100 mL

Standards / Guidelines Referenced in this Report:

Guidelines for Canadian Drinking Water Quality (Oct 2014)

Website: http://www.hc-sc.gc.ca/ewh-semt/pubs/water-eau/2012-sum_guide-res_recom/index-eng.php

Note: In some cases, the values displayed on the report represent the lowest guideline and are to be verified by the end user

Page 2 of 3CARO Analytical ServicesRev 09/15/14 Page 2 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen WORK ORDER

REPORTED Nov-21-14

SAMPLE ANALYTICAL DATA

Olalla Water System

4111010

Analyte Result /

Recovery

Standard /

Guideline

MRL /

Limits

Units Prepared Analyzed Notes

Sample ID: Pump House (4111010-01) [Water] Sampled: Nov-18-14 08:10

Microbiological Parameters

CFU/100 mL< 1Coliforms, Total Nov-20-141 Nov-19-14MAC = None

Detected

CFU/100 mL< 1E. coli Nov-20-141 Nov-19-14MAC = None

Detected

Sample ID: 12th St. (4111010-02) [Water] Sampled: Nov-18-14 08:35

Microbiological Parameters

CFU/100 mL< 1Coliforms, Total Nov-20-141 Nov-19-14MAC = None

Detected

CFU/100 mL< 1E. coli Nov-20-141 Nov-19-14MAC = None

Detected

Page 3 of 3CARO Analytical ServicesRev 09/15/14 Page 3 of 3

REPORTED TO Regional District of Okanagan Similkameen

Penticton, BC V2A 5J9

TEL

FAX

ATTENTION WORK ORDER

General Comments:

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate

regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing

methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition

document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage

resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis .

Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Issued By:

#110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue

Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7

Tel: 604-279-1499 Fax: 604-279-1599 Tel: 250-765-9646 Fax: 250-765-3893 Tel: 780-489-9100 Fax: 780-489-9700

www.caro.ca

Locations:

4120199

Please contact CARO if more information is needed or to provide feedback on our services.

CERTIFICATE OF ANALYSIS

PO NUMBER RECEIVED / TEMP Dec-03-14 10:15 / 1°C

PROJECT REPORTED Dec-05-14

PROJECT INFO COC NUMBER B 23684

101 Martin Street 1-250-490-4106

(250) 492-0063

Rob Palmer

Olalla Water System

Administration Coordinator

Jennifer Shanko, AScT

Work Order Comments:

Custody seals intact when received at Caro!

Page 1 of 3CARO Analytical ServicesRev 09/15/14 Page 1 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen WORK ORDER

REPORTED Dec-05-14

ANALYSIS INFORMATION

Olalla Water System

4120199

Technique LocationAnalysis Description Method Reference

E. coli (CCA) APHA 9222 * Membrane Filtration Kelowna

Total Coliforms (CCA) APHA 9222 * Membrane Filtration Kelowna

Note: An asterisk in the Method Reference indicates that the CARO method has been modified from the reference method

Method Reference Descriptions:

APHA Standard Methods for the Examination of Water and Wastewater, 22nd Edition, American Public Health

Association/American Water Works Association/Water Environment Federation

Glossary of Terms:

MRL Method Reporting Limit

Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to various factors such

as dilutions, limited sample volume, high moisture, or interferences

<

AO Aesthetic objective

MAC Maximum acceptable concentration (health based)

OG Operational guideline (treated water)

Colony Forming Units per 100 millilitresCFU/100 mL

Standards / Guidelines Referenced in this Report:

Guidelines for Canadian Drinking Water Quality (Oct 2014)

Website: http://www.hc-sc.gc.ca/ewh-semt/alt_formats/pdf/pubs/water-eau/sum_guide-res_recom/sum_guide-res_recom-e

ng.pdf

Note: In some cases, the values displayed on the report represent the lowest guideline and are to be verified by the end user

Page 2 of 3CARO Analytical ServicesRev 09/15/14 Page 2 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen WORK ORDER

REPORTED Dec-05-14

SAMPLE ANALYTICAL DATA

Olalla Water System

4120199

Analyte Result /

Recovery

Standard /

Guideline

MRL /

Limits

Units Prepared Analyzed Notes

Sample ID: Pump House (4120199-01) [Water] Sampled: Dec-02-14 08:20

Microbiological Parameters

CFU/100 mL< 1Coliforms, Total Dec-04-141 Dec-03-14MAC = None

Detected

CFU/100 mL< 1E. coli Dec-04-141 Dec-03-14MAC = None

Detected

Sample ID: N Main St. (4120199-02) [Water] Sampled: Dec-02-14 08:45

Microbiological Parameters

CFU/100 mL< 1Coliforms, Total Dec-04-141 Dec-03-14MAC = None

Detected

CFU/100 mL< 1E. coli Dec-04-141 Dec-03-14MAC = None

Detected

Page 3 of 3CARO Analytical ServicesRev 09/15/14 Page 3 of 3

REPORTED TO Regional District of Okanagan Similkameen

Penticton, BC V2A 5J9

TEL

FAX

ATTENTION WORK ORDER

General Comments:

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate

regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing

methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition

document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage

resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis .

Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Issued By:

#110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue

Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7

Tel: 604-279-1499 Fax: 604-279-1599 Tel: 250-765-9646 Fax: 250-765-3893 Tel: 780-489-9100 Fax: 780-489-9700

www.caro.ca

Locations:

4121023

Please contact CARO if more information is needed or to provide feedback on our services.

CERTIFICATE OF ANALYSIS

PO NUMBER RECEIVED / TEMP Dec-17-14 10:45 / 3°C

PROJECT REPORTED Dec-18-14

PROJECT INFO COC NUMBER B 19859

101 Martin Street 1-250-490-4106

(250) 492-0063

Rob Palmer

Olalla Water System

Administration Coordinator

Jennifer Shanko, AScT

Work Order Comments:

Custody Seals intact when received at Caro!

Page 1 of 3CARO Analytical ServicesRev 09/15/14 Page 1 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen WORK ORDER

REPORTED Dec-18-14

ANALYSIS INFORMATION

Olalla Water System

4121023

Technique LocationAnalysis Description Method Reference

E. coli (CCA) APHA 9222 * Membrane Filtration Kelowna

Total Coliforms (CCA) APHA 9222 * Membrane Filtration Kelowna

Note: An asterisk in the Method Reference indicates that the CARO method has been modified from the reference method

Method Reference Descriptions:

APHA Standard Methods for the Examination of Water and Wastewater, 22nd Edition, American Public Health

Association/American Water Works Association/Water Environment Federation

Glossary of Terms:

MRL Method Reporting Limit

Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to various factors such

as dilutions, limited sample volume, high moisture, or interferences

<

AO Aesthetic objective

MAC Maximum acceptable concentration (health based)

OG Operational guideline (treated water)

Colony Forming Units per 100 millilitresCFU/100 mL

Standards / Guidelines Referenced in this Report:

Guidelines for Canadian Drinking Water Quality (Oct 2014)

Website: http://www.hc-sc.gc.ca/ewh-semt/alt_formats/pdf/pubs/water-eau/sum_guide-res_recom/sum_guide-res_recom-e

ng.pdf

Note: In some cases, the values displayed on the report represent the lowest guideline and are to be verified by the end user

Page 2 of 3CARO Analytical ServicesRev 09/15/14 Page 2 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen WORK ORDER

REPORTED Dec-18-14

SAMPLE ANALYTICAL DATA

Olalla Water System

4121023

Analyte Result /

Recovery

Standard /

Guideline

MRL /

Limits

Units Prepared Analyzed Notes

Sample ID: Pump House (4121023-01) [Water] Sampled: Dec-16-14 09:15

Microbiological Parameters

CFU/100 mL< 1Coliforms, Total Dec-18-141 Dec-17-14MAC = None

Detected

CFU/100 mL< 1E. coli Dec-18-141 Dec-17-14MAC = None

Detected

Sample ID: 12th St. (4121023-02) [Water] Sampled: Dec-16-14 09:25

Microbiological Parameters

CFU/100 mL< 1Coliforms, Total Dec-18-141 Dec-17-14MAC = None

Detected

CFU/100 mL< 1E. coli Dec-18-141 Dec-17-14MAC = None

Detected

Page 3 of 3CARO Analytical ServicesRev 09/15/14 Page 3 of 3

REPORTED TO Regional District of Okanagan Similkameen

Penticton, BC V2A 5J9

TEL

FAX

ATTENTION WORK ORDER

General Comments:

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate

regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing

methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition

document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage

resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis .

Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Issued By:

#110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue

Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7

Tel: 604-279-1499 Fax: 604-279-1599 Tel: 250-765-9646 Fax: 250-765-3893 Tel: 780-489-9100 Fax: 780-489-9700

www.caro.ca

Locations:

4121261

Please contact CARO if more information is needed or to provide feedback on our services.

CERTIFICATE OF ANALYSIS

PO NUMBER RECEIVED / TEMP Dec-22-14 14:45 / 6°C

PROJECT REPORTED Dec-24-14

PROJECT INFO COC NUMBER B17274

101 Martin Street 1-250-490-4106

(250) 492-0063

Rob Palmer

Olalla Water System

Administration Coordinator

Karin Miyazaki For Jennifer Shanko, AScT

Work Order Comments:

Custody Seal Intact

Page 1 of 3CARO Analytical ServicesRev 09/15/14 Page 1 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen WORK ORDER

REPORTED Dec-24-14

ANALYSIS INFORMATION

Olalla Water System

4121261

Technique LocationAnalysis Description Method Reference

E. coli (CCA) APHA 9222 * Membrane Filtration Kelowna

Total Coliforms (CCA) APHA 9222 * Membrane Filtration Kelowna

Note: An asterisk in the Method Reference indicates that the CARO method has been modified from the reference method

Method Reference Descriptions:

APHA Standard Methods for the Examination of Water and Wastewater, 22nd Edition, American Public Health

Association/American Water Works Association/Water Environment Federation

Glossary of Terms:

MRL Method Reporting Limit

Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to various factors such

as dilutions, limited sample volume, high moisture, or interferences

<

AO Aesthetic objective

MAC Maximum acceptable concentration (health based)

OG Operational guideline (treated water)

Colony Forming Units per 100 millilitresCFU/100 mL

Standards / Guidelines Referenced in this Report:

Guidelines for Canadian Drinking Water Quality (Oct 2014)

Website: http://www.hc-sc.gc.ca/ewh-semt/alt_formats/pdf/pubs/water-eau/sum_guide-res_recom/sum_guide-res_recom-e

ng.pdf

Note: In some cases, the values displayed on the report represent the lowest guideline and are to be verified by the end user

Page 2 of 3CARO Analytical ServicesRev 09/15/14 Page 2 of 3

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen WORK ORDER

REPORTED Dec-24-14

SAMPLE ANALYTICAL DATA

Olalla Water System

4121261

Analyte Result /

Recovery

Standard /

Guideline

MRL /

Limits

Units Prepared Analyzed Notes

Sample ID: Pump House (4121261-01) [Water] Sampled: Dec-22-14 08:15

Microbiological Parameters

CFU/100 mL< 1Coliforms, Total Dec-23-141 Dec-22-14MAC = None

Detected

CFU/100 mL< 1E. coli Dec-23-141 Dec-22-14MAC = None

Detected

Sample ID: N Main St. (4121261-02) [Water] Sampled: Dec-22-14 08:30

Microbiological Parameters

CFU/100 mL< 1Coliforms, Total Dec-23-141 Dec-22-14MAC = None

Detected

CFU/100 mL< 1E. coli Dec-23-141 Dec-22-14MAC = None

Detected

Page 3 of 3CARO Analytical ServicesRev 09/15/14 Page 3 of 3

APPENDIX B

DATE FIXED LOCATION

Pump House TC E.coli Time Temp TDS Cond pH Free Total Turbidity Comments

P/A P/A C mg/L uS/cm mg/L mg/L NTU

13-Jan-14 805

28-Jan-14 810

11-Feb-14 808

14-Feb-14

25-Feb-14 1038

10-Mar-14 812

25-Mar-14 820

9-Apr-14 710

23-Apr-14 807

6-May-14 745

20-May-14 730

2-Jun-14 720

16-Jun-14 710

2-Jul-14 711

14-Jul-14 800

28-Jul-14 725

11-Aug-14 705 Hold times exceeded

26-Aug-14 805 9.5 429 201 7.7 Potablity Test / No bact

8-Sep-14 834

24-Sep-13 1400

7-Oct-14 800

20-Oct-14 810

21-Oct-14

3-Nov-14 810

18-Nov-14 810

2-Dec-14 820

16-Dec-14 915

22-Dec-14 815

Colilert Chlorine

DATE FIXED LOCATION

N. Main St. SS TC E.coli Time Temp TDS Cond pH Free Total Turbidity Comments

P/A P/A C mg/L uS/cm mg/L mg/L NTU

13-Jan-14

28-Jan-14 820

11-Feb-14 935

14-Feb-14 828 Resample

25-Feb-14 1107

10-Mar-14 841

25-Mar-14

9-Apr-14 720

23-Apr-14

6-May-14 755

20-May-14

2-Jun-14 732

16-Jun-14

2-Jul-14 733

14-Jul-14

28-Jul-14 740

11-Aug-14

26-Aug-14 850

8-Sep-14

24-Sep-13

7-Oct-14 825

20-Oct-14

21-Oct-14

3-Nov-14 820

18-Nov-14

2-Dec-14 845

16-Dec-14

22-Dec-14 830

Colilert Chlorine

DATE FIXED LOCATION

12th St. Sample Station TC E.coli Time Temp TDS Cond pH Free Total Turbidity Comments

P/A P/A C mg/L uS/cm mg/L mg/L NTU

13-Jan-14 818

28-Jan-14

11-Feb-14

14-Feb-14

25-Feb-14 1054

10-Mar-14

25-Mar-14 825

9-Apr-14

23-Apr-14 822

6-May-14

20-May-14 740

2-Jun-14

16-Jun-14 723

2-Jul-14

14-Jul-14 810

28-Jul-14

11-Aug-14 705 Hold times exceeded

26-Aug-14

8-Sep-14 845

24-Sep-13 1348

7-Oct-14

20-Oct-14 820

21-Oct-14

3-Nov-14

18-Nov-14 835

2-Dec-14

16-Dec-14 925

22-Dec-14

Colilert Chlorine

DATE ALTERNATE LOCATION

TC E.coli Time Temp TDS Cond pH Free Total Turbidity Comments

P/A P/A C mg/L uS/cm mg/L mg/L NTU

13-Jan-14

28-Jan-14

11-Feb-14

14-Feb-14

25-Feb-14

10-Mar-14

25-Mar-14

9-Apr-14

23-Apr-14

6-May-14

20-May-14

2-Jun-14

16-Jun-14

2-Jul-14

14-Jul-14

28-Jul-14

11-Aug-14

26-Aug-14

8-Sep-14

24-Sep-13

7-Oct-14

20-Oct-14

21-Oct-14 2637 1ST STREET 830

3-Nov-14

18-Nov-14

2-Dec-14

16-Dec-14

22-Dec-14

Colilert Chlorine

APPENDIX C

REPORTED TO Regional District of Okanagan Similkameen

Penticton, BC V2A 5J9

TEL

FAX

ATTENTION WORK ORDER

General Comments:

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate

regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing

methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition

document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage

resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis .

Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Issued By:

#110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue

Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7

Tel: 604-279-1499 Fax: 604-279-1599 Tel: 250-765-9646 Fax: 250-765-3893 Tel: 780-489-9100 Fax: 780-489-9700

www.caro.ca

Locations:

4081680

Please contact CARO if more information is needed or to provide feedback on our services.

CERTIFICATE OF ANALYSIS

PO NUMBER RECEIVED / TEMP Aug-27-14 09:48 / 9°C

PROJECT REPORTED Sep-05-14

PROJECT INFO COC NUMBER B11099

101 Martin Street 1-250-490-4106

(250) 492-0063

Rob Palmer

Olalla Water System

Administration Coordinator

Jennifer Shanko, AScT

Work Order Comments:

Custody Seal Intact when received by CARO.

Sept.5/14- This is an amended report from the original issued Sept.4/14. Please note that the TDS value has been

revised for sample 4081680-01 (due to transcription error).- JLS

Page 1 of 4CARO Analytical ServicesRev 08/19/14 Page 1 of 4

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen WORK ORDER

REPORTED Sep-05-14

ANALYSIS INFORMATION

Olalla Water System

4081680

Technique LocationAnalysis Description Method Reference

Alkalinity, speciated APHA 2320 B Titration with H2SO4 to pH 4.5 Kelowna

Anions in Water by IC APHA 4110 B Ion Chromatography with Chemical Suppression of

Eluent Conductivity

Kelowna

Colour, True APHA 2120 C * Spectrophotometry (410 nm) Kelowna

Conductivity in Water APHA 2510 B Conductivity Meter Kelowna

Cyanide, Total in Liquids APHA 4500-CN- C /

APHA 4500-CN- E

Distillation / Colorimetry Kelowna

Hardness (as CaCO3) APHA 2340 B Calculation N/A

pH in Water APHA 4500-H+ B Electrometry Kelowna

Total Dissolved Solids (GRAV) APHA 2540 C Gravimetry (Dried at 103-105C) Kelowna

Total Recoverable Metals APHA 3030E * / APHA

3125 B

HNO3+HCl Hot Block Digestion / Inductively Coupled

Plasma Mass Spectrometry (ICP-MS)

Richmond

Transmissivity at 254 nm APHA 5910 B Ultraviolet Absorption Kelowna

Turbidity APHA 2130 B Nephelometry Kelowna

Note: An asterisk in the Method Reference indicates that the CARO method has been modified from the reference method

Method Reference Descriptions:

APHA Standard Methods for the Examination of Water and Wastewater, 22nd Edition, American Public Health

Association/American Water Works Association/Water Environment Federation

Glossary of Terms:

MRL Method Reporting Limit

Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to various factors such

as dilutions, limited sample volume, high moisture, or interferences

<

AO Aesthetic objective

MAC Maximum acceptable concentration (health based)

OG Operational guideline (treated water)

Percent Transmittance% T

Colour Units (referenced against a platinum cobalt standard)CU

Milligrams per litremg/L

Nephelometric Turbidity UnitsNTU

pH < 7 = acidic, ph > 7 = basicpH units

Microsiemens per centimetreµS/cm

Standards / Guidelines Referenced in this Report:

Guidelines for Canadian Drinking Water Quality (2012)

Website: http://www.hc-sc.gc.ca/ewh-semt/pubs/water-eau/2012-sum_guide-res_recom/index-eng.php

Note: In some cases, the values displayed on the report represent the lowest guideline and are to be verified by the end user

Page 2 of 4CARO Analytical ServicesRev 08/19/14 Page 2 of 4

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen WORK ORDER

REPORTED Sep-05-14

SAMPLE ANALYTICAL DATA

Olalla Water System

4081680

Analyte Result /

Recovery

Standard /

Guideline

MRL /

Limits

Units Prepared Analyzed Notes

Sample ID: Pump House (4081680-01) [Water] Sampled: Aug-26-14 08:05

Anions

mg/L148Alkalinity, Total as CaCO3 Aug-27-141 N/AN/A

mg/L< 1Alkalinity, Phenolphthalein as CaCO3 Aug-27-141 N/AN/A

mg/L148Alkalinity, Bicarbonate as CaCO3 Aug-27-141 N/AN/A

mg/L< 1Alkalinity, Carbonate as CaCO3 Aug-27-141 N/AN/A

mg/L< 1Alkalinity, Hydroxide as CaCO3 Aug-27-141 N/AN/A

mg/L8.66Chloride Aug-28-140.10 N/AAO 250

mg/L< 0.10Fluoride Aug-28-140.10 N/AMAC = 1.5

mg/L0.349Nitrogen, Nitrate as N Aug-28-140.010 N/AMAC = 10

mg/L< 0.010Nitrogen, Nitrite as N Aug-28-140.010 N/AMAC = 1

mg/L57.2Sulfate Aug-28-141.0 N/AAO 500

General Parameters

CU< 5Colour, True Aug-28-145 Aug-28-14AO 15

µS/cm419Conductivity (EC) Aug-27-142 N/AN/A

mg/L< 0.010Cyanide, total Sep-02-140.010 Sep-02-14MAC = 0.2

pH units7.94pH Aug-27-140.01 N/A6.5-8.5

mg/L272Solids, Total Dissolved Aug-28-1410 N/AAO 500

NTU< 0.1Turbidity Aug-28-140.1 N/AOG < 0.1

% T99.0UV Transmittance @ 254nm Aug-29-140.1 N/AN/A

Calculated Parameters

mg/L199Hardness, Total (Total as CaCO3) N/A5.0 N/AN/A

mg/L0.349Nitrogen, Nitrate+Nitrite as N N/A0.020 N/AN/A

Total Recoverable Metals

mg/L< 0.05Aluminum, total Aug-28-140.05 Aug-28-14OG < 0.1

mg/L0.001Antimony, total Aug-28-140.001 Aug-28-14MAC = 0.006

mg/L< 0.005Arsenic, total Aug-28-140.005 Aug-28-14MAC = 0.01

mg/L0.07Barium, total Aug-28-140.05 Aug-28-14MAC = 1

mg/L< 0.001Beryllium, total Aug-28-140.001 Aug-28-14N/A

mg/L< 0.001Bismuth, total Aug-28-140.001 Aug-28-14N/A

mg/L0.04Boron, total Aug-28-140.04 Aug-28-14MAC = 5

mg/L< 0.0001Cadmium, total Aug-28-140.0001 Aug-28-14MAC = 0.005

mg/L60.4Calcium, total Aug-28-142.0 Aug-28-14N/A

mg/L< 0.005Chromium, total Aug-28-140.005 Aug-28-14MAC = 0.05

mg/L< 0.0005Cobalt, total Aug-28-140.0005 Aug-28-14N/A

mg/L0.005Copper, total Aug-28-140.002 Aug-28-14AO 1

mg/L< 0.10Iron, total Aug-28-140.10 Aug-28-14AO 0.3

mg/L< 0.001Lead, total Aug-28-140.001 Aug-28-14MAC = 0.01

mg/L0.003Lithium, total Aug-28-140.001 Aug-28-14N/A

mg/L11.8Magnesium, total Aug-28-140.1 Aug-28-14N/A

mg/L< 0.002Manganese, total Aug-28-140.002 Aug-28-14AO 0.05

mg/L< 0.0002Mercury, total Aug-29-140.0002 Aug-28-14MAC = 0.001

mg/L0.004Molybdenum, total Aug-28-140.001 Aug-28-14N/A

mg/L< 0.002Nickel, total Aug-28-140.002 Aug-28-14N/A

mg/L< 0.2Phosphorus, total Aug-28-140.2 Aug-28-14N/A

mg/L2.0Potassium, total Aug-28-140.2 Aug-28-14N/A

Page 3 of 4CARO Analytical ServicesRev 08/19/14 Page 3 of 4

REPORTED TO

PROJECT

Regional District of Okanagan Similkameen WORK ORDER

REPORTED Sep-05-14

SAMPLE ANALYTICAL DATA

Olalla Water System

4081680

Analyte Result /

Recovery

Standard /

Guideline

MRL /

Limits

Units Prepared Analyzed Notes

Sample ID: Pump House (4081680-01) [Water] Sampled: Aug-26-14 08:05, Continued

Total Recoverable Metals, Continued

mg/L< 0.005Selenium, total Aug-28-140.005 Aug-28-14MAC = 0.01

mg/L7Silicon, total Aug-28-145 Aug-28-14N/A

mg/L< 0.0005Silver, total Aug-28-140.0005 Aug-28-14N/A

mg/L11.3Sodium, total Aug-28-140.2 Aug-28-14AO 200

mg/L0.29Strontium, total Aug-28-140.01 Aug-28-14N/A

mg/L11Sulfur, total Aug-28-1410 Aug-28-14N/A

mg/L< 0.002Tellurium, total Aug-28-140.002 Aug-28-14N/A

mg/L< 0.0002Thallium, total Aug-28-140.0002 Aug-28-14N/A

mg/L< 0.001Thorium, total Aug-28-140.001 Aug-28-14N/A

mg/L< 0.002Tin, total Aug-28-140.002 Aug-28-14N/A

mg/L< 0.05Titanium, total Aug-28-140.05 Aug-28-14N/A

mg/L0.0008Uranium, total Aug-28-140.0002 Aug-28-14MAC = 0.02

mg/L< 0.01Vanadium, total Aug-28-140.01 Aug-28-14N/A

mg/L< 0.04Zinc, total Aug-28-140.04 Aug-28-14AO 5

mg/L< 0.001Zirconium, total Aug-28-140.001 Aug-28-14N/A

Page 4 of 4CARO Analytical ServicesRev 08/19/14 Page 4 of 4

Olalla Source Water Quality

0.005

0

0.005

0 0 0 0 0 0

0.01

0.02

0.03

0.04

0.05

0.06

0.07

0.08

0.09

0.1

23/08/2007 25/08/2008 24/08/2009 15/09/2010 07/09/2011 13/08/2012 27/08/2013 26/08/2014

mg/

L -

IMA

C

Aluminum

Aluminum

Olalla Source Water Quality

0 0 0 0.0001

0 0 0

0.001

0

0.001

0.002

0.003

0.004

0.005

0.006

23/08/2007 25/08/2008 24/08/2009 15/09/2010 07/09/2011 13/08/2012 27/08/2013 26/08/2014

mg/

L -

MA

C

Antimony

Antimony

Olalla Source Water Quality

0.0008 0.0009

0.0015

0.0008

0 0 0 0 0

0.002

0.004

0.006

0.008

0.01

23/08/2007 25/08/2008 24/08/2009 15/09/2010 07/09/2011 13/08/2012 27/08/2013 26/08/2014

mg/

L -

MA

C

Arsenic

Arsenic

Olalla Source Water Quality

0.07 0.072 0.091

0.0721 0.069 0.07 0.08 0.07

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

23/08/2007 25/08/2008 24/08/2009 15/09/2010 07/09/2011 13/08/2012 27/08/2013 26/08/2014

mg/

L -

MA

C

Barium

Barium

Olalla Source Water Quality

0.015 0.02 0.015 0.014 0 0 0 0.04

0

0.5

1

1.5

2

2.5

3

3.5

4

4.5

5

23/08/2007 25/08/2008 24/08/2009 15/09/2010 07/09/2011 13/08/2012 27/08/2013 26/08/2014

mg/

L -

IMA

C

Boron

Boron

Olalla Source Water Quality

0

0.001

0.002

0.003

0.004

0.005

23/08/2007 25/08/2008 24/08/2009 15/09/2010 07/09/2011 13/08/2012 27/08/2013 26/08/2014

mg/

L -

IMA

C

Cadmium

Cadmium

Olalla Source Water Quality

58.8 58.2

56.1

52.5

56.9 56

55

60.4

0

10

20

30

40

50

60

70

23/08/2007 25/08/2008 24/08/2009 15/09/2010 07/09/2011 13/08/2012 27/08/2013 26/08/2014

mg/

L

Calcium

Calcium

Olalla Source Water Quality

6.4 6.4 8.2 6.96 7.58 8.87 8.06 8.66

0

50

100

150

200

250

23/08/2007 25/08/2008 24/08/2009 15/09/2010 07/09/2011 13/08/2012 27/08/2013 26/08/2014

mg/

L -

AO

Chloride

Chloride

Olalla Source Water Quality

0.0008 0

0.0006 0.0014

0 0 0 0 0

0.005

0.01

0.015

0.02

0.025

0.03

0.035

0.04

0.045

0.05

23/08/2007 25/08/2008 24/08/2009 15/09/2010 07/09/2011 13/08/2012 27/08/2013 26/08/2014

mg/

L -

MA

C

Chromium

Chromium

Olalla Source Water Quality

-1

1

3

5

7

9

11

13

15

23/08/2007 25/08/2008 24/08/2009 15/09/2010 07/09/2011 13/08/2012 27/08/2013 26/08/2014

TCU

- A

O

Color

Colour

Olalla Source Water Quality

0.004 0.002 0.003 0.0029 0.0036 0.004 0.002 0.005 0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

23/08/2007 25/08/2008 24/08/2009 15/09/2010 07/09/2011 13/08/2012 27/08/2013 26/08/2014

mg/

L -

AO

Copper - Total

Copper

Olalla Source Water Quality

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

23/08/2007 25/08/2008 24/08/2009 15/09/2010 07/09/2011 13/08/2012 27/08/2013 26/08/2014

mg/

L -

MA

C

Cyanide

Cyanide

Olalla Source Water Quality

0.17 0.13 0.13 0.12

0.16

0.11 0.12

0 0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

1.1

1.2

1.3

1.4

1.5

23/08/2007 25/08/2008 24/08/2009 15/09/2010 07/09/2011 13/08/2012 27/08/2013 26/08/2014

mg/

L -

MA

C

Fluoride - Dissolved

Fluoride

Olalla Source Water Quality

193 190

185

175

188 187 191

199

0

50

100

150

200

250

23/08/2007 25/08/2008 24/08/2009 15/09/2010 07/09/2011 13/08/2012 27/08/2013 26/08/2014

mg/

L as

CaC

O3

Hardness

Hardness

Olalla Source Water Quality

0 0

0.01

0.03

0 0 0 0 0

0.05

0.1

0.15

0.2

0.25

0.3

23/08/2007 25/08/2008 24/08/2009 15/09/2010 07/09/2011 13/08/2012 27/08/2013 26/08/2014

mg/

L -

AO

Iron

Iron - Total

Olalla Source Water Quality

0.001

0 0.0002

0.0014

0 0 0 0 0

0.002

0.004

0.006

0.008

0.01

23/08/2007 25/08/2008 24/08/2009 15/09/2010 07/09/2011 13/08/2012 27/08/2013 26/08/2014

mg/

L -

MA

C

Lead

Lead

Olalla Source Water Quality

11.2 10.9 11

10.7 11.1

11.6

13.2

11.8

0

2

4

6

8

10

12

14

23/08/2007 25/08/2008 24/08/2009 15/09/2010 07/09/2011 13/08/2012 27/08/2013 26/08/2014

mg/

L Magnesium

Magnesium

Olalla Source Water Quality

0

0.02

0 0 0 0 0 0 0

0.005

0.01

0.015

0.02

0.025

0.03

0.035

0.04

0.045

0.05

23/08/2007 25/08/2008 24/08/2009 15/09/2010 07/09/2011 13/08/2012 27/08/2013 26/08/2014

mg/

L -

AO

Manganese

Manganese - Total

Olalla Source Water Quality

0

0.0002

0.0004

0.0006

0.0008

0.001

23/08/2007 25/08/2008 24/08/2009 15/09/2010 07/09/2011 13/08/2012 27/08/2013 26/08/2014

mg/

L -

MA

C

Mercury

Mercury

Olalla Source Water Quality

0.39 0.4 0.41 0.34 0.442 0.016 0.393 0.349

0

5

10

15

20

25

30

35

40

45

23/08/2007 25/08/2008 24/08/2009 15/09/2010 07/09/2011 13/08/2012 27/08/2013 26/08/2014

mg/

L -

MA

C

Nitrate - N

Nitrate - N

Olalla Source Water Quality

0 0 0 0 0 0 0 0

0.5

1

1.5

2

2.5

3

23/08/2007 25/08/2008 24/08/2009 15/09/2010 07/09/2011 13/08/2012 27/08/2013 26/08/2014

mg/

L -

MA

C

Nitrite - N

Nitrate - N

Olalla Source Water Quality

8.03 8.05 7.84

8.02 7.92 7.84 7.95 7.94

0

2

4

6

8

10

12

14

23/08/2007 25/08/2008 24/08/2009 15/09/2010 07/09/2011 13/08/2012 27/08/2013 26/08/2014

pH

pH

Olalla Source Water Quality

0.001

0.0004

0.0014 0.0013

0.0066

0

0.005

0 0

0.002

0.004

0.006

0.008

0.01

23/08/2007 25/08/2008 24/08/2009 15/09/2010 07/09/2011 13/08/2012 27/08/2013 26/08/2014

mg/

L -

MA

C

Selenium

Selenium

Olalla Source Water Quality

0

0.002

0.004

0.006

0.008

0.01

23/08/2007 25/08/2008 24/08/2009 15/09/2010 07/09/2011 13/08/2012 27/08/2013 26/08/2014

mg/

L Silver

Silver

Olalla Source Water Quality

9.6 9.8 9.6 8.53 10.2 10.6 12.1 11.3

0

20

40

60

80

100

120

140

160

180

200

23/08/2007 25/08/2008 24/08/2009 15/09/2010 07/09/2011 13/08/2012 27/08/2013 26/08/2014

mg/

L -

AO

Sodium

Sodium

Olalla Source Water Quality

51.4 50.5 46.9 52.7 53.4 53.1 51.7 57.2

0

50

100

150

200

250

300

350

400

450

500

23/08/2007 25/08/2008 24/08/2009 15/09/2010 07/09/2011 13/08/2012 27/08/2013 26/08/2014

mg/

L -

AO

Sulfate (SO4)

Sulfate (SO4)

Olalla Source Water Quality

232 231 240

260

234 243

234

272

0

50

100

150

200

250

300

350

400

450

500

23/08/2007 25/08/2008 24/08/2009 15/09/2010 07/09/2011 13/08/2012 27/08/2013 26/08/2014

mg/

L -

AO

Total Dissolved Solids

Total Dissolved Solids

Olalla Source Water Quality

0

0.5

1

1.5

2

2.5

3

3.5

4

4.5

5

23/08/2007 25/08/2008 24/08/2009 15/09/2010 07/09/2011 13/08/2012 27/08/2013 26/08/2014

NTU

- M

AC

Turbidity

Turbidity

Olalla Source Water Quality

0.0009

0

0.0012 0.00077 0.00073 0.0007 0.0008 0.0008

0

0.005

0.01

0.015

0.02

23/08/2007 25/08/2008 24/08/2009 15/09/2010 07/09/2011 13/08/2012 27/08/2013 26/08/2014

mg/

L -

MA

C

Uranium

Uranium

Olalla Source Water Quality

0.006 0.005 0.038 0.003 0 0 0 0 0

0.5

1

1.5

2

2.5

3

3.5

4

4.5

5

23/08/2007 25/08/2008 24/08/2009 15/09/2010 07/09/2011 13/08/2012 27/08/2013 26/08/2014

mg/

L -

AO

Zinc

Zinc

APPENDIX D

Regional District Okanagan-Similkameen Page : 1Date : Apr 01, 2015 Time : 12:20 pmCOMPARATIVE INCOME STATEMENT (2011-2014)

For Period Ending 31-Dec-2014

2011 2011 2012 2012 2013 2013 2014 2014

ACTUAL ANNUALBUDGET

ACTUAL ANNUALBUDGET

ACTUAL ANNUALBUDGET

ACTUAL (YTD) ANNUALBUDGETWATER REVENUE FUND

GL5410

DEPARTMENT 3960

REVENUES

WATER SYSTEM - OLALLA

))))))))3-1-3960-1000 TAX REQUISITION (16,505 (16,505 (17,497 (17,497 (13,316 (13,316 (15,774 (15,774))))3-1-3960-2700 INTEREST INCOME (3,667 0 (2,849 0 (2,287 0 (4,322 0

))))))))3-1-3960-4500 USER FEES (78,454 (74,386 (80,800 (77,385 (89,205 (90,335 (93,490 (90,335)))3-1-3960-6000 TRANSFER FROM RESERVE 0 0 0 (50,000 0 (32,000 0 (35,000

))3-1-3960-6070 TRANSFER FROM RESERVE - GASTAX (130,000 (130,000 0 0 0 0 0 0)3-1-3960-8040 PROVINCIAL GRANTS - WATER SYSTEM STUDY (1,290 0 0 0 0 0 0 0

))3-1-3960-9000 MISCELLANEOUS REVENUE 0 0 (146 0 0 0 (404 0))))))))3-1-3960-9990 PRIOR YEARS SURPLUS (53,109 (23,000 (28,459 (30,000 (9,820 (5,000 (21,351 (11,000

))))))))Total REVENUES (283,025 (243,891 (129,751 (174,882 (114,629 (140,651 (135,340 (152,109EXPENSES

WATER SYSTEM - OLALLA

3-2-3960-1000 SALARIES & WAGES 31,200 32,376 42,609 44,525 33,358 49,190 28,628 49,6723-2-3960-1400 ADMINISTRATION CHARGES 5,570 5,570 6,963 6,963 8,704 8,704 7,398 7,3983-2-3960-1500 IS 4,311 4,311 3,884 3,884 4,014 4,014 3,426 3,4263-2-3960-2500 OPERATIONS 14,410 7,000 6,135 9,990 3,221 8,373 8,031 8,4823-2-3960-2621 OP - W&S - WATER QUALITY MONITORING 1,331 1,621 1,577 1,642 1,211 2,105 1,229 2,0003-2-3960-2640 OPERATIONS - HEALTH & SAFETY 22 155 0 164 46 169 0 1693-2-3960-2900 LEAK DETECTION STUDY GRANT EXPENSES 3,070 0 0 0 0 0 0 03-2-3960-3000 CONSULTANTS 0 522 0 529 0 536 1,984 6863-2-3960-4000 EDUCATION & TRAINING 679 522 238 529 340 536 423 4003-2-3960-4200 SPECIAL PROJECTS 0 0 0 0 409 0 0 03-2-3960-5400 DEPRECIATION 5,628 5,628 5,796 5,796 5,970 5,970 5,970 5,9703-2-3960-5600 CAPITAL PROJECTS 136,836 130,000 530 50,000 4,881 32,000 1,320 35,0003-2-3960-6000 INSURANCE - PROPERTY 422 773 448 796 448 448 471 4613-2-3960-6050 INSURANCE - LIABILITY 456 536 470 552 527 527 580 5383-2-3960-6200 LEGAL FEES 0 500 0 500 0 500 0 5003-2-3960-7000 SUPPLIES 5 0 40 0 10 0 0 03-2-3960-8200 TRAVEL/LEASING 3,477 4,457 3,362 4,515 3,317 4,574 3,403 4,6333-2-3960-8500 UTILITIES 9,206 7,647 9,208 7,139 8,761 7,232 10,759 9,0003-2-3960-9010 DEBT INTEREST 6,111 6,110 6,111 6,110 6,111 6,110 4,304 6,1113-2-3960-9020 DEBT PRINCIPAL 9,663 9,663 9,663 9,663 9,663 9,663 9,663 9,6633-2-3960-9200 TRANSFER TO RESERVE 10,000 10,000 20,000 20,000 0 0 30,000 5,0003-2-3960-9205 TRANSFER INTEREST TO RESERVES 3,667 0 2,849 0 2,287 0 4,322 03-2-3960-9290 TRANSFER TO OPERATING RESERVE 8,500 8,500 0 0 0 0 0 03-2-3960-9300 CONTINGENCY 0 5,000 48 1,585 0 0 0 3,0003-2-3960-9600 ELECTION - WATER BOARD 0 3,000 0 0 0 0 0 0

Total EXPENSES 254,566 243,891 119,931 174,882 93,278 140,651 121,911 152,109

))))Total DEPARTMENT 3960 (28,459 0 (9,820 0 (21,351 0 (13,430 0