1 Appendix D to 2015 CPUC Annual Report Safety Incidents Open as of 1-1-2015 and Incidents Reported in 2015 Gas Incidents (In Compliance with CA Public Utilities Code Section 911 & Senate Bill 1409 signed into law on September 25, 2014) Incident ID: This number reflects the year, month, the day, the sequence the incident is reported/occurred Incident ID (YYYYMMDD -XX) Facility Owner Reason for Investigation Facility Type Brief Description of Incident Open or Closed 20121201- 01 PG&E Damages Above 50K Transmission PG&E was notified at 8:40AM of a release of gas at 3205 E Miner Street, Stockton, San Joaquin County. PG&E arrived on-site at 9:05AM and the flow of gas was stopped at 9:56AM. Release of gas caused by pipeline rupture. Approximately 100 customers expected Open 20130106- 01 SoCalGas Damages Above 50K Transmission An overpressurization event caused a gas release from relief valve that ignited at the relief valve vent in the Playa del Rey Underground Storage facility. Fire extinguished and there were no injuries reported. However, clean-up estimates coming in indicate total cost has potential to exceed $50,000. Closed 20140114- 01 SoCalGas Media Coverage Main A leak was called into the city of Palm Desert. The gas company has responded to control gas and make repairs on a cracked Aldyl-A tee. This incident was reported due to the presence of media. Gas co. is currently on scene doing repairs. Closed 20140114- 02 SoCalGas Damages Above 50K Service Line A 3/4" steel service riser was damaged due to electrical arching that travelled through the grounded line and ignited. The ignition caused damage to a nearby wooden fence and garage estimated to exceed $50,000. Closed 20140123- 01 SoCalGas Media Coverage Regulator An area oder was called in. The Socal Gas representative found a leaking regulator at a regulator station. M&R was dispatched and made permanent repairs. The incident was reported late as Socal Gas was initially unaware of media coverage. Closed 20140214- 01 SoCalGas Media Coverage Main The customer at the location called in a gas leak/odor on 2/13/2014. SoCal Gas crews responded and confirmed nonhazardous leak indications in the area of the parkway near the street and notified the customer that it was nonhazardous but would return for the repairs. On 2/14/2014, SoCal Gas found that the customer reported the gas leak to Channel 4 news, and later repaired the code 3 leak. The incident was reported to the CPUC due to media coverage. Closed 20140218- 02 SoCalGas Media Coverage Main A third-party contractor working on street lighting construction hit a 3-inch plastic gas main. This incident became reportable due to media presence. Closed 20140218- 03 PG&E Media Coverage Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of gas. Closed 20140218- 04 PG&E Media Coverage Main A third-party dig-in at the intersection of 25th St & Diamond St in San Francisco damaged a 4" plastic main causing an unintentional release of gas. The line struck was a 4" plastic main. Closed 20140219- 01 SoCalGas Damages Above 50K Main High pressure water main break intruded into an 8" steel gas main causing service interruption and estimated property damage cost exceeding $50,000. Closed 20140219- 02 SoWEST Damages Above 50K Southwest Gas notified by customer of "no Gas" and found zero pressure at Needles City Gate due to inadvertent closure of a PG&E valve that supplies Southwest Gas' distribution system. Closed

Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

1

AppendixDto2015CPUCAnnualReport

SafetyIncidentsOpenasof1-1-2015andIncidentsReportedin2015GasIncidents

(InCompliancewithCAPublicUtilitiesCodeSection911&SenateBill1409signedintolawonSeptember25,2014)

IncidentID:Thisnumberreflectstheyear,month,theday,thesequencetheincidentisreported/occurred

IncidentID(YYYYMMDD

-XX)FacilityOwner

ReasonforInvestigation FacilityType BriefDescriptionofIncident

OpenorClosed

20121201-01 PG&E Damages

Above50K Transmission

PG&Ewasnotifiedat8:40AMofareleaseofgasat3205EMinerStreet,Stockton,SanJoaquinCounty.PG&Earrivedon-siteat9:05AMandtheflowofgaswasstoppedat9:56AM.Releaseofgascausedbypipelinerupture.Approximately100customersexpected

Open

20130106-01 SoCalGas Damages

Above50K Transmission

AnoverpressurizationeventcausedagasreleasefromreliefvalvethatignitedatthereliefvalveventinthePlayadelReyUndergroundStoragefacility.Fireextinguishedandtherewerenoinjuriesreported.However,clean-upestimatescominginindicatetotalcosthaspotentialtoexceed$50,000.

Closed

20140114-01 SoCalGas Media

Coverage Main

AleakwascalledintothecityofPalmDesert.ThegascompanyhasrespondedtocontrolgasandmakerepairsonacrackedAldyl-Atee.Thisincidentwasreportedduetothepresenceofmedia.Gasco.iscurrentlyonscenedoingrepairs.

Closed

20140114-02 SoCalGas Damages

Above50K ServiceLine

A3/4"steelserviceriserwasdamagedduetoelectricalarchingthattravelledthroughthegroundedlineandignited.Theignitioncauseddamagetoanearbywoodenfenceandgarageestimatedtoexceed$50,000.

Closed

20140123-01 SoCalGas Media

Coverage Regulator

Anareaoderwascalledin.TheSocalGasrepresentativefoundaleakingregulatorataregulatorstation.M&Rwasdispatchedandmadepermanentrepairs.TheincidentwasreportedlateasSocalGaswasinitiallyunawareofmediacoverage.

Closed

20140214-01 SoCalGas Media

Coverage Main

Thecustomeratthelocationcalledinagasleak/odoron2/13/2014.SoCalGascrewsrespondedandconfirmednonhazardousleakindicationsintheareaoftheparkwaynearthestreetandnotifiedthecustomerthatitwasnonhazardousbutwouldreturnfortherepairs.On2/14/2014,SoCalGasfoundthatthecustomerreportedthegasleaktoChannel4news,andlaterrepairedthecode3leak.TheincidentwasreportedtotheCPUCduetomediacoverage.

Closed

20140218-02 SoCalGas Media

Coverage MainAthird-partycontractorworkingonstreetlightingconstructionhita3-inchplasticgasmain.Thisincidentbecamereportableduetomediapresence.

Closed

20140218-03 PG&E Media

Coverage ServiceLine Athird-partyexcavatorstruckanddamageda1"plasticservicelinecausinganunintentionalreleaseofgas. Closed

20140218-04 PG&E Media

Coverage MainAthird-partydig-inattheintersectionof25thSt&DiamondStinSanFranciscodamageda4"plasticmaincausinganunintentionalreleaseofgas.Thelinestruckwasa4"plasticmain.

Closed

20140219-01 SoCalGas Damages

Above50K MainHighpressurewatermainbreakintrudedintoan8"steelgasmaincausingserviceinterruptionandestimatedpropertydamagecostexceeding$50,000.

Closed

20140219-02 SoWEST Damages

Above50K

SouthwestGasnotifiedbycustomerof"noGas"andfoundzeropressureatNeedlesCityGateduetoinadvertentclosureofaPG&EvalvethatsuppliesSouthwestGas'distributionsystem.

Closed

Page 2: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

2

20140219-04 PG&E Media

Coverage ServiceLine Athird-partyexcavatorstruckanddamageda1/2"plasticgasservicelinecausinganunintentionalreleaseofgas. Closed

20140306-01 PG&E Media

Coverage Main Athird-partydig-inatSutterandJonesinSanFranciscodamageda2"plasticgasmaincausinganunintentionalreleaseofgas. Closed

20140306-02 PG&E Media

Coverage ServiceLine Athird-partydig-indamageda1/2coppergasservicecausinganunintentionalreleaseofgas. Closed

20140306-03 SoCalGas Media

Coverage Main Thirdpartyexcavationdamageon4-inchsteeldistributionmaincausingareleaseofgas. Closed

20140310-02 SDG&E Damages

Above50KCustomerMeter

Ataxicabranoverametersetdamagingtheassemblyandcausingareleaseofgas. Closed

20140314-01 PG&E Damages

Above50K Transmission

PG&EwasperformingworkonL-101on3/13/2014toinstalla2-inchSave-A-Valveteeaspartofainternalpipelineinspectionproject.Duringthetappingandpluggingoperation,thecompletionplugbegantoleakatthethreads.Repairsareexpectedtoexceed$50,000.

Closed

20140324-01 SDG&E Media

Coverage ServiceRiserANSDG&Eemployeeworkingonmeterforafumigationorderbrokevalveoffrisercausingleak.Distributioncrewonsceneworkingongascontrol.ReportedduetoMediaonscene.

Closed

20140326-01 PG&E Damages

Above50K Transmission

PG&Econtractorwasperformingdeactivationworkonwhatwasbelievedtobethedeactivatedtransmissionline172AatthecornerofPineandGreenMeadowStreetsinWestSacramento.Instead,thePG&Econtractorinadvertentlyburnedaholeonaparallel16-inchpressurizedtransmissionpipecausingareleaseofgas.

Closed

20140407-01 PG&E Media

Coverage Regulator Astructurefireat4655MossbrookCircleinSanJose,SantaClaradamagedthegasmetersetassemblycausingareleaseofgas. Closed

20140408-01 SoCalGas Media

Coverage Main Athird-partycontractorstrucka2"plasticgasdistributionmaincausingareleaseofgas. Closed

20140408-04 PG&E Media

Coverage MainAthirdpartycontractorworkingfortheCityofSanFranciscostrucka4-inchplasticdistributionmainwhileexcavatingtoinstallnewsewerlaterals.

Closed

20140409-02 PG&E Media

Coverage ServiceLineAthirdpartyexcavatorstruckandpulleda1-inchplasticservicefroman8-inchsteelgasdistributionmainwhileworkingonasewerline.

Closed

20140425-01 SDG&E Media

Coverage Main Publicworksdeparmentdugoutsidedelineatedandmarkedarea,andstruck1/2"plasticgasservice Closed

20140430-02 SDG&E Media

Coverage ServiceRiser Alandscapermowedoveragasrisercoveredwithgrasscausingaleak. Closed

20140501-01 SoCalGas Media

CoverageCustomerMeter

Firedamagedhomesandburnedapproximatelyonehalfacre.Asoneormorehomesburned,burningdebrisfellontwometersetassemblieswhichbroketherisers.Escapinggasignited,butdidnotcontributetopropertydamageorinjuriesof3personsburnedfromfire.

Closed

20140506-01 SoCalGas Media

Coverage ServiceLine LADWPexcavatingtoinstallelectricalconduithita2"gasservice. Closed

20140507-01 SDG&E Media

Coverage Main Athird-partycontractorstruckanddamageda4"steelgasmainwhileinstallingcommunicationconduits. Closed

20140514-01 PG&E

CasualtiesorInpatient

Hospitalization

CustomerMeter

Avehicletravelingatahighrateofspeedlefttheroadway,struckaresidencecausingsignificantstructuraldamageandalsostruckPG&Egasandelectricfacilitiesat405RamblerRd.,Merced.Theeventresultedinafireandafatality.

Closed

20140515-01 PG&E Media

Coverage Main Athirdpartyexcavatorstrucka6-inchplasticdistributionmainonSummersetDriveinRioVista. Closed

20140522-02 SoCalGas GasLoss Main Athird-partycontractorstruck2"plasticgasmain. Closed

20140524-01 PG&E Operator

JudgementCustomerMeter

Astructurefireat760SirFrancisDrakeBlvdinSanAnselmodamagedagasmetermanifoldcausingareleaseofgas. Closed

Page 3: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

3

20140529-01 PG&E Media

Coverage MainAthird-partypartydig-inattheintersectionofRubyAvenueandTullyRoadinSanJosedamgeda4-inchplasticgasdistributionmaincausingareleaseofgas.

Closed

20140529-02 PG&E Interruption Main

Athird-partydig-inofa4-inchgasdistributionmainat10983N.WolfeRoad,Cupertino(VallcoVillageShoppingCenter)causedareleaseofgas.IncidentwasreportedtotheCPUCduetothelargenumberofcommercialcustomersaffectedbytheserviceinterruption.

Closed

20140529-03 PG&E Interruption ServiceLine

Athird-partydig-inat1050AndersenRoadinSanRafaeldamageda4-inchplasticgasdistributionmain.IncidentwasreportedtotheCPUCduetothelargenumberofcommercialcustomersaffectedbytheserviceinterruption.

Closed

20140530-01 SDG&E Media

Coverage ServiceLine Athird-partyexcavatorstruckanddamageda1/2"plasticgasserviceduringpotholingofthefacility. Closed

20140602-01 SoCalGas Media

Coverage ServiceRiser Debrisfromrooffellandsnappedgasmeterbypassduringremodelcausingareleaseofgas.Reportedduetomediapresence. Closed

20140605-01 SoCalGas Media

CoverageCustomerMeter

Explosion,reportedtobeunrelatedtothegasfacilities,insidearesidentialstructurepushedawallintothegasmeterknockingitoffthemetersetassembly.

Closed

20140606-01 SoCalGas Media

CoverageCustomerMeter

Avehicledroveoveraparkingspotthroughagrassareaandhitthemetersetassemblycausingaleak. Closed

20140609-01 PG&E Media

Coverage ServiceLine Athirdpartydig-inat580TexasSt.,Fairfielddamageda1"plasticgasserviceresultinginareleaseofgas. Closed

20140610-01 SDG&E Media

Coverage ServiceLine Athird-partycontractorstruckanddamageda1/2"plasticgasservicelinewithapostholedigger.Reportedduetomediacoverage. Closed

20140611-01 SDG&E Media

Coverage ServiceRiser Policehighspeedchaseendinginvehicleaccidentdamagedthegasmetersetassemblyatabusinesslocation. Closed

20140611-02 SoCalGas Media

Coverage ServiceRiser Avehiclestruckthegasmetersetassemblyresultinginagasleak.Theincidentwasreportedduetomediapresence. Closed

20140611-03 SoCalGas GasLoss

Reportofgasodorcausedbyacrackedfittingona4"plasticgasfitting.Thisincidentwasreportedduetomediapresence. Closed

20140613-01 PG&E Damages

Above50KCustomerMeter

Structurefirereportedatmultiplehomesat1000,1002,and1008StevensSt.inTaft,CAofKernCountydamagedgasmeter.Propertydamageestimatedtoexceed$50,000.

Closed

20140618-01 PG&E Media

Coverage MainAPG&Econtractordiginincidentoccurredat1640SchoolStreetinMoraga.Thecontractorstrucka2.5"steeldistributionmainduringsaw-cuttingactivities.

Closed

20140620-01 PG&E Damages

Above50K MainAthird-partydig-inoccurrednearSomersvilleRoadandJamesDonlonBlvd.inAntiochdamageda4"plasticdistributionmainthatcausedanunintentionalreleaseofgas.

Closed

20140620-02 PG&E Media

Coverage ValveAbrushfireonavacantlotmeltedanundergroundgasservicevalveat2117CordeliaAve.inFairfield.Thebrushfirealsoledtotwostructurefiresandanelectricpolefire.

Closed

20140623-01 SDG&E Media

Coverage Main Athird-partylandscapecontractordamageda2"plasticmaincuasingareleaseofgas. Closed

20140624-01 SoCalGas Media

Coverage Main ASoCalGascrewwasexcavatingtoperformmaintenanceonavalve,a3/4"fittingwashitbythebackhoecausingtheleak. Closed

20140627-01 PG&E Media

CoverageCustomerMeter

Astructurefireat435TulipStreetinFairfielddamagedthegasmeter. Closed

20140628-01 PG&E Operator

Judgement ServiceRiser Astructurefireat601WestSchoolStreetinCotatidamagedthegasmetersetcausingareleaseofgas. Closed

20140701-01 SoCalGas Media

Coverage Main Athirdpartycontractordug-ininto3"plasticgasline. Closed

20140702-01 SoCalGas

CasualtiesorInpatient

Hospitalization

ServiceLine

Customer/Homeownerstruck1/2"plasticgasservicelinewithapickaxwhiletrenchingtoinstallelectricalconduit.IncidentreportedtotheCPUCwhentheexcavatorwastakentothehospitalduetoeyeinjury.Itwaslaterdeterminedthattheinjuredhomeownerwasnot

Closed

Page 4: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

4

admittedtothehospital.

20140707-01 PG&E Media

CoverageCustomerMeter

Astructurefireat320VillageLane,LosGatosdamagedthemetersetandareleaseofgas. Closed

20140707-02 PG&E Operator

JudgementCustomerMeter

Astructurefiredamagedthemetersetassemblycausingareleaseofgas.Incidentinitiallyreportedasdamagesmayexceed$50,000. Closed

20140709-01 SDG&E Media

Coverage ServiceLine Athird-partycontractorhitanddamageda1/2"plasticgasservicewithhandtools. Closed

20140709-02 PG&E Media

Coverage ServiceLineAthird-partyinstallingafenceforacustomerat2849S.WhiteRd.,SanJosehitanddamageda1"plasticgasservicelineresultinginareleaseofgas.

Closed

20140711-01 SDG&E Media

Coverage ServiceLine Athird-partycontractorhita11/4"gasservicemainwithanaugerwhilediggingtoinstalltemporarypowerpolescausingaleak. Closed

20140715-01 PG&E Media

Coverage MainAPG&Ecrewstruckanddamageda2"steelgasdistributionmainwithabackhoewhilerepairingaleakonaserviceat242ArletaAvenue,SanFrancisco.

Closed

20140718-01 SoCalGas Damages

Above50K Transmission

Athird-partycontractorstruckanddamageda10"steelgastransmissionlinewhilegradingforapond.Noreportedinjuriesorfatalities.ReportedtoDOTduetopotentialthatdamagecouldexceed$50Kand/orgaslostcouldexceed3millioncubicfeet.

Closed

20140718-02 PG&E Damages

Above50K ServiceRiserAresidentialfireat1840E23rdStreetUnitA,inMercedbytheMariposaFireDepartment.Theeletricalweatherheadreportedfellanddamagedthegasmetersetassemblycausingareleaseofgas.

Closed

20140719-01 SDG&E Media

CoverageCustomerMeter

ThisincidentwascalledintotheCPUCat06:23butdidnotindicatereportingtoDOT.DOTwasnotifiedduetoinjuryofpassengerofcarandisunknownatthistimeiftheindividualwillbehospitalizedbasedonthoseinjuries.Summary:Atornear4:30a

Closed

20140722-01 PG&E Media

CoverageCustomerMeter

Avehicleaccidentdamagedagasmetersetat2045EvansAve,SanFranciscocausingareleaseofgas.Thedriverofthevehiclewastransportedtothehospitalforinjuriessustainedfromthevehicleimpact.

Closed

20140723-01 PG&E Media

Coverage MainAthirdpartydig-inat333SCapitolAve,SanJose,CAdamageda3"plasticgasdistirbutionmainneartheSantaClaraValleyTransportationAuthorityAlumRocklight-railstation.

Closed

20140723-02 SoCalGas Media

Coverage Main Athird-partycontractorpulledoffa4"fittingonagasdistributionmaincausingareleaseofgas. Closed

20140728-01 SDG&E Media

Coverage ServiceLine Athird-partycontractorwasdiggingwithabackhoewhentheystruckthe2"plasticgasmainresultinginagasleak. Closed

20140729-01 Propane Operator

JudgementCustomerMeter

FerrelGasreportedthisincidenttotheCPUCon08/29/2014.AnelectricalfireatWhisperingPinesMHP(PropaneCPUCID1109),space#18,resultedinpartofthecustomer'smeterbeingpartiallymelted.

Closed

20140730-02 SoCalGas Media

Coverage ServiceRiser Avehiclehitthegasmetersetassemblyresultinginaleak.Theincidentwasreportedduetomediapresence. Closed

20140804-01 SoCalGas Media

Coverage ServiceLineAthird-partycontractorwasexcavatingtoinstallelectricalwhentheystrucka1"plasticgasservicecausingaleak.Incidentreportedduetomediacoverage.

Closed

20140804-02 PG&E Media

Coverage Main Athird-partycontractorstruckanddamageda3"plasticgasdistirbutionmainat1975DiamondBoulevardinConcord. Closed

20140810-01 SDG&E Media

CoverageCustomerMeter

Homeowner'svehiclestruckthemetersetassemblycausingareleaseofgas. Closed

20140811-01 PG&E Media

Coverage Main Athird-partydugintoa4"plasticdistributionmaincausingareleaseofgas. Closed

20140818-01 PG&E Media

Coverage ServiceRiser Astructurefireatanabandonedcarpetwarehouseat10121SanLeandroStreetmeltedthegasrisercausingareleaseofgasandfire. Closed

Page 5: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

5

20140819-01 PG&E Damages

Above50K TransmissionWhileexcavatingovertransmissionline173forpipelinework,PG&Ecrewstrucka3/4"teeonatransmissionlinewithpowerequipmentcausingareleaseofgas.

Closed

20140820-01 SoCalGas Media

Coverage Main Athird-partyexcavationdamageda2"plasticgasmainwhileinstallingelectricalconduit. Closed

20140820-02 PG&E Media

Coverage MainAthird-partyexcavatorstruckanddamagedateeoffa4"steelgasdistributionmainat9060Auburn-FolsomBoulevardandEurekaRoadinGraniteBay.

Closed

20140822-01 SoCalGas Media

Coverage Main Athirdpartycontractorwasperformingworktoexcavateforasewerlinewhentheystrucka2”plasticgasmaincausingagasleak. Closed

20140824-01 PG&E Damages

Above50K Main

Amagnitude6.0earthquakestrucktheNapaCountyarea.PG&EhasreceivedandrespondedtocustomerodorcallsandcallsfromFireandPoliceagenciesthroughoutthemorning.PG&Ehasconfirmedandremediatedleaksonanumberofdamagedservicerisers.

Closed

20140902-01 PG&E Media

CoverageCustomerMeter

Avehicleslammedintothehomeon208MidlandWayinDanvilledamagingthemetersetandcausinganunintentionalreleaseofgas. Closed

20140902-02 SDG&E Media

Coverage ServiceLine Athird-partyexcavatorinstallingfencepostsstruckanddamageda1"plasticservicegaslinecausingaleak. Closed

20140903-01 PG&E Media

CoverageCustomerMeter

Astructurefireoccurringat1905TheAlamedainSanJosedamagedthemetersetassemblycausingareleaseofgas. Closed

20140903-02 SDG&E Media

Coverage Main Athird-partyexcavatorhitanddamageda2"plasticgasmainwhileinstallinginanewcopperwaterservice. Closed

20140904-01 PG&E Media

CoverageCustomerMeter

Apolicepursuitendedinavehiclecrashingintoacommercialbuildingat1320PetalumaHillRoadinSantaRosa.Thegasmetersetandriserwasdamagedfromthevehicleimpact,resultinginanunintentionalreleaseofnaturalgas.

Closed

20140905-01 PG&E Operator

Judgement MainAthird-partystruckanddamagedaservicelinesaddleona3"gasdistributionmainatthesouth-westcornerof11thandCaminoRealinCarmelbytheSea.

Closed

20140905-02 PG&E Interruption Main Athird-partywasgradingtheareawhentheystrucka4"steel

distributionmaincausinganunintentionalreleaseofgas. Closed

20140905-03 PG&E Media

Coverage Regulator

AnACtransitbuscrashedintoahome(duplex)at78918thSt.&1770GarvinAve.inRichmond.ThePolicewerechasingastolencarthatcollidedintothebus,causingthebustocrashintothehome,damaginga2-metermanifold.Therewerereportedinjuriesduetothevehicleimpact.

Closed

20140907-01 SDG&E Damages

Above50KCustomerMeter

Electricarcingfromagaspipelinetracerwireagainstthesteelriser,asaresultedinastructurefireataresidenceinFallbrook.Unknowncause.Gasundercontrolatapproximately8:00am.Damageestimatedtobegreaterthan$50,000.

Closed

20140911-01 SDG&E Media

CoverageCustomerMeter

Avehiclestruckametersetassemblycausingaleak.Reportedduetomediacoverage Closed

20140911-02 SoCalGas

CasualtiesorInpatient

Hospitalization

ServiceLine

Athird-partycontractorworkingforthehomeownerat285FlowerDr.,LakeArrowhead,cutintothegasserviceriserwithahacksawcausingareleaseofgas.Thecontractorwastakentothehospitalduetogasinhalationbutlaterreleased.

Closed

20140911-03 SDG&E Media

Coverage Main Athird-partycontractorwasdiggingtoinstallaparkingmeterwhentheystrucka2"plasticgasmaincausingagasleak Closed

20140912-01 SDG&E Media

Coverage ServiceLine AthirdpartycontractorworkingfortheH.O.A.wasexcavatingandstrucka1"plasticlinecausingagasleak.Mediaisonscene. Closed

20140915-01 PG&E Operator

JudgementCustomerMeter

Astructurefirecausedbyadownelectriclineresultedinthehousecollapsingontothemetersetaseemblycausingareleaseofgas. Closed

20140915-02 SDG&E Media

Coverage Other Athirdpartycontractorstruckanddamageda1/2"plasticgasservice.Thiswasreportedduetomediacoverage. Closed

20140915-04 PG&E Damages

Above50K Main Athird-partyexcavatorstruckanddamageda2"steeldistributionmaincausingareleaseofgas.Damagesexceed$50,000. Closed

20140922- PG&E Media Main Athird-partystrucka3"steelgasdistributionmainresultingat Closed

Page 6: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

6

01 Coverage 23185MaudAvenueinHayward.

20140924-01 PG&E Media

Coverage ServiceLine PG&Ecrewstrucka4-inchmainat4245W.AshlanAvenue,Fresnoduringascheduledcutoffofagasservicefromthemain. Closed

20140925-01 PG&E Operator

Judgement ValveAstructurefireat4655KingRoadinLoomisdamagedthemetersetassemblycausingareleaseofgas.Damagetothepropertyestimatedtoexceed$50,000.

Closed

20140925-02 PG&E Media

Coverage Main

Areportofgasleakat3939N.PershingAvenue,BuildingA,inStockton.Thesourceoftheleakwasdeterminedtobeacracked4-inchplasticteeonthedistributionmain,damagedbyatreerootfromthetreetrunklocatedapproximately25feetaway.

Closed

20140930-01 PG&E Damages

Above50K Main Athird-partydamageda4"steelgasdistributionmaininSanJose(neartheintersectionofRidderParkDriveandSchallenbergerRoad). Closed

20141002-01 SDG&E Media

Coverage ServiceLine Athirdpartycontractorwasexcavatingandstrucka1/2"plasticservice.Thiswasreportedduetomediacoverage. Closed

20141005-01 PG&E

CasualtiesorInpatient

Hospitalization

ServiceRiser

Structurefireat935BroadwaySt.KingCity.Gasreleasedatmetersethasignited.Threeinjurieswerereportedforthisincident;twoinjuriesweretreatedandreleasedonsitebutoneresidentreceivedthirddegreeburnsthatrequiredovernighthospitalization.Damagestothestructureexceed$50K.

Closed

20141006-01 SDG&E Media

Coverage Main Athirdpartycontractorstrucka2"plasticgasmain.Thisincidentwasreportedduetomediacoverage. Closed

20141010-01 PG&E Operator

JudgementCustomerValve

Astructurefiredamagedthegasmetersetassemblycausingareleaseofgas. Closed

20141010-02 PG&E Operator

Judgement MainInadvertentclosureofavalveresultedinserviceinterruptiontomultiplegascustomersduringagasclearanceatChelseaAvenueand1stStreetinNapa.

Closed

20141011-01 PG&E Media

Coverage ServiceRiser Astructurefireat1695BlossomAvenue,Fairfielddamagedthemetersetassemblycausinganunintentionalreleaseofgas. Closed

20141013-01 PG&E Media

CoverageCustomerMeter

Avehiclecollisionwithametersetandserviceriserat312ArgonautAvenue,SanFranciscocausedanunintentionalreleaseofgas. Closed

20141015-01 PG&E Media

Coverage ServiceLineAthird-partystrucka1/2"plasticservicelinewithasnakeaugerwhilecleaningoutastormdrainatCStreetand12thStreetinSacramento.

Closed

20141015-02 SoCalGas Damages

Above50K ValveSoCalGaslossservicetomultiplecustomersduringagasclearanceworkwhenavalveataregulatorstationwasclosedcausingtheoutage.

Closed

20141017-01 PG&E Media

Coverage ServiceRiserAnelectricarcfromaSMUDtransformercausedaholeona1.25"steelservicelineat2275BenitaDriveinRanchoCordova,California,andreleasedgastotheatmosphere.

Closed

20141019-01 PG&E Operator

JudgementCustomerMeter

AstructurefireatSouthHazelwoodBoulevardandSouthFirstStreetinFresnodamagedgasmetersetassembliescausingareleaseofgas.

Closed

20141024-01 PG&E Media

Coverage Transmission Afarmerrippingafielddugintoa34"gastransmissionlineL-300AatWibleRoadandHoughtonRoadinBakersfield. Closed

20141026-01 SoCalGas Media

Coverage ServiceRiser Avehiclestruckanddamageda1"plasticserviceriser.Thiswasreportedduetomediacoverage. Closed

20141028-01 SoCalGas Damages

Above50K ServiceLineAthirdpartycontractorexcavatingtoinstallirrigationsystemstruckaserviceline.Itisbelievedthatthegasleakedthroughconduitsgettingintothegarageandcreatedtheexplosion.

Closed

20141029-01 PG&E Damages

Above50K Transmission

DuringaroutineleaksurveyofTransmissionLine,anon-hazardousleakwasdiscoveredatthecasingventonL-132atMilePoint3.07.The30-inchcasingand24-inchL-132crossbeneaththeUnionPacificRailRoadnearLafayetteandGianera.

Closed

20141030-02 PG&E Media

CoverageCustomerMeter

Avehicleimpactintoaservicemeterandriserat3344RioLindaBlvdinSacramentocausedanunintentionalreleaseofgas. Closed

20141104-01 SDG&E Media

Coverage ServiceLine Athird-partycontractorstruckanddamageda1"plasticgasservicelinecausingareleaseofgas. Closed

Page 7: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

7

20141105-01 SDG&E Media

Coverage Main Athird-partycontractorstruck2"plasticgaslineatthecornerofRegentsRd.andLaJollaVillageDr. Closed

20141105-02 PG&E Media

Coverage Main Athird-partycontractordugintoa4"plasticdistributionmaininAlamoneartheintersectionofLivornaRoadandWilsonRoad. Closed

20141105-03 SDG&E Media

Coverage ServiceLine Athirdpartycontractorhitanddamageda1/2"plasticserviceline.Thisincidentwasreportedduetomediacoverage. Closed

20141105-04 SDG&E Media

Coverage ServiceLine Athirdpartycontractorhita1/2"PEservicelinewhileexcavating.Thisincidentwasreportedduetomediacoverage. Closed

20141106-01 SDG&E Media

Coverage MainAthirdcontractorstruck2"plasticgasmainatthecornerofRegentsRd.andLaJollaVillageDr.Thisincidentwasreportedduetomediacoverage.

Closed

20141107-01 PG&E Damages

Above50K Main Athird-partyexcavatorstruckanddamageda4"plasticdistributionmainat1S.MarketSt.,SanJose. Closed

20141110-01 SoCalGas Media

Coverage ServiceLineAthird-partycontractorwasworkingtoinstallnewsignsforshoppingcentercomplexandstrucka2"plasticlinewithanauger.Thisincidentisreportedduetomediacoverage.

Closed

20141113-01 SoCalGas Media

Coverage ServiceLineAthird-partycontractorwastrenchingtoinstallirrigationsystemandstrucka1"plasticserviceline.Thisincidentwasreportedduetomediacoverage.

Closed

20141116-02 PG&E Damages

Above50KCustomerMeter

Avehiclestruckanddamagedafive-metermanifoldriserinSanJose,CAandcausedreleaseofnaturalgaswhichsubsequentlyignited.

Closed

20141120-01 SoCalGas Damages

Above50K TransmissionAfarmtractorrippedSoCalGasTransmissionLine#203resultingreleasenaturalgasintoatmosphere.Therewerenoinjuriesorfatalities.

Closed

20141120-02 SoCalGas

CasualtiesorInpatient

Hospitalization

ServiceRiserAstructurefirewasreportedwhereanillegalbypassonagasmeterfound.TheincidentwasreportedtoDOTdueto2fatalitiesandinjuries.

Closed

20141121-01 SDG&E Media

Coverage ServiceLine Athirdpartyexcavatorhita3/4"steelpipe.Theincidentbecamereportableduetomediaonsite. Closed

20141122-01 SDG&E Media

CoverageCustomerMeter

Avehiclehitametersetassemblycausingaleak.Theincidentbecamereportableduetomediaonscene. Closed

20141125-01 SoCalGas Media

Coverage Main Athirdpartycontractorstrucka2"plasticpipe.Thisbecanereportableduetomediaonscene. Closed

20141128-01 PG&E

CasualtiesorInpatient

Hospitalization

Reportofanexplosioninanapartmentresultinginoneinjury.Itwaslaterdeterminedthatnaturalgaswasinvolvedintheincident. Closed

20141129-01 SoCalGas Media

Coverage ServiceLine Avehicleranintoagasmetersetassembliescausingareleaseofgas.Incidentbecamereportableuponthearrivalofunknownmedia. Closed

20141204-01 SoCalGas Media

Coverage ServiceRiser Flashfloodwaterbrokea3/4"steelservicerisercausingreleaseofgas. Closed

20141208-01 SDG&E Damages

Above50K Main Athirdpartycontractorhita2"Steelgasmainresultingapproximately280customersoutofservice. Closed

20141210-01 PG&E Damages

Above50KCustomerMeter

Astructurefireaffectingtwoadjacenthousesat1928and1932RobertsonRoadinModestomeltedametersetassemblycausingreleaseofgas.

Closed

20141210-02 PG&E Operator

Judgement Transmission

PG&EfieldpersonnelreportedasuspiciousdevicediscoverednearnaturalgastransmissionpipelineLine314approximatelyonemilewestofHinkleyCompressorStation(35863FairviewRd,Hinkley).Thisdidnotresultinareleaseofgas.Therewerenoinjuries,fatalitiesorpropertydamagereported.

Closed

20141212-01 SoCalGas Media

Coverage

AnaturalgasleakwasreportedduetoforcesfrommudslidesatCamarilloSprings,agatedcommunity.Thiswasreportedduetoagasleakandmediacoverage.

Closed

Page 8: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

8

20141212-02 PG&E Media

Coverage Main Athird-partystrucka2"plasticdistributionmainwhileoperatingabackhoeat977EastHillsdaleBlvdinFosterCity(shoppingcenter). Closed

20141218-01 PG&E GasLoss Valve

An8-inchpressurereliefonPG&E's34-inchtransmissionlineL-300Batpressurelimitingstation,PLS4,inArvin,KernCounty,malfunctionedresultinginanunintentionalreleaseofgastotheatmosphere.

Closed

20141221-01 PG&E Media

CoverageCustomerMeter

PG&Ecalledtosceneafteragunexchangebetweenanarmedmanattheresidenceandpoliceisthoughttohavestruckthehousemeterandthenignitecausingastructurefirethatburnedthehousecompletely.

Closed

20141221-02 SoCalGas Media

CoverageCustomerMeter

Atreebranchfellontopofacommercial-sized9-metersetassemblycausingagasleak.Thiswasreportedduetomediacoverage. Closed

20141222-01 SoCalGas

CasualtiesorInpatient

Hospitalization

ServiceLine

Athirdpartycontractorwasexcavatingwithanelectricchippinghammerwhenhestruckaservicelinecausingagasleak.Thisincidentwasreportedduetopossiblehospitalizationofthecontractorandmediacoverage.Thecontractorwastransportedtolocalhospitalwithunknowninjuriesandwasreportedlyreleased.

Closed

20141223-01 PG&E Damages

Above50K Transmission

PG&Ecrewswereperformingaroutineleakinspectionandrepaironanon-hazardousleakonPG&E'stransmissionline(L-50AMP31.64)onHwy99justsouthofSkillinRoad,Oroville.Thecrewsobservedthattheleakcontinuedtomigratethroughtheexcavationandbecameahazardousleakrequiringimmediaterepair.Apin-holeleakduetoexternalcorrosionwasidentified.TheincidentwasreportedtoDOTandCPUCasthecostoftheincidentwasestimatedtoexceed$50,000.

Open

20141228-01 SoCalGas Media

CoverageCustomerMeter

Vehiclehitgasfacilitiesat1378NTowneAveinPomona,LosAngeles. Closed

20141230-01 PG&E Damages

Above50K ValvePG&EcrewswereperformingroutinemaintenanceworkonanautomatedvalveonPGE's6-inchtransmissionlineL105N,whenaleakona6"blowoffvalvewasobserved.

Closed

20150108-01 PG&E Media

CoverageCustomerMeter Avehicleimpactdamagedagasmetersetcausingareleaseofgas. Closed

20150109-01 SDG&E Media

Coverage ServiceLine Athird-partycontractorstruckanddamageda1-1/4"inchplasticservicelinecausingareleaseofgas. Closed

20150109-02 PG&E GasLoss Transmission

An8-inchpressurereliefvalve(onPG&E's34-inchtransmissionlineL-300Batpressurelimitingstation,4-PLS)inArvinopenedpriortoreachingitssetpointof721psig-resultinginanunintentionalreleaseofnaturalgas.

Closed

20150110-01 PG&E Operator

Judgement Regulator Astructurefireat116134thStreet,OaklandCAdamagedagasmetersetassemblythatcausedanunintentionalreleaseofgas. Closed

20150112-01 SDG&E Media

Coverage Main Athirdpartycontractordamageda3"gasmainresultinginagasleak.Thisincidentwasreportedduetomediacoverage. Closed

20150112-02 PG&E Operator

JudgementCustomerPipe

WhilePG&EmaintenancepersonnelwereperformingroutinemaintenanceworkonthemetersetattheAlamedaHospital,locatedat2070ClintonAve,AlamedaCA,slagfromthedistributionmainaccumulatedbetweenthebootandorificecausingtheregulatortofailresultinginanunintentionalreleaseofgasinthehospitalboilerroom.

Closed

20150114-01 SoCalGas Media

Coverage ServiceLine

Thethird-partycontractorwasboringtoinstallaconduitwhentheystrucka2"plasticservice.TheincidentlaterbecamereportableduetomediafollowupquestionsfromtheOCRegisterontheSoCalGasmediahotline.

Open

20150115-01 SDG&E Media

Coverage ServiceRiserAnunknownpersonthrewaconcereteblockataserviceriserinanabandonedbuilding.Theincidentbecamereportableduetomediapresence.

Closed

20150116-01 SoCalGas Media

Coverage Main Athirdpartycontractorwasexcavatingandstrucka3"plasticmaincausingagasleak.Thisincidentwasreportedduetomedia Closed

Page 9: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

9

coverage.

20150119-01 SoCalGas Media

Coverage MainAthirdpartycontractorstrucka3"plasticmainwhileexcavatingtolocateelectricalandreclaimedwater.Reportedduetomediacoverage.

Closed

20150120-01 PG&E Operator

Judgement ServiceLineAthird-partywasboringaconduitwhenitdamageda1-1/4"steelstubat2160TullyRoad,SanJose.Theincidentwasreportedduetoevacuationsinthearea.

Closed

20150121-01 PG&E Media

Coverage Regulator Astructurefireat7505HamilCt.Sacramentospreadandmeltedthegasmeterandriser,causinganunintentionalreleaseofgas. Closed

20150121-02 PG&E Operator

Judgement ServiceRiser Astructurefireat1049PucheuSt.,Mendotameltedthemeterandrisercausingareleaseofgas. Closed

20150122-01 SDG&E Media

Coverage Main Athird-partycontractordamagedandhita2"plasticmain.Reportedduetomediacoverage. Closed

20150122-02 PG&E Media

Coverage Main Athirdd-partydwasusingabackhoetofixawaterservicewhentheystrucka2"plasticmainat507LyonSt,SanFrancisco. Closed

20150122-03 SDG&E Media

Coverage ServiceLine Athird-partycontractorstruckanddamageda1/2"gasservice.Thisincidentwasreportedduetomediacoverage. Closed

20150125-01 PG&E Damages

Above50K ServiceRiser Astructurefireat22787AlderStreetinChowchillameltedthemeterandtheriservalvecausingareleaseofgas. Closed

20150126-01 PG&E Damages

Above50K ValveAvehicleimpactedagasmeterresultingareleaseofgaswhichignitedandcausedastructurefireata992ElCaminoRealinSanBruno.

Closed

20150128-01 PG&E GasLoss Transmission

ApressurelimitingvalveonPG&E's34-inchtransmissionlineL-300B(atpressurelimitingstationPLS-4)inArvinopenedresultinginanunintentionalreleaseofnaturalgastotheatmosphere.

Closed

20150128-02 PG&E Media

Coverage ServiceLine Athird-partycontractorstruckanddamgeda2"steelmaincausinganintentionalreleaseofgasat1855AlumRockAvenueinSanJose. Closed

20150129-01 SoCalGas Media

Coverage ServiceLine

Athird-partyconstructioncrewworkingtoframestepspriortopouringcement,dugastakeintoa1"plasticserviceline.Theconstructioncrewthendugaholeusingametalshovelthatcreatedaspark,resultinginafire.

Closed

20150130-01 SoCalGas Damages

Above50K Main

Abigtruckcaughtacablefromthepowerpolewhiledriving,draggedthecableandeventuallyknockeddownthepole.Theenergizedpowerlinecausedaleakonthegaslineandignitedthegas.

Closed

20150210-01 SoCalGas Media

Coverage ServiceRiserAthird-partycontractorwasworkingforweedandtrashabatementonavacantlotwhenhestrucka1/2"plasticservicerisercausingagasleak.

Closed

20150211-01 SDG&E Media

Coverage ServiceLineAthirdpartycontractorwasexcavatingwhenhestrucka1"plasticservicelinecausingagasleak.Thisincidentwasreportedduetomediacoverage.

Closed

20150212-01 PG&E Media

Coverage ServiceLine Acustomerwasperformingworknearthegasserviceriseranddamagedtheservicevalve. Closed

20150213-01 SoCalGas Media

CoverageCustomerMeter

Thedriverofastolenvehicledrovethevehicleintoahouseanddamagedthemetersetassembly.Thisresultedingasleak. Closed

20150218-01 PG&E Media

Coverage MainCustomerreportedsmellofgasoutinstreet,hissingatcracksinsidewalklaterdeterminedtobecausedfromaleakingserviceteecap.

Closed

20150219-01 SoCalGas Media

CoverageCustomerMeter Vehiclehita3-metermanifoldcausingreleaseofgas. Closed

20150219-02 SoCalGas Media

Coverage ServiceRiser Vehiclehitgasrisercausingreleaseofgas. Closed

20150220-01 SDG&E Media

Coverage ServiceRiserAforkliftstrucka3/4"plasticservicerisercausingagasleak.ThisincidentbecamereportableuntilSDG&Erecentlylearnedofmediainvolvement.

Open

20150226- SoCalGas Media Main Athirdpartywasexcavatingwithabackhoeandstrucka4"plastic Closed

Page 10: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

10

01 Coverage maincausingagasleak.

20150226-02 PG&E Media

Coverage ServiceLine Athird-partyexcavatorstruckanddamageda1/2"plasticservicelineat1066StocktonStreetinSanFrancisco. Closed

20150227-01 PG&E Damages

Above50K Main Athird-partystruckanddamagedan8"plasticmainwithabackhoeatElkGroveFlorinPerkins&GerberRd,inSacramento. Closed

20150228-01 PG&E Damages

Above50K Transmission

Athirdpartydamageda10"steeldistributionfeedermainDFM1815-15whiledoingroadclearing/gradingworknear610ViejoRdinCarmel-By-The-Seathatresultedinanunintentionalreleaseofgas.

Closed

20150301-01 SoCalGas Media

CoverageCustomerMeter

Avehiclestruckametersetassemblyresultingindamageandthesubsequentgasleak.Afatalityoccurredduetothevehiclecrashbutwasnotrelatedtoescapinggas.Thisincidentwasreportedduetomediacoverage.

Closed

20150303-01 PG&E Media

Coverage MainAthirdpartystruckanddamgeda4"plasticdistributionmainat1375SycamoreAveinHerculesthatresultedinanunintentionalreleaseofgas.

Closed

20150304-01 PG&E Media

Coverage Main Athird-partystrucka2"plasticdistributionmainwithanaugerat3737CasaVerdeStinSanJose. Closed

20150310-01 SDG&E Media

CoverageCustomerMeter

Avehiclestruckagasmetercausingagasleak.Thisincidentwasreportedduetomediacoverage. Closed

20150313-01 SoCalGas Media

Coverage ServiceRiser Structurefireoccurredindetachedbuildingwithkitchenequip.Fireengulfedmetersetassemblycausingignitedgasrelease Closed

20150314-01 SDG&E Media

Coverage ServiceLineAcontractorworkingforhomeownerdamageda1¼"plasticserviceservingahousewhiledigging.Incidentreportedduetomediaonscene.

Closed

20150321-01 PG&E Operator

Judgement ServiceLine Astructurefireat8794AlmondAvenueinDosPalosmeltingtheserviceriserandvalveresultinginarelease&ignitionofgas. Closed

20150323-01 PG&E Media

CoverageCustomerMeter

Avehiclerimpactedagasmeterat4045CabrilloStreetinSanFranciscocausingareleaseofgas. Closed

20150324-01 SoCalGas Media

CoverageCustomerMeter

Apowerpolewasknockeddownandlandedonametersetassembly,breakingthenipplebetweentheshuoffvalveandtheregulator.Thisincidentwasreportedduetomediacoverage

Closed

20150327-01 SoCalGas Media

Coverage ServiceRiser Avehiclestrucka½"plasticservicerisercausingagasleak.hisincidentwasreportedduetomediacoverage. Closed

20150406-01 SoCalGas Media

Coverage Main Athirdpartycontractorwasexcavatingforwaterandstrucka2"plasticmain.Thisincidentwasreportedduetomediacoverage. Closed

20150407-01 SoCalGas Media

Coverage Main Athirdpartycontractorwasexcavatingwithabackhoeandstrucka2"plasticgasmain.Thisincidentwasreportedduemediacoverage.S Closed

20150410-01 SDG&E Media

Coverage ServiceRiser Avehiclestruckourgasmetercausingaleak.Thisincidentbecamereportableduetomediapresence. Closed

20150413-01 PG&E Damages

Above50K TransmissionAthirdpartyexcavatorstruckanddamageda10"steeltransmissionline(L-220)milepoint(MP)6.71whileexcavatinganirrigationditch,whichresultedinanunintentionalreleaseofnaturalgas.

Closed

20150417-01 PG&E

CasualtiesorInpatient

Hospitalization

Transmission

AthirdpartygradingonaFresnoCountySheriff'sshootingrangeat7633N.WebberAve,Fresnopuncturedthe12"steelgastransmissionmain(L-118)whilegradingatthefootofslope.Incidentresultedinafatality.

Open

20150420-01 PG&E Media

Coverage ServiceLine Astructurefireatamobilehomepark(261WilburAve.#12,inYubaCity)damagedthemetersetcausingareleaseofgas. Closed

20150422-01 PG&E Media

Coverage ServiceLineAthirdpartycontractorboringforanewfiberopticlinestruckanddamageda1"plasticservicelinedig-inat1340WillowRd.inmeloParkcausinganunintentionalreleaseofgas.

Closed

20150423-01 PG&E Media

Coverage MainAthird-partyexcavatorstruckanddamageda4"plasticdistributionmainattheintersectionofBuchananRdandSomersvilleRdinAntiochthatresultedinanunintentionalreleaseofgas.

Closed

20150423- PG&E Operator Customer Astructurefireat897SanitariumRdinDeerParkinwhichthe Closed

Page 11: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

11

02 Judgement Meter serviceriserandmeterweredestroyedcausinganunintentionalreleaseofgas.

20150424-01 SoCalGas Media

Coverage ServiceLineAcontractorwasexcavatingwhenhestrucka1"plasticservicecausingagasleak.Thisincidentwasreportedduetomediacoverage.

Open

20150428-01 SoCalGas Media

Coverage ServiceLine A1"plasticservicewashitbyathirdpartycontractorcausingareleaseofgas.Incidentisbeingreportedduetomediainquiries. Closed

20150429-01 PG&E Media

Coverage MainAthird-partycontractorstruckanddmageda2"plasticmainwithabackhoeonthecornerofMasonicandHaightinSanFrancisco,causinganunintentionalreleaseofgas.

Closed

20150506-01 SDG&E Media

Coverage ServiceRiser Avehiclebackedintoagasservicerisercausingareleaseofgas.Thisincidentisbeingreportedduetomediacoverage. Open

20150507-01 PG&E Damages

Above50K TransmissionAPG&EcrewsmelledgasatthecornerofGardenHwy&LincolnHwyinYubaCity.Agrade1leakwasdiscoveredonagirthweldonDFM1501-01.

Open

20150507-02 PG&E Media

CoverageCustomerMeter

Astructurefireinademolishedhousespreadtothehousenextdoor(1175PineOakRd.)andmeltedthegasmeterandregulator. Closed

20150508-01 SoCalGas Damages

Above50K Main Waterdiscoveredinthegasline.Thecompanydeterminedthepossibilityoftheassociateddamageexceeding$50,000. Open

20150514-01 PG&E Media

CoverageCustomerMeter

Alightningstrikeonaflagpoleat4715Montclair,GraniteBayarcedtothecustomer'selectricservicewhichwasgroundedtothewaterpipeandbondedtothecustomer'sgashouseline,causingdamagetonylonbushingandasmallreleaseofgas.

Closed

20150516-01 SoCalGas GasLoss Main Athird-partyexcavatorhita6"plasticmaincausingareleaseofgas. Open

20150520-01 PG&E Media

Coverage ServiceLine

Athird-partycontractorwasworkinginanopenexcavationfortheMUNItunnelprojectwhentheexcavationpartiallycollapsedandconcretefellontoa1"plasticdistributionservicelinecausinganunintentionalreleaseofgas.

Closed

20150521-01 SoCalGas Media

Coverage ServiceLine Athirdpartyexcavatordamaged1/2"plasticserviceline.Theincidentwasreportedunderthemediacoveragecriteria. Open

20150526-01 PG&E Operator

Judgement Valve Astructurefireatavacanthouseat116MartinStinVallejomeltedametersetcausingareleaseofgas. Closed

20150527-01 SoCalGas Media

Coverage MainAthird-partycontractorwasworkingtorelocatesewerutilitiesforMetroProjectandstrucka2"plasticmain.Thisincidentwasreportedduetomediacoverage.

Closed

20150528-01 SDG&E Media

Coverage ServiceRiser Vehiclebackedintoameter,causingagasleak.Thisincidentwasreportedduetomediacoverage. Closed

20150529-01 SoCalGas Media

Coverage Main

Athird-partycontractorobservedandreportedagasleakona2"steelmainlaterdeterminedtobecausedbyexternalcorrosion.ThisincidentwasreportedwhenSoCalGasbecameawareofmediacoverage.

Closed

20150601-01 PG&E Damages

Above50KCustomerMeter

Astructurefireat56W.BolivarStreet,Salinasdamagedthemetersetcausingareleaseofgas. Closed

20150602-01 PG&E Media

Coverage Main

APG&Eelectriccrewstruckanddamageda3"steelgasmain.NearbyhomesandatleastthreeChicoStateUniversitybuildingswereevacuated.Media(TelemundoChico,KRCR,etc.)wasobservedonsite.

Closed

20150602-02 SoCalGas Media

Coverage Main Athird-partycontractorboringtoinstalltrafficsignsstrucka2-inchplasticmain.TheIncidentwasreportedduetomediainquiries. Closed

20150609-01 PG&E Media

Coverage ServiceLine Athird-partystruckanddamageda2"plasticstubatGreatOaksandLexingtoninanundevelopedareaofSanJose. Open

20150610-01 SoCalGas Media

Coverage ServiceLineAthird-partycontractorwasexcavatingforlandscapeandstrucka1"plasticservice.ThisincidentwasreportedwhenSoCalGasbecameawareofmediacoverage.

Open

20150611-01 PG&E Operator

Judgement Valve Astructurefireat217E.WarrenAvenue,BakersfieldCAthatcausedanunintentionalreleaseofgas. Open

Page 12: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

12

20150611-02 SoCalGas Media

Coverage Main Athird-partycontractorwasexcavatingwhenhestrucka2"plasticmaincausingagasleak. Closed

20150612-01 PG&E Operator

Judgement ServiceRiser Astructurefireat5540RobertsonAve,Carmichael(Sacramento)meltedthemetercausingareleaseofgas. Closed

20150618-01 PG&E

CasualtiesorInpatient

Hospitalization

ServiceRiserAstructurefireatHartnellSt.andAlvaradoNilesRdinUnionCitythatmayhavedamagedthe5-metermanifold,causinganunintentionalreleaseofgas.Theincidentresultedinafatality.

Closed

20150618-02 PG&E Operator

Judgement ServiceLine Amultiplestructurefiremeltingagasmeterat7915McHenryAveinModesto,causingareleaseofgas. Open

20150621-01 PG&E Media

Coverage RegulatorAgasleakwasreportedat582HopeStinMountainView.Thecauseoftheleakwasfoundtobeafailedrubbergasketonadistirbutionfeedermainregulatorstation.

Open

20150622-01 PG&E Media

Coverage ServiceLineAthird-partycontractorwastrnchingwhentheystrucja1/2"plasticserviceat172ForestSideAveinSanFranciscocausinganunintentionalreleaseofgas.

Closed

20150622-02 PG&E Operator

JudgementCustomerMeter

Astructurefireat5834CorteMargaritainPleasantonthatdamagedacustomermetercausinganunintentionalreleaseofgasfromPG&Efacilities.Thefirewasdeterminedtohavestartedinagarbagecannearthemeter.

Closed

20150622-03 PG&E Media

CoverageCustomerMeter

Avehicleimpactintoacustomermeterat3165GardendaleDrinSanJosecausedanunintentionalreleaseofgas. Closed

20150625-01 PG&E Damages

Above50K ServiceRiser Avehicleimpactincidentat8239DonAvenueinStocktoncausedanunintentionalreleaseofnaturalgasandignition. Closed

20150626-01 PG&E Damages

Above50K ServiceLineAresidentialstructurefireat121RobinsonCircle,HealdsburgCa,inSonomaCountydamagedthemetersetassemblycausingareleaseofgas.

Closed

20150628-01 SoCalGas Media

CoverageCustomerMeter

Avehiclebrokeacurbvaultresultinginadamagedstopcock.Theincidentbecamereportableduetomediacoverage. Closed

20150630-01 SoCalGas Media

CoverageCustomerMeter

Avehiclehitmeterdamaged5metermanifold.Electricalpanelfellonmanifoldcausingaleaktoignite.Theincidentbecamereportableduetomediacoverage.

Open

20150630-02 PG&E Media

Coverage ServiceLine

Athird-partycontractorexcavatingforawaterserviceinstallationdamageda1"plasticservicelinewhileusinganacetylenetorchtosolderonthecopperwaterservice,causingareleaseofgasanditssubsequentignition.

Closed

20150701-01 SoCalGas Media

Coverage Main Athird-partycontractorwasdiggingwithatunnelbarwhenhestrucka2"plasticmaincausingagasleak. Closed

20150706-01 PG&E Media

Coverage ServiceLine

Agasodorwasreportedataduplexat4706LargeOakCourtinSacramento.Aleakwasdiscoveredona1/2"plasticservicelinewhichappearedtohavebeenpuncturedbyaplumbingsnakeusedinthesewerline.

Open

20150707-01 PG&E Media

Coverage Main Athirdpartystruckanddamageda2"plasticmainat250HarrisAvenue,Ste.3inSacramento. Closed

20150707-02 SoCalGas Media

CoverageCustomerMeter

Avehiclehitastructureat5440BreckenridgeAveandcontinuedtorolldownhillwhereitstruckametersetassemblyat5448BreckenridgeAvecausingagasleak.

Closed

20150711-01 SDG&E Media

Coverage ServiceLine Athird-partycontractorhitanddamageda3/4"steelservicelinewhilegrindingatreestympcausingareleaseofgas. Closed

20150712-01 PG&E Media

CoverageCustomerMeter

Avegetationfirespreadtoanearbystructureat4904SnowSt.SanJosedamagingthegasmetersetassembly. Closed

20150712-02 SDG&E Media

Coverage ServiceRiser Avehiclehitgasrisercausingareleaseofgas. Closed

20150713-01 PG&E Operator

JudgementCustomerMeter

Astructurefiredamagedagasmetersetassemblycausingareleaseofgas. Closed

20150713-02 PG&E Media

Coverage Main APG&Ecrewperformingaleakrepairdamagedafittingona4"main.BeingreportedtoCPUCduetounknownmediaonsite Open

Page 13: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

13

20150714-01 PG&E Operator

Judgement Main

Athird-partyexcavatorstruckanddamageda4"plasticmainatNMacArthurandW11thst,Tracy,causingalossofserviceto50customers.TheincidentwasreportedtotheCPUCduetopublicattention.

Closed

20150714-02 SoCalGas Damages

Above50K MainContractorwasexcavatingwhenhestrucka6"steelmain.ThisincidentwasreportedtotheCPUCandDOTduetotheassociateddamagethatcouldpotentiallyexceed$50,000.

Open

20150720-01 PG&E Media

Coverage ServiceRiser ASafewaySupermarketemployeeshearedoffthe3/4"steelserviceriserat15551UnionAve,inLosGatoscausingareleaseofgas. Closed

20150723-01 PG&E Operator

JudgementCustomerMeter

Astructurefireat65076thStreet,RiverbankCAthatcausedanunintentionalreleaseofgaswithignition. Closed

20150724-01 SDG&E Media

Coverage ServiceLine

Contractorstrucka1"plasticservicewithabackhoecausingagasleak.Therewerenoinjuriesasaresultofthegasleak.Crewisonsceneworkingtocontrolthegas.ThisincidentwasreportedtotheCPUCwhenSDG&Ebecameawareofmediacoverage.

Closed

20150727-01 PG&E Operator

JudgementCustomerRegulator Structurefiremeltedgasmeterandregulator. Open

20150727-02 SoCalGas Media

Coverage OtherAthird-partycontractorhita3/4"steelcutbackservicewithabackhoecausingareleaseofgas.ThisincidentwasreportedtotheCPUCduetomediainvolvement.

Closed

20150804-01 SoCalGas Media

Coverage Main Athird-partycontractorwasexcavatingfortreeremovalwithabackhoewhenhestrucka2"plasticmaincausingagasleak. Open

20150806-01 PG&E

CasualtiesorInpatient

Hospitalization

CustomerMeter

Anexplosionatahome'sgasstovecausedafireatamobilehomeparkinBakersfieldlocatedat3535StineRoad,space192.Space191alongwithtwootherunitsappearstohavebeendamagedaswell.

Open

20150810-01 PG&E Operator

Judgement Regulator

OnAugust10,2014at0440hours,PG&Ewasnotifiedofastructurefire,ofunknowncause,at113672ndAvenueinOakland.WhenPG&E'sGSRarrivedonsiteatapproximately0515hours,themetersetwasonfireanditwasnotsafetoapproachthehomehowe

Open

20150812-01 SoCalGas Damages

Above50KCustomerMeter

Avehiclestruckametersetinarestaurantparkinglot,whichresultedinareleaseofgasandafire. Closed

20150816-01 SDG&E Media

CoverageCustomerMeter

Housefire(causestillunknown)damagedgasmeter,resultinginareleaseofgas.Crewsarecurrentlyworkingtocontrolthegas.Noinjurieshaveresultedfromthisincident.Theincidentwasreportedduetomediacoverageandthepossibilityofdamage

Open

20150817-01 PG&E Media

Coverage ServiceLineAthird-partydoingroadpatchworkwhenthehotasphaltseepedthroughanopeningandmeltedthe1-1/4"plasticservicelinecausingareleaseofgas,

Closed

20150818-01 PG&E Media

Coverage Main

At0725hoursPG&Ecallcenterwasnotifiedofanodorcomplaintat33915thAve.,SanFrancisco.PG&EGSRarrivedonsiteat0810hours.Aleakwasfoundona2-inchplasticdistributionmain.Atapproximately1030hoursmediawasobservedonsitemaking

Closed

20150819-01 SoCalGas Media

Coverage ServiceLine Athirdpartycontarctordamagedan1"servicelinereleasinggasat223NorthSanLuisstreetinLosAngeles. Open

20150820-01 PG&E Media

Coverage Main A4"plasticmaininHollisterwasdamagedbyathirdpartydigin. Open

20150820-02 PG&E Media

Coverage Main A3/4"steelmaininSacramentowasdamagedbyathirdpartydigin. Open

20150820-03 PG&E Media

Coverage Main A1¼"plasticmaininConcordwasdamagedbyathirdpartydigin. Closed

20150821-01 SDG&E Media

Coverage ServiceLine A1/2"PEservicewasdamagedbythirdpartyexcavation,causingareleaseofgas. Closed

20150824-01 SDG&E Media

Coverage Other Treeinnurseryfellontometersetand2"riser.BecamereportablewhenSDG&ElearnedofTVmediapresence. Closed

Page 14: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

14

20150826-01 PG&E Damages

Above50KCustomerMeter

Avehicleimpactedametersetatacommercialbuildingat2935WhiteOakinSantaClara,resultinginanunintentionalreleaseofgasthatsubsequently

Closed

20150829-01 PG&E Operator

Judgement Regulator Astructurefireat3194MoorparkAveinSanJosedamagedthemetersetassemblycausingareleaseofgas. Closed

20150830-01 SDG&E Media

CoverageCustomerMeter

Avehicledrovethroughafence,struckariserandmetermanifoldresultinginagasleak. Open

20150901-01 PG&E Media

Coverage ServiceLine APG&E'scontractorstruck¾"steelserviceline,withabackhoe,causingareleaseofgas. Closed

20150901-02 SDG&E Media

Coverage Main

Contractorstruckaplasticgaslineresultinginaleak.Crewisonsceneworkingtocontrolthegas.Therewerenoinjuriesorevacuations.ThisincidentwasreportedwhenSDG&Ebecameawareofmediacoverage.

Open

20150903-01 SoCalGas Media

Coverage Main

Contractorwasdiggingwitharipperwhenhestrucka6"plasticgasmainresultinginaleak.Crewisonsceneworkingtocontrolthegas.ThisincidentwasreportedtoCPUCwhenSoCalGasbecameawareofmediacoverage.

Open

20150903-02 SoCalGas Media

Coverage Main Athirdparycontractorhita2-inchplasticmainwithaminiexcavatorwhileexcavatingatrenchtoinstallfiberoptics Closed

20150905-01 SDG&E Media

Coverage ServiceRiser Avehiclestruckanddamagedaserviceriserat8045FletcherParkwayinLaMesa. Open

20150908-01 PG&E Media

Coverage Main Athird-partyperformingirrigationworkdamagedthegasmainat2752BetteStreetinAlameda. Closed

20150909-01 SoCalGas Media

CoverageCustomerMeter

Atreefellontheroofofaresidencesnappingthehouselineanddamagingthemetersetassemblyresultinginagasleak. Closed

20150910-01 PG&E Media

Coverage ServiceLine Athird-partystrucka1/2-inchplasticinsertedintoa3/4-inchsteellinewithaconcretecutterthatresultedinareleaseofgas. Closed

20150912-01 SoCalGas Media

Coverage ServiceLineWhilemakingemergencyrepairstoanelectricalline,PG&Ecrewstrucka1/2"gasservice.Thisincidentwasreportedduetothepresenceofmedia.

Closed

20150914-01 SoCalGas Damages

Above50KCustomerMeter

Astructurefirereportedat531NLomitaSt,Burbank.CrewrespondedandfoundtheinlettoanMSAfoundbroken.ThiswasreportedtoCPUCandDOTduetoagasleakandtheassociateddamagepossiblyexceeding$50,000.

Open

20150915-01 SoCalGas Media

CoverageCustomerPipe

Heavyraincausedlanderosiontoaportionofahousetoslideintoawash.Asaresult,thedownstreampipingoftheregulatoratthemetersetwasdamagedcausingagasleak.

Closed

20150918-01 PG&E Operator

JudgementCustomerMeter

Astructurefireat108ElCaminoRealinGreenfieldmeltedametercausinganunintentionalreleaseofgas. Open

20150918-02 PG&E Operator

JudgementCustomerMeter

Astructurefireat1920OceanStinSanFranciscothatmeltedametercausinganunintentionalreleaseofgas. Closed

20150922-01 SDG&E Media

Coverage ServiceLine A1-1/4"plasticservicewasstruckbythirdpartyexcavation,resultinginaleak. Closed

20150922-02 SDG&E Media

Coverage ServiceLine A1"steelservicewasstruckbythirdpartyexcavator,resultinginaleak. Open

20150923-01 PG&E Damages

Above50KCustomerMeter

StructurefireinvolvingtwohomesdamagedPG&E'smetersets.Incidentreportedduetocostsofdamagesrelatedtothefireexceeding$50,000.

Open

20150923-02 SoCalGas Media

Coverage ServiceLine Athirdpartycontractorstruckanddamgeda3/4"steelservicelinecausingaleak. Open

20150924-01 SDG&E Media

Coverage OtherAThirdpartycontractorstuck3"steelmainwithatrackhoe.ThiswasreportedtoCPUCwhenSDG&Ebecameawareofmediacoverage.

Open

20150928-01 SDG&E Media

Coverage Athirdpartyexcavatordamageof2"plasticgasmain.ThiswasreportedtoCPUCwhenSDG&Ebecameawareofmediacoverage. Open

20150929-01 SDG&E Media

Coverage Main Athirdpartyexcavationdamageof3"plasticgasmain.ThiswasreportedtoCPUCwhenSDG&Ebecameawareofmediacoverage. Closed

Page 15: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

15

20151003-01 SDG&E Media

Coverage ServiceRiser Avehiclecrashedthroughbrickwall,intoahouseanddamagedasteelriser.ThisbecomereportablewhenTVmediaarrived. Open

20151006-01 SoCalGas Media

Coverage MainAthirdpartycontractorstrucka4"plasticmain.Gasisundercontrolledat11:28am.Noinjuriesandnoignitions.ThisbecamereportablewhenSoCalGasbecameawareofmediacoverage.

Open

20151006-02 PG&E Media

Coverage ServiceLine Athirdpartycontractordoingpipeburstingonasewerlateralda,aheda3/4"steelservicelinecausingagasleak. Open

20151006-03 PG&E Media

CoverageCustomerRegulator

PG&EwasnotifiedofaNaturalGasrelatedstructurefire.Atthistime,thecauseofthefireisunknown. Open

20151006-04 SoCalGas Media

Coverage ValveFireDepartmentreportedaleakingvalveataregulatorstation.ThiswasreportedtoCPUCwhenSOCALGASbecameawareofmediacoverage.

Open

20151007-01 SoCalGas Media

CoverageCustomerMeter

Majorfiresweptthroughoveradozenbusinesses,meltingthemetersetassemblythatignited. Open

20151009-01 PG&E Media

Coverage ServiceLine Athird-aprtycontractorstucka1"plasticservicelinewithashovelcausinganunintentionalreleaseofgas. Closed

20151012-01 SoCalGas Media

Coverage ServiceLine A1/2"plasticservicewasstruckbythirdpartyexcavation,resultinginaleak. Closed

20151013-01 PG&E Media

Coverage Other Athird-partycontractorstucka2"plasticdistributionmainwithanaugercausinganunintentionalreleaseofgas. Open

20151015-01 SoCalGas

CasualtiesorInpatient

Hospitalization

ServiceLine

Athirdpartycontractorstrucka½"plasticservicelinecausingagasrelease.Contractorwasflashedandtakentolocalhospital.Hisconditionsareunknownatthistime.ThisincidentwasreportedtoDOTandCPUCduetoagasreleaseandaninjuredco

Open

20151015-02 SoCalGas Media

Coverage ServiceLineThirdpartycontractorstruck1/2"plasticservicewhilediggingforsewer.ThiswasreportedtoCPUCwhenSoCalGasbecameawareofmediacoverage.

Closed

20151019-01 SDG&E Media

Coverage MainThirdpartycontractorstrucka3"plasticmaincausingagasleak.ThiswasreportedtoCPUCwhenSoCalGasbecameawareofmediacoverage.

Closed

20151020-01 SoCalGas Media

Coverage ServiceLine Landscapingcontractordamagedplasticservicelinecausingaleak.Reportedduetomediacoverage. Closed

20151020-02 SoCalGas Media

Coverage MainThirdpartycontractorwasexcavatingstrucka2"plasticmainresultinginagasleak.ThisincidentbecamereportablewhenSoCalGasbecameawareofmed

Closed

20151023-01 PG&E Damages

Above50K Transmission Agriculturaldig-inontransmissionline150inWinters.Noinjuries,fatalities,orignition.6-inchlineseveredcausingreleaseofgas. Open

20151025-01 SoCalGas Operator

Judgement OtherLeakfromanexistingAlisoCanyongasstoragewell.Noignition,noinjury.Nomedia.Notificationduetooperatorjudgementonly.ReportedtoDOGGR.Failureunderinvestigation.

Open

20151027-01 PG&E Media

Coverage MainAPG&Econtractcrewwasbackfillingovera2-inchelectrofusionfittingthathadjustbeeninstalledandputinservicewhenitwasobservedthatthefittingbeganleaking.

Open

20151028-01 SoCalGas Media

CoverageCustomerMeter

Astructurefirewasreportedat1258NCoatesAve,LosAngeles.Thefirecharredthemeterdialcausinggastoescapeandignition. Open

20151029-01 SDG&E Media

Coverage Thirdpartycontractorstrucka½"plasticservice.ThiswasreportedwhenSDG&Ebecameawareofmediacoverage. Open

20151029-02 PG&E Damages

Above50K Main Acontractorperformingboringhita6-inchgasdistributionmain.Noinjuries,fatalities,orignition. Closed

20151031-01 SDG&E Media

Coverage ServiceLineAthirdpartycontractorwasexcavatingandtheystrucka1.25"PLserviceresultinginaleak.Thisincidentwasreportedduetomediapresence.

Open

20151103-01 PG&E Media

Coverage Main Athirdpartycontractorremovingatreestumpdamageda4-inchsteelgasdistributionmainat525FitchStHealdsburg. Closed

Page 16: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

16

20151104-01 PG&E Operator

JudgementCustomerMeter

Astructurefireat1451ConestogaDr,Merced,startedbyhotcharcoalsinagarbagecan,meltedanearbytwo-metermanifoldandregulatorresultinginareleaseofgas.

Open

20151105-01 SoCalGas Media

CoverageCustomerMeter

Avehiclestruckthemetersetassemblyresultinginagasleak.Therewasnoignition.Thisincidentwasreportedduetomediainterest. Closed

20151105-02 SDG&E Media

Coverage Main Athirdpartycontractorstruckthe2"plasticmainwithadiggingbar.Thisincidentwasreportedduetomediainterest. Open

20151106-01 PG&E Media

Coverage Main Athird-partyexcavatorstrucka2-inchplasticmaincausingareleaseofgas. Open

20151106-02 SDG&E Media

Coverage ServiceLine Athirdpartycontractorstucka½"plasticservice.ThisincidentwasreportedtoCPUCwhenSDG&Ebecameawareofmediacoverage. Open

20151107-01 PG&E Media

Coverage ServiceRiserAvehicleimpactattheintersectionofSanFelipeRoadandMeadowlandsLaneinSanJosehitanRTU½inchplasticsenselinecausingareleaseofgas.

Open

20151109-01 PG&E

CasualtiesorInpatient

Hospitalization

ServiceRiser Astructurefireat127E.GroveStreetinStocktonmeltingthegasmeter.Theincidentresultedinafatality. Open

20151109-02 SoCalGas Media

Coverage Other Semitruckhitabuildingdamagingmetercausingareleaseofgas. Closed

20151109-03 PG&E Damages

Above50KCustomerMeter

Astructurefireat28281BlackGoldWayinTehachapimeltedthegasmetercausingareleaseofgas. Open

20151110-01 PG&E Media

Coverage ServiceRiser Asemi-truckhadlostcontrolanddamagedthe1-1/4"servicelineabovetheriservalvecausingareleaeofgas. Open

20151113-01 PG&E

CasualtiesorInpatient

Hospitalization

TransmissionAripperstruckL300AatMP269,34"transmissionlineatWibleRd&EngleRdinBakersfield,resultinginareleaseofgasandsubsequentignition.Theincidentresultedinafatality.

Open

20151115-01 PG&E Media

Coverage ServiceLine

PG&Ewasnotifiedofafirenear4850HarwoodRdinSanJose.PG&E'srepaircrewarrivedon-siteat1359hours.Thecauseofthefireiscurrentlyunderinvestigation;however,itappearsPG&E'sgasfacilitiesweresecondarilyinvolved.PG&

Open

20151117-01 SDG&E Media

Coverage ServiceLine Athirdpartycontractorstrucka1/2"plasticgasservice.ThiswasreportedtoCPUCwhenSDG&Ebecameawareofmediacoverage. Closed

20151118-01 PG&E Operator

Judgement Main

PG&Ewasperformingatie-inona2'gasmainnearLelandandLynbrookDrinPittsburg.Intheprocess,theworkersettingupabypass,inadvertentlyshutinandsqueezedthebacksideofthe2-inchmain,resultinginaserviceinterruptionto90customers.

Open

20151118-02 SoCalGas Media

Coverage ServiceLine Ahomeowberstruckanddamageda1/2"plasticservicelinewhiledoinglandscaping. Open

20151123-1928 SoCalGas Media

Coverage ServiceLineAthirdpartycontractorwasdiggingforplumbingwhenhestrucka1/2"plasticservicecausingareleaseofgas.ThisincidentwasreportedtoCPUCwhenSoCalGasbecameawareofmediacoverage.

Closed

20151125-1929 SDG&E Media

Coverage ServiceLineAthirdpartycontractordiggingandstrucka1-1/4"plasticservicecausingareleaseofgas.Noinjuries.ThiswasreportedtoCPUCduetomedia.

Open

20151202-1931 SoCalGas Media

Coverage ServiceRiserWhileattemptingtoturnoffthegas,themaintenancepersonnelataschoolbrokethetangonthestopcockcausingareleaseofgas.Thisincidentwasreportedduetomediacoverage.

Open

20151204-1933 PG&E Media

Coverage Main Athird-partycontractorhitanddamageda1¼"plasticmainwithabackhoe. Open

20151207-1934 PG&E Media

CoverageCustomerMeter

Avehicleimpactsheareda1/2"gasriserat10136BlossomRidgeDrive,ElkGrovecausedanunintentionalreleaseofgas. Open

20151208-1935 SoCalGas Media

Coverage Main Athirdpartydugintoa2"plasticmaincausingareleaseofgas.ThiswasincidentwasreportedtoCPUCduetomediainquiry. Open

20151214-1936 SoCalGas Media

CoverageCustomerMeter

Astructurefiredamagedthegasmetercausingreleaseofgaswhichignited. Open

Page 17: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

17

20151216-1937 PG&E Operator

Judgement Main Athirdpartycontractorstrucka4"plasticmainwhileusingabackhoeinSalinas. Closed

20151217-1938 SDG&E Media

Coverage ServiceLine Athirrdpartycontractorhit3/4"steelservicecausingreleaseofgas.Incidentreportedduetomediapresence. Open

20151223-1939 PG&E Media

CoverageCustomerMeter

Astructurefireat6730E.FlintWay,Fresnomeltedthegasmeterscausingareleaseofgas.Perthefiredepartment,thehomeownerdiscardedhotcoalsfromafireplaceintoatrashcanlocatedadjacenttoPG&Eelectricandgasmeters.Thecoalsstartedaf

Open

20151227-1940 PG&E Media

Coverage Regulator Astructurefireat618NFisher,Fresnomeltedthegasmeterandregulator,causingareleaseofgas. Open

20151228-1941 PG&E Operator

JudgementCustomerMeter

Astructurefireat2244WashingtonSt,SanFranciscodamagedthegasmetercausingareleaseofgas.Damageexpectedtoexceed$50,000.

Open

20151230-1942 SDG&E Media

Coverage ServiceLineAthirdpartycontractorstrucka1-1/4"plasticservicewithabackhoecausingareleaseofgas.ThisincidentwasreportedwhenSDG&Ebecameawareofmediacoverage.

Open

20151230-1943 PG&E Media

Coverage ServiceLine Athird-partyexcavatorstruckanddamageda1/4"plasticservicewithaabackhoeat1275MinnesotaSt,SanFrancisco. Open

20151230-1944 PG&E Media

CoverageCustomerMeter

Astructurefireat1985N3rdSt,Concord.Perthefiredepartment,thecauseofthefireisunknownatthistime;however,thehousesustaineddamagesthatexceed$50,000.

Open

SafetyIncidentsOpenasof1-1-2015andIncidentsReportedin2015ElectricIncidents

(InCompliancewithCAPublicUtilitiesCodeSection911&SenateBill1409signedintolawonSeptember25,2014)

IncidentID:Thisnumberreflectstheyear,month,theday,thesequencetheincidentisreported/occurred

IncidentNumberYYYY-MO-DD-XX

FacilityOwner

ReasonforInvestigation

FacilityTypeInvolved BriefDescriptionofIncident

OpenorClosedasof12-31-2015

20111101-03 SDG&E

Mediaattentionduetoanelectrical

fire

Anoverhead12kVconductor

Anoverheadconductorbrokeandfelltotheground,startingasmallgrassfire. CLOSED

20120619-01 PG&E Fatality Powerplant APG&Econtractordismantlingafueloiltankfelltohisdeath

whenhismanliftwasstruckbyacollapsingtankwall. CLOSED

20120813-07 PG&E Athirdparty

wasinjuredAnoverhead21kV

conductorAthirdpartywasinanaerialbucketsplicingacablewhenhereceivedburninjuriesfroma21kVoverheadconductor. CLOSED

20121002-01 PG&E

Outageattractedmedia

attention

Anundergroundsplice

OnOctober1,2012,anoutageoccurredonvariouscircuitsduetoafailedundergroundsplice CLOSED

20130211-03 SCE Damageclaim Twooverhead12

kVconductors

ApalmfrondwasdislodgedfromapalmtreeinGardenGroveandresultedinaphasetophasefaultwhichultimatelycausedtheoverheadconductorstofailandignitestructurefiresattwohomes.

CLOSED

Page 18: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

18

20130303-01 PG&E

Outageattractedmedia

attention

Two115kVbuses Two115kVbusesatasubstationtripped.Anoutageto58,855customersresulted. CLOSED

20130307-01 SCE

Injuryduetocontactwith

electricfacilities

Overhead33kVconductor

AnSCEcontractorwasinjuredwhenade-energized33kVconductorhewasworkingonbecameenergized. CLOSED

20130307-02 PG&E

Injuryduetocontactwith

electricfacilities

Overhead12kVconductor

Athirdpartycontractorwasinjuredwhenhecontacteda12kVoverheadconductorwhileworkingonarooftop. CLOSED

20130307-03 PG&E

Outageattractedmedia

attention

Substation Anoutageoccurredto18,501customersservedbyaPG&EsubstationintheCityofBakersfield. CLOSED

20130316-01 PG&E

Outageattractedmedia

attention

Threeoverhead12kVconductors

Anoutageoccurredto3,680customersintheCityofSanFranciscoduetothreespansofaPG&E12kVcircuitconductorfallingtotheground.

CLOSED

20130408-01 SDG&E

Outageattractedmedia

attention

Eightpoles EightpolesfailedandfelltothegroundduringareportedlyhighwindeventintheareaofBorregoSprings. CLOSED

20130411-01 PG&E

Outageattractedmedia

attention

CrossarmAnoutageoccurredona12kVcircuitduetoabrokencrossarm.Theoutageleft1,820customerswithoutpowerforapproximately7½hours.

CLOSED

20130422-01 PG&E

Outageattractedmedia

attention

Fuses Anoutageoccurredto87customersona21kVcircuitinGilroy. CLOSED

20130423-01 PG&E

Outageattractedmedia

attention

Transmission230kVline 8,867customerslostpowerduetoatransmissionlinefailure. CLOSED

20130425-01 SCE Fatality Tapreducingplug

AnSCElinemansufferedfatalinjuriesafterinadvertentlyexposinganenergizedtapreducingplugona12kVcircuitandcausinganarc.

CLOSED

20130501-02 PG&E

Outageattractedmedia

attention

Undergroundconnector

Anundergroundconnectorfailedresultinginanoutagetoover3,000customers. CLOSED

20130501-04 PG&E Damageclaim Overhead12kV

conductorAnoaktreefailedbelowgroundlevelduetocatastrophicrootfailureandfellintoa12kVcircuitinthecityofCalistoga. CLOSED

20130505-01 PG&E Injury Underground

groundwire

AnarcflashoccurredwhilePG&EemployeeswereintheprocessofremovinginstalledgroundsfromanundergroundtransformerenclosureintheCityofSanFrancisco.AnemployeesufferedburnstohishandsandfacefromthearcflashandwastransportedtoahospitalinSanFrancisco.

CLOSED

20130602-01 PG&E

Outageattractedmedia

attention

Undergroundsplice

Anoutageoccurredto9,100customersona21kVcircuitduetoafailedundergroundspliceintheCityofDanville. CLOSED

Page 19: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

19

20130602-02 SCE Damageclaim Seventy-fivepoles Afireconsumedapproximately75SCEpoles.Thefirewas

ignitedasaresultofLADWPelectricalfacilitiesinthearea. CLOSED

20130602-03 PG&E

Outageattractedmedia

attention

Switch Anoutageoccurredaffecting3,558customersona12kVcircuitduetoafailedswitchinthecityofDavis. CLOSED

20130604-01 PG&E

Outageattractedmedia

attention

CircuitBreakerAcircuitbreakeratasubstationunexpectedlyopenedforunknownreasons.Theeventresultedinanoutagetoalmost10,000customers.

CLOSED

20130610-01 SCE Injury Underground

equipment

ThreeelectricalworkerswithanSCEcontractorwereworkinginsideavaultwhenoneoftheworkersremovedanenergizedcomponentandanarcflashoccurred.Twoofthethreeworkerswereinjuredasaresult.

CLOSED

20130618-01 PG&E

Outageattractedmedia

attention

Twopoles

Twopolescaughtfireduetotwoseparateelectricflashovers.Thefirstflashoverandresultingfirecausedanoutagetoover2,000customers.Toperformtherequiredrepairsonthesecondpole,thecircuitwasde-energizedleavingatotalof5,000customerswithoutpower.

CLOSED

20130618-02 PG&E

Outageattractedmedia

attention

Overhead12kVinsulator

Apolefirewascausedbyhighhumidityconditionsinitiatinganarcacrossoneormoreinsulators.Asaresultofthefire1,774customerswereoutofpowerandanadditional174customerswereintentionallydisconnectedtosafelyperformrestorationprocedures.

CLOSED

20130618-03 PG&E

Outageattractedmedia

attention

Overhead12kVconductor

Anoutageoccurredona12kVcircuitduetoafailedcableintheCityofBerkeley. CLOSED

20130620-01 PG&E Injury Overhead12kV

conductorAthirdpartywasinjuredwhenaconductorfellonhishandashewasgraspingawoodenfenceathisresidence. CLOSED

20130623-01 PG&E

Outageattractedmedia

attention

Substation Aseriesofoutagesoccurredto149,013customersintheSanLuisObispoareaduetomultiplearc-flasheventsatasubstation. CLOSED

20130623-02 PG&E Injury Overhead12kV

conductorAparachutistcontactedaconductorona12kVcircuitduringajump. CLOSED

20130718-01 PG&E

Outageattractedmedia

attention

Overhead12kVconductors

Twospansofprimaryconductorsfailedcausinganoutageto82customers. CLOSED

20130803-02 PG&E Injury Powerplant

Amemberofthepublicwatchingdemolitionofthepowerplantwasinjuredwhenshrapnelfromaboilerimplosionstruckhisleg.

CLOSED

20130815-01 SCE Damageclaim Overheadjumper

wire

OneSCEoverheadjumperwireandtwoSCEoverheadconductorsfailed.Theoverheadconductorsfelltothegroundandignitedafire.

CLOSED

20130817-01 PG&E

Outageattractedmedia

Switch Animproperlysetswitchcausedanoutagetoalmost5,000customers. CLOSED

Page 20: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

20

attention

20130930-01 SCE Fatality Underground

elbow

Asubcontractorwasfatallyinjuredwhenheinadvertentlyremovedanenergizeddead-breakelbowwhileworkinginanundergroundvaultinHuntingtonBeach.

OPEN

20131006-01 SDG&E

Mediaattentiondue

tofire

Overheadsecondary

AsecondaryservicewiresupplyingasignallightandaSanDiegoTrolleyServicecrossingarmapparatusseparatedandfelltothegroundcausingasmallbrushfire.

CLOSED

20131006-03 PG&E

Outageattractedmedia

attention

OverheadspliceAnautomaticsplicefailedanddroppedthemiddlephaseconductortothegroundcausinganoutageto5,590customersinArroyoGrande.

CLOSED

20131009-01 PG&E Injury Meterbase APG&Econtractorwasinjuredbyanarcflashwhileattempting

toinstallaglassmetercoveronanenergized480Vmeterbase. CLOSED

20131019-01 SCE Damageclaim Underground12

kVcable

Anundergroundcableofa12kVcircuitfailed,causingthecircuittorelayandlockout.Subsequently,afirewasreportedatabankthatcaused$2,000,000indamages.

CLOSED

20131019-02 PG&E Damageclaim Substation

Ashootingoccurredatasubstation.Suspectsvandalizedfacilitieswithseveralbulletroundsdamagingtransformers,acircuitbreaker,acapacitorbank,andcontrolequipment.

CLOSED

20131021-02 PG&E Fatality Overhead12kV

conductor

Athirdpartyfatallycontacteda12kVoverheadcircuitwhilehewasintheprocessofraisingaflagpoleatafleamarketinthecityofFresno.

CLOSED

20131107-01 SDG&E Damageclaim Underground12

kVcable

AnSDG&Econtractorstruckanddamageda12kVprimaryundergroundcableandductownedbySDG&EwhileattemptingtoinstallgroundrodsforthegroundgridaspartofaSDG&Esubstationexpansionproject.

CLOSED

20131107-02 PG&E

Outageattractedmedia

attention

Overhead21kVconductors Anoutageoccurredona21kVcircuitintheCityofWatsonville. CLOSED

20131111-01 PG&E

Outageattractedmedia

attention

Overheadsplice Anoutageoccurredona12kVcircuitduetoafailedsplice. CLOSED

20131112-02 PG&E

Outageattractedmedia

attention

Substation AtransmissionleveloutageoccurredinthegreaterStocktonarea. CLOSED

20131114-01 PG&E

Outageattractedmedia

attention

Overhead12kVconductors Anoutageoccurredona12kVcircuitaffecting3,653customers. CLOSED

20131115-01 PG&E Injury Powerplant APG&Eworkerinjuredhislegwhileridingatramtransporting

himfromthepowerhouse. CLOSED

20131118-01 PG&E

Outageattractedmedia

Overhead4kVconductor

Anoutageoccurredto3,312customersafteraMylarballooncameintocontactwithoverheadconductors. CLOSED

Page 21: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

21

attention

20131120-01 PG&E Media

attentionUndergroundsecondary Secondarycableoverheatedandmeltedforunknownreasons. CLOSED

20131122-01 PG&E Damageclaim Transmission115

kVlinesThreetransmissionlinesrelayedataswitchyardwithoutinterruptiontocustomers. CLOSED

20131125-01 PG&E

Outageattractedmedia

attention

Undergroundsplice Anoutageoccurredona12kVcircuitduetoafailedsplice. CLOSED

20131125-02 PG&E Media

attentionTransmission115

kVlineOnephaseofatransmissionlineseparatedatmidspanbetweentwotowers. CLOSED

20131125-04 PG&E

Outageattractedmedia

attention

Overheadparallelgrooveconnector

Anoverheadparallelgrooveconnectorfailedanddroppedaconductortotheground.Thedownedconductorcausedanoutagetoabout3,500customers.

CLOSED

20131127-01 PG&E

Outageattractedmedia

attention

Transformer AnoutageoccurredonPG&Ecircuitduetoanimalintrusion. CLOSED

20131203-01 PG&E

Outageattractedmedia

attention

Switch Anoutageoccurredona12kVoverheadcircuitduetoamanualswitchingerror. CLOSED

20131205-01 PG&E

Outageattractedmedia

attention

Overheaddead-endshoe(clamp)

Anoutageoccurredona12kVcircuitanda4kVcircuitduetoafailedoverhead"deadendshoe". CLOSED

20131206-01 PG&E

Outageattractedmedia

attention

Transformer APG&Etransformerandswitchesfailed.Atotalof5,132customerswereoutofpowerasaresultofthefailure. CLOSED

20131208-01 PG&E Injury Transformer APG&Eemployeewasinjuredwhiletroubleshootinga

transformerafterarelatedoutageoccurred. CLOSED

20131210-01 SCE

Mediaattentiondue

tofire

Overhead16kVconductor

SCEpersonneldrivingnearbywitnessedaflashona16kVcircuit. CLOSED

20131210-02 PG&E

Outageattractedmedia

attention

Overhead12kVconductors

Anunexpectedfaultoccurredatanunknownlocationandcausedanoutagefor2,550customersona12kVcircuit. CLOSED

20131212-01 PG&E

Outageattractedmedia

attention

Substation AnoutageoccurredatasubstationinthecityofAndersonaffecting3,734customers. CLOSED

20131213-01 PG&E Media Transformer Astationservicetransformercatastrophicallyfailedata

substation CLOSED

20131215-01 PG&E Damageclaim Third-party

electricalline

AfirestartednearthePfeifferRidgeinLosPadresNationalForest,BigSur.Theincidentresultedinaoutageto106customersandreplacementofPG&Efacilities.

CLOSED

20131219-01 PG&E

Outageattractedmedia

Transmission115kVline

A115kVlineanda70kVlineexperiencedasustainedoutagecausinganoutageto26,379customers. CLOSED

Page 22: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

22

attention

20131219-02 PG&E

Outageattractedmedia

attention

Transformer Atransformerfailedresultinginanoutageto6,127customersontwocircuits. CLOSED

20131220-01 PG&E

Outageattractedmedia

attention

Overhead12kVconductor

Anoutageoccurredto1,514customersona12kVcircuitduetoabirdcontact. CLOSED

20131221-01 PG&E

Outageattractedmedia

attention

Fourundergroundcables

Anoutageoccurredona12kVcircuitresultingin125customerswithoutpower.Atotaloffourundergroundcablefailurescausedtheoutage.

CLOSED

20131223-01 PG&E

Outageattractedmedia

attention

UndergroundcableAPG&Eundergroundcablefailedandcausedanoutageto1,960customers.Thetypeofcablethatfailedwaspaperinsulatedleadcables.

CLOSED

20131225-02 SCE

Outageattractedmedia

attention

Overhead16kVconductors

TheSimiValleyareaexperiencedhighwindconditionsresultingintheissuanceofredflagwarnings.Two16kVcircuitrelayedduetothehighwindconditionsandcausedoutages.

CLOSED

20131227-01 PG&E

Outageattractedmedia

attention

Switch AsquirrelcausedaphasetogroundfaultattheRossmoorSubstation.Thefaultaffected11,561customers. CLOSED

20140103-01 PG&E

Outageattractedmedia

attention

Undergroundsplice

Anundergroundsplicefailedresultinginanoutagefor1,395customers. CLOSED

20140107-01 PG&E

Outageattractedmedia

attention

Two12kVconductors

Asubstationrelayregisteredaphasetophasefaultandopenedacircuitbreakerprotectinga12kVcircuit.Asaresult,4,982customerswereoutofpowerforalmosttwohours.

CLOSED

20140108-01 PG&E

Outageattractedmedia

attention

Switch Ananimalcausedanarconairswitchatasubstationresultinginanoutageto22,967customers. CLOSED

20140111-01 PG&E

Outageattractedmedia

attention

Overhead12kVconductor

Anoutageoccurredona12kVcircuitduetoaseparatedoverheadprimaryphase. CLOSED

20140111-02 SDG&E Injury Powerplant AnSDG&Eemployeefellthroughahatchandsustainedahip

injury. CLOSED

20140114-01 PG&E

Outageattractedmedia

attention

Threeoverhead12kVconductors

Anoutageoccurredona12kVcircuitduetoallthreeconductorsseparating. CLOSED

20140128-01 PG&E Damageclaim Switch Anoutageoccurredona21kVcircuitduetoaflashedairswitch

duringamanualswitchingoperation. CLOSED

20140207-01 PG&E Damageclaim Lightningarrestor Aresidentialstructurefireoccurredonpropertylocatedinthe

townofTwaininPlumasCounty. CLOSED

Page 23: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

23

20140217-02 PG&E

Outageattractedmedia

attention

Elbowconnector Anoutageoccurredto1,366customersona12kVcircuitduetoafailedelbowinavaultinthecityofChico. CLOSED

20140220-01 PG&E Injury Overhead12kV

conductorAthirdpartyoperatedaforkliftintoanoverheadPG&Econductorandreceivedelectricalburns. CLOSED

20140223-01 PG&E

Outageattractedmedia

attention

Underground12kVcable

Anundergroundcablefailedona12kVcircuitresultinginanoutagefor6,687customers. CLOSED

20140224-01 PG&E

Outageattractedmedia

attention

Undergroundconnector

Anundergroundconnectorfailedona21kVcircuitresultinginanoutagefor4,623customers. CLOSED

20140226-01 PG&E

Outageattractedmedia

attention

Underground12kVcable

Anundergroundcablefailedona12kVcircuitresultinginanoutagefor6,139customers. CLOSED

20140301-01 PG&E

Outageattractedmedia

attention

Overhead12kVconductor

AnoutageoccurredonaPG&Ecircuitasaresultofafaultydirectcurrentsupplyconductorconnectedtoacircuitbreaker. CLOSED

20140301-02 SCE Damageclaim Threeoverhead16

kVconductors

Duringarainstorm,aheliumballoonmadecontactwiththreeconductorsofdifferentphases.Trackingoccurredacrosstheheliumballoon,resultinginaphase-to-phasefault.Thisfaultconditioncausedallconductorstoseparateandfall,causingdamagetostructuresandatruck.

CLOSED

20140303-02 SCE

Outageattractedmedia

attention

Threeoverhead16kVconductors

AeucalyptustreefellacrossSCEprimaryoverheadconductors.Shortlythereafter,afirestartedinanearbystructure. CLOSED

20140303-03 PG&E Injury Pole

AvehiclehitapoleinthetownofCarruthers,FresnoCounty.Theincidentresultedinthepoleandaconductorona12kVcircuittofallontotheground.Thethirdpartyexitedhisvehicleandhecontactedanenergizeddownconductorandwasinjured.

CLOSED

20140304-01 PG&E

Outageattractedmedia

attention

Undergroundsplice

Anundergroundsplicefailedona12kVcircuitresultinginanoutagefor2,304customers. CLOSED

20140310-01 PG&E

Outageattractedmedia

attention

TransformerThetertiarybushingonabank(115/60kV)failedatasubstation,andthetransformerbankrelayed.Thisresultedinanoutageto7,127customers.

CLOSED

20140310-02 BVES Majoroutage Capacitorbank

Acapacitorbankatasubstationcaughtonfire.Thisinterrupteda34.5kVlinethatfedBearValleyElectricService'sentireserviceterritory.

CLOSED

20140311-01 PG&E Injury Overhead12kV

conductor

AthirdpartywasoperatingawaterwelldrillingrigwhenoneofthelineshepulledmadecontactwithaPG&E12kVoverheadconductor.

CLOSED

20140314-02 PG&E Outage

attracted Disconnect Anoutageoccurredona12kVcircuitduetoafailedsolidbladedisconnect. CLOSED

Page 24: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

24

mediaattention

20140319-02 PG&E

Outageattractedmedia

attention

Twooverhead12kVconductors Anoutageoccurredona12kVcircuitduetoasquirrelcontact. CLOSED

20140327-01 SDG&E Damageclaim Reactorbank

Thewindingsofametalclad12kVreactorbankinasubstationfaulted.Thefaultcausedasmallfirewhichburnedallthewindingswithinthe12kVreactorbankmetalcladenclosure.

CLOSED

20140328-01 SCE Injury Fuse

ASCElinemanwasworkinginanelevatedpositioninabuckettruckwhenheinadvertentlycontactedenergizedfuseholdersandsustainedburninjuries.

CLOSED

20140329-01 PG&E

Outageattractedmedia

attention

Overheadservice

Atreeuprootedduetostormyweatherconditionsandfellonacustomer’sserviceline.Thecustomer’sweatherheadwasdamagedintheincidentandrequiredahomeelectriciantomakeappropriaterepairs.

CLOSED

20140331-01 PG&E

Outageattractedmedia

attention

Fourteentransformers

Lightningstrikesintheareacausedoutagesto185customersona12kVcircuit.Fourteentransformersweredamagedduringthisstormevent.

CLOSED

20140402-01 PG&E

Outageattractedmedia

attention

Overhead12kVconductors Anoutageoccurred,affecting1764customersona12kVcircuit. CLOSED

20140412-01 PG&E

Outageattractedmedia

attention

Overhead12kVconductors Anoutageoccurredona12kVcircuitduetoathirdpartyfire. CLOSED

20140414-01 PG&E

Outageattractedmedia

attention

Undergroundconnector

Anoutageoccurredona12kVcircuitduetoafailedunderground600ampelbow. CLOSED

20140418-01 PG&E

Outageattractedmedia

attention

Overhead4kVconductors Anoutageoccurredona4kVcircuitduetoanuprootedtree. CLOSED

20140422-01 PG&E

Outageattractedmedia

attention

OverheadspliceAPG&Eoverheadsplicefaileddroppingtheconductortotheground.A12kVcircuitopenedresultinginanoutageto2,318customers.

CLOSED

20140429-01 PG&E

Outageattractedmedia

attention

Overhead12kVconductors Anoutageoccurredona12kVcircuitduetoaMylarballoon. CLOSED

20140429-02 SCE

Outageattractedmedia

attention

Overhead12kVconductors

Awindgustupto14mphcausedalargebranchinapinetreeinthecityofPlacentiatobreakandfallacrossSCEoverheadconductors.Theconductorsfell,resultinginfiredamagetomultiplelocationsinPlacentia.

CLOSED

20140429-03 SCE

Outageattractedmedia

attention

Twopoles Twopolesfailedandfelltotheground. CLOSED

Page 25: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

25

20140429-04 PG&E

Outageattractedmedia

attention

Undergroundsplice

Anoutageoccurredona21kVcircuitduetoafailedundergroundsplice. CLOSED

20140430-02 SCE

Outageattractedmedia

attention

Pole Apolebrokeatitsgroundlineandfelltotheground. CLOSED

20140430-03 SCE Damageclaim Overhead12kV

conductors

Strongwindcausedthreelimbsofalargeeucalyptustreetobreakandfallonoverheadelectricalfacilitiesona12kVcircuit.ThecontactresultedinavegetationfireinthecityofHemet.

CLOSED

20140502-01 PG&E

Outageattractedmedia

attention

Overheadsplice APG&Eoverheadsplicefailedandcausedaconductortofalltothegroundresultinginanoutageto4,034customers. CLOSED

20140504-02 PG&E Injury Regulator Athirdpartycontacteda60kVregulatorinsideasubstation. CLOSED

20140511-01 SCE Injury Transformer ASCE12kVcircuitrelayedandlockedout.SCEfoundapad

mountedtransformerhadbeenvandalized. CLOSED

20140513-01 SDG&E Majoroutage Variousoverhead

facilities

Highwindsreachinggustsofapproximately90mphpersistedforaboutthreedaysinSanDiegoCountyandresultedinmultiplepoweroutages.

CLOSED

20140514-01 PG&E

Outageattractedmedia

attention

Undergroundswitch

Anoutageoccurredona21kVcircuitduetoafailedundergroundswitch. CLOSED

20140515-01 SCE Fatality Overhead12kV

conductor

AnSCE12kVoverheadcopperconductorbrokeandfelltotheground.Apersoncontactedthedownedconductorandwaselectrocuted.

OPEN

20140515-02 SCE

Outageattractedmedia

attention

Twooverhead12kVconductors

AMylarballooncontactedtwooverheadconductorsresultinginafaultcurrentthatcausedanoverheadconductortofalltothegroundstartingfireandcausingacommercialbuildingtocatchfire.

CLOSED

20140516-01 SCE Damageclaim Transformer A75kVAtransformerinthecityofSantaMonica

catastrophicallyfailedresultinginastructurefire. CLOSED

20140516-02 SCE Injury Overheadservice

conductor

Afiredestroyedapropertyandcausednearly$2,000,000indamages.Thefiremayhavebeencausedbyarcingofelectricservicedropwiresasaresultofabrasionfromanadjacenttree.

CLOSED

20140517-01 SCE Damageclaim Relay Atransformerbankrelayedandlockedout. CLOSED

20140523-02 PG&E

Outageattractedmedia

attention

Insulators Apoletopcaughtfireandfellontothe4kVlinesbelowresultinginanoutagefor2,041customers. CLOSED

20140606-01 PG&E

Outageattractedmedia

attention

Overhead12kVconductor Anoutageoccurredona12kVcircuitduetoadownconductor. CLOSED

Page 26: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

26

20140606-02 PG&E

Outageattractedmedia

attention

Transformer APG&Eemployeemadeaswitchingerrorresultinginanoutagefor18,348customers. CLOSED

20140610-01 PG&E Damageclaim Transformer Anoutageoccurredona12kVcircuitduetoafailed

undergroundtransformer. CLOSED

20140612-01 PG&E

Outageattractedmedia

attention

Overheadrecloser Anoutageoccurredona12kVcircuitduetoasquirrelcontact. CLOSED

20140612-02 PG&E

Outageattractedmedia

attention

Undergroundconnector

Anoutageoccurredona21kVcircuitduetoafailedundergroundconnector. CLOSED

20140612-03 PG&E

Outageattractedmedia

attention

Insulators A12kVwasde-energizedtorepairapoletopthatwasdamagedfromafire. CLOSED

20140612-04 PG&E

Outageattractedmedia

attention

Overheadrecloser Alinerecloserona21kVcircuitopenedresultinginanoutagefor1,027customers. CLOSED

20140615-01 SCE Injury Underground16

kVcables

Athirdpartysustainedelectricalburninjurieswhileattemptingtocutinto16kVundergroundcableshousedinconduitinstalledonarisepole.

CLOSED

20140616-02 SCE Injury Overhead16kV

conductor

AthirdpartywasonaroofofapartiallycompletedbuildingfinishingconcretewhenheinadvertentlycontactedanSCE16kVoverheadconductorwithanaluminumtoolandwasinjured.

CLOSED

20140617-01 SCE

Outageattractedmedia

attention

Overhead12kVconductors

Areportofabrushfireindicatedthatthefireinvolveddownedpowerlines,butSCEpersonnelwereunabletolocateanydownedpowerlines.

CLOSED

20140627-01 PG&E

Outageattractedmedia

attention

Undergroundcable AnundergroundsecondaryconnectionfailedinthecityofChicoresultinginanoutageto50commercialcustomers. CLOSED

20140701-01 PG&E

Outageattractedmedia

attention

Insulators Twopolefirescausedanoutageto5,948customersona12kVcircuit. CLOSED

20140705-01 PG&E Fatality Overhead12kV

conductor

AnoverheadconductorfelltothegroundinOakland.Twopersonswereinjuredwhentheymadecontactwiththedownedconductor;oneoftheinjurieswasfatal.

CLOSED

20140705-02 SCE Damageclaim Poles EighteenSCEpolesbrokeandfelltothegroundduring

moderatewindconditions. CLOSED

20140708-01 PG&E

Outageattractedmedia

attention

Overhead4kVconductor

Anoutageoccurredona4kVcircuitduetothird-partyfireworks. CLOSED

20140709-02 PG&E Injury Overhead12kV

conductor

AthirdpartywasinjuredwhenahomemademetalflagpolehesetinthecityofMarysvillecontactedPG&E’soverheadconductor.

CLOSED

Page 27: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

27

20140710-01 PG&E

Outageattractedmedia

attention

Undergroundsplice

Anundergroundsplicefailedona12kVcircuitresultinginanoutagefor1,403customers. CLOSED

20140711-01 PG&E Damageclaim Transformer Anoutageoccurredto16customersona12kVcircuit. CLOSED

20140715-02 PG&E

Outageattractedmedia

attention

CircuitbreakerAPG&E115kVlinewasmistakenlyde-energizedbyPG&Eemployees.Asaresult,26,983customerswerewithoutpowerforsixminutes.

CLOSED

20140716-01 PG&E Damageclaim Substation Athirdpartystructuralfireoccurredduetoovervoltagefrom

PG&E'sfacility. CLOSED

20140717-01 SDG&E Fatality Overhead12kV

conductor

TwoworkerswereontopofscaffoldingwhenoneoftheworkerscontactedanoverheadSDG&Eprimaryconductorandsustainedfatalinjuries.Theotherworkerwhosubsequentlyattemptedtoprovideassistancereceivedanelectricalshock.

CLOSED

20140718-01 PG&E Injury Overhead12kV

conductorAcrop-dustinghelicopterstruckaPG&Eguywireona12kVcircuitandcausedanoutage. CLOSED

20140718-02 SCE Injury Poles TwopolesinstallednexttoStateRoute14fracturedandfailed,

causing16kVoverheadconductorstofallonthehighway. CLOSED

20140718-03 PG&E

Outageattractedmedia

attention

Overheadconductors

AnoutageoccurredtotheWhitmoreandCedarCreekSubstations,affecting1,326customersontheKilarc-Deschutes60kVline.

CLOSED

20140719-01 SCE

Outageattractedmedia

attention

Underground12kVcable

A12kVundergroundcablefaultedandfailedinsideatrench,resultinginanoutagetoapproximately1,200customers. CLOSED

20140720-01 Liberty Majoroutage Substationbus

Alightningstrikecausedanoutagetoseveralsubstations.Theoutageaffectedapproximately25,000LibertyUtilitiescustomers.

CLOSED

20140721-01 PG&E Injury Fuse AcontractorhiredbyPG&Etocompleteapolereplacementwas

shockedwhenhemadecontactwithaprotectiondevice. CLOSED

20140722-01 SDG&E Injury Overhead12kV

conductor

AnSDG&Econtractorwasinstallinga"HighVoltage"warningsignonahollowsteelpolethathousedthree12kVcableswhenhedrilledintoa12kVcableandwasinjured.

CLOSED

20140722-02 PG&E

Outageattractedmedia

attention

Overhead12kVconductor Anoutageoccurredona12kVcircuitduetoconductorfailure. CLOSED

20140724-01 SCE Majoroutage Transformer

Awindingofatransformerinasubstationexperiencedaphase-to-groundfaultandcaughtonfire.Thiscauseanoutagetoover26,800customers.

CLOSED

20140724-02 PG&E

Outageattractedmedia

attention

Overhead60kVconductors

Anoutageoccurredona60kVtransmissioncircuitduetoanuprootedtree. CLOSED

Page 28: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

28

20140727-01 PG&E Damageclaim Overhead12kV

conductor

AnoaktreeinthetownofElPortalfellandcontactedaconductor.Thecontactcreatedafireinwhich4,690acreswereburntandpropertydamageexceeded$50,000.Thefirecausedanoutageaffecting591customers.

CLOSED

20140728-01 SCE

Outageattractedmedia

attention

Threeoverhead12kVconductors

A4kVoverheadinsulatorfailedandcausedagroundfaultcurrent.Thiscausedmultipleconnectorstooverheatandfailwithinthreeconductorspans.

CLOSED

20140730-01 PG&E

Outageattractedmedia

attention

Overhead4kVcircuit PG&Ede-energizeda4kVcircuitduetoathird-partyfire. CLOSED

20140801-01 PP&L Fatality Overhead12kV

conductorsAcropdusterflyingunder12kVcircuitpowerlinesmadecontactwith12kVconductorsandcrashed. CLOSED

20140802-02 PG&E

Outageattractedmedia

attention

Fouroverhead12kVconductors

FourspansofPG&Econductorona12kVcircuitfelltothegroundcausinganoutageto3,192customers CLOSED

20140804-01 SCE

Outageattractedmedia

attention

Undergroundsplice

Insulationona16kVundergroundcircuitfailedatasplicelocatedinsideavaultandcausedanoutage. CLOSED

20140804-02 SCE Media

attention Pole ApolefirewasreportedtoSCEbythefiredepartment. CLOSED

20140804-03 PG&E

Outageattractedmedia

attention

Circuitbreaker APG&Ecircuitbreakeropenedona12kVconductorcausinganoutagefor3,828customers. CLOSED

20140805-01 SCE Injury Underground12

kVcable

Athirdpartyinadvertentlycutintoa12kVSCEundergroundcableandsustainedelectricalburninjurieswhileworkingonasewerpipe.

CLOSED

20140806-02 PG&E Injury Overhead12kV

conductor

AthirdpartylandscaperwastrimmingatreewhenthepruningtoolhewasusingmadecontactwithaPG&E12kVoverheadconductor.

CLOSED

20140806-03 SCE Damageclaim Undergroundcable

AnundergroundSCEsecondaryneutralcablefailed.Asaresult,residenciesexperiencedfloatingvoltageconditions.Oneoftheresidents'powerstripfailedandignitedafire.

CLOSED

20140806-05 SCE Damageclaim Pole SCEfinalizedapolereplacementproject.Afterre-energizingthe

serviceline,afireeruptedintworesidences. CLOSED

20140810-01 PG&E

Outageattractedmedia

attention

Twooverhead12kVconductors

3,854customersexperiencedanoutageona12kVcircuitwhenalinerecloseroperatedinthecityofPleasanton. CLOSED

20140811-01 SCE Damageclaim None

TherewasastructurefireinthecityofGrandTerrace.Theinsurancecompanystatedthedamagetothehomeisapproximately$260,000.

CLOSED

20140812-01 SCE Injury Underground12

kVcableAnSCEcontractorsustainedelectricalburninjurieswhenhecutintoaconduithousinganenergized12kVcircuit. CLOSED

Page 29: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

29

20140818-01 PG&E

Outageattractedmedia

attention

Threeoverhead12kVconductors Anoutageoccurredona12kVcircuitduetoathird-partyfire. CLOSED

20140818-02 SCE Damageclaim Nineteenpoles NineteenSCEwoodpolesofGradeBconstructionbrokeandfell

totheground. CLOSED

20140818-03 SCE Damageclaim Insulator/overhead

12kVconductor

Aninsulatorand/orconductorona12kVcircuitfailed,causingthecircuittorelayandlockout.Subsequently,afirewasreportedwhichultimatelyconsumed4,045acresofvegetation,twovehicles,14properties,nineSCEpoles,andseveralspansofconductors.

CLOSED

20140819-01 PG&E

Outageattractedmedia

attention

Transformer Anoutageoccurredona12kVcircuitduetoafailedoverheadtransformer. CLOSED

20140819-02 PG&E

Outageattractedmedia

attention

Overheadconductors AnoutageoccurredonaPG&EcircuitduetoaMylarballoon. CLOSED

20140822-01 PG&E

Outageattractedmedia

attention

Undergroundsplice

APG&Eundergroundsplicefailedona12kVcircuitcausinganoutageto1,828customers. CLOSED

20140824-01 PG&E Outage Variousfacilities Amagnitude6.0earthquakeoccurredinNapacausingoutages

to75,509customers. CLOSED

20140826-01 SCE Fatality Transmission

tower

Anindividualclimbeda105-footsteellatticetransmissiontowerthatsupporteda66kVSCEcircuit,andjumpedtothegroundandcommittedsuicide.

CLOSED

20140827-01 PG&E Vandalism Substation

Asubstationwasburglarizedbyunknownsuspects.Thesuspectsbreachedthefenceandstoleconstructionequipmentfromthestagingyardandthesubstationoperationsyard.Itwasreportedthatapproximately$40,000inequipmentwasmissingfromthesubstation.

CLOSED

20140829-01 SCE Injury Overhead4kV

conductors

TwofirefightersreceivedshockinjurieswhentheyinadvertentlycontactedadownedSCEoverheadconductorwhileextinguishingafireinElCerrito(RiversideCounty).

CLOSED

20140902-01 PG&E

Outageattractedmedia

attention

Undergroundconnector

Anundergroundconnectorfailedona12kVcircuitcausinganoutageto3,558customers. CLOSED

20140904-01 SCE Damageclaim Overhead

conductors

AtreecontactedoneormoreSCEoverheadsecondaryconductorsduringstrongwindconditionsresultinginanover-voltagethatresultedinafireatapropertywhichcausedover$50,000indamages.

CLOSED

Page 30: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

30

20140906-01 SCE

Outageattractedmedia

attention

Pole

AnSCEpolebrokeatapproximately7feetfromthetopofthepole.The7-footpolesegment-supportingSCE16kVoverheadconductors–felltotheground,causingtheSCEoverheadconductorstohangacrossPacificCoastHighway.

CLOSED

20140909-01 SDG&E Damageclaim Capacitorbank

Acapacitorbankcaughtfireinasubstation.Smokefromthefirecausedsoottobuildupontwotielines,resultinginaflashover.Thistrippeda138kVbustie,de-energizinga138kVbusanda128/12kVtransformer.

CLOSED

20140909-02 SCE Media

attentionOverheadconductors

AnSCEsubcontractorwaspullingconductorsacrosstwotransmissiontowers.TheequipmentusedtopulltheconductorbrokecausingtheequipmentandaconductortofalldownacrossStateRoute60freeway.

CLOSED

20140909-03 SCE Judgmentcall Overhead

conductors

AnSCEcontractorwasinstallinganewconductorusingahoist.Thehoistfailedandcausedaconductortofallanddamageasmallagriculturalshadeshed.Also,anemployeeofthecontractorsustainedminorinjurytohishandasaresultoftheincident.

CLOSED

20140912-01 SDG&E Damageclaim Twopoles Twopolesfractured,felltotheground,andcameincontact

withapassingvehicle. CLOSED

20140916-01 PP&L Damageclaim Various AlargewildfireinWeeddamagedPacificPowerfacilities. CLOSED

20140917-01 PG&E Damageclaim Pole

Asemi-truckveeredofftheroadandhitapoleinthecityofOrland.Thiscausedconductorstofalltothegroundandstartafirethatdamagedahouseneartheincident.

CLOSED

20140918-01 PG&E

Outageattractedmedia

attention

Various AstormresultedinmultipleoutagesintheEastBay. CLOSED

20140923-01 SCE Damageclaim Pole AnSCEpoleburned,brokenearitsmidpoint,andfelltothe

ground. CLOSED

20140924-01 SCE Injury Ladder

TwolaborersworkingforanSCEcontractorwereinsideanSCEvault,whenaladderalaborerwasusingtoexitthevaultbuckled,causinghimtofallontotheotherlaborer,whohadbeenstandingbelowsecuringtheladder.

CLOSED

20140924-02 PG&E Judgmentcall Overhead12kV

conductors

Twooccupantsinasingleengineplaneflewintoa12kVcircuitcausingtheconductorstofalltotheground.All63customerswithoutpowerwererestoredwithintwelvehours.

CLOSED

20140927-01 PG&E Injury Guywire Athirdpartymadecontactwithan"energized"guywirewhile

descendingthepole. CLOSED

20141003-01 SCE Damageclaim Transformer

AtransformerfailedinsideasubstationandcausedSCEtoutilizeloadsheddingproceduresforapproximatelythreehours,affectingapproximately18,000customers.

CLOSED

20141003-02 PG&E

Outageattractedmedia

attention

Overhead12kVconductors Anoutageoccurredona12kVcircuitduetoafallentree. CLOSED

Page 31: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

31

20141005-01 PG&E Injury Overhead12kV

conductorAthirdpartywasinjuredwhenhelifteda47footantennaontoPG&E’s12kVconductorinthecityofAtwater. CLOSED

20141009-01

TransBayCable Damage Submarinecable

AvesseldroppedanchorsintheCarquinezStraitdueenginemalfunction.TheanchorsstruckanddamagedTransBayCable’s200kVdirectcurrentsubmarinecable.

CLOSED

20141018-01 PG&E Injury Overhead12kV

conductorAPG&Elinemanwasinjuredwhileinstallinganoverheadconductor. CLOSED

20141022-01 SCE

Outageattractedmedia

attention

TransformerTransformersfailedafterSCEcrewcompletedaplannedmaintenanceworkinvolvingreplacementofagasswitchofa16kVcircuitinanundergroundvault.

CLOSED

20141027-01 SCE Fatality Transmission

tower

TheSheriff'sDepartmentreceiveda911callfromanindividualthreateningtojumpfromatower.Thatsameday,abodywasdiscoverednearthebaseofanSCEtransmissiontower,whichwasunderconstruction.

CLOSED

20141106-01 SCE Injury Underground

elbow

TwoSCEworkerssustainedelectricalburninjurieswhentheyremovedadummyelbowfromanenergized,12kVswitchinsideavault.

CLOSED

20141109-01 PG&E Fatality Overhead

conductors Anaircraftcollidedwitha21kVcircuitandcausedanoutage. CLOSED

20141112-01 PG&E Injury Underground21

kVcable

SanJosecityemployeewasreplacingasewerlinewhenhehitanddamagedaPG&E21kVundergroundconductor.Asaresult,hereceivedburninjuriestohisfaceandarms.

CLOSED

20141125-01 SDG&E

Intentionaloutage-

responsetoRedFlagWarning

Transmissioncircuit

InresponsetoaRedFlagWarningissuedbytheNationalWeatherServiceinSanDiegoandOrangecounties,SDG&Eproactivelyde-energizedtwodistributioncircuitsandonetransmissioncircuit.

CLOSED

20141125-02 SCE Fatality Overhead16kV

conductor

AtreetrimmerwastrimmingatreewhenheinadvertentlycontactedanSCEoverheadconductorwithanaluminumpruningpoleandwasfatallyinjured.

CLOSED

20141205-01 PP&L Outage Overhead

conductors

APacificCoaststormaffectedelectricreliabilityacrossthenorthcoastofCalifornia.Theheavyrainandhighwindscauselargenumbersoftreestobecomeunstableandfallontotransmissionanddistributionpowerlines.

CLOSED

20141207-01 SCE Injury Twounderground

12kVcables

TwoSCEcontractorswerechippingconcreteinaconcreteductadjacenttoanSCEvaultwhentheyinadvertentlystrucktwoenergizedSCE12kVcables,resultinginarcburninjuries.

CLOSED

20141208-01 TBC Judgment Phasearm Anoutageoccurredataconverterstationduetoexcessive

corona. CLOSED

20141210-01 PP&L Injury Overhead12kV

conductor

Athirdpartywasinjuredwhenheliftedanirrigationpipeintoa12kVoverheadconductor.Hesustainedburninjuriestohisrightshoulderandfeet.

CLOSED

20141211-01 PG&E

Outageattractedmedia

Underground12kVcable

AnundergroundcablefailedintheCityofSanFranciscoandcausedanoutageto86,000customers. CLOSED

Page 32: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

32

attention

20141215-01 PG&E

Outageattractedmedia

attention

Twopoles Anoutageoccurredona21kVcircuitduetoastorm. CLOSED

20141219-01 PG&E

Outageattractedmedia

attention

Undergroundsplice

APG&Eundergroundspliceona12kVcircuitfailedcausinganoutagefor38customers. CLOSED

20141222-01 SCE Outage Circuitbreaker

A66kVcircuitbreakerfailedandcaughtonfireatasubstation.Theeventcausedanoutagetoapproximately20,000customersforapproximatelyfourhours.

CLOSED

20141227-01 SDG&E Outage Underground

connector AT-bodyconnectorinsideamanholefailed,causinganoutage. CLOSED

20141230-01 PG&E Fatality Overhead

conductors

AmetallictruckbedmadecontactwithanoverheadPG&Ecircuit.Whilethebedwasincontactwiththeenergizedconductor,thedriversteppedoutontothegroundandwaselectrocuted.

CLOSED

20150103-01 PG&E

Mediaattentionduetoplanecrashintooverhead

circuit

Overhead12kVcircuit

Anairplanestrucka12kVcircuitandcausedanoutageto155customers. CLOSED

20150105-01 SDG&E Damageclaim Overhead

transformer

Anoverheaddistributiontransformerfailed,causinganovervoltageconditiononthesecondaryconductorsservicinganadjacentresidence.Subsequently,afireoccurredinsidetheresidencethatresultedinnearly$100,000ofdamages.

CLOSED

20150106-01 PG&E Fatality Overhead60kV

conductor

Athird-partycontractorwasfatallyinjuredwhileoperatingabucketliftthateithermadecontactorreceivedanarcflashfroma60kVconductor.

CLOSED

20150108-08 PG&E

Outageattractedmedia

attention

Underground12kVconductor

Athirdpartydugintoaunderground12kVconductor.Thedig-incausedafireandanoutageonthe12kVcircuit. CLOSED

20150120-01 PG&E

Outageattractedmedia

attention

Circuitbreaker

TwoPG&EelectricianswereconductingatestofsubstationequipmentinaPG&Esubstation.Duringthetestingprocedure,theelectricianscausedaphasetophasefaultinsideacircuitbreaker.

CLOSED

20150126-01 SCE

Outageattractedmedia

attention

Overhead12kVconductorand

poles

AeucalyptustreeinthecityofFontanauprootedduringawindstorm,fellontothreeSCEoverheadconductors,anddamagedthreeSCEpolesandassociatedequipment.Thesubsequentoutageaffected1,345customersforapproximately11hours.

CLOSED

Page 33: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

33

20150204-01 SDG&E

Outageattractedmedia

attention

Splice

DuringundergroundworkinBalboaPark,SDG&Epersonnelinadvertentlymovedanundergroundprimarycable,damaginganagedhandspliceconnectionattheendoftheline.Thesubsequentinterruptionaffectedsevencustomersforapproximately13hoursand30minutes.

CLOSED

20150206-01 SCE Damage 12kVcircuit SCEreceivedreportsofabrushfirewhichstartedinBishop,Inyo

Countyandmayhaveinvolveditsfacilities. OPEN

20150207-01 SCE Damage

Pole,16kVcircuitandsubstationequipment

Afireburnedapproximately509acresinMonoCountyanddamagedsevenpolesthatsupportedtwo16kVcircuits,andfacilitiesinsideasubstation.

CLOSED

20150210-01 PG&E

Damage(Incident

occurredon2/21/2013,butPG&Ewasnotawareofthedamageuntil2/10/2015)

TransformerWhilereplacingatransformer,afaultoccurredkillingabout39,000lbs.ofRainbowTroutintheirpondsystem.Thecostoflostfishinventoryisinexcessofthe$50,000criterion.

OPEN

20150213-01 SCE Injury Overhead16kV

conductor

AthirdpartywasmovingaladderwhentheladdercontactedanenergizedSCEoverheadconductorresultinginburninjuriestothethirdparty..

CLOSED

20150224-01 SCE Injury Fuseholder Acontractorworkerwasascendingapolewhenhe

inadvertentlycontactedanenergizedfuseholder. CLOSED

20150226-01 PG&E

Outageattractedmedia

attention

60kVcircuit A60kVlineexperienceafaultcausinganoutagetoonemajorcustomer(CityofHealdsburg). CLOSED

20150227-01 PG&E Injury Overhead12kV

conductor

Acropdustinghelicopterstruck12kVdistributionconductorsinatangerineorchardinVisalia,causinganoutagetoacustomeronthatcircuit,andinjuringthepilot.

CLOSED

20150228-01 SCE Injury Overhead66kV

conductorApersonclimbedanSCEsteellatticepoleandmadecontactwitha66kVoverheadconductor. CLOSED

20150303-01 SCE Injury Polereplacement

equipmentAlinemansustainedinjurytothelefthandfingerswhilereplacingapole. CLOSED

20150318-01 SCE Injury Poleand12kV

conductor

AlaborerwasoperatingaforkliftwhenheinadvertentlystruckanSCEpolewiththeforklift,causingthepoleandassociatedoverheadconductorstofalltotheground.Hesufferedseconddegreeburnsasaresultofelectricalcontact.

CLOSED

20150325-01 SDG&E Damage Underground12

kVconductor

Asub-contractingexcavatorstrucka12kVundergroundcable,resultinginanoutageto24customersanddamagestoSDG&Efacilitiesinexcessof$50,000.

CLOSED

20150325-02 SCE

Outageattractedmedia

attention

16kVcircuit A16kVcircuitrelayedandlockedoutcausingoutages. CLOSED

Page 34: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

34

20150325-04 PG&E Fatality 12kVcircuit

Athirdpartyfatalityduetoelectricalcontactandreportedoutageto50customersona12kVcircuitinFresno. OPEN

20150329-01 SCE Fatalityand

injury 16kVconnectorThreelinemancontractorswerereportedlyinjuredastheywerefinishingaplannedoutageinHermosaBeach,LosAngelesCounty.

OPEN

20150403-01 SCE Damage Underground

secondarycableAresidentialunitsustainedfiredamageduetothefailureofinsulationonanundergroundsecondaryneutralcable. CLOSED

20150406-01 PG&E

Outageattractedmedia

attention

Substation Asustainedoutageaffectingapproximately74,000customersintheChicoareaoccurred. OPEN

20150409-01 SDG&E Injury Treeduringtree

trimmingAtreetrimmerwastrappedunderdeadfrondsofapalmtree,andstayedovernightatahospitalforobservation. CLOSED

20150409-02 PG&E Injury Overhead115kV

conductorAtransmissionlinemansustainednonlifethreateninginjuryaftercontactinga115kVconductorinthecityofNewark. OPEN

20150410-01 PG&E Fatalityand

injuryPadmountedtransformer

OnepersonwaselectrocutedandonewasinjuredwhentheyattemptedtoopenandvandalizeaPG&Epad-mounttransformerinanundergroundlinesectionofa12kVcircuitinthecityofStockton.

OPEN

20150413-01 SDG&E

Outageattractedmedia

attention

Lightningarrestor Alightningarrestorfailedonapole,causinga275acrefireonCampPendleton. CLOSED

20150414-01 SCE Injury Equipmentin

undergroundvault

A16kVdistributioncircuitrelayedandreclosed.SCEsubsequentlyreceivedareportthattwocontractorlinemenwereinjuredwhileworkinginavaultandtransportedtoahospital.

OPEN

20150422-01 SCE Fatality Transmission

towerThepolicedepartmentreceivednotificationofabodylocatedonthegroundincloseproximitytoatransmissiontower. OPEN

20150504-01 SCE Fatality Transmission

tower

Athirdpartyclimbeda90-footsteelpolejointlyusedbySCEandLADWP,contactedanLADWP34.5kVoverheadconductor,andfelltotheground.Hereceivedfatalinjuries.

CLOSED

20150506-01 PG&E

Outageattractedmedia

attention

Pole-mountedtransformer

AMylarballooncameintocontactwithapole-mounted12kVtransformerinSanLeandro.Theincidentcausedanoutagetocustomersonthe12kVcircuit.

CLOSED

20150507-01 PG&E Injury Pole APG&Elinemanwasinjured(brokenleg)whileremovingapole

onaPG&Ejobsite. OPEN

Page 35: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

35

20150514-01 PG&E

Outageattractedmedia

attention

50kVAtransformer

Lightningstruckaflagpoleandarcedfromtheflagpoletoacustomer’sservicedropcausingavoltagesurgeleadingtoequipmentfailure.Theincidentresultedinanoutagetocustomers.

CLOSED

20150518-01 PG&E

Outageattractedmedia

attention

Overhead12kVconductor

AMylarballooncameintocontactwitha12kVcircuitcausinganoutagetocustomers. CLOSED

20150519-01 SCE Damage 16kVcircuit Aresidentialfirecausednearly$100,000inpropertydamage. CLOSED

20150523-01 SCE Injury Overhead12kV

conductorAhanggliderwasinjuredwhenhecontactedSCEoverheadconductors,causinga12kVcircuittorelayandlockout. CLOSED

20150528-01 PG&E

Outageattractedmedia

attention

LightningarresterAlightningarrestermountedonaself-protectedtransformerbrokefromitsmountandcameincontactwiththetransformercasing.Theincidentresultedinanoutagetotwocustomers.

CLOSED

20150601-01 PG&E

Injury(incidentoccurredon5/22/2015,

PG&Ewasnotawareofit

until6/1/2015)

12kVcircuit

PG&EwasnotifiedbyOSHAofaninjurybasedonareportfiledbyaninjuredthirdparty'semployer.Aboommadecontactwithanoverheadconductorwhilemovingpipescausingtheinjurytooneperson.

OPEN

20150604-01 SDG&E

Outageattractedmedia

attention

4kVcircuit Aeucalyptustreefellona4kVcircuitcausinganoutage. CLOSED

20150606-01 PG&E Fatality Overhead12kV

conductor

Athirdpartywasusingacranetoinstallanewwellpumpmotor,whenthecablesusedtoraisethecranecontactedaPG&Eoverheadconductor.

CLOSED

20150608-01 SDG&E

Outageattractedmedia

attention

230kVcircuit

A230kVtransmissioncircuitexperiencedvoltagefluctuations.Thisaffectedapproximately125,000customersforaboutthreehours,andresultedinflickeringlights,anddamagetoelectronicappliancesthattotaledapproximately$12,000.

CLOSED

20150609-01 SDG&E

Mediaattentiondue

tofire69kVconductors Ahawkmadecontactwith69kVoverheadconductorsstartinga

fire. CLOSED

20150609-02 PG&E Damage Poleand12kV

conductorApoleandwirefellonahouseintheCityofTraverandcausedtotallossofthehouse. OPEN

20150610-01 SDG&E Injury 138kVcircuit Acontractorwasinjuredwhileworkingonanoverheadcircuit. OPEN

20150613-01 BVES Outage

Lightningstrikeaffectingoverhead

equipment

BearValleyElectricalService(BVES)experiencedasystem-wideoutage. CLOSED

20150613-02 BVES Outage

Lightningstrikeaffectingoverhead

equipment

BearValleyElectricalService(BVES)experiencedasystem-wideoutagefor20minutes. CLOSED

20150621-01 SCE Injury 12kVprimaryriser Onepersonwasinjuredwhiteattemptingtovandalizea12kV

primaryriser,causingasmallpolefire. CLOSED

Page 36: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

36

20150623-01 PG&E

Outageattractedmedia

attention

Pole

AthirdpartyexcavatorstruckadistributionpoleandtelephonespanguywhichcausedtheprimaryoverheadconductortobreakandfalltothegroundintheCityofArvin.Theincidentresultedinanoutageaffecting102customers.

CLOSED

20150624-01 SCE Injury 16kVcircuit

Athirdpartywasinjuredwhenthetoolhewasusingtochipencasementonaductmadecontactwithanunderground16kVcable.

OPEN

20150625-01 PG&E

Mediaattentiondue

topublictransitdelays

andfire

Overheadconnector

Afaultoccurredonadistributioncircuitcausingaconnectortofail.ThefailurecausedconductorstofallontothegroundandacrossBayAreaRapidTransit(BART)tracksresultinginagrassfire.

CLOSED

20150626-01 SCE Injury Fiberglassinsulator

Asub-contractorsustainedaheadinjurywhilediggingaholetoreplaceapole,fromafallingfiberglassinsulatorthathadbeenlooselyhungonanaerialbuckettruck.

CLOSED

20150703-01 SDG&E

Outageattractedmedia

attention

12kVcircuit SDG&Eexperiencedacircuitoutageaffecting6288customersforapproximatelyfifteenhours. CLOSED

20150703-02 SCE

Mediaattentionduetobrushfire

Overhead12kVconductor

Apinetreelocatedadjacenttoaspanof12kVoverheadconductorsfellontoaeucalyptustree,whichinturncontactedthe12kVconductors,causingafault,andfelltotheground.

CLOSED

20150707-01 PG&E Injury Overhead12kV

conductorAworkermadecontactwithanoverheadconductorwhileonscaffolding. OPEN

20150709-01 SCE Injury Overhead12kV

conductor

Acontractorworkingonapolereplacementprojectmadecontactwithoverheadfacilitiesandsustainedflashburnstohisface.

OPEN

20150709-02 SCE Damage Underground66

kVcable

Athirdpartycontractor,whileperformingdirectionalboringfortheinstallationofgasfacilities,struckanddamagedunmarked66kVundergroundsub-transmissioncables.

CLOSED

20150713-01 SDG&E

Outageattractedmedia

attention

Overheadswitch Anoverheadswitchfailedandcausedanoutageto1700customers. OPEN

20150713-02 SDG&E

Outageattractedmedia

attention

Undergroundconnector

Anundergroundconnectorfailedandcausedanoutageto2855customers. CLOSED

20150713-03 SDG&E

Outageattractedmedia

attention

Undergroundconnector Anundergroundconnectorfailedcausingoutages. OPEN

20150714-01 SCE

Damage(incident

occurredon10/12/2012;however,SCEwasnotawareofthedamages

until7/14/2015

TransformerSCEreceivedasummonsindicatingthatlightningstruckatransformerwhichservesaresidenceandcaused$424,957.68indamages.

OPEN

Page 37: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

37

20150715-01 SCE

Mediaattentiondue

tofire12kVcircuit Newsmediareportedavaultfireandinterruptionofelectrical

servicetocustomersintheLongBeacharea. OPEN

20150719-01 SCE

Mediaattentionduetooutageand

fire

Overhead12kVconductor

Ahighwindeventcauseddamagetooverheadelectricalfacilitiesona12kVcircuitwhichrelayedandlocked-out.SixpolessustaineddamageresultingindownedconductorsandtheclosureofHighway74bytheCaliforniaHighwayPatrol.

OPEN

20150720-01 SCE

Mediaattentionduetooutageand

fire

16kVcircuit A16kVcircuitrelayedandlocked-out.SCEsubsequentlyreceivednotificationofavaultfireinthecityofValVerde. CLOSED

20150727-01 PG&E Fatality Overhead21kV

conductorAtreetrimmerwaselectrocutedwhenhecontacteda21KVline. CLOSED

20150727-02 PG&E Damage Overhead115kV

circuit AnairplanestruckPG&E’sfacilitycausingdamageover$50,000. CLOSED

20150730-01 PG&E Injury Overhead12kV

conductor

PG&EreceivedreportofathirdpartyinjurycausedbycontactwithanoverheadconductorthroughametalobjectinthecityofPasoRobles.

CLOSED

20150730-02 PG&E Damage Transformer

AhouseinthecityofDixoncaughtfire.Preliminaryreportsindicatethatthefiremayhavestartedatafailedtransformerona12kVcircuitnearthehouse.

OPEN

20150731-01 PG&E Damage Overhead

connectorAnoverheadconnectorfailedandcauseddamagetoapropertyexceeding$50,000. CLOSED

20150801-01 SCE Injury Overhead12kV

conductorTwoindividualsridingmotorcyclescontactedoverheadelectricalfacilitiesandsustainedinjuries. OPEN

20150812-01 SCE Damage Underground

secondarycable

Anexcavatorstruckanundergroundsecondarycable.Shortlyafterthecablewasstruck,afireeruptedatanearbyhouse. OPEN

20150813-01 PG&E Injury Substation Athirdpartyenteredasubstationandmadecontactwith

energizedfacilities. OPEN

20150814-01 PG&E

Mediaattentionduetothirdparty

contact

Overhead115kVconductor Athird-partyoperatedcranecontacteda115kVconductor. CLOSED

20150815-01 PG&E Injury Overhead12kV

conductor

AthirdpartycutaPG&Edistributionpoleandcauseda12kVcircuittofalldown.Thethirdpartymadecontactwiththecircuitwhiletryingtoexitthetractor.

CLOSED

20150821-01 SCE Damage Poles AfirestartedintheSanGabrielCanyonareaofLosAngeles

Countyanddamaged30polesbelongingtoSCE. OPEN

20150823-01 SCE Damage Poles AfirebrokeoutintheWhittierNarrowsareainMontebello

damagingSCEoverheadfacilities. OPEN

20150828-01 SCE Injury 138kVtieline AnSDG&Eemployeewasinjuredworkingoverhead. OPEN

Page 38: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

38

20150828-02 PG&E Media

attentionTransmission

towerAcranehitatransmissiontowercausingthetowertocollapseandwirestocomedowninBurlingame. OPEN

20150902-01 PG&E Damage Unknown

PG&EwasputonnoticebyWalmartintheCityofAndersonthattheysustaineddamagesinexcessof$50,000fromavoltageincidentonAugust17,2015.

OPEN

20150914-01 SCE Damage Secondaryservice

SCEreceivedcorrespondencefromainsurancecompanyclaimingpropertydamageinexcessof$50,000asaresultoffluctuatingvoltagetoahomeinManhattanBeach,LosAngelesCounty.

OPEN

20150915-01 SCE Outage Substationbus

Anoperatingbusatasubstationrelayedtolockoutaffectingfivecircuitstotaling9,172customers.Anotheroperatingbusrelayedtolockoutaffectingsixcircuitsaffectinganadditional13,485customers.

OPEN

20150916-01 PG&E Fatality Overhead12kV

conductorAtreemayhavecontactedaPG&ElineinButte,causingafirethatresultedintwofatalities. OPEN

20150916-02 SCE

Outageattractedmedia

attention

Customerprimarymeter

Acustomer-ownedprimarymeterfailedandcausedSCE's12kVdistributioncircuittorelayandlockout. OPEN

20150920-02 SCE

Outageattractedmedia

attention

16kVcircuit Adownedconductorcauseda16kVdistributioncircuittorelayandlockoutcausinganoutage. OPEN

20150921-01 SCE

Outageattractedmedia

attention

Pole-mountedtransformer

Atransformerfailureonapolecausedanoutageandafireinapalmtree. OPEN

20150923-01 SDG&E Damage 69kVConductor A69kVoverheadconductorfellontoa4kVconductorand

trolleycatenaryconductor. CLOSED

20150925-01 PG&E Fatality Padmounted

transformerAnindividualsustainedfatalinjurieswhileattemptingtovandalizeapadmountedtransformer. CLOSED

20150925-02 SCE Fatality Padmounted

transformerAnindividualsustainedfatalinjurieswhileattemptingtovandalizeapadmountedtransformer. OPEN

20150926-01 PG&E Injury Subsurface

transformer

Anoutageoccurredona12kVcircuitinSanFrancisco.Duringtherestorationprocess,anundergroundPG&Etransformercatastrophicallyfailedresultingininjurytotwonearbyindividuals.

OPEN

20150930-01 SCE Outage Overheadinsulator Aflashoveronaninsulatorsupportinga115kVtransmissionline

resultedinanoutagetoover40,000customers. CLOSED

20150930-02 PG&E Fatality Pole

APG&Eemployeewasutilizingriggingwhilepreparingtoreplaceapolewhenapulleyfailedandstrucktheemployeeresultinginhisfatalinjury..

CLOSED

20151001-01 SCE Outage 12kVcircuit

Two12kVcircuitscausedanoutagetoapproximately3,500customersintheCityofFountainValleyand35,988intheCityofHuntingtonBeach.

OPEN

Page 39: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

39

20151002-01 PG&E Injury 230kVconductors Acontractorreceivedaninductionshockatastructureona230

kVtransmissionlinewhileworkingonoverheadfacilitires. OPEN

20151005-01 SCE Injury Manhole

AwomanslippedandfellintoanopenmanholewhensheapproachedSCEcontractors,whowereengagedinperformingundergroundmaintenanceandrepairworkinthemanhole.

OPEN

20151005-02 SCE Injury Underground12

kVconductorAconstructionworkerdugupandcontactedanundergroundcablesectionofa12kVdistributionline. OPEN

20151013-01 BVES

Outageattractedmedia

attention

34kVcircuitAtreebranchmadecontactwith34kVoverheadlinescausinganoutagetoapproximately9,200customersinthecityofBigBear.

OPEN

20151018-01 PG&E Judgment 230kVconductors

Atowersupportingtwo230kVlinesfailedresultingintheconductorsfallingacrosstwo115kVlines,affectingapproximately55,000customers.

OPEN

20151019-01 PG&E Injury 500kVcircuit APG&Elinemanreceivedelectricalburnsonhiswristsandfeet

whileworkingonoverheadfacilities. OPEN

20151026-01 SCE

Outageattractedmedia

attention

Overhead4kVcircuit

A4kVcircuitrelayedasaresultofadroneflyingintothepowerlinesandcausedoneoftheconductorstofallresultinginanoutage.

CLOSED

20151103-01 PG&E

Outageattractedmedia

attention

Poles Astormrelatedevent(heavyrain,windandlightning)resultedin8polesdowninChicoandanoutageto7,585customers. OPEN

20151104-01 SDG&E

Mediaattentiondue

tovaultexplosion

Vault ASanDiegoGasandElectricelectricalvaultexploded. OPEN

20151105-01 SCE Injury Underground12

kVconductor

AnemployeeoftheCityofTulareWaterDepartmentwasusingajack-hammerthatcontactedanddamagedundergroundelectricalfacilitiesresultinginburninjuriestobothofhishands.

OPEN

20151106-01 PG&E Damage Pole

ApolefireoccurredduringastormonNovember2,2015.OPEN

20151107-01 SCE

Mediaattentionduetooutageand

fire

16kVcircuit Afiremayhavebeencausedbyoverheadelectricfacilities. OPEN

20151114-01 SCE Injury 12kVcircuit Anindividualcutaprimarycableconduitthatwaslocatedunder

abridge(vandalism). CLOSED

20151116-01 PG&E

Outageduetoequipment

issues

Overhead12kVconductor

AprimaryconductorcamedowninSanJoseona12kVcircuitresultinginanoutageto2,156customers. CLOSED

20151118-01 SCE Damage Boltconnector Asecondaryconnectormayhavefailedandcausedastructure

fire. OPEN

20151120-01 PG&E

Injuryduetocontactwithelectricalconductor

230kVconductors TwoemployeesofaPG&Econtractorwereinjuredwhileworkingonoverheadfacilities. OPEN

Page 40: Annual Report Appendix D - California Public Utilities ... · Service Line A third-party excavator struck and damaged a 1" plastic service line causing an unintentional release of

40

20151122-01 SCE Injury Overhead12kV

conductor

Athirdpartycontactedasectionofa12kVcircuitfromanelevatedpositioninabuckettruckwhiletrimmingtreesfortheownerofahomeinWeldon.

OPEN

20151125-01 SDG&E

Outageattractedmedia

attention

Overhead12kVconductor

AbigrigtrucktransportinganoversizedloadstruckSDG&EoverheadelectricalconductorsspanningacrossInterstate8Freewayandcausedapoweroutage.

OPEN

20151128-01 SCE Injury Substation Anindividualaccessedenergizedequipmentwithinasubstation

andsufferedsevereburninjuries. OPEN

20151208-01 SCE

Mediaattentionduetooilrelease

Polereplacementequipment

AnundergroundoilpipelinewasdamagedbyacontractorworkingforSCEduringapolereplacementresultinginanoilrelease.

OPEN

20151209-01 PG&E Damage Overhead12kV

conductor

Atruckmadecontactwithanoverheadconductorcausingtheconductortofalldownandresultingindamagestothevehicleinexcessof$50,000.

OPEN

20151210-01 SCE Damage Substation

transformerA220/66kVsubstationtransformerfailedatasubstationlocatednearIrwindale,LosAngelesCounty. OPEN

20151210-02 PG&E Injury Overhead21kV

conductorPG&EreceivednoticeofathirdpartycontactwithenergizedoverheadlinesinWatsonville. OPEN

20151211-01 SCE Injury 12kVcircuit Acontractorworkingonoverheadfacilitiessustainedinjuriesin

aflashevent. OPEN

20151212-01 SCE

Mediaattentionduetooutageand

fire

16kVcircuit Abrushfireunderoverheadfacilitiescauseda16kVcircuittorelayandreclose. OPEN

20151230-01 SCE Injury 12KVcircuit-

ConnectorAnSCEemployeeworkingonapolewasinjuredwhilereplacingaconnectoronaconductor. OPEN