Anderson Construction And Home Inspection Of Idaho
2586 W. Primeland
Meridian , ID 83646(208) 917-2023
www.andersonhomeinspectionboise.comsteve@achomeinspectionboise.com
Inspected By: Steven Anderson, CPI
Home Inspection ReportPrepared For:
John SmithProperty Address:
Unspecified AddressInspected on Sat, Mar 10 2018 at 11:28 AM
Unspecified Address
Table of Contents
General 4Site 4Exterior 5Garage 6Roofing 7Structure 10Electrical 12HVAC 14Plumbing 17Bathrooms 18Kitchen 20Laundry 24Interior 26Report Summary 28
Page 2 of 41
Unspecified Address
Thank you for the opportunity to conduct a home inspection of the property listed above. We understand that the function of this report is to assist you in understanding the condition of the property to assist in making an informed purchase decision.The report contains a review of components in the following basic categories: site, exterior, roofing, structure, electrical, HVAC, plumbing, and interior. Additional categories may or may not be included. The report is designed to be easy to read and comprehend however it is important to read the entire report to obtain a full understanding of the scope, limitations and exclusions of the inspection.In addition to the checklist items of the report there are several comments which are meant to help you further understand certain conditions observed. These are easy to find by looking for their icons along the left side margin. Comments with the blue icon are primarily informational and comments with the orange icon are also displayed on the summary. Please read them all.DEFINITION OF CONDITION TERMSSatisfactory: At the time of inspection the component is functional without observed signs of a substantial defect.Marginal: At the time of inspection the component is functioning but is estimated to be nearing end of useful life. Operational maintenance recommended. Replacement anticipated.Repair or Replace: At the time of inspection the component does not function as intended or presents a Safety Hazard. Repair or replacement is recommended.Further Evaluation: The component requires further technical or invasive evaluation by qualified professional tradesman or service technician to determine the nature of any potential defect, the corrective action and any associated cost.
Page 3 of 41
Unspecified Address
GeneralClient's Signature:Property Type: Single FamilyStories: TwoApproximate Age: 2001Age Based On: ListingBedrooms/Baths: 4/2Door Faces: SouthwestFurnished: YesOccupied: YesWeather: OvercastTemperature: 67Soil Condition: DampUtilities On During Inspection: Electric Service, Gas Service, Water ServicePeople Present: Owner
SiteThe condition of the vegetation, grading, surface drainage and retaining walls that are likely to adversely affect the building is inspected visually as well as adjacent
walkways, patios and driveways.
Site Grading: Sloped Toward StructureCondition: Further Evaluation Required
Vegetation: Generally MaintainedCondition: Satisfactory
Retaining Walls: 3ft in heightCondition: Satisfactory
Driveway: ConcreteCondition: Satisfactory
Walkways: Concrete Condition: Satisfactory
Steps/Stoops: ConcreteCondition: Satisfactory
Patios/Decks: Wood, Rim joist not properly fasten Condition: Repair or Replace
Page 4 of 41
Unspecified Address
(Site continued)
Comment 1:
Figure 1-1 Figure 1-2
ExteriorThe visible condition of exterior coverings, trim and entrances are inspected with
respect to their effect on the condition of the building.
Exterior Covering: Vinyl SidingCondition: Satisfactory
Exterior Trim Material: WoodCondition: Painting may be required within the next two years
Windows: VinylCondition: Satisfactory
Entry Doors: FiberglassCondition: Satisfactory
Balconies: WoodCondition: Satisfactory
Railings: MetalCondition: Satisfactory
Page 5 of 41
Unspecified Address
(Exterior continued)
Comment 2:
Figure 2-1
GarageGarage Type: Attached
Condition: SatisfactoryGarage Size: 2 CarDoor Opener: Chain Drive
Condition: SatisfactoryOpener Safety Feature: Light Beam
Condition: Satisfactory
Page 6 of 41
Unspecified Address
(Garage continued)
Comment 3:
Figure 3-1
RoofingThe visible condition of the roof covering, flashings, skylights, chimneys and roof penetrations are inspected. The purpose of the inspection is to determine general
condition, NOT to determine life expectancy.
Inspection Method: From Ground with Binoculars, Walked Roof/Arms Length, Ladder on corners
Roof Design: Gable
Page 7 of 41
Unspecified Address
(Roofing continued)
Comment 4:
Figure 4-1 Figure 4-2
Figure 4-3
Roof Covering: 3 Tab ShingleCondition: With8n four years of most manufactures lifespan
Approximate Roof Age: 15Ventilation Present: Gable Ends
Condition: SatisfactoryVent Stacks: Plastic
Condition: SatisfactoryChimney : Wood Frame
Condition: Satisfactory
Page 8 of 41
Unspecified Address
(Roofing continued)
Sky Lights: YesCondition: Satisfactory
Flashings: MetalCondition: Satisfactory
Soffit and Fascia: VinylCondition: Satisfactory
Gutters & Downspouts: MetalCondition: Satisfactory
Comment 5:
Figure 5-1
Figure 5-2
Figure 5-3
Page 9 of 41
Unspecified Address
(Roofing continued)
Comment 6:
Figure 6-1 Figure 6-2
StructureThe visible condition of the structural components is inspected. The determination of adequacy of structural components is beyond the scope of a home inspection.
Foundation Types: Crawl SpaceFoundation Material: Poured Concrete
Condition: SatisfactorySigns of Water Penetration: Efflorescence
Condition: SatisfactoryPrior Waterproofing: Not PresentFloor Structure: Engineered I-Joist
Condition: SatisfactorySubflooring: Plywood
Condition: SatisfactoryWall Structure: Wood Frame
Condition: Satisfactory
Page 10 of 41
Unspecified Address
(Structure continued)
Comment 7:
Figure 7-1 Figure 7-2
Figure 7-3
AtticAttic Entry: Hallway, UpstairsRoof Framing Type: Wood Trusses
Condition: SatisfactoryRoof Deck Material: Oriented Strand Board
Condition: SatisfactoryVent Risers: PVC
Condition: SatisfactoryInsulation: Fiberglass Batts, 10 inch depth
Condition: Satisfactory
Page 11 of 41
Unspecified Address
(Structure continued)
CrawlspaceIf the clearance from the ground to the bottom of the joists is less than 36", or other adverse conditions exist, the inspector is not obligated to enter the
crawl space.
Inspection Method: InsideVapor Retarder: Installed, Some area to be fixed
Condition: SatisfactoryUnderfloor Insulation: Fiberglass Batts
Condition: Installed wrong direction. Paper side should be placed towards living space
Ventilation Present: YesCondition: Satisfactory
Moisture Condition: DryCondition: Satisfactory
ElectricalThe inspector can not inspect hidden wiring or verify if the number of outlets is per
the National Electric Code. A representative number of outlets, switches and fixtures are tested for operation.
Type of Service: UndergroundMain Disconnect Location: Service PanelService Panel Location: East sideService Panel Manufacturer: General Electric
Condition: SatisfactoryService Line Material: Copper
Condition: SatisfactoryService Voltage: 240 voltsService Amperage: 200 ampsService Panel Ground: Cold Water PipeBranch Circuit Wiring: Non-Metallic Shielded Copper
Condition: SatisfactoryOvercurrent Protection: Breakers
Condition: Satisfactory
Page 12 of 41
Unspecified Address
(Electrical continued)
GFCI/AFCI Breakers: NoCondition: Further Evaluation Required
Smoke Detectors: Hard WiredCondition: Satisfactory
Comment 8:
Figure 8-1 Figure 8-2
Figure 8-3 Figure 8-4
Page 13 of 41
Unspecified Address
(Electrical continued)
Figure 8-5
Sub PanelLocation: NoneService Line Material:Overcurrent Protection:Branch Circuit Wiring:GFCI/AFCI Breakers:
HVACHVAC System Type: Central Split SystemThermostat: Digital
Condition: Satisfactory
Page 14 of 41
Unspecified Address
(HVAC continued)
Comment 9:
Figure 9-1 Figure 9-2
Figure 9-3 Figure 9-4
HeatingThe heating system is inspected visually and operated by normal controls to determine general condition NOT life expectancy. The capacity or adequacy of the heating system is beyond the scope of a home inspection. A licensed
HVAC contractor should be consulted if in question.
Location: GarageType of Equipment: Forced Air
Condition: SatisfactoryManufacturer: Lennox
Page 15 of 41
Unspecified Address
(Heating continued)
Heating Fuel: GasCondition: Satisfactory
Input BTUs: 45,000Output BTUs: UnknownApproximate Age: 20 YearsFilter Type: Disposable
Condition: SatisfactoryOutput Temperature: 78Type of Distribution: Metal Ducting
Condition: Satisfactory
Furnaces over 10 years old should be checked, cleaned and serviced yearly by a licensed contractor.
CoolingThe cooling system is inspected by operation of the equipment by normal
controls to determine general condition NOT life expectancy. The capacity or adequacy of cooling system is beyond the scope of a home inspection. A
licensed HVAC contractor should be consulted if in question.
Energy Source: ElectricType of Equipment: Split System
Condition: SatisfactoryCondenser Make: LennoxCondensor Size: 48,000 BTU (4 Tons)Condenser Approximate Age: 21 YearsExpansion Coil Make: Not InspectedExpansion Coil Size: Not InspectedExpansion Coil Approximate Age: UnknownCondesate Drainage: To Exterior
Condition: SatisfactoryAC Supply Air Temp: 70AC Return Air Temp: 60AC Temperature Drop: 10
Air conditioners over 10 years old and heat pumps over 5 years old should
Page 16 of 41
Unspecified Address
(Cooling continued)
be checked, cleaned and serviced yearly by a licensed contractor.
PlumbingThe plumbing system is inspected visually and by operating a representative
number of fixtures and drains. Private water and waste systems are beyond the scope of a home inspection.
Water Service: PublicSupply Pipe Material: PVC
Condition: SatisfactoryLocation of Main Water Shutoff: At MeterSewer System: PublicWaste Pipe Material: ABS Plastic
Condition: SatisfactorySump Pump: Not PresentLocation of Fuel Shutoff: At Meter
Water HeaterManufacturer: American StandardFuel: Natural GasCapacity: 50 galApproximate Age: 18Temp & Pressure Relief Valve: Present With Blow Off Leg, Not Tested
Condition: SatisfactoryFuel Disconnect: Within Sight of EquipmentSeismic Straps Installed: No
Condition: Repair or Replace
Page 17 of 41
Unspecified Address
(Water Heater continued)
Comment 10:
Figure 10-1 Figure 10-2
Figure 10-3 Figure 10-4
Bathrooms
Bathroom #1Location: Main Level Bath Tub: Recessed
Condition: MarginalShower: In Tub
Condition: Marginal
Page 18 of 41
Unspecified Address
(Bathroom #1 continued)
Sink(s): Single VanityCondition: Marginal
Toilet: Standard TankCondition: Possible leaking base ring
Bidet: Not PresentShower Walls: Fiberglass
Condition: Repair or ReplaceTub Surround: Fiberglass
Condition: MarginalFloor: Vinyl
Condition: MarginalVentilation Type: Window
Condition: MarginalGFCI Protection: Outlets
Condition: Marginal
Bathroom #2Location: UpstairsBath Tub: Not PresentShower: Stall
Condition: SatisfactorySink(s): Single Vanity
Condition: MarginalToilet: Standard Tank
Condition: Further Evaluation RequiredBidet: Not PresentShower Walls: Tile
Condition: SatisfactoryTub Surround: Fiberglass
Condition: SatisfactoryFloor:Ventilation Type: Ventilator
Condition: Further Evaluation RequiredGFCI Protection: Outlets
Condition: Further Evaluation Required
Page 19 of 41
Unspecified Address
(Bathrooms continued)
Bathroom #3Location:Bath Tub:Shower:Sink(s):Toilet:Bidet:Shower Walls:Tub Surround:Floor:Ventilation Type:GFCI Protection:
KitchenCabinets: Wood
Condition: SatisfactoryCountertops: Granite
Condition: SatisfactorySink: Single
Condition: Marginal
Page 20 of 41
Unspecified Address
(Kitchen continued)
Comment 11:
Figure 11-1 Figure 11-2
Figure 11-3 Figure 11-4
Comment 12:
Page 21 of 41
Unspecified Address
(Kitchen continued)
AppliancesThis is a cursory check only of the specified appliances. The accuracy or
operation of timers, temperature or power level controls is beyond the scope of this inspection.
Oven: BoschCondition: Marginal
Range: BoschCondition: Further Evaluation Required
Cooktop: KenmoreCondition: Repair or Replace
Range Hood: BoschCondition: Repair or Replace
Refrigerator: Not InspectedDishwasher: Maytag
Condition: No leaks observed short cycleMicrowave: Kenmore
Condition: Marginal
Page 22 of 41
Unspecified Address
(Appliances continued)
Comment 13:Used microwave testier.
Figure 13-1
Disposal: FrigidaireCondition: Marginal
Washer: FrigidaireCondition: Satisfactory
Dryer: FrigidaireCondition: Repair or Replace
Page 23 of 41
Unspecified Address
(Appliances continued)
Comment 14:
Figure 14-1 Figure 14-2
Figure 14-3 Figure 14-4
LaundryBuilt In Cabinets: Yes
Condition: SatisfactoryLaundry Sink: Yes
Condition: Repair or ReplaceDryer Venting: To Attic
Condition: Satisfactory
Page 24 of 41
Unspecified Address
(Laundry continued)
Comment 15:Limited access.
Figure 15-1
GFCI Protection: NoCondition: Further Evaluation Required
Comment 16:
Figure 16-1
Laundry Hook Ups:Washer:Dryer:
Page 25 of 41
Unspecified Address
InteriorThe interior inspection is limited to readily accessible areas that are not concealed
by furnishings or stored items. A representative number of windows and doors.
Floors: TileCondition: Marginal
Walls: Textured Over DrywallCondition: Satisfactory
Window Types: Single HungCondition: Satisfactory
Window Materials: VinylEntry Door Types: Hinged
Condition: SatisfactoryEntry Door Materials: WoodInterior Door Materials: MasoniteFireplace: Manufactured
Condition: Further Evaluation Required
Comment 17:
Figure 17-1 Figure 17-2
Page 26 of 41
Unspecified Address
(Interior continued)
Figure 17-3 Figure 17-4
Page 27 of 41
Unspecified Address
Report Summary
This summary page is not the entire report. The complete report may include additional information of interest or concern to you. It is strongly recommended that you promptly read the complete report. For information regarding the negotiability of
any item in this report under the real estate purchase contract, contact your real estate agent or an attorney.
Site1)
Figure 1-1 Figure 1-2
Page 28 of 41
Unspecified Address
(Report Summary continued)
Exterior2)
Figure 2-1
Garage3)
Figure 3-1
Page 29 of 41
Unspecified Address
(Report Summary continued)
Roof Design4)
Figure 4-1 Figure 4-2
Figure 4-3
Page 30 of 41
Unspecified Address
(Report Summary continued)
Roofing5)
Figure 5-1
Figure 5-2
Figure 5-3
6)
Page 31 of 41
Unspecified Address
(Report Summary continued)
Figure 6-1 Figure 6-2
Structure7)
Figure 7-1 Figure 7-2
Page 32 of 41
Unspecified Address
(Report Summary continued)
Figure 7-3
Electrical8)
Figure 8-1 Figure 8-2
Page 33 of 41
Unspecified Address
(Report Summary continued)
Figure 8-3 Figure 8-4
Figure 8-5
Page 34 of 41
Unspecified Address
(Report Summary continued)
HVAC9)
Figure 9-1 Figure 9-2
Figure 9-3 Figure 9-4
Page 35 of 41
Unspecified Address
(Report Summary continued)
Plumbing: Water Heater10)
Figure 10-1 Figure 10-2
Figure 10-3 Figure 10-4
Page 36 of 41
Unspecified Address
(Report Summary continued)
Kitchen11)
Figure 11-1 Figure 11-2
Figure 11-3 Figure 11-4
12)
Page 37 of 41
Unspecified Address
(Report Summary continued)
Microwave13) Used microwave testier.
Figure 13-1
Kitchen: Appliances14)
Figure 14-1 Figure 14-2
Page 38 of 41
Unspecified Address
(Report Summary continued)
Figure 14-3 Figure 14-4
Dryer Venting15) Limited access.
Figure 15-1
Page 39 of 41
Unspecified Address
(Report Summary continued)
GFCI Protection16)
Figure 16-1
Interior17)
Figure 17-1 Figure 17-2
Page 40 of 41
Unspecified Address
(Report Summary continued)
Figure 17-3 Figure 17-4
Page 41 of 41