DRAWN BY: SARA N. BRIGGS
DATE:
SCALE: NOT TO SCALE
DRAWING TITLE: ANCHOR BOLT PLAN & SECTION
CAD FILE: F:\MULTIVIEW DRAWINGS\ANCHOR BOLT PLAN
4/28/2015 DRAWING NO: S2
SIZE:
B
CENTRAL CAROLINA TECHNICAL COLLEGE
ENGINEERING GRAPHICS TECHNOLOGY
CHECKED BY:
GRADE:
1'-7
1
2
"
24'-0"
48'-0"
24'-0"
1'-7
1
2
"
2" T
YP
.
3/4" ANCHOR BOLTS
(ALL LOCATIONS)
EDGE OF CONCRETE SLAB
2" TYP.2" TYP.
2"T
YP
.
5 1
/2
"5
1
/2
"
24
'-0
"
12
'-0
"1
2'-0
"
EDGE OF CONCRETE SLAB
5 1/2"
1
'
-
4
"
B
L
O
C
K
O
U
T
1
'
-
4
"
B
L
O
C
K
O
U
T
2"
4"
3/4" ANCHOR
BOLTS
NOTE: TOP OF
FOOTING AT
ANCHOR BOLT
SHALL BE 8"
BELOW FINISH
FLOOR
FOUNDATION NOTES:
CONCRETE SHALL BE 3000 PSI IN 28 DAYS
CONCRETE SLAB, APRONS AND DOOR STOOPS SHALL BE REINFORCED WITH 6X6 10/10 WWM
6 MIL POLY VAPOR BARRIER SHALL BE PLACED BETWEEN FLOOR SLAB AND COMPACTED SUB-GRADE
ALL REINFORCEMENT BARS SHALL BE GRADE 60
VERIFY ANCHOR BOLT SIZE AND LOCATIONS WITH BUILDING MANUFACTURER'S DRAWINGS PRIOR TO
CONCRETE PLACEMENT
ANCHOR BOLTS SHALL HAVE A 3" PROJECTION AND EXTEND TO LOWER 1/3 OF FOOTING DEPTH
ANCHOR BOLTS STRENGTH SHALL BE A36 GRADE
6'-0" SQ.
1'-4
"8
"
4"
6 X 6 10/10 WWM
1/2" EXPANSION
JOINT
COLUMN TO BE
RECESSED 6 1/2"
BELOW FINISHED
FLOOR
2'-0" SQ.
VAPOR
BARRIER
(12) - #6
EACH WAY
DETAILS
NOT TO SCALE