39

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

  • Upload
    others

  • View
    139

  • Download
    13

Embed Size (px)

Citation preview

Page 1: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation
Page 2: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

___________________

___________________

___________________

___________________

___________________

___________________

___________________

___________________

___________________

SIMATIC

ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual

04/2018 A5E36104399-AB

Preface

Documentation guide 1

Product overview 2

Wiring 3

Parameters/address space 4

Interrupts/diagnostics alarms 5

Technical specifications 6

Parameter data record A

Representation of analog values

B

Page 3: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Siemens AG Division Digital Factory Postfach 48 48 90026 NÜRNBERG GERMANY

A5E36104399-AB 05/2018 Subject to change

Copyright © Siemens AG 2015 - 2018. All rights reserved

Legal information Warning notice system

This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger.

DANGER indicates that death or severe personal injury will result if proper precautions are not taken.

WARNING indicates that death or severe personal injury may result if proper precautions are not taken.

CAUTION indicates that minor personal injury can result if proper precautions are not taken.

NOTICE indicates that property damage can result if proper precautions are not taken.

If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage.

Qualified Personnel The product/system described in this documentation may be operated only by personnel qualified for the specific task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems.

Proper use of Siemens products Note the following:

WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems. The permissible ambient conditions must be complied with. The information in the relevant documentation must be observed.

Trademarks All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.

Disclaimer of Liability We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions.

Page 4: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual, 04/2018, A5E36104399-AB 3

Preface

Preface

Purpose of the documentation This manual supplements the ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293) system manual.

Functions that generally relate to the system are described in this manual.

The information provided in this manual and in the system/function manuals supports you in commissioning the system.

Changes compared to the previous version Compared to the previous version, this manual contains the following changes:

Connection diagram has been updated

Technical specifications have been updated:

Comments on the previous version of this manual were included in the current edition.

Conventions CPU: When the term "CPU" is used in this manual, it applies to the CPUs of the S7-1500 automation system as well as to the CPUs/interface modules of the distributed I/O system ET 200SP.

STEP 7: In this documentation, "STEP 7" is used as a synonym for all versions of the configuration and programming software "STEP 7 (TIA Portal)".

Please also observe notes marked as follows:

Note

A note contains important information on the product described in the documentation, on the handling of the product or on the section of the documentation to which particular attention should be paid.

Recycling and disposal For environmentally friendly recycling and disposal of your old equipment, contact a certified electronic waste disposal company and dispose of the equipment according to the applicable regulations in your country.

Page 5: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Preface

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) 4 Manual, 04/2018, A5E36104399-AB

Security information Siemens provides products and solutions with industrial security functions that support the secure operation of plants, systems, machines and networks.

In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial security concept. Siemens' products and solutions constitute one element of such a concept.

Customers are responsible for preventing unauthorized access to their plants, systems, machines and networks. Such systems, machines and components should only be connected to an enterprise network or the internet if and to the extent such a connection is necessary and only when appropriate security measures (e.g. firewalls and/or network segmentation) are in place.

For additional information on industrial security measures that may be implemented, please visit (http://www.siemens.com/industrialsecurity).

Siemens' products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customers' exposure to cyber threats.

To stay informed about product updates, subscribe to the Siemens Industrial Security RSS Feed under (http://www.siemens.com/industrialsecurity).

Page 6: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual, 04/2018, A5E36104399-AB 5

Table of contents

Preface ................................................................................................................................................... 3

1 Documentation guide .............................................................................................................................. 6

2 Product overview .................................................................................................................................. 11

2.1 Properties ................................................................................................................................ 11

3 Wiring ................................................................................................................................................... 14

3.1 Wiring and block diagram ....................................................................................................... 14

4 Parameters/address space ................................................................................................................... 16

4.1 Measurement types and measuring ranges ........................................................................... 16

4.2 Parameters ............................................................................................................................. 17

4.3 Description of parameters ....................................................................................................... 19

4.4 Address space ........................................................................................................................ 22

5 Interrupts/diagnostics alarms ................................................................................................................. 23

5.1 Status and error displays ........................................................................................................ 23

5.2 Interrupts ................................................................................................................................. 25

5.3 Diagnostics alarms .................................................................................................................. 26

6 Technical specifications ........................................................................................................................ 27

6.1 Technical specifications .......................................................................................................... 27

A Parameter data record .......................................................................................................................... 31

A.1 Dependencies when configuring with GSD file ....................................................................... 31

A.2 Parameter assignment and structure of the parameter data record ....................................... 32

B Representation of analog values ........................................................................................................... 36

B.1 Representation of analog values for analog inputs ................................................................ 36

B.2 Representation of input ranges ............................................................................................... 37

B.3 Representation of analog values in the current measuring ranges ........................................ 38

Page 7: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) 6 Manual, 04/2018, A5E36104399-AB

Documentation guide 1

The documentation for the SIMATIC ET 200SP distributed I/O system is arranged into three areas. This arrangement enables you to access the specific content you require.

Basic information

The system manual describes in detail the configuration, installation, wiring and commissioning of the SIMATIC ET 200SP. distributed I/O system. The STEP 7 online help supports you in the configuration and programming.

Device information

Product manuals contain a compact description of the module-specific information, such as properties, wiring diagrams, characteristics and technical specifications.

Page 8: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Documentation guide

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual, 04/2018, A5E36104399-AB 7

General information

The function manuals contain detailed descriptions on general topics regarding the SIMATIC ET 200SP distributed I/O system, e.g. diagnostics, communication, Web server, motion control and OPC UA.

You can download the documentation free of charge from the Internet (https://support.industry.siemens.com/cs/ww/en/view/109742709).

Changes and supplements to the manuals are documented in a Product Information.

You can download the product information free of charge from the Internet (https://support.industry.siemens.com/cs/us/en/view/73021864).

Manual Collection ET 200SP The Manual Collection contains the complete documentation on the SIMATIC ET 200SP distributed I/O system gathered together in one file.

You can find the Manual Collection on the Internet (http://support.automation.siemens.com/WW/view/en/84133942).

"mySupport" With "mySupport", your personal workspace, you make the most of your Industry Online Support.

In "mySupport" you can store filters, favorites and tags, request CAx data and put together your personal library in the Documentation area. Furthermore, your data is automatically filled into support requests and you always have an overview of your current requests.

You need to register once to use the full functionality of "mySupport".

You can find "mySupport" in the Internet (https://support.industry.siemens.com/My/ww/en).

"mySupport" - Documentation In the Documentation area of "mySupport", you have the possibility to combine complete manuals or parts of them to make your own manual. You can export the manual in PDF format or in an editable format.

You can find "mySupport" - Documentation in the Internet (http://support.industry.siemens.com/My/ww/en/documentation).

Page 9: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Documentation guide

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) 8 Manual, 04/2018, A5E36104399-AB

"mySupport" - CAx Data In the CAx Data area of "mySupport", you can have access the latest product data for your CAx or CAe system.

You configure your own download package with a few clicks.

In doing so you can select:

Product images, 2D dimension drawings, 3D models, internal circuit diagrams, EPLAN macro files

Manuals, characteristics, operating manuals, certificates

Product master data

You can find "mySupport" - CAx Data in the Internet (http://support.industry.siemens.com/my/ww/en/CAxOnline).

Application examples The application examples support you with various tools and examples for solving your automation tasks. Solutions are shown in interplay with multiple components in the system - separated from the focus in individual products.

You can find the application examples on the Internet (https://support.industry.siemens.com/sc/ww/en/sc/2054).

TIA Selection Tool With the TIA Selection Tool, you can select, configure and order devices for Totally Integrated Automation (TIA). This tool is the successor of the SIMATIC Selection Tool and combines the known configurators for automation technology into one tool. With the TIA Selection Tool, you can generate a complete order list from your product selection or product configuration.

You can find the TIA Selection Tool on the Internet (http://w3.siemens.com/mcms/topics/en/simatic/tia-selection-tool).

Page 10: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Documentation guide

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual, 04/2018, A5E36104399-AB 9

SIMATIC Automation Tool You can use the SIMATIC Automation Tool to run commissioning and maintenance activities simultaneously on various SIMATIC S7 stations as a bulk operation independently of the TIA Portal.

The SIMATIC Automation Tool provides a multitude of functions:

Scanning of a PROFINET/Ethernet network and identification of all connected CPUs

Address assignment (IP, subnet, gateway) and station name (PROFINET device) to a CPU

Transfer of the data and the programming device/PC time converted to UTC time to the module

Program download to CPU

Operating mode switchover RUN/STOP

Localization of the CPU by means of LED flashing

Reading out CPU error information

Reading the CPU diagnostic buffer

Reset to factory settings

Updating the firmware of the CPU and connected modules

You can find the SIMATIC Automation Tool on the Internet (https://support.industry.siemens.com/cs/ww/en/view/98161300).

PRONETA With SIEMENS PRONETA (PROFINET network analysis), you analyze the plant network during commissioning. PRONETA features two core functions:

The topology overview independently scans PROFINET and all connected components.

The IO check is a fast test of the wiring and the module configuration of a system.

You can find SIEMENS PRONETA on the Internet (https://support.industry.siemens.com/cs/ww/en/view/67460624).

Page 11: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Documentation guide

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) 10 Manual, 04/2018, A5E36104399-AB

SINETPLAN SINETPLAN, the Siemens Network Planner, supports you in planning automation systems and networks based on PROFINET. The tool facilitates professional and predictive dimensioning of your PROFINET installation as early as in the planning stage. In addition, SINETPLAN supports you during network optimization and helps you to exploit network resources optimally and to plan reserves. This helps to prevent problems in commissioning or failures during productive operation even in advance of a planned operation. This increases the availability of the production plant and helps improve operational safety.

The advantages at a glance

Network optimization thanks to port-specific calculation of the network load

Increased production availability thanks to online scan and verification of existing systems

Transparency before commissioning through importing and simulation of existing STEP 7 projects

Efficiency through securing existing investments in the long term and optimal exploitation of resources

You can find SINETPLAN on the Internet (https://www.siemens.com/sinetplan).

Page 12: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual, 04/2018, A5E36104399-AB 11

Product overview 2 2.1 Properties

Article number 6ES7134-6GB00-0BA1

View of the module

① Module type and name ⑦ Function class ② LED for diagnostics ⑧ Color coding module type ③ 2D matrix code ⑨ Function and firmware version ④ Wiring diagram ⑩ Color code for selecting the color identification

labels ⑤ LEDs for channel status ⑪ BU type ⑥ LED for supply voltage ⑫ Article number

Figure 2-1 View of the module AI 2×I 2-/4-wire ST

Page 13: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Product overview 2.1 Properties

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) 12 Manual, 04/2018, A5E36104399-AB

Properties The module has the following technical properties:

Analog input module with 2 inputs

Measuring type current for 2- and 4-wire transducers

Input ranges for current measurement:

– 0 mA to 20 mA, resolution 15 bits

– 4 to 20 mA, resolution 15 bits

– ± 20 mA, resolution 16 bit incl. sign

Electrically isolated from supply voltage L+

Permitted common mode voltage: 10 Vpp/3.5 Vrms

Configurable diagnostics (per module)

Constant cycle time for processing measured values

– 500 μs, regardless of the number of channels used and the configuration

The module supports the following functions:

Table 2- 1 Version dependencies of the functions

Function

HW version FW version STEP 7 GSD file TIA Portal V5.x PROFINET IO PROFIBUS DP

Firmware update FS01 V1.0.0 or higher

V13 SP1 or higher

as of V5.5 SP4 with HSP 0227 V6.0 or higher

X X

Identification data I&M0 to I&M3

FS01 V1.0.0 or higher

V13 SP1 or higher

as of V5.5 SP4 with HSP 0227 V6.0 or higher

X X

Configuration in RUN FS01 V1.0.0 or higher

V13 SP1 or higher

as of V5.5 SP4 with HSP 0227 V6.0 or higher

X X

Value status FS01 V1.0.0 or higher

V13 SP1 or higher

as of V5.5 SP4 with HSP 0227 V6.0 or higher

X

PROFIenergy FS01 V1.0.0 or higher

V13 SP1 or higher

as of V5.5 SP4 with HSP 0227 V6.0 or higher

X X

You can configure the module with STEP 7 and with GSD file.

Page 14: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Product overview 2.1 Properties

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual, 04/2018, A5E36104399-AB 13

Accessories The following accessories must be ordered separately:

Labeling strips

Color identification labels

Reference identification label

Shield connector

See also You can find additional information on the accessories in the ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293) system manual.

Page 15: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) 14 Manual, 04/2018, A5E36104399-AB

Wiring 3 3.1 Wiring and block diagram

This section includes the block diagram of the AI 2xI 2-/4-wire ST module with the various terminal assignments for a 2- und 4-wire connection.

You can find information on wiring the BaseUnit in the ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293) system manual.

Note

You can use and combine the different wiring options for all channels.

Note

The load group of the module must begin with a light-colored BaseUnit. Keep this in mind also during the configuration.

Page 16: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Wiring 3.1 Wiring and block diagram

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual, 04/2018, A5E36104399-AB 15

Wiring: Current measurement 2-wire and 4-wire connection (2-wire and 4-wire transducer) The following figure shows the block diagram and an example of the terminal assignment of the analog input module AI 2xI 2-/4-wire ST on the BaseUnit BU type A0/A1.

① 2-wire connection for current measurement (2-wire

transducer) In+ Current input positive, channel n

② 4-wire connection for current measurement (4-wire transducer)

In- Current input negative, channel n

③ Backplane bus interface 1UVn Supply voltage (2-wire transducer), channel n ④ Analog-to-digital converter (ADC) 2UVn Supply voltage (4-wire transducer), channel n ⑤ Current limitation 2Mn Reference potential (4-wire transducer) ⑥ Switchover 2-wire / 4-wire RES Reserve, must remain unused for future function

extensions ⑦ Color-coded label with color code CC05 (optional) L+ 24 V DC (infeed only with light-colored BaseUnit) ⑧ Temperature recording for BU type A1 only (func-

tion cannot be used for this module) P1, P2, AUX Internal self-assembling voltage buses

Connection to left (dark-colored BaseUnit) Connection to left interrupted (light-colored BaseUnit)

⑨ Filter connection supply voltage (only when light-colored BaseUnit is present)

DIAG Diagnostics LED (green, red)

AI0, AI1 Channel status LED (green) PWR Power LED (green) Figure 3-1 Wiring and block diagram for current measurement 2-wire and 4-wire connection (2-wire and 4-wire

transducer)

Page 17: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual, 04/2018, A5E36104399-AB 16

Parameters/address space 4 4.1 Measurement types and measuring ranges

The analog input module AI 2×I 2-/4-wire ST has the following measuring ranges:

Table 4- 1 Measuring ranges

Measurement type Measuring range Resolution Current (2-wire transducer) 0 to 20 mA

4 mA to 20 mA 15 bits 15 bits

Current (4-wire transducer) 0 mA to 20 mA 4 mA to 20 mA ± 20 mA

15 bit 15 bits 16 bits incl. sign

You can find the tables of measuring ranges and overflow, overrange, etc. in the section Representation of analog values in the current measuring ranges (Page 38) and the "Analog value processing" function manual.

Page 18: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Parameters/address space 4.2 Parameters

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual, 04/2018, A5E36104399-AB 17

4.2 Parameters

Parameters of AI 2xI 2-/4-wire ST During configuration of the module with STEP 7, define the properties of the module via various parameters. The following table lists the configurable parameters. The effective range of the configurable parameters depends on the type of configuration. The following configurations are possible:

Central operation with an ET 200SP CPU

Distributed operation on PROFINET IO in an ET 200SP system

Distributed operation on PROFIBUS DP in an ET 200SP system

When assigning parameters in the user program, use the "WRREC" instruction to transfer the parameters to the module using the data records; refer to section Parameter assignment and structure of the parameter data record (Page 32).

The following parameter settings are possible:

Table 4- 2 Configurable parameters and their defaults (GSD file)

Parameter Range of values Default Configuration in RUN

Effective range with configuration software, e.g. STEP 7 (TIA Portal)

GSD file PROFINET IO

GSD file PROFIBUS DP

Diagnostics: No supply voltage L+

• Disable • Enable

Disable Yes Channel Channel

Diagnostics: Short-circuit to ground

• Disable • Enable

Disable Yes Channel Channel

Diagnostics: Overflow 1

• Disable • Enable

Disable Yes Channel Channel 1

Diagnostics: Underflow 1

• Disable • Enable

Disable Yes Channel

Diagnostics: Wire break

• Disable • Enable

Disable Yes Channel Channel

Page 19: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Parameters/address space 4.2 Parameters

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) 18 Manual, 04/2018, A5E36104399-AB

Parameter Range of values Default Configuration in RUN

Effective range with configuration software, e.g. STEP 7 (TIA Portal)

GSD file PROFINET IO

GSD file PROFIBUS DP

Measurement type/measuring range

• Deactivated • Current (4-wire trans-

ducer) 0 to 20 mA • Current (4-wire trans-

ducer) 4 to 20 mA • Current (4-wire trans-

ducer) +/- 20 mA • Current (2-wire trans-

ducer) 0 to 20 mA • Current (2-wire trans-

ducer) 4 to 20 mA

Current (4-wire trans-ducer) 4 to 20 mA

Yes Channel Channel

Smoothing • None • Weak • Medium • Strong

None Yes Channel Channel

Interference fre-quency suppression 2

• 60 Hz (50 ms) • 50 Hz (60 ms) 3 • 16.6 Hz (180 ms) • None

• 50 Hz (60 ms)

Yes Channel Module

Potential group • Use potential group of the left module (mod-ule plugged into a dark-colored BaseUnit)

• Enable new potential group (module plugged into light-colored BaseUnit)

Use potential group of the left module

No Module Module

1 Due to the limited number of parameters at a maximum of 244 bytes per ET 200SP station with a PROFIBUS GSD configuration, the configuration options are restricted. The parameter length of the I/O module is 4 bytes for PROFIBUS GSD configuration. If necessary, you can set this parameter by using the data record 128, see the appendix "Parameter data record".

2 The settings in the "Interference frequency suppression" parameter have a direct effect on the conversion time of the channel. The analog value is therefore also affected by additionally set filtering via the "Smoothing" parameter.

3 Interference frequency suppression: Noise at 400 Hz is automatically included in the filtering at 50 Hz.

Page 20: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Parameters/address space 4.3 Description of parameters

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual, 04/2018, A5E36104399-AB 19

Note Unused channels

"Deactivate" the unused channels in the parameter assignment.

A deactivated channel always returns the value 7FFFH.

4.3 Description of parameters

Diagnostics: No supply voltage L+ Enabling of the diagnostics alarm for no or insufficient supply voltage L+.

Diagnostics: Short-circuit to ground Enabling of the diagnostics in the event of a short-circuit of the encoder supply to ground or of an input to the encoder supply.

The short-circuit and underflow diagnostics can be activated simultaneously. If both diagnostics events occur simultaneously, the short-circuit diagnostics is output.

Diagnostics: Overflow Enabling of the diagnostics when the measured value exceeds the overrange.

Diagnostics: Underflow Enabling of the diagnostics when the measured value falls below the underrange.

Diagnostics: Wire break Enabling of the diagnostics if the module has no current flow or has too little current for the measurement in the range of 4 mA to 20 mA.

The wire break and underflow diagnostics can be activated simultaneously. If both diagnostics events occur simultaneously, the wire break diagnostics is output.

Measurement type/measuring range See the section Measurement types and measuring ranges (Page 16).

Page 21: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Parameters/address space 4.3 Description of parameters

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) 20 Manual, 04/2018, A5E36104399-AB

Smoothing The individual measured values are smoothed by filtering. The smoothing can be set in 4 levels.

Smoothing time = Number of conversion cycles (k) x conversion time (≙ of the integration time set in the "Interference frequency suppression" parameter) of the channel.

The following figure shows how many conversion cycles it takes for the smoothed analog value to approach 100%, depending on the configured smoothing. This applies to every signal change at the analog input.

① No smoothing ② Weak (k = 4) ③ Medium (k = 8) ④ Strong (k = 16)

Figure 4-1 Smoothing for AI 2×I 2-/4-wire ST

Interference frequency suppression Suppresses the interference affecting analog input modules that is caused by the frequency of the AC voltage network used.

The frequency of the AC voltage network can negatively affect the measured value, in particular when measuring in the low voltage range and with thermocouples. With this parameter, the user specifies the line frequency that is predominant in the plant.

Note:

The interference frequency suppression works parallel to the sampling of channels 0 and 1. The cycle time of the module is 500 μs regardless of the number of channels used and the configured interference frequency suppression.

Page 22: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Parameters/address space 4.3 Description of parameters

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual, 04/2018, A5E36104399-AB 21

Potential group A potential group consists of a group of directly adjacent I/O modules within an ET 200SP station, which are supplied via a common supply voltage.

A potential group begins with a light-colored BaseUnit through which the required voltage is supplied for all modules of the potential group. The light-colored BaseUnit interrupts the three self-assembling voltage buses P1, P2 and AUX to the left neighbor.

All additional I/O modules of this potential group are plugged into dark-colored BaseUnits. You take the potential of the self-assembling voltage buses P1, P2 and AUX from the left neighbor.

A potential group ends with the dark-colored BaseUnit, which follows a light-colored BaseUnit or server module in the station configuration.

See also You can find additional information in the system manual ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293).

Page 23: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Parameters/address space 4.4 Address space

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) 22 Manual, 04/2018, A5E36104399-AB

4.4 Address space

Configuration options The following configurations are possible:

Configuration 1: Without value status

Configuration 2: With value status

Evaluating the value status If you enable the value status for the analog module, an additional byte is occupied in the input address space. Bits 0 to 1 in this byte are assigned to a channel. They provide information about the validity of the analog value.

Bit = 1: There are no errors on the module.

Bit = 0: Channel is deactivated or there is a fault on the module.

If a fault occurs on a channel with this module, the value status for all channels is 0.

Address space The following figure shows the assignment of the address space for the AI 2xI 2-/4-wire ST with value status (Quality Information (QI)). The addresses for the value status are only available if the value status is enabled.

Figure 4-2 Address space of the AI 2xI 2-/4-wire ST with value status

Page 24: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) 23 Manual, 04/2018, A5E36104399-AB

Interrupts/diagnostics alarms 5 5.1 Status and error displays

LED displays The following figure shows you the LED display of the AI 2×I 2-/4-wire ST.

① DIAG (green/red) ② Channel status (green) ③ PWR (green)

Figure 5-1 LED displays

Page 25: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Interrupts/diagnostics alarms 5.1 Status and error displays

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) 24 Manual, 04/2018, A5E36104399-AB

Meaning of the LEDs The following tables show the meaning of the status and error displays. Corrective measures for diagnostics alarms can be found in section Diagnostics alarms (Page 26).

DIAG LED

Table 5- 1 Error display of the DIAG LED

DIAG Meaning

Off

Backplane bus supply of the ET 200SP not OK

Flashes

Module parameters not assigned

On

Module parameters assigned and no module diagnostics

Flashes

Module parameters assigned and module diagnostics

Channel status LED

Table 5- 2 Status display of the channel status LED

Channel status Meaning

Off

Channel disabled

On

Channel activated

PWR LED

Table 5- 3 Status display of the PWR LED

PWR Meaning

Off

Missing supply voltage L+

On

Supply voltage L+ present

Page 26: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Interrupts/diagnostics alarms 5.2 Interrupts

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual, 04/2018, A5E36104399-AB 25

5.2 Interrupts The AI 2×I 2-/4-wire ST analog input module supports diagnostics interrupts.

Diagnostics interrupts The module generates a diagnostic interrupt at the following events:

Short-circuit (encoder supply)

Wire break (current 4 to 20 mA)

High limit violated

Low limit violated

Error

Parameter assignment error

Supply voltage missing

Channel temporarily unavailable

Page 27: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Interrupts/diagnostics alarms 5.3 Diagnostics alarms

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) 26 Manual, 04/2018, A5E36104399-AB

5.3 Diagnostics alarms A diagnostics alarm is generated and the DIAG-LED flashes on the module for each diagnostics event. You can read out the diagnostics alarms, for example, in the diagnostics buffer of the CPU. You can evaluate the error codes with the user program.

Table 5- 4 Diagnostics alarms, their meaning and corrective measures

Diagnostics alarm Error code Meaning Solution Short-circuit (encoder supply) 1

1H Encoder supply to ground Correct interplay between module and encoder Input after encoder supply

Wire break (current 4 to 20 mA)

6H Impedance of encoder circuit too high Use a different encoder type or modify the wiring, e.g. use cables with larger cross-section

Wire break between the module and sen-sor

Connect the cable

Channel not connected (open) • Deactivate channel • Connect the encoder contacts

High limit violated 7H Value is above the overrange. Correct interplay between module and encoder

Low limit violated 8H Value is below the underrange. Correct interplay between module and encoder

Error 9H Internal module error has occurred (diag-nostics alarm on channel 0 applies for the entire module).

Replace the module

Parameter assignment error

10H • The module cannot evaluate parame-ters for the channel.

• Incorrect parameter assignment.

Correct the parameter assignment (wire break diagnostics set only with the permitted measuring ranges).

Supply voltage missing 11H Missing or insufficient supply voltage L+ • Check supply voltage L+ on the BaseUnit

• Check BaseUnit type

Channel temporarily unavailable

1FH Firmware update in progress or update has been canceled. The module does not read any process values in this state.

• Wait for firmware update. • Restart the firmware update.

1 Since the module has no encoder supply for separate channels, a short-circuit in a channel has a permanent effect on the other channel.

Page 28: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) 27 Manual, 04/2018, A5E36104399-AB

Technical specifications 6 6.1 Technical specifications

Technical specifications of AI 2xI 2-/4-wire ST

Article number 6ES7134-6GB00-0BA1 General information

Product type designation AI 2xI 2-/4-wire ST Firmware version V1.0 • FW update possible Yes

usable BaseUnits BU type A0, A1 Color code for module-specific color identifica-tion plate

CC05

Product function • I&M data Yes; I&M0 to I&M3

• Measuring range scalable No

Engineering with • STEP 7 TIA Portal configurable/integrated

as of version V13 SP1

• STEP 7 configurable/integrated as of ver-sion

V5.5 SP3

• PROFIBUS as of GSD version/GSD revi-sion

GSD Revision 5

• PROFINET as of GSD version/GSD revi-sion

V2.3 / -

Operating mode • Oversampling No

• MSI No

CiR – Configuration in RUN Reparameterization possible in RUN Yes Calibration possible in RUN No

Supply voltage Rated value (DC) 24 V permissible range, lower limit (DC) 19.2 V permissible range, upper limit (DC) 28.8 V Reverse polarity protection Yes

Input current Current consumption, max. 45 mA; without sensor supply

Page 29: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Technical specifications 6.1 Technical specifications

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) 28 Manual, 04/2018, A5E36104399-AB

Article number 6ES7134-6GB00-0BA1 24 V encoder supply

• 24 V Yes

• Short-circuit protection Yes

• Output current, max. 50 mA; Total current for both channels (two-wire)

Additional 24 V encoder supply • 24 V Yes

• Short-circuit protection Yes; Module-wise

• Output current, max. 200 mA; Total current for both channels (four-wire)

Power loss Power loss, typ. 1.1 W

Address area Address space per module

• Address space per module, max. 4 byte; + 1 byte for QI information

Analog inputs Number of analog inputs 2 • For current measurement 2

permissible input current for current input (de-struction limit), max.

50 mA

Cycle time (all channels), min. 500 µs Input ranges (rated values), currents

• 0 to 20 mA Yes; 15 bit

• Input resistance (0 to 20 mA) 130 Ω; 90 ohms with two wires

• -20 mA to +20 mA Yes; 16 bit incl. sign

• Input resistance (-20 mA to +20 mA) 130 Ω

• 4 mA to 20 mA Yes; 15 bit

• Input resistance (4 mA to 20 mA) 130 Ω; 90 ohms with two wires

Cable length • shielded, max. 1 000 m

Analog value generation for the inputs Measurement principle Sigma Delta

Integration and conversion time/resolution per channel

• Resolution with overrange (bit including sign), max.

16 bit

• Integration time, parameterizable Yes

• Interference voltage suppression for inter-ference frequency f1 in Hz

16.6 / 50 / 60 Hz / off

Page 30: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Technical specifications 6.1 Technical specifications

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual, 04/2018, A5E36104399-AB 29

Article number 6ES7134-6GB00-0BA1 Smoothing of measured values

• Number of smoothing levels 4

• parameterizable Yes

• Step: None Yes; 1x conversion time

• Step: low Yes; 4x conversion time

• Step: Medium Yes; 8x conversion time

• Step: High Yes; 16x conversion time

Encoder Connection of signal encoders

• for current measurement as 2-wire trans-ducer

Yes

– Burden of 2-wire transmitter, max. 650 Ω

• for current measurement as 4-wire trans-ducer

Yes

Errors/accuracies Linearity error (relative to input range), (+/-) 0.01 % Temperature error (relative to input range), (+/-)

0.005 %/K

Crosstalk between the inputs, min. -50 dB Repeat accuracy in steady state at 25 °C (rela-tive to input range), (+/-)

0.05 %

Operational error limit in overall temperature range

• Current, relative to input range, (+/-) 0.5 %

Basic error limit (operational limit at 25 °C) • Current, relative to input range, (+/-) 0.3 %

Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency

• Series mode interference (peak value of interference < rated value of input range), min.

70 dB

• Common mode voltage, max. 10 V

• Common mode interference, min. 90 dB

Isochronous mode Isochronous operation (application synchro-nized up to terminal)

No

Interrupts/diagnostics/status information Diagnostics function Yes

Page 31: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Technical specifications 6.1 Technical specifications

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) 30 Manual, 04/2018, A5E36104399-AB

Article number 6ES7134-6GB00-0BA1 Alarms

• Diagnostic alarm Yes

• Limit value alarm No

Diagnostic messages • Monitoring the supply voltage Yes

• Wire-break Yes; at 4 to 20 mA

• Short-circuit Yes; Short-circuit of the encoder supply

• Group error Yes

• Overflow/underflow Yes

Diagnostics indication LED • Monitoring of the supply voltage (PWR-

LED) Yes; green PWR LED

• Channel status display Yes; Green LED

• for channel diagnostics No

• for module diagnostics Yes; green/red DIAG LED

Potential separation Potential separation channels

• between the channels No

• between the channels and backplane bus Yes

• between the channels and the power sup-ply of the electronics

Yes

Permissible potential difference between the inputs (UCM) 10 Vpp

Isolation Isolation tested with 707 V DC (type test)

Dimensions Width 15 mm Height 73 mm Depth 58 mm

Weights Weight, approx. 32 g

Dimension drawing See manual ET 200SP BaseUnits (http://support.automation.siemens.com/WW/view/en/59753521)

Page 32: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) 31 Manual, 04/2018, A5E36104399-AB

Parameter data record A A.1 Dependencies when configuring with GSD file

When configuring the module with a GSD file, remember that the settings of some parameters are dependent on each other.

Configuring with a PROFINET GSD file The table lists the properties and their dependencies on the measurement type and measuring range for PROFINET.

Measurement type Measuring

range Diagnostics

No supply volt-age L+

Short-circuit to ground

Overflow Underflow Wire break

Deactivated * * * * * Current (4-wire transducer)

0 mA to 20 mA

x x x x -

4 mA to 20 mA

x x x x x

±20 mA x x x x - Current (2-wire transducer)

0 mA to 20 mA

x x x - -

4 mA to 20 mA

x x x x x

x = Property is allowed, - = Property is not allowed, * = Property is not relevant

Configuring with a PROFIBUS GSD file The table lists the properties and their dependencies on the measurement type and measuring range for PROFIBUS.

Measurement type Measuring

range Diagnostics

No supply voltage L+

Short-circuit to ground

Overflow/underflow Wire break

Deactivated * * * * Current (4-wire transducer)

0 mA to 20 mA x x x - 4 mA to 20 mA x x x x +/- 20 mA x x x -

Current (2-wire transducer)

0 mA to 20 mA x x x - 4 mA to 20 mA x x x x

x = Property is allowed, - = Property is not allowed, * = Property is not relevant

Page 33: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Parameter data record A.2 Parameter assignment and structure of the parameter data record

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) 32 Manual, 04/2018, A5E36104399-AB

A.2 Parameter assignment and structure of the parameter data record

Parameter assignment in the user program You can reassign the module parameters in RUN. For example, the voltage or current values of selected channels can be changed in RUN without having an effect on the other channels.

Changing parameters in RUN The "WRREC" instruction is used to transfer the parameters to the module using data record 128. The parameters set in STEP 7 are not changed in the CPU, which means that the parameters set in STEP 7 will be valid again after a restart.

Output parameter STATUS The module ignores errors that occur during the transfer of parameters with the "WRREC" instruction and continues operation with the previous parameter assignment. The STATUS output parameter contains a corresponding error code.

You will find a description of the "WRREC" instruction and the error codes in the STEP 7 online help.

Structure of data record 128 for entire module

Note

Channel 0 includes the diagnostics enable for the entire module.

Figure A-1 Structure of data record 128 for entire module

Page 34: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Parameter data record A.2 Parameter assignment and structure of the parameter data record

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual, 04/2018, A5E36104399-AB 33

Header information The figure below shows the structure of the header information.

Figure A-2 Header information

Parameters The following figure shows the structure of the parameters for channels 0 and 1.

You enable a parameter by setting the corresponding bit to "1".

Page 35: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Parameter data record A.2 Parameter assignment and structure of the parameter data record

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) 34 Manual, 04/2018, A5E36104399-AB

Figure A-3 Structure of bytes x to x+17 for channels 0 and 1

Codes for measurement types The following table contains the codes for the measuring types of the analog input module. You must enter these codes in byte x (see channel parameter block figure).

Table A- 1 Codes for measurement types

Measurement type Code Deactivated 0000 0000 Current, 4-wire transducer 0000 0010 Current, 2-wire transducer 0000 0011

Codes for measuring ranges The following table contains the codes for the measuring ranges of the analog input module. You must enter these codes in byte x+1 (see channel parameter block figure).

Table A- 2 Codes for measuring ranges

Measuring range Coding Current 0 mA to 20 mA 4 mA to 20 mA ±20 mA

0000 0010 0000 0011 0000 0100

Page 36: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Parameter data record A.2 Parameter assignment and structure of the parameter data record

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual, 04/2018, A5E36104399-AB 35

Error transmitting the data record The module always checks all values of the transmitted data record. The module applies the values from the data record only when all values have been transmitted without errors.

The WRREC instruction for writing data records returns the appropriate error codes if there are errors in the STATUS parameter.

The following table shows the module-specific error codes and their meaning for parameter data record 128.

Error code in the STATUS pa-

rameter (hexadecimal)

Meaning Solution

Byte 0 Byte 1 Byte 2 Byte 3 DF 80 B0 xx Number of the data record unknown Enter valid number for data record. DF 80 B1 xx Length of the data record incorrect Enter valid value for data record length. DF 80 B2 xx Slot invalid or unavailable • Check the station to determine if the

module is plugged in or pulled. • Check assigned values for the parame-

ters of the WREC instruction.

DF 80 I0 xx Incorrect version or error in the header information

Correct the version, length and number of parameter blocks.

DF 80 I1 xx Parameter error Check the parameters of the module.

Page 37: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual, 04/2018, A5E36104399-AB 36

Representation of analog values B B.1 Representation of analog values for analog inputs

This appendix shows the analog values for all measuring ranges that you can use with the analog module.

Measured value resolution The resolution of the analog values differs depending on the analog module and its parameter assignment.

The table below shows the representation of binary analog values and of the associated decimal and hexadecimal units of the analog values.

Each analog value is written left aligned to the tags. The bits marked with "x" are set to "0".

Table B- 1 Resolution of the analog values

Resolution in bits including sign

Values Analog value

Decimal Hexadecimal High byte Low byte 15 2 2H Sign 0 0 0 0 0 0 0 0 0 0 0 0 0 1 x 16 1 1H Sign 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1

Page 38: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Representation of analog values B.2 Representation of input ranges

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual, 04/2018, A5E36104399-AB 37

B.2 Representation of input ranges In the following tables, you can find the digitized representation of the bipolar and unipolar input ranges. The resolution is 16 bits.

Table B- 2 Bipolar input ranges

Dec. value

Measured value in %

Data word Range

215 214 213 212 211 210 29 28 27 26 25 24 23 22 21 20 32767 >117.589 0 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Overflow 32511 117.589 0 1 1 1 1 1 1 0 1 1 1 1 1 1 1 1 Overrange 27649 100.004 0 1 1 0 1 1 0 0 0 0 0 0 0 0 0 1 27648 100.000 0 1 1 0 1 1 0 0 0 0 0 0 0 0 0 0

Nominal range

1 0.003617 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0.000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 -1 -0.003617 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 -27648 -100.000 1 0 0 1 0 1 0 0 0 0 0 0 0 0 0 0 -27649 -100.004 1 0 0 1 0 0 1 1 1 1 1 1 1 1 1 1 Underrange -32512 -117.593 1 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 -32768 <-117.593 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Underflow

Table B- 3 Unipolar input ranges

Dec. value

Measured value in %

Data word Range

215 214 213 212 211 210 29 28 27 26 25 24 23 22 21 20 32767 >117.589 0 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Overflow 32511 117.589 0 1 1 1 1 1 1 0 1 1 1 1 1 1 1 1 Overrange 27649 100.004 0 1 1 0 1 1 0 0 0 0 0 0 0 0 0 1 27648 100.000 0 1 1 0 1 1 0 0 0 0 0 0 0 0 0 0 Nominal

range 1 0.003617 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0.000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 -1 -0.003617 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Underrange -4864 -17.593 1 1 1 0 1 1 0 1 0 0 0 0 0 0 0 0 -32768 <-17.593 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Underflow

Page 39: Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) · SIMATIC ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Manual 04/2018 A5E36104399-AB Preface Documentation

Representation of analog values B.3 Representation of analog values in the current measuring ranges

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) 38 Manual, 04/2018, A5E36104399-AB

B.3 Representation of analog values in the current measuring ranges The following tables list the decimal and hexadecimal values (codes) of the possible current measuring ranges.

Table B- 4 Current measuring range ±20 mA

Values Current measuring range Range Dec. Hex. ±20 mA 32767 7FFF > 23.52 mA Overflow 32511 7EFF 23.52 mA Overrange 27649 6C01 27648 6C00 20 mA Nominal range 20736 5100 15 mA 1 1 723.4 nA 0 0 0 mA -1 FFFF -20736 AF00 -15 mA -27648 9400 -20 mA -27649 93FF Underrange -32512 8100 -23.52 mA -32768 8000 < -23.52 mA Underflow

Table B- 5 Current measuring ranges 0 to 20 mA and 4 to 20 mA

Values Current measuring range Range Dec. Hex. 0 to 20 mA* 4 to 20 mA 32767 7FFF > 23.52 mA > 22.81 mA Overflow 32511 7EFF 23.52 mA 22.81 mA Overrange 27649 6C01 27648 6C00 20 mA 20 mA Nominal range 20736 5100 15 mA 16 mA 1 1 723.4 nA 4 mA + 578.7 nA 0 0 0 mA 4 mA -1 FFFF Underrange -4864 ED00 -3.52 mA 1.185 mA -32768 8000 < -3.52 mA < 1.185 mA Underflow * For measurement type "2-wire transducer", negative values are not possible for the range "0 to

20 mA". Therefore, no underrange or underflow exists here.