An Application for Upgrading the Reliability of Electrical System in an Industrial Plant

  • Upload
    yxp2237

  • View
    221

  • Download
    0

Embed Size (px)

Citation preview

  • 8/3/2019 An Application for Upgrading the Reliability of Electrical System in an Industrial Plant

    1/5

    The Online Journal on Electronics and Electrical Engineering (OJEEE) Vol. (3) No. (3)

    Reference Number: W11-0068 443

    An Application For Upgrading The Reliability

    of Electrical System in An Industrial Plant

    H. Can

    Tupras Izmit Refinery, Project Department, Kocaeli, Turkey

    Dr. C. Perdahci

    Department of Electrical Engineering, Kocaeli University, Kocaeli, Turkey

    Abstract-In this paper, respectively, the requirement for

    digital protection relays, current status of the industrial

    plants, protective functions of digital protection relays,

    relay types, electrical equipments and remote monitoring

    relays were examined in an industrial plants. A large-scale

    industrial plants must be robust to operate efficiently and

    without interruption of power network. Unreliable

    electrical network can cause unexpected power

    interruptions. Interruptions will damage to operate the

    plants and these may also cause significant financial loses.

    To make reliable electrical system of the plants, provides

    important advantages in terms of operation and

    maintenance. In industrial plants examined for this

    purpose to establish the digital protection relays and

    power relays with the method of monitoring via SCADA

    system to increase the reliability of an application is

    examined.

    Keywords-Protection relays, reliability

    I. INTRODUCTION

    Today one of the most important factors which ensure that

    industrial plants have sustainable production is uninterrupted

    and high-quality provision of power to the plant. Ill-timed

    power failures due to the own structure of the facility and

    national network of which it is a part have significant impact

    on the production of facility. The power failures also have

    significant financial losses. Therefore the less power failures,

    the less financial losses there will be.

    Another reason of the significant of power failures is that

    the interruption experienced during operation can damage

    equipment and due to this damage they can be completely

    non-operable and in need of repair. If there is no replacementfor the equipment at the facility, the damage can be

    multiplied.

    Parallel to the experienced technological developments,

    large industrial facilities renew their infrastructures so as to

    improve the reliability of their electrical systems (1). One of

    the best-known methods is to install digital protective relays

    on engines, transformers and entry-exit coupling cells and

    corrections of failures at minimum location at minimum time.

    At large industrial facilities which have protective functions

    assigned to digital protective relays, as well as different

    voltage levels and a widespread distribution infrastructure,

    high-level of protection can be provided with properselectivity efforts; however, failure and measurement data of

    these equipment are transferred to SCADA system at main

    focus and they can be used in an effective manner; it also

    helps optimize the reliability of the facility. In addition, with

    the failure record data obtained from relays, the failure

    characteristic of the equipment can be generated and potential

    failure risks can be estimated for the future [2].

    In the industrial facility, which is the reference of thisstudy, protective equipment have been used since its

    foundation which have the highest technology. However, there

    are no digital protective relays in several engines,

    transformers, entry-exit and coupling cells of the facility. This

    application covers replacement of current mechanical relays

    with digital protective relays and installation of digital

    protective relays to those which had no relays on.

    II ELECTRICAL SYSTEM of THE FACILITY

    Electricity production capacity of the plant is 85MW and

    maximum consumption is 57MW; it also has an auto-producer

    license. The facility can satisfy all or part of its own electrical

    power need from its production; it can also provide theelectrical power needed from outside as it is connected to the

    interconnected network. The purpose of the facility in

    producing its own electricity is to create alternatives for

    meetings its electricity need rather than selling it to third

    parties. As can be understood from the single line graphic of

    the facility, all busbars have two supplies. The power is being

    distributed to three secondary distribution stations at 11kV

    and 3.3kV voltage levels from closed switch station. These 6

    secondary distribution stations distribute to 14 secondary

    stations. The voltage levels of secondary distribution stations

    are 11kV or 3.3kV. There are digital protective relays at

    engine, transformer, entry-exit or coupling cells; however

    these relays have been established at different times and with

    different models since the foundation of the facility [3].

    1. Current busbars and protective relays

    34,5kV, 11kV and 3,3kV distribution stations which

    constitute the distribution infrastructure of the facility are

    given in Table 1.

  • 8/3/2019 An Application for Upgrading the Reliability of Electrical System in an Industrial Plant

    2/5

    The Online Journal on Electronics and Electrical Engineering (OJEEE) Vol. (3) No. (3)

    Reference Number: W11-0068 444

    Distribution

    Stations

    Voltage

    Level

    Supplying

    Busbar1 9HS-1 34,5kV TEK-2

    2 9MMS-1 11kV 9HS-1

    3 9MMS-2 11kV 9HS-1

    4 9MMS-3 11kV 9HS-1

    5 10R-102A 3,3kV 9HS-1

    6 10R-6A 3,3kV 9HS-1

    7 10R-18A 3,3kV 9HS-1

    8 PLANT-5-6-7-8 3,3kV 9MMS-1

    9 PLANT-21-25-36 3,3kV 9MMS-1

    10 9MS-1 3,3kV 9MMS-1

    11 PLANT-6 3,3kV 9MS-1

    12 PLANT-73-74 3,3kV 10R-102A

    13 10R-102 3,3kV 10R-102A

    14 PLANT-33 3,3kV 10R-102A

    15 10R-6 3,3kV 10R-6A

    16 10R-8 3,3kV 10R-18A

    17 47MMS-1 11kV 9MMS-2

    18 47MS-1 3,3kV 47MMS-1

    19 10MS-1 3,3kV 9MMS-320 63MMS-1 11kV 9MMS-3

    21 63MS-1 3,3kV 63MMS-1

    Table 1 : Distribution Stations

    2. System equipment with digital protective relays

    installed

    Digital protective relays will be used for the purpose of

    protecting several equipment in the facility and improving the

    reliability of electrical system. These relays will be installed

    on engine feeders, transformer feeders, entry-exit and

    coupling cells [3].

    Digital protective relays will be installed on 10R-6 and10R-6A power switch building, 10R-102A power switch

    building, Plant 25-36 , Plant 5-6-7-8 , Plant 47-48 , Plant 26,

    Plant-33, Plt 9 and 34,5kV switch facility engine feeders,

    transformer feeders, entry-exit and coupling cells shown in

    Table 1 [2].

    Digital protective relays have been applied on more than

    200 medium-voltage system equipment; those installed on 47-

    48 unit are given in Table 2 [3]. 47-48 (Hydrocracker) unit

    constitutes one of the most important processes of the facility.

    PLANT 47/48 UNIT SWITCH ROOM

    CellNo Name Of TheEqupment Description of Equipment

    11 kV BUSBAR 47 MMS-1

    5L 9GM-601A 11kV 1200kW Pump Motor

    4L 47GM-2A 11kV 1550kW Pump Motor

    3L 47KM-2A

    11kV 3500kW Compressor

    Motor

    2L

    47TMM-1A

    Trafosu Fideri 11kV to 3,5kV 6,3MVA

    1L Incoming L INCOMING LEFT

    0 BUS TIE

    0 BUS RISER

    1R Incoming R INCOMING RIGHT

    2R

    47TMM-1B

    Transformer

    Feeder 11kV to 3,5kV 6,3MVA

    3R 47KM-2B

    11kV 3500kW Compressor

    Motor

    4R 47KM-2C

    11kV 3500kW Compressor

    Motor

    5R 47GM-2B 11kV 1550kW Pump Motor

    6R 9GM-601B 11kV 1200kW Pump Motor

    3,3 kV BUSBAR

    11L 47GM-4C 3,3kV 153kW Pump Motor

    9L 9KM-601E3,3kV 120kW CompressorMotor

    8L 9KM-601C

    3,3kV 120kW Compressor

    Motor

    7L 9KM-601A

    3,3kV 120kW Compressor

    Motor

    6L 47GM-302A 3,3kV 120kW Pump Motor

    5L 48KM-1A

    3,3kV 315kW Compressor

    Motor

    4L

    47TML-1C

    Transformer

    Feeder 3,3kV to 0,4kV 2MVA

    3L EMPTY

    2L

    47TML-1A

    Transformer

    Feeder 3,3kV to 0,4kV 2MVA

    1L Incoming L INCOMING LEFT

    0 BUS TIE

    0 BUS RISER

    1R Incoming R INCOMING RIGHT

    2R

    47TML-1B

    Transformer

    Feeder 3,3kV to 0,4kV 2MVA

    3R

    47TML-1D

    TransformerFeeder 3,3kV to 0,4kV 2MVA

  • 8/3/2019 An Application for Upgrading the Reliability of Electrical System in an Industrial Plant

    3/5

  • 8/3/2019 An Application for Upgrading the Reliability of Electrical System in an Industrial Plant

    4/5

    The Online Journal on Electronics and Electrical Engineering (OJEEE) Vol. (3) No. (3)

    Reference Number: W11-0068 446

    87M: Engine differential protection*

    *Engine differential protection is not compulsory;

    nevertheless, differential protection is recommended on

    engines higher than IMW power. Differential protections at

    powerful engines bigger than IMW at this facility have been

    enabled. Protection functions employed on transformers:

    49: Motor Thermal protection

    50, 50N: Instant opening

    51, 51N: Opening at overflow

    Inrush restraint (valid for 50,50N, 51, 51N, 67, 67N functions)

    74: Alarm

    74TC: Trip Circuit Supervision

    87T: Transformer Differential Protection*

    *at transformers of 5MVA and higher at the facility 49: used in relays at primary sides of thermal protection

    transformers; not enabled on relays at secondary side.

    The protection functions defined in digital protection relays

    installed on transformer feeders have been enabled and

    adjustment values have been given. 67, 67N: Directional

    Overflow Protections have been enabled as these generators

    exist at 11kV outlets of 34,5/ 11kV transformers in the

    facility; which means at facility entrances, and as it is not

    possible to feed from TEA and generators alike. In addition,

    32G, 32P: Inverse Power Protections are also enabled.

    Protection Functions used in the Generators: 27 : Low Voltage Protection

    32R: Diverse Power Protection

    46 : Current Protection for Negative Component Phase Balance

    49 : Thermal Protection

    50, 50N : Instant turn-on protection (Short circuit protection)

    51, 51N(51G) : Over-current protection (reverse time protection)

    59 : Over-Voltage Protection

    81 : Low / Excessive Frequency protection

    87G : Generator Differantial Protection (G Generator)

    3.1 Measurement with Digital Protection Relays

    As the digital protection relays to be used also have

    measurement functions, the demanded cells will also be

    measured. In addition to protection, which is their mainfunction, digital protective relays are able to measure the

    current, voltage and frequency values of the cells on which

    they are installed this cell can be an engine feeder,

    transformer feeder or entry-exit and coupling feeder. In

    addition, they can transmit these measured values to SCADA

    system, just like they transmit protection functions to SCADA

    system. As a result, in addition to their major function which

    is protection, these relays used within the Refinery Plant will

    transfer such values as the current voltage frequency of the

    equipment to which they are installed to the SCADA system

    to make the electrical system of the plant more traceable and

    reliable, as electrical systems which can be monitored are

    always more reliable. Measurements which will be made by

    relays are as follows: [2]

    Component values with symetry for voltages

    Voltages (VL1,VL2,VL3,VL1L2,VLL1L3,VL2L3)

    Current power, Reactive power, Visible power (Eachphase seperately and totally)

    Aktive and Reactive Energy

    Power Factor and Frequency

    Working hour gauge, breaker opener gauge

    Measuring of average operating temperature in case of

    overload

    IV. DIGITAL PROTECTION RELAYS USED

    A. Local-control multi-functional protective relay 7SJ64

    Digital, multi-functional SIPROTEC 4 7SJ64 relays are

    multi-faceted devices designed for protection, control and

    monitoring of busbar relays. These devices can be used as lineprotection in grounded, low-resistant grounded, non-rounded

    or compensated neutral point-structured networks. Devices

    are proper for radial, eyed or interconnected networks and

    single or multi-edged fed lines. 7SJ64 has been equipped with

    engine protection function which can be adjusted for every

    size of non-synchronize engines. 7SJ64 has necessary

    functions for command of breakers at1 breaker busbars or

    monitoring of protective, breaker positions and flat busbar

    applications. Therefore the device can be used universally.

    7SJ64 provides after-effect protective features for differential

    protective arrangements of the lines, transformers, generators,

    engines and busbars in all voltage levels.

    Protection of non-directional overflow is the basic function

    of the device. There are three fixed-time overflow protective

    elements and one inverse time overflow protective component

    for phase currents and ground current. Several curves at

    different standards are provided for inverse-time overflow

    protective elements.[5]

    B. Differential protective relay 7UT613

    SIPROTEC 4 7UT613 digital differential protection

    provides a fast and selective short circuit protection for

    transformers at all voltage levels, rotary machines, serial and

    shunt reactors or short lines and mini busbars consisting of 2

    to 5 feeders. In addition, it can also be used as a single-phaseprotection for busbars up to 9 or 12 feeders (depending on the

    version). Specific application can be customized which will

    ensure the most appropriate adaptation to the protected object.

    The major advantage of differential protection principle is

    that it can perform instant turn-on at a short circuit failure at

    any point within the protected area. The current transformers

    at the edges of protected object limits the protected area

    towards the network. This certain limit is the main reason for

    which the differential protection mechanism shows such an

    ideal selectivity. [6].

    1. Remote Monitoring of Digital Protective Relays

    All established protective relays will be monitored fromPower CC SCADA system which is installed in Plant-9. All

    trips, alarms, external data and analogue value signals will be

  • 8/3/2019 An Application for Upgrading the Reliability of Electrical System in an Industrial Plant

    5/5

    The Online Journal on Electronics and Electrical Engineering (OJEEE) Vol. (3) No. (3)

    Reference Number: W11-0068 447

    sent to Power CC scada system from these relays. Only the

    Power CC in Plant-9 will be controlled by SCADA system

    and switch will be opened and closed from there [2].

    V. CONCLUSION

    As a result of this paper which aimed at improving the

    reliability of current electrical system, the system has been

    made more reliable with the protection functions from which

    digital protective relays are entered. Protective functions have

    been parametered as required according to the type and

    importance of the equipment to which the relays are

    connected, and it has been ensured that the system makes less

    trips. In addition, remote monitoring of the system has

    allowed for receiving instant information from relays which

    turn on or give alarm and thus faster intervention.

    In this study, not only the electrical system of the plant hasbeen made more reliable, but the plant also enjoyed several

    advantages such as costing, operation and maintenance.

    REFERENCES

    [1] Xiaoqiang, Z., "Energy&Utilities Control System ofRefinery",2009 third International Symposium on

    Intelligent Information Technology Application, 2009,

    408-411

    [2] etinkaya, B, Akduman, B, Tpra Izmit Role

    Koordinasyon Raporu, Siemens A.S., Kocaeli, 2009

    [3] TUPRA General Project Design Specification P1,

    TUPRA, Kocaeli, 2006

    [4] Koruma Rolelerinin Fonksiyon Acklamalar, Siemens E

    E&C PTI, Istanbul, 2008

    [5] SIPROTEC 7SJ62/64 Kullanm Klavuzu C53000-

    G115A-C207-1, SIEMENS AG, Istanbul, 2009

    [6] SIPROTEC 7UT613/63x Kullanm Klavuzu V4.60,

    SIEMENS AG, Istanbul, 2006