Analogue Fire Alarm Control Panel
FireFinderTM
DUE TO AMPAC’S COMMITMENT TO CONTINUOUS
IMPROVEMENT, SPECIF ICATIONS MAY CHANGE
WITHOUT NOTICE
FOR A QUOTATION AND FURTHER INFORMATION, GO TO:
w w w . a m p a c . n e t32
FIRE A
LAR
MC
ON
TRO
LPA
NELS
• Programming via front panel – The menu driven LCD display helps the user to make changes to the system,quickly and efficiency.
• Programming with a notebook computer – allows theuser to program more complex functions. Typically toconfigure fan controls
• Remote upload/download of software – using a modemto upload or download software from remote site cutsdown travel time, increases productivity.
• Remote system interrogation – supports diagnosticchecks and interrogation to be executed from a remotelocation
• Password protection – there are four levels of access• Self Learn Capabilities – ability to interrogate the
configuration of an analogue and download thisinformation ready for immediate use
• Sensitivity adjustment – the 5 sensitivity adjustmentsallow the user to adapt the individual detectors to suitdifferent environments
• Day/Night sensitivity settings – the FACP can be set-upto change sensitivity at specific times
• Event logs – events are captured giving informationregarding alarms, faults and sources/disables.
• Manual Operation of all inputs/outputs via keypad– status of control inputs/outputs can be monitored and manually activated for testing
• Brigade output interrogation – provides a quick displayof the brigade board status
• Pre-alarm level available – pre-alarm levels of detectorsraised may be used for early warning.
• Digital voltage readout – battery voltage can bedisplayed on the LCD
• Readout of detector analogue count – the analoguevalue of the detector expressed in ‘counts’ may bedisplayed
• Printer connection capability – provides a hard copy ofall the activities on the panel
• Single Person Operation Test (S.P.O.T.) – allows detectortesting by a single person
• Network capabilities – expands the capabilities ofFireFinder™ to support Peer-to-Peer, Master/Sub FIP,Distributed FACP System, Colour Graphic Interface, andLCD Repeater Panel
• Multi-language support – has the capability to downloaddifferent fonts thus allowing display and print-out inselected language
• Information of service company displayed on LCDreadout – customise the LCD with your company detailswhen system is normal
• Approved to AS4428.1 & 5• Approved to NZS54512:1997• Complies with EN54 PT 1 & 4
The Ampac FireFinder™ Fire Alarm Control Panel is a product of extensive customer research and feedback – a user-friendly system that puts the operator in control. FireFinder™ operates with world-renowned smoke and thermal detectors, and ancillary devices. It can be configured to operate with both analogue and conventional devices in the one system. FireFinder™ features on-site programmability, and allows users to have remote access via a modem if required by utilising Ampac’s unique LineManager™ software.Leading edge tools are available to help you install and commission a FireFinder™ fire detection system, effectively and efficiently.FireFinder™ has been designed not just for today, but for the future and incorporates many features that can be enhanced over the life of the system if and when required.Network capabilities features available to FireFinder™include Peer-to-Peer configuration, Master/Sub FACP, Distributed Fire Detection System, SmartGraphics,Remote LED and LCD Repeater Panels.
FireFinder™
REFER TO DATA SHEET: AS4428 VERSION PDS8550-1100EN54 VERSION PDS112-0037NZS4512 VERSION PDS112-0011
Product Information
Features
Analogue Fire Alarm Control Panel
FireFinderTM (cont.)
DUE TO AMPAC’S COMMITMENT TO CONTINUOUS
IMPROVEMENT, SPECIF ICATIONS MAY CHANGE
WITHOUT NOTICE
FOR A QUOTATION AND FURTHER INFORMATION, GO TO:
w w w . a m p a c . n e t 33
FIRE A
LAR
MC
ON
TRO
LPA
NELS
Network Communications BusSub/Slave FACP
LCD RepeaterSmartGraphicsModem Interface
Main FACP
Addressable Loop
Sub/Slave FACP
Addressable Loop
Addressable Loop
Networked System
Convent ional / Analogue System
Analogue Detectors
Short-Circuit Isolator
Manual Call Point Single Input Device
24 VDC
Zone Interface Device
Three Input Device
EOL
EOL
EOL
EOL
Analogue Detectors
Short-Circuit Isolator
Conv
entio
nal Z
ones
Conventional Detectors
Addressable Loop
FireFinder™
FireFinder™ S P 1 X
FireFinder™ S P 8 X
MECHANICAL SPECIFICATIONS
Materials 1.2mm steelConstruction ModularCase Finish Arch White powder coatDimension SP1X 500H x 405W x 145D mm SP8X 840H x 515W x 170D mm SP16X 1200H x 625W x 240D mm 10U 700H x 625W x 240D mm 16U 1200H x 700W x 350D mm 29U 1800H x 700W x 350D mm SP1X Anc Cab 250H x 405W x 145D mm SP8X Anc Cab 418H x 515W x 170D mmWeight SP1X 10 kg
SP8X 20 kg SP16X 35 kg 10U 40 kg 16U 90 kg 29U 130 kg SP1X Anc Cab 3 kg SP8X Anc Cab 5 kg
TECHNICALPower SupplyMain Supply 85-264 VACOutput Voltage 27 VoltsQuiescent Current 450mA (min)Battery Capacity 12 Ah (min)
OUTPUTSBell 1 (monitored) Switched 24 VDC 2ABell 2 (monitored) Switched 24 VDC 2AAuxiliary (monitored) Switched 24 VDC 2AAuxiliary (unmonitored) Volt free 1A @ 24 VDCEWS (monitored) Switched 24 VDC 2AEWS (unmonitored) Volt free 1A @ 24 VDCFault Volt free 1A @ 24 VDCIsolate Volt free 1A @ 24 VDCAlarm Volt free 1A @ 24 VDCValve Monitor Volt free 1A @ 24 VDCBattery Fail Volt free 1A @ 24 VDC
INDICATORS
Alarm RedFault YellowIsolate YellowWarning System Isolate YellowExternal bell isolate YellowPower On GreenFire Alarm RedAuxiliary Alarm RedAIF Active YellowSupply Fault YellowEarth Fault YellowSystem Fault YellowTest Mode YellowWarning System Fault YellowFault output Isolate YellowAuxiliary Fault Isolate YellowOutput Delay Active Yellow
CONTROLS
Membrane type with acousticfeedbackAlpha-numeric keypadCursor controlMenu and function keys
Order Code Model Compliance Approved By8550-1100 SP1X 1Loop AS4428 AS4428.1&5 SSL8550-1200 SP1X 1Loop ASE AS4428 AS4428.1&5 SSL8550-1400 SP1X 1Loop EV20+Mic 5.6A AS4428 AS4428.1&5 SSL8550-1440 SP1X 1Loop EV40+Mic 5.6A AS4428 AS4428.1&5 SSL8550-4100 SP8X 1Loop 5.6A AS4428 AS4428.1&5 SSL8550-4200 SP8X 1Loop ASE 5.6A AS4428 AS4428.1&5 SSL8550-4400 SP8X 1Loop EV40+Mic 5.6A AS4428 AS4428.1&5 SSL8550-4470 SP8X 1Loop EV60+Mic 5.6A AS4428 AS4428.1&5 SSL8550-4490 SP8X 1Loop EV120+Mic 18A AS4428 AS4428.1&5 SSL8550-5100 SP16X 1Loop 5.6A AS4428 AS4428.1&5 SSL8550-6100 10U 1Loop 5.6A AS4428 AS4428.1&5 SSL8550-6200 16U 1Loop 5.6A AS4428 AS4428.1&5 SSL8550-6300 29U 1Loop 5.6A AS4428 AS4428.1&5 SSL8510-9003 SP1X Ancillary Cabinet8510-9010 SP8X Ancillary CabinetENC1798-F SP1X Surround158-0033 SP8X SurroundENC2844-F SP16X SurroundENC1797-F SP1X+Ancillary Cabinet Surround158-0027 SP8X+Ancillary Cabinet Surround
DUE TO AMPAC’S COMMITMENT TO CONTINUOUS
IMPROVEMENT, SPECIF ICATIONS MAY CHANGE
WITHOUT NOTICE
FOR A QUOTATION AND FURTHER INFORMATION, GO TO:
w w w . a m p a c . n e t34
FIRE A
LAR
MC
ON
TRO
LPA
NELS
AS4428 VERSION
Analogue Fire Alarm Control Panel
FireFinderTM (cont.)
MECHANICAL SPECIFICATIONS
Materials 1.2mm steelConstruction ModularCase Finish Arch White RippleDimension SP1 450H x 400W x 130D mm SP2 450H x 400W x 130D mm SP8 840H x 515W x 140D mmWeight SP1 10 kg SP2 10 kg SP8 20 kg
ELECTRICAL
Power SupplyMain Supply 85 to 264 VAC @ 47 to 63HzOutput Voltage 27 VDC
Max. Power Supply CurrentSP1 2.2 AmpsSP2 2.2 AmpsSP8 5.6 AmpsQuiescent Current 450 mA (min.)
Maximum Battery Capacity within panelSP1 12AhSP2 12AhSP8 24Ah
OUTPUTS
Sounder 1-1 Programmable MonitoredSwitched 24 VDC
Sounder 1-2 Programmable MonitoredSwitched 24 VDC
Sounder 2 Programmable MonitoredSwitched 24 VDC
Sounder 2 Unmonitored Voltage free 1A@ 24 VDC
F.A.R.E Fire Alarm Routing EquipmentF.W.R.E Fire Warning Routing EquipmentDisable RelayAlarm RelayValve Monitor RelayBattery Fail Relay
INDICATORS
Graphics based LCD 240 by 64 dotsFire RedFault AmberDisabled AmberSounder Disable YellowEvacuate YellowPower on GreenPre-Alarm RedTest Mode RedSounder fault disable YellowSupply Fault YellowEarth Fault YellowSystem Fault YellowF.W.R.E Active YellowF.A.R.E Active RedF.W.R.E. Fault/Disable YellowF.A.R.E Fault/Disable YellowOutput Delay Active Yellow
CONTROLS
Membrane type with acoustic feedbackAlpha-numeric KeypadCursor ControlMenu and function keys
FireFinder™ S P 1
FireFinder™ S P 2
Order Code Model Compliance
112-0016 FireFinder SP1 1 Loop (No Zone LED’s) EN54.1&4
112-0018 FireFinder SP2 1 Loop EN54.1&4
112-0019 FireFinder SP2 1 Loop c/w printer EN54.1&4
112-0029 FireFinder SP8 1 Loop EN54.1&4
112-0030 FireFinder SP8 2 Loop EN54.1&4
112-0031 FireFinder SP8 3 Loop EN54.1&4
112-0032 FireFinder SP8 4 Loop EN54.1&4
DUE TO AMPAC’S COMMITMENT TO CONTINUOUS
IMPROVEMENT, SPECIF ICATIONS MAY CHANGE
WITHOUT NOTICE
FOR A QUOTATION AND FURTHER INFORMATION, GO TO:
w w w . a m p a c . n e t 35
FIRE A
LAR
MC
ON
TRO
LPA
NELS
EN54 VERSION
Analogue Fire Alarm Control Panel
FireFinderTM (cont.)
PANEL ADD-ON MODULES
ORDER CODE DESCRIPTION
159-0001 FireFinder SP1X Even. No. Loop
159-0002 FireFinder SP16/Rack Even no. Loop
159-0003 FireFinder SP8X Odd No. Loop
159-0004 FireFinder SP16/Rack Odd no. Loop
159-0005 FireFinder SP8X 16 AZF Expansion Module
159-0006 FireFinder SP16/Rack 16 AZF Module
159-0007 FireFinder 128/128 I/O Module
159-0009 FireFinder SP16/Rack 16/16 I/O interconnection
159-0010 FireFinder SP8X 16 Opto Input
159-0011 FireFinder SP16/Rack 16 opto input
159-0013 FireFinder SPIX/SP8X Way 5A O/P Relay
159-0015 FireFinder SP16/Rack 8 Way 5A O/P relay
159-0022 FireFinder SP16/Rack 4 Module expansion (modules 5-8)
159-0023 FireFinder SP CFA Flam Victoria Interface
159-0024 FireFinder SP N.S.W. Country Telephone Handset, Coder andTelecom Approved Relay
159-0025 FireFinder SP NSW, ACT, N.T Transponder
159-0026 FireFinder SP QLD Metro Telecom approved
159-0027 FireFinder SP QLD South Coast Deltec Interface
159-0028 FireFinder SP QLD PPU Interface
159-0030 FireFinder SP Vic Metro A.I.U Interface
159-0031 FireFinder SP WA, SA Deltec Interface
159-0034 WA Fire Brigade Deltec Interface
159-0035 SA Fire Brigade Deltec Interface
159-0036 N.S.W. Country Telephone Handset, Coder & TelecomApproved Relay
159-0037 ACT, NSW Metro, N.T. Transponder
159-0038 CFA Victoria Interface
159-0039 QLD Metro Telecom Approved
159-0040 QLD South Coast Deltec Interface
159-0041 QLD PPU Interface
159-0042 Tasmania Deltec Interface
159-0043 Vic Metro A.I.U Interface
159-0046 FireFinder SP8X Even No. Loop
159-0049 FireFinder SP Vic Metro ASE
159-0051 FireFinder SP8X 16/16 I/O Interconnect
159-0054 FireFinder Controller Interface Card
159-0065 FireFinder SP16/RackModem for Racks
159-0067 FireFinder SP16/Rack Expansion Controller (Rack)
159-0069 FireFinder 4 Plus 4 Bell Monitor Kit
159-0071 FireFinder 8 way Bell Monitor Kit
159-0072 FireFinder Serial Relay Board
159-0077 FireFinder Expansion Controller (SP16 only)
159-0079 FireFinder SP1X Serial Relay Board
159-0084 FireFinder SP1X Panel Printer
159-0087 FireFinder 4 Wire to 2 Wire Network Interface
159-0089 FireFinder SP8X 32Z Alarm Ind (Red Led)
159-0091 FireFinder Fibre Optic Network Interface (Multi mode)
159-0098 FireFinder SP1X EV3000 HLI Interface
159-0113 FireFinder SP1X 16/16 I/O Interconnect
159-0114 FireFinder SP1X 16 OPTO Input
159-0115 FireFinder SP8X Controller Interface Card
159-0116 FireFinder SP8X Network Interface Card
159-0117 FireFinder SP16/Rack Agent Release
159-0119 FireFinder SP16/Rack Fire Fan Module Hard Wired
159-0120 FireFinder SP16/Rack 32 Zone Alarm Indicator (Red LED)
159-0121 FireFinder SP16/Rack 16 Zone Alarm/Fault Indicator
159-0122 FireFinder SP16/Rack EV3000 HLI Interface
159-0123 FireFinder SP1X 32Z General Indicator (Amber LED)
159-0124 FireFinder SP8X General Indicator (Amber LED)
159-0125 FireFinderTM Fibre Optic Network Interface (Single mode– 2 fibre)
159-0127 FireFinder SP1X/SP16/Rack Network Interface Card
330-0003 2 Amp Door Holder Supply
330-0020 FireFinder 18A 27 P/S complete with Current Limiter fuseboard
330-0031 FireFinder 5A 27V P/S
4310-0014 Agent Release Local Control Station IP40 AS
4310-0015 Agent Release Local Control Station IP65 AS
BRD85CLFBI-A Current Limiter Fuse Board
ANCILLARY CABINETS & SURROUNDS
ORDER CODE DESCRIPTION
8510-9003 FireFinder SP1X Ancillary Cabinet
8510-9010 FireFinder SP8X Ancillary Cabinet
ENC1798-F FireFinder SP1X Surround
158-0033 FireFinder SP8X Surround
ENC1797-F FireFinder SP1X + Ancillary Cabinet Surround
158-0027 FireFinder SP8X + Ancillary Cabinet Surround
ENC2844-F FireFinder SP16X Surround
158-0006 Battery Box for 10U cabinet
158-0011 Surround for 10U Cabinet C/W Battery Cabinet
158-0019 Surround for 16U Cabinet C/W Battery Cabinet
158-0012 Surround for 29U Cabinet C/W Battery Cabinet
SYSTEM OPTIONS, TOOLS & ACCESSORIES
ORDER CODE DESCRIPTION
159-0032 FireFinder Remote Colour Inkjet Printer
159-0044 LCD Repeater Panel
159-0066 FireFinder SiteSimulator
159-0068 FireFinder Wireless Modem
159-0074 SmartGraphics Complete System
159-0096 LCD Repeater Panel flush mount stainless steel
159-0126 FireFinder RS232/485 Converter
204-0016 LoopManager Apollo
293-0009 FireFinder Operators Manual
293-0010 FireFinder Technical Manual
302-7150 FireFinder LED Driver board
322-0008 FireFinder/ FastSense Notebook cable
326-0004 LoopManager Apollo printer
Analogue Fire Alarm Control Panel
FireFinderTM (cont.)
DUE TO AMPAC’S COMMITMENT TO CONTINUOUS
IMPROVEMENT, SPECIF ICATIONS MAY CHANGE
WITHOUT NOTICE
FOR A QUOTATION AND FURTHER INFORMATION, GO TO:
w w w . a m p a c . n e t38
FIRE A
LAR
MC
ON
TRO
LPA
NELS
• This kit adds an analogue loop to the FACP• For an odd numbered loop upgrade the kit
consists of 128/128 I/O module, cable andtermination card
• An even numbered loop upgrade consists of a128/128 I/O module and cable
Voltage 24 VDCQuiescent current 40 mALoop current 250 mA max.Operating temp. -5°C to 55°CHumidity 0 to 95% relative humidityWeight 200 grams
Order Code159-0001 SP Even No. Loop159-0002 Rack Even No. Loop159-0003 SP Odd No. Loop159-0004 Rack Odd No. Loop
L o o p Te r m i n a t i o n b o a r d s h o w n
1 2 8 / 1 2 8 I / O M o d u l e s h o w n
16 Conventional Zones
• Adds 16 conventional Alarm Zone Facility (AZF)• Kit consists of a 128/128 I/O module, cable and
16 AZF termination card
Voltage 24 VDCQuiescent current 145 mAOperating temp. -5°C to 55°CHumidity 0 to 95% relative humidityWeight 185 grams
Order Code 159-0005 SP4/8/16 16AZF Expansion159-0006 Rack 16AZF Expansion
1 6 A Z F Te r m i n a t i o n b o a r d s h o w n
1 2 8 / 1 2 8 I / O M o d u l e s h o w n
16 Opto Inputs
• The Opto Input panel add-on provides16 programmable electrically isolatedinputs to the FACP
• The input from a third party source shouldbe a volt-free contact
• This upgrade requires spare capacity available ona 128/128 I/O and 16/16 I/O Interconnect Module
Order Code159-0010 SP 16 Opto Input159-0011 Rack 16 Opto Input159-0055 NZ 16 Opto Input
Voltage 24 VDCQuiescent current 5 mAOperating temp. -5°C to 55°CHumidity 0 to 95% relative humidityWeight 185 grams
Analogue Loop
FireFinderTM (cont.) Panel Add-ons
Analogue Fire Alarm Control PanelFIR
E ALA
RM
CO
NTR
OL
PAN
ELS
DUE TO AMPAC’S COMMITMENT TO CONTINUOUS
IMPROVEMENT, SPECIF ICATIONS MAY CHANGE
WITHOUT NOTICE
FOR A QUOTATION AND FURTHER INFORMATION, GO TO:
w w w . a m p a c . n e t 39
Features
Features
Features
DUE TO AMPAC’S COMMITMENT TO CONTINUOUS
IMPROVEMENT, SPECIF ICATIONS MAY CHANGE
WITHOUT NOTICE
FOR A QUOTATION AND FURTHER INFORMATION, GO TO:
w w w . a m p a c . n e t40
Features
Features
FIRE A
LAR
MC
ON
TRO
LPA
NELS
Features
Product name Description
• Each upgrade panel add-on offers 8 voltage freerelay outputs. Each output is rated at 5 amps, 24 VDC
• Each relay has a single normally open/closevolt-free contact extended to a wire-protectedscrew terminal
• The standard 8-way relay upgrade requiresspare capacity available on a 128/128 I/O and16/16 I/O module
• The serial 8-way relay is driven directly from themain controller board
Voltage 24 VDCQuiescent current 5 mA (Serial Relay Board)Operating temp. -5°C to 55°CHumidity 0 to 95% relative humidityWeight 190 grams
• The Dot Matrix printer provides hardcopyactivity report
• Alarms, faults, isolates and system logs maybe printed
Order Code159-0013 SP 8-way 5A O/P Relay159-0015 Rack 8-way 5A O/P Relay
159-0013 NZ 8-way 5A O/P Relay159-0072 Serial 8-way 5A O/P Relay
159-0079 SP Serial 8-way 5A O/P Relay
Voltage 5 VDCQuiescent current 1A @ 5 VDCPrinter Type Dot MatrixCharacter size 5 x 7 dotsOperating temp. -5°C to 55°CHumidity 25 to 95% relative humidityWeight 380 grams
Order Code 159-0084 Dot Matrix Printer
Dot Matrix Printer
8-way 5A Relay
8 - Way R e l ay B o a r d s h o w n
S e r i a l R e l ay B o a r d s h o w n
REFER TO DATA SHEET: PDS159-0079 (SER IAL RELAY)
REFER TO DATA SHEET: PDS159-0016
FireFinderTM (cont.) Panel Add-ons
Analogue Fire Alarm Control Panel
Voltage 24 VDCQuiescent current 5 mAOperating temp. -5°C to 55°CHumidity 0 to 95% relative humidityWeight 110 grams
• Expands the capacity of the FireFinder toaccommodate a further four (4) 128/128 I/Omodules, four (4) loops, 64 conventional zonesor combination of the above
• Requires a main controller board
4 Module Expansion
Order Code 159-0022 Rack 4 Module Expansion159-0045 SP8 4 Module Expansion
• The modem allows a remote access toFireFinder™
• Configuration and application software can beuploaded or downloaded via the modem
• Wireless Modem requires available signal fromappropriate network
• All modems are AUSTEL approved
Order Code 159-0033 SP Modem159-0065 Rack Modem159-0068 Wireless Modem
Voltage 27 VDCData transfer rate 9600 baud maxComms to FACP RS 232Operating temp. -5°C to 55°CHumidity 0 to 95% relative humidityWeight SP & Rack 1kg
Wireless 5kg
REFER TO DATA SHEET: PDS159-0068 (WIRELESS)
FireFinderTM (cont.) Panel Add-ons
Analogue Fire Alarm Control PanelFIR
E ALA
RM
CO
NTR
OL
PAN
ELS
DUE TO AMPAC’S COMMITMENT TO CONTINUOUS
IMPROVEMENT, SPECIF ICATIONS MAY CHANGE
WITHOUT NOTICE
FOR A QUOTATION AND FURTHER INFORMATION, GO TO:
w w w . a m p a c . n e t 41
Features
Features
Features
Modem
4 Plus 4 Bell Monitor
• The 4 Plus 4 Bell Monitor has offers screwterminals for four (4) voltage free contacts andFour (4) mA switched 24V DC sounder outputs
• The outputs are monitored for open orshort circuit
• The board connects directly to the maincontroller board
Voltage 24 VDCQuiescent current 20 mAMax current 60 mACapacity 8 boards per main controllerOperating temp. -5°C to 55°CHumidity 0 to 95% relative humidityWeight 250 grams
Order Code 159-0069
REFER TO DATA SHEET: PDS159-0069
• The 8-Way Bell Monitor has offers screwterminals eight (8) mA switched 24V DC outputs
• The outputs are monitored for open orshort circuit
• The board connects directly to the maincontroller board
Voltage 27 VDCQuiescent current 20 mAMax current 60 mAOperating temp. -5°C to 55°CHumidity 0 to 95% relative humidityWeight 250 grams
Order Code 159-0071
REFER TO DATA SHEET: PDS159-0071
8-Way Bell Monitor
DUE TO AMPAC’S COMMITMENT TO CONTINUOUS
IMPROVEMENT, SPECIF ICATIONS MAY CHANGE
WITHOUT NOTICE
FOR A QUOTATION AND FURTHER INFORMATION, GO TO:
w w w . a m p a c . n e t42
Features
Features
FIRE A
LAR
MC
ON
TRO
LPA
NELS
Features
Product name Description
Fire Fan Module
• Controls and monitors fire fans, dampers,sprinkler pumps etc.
• 4 controls per module• Separate start and stop output per control• 3 status inputs per control• Labels can be modified on site• Serial connection to Fire Alarm Control Panel
Voltage 27 VDCQuiescent current 12.5 mAMax current 50 mARelay contact rating 3 amp at 24 VDCOperating temp. -5°C to 55°CHumidity 25 to 75% relative humidityWeight 230 grams
Order Code 159-0119
• Controls and monitors agent release systems• Provides outputs for warning signs, and
activation devices• Provides inputs for pressure switches and
valves• Serial connection to Fire Alarm Control Panel
Voltage 24 VDCQuiescent current 10 mAMax current 1.5 ARelay contact rating 3 amp at 24 VDCOperating temp. -5°C to 55°CHumidity 25 to 75% relative humidityWeight 250 grams
Order Code 159-0117
Agent Release
FireFinderTM (cont.) Panel Add-ons
Analogue Fire Alarm Control Panel
• Remote control of FireFinder FACP viaGraphical User Interface system
• Suports embedded photographs• Supports user defined messages
i.e. HAZCHEM information, special instructions)• Supports multiple user levels• Supports multiple zoom levels• Supports user defined maps• Event & user access logs• Displays status of devices, zones & network• Key Map assists in navigation
Environment PC based systemPC Specifications Pentium 3, 1Ghz processor,
1GB hardrive space,CDROM, and, parallel andserial ports
Monitor 17” or larger recommendedCommunications RS232 RS485Baud rate 9600 to 9600 to
38400 38400Max distance 15m 1200m
Order Code 159-0074
REFER TO DATA SHEET: PDS159-0074
SmartGraphics
FireFinderTM (cont.) Panel Add-ons
Analogue Fire Alarm Control PanelFIR
E ALA
RM
CO
NTR
OL
PAN
ELS
DUE TO AMPAC’S COMMITMENT TO CONTINUOUS
IMPROVEMENT, SPECIF ICATIONS MAY CHANGE
WITHOUT NOTICE
FOR A QUOTATION AND FURTHER INFORMATION, GO TO:
w w w . a m p a c . n e t 43
Features
Features
• Remote zone indication in 3 options – 16/16 Alarm/Fault zone indication – 32 Alarm only indication – 32 general indication• Serial connection to Fire Alarm Control Panel
Voltage 24 VDCQuiescent current 30 mAMax current 40 mAOperating temp. -5°C to 55°CHumidity 25 to 75% relative humidityWeight 100 grams
Order Code 159-0120 32 Alarm only indication (Red)159-0121 16 Alarm/Fault indication (Red/Amber)159-0123 32 General indication (Amber)
LED Indicator Cards
• Allows network node to be connected via fibreoptics instead of hardwire
• Extends distances between nodes
Voltage 12 VDCQuiescent current 220 mAPorts Available RS422Fibre Connector ST StandardMode Multimode/SinglemodeEmitter Type LEDOperating temp. -40°C to +75°CHumidity 0 to 95% rleative,
noncondensing
Order Code 159-0091 Multi mode, dual fibre159-0125 Single mode, dual fibre159-0133 Single mode, single fibre
REFER TO DATA SHEET: PDS159-0091
Optic Fibre Modems