  • Substation Name 0 Location 0 Relay Model Number 0 Relay Serial Number 0 Rated Primary Current 1000 AmpsRated Secondary Current 1 AmpsRated Primary Voltage 400000 VoltsRated Secondary Voltage 110 VoltsProtected Line Impedance 10 Ohms

    Line Angle (Positive seq.) 75 Degree

    Enable Zone1: Yes

    Zone1 Settings FW

    Z1 5 OhmsCharAngle 90 Degree1 QUAD Z1G 5 OhmsCharAngle 90 Degreet1 for Zone1 0 secondsZGroundK0 3

    Z1SURREACH 10 OhmsZGCharangle 90 SDegreeEnable Zone2: Yes

    Zone2 Settings FW

    Z2 20 OhmsCharAngle 90 Degree

    Z2G 20 OhmsCharAngle 90 Degreet2 for Zone2 0.3 secondsZGroundK0 3

    Enable Zone3: Yes

    Zone3 Settings FW

    Z3 30 OhmsCharAngle 90 Degree

    Z3G 30 OhmsCharAngle 90 Degreet3 for Zone3 0.6 secondsZGroundK0 3

    Enable Zone4: Yes

    Zone4 Settings RW

  • Z4 20 OhmsCharAngle 90 Degree

    Z4G 20 OhmsCharAngle 90 Degreet4 for Zone4 1 secondsZGroundK0 3