© 2005 American Standard Inc. All Rights Reserved PUB. NO. 12-1200-02 March 2005 ALLEGIANCE ® 16 MODELS 4A7A6024,036,048 & 060B SPLIT SYSTEM COOLING 2, 3, 4 & 5 TON

ALLEGIANCE 16 MODELS 4A7A6024,036,048 & 060Bfurnacefactorydirect.ca/pdf/4a7a6 Product Data.pdf · ALLEGIANCE® 16 MODELS 4A7A6024,036,048 & 060B SPLIT SYSTEM ... the Unitary Air-Conditioner

Embed Size (px)

Citation preview

Page 1: ALLEGIANCE 16 MODELS 4A7A6024,036,048 & 060Bfurnacefactorydirect.ca/pdf/4a7a6 Product Data.pdf · ALLEGIANCE® 16 MODELS 4A7A6024,036,048 & 060B SPLIT SYSTEM ... the Unitary Air-Conditioner

© 2005 American Standard Inc. All Rights Reserved

PUB. NO. 12-1200-02March 2005

ALLEGIANCE® 16MODELS 4A7A6024,036,048 & 060B

SPLIT SYSTEM COOLING2, 3, 4 & 5 TON

Page 2: ALLEGIANCE 16 MODELS 4A7A6024,036,048 & 060Bfurnacefactorydirect.ca/pdf/4a7a6 Product Data.pdf · ALLEGIANCE® 16 MODELS 4A7A6024,036,048 & 060B SPLIT SYSTEM ... the Unitary Air-Conditioner

PRODUCT DATAAmerican Standard Inc., Tyler, TX 75711-9010

2 DATA SUBJECT TO CHANGE WITHOUT NOTICE

Featuresand Benefits

◆ Duration™ staged scroll compressor◆ Efficiency up to 17.15 SEER◆ Attractive warm gray cabinet with

accent Grill, Badge and Grill Caps◆ Corrosion resistant finish and

fasteners◆ DuraBase™ base pan won’t rust,

drains completely◆ Control and service valve cover◆ Multi-use service valves◆ Two speed fan motor◆ Full coil protection with seacoast

shield◆ Liquid line filter-drier◆ All aluminum Spine Fin™ coil◆ Easy-Sess™ service access for

installation, service and maintenance◆ Comfort “R”™ mode approved◆ Low sound with advanced fan system

and compressor sound insulator◆ American Standard and Allegiance 16

badge identifier

◆ Factory installed start kit on 024 &060 models

◆ 060 ships with sump heat◆ High pressure switch and internal

compressor temperature/pressureprotection

◆ Vertical air discharge◆ Factory supplied charge of

R-410A refrigerant◆ 10 year limited warranty on

compressor, coil, and 5 yearson parts

◆ Low ambient cooling to 55°F asshipped

◆ Low ambient cooling to 40°F withEDC accessory AY28X079

◆ Low ambient cooling to 30°F withEDC accessory AY28X079 and TXV

◆ Optional extended warranties

Page 3: ALLEGIANCE 16 MODELS 4A7A6024,036,048 & 060Bfurnacefactorydirect.ca/pdf/4a7a6 Product Data.pdf · ALLEGIANCE® 16 MODELS 4A7A6024,036,048 & 060B SPLIT SYSTEM ... the Unitary Air-Conditioner

DATA SUBJECT TO CHANGE WITHOUT NOTICE 3

PRODUCT DATAAmerican Standard Inc., Tyler, TX 75711-9010

Manufacturing ControlAmerican Standard’s exclusive controlover the design and manufacturing of allmajor components is unique in theindustry. This approach assures us totalcontrol over both the quality and reliabilityof these components. It also allows us tocustom match components to deliver thebest in split system performance.

Designing the DetailsCareful attention was given to designingthe details — from control wiring to theaccess panels. These units feature time-saving color-coded wiring and removablepanels which allow complete access to allmajor components and controls. Alloutdoor units feature external high andlow pressure gauge port connections.Service valves for easy diagnosing andservicing of the unit are provided.

Standardized CabinetsIn addition all cabinets have beenstandardized; so when you are servicingan outdoor unit or an air handler allcomponents are in the same locationfrom unit to unit.

UL ListedAmerican Standard meets or exceeds allnationally recognized agency safety anddesign standards. Each condensing unitis UL designed, approved, and labeled inaccordance to UL Standards, 1995,including approval for use in Canada.Each unit is rated in accordance withARI Standard 210/240 and 270.

DATA SUBJECTTO CHANGE

WITHOUT NOTICE

Contents

Features and Benefits 2

General Data 4Product Specifications 4A-weighted Sound

Power Level [dB(A)] 4Accessory Description

and Usage 5ARI Standard Capacity

Rating Conditions 5

Model Nomenclature 6

System Ratings 74A7A6024B1 74A7A6036B1 84A7A6048B1 94A7A6060B1 10

Performance Data Cooling 114A7A6024B1 114A7A6036B1 154A7A6048B1 194A7A6060B1 22

Typical Wiring 24

Dimensional Data 27

Mechanical Specifications 28

Page 4: ALLEGIANCE 16 MODELS 4A7A6024,036,048 & 060Bfurnacefactorydirect.ca/pdf/4a7a6 Product Data.pdf · ALLEGIANCE® 16 MODELS 4A7A6024,036,048 & 060B SPLIT SYSTEM ... the Unitary Air-Conditioner

PRODUCT DATAAmerican Standard Inc., Tyler, TX 75711-9010

4 DATA SUBJECT TO CHANGE WITHOUT NOTICE

GeneralData

Product SpecificationsModel No. 1 4A7A6024B1 4A7A6036B1 4A7A6048B1 4A7A6060B1Electrical Data V/Ph/Hz 2 230/1/60 230/1/60 230/1/60 230/1/60Min Cir Ampacity 13 24 29 35Max Fuse Size (Amps) 20 40 50 60Compressor DURATION™ - SCROLL DURATION™ - SCROLL DURATION™ - SCROLL DURATION™ - SCROLLRL Amps - LR Amps 10.3 - 52 16.7 - 82 21.2 - 96 25.6 - 118Outdoor Fan FL Amps 0.60 2.80 2.80 2.80Fan HP 1/15 1/3 1/3 1/3Fan Dia (inches) 23 27.6 27.6 27.6Coil Spine Fin™ Spine Fin™ Spine Fin™ Spine Fin™Refrigerant R-410A 5/09-LB/OZ 6/10-LB/OZ 7/08-LB/OZ 10/00-LB/OZLine Size - (in.) O.D. Gas 3 5/8 3/4 7/8 7/8Line Size - (in.) O.D. Liquid 3 5/16 3/8 3/8 3/8Dimensions H x W x D (Crated) 42 x 30.1 x 33 38.4 x 35.1 x 38.7 46.4 x 35.1 x 38.7 46.4 x 35.1 x 38.7Weight - Shipping 235 255 278 322Weight - Net 206 222 242 286Start Components YES NO NO YESSound Enclosure YES YES YES YESCompressor Sump Heat NO NO NO YESOptional Accessories: 4Anti-short Cycle Timer TAYASCT501A TAYASCT501A TAYASCT501A TAYASCT501AEvaporator Defrost Control A/C AY28X079 AY28X079 AY28X079 AY28X079Rubber Isolator Kit BAYISLT101 BAYISLT101 BAYISLT101 BAYISLT101Crank Case Heater Scroll BAYCCHT301 BAYCCHT301 BAYCCHT301Hard Start Kit Scroll BAYKSKT260 BAYKSKT260Extreme Condition Mounting Kit BAYECMT001 BAYECMT001 BAYECMT001 BAYECMT001Refrigerant Lineset 5 TAYREFLN6* TAYREFLN7* TAYREFLN3* TAYREFLN3*1 Certified in accordance with the Unitary Air-Conditioner equipment certification program which is based on ARI Standard 210/240.2 Calculated in accordance with N.E.C. Use only HACR circuit breakers or fuses.3 Standard line lengths - 80'. Standard lift - 25' Suction and Liquid line.

For Greater lengths and lifts refer to refrigerant piping software Pub# 32-3312-0†. (†denotes latest revision)4 For accessory description and usage, see page 5.5 * = 15, 20, 25, 30, 40 and 50 foot lineset available.

A-weighted Sound Power Level [dB(A)]

SOUND POWER A-WEIGHTED FULL OCTAVE SOUND POWER LEVEL dB - [dB(A)]MODEL LEVEL [dB(A)] 63 125 250 500 1000 2000 4000 8000

4A7A6024B1 73 42.3 53.1 57.2 68.9 63.4 61.2 51.7 44.5

4A7A6036B1 72 49.7 57.5 60.5 64.4 65.0 61.4 57.7 52.2

4A7A6048B1 74 52.7 54.6 60.6 71.6 68.8 61.8 59.0 50.4

4A7A6060B1 74 52.7 54.6 60.6 71.6 68.8 61.8 59.0 50.4Note: Tested in accordance with ARI Standard 270.95. (Not listed with ARI)

Page 5: ALLEGIANCE 16 MODELS 4A7A6024,036,048 & 060Bfurnacefactorydirect.ca/pdf/4a7a6 Product Data.pdf · ALLEGIANCE® 16 MODELS 4A7A6024,036,048 & 060B SPLIT SYSTEM ... the Unitary Air-Conditioner

DATA SUBJECT TO CHANGE WITHOUT NOTICE 5

PRODUCT DATAAmerican Standard Inc., Tyler, TX 75711-9010

GeneralData

ARI Standard Capacity Rating ConditionsARI STANDARD 210/240 RATING CONDITIONS —

(A) Cooling 80°F DB, 67°F WB air entering indoor coil,95°F DB air entering outdoor coil.

(B) High Temperature Heating 47°F DB, 43°F WB air enteringoutdoor coil, 70°F DB air entering indoor coil.

(C) Low Temperature Heating 17°F DB, 15°F WB air enteringoutdoor coil, 70°F DB air entering indoor coil.

(D) Rated indoor airflow for heating is the same as for cooling.ARI STANDARD 270 RATING CONDITIONS — (Noise ratingnumbers are determined with the unit in cooling operation.)Standard Noise Rating number is at 95°F outdoor air.

Accessory Description and UsageAnti-Short Cycle Timer — Solid state timing device thatprevents compressor recycling until 5 minutes have elapsedafter satisfying call or power interruptions. Use in area withquestionable power delivery, commercial applications, longlineset, etc.

Evaporator Defrost Control — SPST Temperature actuatedswitch that cycles the condenser off as indoor coil reachesfreeze-up conditions. Used for low ambient cooling to 30°Fwith TXV.

Rubber Isolators — 5 large rubber donuts to isolatecondensing unit from transmitting energy into mounting frameor pad. Use on any application where sound transmissionneeds to be minimized.Hard Start kit — Start capacitor and relay to assistcompressor motor startup. Use in areas with marginal powersupply, on long linesets, low ambient conditions, etc.Extreme Condition Mount Kit — Bracket kits to securelymount condensing unit to a frame or pad without removing anypanels. Use in areas with high winds, or on commercial rooftops, etc. SPLIT SYSTEM

Page 6: ALLEGIANCE 16 MODELS 4A7A6024,036,048 & 060Bfurnacefactorydirect.ca/pdf/4a7a6 Product Data.pdf · ALLEGIANCE® 16 MODELS 4A7A6024,036,048 & 060B SPLIT SYSTEM ... the Unitary Air-Conditioner

PRODUCT DATAAmerican Standard Inc., Tyler, TX 75711-9010

6 DATA SUBJECT TO CHANGE WITHOUT NOTICE

ModelNomenclature

Refrigerant Type4 = R-410A2 = R-22

ApplicationTE = Fully ConvertibleTG = Semi ConvertibleTF = Front ReturnTV = Vertical

Product FamilyE = Leadership – Variable SpeedP = LeadershipC = Replacement/RetailB = Basic

Flow Control3 = Nonbleed TXV4 = FCCV*

Feature Identifier0 = Standard UnitF = Air-Tite™

Nominal Capacity in 000s of BTUs

Major Design Modifications

Power Supply1 = Single Phase

Electrical Connection0 = Pig TailsB = Circuit BreakerD = Pull Disconnect

Future Option – Factory Installed Heater Nominal KW Value

Minor Design Modifications

Unit Parts Identifier

NOTE: There will be a phase-in of new model numbers for new air handlers over next 2 years.*Shipped with R-22 FCCV

Air Handlers –Residential

4 T E E 3 F 3 6 A 1 0 0 0 A A

Refrigerant Type2 = R-224 = R-410A

AMERICAN STANDARD

Product Type6 = Split Heat Pump7 = Split Cooling

Product FamilyA = AllegianceH = HeritageB = BasicC = Light Commercial

Family SEER0 = 10 3 = 13 6 = 161 = 11 4 = 14 8 = 182 = 12 5 = 15 9 = 19

Split System Connections 1-6 Tons0 = Brazed

Nominal Capacity in 000s of BTUs

Major Design Modifications

Power Supply1 = 200-230/1/60 or 208-230/1/603 = 200-230/3/604 = 460/3/60

Secondary Function

Minor Design Modifications

Unit Parts Identifier

Outdoor Units4 A 7 A 6 0 3 6 B 1 0 0 0 A A

Furnace ConfigurationTU = Upflow/HorizontalTD = Downflow/Horizontal

TypeC = CondensingD = Induced DraftE = Electronic IgnitionX = Direct Vent CondensingY = Direct Vent Condensing Variable Speed

Heating Input MBTUH080 = 80,000 BTUH

Major Design ChangeC = Single Stage R = Two StageAll other = Standard System

Power Supply and Fuel115 Volt Natural Gas

Airflow Capacity for CoolingExample: 36 = 3 Tons 400 CFM/Ton 400 x 3 Tons = 1200 CFMV3 = 1 1/2 – 3 Tons, Varible Speed Motor (ICM)V4 = 2 – 4 Tons, Varible Speed Motor (ICM)V5 = 3 – 5 Tons, Varible Speed Motor (ICM)

Minor Design Change

Service Digit – Not Orderable

Gas FurnacesT U Y 0 8 0 R 9 V 3 W 0

Refrigerant TypeT = R-22R = R-410AC = Cooling only

Furnace CoilsXA = Uncased “A” Coil Upflow/DownflowXC = Cased Coil Upflow/Downflow/HorizontalXH = Cased Horizontal OnlyCB = Cased/Brazed Upflow – Cooling OnlyUB = Uncased/Brazed Upflow – Cooling Only

Coupling0 = Braze

Nominal CapacityNominal Capacity in 000s of BTUs

Product FamilyC = UniversalS = High Efficiency – Nonbleed TXVE = High Efficiency – Bleed TXVA = Upflow OnlyD = Reverse Airflow

Refrigerant Control2 = Cap Tube3 = Nonbleed TXV4 = Accutron™ Flow Control/Check Valve (FCCV)5 = Bleed TXV

HP = Heat Pump00 = Cooling only (7 1/2 to 10 ton)

Minor Design Change

Service Digit – Not Orderable

Furnace CoilsT X C 0 2 4 C 4 H P C 0

Page 7: ALLEGIANCE 16 MODELS 4A7A6024,036,048 & 060Bfurnacefactorydirect.ca/pdf/4a7a6 Product Data.pdf · ALLEGIANCE® 16 MODELS 4A7A6024,036,048 & 060B SPLIT SYSTEM ... the Unitary Air-Conditioner

DATA SUBJECT TO CHANGE WITHOUT NOTICE 7

PRODUCT DATAAmerican Standard Inc., Tyler, TX 75711-9010

System Ratings —

CONDENSING UNIT WITH AIR HANDLERSAIR TOTAL SENSIBLEHANDLER CFM CAPACITY CAPACITY KW SEER EER

4TEE3F31A1 780 24200 17500 1.98 16.30 12.20

4TEE3F37A1 800 24000 18100 1.97 16.25 12.20

CONDENSING UNIT WITH FURNACE AND COILSFURNACE TOTAL SENSIBLEAND COIL CFM CAPACITY CAPACITY KW SEER EER

ADD060R9V3+RXC025S3 810 22800 16900 2.00 15.25 11.40

ADD060R9V3+RXC031S3 810 24200 18300 2.00 16.25 12.10

ADD060R9V3+RXC036S3 800 24600 18600 2.00 16.50 12.30

ADD060R9V3+TXH025A4+4AYTXV-3 800 23000 17000 1.98 15.50 11.60

ADD060R9V3+TXH033A4+4AYTXV-3 800 24000 18200 1.97 16.25 12.20

ADD080R9V3+RXC025S3 760 22600 16400 1.97 15.25 11.50

ADD080R9V3+RXC031S3 770 24000 17900 1.98 16.25 12.10

ADD080R9V3+RXC036S3 770 24400 18200 1.98 16.50 12.30

ADD080R9V3+TXH025A4+4AYTXV-3 770 22800 16600 1.95 15.50 11.70

ADD080R9V3+TXH033A4+4AYTXV-3 780 24000 18000 1.97 16.25 12.20

ADY060R9V3+RXC025S3 710 22400 15900 1.96 15.00 11.40

ADY060R9V3+RXC031S3 710 23800 17200 1.97 16.00 12.10

ADY060R9V3+RXC036S3 700 24000 17300 1.97 16.25 12.20

ADY060R9V3+TXH025A4+4AYTXV-3 710 22600 16100 1.95 15.25 11.60

ADY060R9V3+TXH033A4+4AYTXV-3 700 23600 17100 1.95 16.25 12.10

ADY080R9V3+RXC025S3 710 22400 15900 1.95 15.25 11.50

ADY080R9V3+RXC031S3 710 23800 17200 1.97 16.00 12.10

ADY080R9V3+RXC036S3 710 24200 17500 1.97 16.50 12.30

ADY080R9V3+TXH025A4+4AYTXV-3 710 22600 16100 1.95 15.25 11.60

ADY080R9V3+TXH033A4+4AYTXV-3 710 23600 17100 1.95 16.25 12.10

4A7A6024B1

CONDENSING UNIT WITH FURNACE AND COILSFURNACE TOTAL SENSIBLEAND COIL CFM CAPACITY CAPACITY KW SEER EER

AUD060R9V3+RXC025S3 830 22800 17100 2.02 15.00 11.30

AUD060R9V3+RXC031S3 830 24200 18500 2.03 16.00 11.90

AUD060R9V3+RXC036S3 830 24600 18800 2.02 16.50 12.20

AUD060R9V3+TXH025A4+4AYTXV-3 830 23000 17200 2.00 15.25 11.50

AUD060R9V3+TXH033A4+4AYTXV-3 820 24000 18300 2.00 16.25 12.00

AUD080R9V3+RXC025S3 810 22800 16900 2.00 15.25 11.40

AUD080R9V3+RXC031S3 820 24200 18400 2.02 16.00 12.00

AUD080R9V3+RXC036S3 820 24600 18700 2.00 16.50 12.30

AUD080R9V3+TXH025A4+4AYTXV-3 820 23000 17100 1.98 15.50 11.60

AUD080R9V3+TXH033A4+4AYTXV-3 820 24200 18500 2.00 16.25 12.10

AUD100R9V3+RXC025S3 820 22800 17000 2.02 15.00 11.30

AUD100R9V3+RXC031S3 810 24000 18200 2.02 16.00 11.90

AUD100R9V3+RXC036S3 800 24600 18600 2.02 16.50 12.20

AUD100R9V3+TXH025A4+4AYTXV-3 800 22800 16800 1.98 15.25 11.50

AUD100R9V3+TXH033A4+4AYTXV-3 790 24000 18100 2.00 16.25 12.00

AUY060R9V3+RXC025S3 720 22400 16000 1.98 15.00 11.30

AUY060R9V3+RXC031S3 720 23800 17300 2.00 16.00 11.90

AUY060R9V3+RXC036S3 720 24200 17600 1.98 16.25 12.20

AUY060R9V3+TXH025A4+4AYTXV-3 720 22600 16200 1.97 15.25 11.50

AUY060R9V3+TXH033A4+4AYTXV-3 710 23600 17100 1.97 16.00 12.00

AUY080R9V3+RXC025S3 690 22400 15800 1.96 15.00 11.40

AUY080R9V3+RXC031S3 700 23600 17000 1.97 16.00 12.00

AUY080R9V3+RXC036S3 710 24200 17500 1.97 16.25 12.30

AUY080R9V3+TXH025A4+4AYTXV-3 700 22600 16000 1.95 15.25 11.60

AUY080R9V3+TXH033A4+4AYTXV-3 710 23600 17100 1.95 16.25 12.10

Page 8: ALLEGIANCE 16 MODELS 4A7A6024,036,048 & 060Bfurnacefactorydirect.ca/pdf/4a7a6 Product Data.pdf · ALLEGIANCE® 16 MODELS 4A7A6024,036,048 & 060B SPLIT SYSTEM ... the Unitary Air-Conditioner

PRODUCT DATAAmerican Standard Inc., Tyler, TX 75711-9010

8 DATA SUBJECT TO CHANGE WITHOUT NOTICE

System Ratings —

CONDENSING UNIT WITH AIR HANDLERSAIR TOTAL SENSIBLEHANDLER CFM CAPACITY CAPACITY KW SEER EER

4TEE3F37A1 1160 35200 26200 2.96 16.25 11.90

4TEE3F40A1 1230 37600 27600 2.94 17.15 12.80

CONDENSING UNIT WITH FURNACE AND COILSFURNACE TOTAL SENSIBLEAND COIL CFM CAPACITY CAPACITY KW SEER EER

ADD060R9V3+RXC031S3 1220 35200 26600 3.06 15.75 11.50

ADD060R9V3+RXC036S3 1220 36200 27400 3.07 16.25 11.80

ADD060R9V3+TXH033A4+4AYTXV-3 1210 35200 26800 3.03 16.00 11.60

ADD060R9V3+TXH041A4+4AYTXV-3 1210 36000 27200 3.03 16.25 11.90

ADD080R9V3+RXC031S3 1120 35000 25800 2.99 16.00 11.70

ADD080R9V3+RXC036S3 1130 36000 26600 3.03 16.50 11.90

ADD080R9V3+TXH033A4+4AYTXV-3 1130 35000 26000 3.02 16.00 11.60

ADD080R9V3+TXH041A4+4AYTXV-3 1140 35800 26400 2.98 16.25 12.00

ADD100R9V5+RXC037S3 1180 36400 27200 2.96 17.00 12.30

ADY060R9V3+RXC036S3 1090 35800 26000 3.01 16.50 11.90

ADY080R9V3+RXC031S3 1090 34600 25200 3.04 15.75 11.40

ADY080R9V3+RXC036S3 1100 35400 25800 3.05 16.00 11.60

ADY080R9V3+TXH033A4+4AYTXV-3 1110 34600 25600 3.06 15.75 11.30

ADY100R9V4+RXC037S3 1050 35800 25800 2.98 16.50 12.00

ADY100R9V4+TXH033A4+4AYTXV-3 1050 34600 25200 2.98 16.00 11.60

ADY100R9V4+TXH041A4+4AYTXV-3 1060 35400 25600 2.97 16.25 11.90

AUD060R9V3+RXC031S3 1190 35000 26200 3.07 15.50 11.40

4A7A6036B1

CONDENSING UNIT WITH FURNACE AND COILSFURNACE TOTAL SENSIBLEAND COIL CFM CAPACITY CAPACITY KW SEER EER

AUD060R9V3+RXC036S3 1200 36000 27200 3.10 16.00 11.60

AUD060R9V3+TXH033A4+4AYTXV-3 1210 35000 26600 3.10 15.75 11.30

AUD060R9V3+TXH041A4+4AYTXV-3 1210 35800 27000 3.06 16.00 11.70

AUD080R9V3+RXC031S3 1190 35200 26400 3.09 15.75 11.40

AUD080R9V3+RXC036S3 1200 36000 27200 3.08 16.25 11.70

AUD080R9V3+TXH033A4+4AYTXV-3 1200 35000 26600 3.07 16.00 11.40

AUD080R9V3+TXH041A4+4AYTXV-3 1200 35800 26800 3.03 16.25 11.80

AUD080R9V4+RXC037S3 1180 36600 27400 2.98 16.75 12.30

AUD080R9V4+TXH033A4+4AYTXV-3 1180 35400 26600 2.97 16.25 11.90

AUD080R9V4+TXH041A4+4AYTXV-3 1180 36200 27000 2.97 16.75 12.20

AUD100R9V3+RXC031S3 1240 35200 26800 3.17 15.50 11.10

AUD100R9V3+RXC036S3 1250 36200 27600 3.18 16.00 11.40

AUD100R9V3+TXH033A4+4AYTXV-3 1240 35000 26800 3.13 15.50 11.20

AUD100R9V3+TXH041A4+4AYTXV-3 1230 35800 27200 3.11 16.00 11.50

AUD100R9V5+RXC037S3 1210 36600 27600 3.00 16.75 12.20

AUY060R9V3+RXC036S3 1080 35600 25800 3.02 16.25 11.80

AUY080R9V3+RXC036S3 1030 35600 25400 2.97 16.50 12.00

AUY080R9V3+TXH033A4+4AYTXV-3 1030 34400 24800 2.94 16.00 11.70

AUY080R9V3+TXH041A4+4AYTXV-3 1030 35600 25400 2.97 16.25 12.00

AUY100R9V4+RXC037S3 1050 36000 26000 2.95 16.50 12.20

AUY100R9V4+TXH033A4+4AYTXV-3 1050 34800 25200 2.95 16.00 11.80

AUY100R9V4+TXH041A4+4AYTXV-3 1050 35400 25400 2.93 16.50 12.10

Page 9: ALLEGIANCE 16 MODELS 4A7A6024,036,048 & 060Bfurnacefactorydirect.ca/pdf/4a7a6 Product Data.pdf · ALLEGIANCE® 16 MODELS 4A7A6024,036,048 & 060B SPLIT SYSTEM ... the Unitary Air-Conditioner

DATA SUBJECT TO CHANGE WITHOUT NOTICE 9

PRODUCT DATAAmerican Standard Inc., Tyler, TX 75711-9010

System Ratings —

CONDENSING UNIT WITH AIR HANDLERSAIR TOTAL SENSIBLEHANDLER CFM CAPACITY CAPACITY KW SEER EER

4TEE3F40A1 1400 47500 34800 4.06 16.00 11.70

4TEE3F49A1 1600 49000 35000 4.12 16.35 11.90

CONDENSING UNIT WITH FURNACE AND COILSFURNACE TOTAL SENSIBLEAND COIL CFM CAPACITY CAPACITY KW SEER EER

ADD100R9V5+RXC054S3 1620 46500 34800 4.15 15.50 11.20

ADD100R9V5+TXC043C4+4AYTXV-3 1620 45500 33800 4.17 15.00 10.90

ADD100R9V5+TXC049C4+4AYTXV-3 1620 46000 34400 4.14 15.25 11.10

ADD100R9V5+TXH054A4+4AYTXV-3 1620 47500 36400 4.17 15.75 11.40

ADD120R9V5+TXC050C4+4AYTXV-3 1630 46500 34800 4.12 15.50 11.30

ADD120R9V5+TXH054A4+4AYTXV-3 1630 48000 37000 4.14 16.00 11.60

ADY100R9V4+RXC054S3 1450 45500 32800 4.14 15.00 11.00

ADY100R9V4+TXC043C4+4AYTXV-3 1450 44500 32000 4.12 14.75 10.80

ADY100R9V4+TXC049C4+4AYTXV-3 1450 45500 32800 4.17 15.00 10.90

ADY100R9V4+TXH054A4+4AYTXV-3 1450 47000 34600 4.16 15.50 11.30

ADY120R9V5+TXC050C4+4AYTXV-3 1430 45500 32800 4.06 15.25 11.20

ADY120R9V5+TXH054A4+4AYTXV-3 1430 47000 34600 4.09 15.75 11.50

AUD080R9V4+RXC054S3 1590 46500 34600 4.15 15.50 11.20

4A7A6048B1

CONDENSING UNIT WITH FURNACE AND COILSFURNACE TOTAL SENSIBLEAND COIL CFM CAPACITY CAPACITY KW SEER EER

AUD080R9V4+TXC043C4+4AYTXV-3 1590 45500 33800 4.17 15.00 10.90

AUD080R9V4+TXC049C4+4AYTXV-3 1590 46000 34200 4.14 15.25 11.10

AUD080R9V4+TXH054A4+4AYTXV-3 1590 47500 36200 4.17 15.75 11.40

AUD100R9V5+RXC054S3 1670 46500 35200 4.19 15.25 11.10

AUD100R9V5+TXC043C4+4AYTXV-3 1670 45500 34200 4.21 15.00 10.80

AUD100R9V5+TXC049C4+4AYTXV-3 1670 46500 35200 4.23 15.25 11.00

AUD100R9V5+TXH054A4+4AYTXV-3 1670 48000 37200 4.25 15.50 11.30

AUD120R9V5+TXC050C4+4AYTXV-3 1630 46500 34800 4.15 15.50 11.20

AUD120R9V5+TXH054A4+4AYTXV-3 1630 48000 37000 4.17 15.75 11.50

AUD140R9V5+TXC050C4+4AYTXV-3 1590 46000 34200 4.07 15.50 11.30

AUD140R9V5+TXH054A4+4AYTXV-3 1590 48000 36600 4.14 16.00 11.60

AUY100R9V4+RXC054S3 1430 45500 32800 4.06 15.25 11.20

AUY100R9V4+TXC043C4+4AYTXV-3 1430 44500 32000 4.08 14.75 10.90

AUY100R9V4+TXC049C4+4AYTXV-3 1430 45500 32800 4.10 15.00 11.10

AUY100R9V4+TXH054A4+4AYTXV-3 1430 47000 34600 4.12 15.50 11.40

AUY120R9V5+TXC050C4+4AYTXV-3 1430 45500 32800 4.06 15.25 11.20

AUY120R9V5+TXH054A4+4AYTXV-3 1430 47000 34600 4.05 15.75 11.60

Page 10: ALLEGIANCE 16 MODELS 4A7A6024,036,048 & 060Bfurnacefactorydirect.ca/pdf/4a7a6 Product Data.pdf · ALLEGIANCE® 16 MODELS 4A7A6024,036,048 & 060B SPLIT SYSTEM ... the Unitary Air-Conditioner

PRODUCT DATAAmerican Standard Inc., Tyler, TX 75711-9010

10 DATA SUBJECT TO CHANGE WITHOUT NOTICE

System Ratings —

CONDENSING UNIT WITH AIR HANDLERSAIR TOTAL SENSIBLEHANDLER CFM CAPACITY CAPACITY KW SEER EER

4TEE3F65A1 1765 58500 40000 5.52 15.10 10.60

CONDENSING UNIT WITH FURNACE AND COILSFURNACE TOTAL SENSIBLEAND COIL CFM CAPACITY CAPACITY KW SEER EER

ADD100R9V5+RXH063S3 1760 58000 42500 5.42 14.75 10.70

ADD120R9V5+RXC061S3 1750 56500 41000 5.33 14.50 10.60

ADD120R9V5+RXH063S3 1750 59000 43500 5.41 15.00 10.90

ADY120R9V5+RXC061S3 1780 56000 40500 5.54 14.00 10.10

ADY120R9V5+RXH063S3 1730 58000 42500 5.69 14.50 10.20

AUD100R9V5+RXC061S3 1800 56500 41000 5.43 14.25 10.40

AUD100R9V5+RXC065S3 1820 56500 41000 5.59 14.00 10.10

4A7A6060B1

CONDENSING UNIT WITH FURNACE AND COILSFURNACE TOTAL SENSIBLEAND COIL CFM CAPACITY CAPACITY KW SEER EER

AUD100R9V5+RXH063S3 1800 58500 43500 5.47 15.00 10.70

AUD120R9V5+RXC061S3 1740 56500 40500 5.38 14.50 10.50

AUD120R9V5+RXC065S3 1790 56500 41000 5.54 14.25 10.20

AUD120R9V5+RXH063S3 1740 59000 43000 5.46 15.00 10.80

AUD140R9V5+RXC061S3 1710 56000 40000 5.28 14.50 10.60

AUD140R9V5+RXC065S3 1730 56500 40500 5.43 14.25 10.40

AUD140R9V5+RXH063S3 1710 58500 42500 5.37 15.00 10.90

AUY120R9V5+RXC061S3 1800 56000 41000 5.49 14.00 10.20

AUY120R9V5+RXC065S3 1790 56000 40500 5.60 14.00 10.00

AUY120R9V5+RXH063S3 1790 58000 43000 5.63 14.50 10.30

Page 11: ALLEGIANCE 16 MODELS 4A7A6024,036,048 & 060Bfurnacefactorydirect.ca/pdf/4a7a6 Product Data.pdf · ALLEGIANCE® 16 MODELS 4A7A6024,036,048 & 060B SPLIT SYSTEM ... the Unitary Air-Conditioner

PRODUCT DATAAmerican Standard Inc., Tyler, TX 75711-9010

DATA SUBJECT TO CHANGE WITHOUT NOTICE 11

Performance DataCooling —

4A7A6024B1 WITH 4TEE3F31A1 AT 800 CFM 2ND STAGEO.D. I.D. TOT. SENS. CAP. AT ENTERING D.B. TEMP. TOTALD.B. W.B. CAP. 72 75 78 80 KW

59 23.0 18.2 20.3 22.4 23.0 1.6985 63 23.8 15.0 17.2 19.4 20.8 1.70

67 25.4 11.9 14.2 16.5 18.0 1.7371 27.2 8.8 11.1 13.4 14.9 1.74

59 21.9 17.8 20.0 21.9 21.9 1.9495 63 22.7 14.6 16.9 19.1 20.5 1.96

67 24.3 11.6 13.9 16.1 17.6 1.9971 26.0 8.4 10.7 13.0 14.6 2.01

59 20.8 17.4 19.6 20.8 20.8 2.22105 63 21.6 14.3 16.5 18.7 20.1 2.23

67 23.1 11.2 13.5 15.8 17.2 2.2771 24.7 8.0 10.3 12.6 14.2 2.29

59 19.6 17.0 19.2 19.6 19.6 2.52115 63 20.3 13.8 16.1 18.3 19.7 2.53

67 21.7 10.7 13.0 15.3 16.8 2.5871 23.2 7.5 9.9 12.2 13.8 2.60

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITY

LOW 700 0.98 0.93HIGH 900 1.01 1.07

NOTE: ALL TABLES ABOVE ARE AT ARI RATING CONDITIONS RATED WITH 25 FEET OF REFRIGERANT LINES.* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE VALID ONLY FOR WET COIL. ALL TEMPERATURES IN DEGREES F.

CORRECTION FACTORS FOR OTHER COMBINATIONS (MULTIPLY DATA BY FACTOR)MBTUH MBTUH SYST

INDOOR MODEL CFM TOT SEN KW4TEE3F37A1 RATED 800 0.98 1.01 0.98

LOW 700 0.97 0.94 0.97HIGH 900 1.00 1.08 0.99

ADD060R9V3+RXC025S3 RATED 800 0.93 0.93 1.00LOW 700 0.91 0.86 0.99HIGH 900 0.94 0.99 1.01

ADD060R9V3+RXC031S3 RATED 800 0.99 1.00 1.00LOW 700 0.97 0.93 0.99HIGH 900 1.00 1.07 1.01

ADD060R9V3+RXC036S3 RATED 800 1.01 1.04 1.00LOW 700 0.99 0.96 0.99HIGH 900 1.02 1.11 1.01

ADD060R9V3+TXH025A4+4AYTXV-3 RATED 800 0.94 0.94 0.99LOW 700 0.92 0.87 0.98HIGH 900 0.96 1.01 1.00

ADD060R9V3+TXH033A4+4AYTXV-3 RATED 800 0.98 0.99 0.98LOW 700 0.96 0.92 0.97HIGH 900 1.00 1.06 1.00

ADD080R9V3+RXC025S3 RATED 800 0.93 0.93 0.99LOW 700 0.91 0.86 0.98HIGH 900 0.94 0.99 1.00

ADD080R9V3+RXC031S3 RATED 800 0.99 1.01 1.00LOW 700 0.97 0.94 0.98HIGH 900 1.00 1.08 1.01

ADD080R9V3+RXC036S3 RATED 800 1.01 1.04 1.00LOW 700 0.98 0.96 0.98HIGH 900 1.02 1.11 1.01

ADD080R9V3+TXH025A4+4AYTXV-3 RATED 800 0.94 0.94 0.98LOW 700 0.92 0.87 0.97HIGH 900 0.95 1.01 0.99

ADD080R9V3+TXH033A4+4AYTXV-3 RATED 800 0.99 0.99 0.99LOW 700 0.97 0.93 0.98HIGH 900 1.00 1.06 1.00

ADY060R9V3+RXC025S3 RATED 800 0.93 0.93 0.99LOW 700 0.92 0.86 0.98HIGH 900 0.94 0.99 1.01

ADY060R9V3+RXC031S3 RATED 800 0.99 1.01 1.00LOW 700 0.97 0.94 0.98HIGH 900 1.01 1.08 1.01

4A7A6024B1

4A7A6024B1 WITH 4TEE3F31A1 AT 600 CFM 1ST STAGEO.D. I.D. TOT. SENS. CAP. AT ENTERING D.B. TEMP. TOTALD.B. W.B. CAP. 72 75 78 80 KW

59 17.3 14.1 15.8 17.3 17.3 1.2385 63 18.0 11.6 13.3 15.0 16.1 1.23

67 19.5 9.3 11.0 12.8 13.9 1.2571 21.0 6.9 8.7 10.4 11.6 1.25

59 16.5 13.8 15.4 16.5 16.5 1.4395 63 17.1 11.3 13.0 14.7 15.8 1.44

67 18.5 9.0 10.7 12.5 13.6 1.4671 20.0 6.6 8.3 10.1 11.3 1.46

59 15.6 13.4 15.1 15.6 15.6 1.67105 63 16.2 11.0 12.7 14.4 15.5 1.67

67 17.5 8.6 10.4 12.2 13.3 1.6971 18.9 6.2 8.0 9.8 11.0 1.70

59 14.6 13.1 14.6 14.6 14.6 1.93115 63 15.2 10.6 12.4 14.1 15.2 1.94

67 16.4 8.3 10.1 11.8 13.0 1.9671 17.8 5.8 7.6 9.4 10.6 1.96

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITY

LOW 550 0.98 0.95HIGH 700 1.02 1.09

NOTE: ALL TABLES ABOVE ARE AT ARI RATING CONDITIONS RATED WITH 25 FEET OF REFRIGERANT LINES.* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE VALID ONLY FOR WET COIL. ALL TEMPERATURES IN DEGREES F.

CORRECTION FACTORS FOR OTHER COMBINATIONS (MULTIPLY DATA BY FACTOR)MBTUH MBTUH SYST

INDOOR MODEL CFM TOT SEN KW4TEE3F37A1 RATED 600 1.00 1.01 0.99

LOW 550 0.98 0.96 0.99HIGH 700 1.02 1.11 1.00

ADD060R9V3+RXC025S3 RATED 600 0.94 0.94 1.00LOW 550 0.93 0.89 0.99HIGH 700 0.96 1.03 1.01

ADD060R9V3+RXC031S3 RATED 600 1.00 1.01 1.00LOW 550 0.98 0.96 0.99HIGH 700 1.02 1.11 1.01

ADD060R9V3+RXC036S3 RATED 600 1.02 1.04 1.00LOW 550 1.00 0.99 0.99HIGH 700 1.04 1.14 1.01

ADD060R9V3+TXH025A4+4AYTXV-3 RATED 600 0.95 0.95 0.99LOW 550 0.93 0.90 0.99HIGH 700 0.97 1.04 1.00

ADD060R9V3+TXH033A4+4AYTXV-3 RATED 600 1.00 1.00 1.00LOW 550 0.99 0.96 0.99HIGH 700 1.03 1.10 1.00

ADD080R9V3+RXC025S3 RATED 600 0.94 0.94 1.00LOW 550 0.93 0.90 0.99HIGH 700 0.96 1.03 1.00

ADD080R9V3+RXC031S3 RATED 600 1.00 1.01 1.00LOW 550 0.98 0.96 0.99HIGH 700 1.02 1.11 1.01

ADD080R9V3+RXC036S3 RATED 600 1.02 1.04 1.00LOW 550 1.00 0.99 0.99HIGH 700 1.04 1.14 1.01

ADD080R9V3+TXH025A4+4AYTXV-3 RATED 600 0.95 0.95 0.99LOW 550 0.93 0.90 0.99HIGH 700 0.97 1.04 1.00

ADD080R9V3+TXH033A4+4AYTXV-3 RATED 600 1.00 1.00 0.99LOW 550 0.99 0.96 0.99HIGH 700 1.03 1.10 1.00

ADY060R9V3+RXC025S3 RATED 600 0.94 0.94 1.00LOW 550 0.93 0.89 0.99HIGH 700 0.96 1.03 1.01

ADY060R9V3+RXC031S3 RATED 600 1.00 1.01 1.00LOW 550 0.98 0.96 0.99HIGH 700 1.02 1.11 1.01

Page 12: ALLEGIANCE 16 MODELS 4A7A6024,036,048 & 060Bfurnacefactorydirect.ca/pdf/4a7a6 Product Data.pdf · ALLEGIANCE® 16 MODELS 4A7A6024,036,048 & 060B SPLIT SYSTEM ... the Unitary Air-Conditioner

12 DATA SUBJECT TO CHANGE WITHOUT NOTICE

PRODUCT DATAAmerican Standard Inc., Tyler, TX 75711-9010

Performance DataCooling —

4A7A6024B1 WITH 4TEE3F31A1 AT 800 CFM 2ND STAGEO.D. I.D. TOT. SENS. CAP. AT ENTERING D.B. TEMP. TOTALD.B. W.B. CAP. 72 75 78 80 KW

59 23.0 18.2 20.3 22.4 23.0 1.6985 63 23.8 15.0 17.2 19.4 20.8 1.70

67 25.4 11.9 14.2 16.5 18.0 1.7371 27.2 8.8 11.1 13.4 14.9 1.74

59 21.9 17.8 20.0 21.9 21.9 1.9495 63 22.7 14.6 16.9 19.1 20.5 1.96

67 24.3 11.6 13.9 16.1 17.6 1.9971 26.0 8.4 10.7 13.0 14.6 2.01

59 20.8 17.4 19.6 20.8 20.8 2.22105 63 21.6 14.3 16.5 18.7 20.1 2.23

67 23.1 11.2 13.5 15.8 17.2 2.2771 24.7 8.0 10.3 12.6 14.2 2.29

59 19.6 17.0 19.2 19.6 19.6 2.52115 63 20.3 13.8 16.1 18.3 19.7 2.53

67 21.7 10.7 13.0 15.3 16.8 2.5871 23.2 7.5 9.9 12.2 13.8 2.60

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITY

LOW 700 0.98 0.93HIGH 900 1.01 1.07

NOTE: ALL TABLES ABOVE ARE AT ARI RATING CONDITIONS RATED WITH 25 FEET OF REFRIGERANT LINES.* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE VALID ONLY FOR WET COIL. ALL TEMPERATURES IN DEGREES F.

CORRECTION FACTORS FOR OTHER COMBINATIONS (MULTIPLY DATA BY FACTOR)MBTUH MBTUH SYST

INDOOR MODEL CFM TOT SEN KWADY060R9V3+RXC036S3 RATED 800 1.00 1.04 1.00

LOW 700 0.98 0.96 0.98HIGH 900 1.02 1.11 1.01

ADY060R9V3+TXH025A4+4AYTXV-3 RATED 800 0.94 0.94 0.98LOW 700 0.92 0.88 0.97HIGH 900 0.96 1.01 1.00

ADY060R9V3+TXH033A4+4AYTXV-3 RATED 800 0.99 0.99 0.99LOW 700 0.97 0.92 0.98HIGH 900 1.00 1.06 1.00

ADY080R9V3+RXC025S3 RATED 800 0.93 0.93 0.99LOW 700 0.92 0.87 0.97HIGH 900 0.95 1.00 1.00

ADY080R9V3+RXC031S3 RATED 800 0.99 1.01 1.00LOW 700 0.97 0.94 0.98HIGH 900 1.01 1.08 1.01

ADY080R9V3+RXC036S3 RATED 800 1.01 1.04 1.00LOW 700 0.99 0.97 0.98HIGH 900 1.03 1.11 1.01

ADY080R9V3+TXH025A4+4AYTXV-3 RATED 800 0.94 0.94 0.98LOW 700 0.92 0.88 0.97HIGH 900 0.96 1.01 1.00

ADY080R9V3+TXH033A4+4AYTXV-3 RATED 800 0.98 0.99 0.99LOW 700 0.96 0.92 0.98HIGH 900 1.00 1.06 1.00

AUD060R9V3+RXC025S3 RATED 800 0.93 0.92 1.01LOW 700 0.91 0.85 0.99HIGH 900 0.94 0.98 1.02

AUD060R9V3+RXC031S3 RATED 800 0.99 1.00 1.01LOW 700 0.97 0.93 1.00HIGH 900 1.00 1.06 1.03

AUD060R9V3+RXC036S3 RATED 800 1.00 1.03 1.01LOW 700 0.98 0.95 0.99HIGH 900 1.02 1.10 1.02

AUD060R9V3+TXH025A4+4AYTXV-3 RATED 800 0.94 0.93 1.00LOW 700 0.92 0.87 0.98HIGH 900 0.95 1.00 1.01

AUD060R9V3+TXH033A4+4AYTXV-3 RATED 800 0.98 0.98 1.00LOW 700 0.96 0.91 0.99HIGH 900 1.00 1.05 1.01

4A7A6024B1

4A7A6024B1 WITH 4TEE3F31A1 AT 600 CFM 1ST STAGEO.D. I.D. TOT. SENS. CAP. AT ENTERING D.B. TEMP. TOTALD.B. W.B. CAP. 72 75 78 80 KW

59 17.3 14.1 15.8 17.3 17.3 1.2385 63 18.0 11.6 13.3 15.0 16.1 1.23

67 19.5 9.3 11.0 12.8 13.9 1.2571 21.0 6.9 8.7 10.4 11.6 1.25

59 16.5 13.8 15.4 16.5 16.5 1.4395 63 17.1 11.3 13.0 14.7 15.8 1.44

67 18.5 9.0 10.7 12.5 13.6 1.4671 20.0 6.6 8.3 10.1 11.3 1.46

59 15.6 13.4 15.1 15.6 15.6 1.67105 63 16.2 11.0 12.7 14.4 15.5 1.67

67 17.5 8.6 10.4 12.2 13.3 1.6971 18.9 6.2 8.0 9.8 11.0 1.70

59 14.6 13.1 14.6 14.6 14.6 1.93115 63 15.2 10.6 12.4 14.1 15.2 1.94

67 16.4 8.3 10.1 11.8 13.0 1.9671 17.8 5.8 7.6 9.4 10.6 1.96

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITY

LOW 550 0.98 0.95HIGH 700 1.02 1.09

NOTE: ALL TABLES ABOVE ARE AT ARI RATING CONDITIONS RATED WITH 25 FEET OF REFRIGERANT LINES.* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE VALID ONLY FOR WET COIL. ALL TEMPERATURES IN DEGREES F.

CORRECTION FACTORS FOR OTHER COMBINATIONS (MULTIPLY DATA BY FACTOR)MBTUH MBTUH SYST

INDOOR MODEL CFM TOT SEN KWADY060R9V3+RXC036S3 RATED 600 1.02 1.04 1.00

LOW 550 1.00 0.99 0.99HIGH 700 1.04 1.14 1.01

ADY060R9V3+TXH025A4+4AYTXV-3 RATED 600 0.95 0.95 0.99LOW 550 0.93 0.90 0.99HIGH 700 0.97 1.04 1.00

ADY060R9V3+TXH033A4+4AYTXV-3 RATED 600 1.00 1.01 0.99LOW 550 0.99 0.96 0.99HIGH 700 1.03 1.10 1.00

ADY080R9V3+RXC025S3 RATED 600 0.94 0.94 0.99LOW 550 0.93 0.90 0.99HIGH 700 0.96 1.04 1.00

ADY080R9V3+RXC031S3 RATED 600 1.00 1.01 1.00LOW 550 0.98 0.96 0.99HIGH 700 1.02 1.11 1.01

ADY080R9V3+RXC036S3 RATED 600 1.02 1.04 1.00LOW 550 1.00 0.99 0.99HIGH 700 1.04 1.14 1.01

ADY080R9V3+TXH025A4+4AYTXV-3 RATED 600 0.95 0.95 0.99LOW 550 0.93 0.90 0.99HIGH 700 0.97 1.04 1.00

ADY080R9V3+TXH033A4+4AYTXV-3 RATED 600 1.00 1.00 0.99LOW 550 0.99 0.96 0.99HIGH 700 1.03 1.10 1.00

AUD060R9V3+RXC025S3 RATED 600 0.94 0.93 1.01LOW 550 0.93 0.89 1.00HIGH 700 0.96 1.02 1.02

AUD060R9V3+RXC031S3 RATED 600 1.00 1.01 1.01LOW 550 0.98 0.96 1.00HIGH 700 1.02 1.10 1.02

AUD060R9V3+RXC036S3 RATED 600 1.02 1.03 1.01LOW 550 1.00 0.98 1.00HIGH 700 1.04 1.13 1.02

AUD060R9V3+TXH025A4+4AYTXV-3 RATED 600 0.95 0.95 1.00LOW 550 0.93 0.90 0.99HIGH 700 0.97 1.04 1.01

AUD060R9V3+TXH033A4+4AYTXV-3 RATED 600 1.00 1.00 1.00LOW 550 0.99 0.95 1.00HIGH 700 1.03 1.09 1.01

Page 13: ALLEGIANCE 16 MODELS 4A7A6024,036,048 & 060Bfurnacefactorydirect.ca/pdf/4a7a6 Product Data.pdf · ALLEGIANCE® 16 MODELS 4A7A6024,036,048 & 060B SPLIT SYSTEM ... the Unitary Air-Conditioner

PRODUCT DATAAmerican Standard Inc., Tyler, TX 75711-9010

DATA SUBJECT TO CHANGE WITHOUT NOTICE 13

Performance DataCooling —

4A7A6024B1 WITH 4TEE3F31A1 AT 800 CFM 2ND STAGEO.D. I.D. TOT. SENS. CAP. AT ENTERING D.B. TEMP. TOTALD.B. W.B. CAP. 72 75 78 80 KW

59 23.0 18.2 20.3 22.4 23.0 1.6985 63 23.8 15.0 17.2 19.4 20.8 1.70

67 25.4 11.9 14.2 16.5 18.0 1.7371 27.2 8.8 11.1 13.4 14.9 1.74

59 21.9 17.8 20.0 21.9 21.9 1.9495 63 22.7 14.6 16.9 19.1 20.5 1.96

67 24.3 11.6 13.9 16.1 17.6 1.9971 26.0 8.4 10.7 13.0 14.6 2.01

59 20.8 17.4 19.6 20.8 20.8 2.22105 63 21.6 14.3 16.5 18.7 20.1 2.23

67 23.1 11.2 13.5 15.8 17.2 2.2771 24.7 8.0 10.3 12.6 14.2 2.29

59 19.6 17.0 19.2 19.6 19.6 2.52115 63 20.3 13.8 16.1 18.3 19.7 2.53

67 21.7 10.7 13.0 15.3 16.8 2.5871 23.2 7.5 9.9 12.2 13.8 2.60

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITY

LOW 700 0.98 0.93HIGH 900 1.01 1.07

NOTE: ALL TABLES ABOVE ARE AT ARI RATING CONDITIONS RATED WITH 25 FEET OF REFRIGERANT LINES.* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE VALID ONLY FOR WET COIL. ALL TEMPERATURES IN DEGREES F.

CORRECTION FACTORS FOR OTHER COMBINATIONS (MULTIPLY DATA BY FACTOR)MBTUH MBTUH SYST

INDOOR MODEL CFM TOT SEN KWAUD080R9V3+RXC025S3 RATED 800 0.93 0.92 1.00

LOW 700 0.92 0.86 0.99HIGH 900 0.94 0.99 1.01

AUD080R9V3+RXC031S3 RATED 800 0.99 1.00 1.01LOW 700 0.97 0.93 0.99HIGH 900 1.00 1.07 1.02

AUD080R9V3+RXC036S3 RATED 800 1.00 1.03 1.00LOW 700 0.98 0.96 0.99HIGH 900 1.02 1.10 1.01

AUD080R9V3+TXH025A4+4AYTXV-3 RATED 800 0.94 0.94 0.99LOW 700 0.92 0.87 0.98HIGH 900 0.95 1.00 1.00

AUD080R9V3+TXH033A4+4AYTXV-3 RATED 800 0.99 0.99 1.00LOW 700 0.97 0.92 0.99HIGH 900 1.00 1.06 1.01

AUD100R9V3+RXC025S3 RATED 800 0.93 0.92 1.01LOW 700 0.91 0.85 0.99HIGH 900 0.94 0.98 1.02

AUD100R9V3+RXC031S3 RATED 800 0.98 1.00 1.01LOW 700 0.96 0.92 0.99HIGH 900 1.00 1.06 1.02

AUD100R9V3+RXC036S3 RATED 800 1.01 1.03 1.01LOW 700 0.99 0.96 1.00HIGH 900 1.02 1.10 1.02

AUD100R9V3+TXH025A4+4AYTXV-3 RATED 800 0.93 0.93 0.99LOW 700 0.92 0.86 0.98HIGH 900 0.95 1.00 1.00

AUD100R9V3+TXH033A4+4AYTXV-3 RATED 800 0.98 0.99 1.00LOW 700 0.97 0.92 0.99HIGH 900 1.00 1.05 1.01

AUY060R9V3+RXC025S3 RATED 800 0.93 0.92 1.00LOW 700 0.91 0.86 0.99HIGH 900 0.94 0.99 1.02

AUY060R9V3+RXC031S3 RATED 800 0.99 1.00 1.01LOW 700 0.97 0.93 1.00HIGH 900 1.00 1.07 1.02

AUY060R9V3+RXC036S3 RATED 800 1.01 1.03 1.00LOW 700 0.99 0.96 0.99HIGH 900 1.02 1.10 1.01

4A7A6024B1

4A7A6024B1 WITH 4TEE3F31A1 AT 600 CFM 1ST STAGEO.D. I.D. TOT. SENS. CAP. AT ENTERING D.B. TEMP. TOTALD.B. W.B. CAP. 72 75 78 80 KW

59 17.3 14.1 15.8 17.3 17.3 1.2385 63 18.0 11.6 13.3 15.0 16.1 1.23

67 19.5 9.3 11.0 12.8 13.9 1.2571 21.0 6.9 8.7 10.4 11.6 1.25

59 16.5 13.8 15.4 16.5 16.5 1.4395 63 17.1 11.3 13.0 14.7 15.8 1.44

67 18.5 9.0 10.7 12.5 13.6 1.4671 20.0 6.6 8.3 10.1 11.3 1.46

59 15.6 13.4 15.1 15.6 15.6 1.67105 63 16.2 11.0 12.7 14.4 15.5 1.67

67 17.5 8.6 10.4 12.2 13.3 1.6971 18.9 6.2 8.0 9.8 11.0 1.70

59 14.6 13.1 14.6 14.6 14.6 1.93115 63 15.2 10.6 12.4 14.1 15.2 1.94

67 16.4 8.3 10.1 11.8 13.0 1.9671 17.8 5.8 7.6 9.4 10.6 1.96

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITY

LOW 550 0.98 0.95HIGH 700 1.02 1.09

NOTE: ALL TABLES ABOVE ARE AT ARI RATING CONDITIONS RATED WITH 25 FEET OF REFRIGERANT LINES.* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE VALID ONLY FOR WET COIL. ALL TEMPERATURES IN DEGREES F.

CORRECTION FACTORS FOR OTHER COMBINATIONS (MULTIPLY DATA BY FACTOR)MBTUH MBTUH SYST

INDOOR MODEL CFM TOT SEN KWAUD080R9V3+RXC025S3 RATED 600 0.94 0.94 1.00

LOW 550 0.93 0.89 1.00HIGH 700 0.96 1.03 1.01

AUD080R9V3+RXC031S3 RATED 600 1.00 1.01 1.00LOW 550 0.98 0.96 1.00HIGH 700 1.02 1.11 1.01

AUD080R9V3+RXC036S3 RATED 600 1.02 1.04 1.00LOW 550 1.00 0.99 1.00HIGH 700 1.04 1.13 1.01

AUD080R9V3+TXH025A4+4AYTXV-3 RATED 600 0.95 0.95 1.00LOW 550 0.93 0.90 0.99HIGH 700 0.97 1.04 1.00

AUD080R9V3+TXH033A4+4AYTXV-3 RATED 600 1.00 1.00 1.00LOW 550 0.99 0.95 0.99HIGH 700 1.03 1.10 1.01

AUD100R9V3+RXC025S3 RATED 600 0.94 0.93 1.01LOW 550 0.93 0.89 1.00HIGH 700 0.96 1.02 1.02

AUD100R9V3+RXC031S3 RATED 600 1.00 1.01 1.01LOW 550 0.98 0.96 1.00HIGH 700 1.02 1.10 1.02

AUD100R9V3+RXC036S3 RATED 600 1.02 1.03 1.01LOW 550 1.00 0.98 1.00HIGH 700 1.04 1.13 1.02

AUD100R9V3+TXH025A4+4AYTXV-3 RATED 600 0.95 0.95 1.00LOW 550 0.93 0.90 0.99HIGH 700 0.97 1.04 1.01

AUD100R9V3+TXH033A4+4AYTXV-3 RATED 600 1.00 1.00 1.00LOW 550 0.99 0.95 0.99HIGH 700 1.03 1.09 1.01

AUY060R9V3+RXC025S3 RATED 600 0.94 0.94 1.00LOW 550 0.93 0.89 1.00HIGH 700 0.96 1.03 1.01

AUY060R9V3+RXC031S3 RATED 600 1.00 1.01 1.00LOW 550 0.98 0.96 1.00HIGH 700 1.02 1.10 1.01

AUY060R9V3+RXC036S3 RATED 600 1.02 1.03 1.00LOW 550 1.00 0.98 1.00HIGH 700 1.04 1.13 1.01

Page 14: ALLEGIANCE 16 MODELS 4A7A6024,036,048 & 060Bfurnacefactorydirect.ca/pdf/4a7a6 Product Data.pdf · ALLEGIANCE® 16 MODELS 4A7A6024,036,048 & 060B SPLIT SYSTEM ... the Unitary Air-Conditioner

14 DATA SUBJECT TO CHANGE WITHOUT NOTICE

PRODUCT DATAAmerican Standard Inc., Tyler, TX 75711-9010

Performance DataCooling —

4A7A6024B1 WITH 4TEE3F31A1 AT 800 CFM 2ND STAGEO.D. I.D. TOT. SENS. CAP. AT ENTERING D.B. TEMP. TOTALD.B. W.B. CAP. 72 75 78 80 KW

59 23.0 18.2 20.3 22.4 23.0 1.6985 63 23.8 15.0 17.2 19.4 20.8 1.70

67 25.4 11.9 14.2 16.5 18.0 1.7371 27.2 8.8 11.1 13.4 14.9 1.74

59 21.9 17.8 20.0 21.9 21.9 1.9495 63 22.7 14.6 16.9 19.1 20.5 1.96

67 24.3 11.6 13.9 16.1 17.6 1.9971 26.0 8.4 10.7 13.0 14.6 2.01

59 20.8 17.4 19.6 20.8 20.8 2.22105 63 21.6 14.3 16.5 18.7 20.1 2.23

67 23.1 11.2 13.5 15.8 17.2 2.2771 24.7 8.0 10.3 12.6 14.2 2.29

59 19.6 17.0 19.2 19.6 19.6 2.52115 63 20.3 13.8 16.1 18.3 19.7 2.53

67 21.7 10.7 13.0 15.3 16.8 2.5871 23.2 7.5 9.9 12.2 13.8 2.60

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITY

LOW 700 0.98 0.93HIGH 900 1.01 1.07

NOTE: ALL TABLES ABOVE ARE AT ARI RATING CONDITIONS RATED WITH 25 FEET OF REFRIGERANT LINES.* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE VALID ONLY FOR WET COIL. ALL TEMPERATURES IN DEGREES F.

CORRECTION FACTORS FOR OTHER COMBINATIONS (MULTIPLY DATA BY FACTOR)MBTUH MBTUH SYST

INDOOR MODEL CFM TOT SEN KWAUY060R9V3+TXH025A4+4AYTXV-3 RATED 800 0.94 0.94 0.99

LOW 700 0.92 0.87 0.98HIGH 900 0.95 1.00 1.01

AUY060R9V3+TXH033A4+4AYTXV-3 RATED 800 0.98 0.99 1.00LOW 700 0.96 0.92 0.98HIGH 900 1.00 1.05 1.01

AUY080R9V3+RXC025S3 RATED 800 0.94 0.93 1.00LOW 700 0.92 0.86 0.98HIGH 900 0.95 1.00 1.01

AUY080R9V3+RXC031S3 RATED 800 0.99 1.01 1.00LOW 700 0.97 0.93 0.98HIGH 900 1.00 1.07 1.01

AUY080R9V3+RXC036S3 RATED 800 1.01 1.04 1.00LOW 700 0.99 0.97 0.98HIGH 900 1.03 1.11 1.01

AUY080R9V3+TXH025A4+4AYTXV-3 RATED 800 0.94 0.94 0.99LOW 700 0.93 0.87 0.97HIGH 900 0.96 1.01 1.00

AUY080R9V3+TXH033A4+4AYTXV-3 RATED 800 0.98 0.99 0.99LOW 700 0.96 0.92 0.98HIGH 900 1.00 1.06 1.00

4A7A6024B1

4A7A6024B1 WITH 4TEE3F31A1 AT 600 CFM 1ST STAGEO.D. I.D. TOT. SENS. CAP. AT ENTERING D.B. TEMP. TOTALD.B. W.B. CAP. 72 75 78 80 KW

59 17.3 14.1 15.8 17.3 17.3 1.2385 63 18.0 11.6 13.3 15.0 16.1 1.23

67 19.5 9.3 11.0 12.8 13.9 1.2571 21.0 6.9 8.7 10.4 11.6 1.25

59 16.5 13.8 15.4 16.5 16.5 1.4395 63 17.1 11.3 13.0 14.7 15.8 1.44

67 18.5 9.0 10.7 12.5 13.6 1.4671 20.0 6.6 8.3 10.1 11.3 1.46

59 15.6 13.4 15.1 15.6 15.6 1.67105 63 16.2 11.0 12.7 14.4 15.5 1.67

67 17.5 8.6 10.4 12.2 13.3 1.6971 18.9 6.2 8.0 9.8 11.0 1.70

59 14.6 13.1 14.6 14.6 14.6 1.93115 63 15.2 10.6 12.4 14.1 15.2 1.94

67 16.4 8.3 10.1 11.8 13.0 1.9671 17.8 5.8 7.6 9.4 10.6 1.96

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITY

LOW 550 0.98 0.95HIGH 700 1.02 1.09

NOTE: ALL TABLES ABOVE ARE AT ARI RATING CONDITIONS RATED WITH 25 FEET OF REFRIGERANT LINES.* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE VALID ONLY FOR WET COIL. ALL TEMPERATURES IN DEGREES F.

CORRECTION FACTORS FOR OTHER COMBINATIONS (MULTIPLY DATA BY FACTOR)MBTUH MBTUH SYST

INDOOR MODEL CFM TOT SEN KWAUY060R9V3+TXH025A4+4AYTXV-3 RATED 600 0.95 0.95 1.00

LOW 550 0.93 0.90 0.99HIGH 700 0.97 1.04 1.01

AUY060R9V3+TXH033A4+4AYTXV-3 RATED 600 1.00 1.00 1.00LOW 550 0.99 0.95 0.99HIGH 700 1.03 1.09 1.01

AUY080R9V3+RXC025S3 RATED 600 0.94 0.94 1.00LOW 550 0.93 0.90 0.99HIGH 700 0.96 1.03 1.01

AUY080R9V3+RXC031S3 RATED 600 1.00 1.01 1.00LOW 550 0.98 0.96 0.99HIGH 700 1.02 1.11 1.01

AUY080R9V3+RXC036S3 RATED 600 1.02 1.04 1.00LOW 550 1.00 0.99 0.99HIGH 700 1.04 1.14 1.01

AUY080R9V3+TXH025A4+4AYTXV-3 RATED 600 0.95 0.95 0.99LOW 550 0.93 0.90 0.99HIGH 700 0.97 1.04 1.00

AUY080R9V3+TXH033A4+4AYTXV-3 RATED 600 1.00 1.00 0.99LOW 550 0.99 0.96 0.99HIGH 700 1.03 1.10 1.00

Page 15: ALLEGIANCE 16 MODELS 4A7A6024,036,048 & 060Bfurnacefactorydirect.ca/pdf/4a7a6 Product Data.pdf · ALLEGIANCE® 16 MODELS 4A7A6024,036,048 & 060B SPLIT SYSTEM ... the Unitary Air-Conditioner

PRODUCT DATAAmerican Standard Inc., Tyler, TX 75711-9010

DATA SUBJECT TO CHANGE WITHOUT NOTICE 15

Performance DataCooling —

4A7A6036B1 WITH 4TEE3F40A1 AT 900 CFM 1ST STAGEO.D. I.D. TOT. SENS. CAP. AT ENTERING D.B. TEMP. TOTALD.B. W.B. CAP. 72 75 78 80 KW

59 25.3 21.5 24.1 25.3 25.3 1.6485 63 25.6 17.3 20.0 22.7 24.5 1.64

67 27.6 13.6 16.3 19.1 20.9 1.6671 29.8 9.8 12.6 15.3 17.2 1.65

59 24.0 21.0 23.6 24.0 24.0 1.8995 63 24.3 16.8 19.5 22.2 24.0 1.90

67 26.2 13.1 15.8 18.6 20.4 1.9171 28.3 9.3 12.1 14.8 16.7 1.91

59 22.6 20.4 22.6 22.6 22.6 2.17105 63 22.9 16.3 19.0 21.7 22.9 2.17

67 24.7 12.6 15.3 18.1 19.9 2.1971 26.7 8.8 11.6 14.4 16.2 2.18

59 21.2 19.9 21.2 21.2 21.2 2.46115 63 21.5 15.8 18.5 21.2 21.5 2.47

67 23.2 12.0 14.8 17.6 19.4 2.4971 25.0 8.3 11.0 13.8 15.7 2.48

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITY

LOW 800 0.98 0.93HIGH 1000 1.01 1.06

NOTE: ALL TABLES ABOVE ARE AT ARI RATING CONDITIONS RATED WITH 25 FEET OF REFRIGERANT LINES.* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE VALID ONLY FOR WET COIL. ALL TEMPERATURES IN DEGREES F.

CORRECTION FACTORS FOR OTHER COMBINATIONS (MULTIPLY DATA BY FACTOR)MBTUH MBTUH SYST

INDOOR MODEL CFM TOT SEN KW4TEE3F37A1 RATED 900 0.94 0.94 1.00

LOW 800 0.92 0.87 0.99HIGH 1000 0.95 0.99 1.01

ADD060R9V3+RXC031S3 RATED 900 0.94 0.92 1.03LOW 800 0.92 0.86 1.02HIGH 1000 0.95 0.98 1.04

ADD060R9V3+RXC036S3 RATED 900 0.96 0.96 1.02LOW 800 0.95 0.90 1.01HIGH 1000 0.98 1.02 1.03

ADD060R9V3+TXH033A4+4AYTXV-3 RATED 900 0.94 0.92 1.01LOW 800 0.92 0.86 1.00HIGH 1000 0.95 0.97 1.02

ADD060R9V3+TXH041A4+4AYTXV-3 RATED 900 0.95 0.95 1.01LOW 800 0.94 0.89 1.00HIGH 1000 0.97 1.01 1.02

ADD080R9V3+RXC031S3 RATED 900 0.94 0.93 1.02LOW 800 0.92 0.87 1.01HIGH 1000 0.96 0.99 1.03

ADD080R9V3+RXC036S3 RATED 900 0.96 0.96 1.02LOW 800 0.95 0.90 1.01HIGH 1000 0.98 1.02 1.03

ADD080R9V3+TXH033A4+4AYTXV-3 RATED 900 0.94 0.92 1.01LOW 800 0.92 0.86 1.00HIGH 1000 0.95 0.98 1.02

ADD080R9V3+TXH041A4+4AYTXV-3 RATED 900 0.95 0.95 1.01LOW 800 0.94 0.89 1.00HIGH 1000 0.97 1.01 1.02

ADD100R9V5+RXC037S3 RATED 900 0.97 0.97 1.00LOW 800 0.95 0.91 0.99HIGH 1000 0.99 1.04 1.00

ADY060R9V3+RXC036S3 RATED 900 0.96 0.96 1.02LOW 800 0.95 0.90 1.01HIGH 1000 0.98 1.02 1.03

ADY080R9V3+RXC031S3 RATED 900 0.94 0.92 1.03LOW 800 0.92 0.86 1.02HIGH 1000 0.95 0.98 1.04

ADY080R9V3+RXC036S3 RATED 900 0.96 0.95 1.03LOW 800 0.94 0.89 1.02HIGH 1000 0.98 1.02 1.04

4A7A6036B1

4A7A6036B1 WITH 4TEE3F40A1 AT 1200 CFM 2ND STAGEO.D. I.D. TOT. SENS. CAP. AT ENTERING D.B. TEMP. TOTALD.B. W.B. CAP. 72 75 78 80 KW

59 35.6 28.5 31.9 35.3 35.6 2.5785 63 36.7 23.4 26.9 30.3 32.6 2.58

67 39.3 18.5 22.1 25.6 28.0 2.6271 42.2 13.7 17.2 20.8 23.2 2.64

59 33.9 27.9 31.3 33.9 33.9 2.8895 63 35.0 22.7 26.2 29.7 32.0 2.89

67 37.5 17.9 21.5 25.0 27.4 2.9371 40.2 13.0 16.6 20.2 22.5 2.95

59 32.1 27.2 30.6 32.1 32.1 3.20105 63 33.1 22.1 25.6 29.0 31.3 3.21

67 35.4 17.2 20.8 24.4 26.7 3.2571 38.0 12.3 15.9 19.5 21.9 3.27

59 30.0 26.5 29.8 30.0 30.0 3.53115 63 31.0 21.3 24.9 28.3 30.6 3.54

67 33.2 16.5 20.1 23.6 25.9 3.5971 35.6 11.5 15.1 18.7 21.2 3.62

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITY

LOW 1050 0.98 0.93HIGH 1350 1.02 1.06

NOTE: ALL TABLES ABOVE ARE AT ARI RATING CONDITIONS RATED WITH 25 FEET OF REFRIGERANT LINES.* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE VALID ONLY FOR WET COIL. ALL TEMPERATURES IN DEGREES F.

CORRECTION FACTORS FOR OTHER COMBINATIONS (MULTIPLY DATA BY FACTOR)MBTUH MBTUH SYST

INDOOR MODEL CFM TOT SEN KW4TEE3F37A1 RATED 1200 0.94 0.92 1.01

LOW 1050 0.92 0.85 0.99HIGH 1350 0.95 0.97 1.02

ADD060R9V3+RXC031S3 RATED 1200 0.93 0.90 1.04LOW 1050 0.92 0.84 1.02HIGH 1350 0.95 0.95 1.05

ADD060R9V3+RXC036S3 RATED 1200 0.96 0.94 1.04LOW 1050 0.94 0.88 1.02HIGH 1350 0.97 1.00 1.06

ADD060R9V3+TXH033A4+4AYTXV-3 RATED 1200 0.93 0.89 1.03LOW 1050 0.92 0.83 1.01HIGH 1350 0.95 0.94 1.05

ADD060R9V3+TXH041A4+4AYTXV-3 RATED 1200 0.96 0.94 1.03LOW 1050 0.94 0.87 1.01HIGH 1350 0.97 1.00 1.04

ADD080R9V3+RXC031S3 RATED 1200 0.94 0.91 1.02LOW 1050 0.92 0.85 1.01HIGH 1350 0.95 0.96 1.04

ADD080R9V3+RXC036S3 RATED 1200 0.96 0.95 1.03LOW 1050 0.95 0.89 1.02HIGH 1350 0.98 1.01 1.05

ADD080R9V3+TXH033A4+4AYTXV-3 RATED 1200 0.94 0.89 1.03LOW 1050 0.92 0.83 1.02HIGH 1350 0.95 0.95 1.05

ADD080R9V3+TXH041A4+4AYTXV-3 RATED 1200 0.96 0.94 1.02LOW 1050 0.94 0.88 1.00HIGH 1350 0.97 1.00 1.03

ADD100R9V5+RXC037S3 RATED 1200 0.97 0.97 1.01LOW 1050 0.95 0.90 0.99HIGH 1350 0.98 1.03 1.02

ADY060R9V3+RXC036S3 RATED 1200 0.96 0.95 1.03LOW 1050 0.95 0.88 1.02HIGH 1350 0.98 1.01 1.05

ADY080R9V3+RXC031S3 RATED 1200 0.93 0.89 1.04LOW 1050 0.91 0.83 1.03HIGH 1350 0.94 0.95 1.06

ADY080R9V3+RXC036S3 RATED 1200 0.95 0.93 1.05LOW 1050 0.93 0.87 1.03HIGH 1350 0.96 0.99 1.07

Page 16: ALLEGIANCE 16 MODELS 4A7A6024,036,048 & 060Bfurnacefactorydirect.ca/pdf/4a7a6 Product Data.pdf · ALLEGIANCE® 16 MODELS 4A7A6024,036,048 & 060B SPLIT SYSTEM ... the Unitary Air-Conditioner

16 DATA SUBJECT TO CHANGE WITHOUT NOTICE

PRODUCT DATAAmerican Standard Inc., Tyler, TX 75711-9010

Performance DataCooling —

4A7A6036B1 WITH 4TEE3F40A1 AT 900 CFM 1ST STAGEO.D. I.D. TOT. SENS. CAP. AT ENTERING D.B. TEMP. TOTALD.B. W.B. CAP. 72 75 78 80 KW

59 25.3 21.5 24.1 25.3 25.3 1.6485 63 25.6 17.3 20.0 22.7 24.5 1.64

67 27.6 13.6 16.3 19.1 20.9 1.6671 29.8 9.8 12.6 15.3 17.2 1.65

59 24.0 21.0 23.6 24.0 24.0 1.8995 63 24.3 16.8 19.5 22.2 24.0 1.90

67 26.2 13.1 15.8 18.6 20.4 1.9171 28.3 9.3 12.1 14.8 16.7 1.91

59 22.6 20.4 22.6 22.6 22.6 2.17105 63 22.9 16.3 19.0 21.7 22.9 2.17

67 24.7 12.6 15.3 18.1 19.9 2.1971 26.7 8.8 11.6 14.4 16.2 2.18

59 21.2 19.9 21.2 21.2 21.2 2.46115 63 21.5 15.8 18.5 21.2 21.5 2.47

67 23.2 12.0 14.8 17.6 19.4 2.4971 25.0 8.3 11.0 13.8 15.7 2.48

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITY

LOW 800 0.98 0.93HIGH 1000 1.01 1.06

NOTE: ALL TABLES ABOVE ARE AT ARI RATING CONDITIONS RATED WITH 25 FEET OF REFRIGERANT LINES.* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE VALID ONLY FOR WET COIL. ALL TEMPERATURES IN DEGREES F.

CORRECTION FACTORS FOR OTHER COMBINATIONS (MULTIPLY DATA BY FACTOR)MBTUH MBTUH SYST

INDOOR MODEL CFM TOT SEN KWADY080R9V3+TXH033A4+4AYTXV-3 RATED 900 0.94 0.91 1.02

LOW 800 0.92 0.85 1.01HIGH 1000 0.95 0.97 1.03

ADY100R9V4+RXC037S3 RATED 900 0.97 0.97 1.01LOW 800 0.95 0.90 1.00HIGH 1000 0.98 1.03 1.02

ADY100R9V4+TXH033A4+4AYTXV-3 RATED 900 0.94 0.92 1.01LOW 800 0.92 0.86 1.00HIGH 1000 0.95 0.98 1.02

ADY100R9V4+TXH041A4+4AYTXV-3 RATED 900 0.95 0.95 1.01LOW 800 0.94 0.89 1.00HIGH 1000 0.97 1.01 1.01

AUD060R9V3+RXC031S3 RATED 900 0.94 0.92 1.04LOW 800 0.92 0.86 1.02HIGH 1000 0.95 0.98 1.05

AUD060R9V3+RXC036S3 RATED 900 0.96 0.95 1.03LOW 800 0.94 0.89 1.02HIGH 1000 0.98 1.01 1.04

AUD060R9V3+TXH033A4+4AYTXV-3 RATED 900 0.94 0.91 1.02LOW 800 0.92 0.85 1.01HIGH 1000 0.95 0.97 1.03

AUD060R9V3+TXH041A4+4AYTXV-3 RATED 900 0.95 0.94 1.02LOW 800 0.93 0.88 1.01HIGH 1000 0.96 1.00 1.03

AUD080R9V3+RXC031S3 RATED 900 0.94 0.92 1.03LOW 800 0.92 0.86 1.02HIGH 1000 0.95 0.98 1.04

AUD080R9V3+RXC036S3 RATED 900 0.96 0.96 1.03LOW 800 0.94 0.89 1.02HIGH 1000 0.98 1.02 1.04

AUD080R9V3+TXH033A4+4AYTXV-3 RATED 900 0.94 0.91 1.02LOW 800 0.92 0.85 1.01HIGH 1000 0.95 0.97 1.03

AUD080R9V3+TXH041A4+4AYTXV-3 RATED 900 0.95 0.95 1.02LOW 800 0.93 0.89 1.01HIGH 1000 0.97 1.01 1.02

AUD080R9V4+RXC037S3 RATED 900 0.97 0.97 1.00LOW 800 0.95 0.91 0.99HIGH 1000 0.99 1.04 1.01

4A7A6036B1

4A7A6036B1 WITH 4TEE3F40A1 AT 1200 CFM 2ND STAGEO.D. I.D. TOT. SENS. CAP. AT ENTERING D.B. TEMP. TOTALD.B. W.B. CAP. 72 75 78 80 KW

59 35.6 28.5 31.9 35.3 35.6 2.5785 63 36.7 23.4 26.9 30.3 32.6 2.58

67 39.3 18.5 22.1 25.6 28.0 2.6271 42.2 13.7 17.2 20.8 23.2 2.64

59 33.9 27.9 31.3 33.9 33.9 2.8895 63 35.0 22.7 26.2 29.7 32.0 2.89

67 37.5 17.9 21.5 25.0 27.4 2.9371 40.2 13.0 16.6 20.2 22.5 2.95

59 32.1 27.2 30.6 32.1 32.1 3.20105 63 33.1 22.1 25.6 29.0 31.3 3.21

67 35.4 17.2 20.8 24.4 26.7 3.2571 38.0 12.3 15.9 19.5 21.9 3.27

59 30.0 26.5 29.8 30.0 30.0 3.53115 63 31.0 21.3 24.9 28.3 30.6 3.54

67 33.2 16.5 20.1 23.6 25.9 3.5971 35.6 11.5 15.1 18.7 21.2 3.62

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITY

LOW 1050 0.98 0.93HIGH 1350 1.02 1.06

NOTE: ALL TABLES ABOVE ARE AT ARI RATING CONDITIONS RATED WITH 25 FEET OF REFRIGERANT LINES.* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE VALID ONLY FOR WET COIL. ALL TEMPERATURES IN DEGREES F.

CORRECTION FACTORS FOR OTHER COMBINATIONS (MULTIPLY DATA BY FACTOR)MBTUH MBTUH SYST

INDOOR MODEL CFM TOT SEN KWADY080R9V3+TXH033A4+4AYTXV-3 RATED 1200 0.93 0.88 1.05

LOW 1050 0.91 0.82 1.03HIGH 1350 0.94 0.93 1.07

ADY100R9V4+RXC037S3 RATED 1200 0.97 0.96 1.03LOW 1050 0.95 0.89 1.01HIGH 1350 0.98 1.02 1.04

ADY100R9V4+TXH033A4+4AYTXV-3 RATED 1200 0.94 0.89 1.03LOW 1050 0.92 0.83 1.01HIGH 1350 0.95 0.95 1.04

ADY100R9V4+TXH041A4+4AYTXV-3 RATED 1200 0.96 0.94 1.02LOW 1050 0.94 0.88 1.01HIGH 1350 0.97 1.00 1.04

AUD060R9V3+RXC031S3 RATED 1200 0.93 0.89 1.04LOW 1050 0.91 0.83 1.02HIGH 1350 0.94 0.94 1.06

AUD060R9V3+RXC036S3 RATED 1200 0.96 0.93 1.05LOW 1050 0.94 0.87 1.03HIGH 1350 0.97 0.99 1.07

AUD060R9V3+TXH033A4+4AYTXV-3 RATED 1200 0.93 0.87 1.05LOW 1050 0.91 0.82 1.03HIGH 1350 0.94 0.93 1.07

AUD060R9V3+TXH041A4+4AYTXV-3 RATED 1200 0.95 0.92 1.04LOW 1050 0.93 0.86 1.02HIGH 1350 0.96 0.98 1.06

AUD080R9V3+RXC031S3 RATED 1200 0.94 0.89 1.05LOW 1050 0.92 0.83 1.03HIGH 1350 0.95 0.95 1.07

AUD080R9V3+RXC036S3 RATED 1200 0.96 0.94 1.04LOW 1050 0.94 0.87 1.03HIGH 1350 0.97 1.00 1.06

AUD080R9V3+TXH033A4+4AYTXV-3 RATED 1200 0.93 0.88 1.04LOW 1050 0.91 0.82 1.03HIGH 1350 0.94 0.93 1.06

AUD080R9V3+TXH041A4+4AYTXV-3 RATED 1200 0.95 0.93 1.03LOW 1050 0.93 0.87 1.01HIGH 1350 0.96 0.99 1.05

AUD080R9V4+RXC037S3 RATED 1200 0.97 0.97 1.01LOW 1050 0.95 0.90 1.00HIGH 1350 0.99 1.03 1.03

Page 17: ALLEGIANCE 16 MODELS 4A7A6024,036,048 & 060Bfurnacefactorydirect.ca/pdf/4a7a6 Product Data.pdf · ALLEGIANCE® 16 MODELS 4A7A6024,036,048 & 060B SPLIT SYSTEM ... the Unitary Air-Conditioner

PRODUCT DATAAmerican Standard Inc., Tyler, TX 75711-9010

DATA SUBJECT TO CHANGE WITHOUT NOTICE 17

Performance DataCooling —

4A7A6036B1 WITH 4TEE3F40A1 AT 900 CFM 1ST STAGEO.D. I.D. TOT. SENS. CAP. AT ENTERING D.B. TEMP. TOTALD.B. W.B. CAP. 72 75 78 80 KW

59 25.3 21.5 24.1 25.3 25.3 1.6485 63 25.6 17.3 20.0 22.7 24.5 1.64

67 27.6 13.6 16.3 19.1 20.9 1.6671 29.8 9.8 12.6 15.3 17.2 1.65

59 24.0 21.0 23.6 24.0 24.0 1.8995 63 24.3 16.8 19.5 22.2 24.0 1.90

67 26.2 13.1 15.8 18.6 20.4 1.9171 28.3 9.3 12.1 14.8 16.7 1.91

59 22.6 20.4 22.6 22.6 22.6 2.17105 63 22.9 16.3 19.0 21.7 22.9 2.17

67 24.7 12.6 15.3 18.1 19.9 2.1971 26.7 8.8 11.6 14.4 16.2 2.18

59 21.2 19.9 21.2 21.2 21.2 2.46115 63 21.5 15.8 18.5 21.2 21.5 2.47

67 23.2 12.0 14.8 17.6 19.4 2.4971 25.0 8.3 11.0 13.8 15.7 2.48

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITY

LOW 800 0.98 0.93HIGH 1000 1.01 1.06

NOTE: ALL TABLES ABOVE ARE AT ARI RATING CONDITIONS RATED WITH 25 FEET OF REFRIGERANT LINES.* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE VALID ONLY FOR WET COIL. ALL TEMPERATURES IN DEGREES F.

CORRECTION FACTORS FOR OTHER COMBINATIONS (MULTIPLY DATA BY FACTOR)MBTUH MBTUH SYST

INDOOR MODEL CFM TOT SEN KWAUD080R9V4+TXH033A4+4AYTXV-3 RATED 900 0.94 0.93 1.00

LOW 800 0.93 0.87 0.99HIGH 1000 0.96 0.98 1.00

AUD080R9V4+TXH041A4+4AYTXV-3 RATED 900 0.96 0.96 0.99LOW 800 0.94 0.90 0.99HIGH 1000 0.97 1.02 1.00

AUD100R9V3+RXC031S3 RATED 900 0.94 0.91 1.04LOW 800 0.92 0.85 1.03HIGH 1000 0.95 0.97 1.06

AUD100R9V3+RXC036S3 RATED 900 0.96 0.95 1.04LOW 800 0.94 0.88 1.03HIGH 1000 0.98 1.01 1.05

AUD100R9V3+TXH033A4+4AYTXV-3 RATED 900 0.93 0.90 1.03LOW 800 0.92 0.85 1.02HIGH 1000 0.95 0.96 1.04

AUD100R9V3+TXH041A4+4AYTXV-3 RATED 900 0.95 0.94 1.03LOW 800 0.93 0.88 1.02HIGH 1000 0.96 1.00 1.04

AUD100R9V5+RXC037S3 RATED 900 0.97 0.97 1.00LOW 800 0.95 0.91 0.99HIGH 1000 0.99 1.04 1.01

AUY060R9V3+RXC036S3 RATED 900 0.96 0.96 1.02LOW 800 0.95 0.90 1.01HIGH 1000 0.98 1.02 1.03

AUY080R9V3+RXC036S3 RATED 900 0.97 0.97 1.01LOW 800 0.95 0.90 1.00HIGH 1000 0.98 1.03 1.02

AUY080R9V3+TXH033A4+4AYTXV-3 RATED 900 0.94 0.92 1.00LOW 800 0.92 0.86 1.00HIGH 1000 0.96 0.98 1.01

AUY080R9V3+TXH041A4+4AYTXV-3 RATED 900 0.96 0.96 1.00LOW 800 0.94 0.89 0.99HIGH 1000 0.97 1.02 1.01

AUY100R9V4+RXC037S3 RATED 900 0.97 0.97 1.00LOW 800 0.95 0.91 0.99HIGH 1000 0.99 1.03 1.01

AUY100R9V4+TXH033A4+4AYTXV-3 RATED 900 0.94 0.92 1.00LOW 800 0.92 0.87 0.99HIGH 1000 0.96 0.98 1.01

4A7A6036B1

4A7A6036B1 WITH 4TEE3F40A1 AT 1200 CFM 2ND STAGEO.D. I.D. TOT. SENS. CAP. AT ENTERING D.B. TEMP. TOTALD.B. W.B. CAP. 72 75 78 80 KW

59 35.6 28.5 31.9 35.3 35.6 2.5785 63 36.7 23.4 26.9 30.3 32.6 2.58

67 39.3 18.5 22.1 25.6 28.0 2.6271 42.2 13.7 17.2 20.8 23.2 2.64

59 33.9 27.9 31.3 33.9 33.9 2.8895 63 35.0 22.7 26.2 29.7 32.0 2.89

67 37.5 17.9 21.5 25.0 27.4 2.9371 40.2 13.0 16.6 20.2 22.5 2.95

59 32.1 27.2 30.6 32.1 32.1 3.20105 63 33.1 22.1 25.6 29.0 31.3 3.21

67 35.4 17.2 20.8 24.4 26.7 3.2571 38.0 12.3 15.9 19.5 21.9 3.27

59 30.0 26.5 29.8 30.0 30.0 3.53115 63 31.0 21.3 24.9 28.3 30.6 3.54

67 33.2 16.5 20.1 23.6 25.9 3.5971 35.6 11.5 15.1 18.7 21.2 3.62

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITY

LOW 1050 0.98 0.93HIGH 1350 1.02 1.06

NOTE: ALL TABLES ABOVE ARE AT ARI RATING CONDITIONS RATED WITH 25 FEET OF REFRIGERANT LINES.* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE VALID ONLY FOR WET COIL. ALL TEMPERATURES IN DEGREES F.

CORRECTION FACTORS FOR OTHER COMBINATIONS (MULTIPLY DATA BY FACTOR)MBTUH MBTUH SYST

INDOOR MODEL CFM TOT SEN KWAUD080R9V4+TXH033A4+4AYTXV-3 RATED 1200 0.94 0.90 1.01

LOW 1050 0.92 0.84 1.00HIGH 1350 0.96 0.96 1.02

AUD080R9V4+TXH041A4+4AYTXV-3 RATED 1200 0.96 0.95 1.01LOW 1050 0.94 0.89 1.00HIGH 1350 0.98 1.02 1.02

AUD100R9V3+RXC031S3 RATED 1200 0.93 0.88 1.07LOW 1050 0.91 0.82 1.05HIGH 1350 0.94 0.93 1.09

AUD100R9V3+RXC036S3 RATED 1200 0.96 0.92 1.07LOW 1050 0.94 0.86 1.05HIGH 1350 0.97 0.98 1.09

AUD100R9V3+TXH033A4+4AYTXV-3 RATED 1200 0.93 0.87 1.06LOW 1050 0.91 0.81 1.04HIGH 1350 0.94 0.92 1.08

AUD100R9V3+TXH041A4+4AYTXV-3 RATED 1200 0.95 0.92 1.05LOW 1050 0.93 0.86 1.03HIGH 1350 0.96 0.98 1.07

AUD100R9V5+RXC037S3 RATED 1200 0.97 0.97 1.02LOW 1050 0.95 0.90 1.00HIGH 1350 0.99 1.03 1.03

AUY060R9V3+RXC036S3 RATED 1200 0.96 0.94 1.04LOW 1050 0.94 0.88 1.02HIGH 1350 0.97 1.00 1.06

AUY080R9V3+RXC036S3 RATED 1200 0.97 0.96 1.03LOW 1050 0.95 0.89 1.01HIGH 1350 0.98 1.02 1.04

AUY080R9V3+TXH033A4+4AYTXV-3 RATED 1200 0.93 0.89 1.01LOW 1050 0.92 0.84 1.00HIGH 1350 0.95 0.95 1.03

AUY080R9V3+TXH041A4+4AYTXV-3 RATED 1200 0.97 0.95 1.02LOW 1050 0.95 0.89 1.01HIGH 1350 0.98 1.01 1.04

AUY100R9V4+RXC037S3 RATED 1200 0.98 0.97 1.02LOW 1050 0.96 0.90 1.00HIGH 1350 0.99 1.03 1.03

AUY100R9V4+TXH033A4+4AYTXV-3 RATED 1200 0.94 0.90 1.02LOW 1050 0.92 0.84 1.00HIGH 1350 0.96 0.96 1.03

Page 18: ALLEGIANCE 16 MODELS 4A7A6024,036,048 & 060Bfurnacefactorydirect.ca/pdf/4a7a6 Product Data.pdf · ALLEGIANCE® 16 MODELS 4A7A6024,036,048 & 060B SPLIT SYSTEM ... the Unitary Air-Conditioner

18 DATA SUBJECT TO CHANGE WITHOUT NOTICE

PRODUCT DATAAmerican Standard Inc., Tyler, TX 75711-9010

Performance DataCooling —

4A7A6036B1 WITH 4TEE3F40A1 AT 900 CFM 1ST STAGEO.D. I.D. TOT. SENS. CAP. AT ENTERING D.B. TEMP. TOTALD.B. W.B. CAP. 72 75 78 80 KW

59 25.3 21.5 24.1 25.3 25.3 1.6485 63 25.6 17.3 20.0 22.7 24.5 1.64

67 27.6 13.6 16.3 19.1 20.9 1.6671 29.8 9.8 12.6 15.3 17.2 1.65

59 24.0 21.0 23.6 24.0 24.0 1.8995 63 24.3 16.8 19.5 22.2 24.0 1.90

67 26.2 13.1 15.8 18.6 20.4 1.9171 28.3 9.3 12.1 14.8 16.7 1.91

59 22.6 20.4 22.6 22.6 22.6 2.17105 63 22.9 16.3 19.0 21.7 22.9 2.17

67 24.7 12.6 15.3 18.1 19.9 2.1971 26.7 8.8 11.6 14.4 16.2 2.18

59 21.2 19.9 21.2 21.2 21.2 2.46115 63 21.5 15.8 18.5 21.2 21.5 2.47

67 23.2 12.0 14.8 17.6 19.4 2.4971 25.0 8.3 11.0 13.8 15.7 2.48

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITY

LOW 800 0.98 0.93HIGH 1000 1.01 1.06

NOTE: ALL TABLES ABOVE ARE AT ARI RATING CONDITIONS RATED WITH 25 FEET OF REFRIGERANT LINES.* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE VALID ONLY FOR WET COIL. ALL TEMPERATURES IN DEGREES F.

CORRECTION FACTORS FOR OTHER COMBINATIONS (MULTIPLY DATA BY FACTOR)MBTUH MBTUH SYST

INDOOR MODEL CFM TOT SEN KWAUY100R9V4+TXH041A4+4AYTXV-3 RATED 900 0.96 0.96 1.00

LOW 800 0.94 0.90 0.99HIGH 1000 0.97 1.02 1.00

4A7A6036B1

4A7A6036B1 WITH 4TEE3F40A1 AT 1200 CFM 2ND STAGEO.D. I.D. TOT. SENS. CAP. AT ENTERING D.B. TEMP. TOTALD.B. W.B. CAP. 72 75 78 80 KW

59 35.6 28.5 31.9 35.3 35.6 2.5785 63 36.7 23.4 26.9 30.3 32.6 2.58

67 39.3 18.5 22.1 25.6 28.0 2.6271 42.2 13.7 17.2 20.8 23.2 2.64

59 33.9 27.9 31.3 33.9 33.9 2.8895 63 35.0 22.7 26.2 29.7 32.0 2.89

67 37.5 17.9 21.5 25.0 27.4 2.9371 40.2 13.0 16.6 20.2 22.5 2.95

59 32.1 27.2 30.6 32.1 32.1 3.20105 63 33.1 22.1 25.6 29.0 31.3 3.21

67 35.4 17.2 20.8 24.4 26.7 3.2571 38.0 12.3 15.9 19.5 21.9 3.27

59 30.0 26.5 29.8 30.0 30.0 3.53115 63 31.0 21.3 24.9 28.3 30.6 3.54

67 33.2 16.5 20.1 23.6 25.9 3.5971 35.6 11.5 15.1 18.7 21.2 3.62

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITY

LOW 1050 0.98 0.93HIGH 1350 1.02 1.06

NOTE: ALL TABLES ABOVE ARE AT ARI RATING CONDITIONS RATED WITH 25 FEET OF REFRIGERANT LINES.* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE VALID ONLY FOR WET COIL. ALL TEMPERATURES IN DEGREES F.

CORRECTION FACTORS FOR OTHER COMBINATIONS (MULTIPLY DATA BY FACTOR)MBTUH MBTUH SYST

INDOOR MODEL CFM TOT SEN KWAUY100R9V4+TXH041A4+4AYTXV-3 RATED 1200 0.96 0.95 1.01

LOW 1050 0.94 0.88 0.99HIGH 1350 0.97 1.01 1.02

Page 19: ALLEGIANCE 16 MODELS 4A7A6024,036,048 & 060Bfurnacefactorydirect.ca/pdf/4a7a6 Product Data.pdf · ALLEGIANCE® 16 MODELS 4A7A6024,036,048 & 060B SPLIT SYSTEM ... the Unitary Air-Conditioner

PRODUCT DATAAmerican Standard Inc., Tyler, TX 75711-9010

DATA SUBJECT TO CHANGE WITHOUT NOTICE 19

Performance DataCooling —

4A7A6048B1 WITH 4TEE3F49A1 AT 1200 CFM 1ST STAGEO.D. I.D. TOT. SENS. CAP. AT ENTERING D.B. TEMP. TOTALD.B. W.B. CAP. 72 75 78 80 KW

59 34.3 28.4 31.9 34.3 34.3 2.4185 63 35.0 23.0 26.5 30.1 32.4 2.41

67 37.7 18.1 21.7 25.3 27.7 2.4171 40.7 13.2 16.8 20.5 22.9 2.38

59 32.6 27.8 31.2 32.6 32.6 2.7795 63 33.2 22.3 25.9 29.4 31.8 2.77

67 35.8 17.4 21.1 24.7 27.1 2.7671 38.7 12.6 16.2 19.8 22.3 2.73

59 30.8 27.1 30.6 30.8 30.8 3.14105 63 31.4 21.7 25.3 28.8 31.1 3.14

67 33.9 16.8 20.4 24.1 26.4 3.1371 36.6 11.9 15.5 19.2 21.6 3.10

59 29.0 26.4 29.0 29.0 29.0 3.54115 63 29.6 21.0 24.6 28.2 29.6 3.53

67 31.9 16.1 19.8 23.4 25.8 3.5371 34.5 11.2 14.8 18.5 20.9 3.49

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITY

LOW 1050 0.98 0.93HIGH 1350 1.02 1.07

NOTE: ALL TABLES ABOVE ARE AT ARI RATING CONDITIONS RATED WITH 25 FEET OF REFRIGERANT LINES.* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE VALID ONLY FOR WET COIL. ALL TEMPERATURES IN DEGREES F.

CORRECTION FACTORS FOR OTHER COMBINATIONS (MULTIPLY DATA BY FACTOR)MBTUH MBTUH SYST

INDOOR MODEL CFM TOT SEN KW4TEE3F40A1 RATED 1200 0.99 0.98 0.99

LOW 1050 0.97 0.92 0.98HIGH 1350 1.00 1.05 1.00

ADD100R9V5+RXC054S3 RATED 1200 0.96 0.96 1.01LOW 1050 0.93 0.89 1.00HIGH 1350 0.97 1.03 1.02

ADD100R9V5+TXC043C4+4AYTXV-3 RATED 1200 0.93 0.93 1.01LOW 1050 0.91 0.86 1.00HIGH 1350 0.95 0.99 1.02

ADD100R9V5+TXC049C4+4AYTXV-3 RATED 1200 0.95 0.95 1.01LOW 1050 0.93 0.88 1.00HIGH 1350 0.96 1.02 1.02

ADD100R9V5+TXH054A4+4AYTXV-3 RATED 1200 0.97 0.97 1.01LOW 1050 0.95 0.90 1.00HIGH 1350 0.99 1.03 1.02

ADD120R9V5+TXC050C4+4AYTXV-3 RATED 1200 0.95 0.96 1.00LOW 1050 0.93 0.89 0.99HIGH 1350 0.96 1.02 1.01

ADD120R9V5+TXH054A4+4AYTXV-3 RATED 1200 0.98 0.98 1.00LOW 1050 0.96 0.91 0.99HIGH 1350 0.99 1.04 1.01

ADY100R9V4+RXC054S3 RATED 1200 0.95 0.96 1.02LOW 1050 0.93 0.89 1.01HIGH 1350 0.97 1.02 1.03

ADY100R9V4+TXC043C4+4AYTXV-3 RATED 1200 0.93 0.92 1.02LOW 1050 0.91 0.85 1.01HIGH 1350 0.94 0.98 1.03

ADY100R9V4+TXC049C4+4AYTXV-3 RATED 1200 0.94 0.94 1.02LOW 1050 0.92 0.88 1.01HIGH 1350 0.96 1.01 1.03

ADY100R9V4+TXH054A4+4AYTXV-3 RATED 1200 0.97 0.96 1.02LOW 1050 0.95 0.90 1.01HIGH 1350 0.99 1.03 1.03

ADY120R9V5+TXC050C4+4AYTXV-3 RATED 1200 0.95 0.95 1.01LOW 1050 0.93 0.88 1.00HIGH 1350 0.96 1.02 1.02

ADY120R9V5+TXH054A4+4AYTXV-3 RATED 1200 0.97 0.97 1.01LOW 1050 0.96 0.90 1.00HIGH 1350 0.99 1.04 1.01

4A7A6048B1

4A7A6048B1 WITH 4TEE3F49A1 AT 1600 CFM 2ND STAGEO.D. I.D. TOT. SENS. CAP. AT ENTERING D.B. TEMP. TOTALD.B. W.B. CAP. 72 75 78 80 KW

59 46.3 36.7 41.2 45.5 46.3 3.6185 63 47.7 30.0 34.6 39.1 42.1 3.62

67 51.2 23.7 28.4 33.1 36.1 3.6971 55.1 17.5 22.0 26.7 29.9 3.72

59 44.3 36.0 40.5 44.3 44.3 4.0395 63 45.7 29.3 33.9 38.4 41.4 4.05

67 49.0 23.0 27.7 32.3 35.4 4.1271 52.7 16.7 21.3 26.0 29.2 4.16

59 42.0 35.2 39.6 42.0 42.0 4.47105 63 43.3 28.5 33.1 37.6 40.6 4.49

67 46.5 22.1 26.9 31.5 34.6 4.5671 50.0 15.8 20.4 25.2 28.3 4.61

59 39.4 34.2 38.7 39.4 39.4 4.92115 63 40.6 27.6 32.2 36.7 39.6 4.94

67 43.6 21.2 25.9 30.6 33.7 5.0371 46.9 14.7 19.5 24.2 27.4 5.07

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITY

LOW 1400 0.98 0.93HIGH 1800 1.01 1.06

NOTE: ALL TABLES ABOVE ARE AT ARI RATING CONDITIONS RATED WITH 25 FEET OF REFRIGERANT LINES.* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE VALID ONLY FOR WET COIL. ALL TEMPERATURES IN DEGREES F.

CORRECTION FACTORS FOR OTHER COMBINATIONS (MULTIPLY DATA BY FACTOR)MBTUH MBTUH SYST

INDOOR MODEL CFM TOT SEN KW4TEE3F40A1 RATED 1600 0.98 0.97 1.00

LOW 1400 0.96 0.91 0.98HIGH 1800 1.00 1.03 1.02

ADD100R9V5+RXC054S3 RATED 1600 0.94 0.95 1.00LOW 1400 0.92 0.89 0.98HIGH 1800 0.96 1.01 1.02

ADD100R9V5+TXC043C4+4AYTXV-3 RATED 1600 0.92 0.90 1.01LOW 1400 0.91 0.85 0.99HIGH 1800 0.93 0.96 1.03

ADD100R9V5+TXC049C4+4AYTXV-3 RATED 1600 0.93 0.93 1.00LOW 1400 0.91 0.87 0.98HIGH 1800 0.95 0.99 1.02

ADD100R9V5+TXH054A4+4AYTXV-3 RATED 1600 0.96 0.95 1.00LOW 1400 0.95 0.89 0.99HIGH 1800 0.98 1.01 1.02

ADD120R9V5+TXC050C4+4AYTXV-3 RATED 1600 0.94 0.95 0.99LOW 1400 0.92 0.88 0.97HIGH 1800 0.96 1.01 1.01

ADD120R9V5+TXH054A4+4AYTXV-3 RATED 1600 0.97 0.96 1.00LOW 1400 0.96 0.90 0.98HIGH 1800 0.99 1.02 1.01

ADY100R9V4+RXC054S3 RATED 1600 0.94 0.94 1.02LOW 1400 0.92 0.87 0.99HIGH 1800 0.95 1.00 1.04

ADY100R9V4+TXC043C4+4AYTXV-3 RATED 1600 0.91 0.89 1.01LOW 1400 0.90 0.83 0.99HIGH 1800 0.93 0.94 1.03

ADY100R9V4+TXC049C4+4AYTXV-3 RATED 1600 0.94 0.92 1.02LOW 1400 0.92 0.86 1.00HIGH 1800 0.95 0.98 1.05

ADY100R9V4+TXH054A4+4AYTXV-3 RATED 1600 0.97 0.94 1.02LOW 1400 0.95 0.88 1.00HIGH 1800 0.98 0.99 1.04

ADY120R9V5+TXC050C4+4AYTXV-3 RATED 1600 0.94 0.94 1.00LOW 1400 0.92 0.87 0.98HIGH 1800 0.95 0.99 1.02

ADY120R9V5+TXH054A4+4AYTXV-3 RATED 1600 0.97 0.95 1.00LOW 1400 0.95 0.89 0.99HIGH 1800 0.98 1.01 1.02

Page 20: ALLEGIANCE 16 MODELS 4A7A6024,036,048 & 060Bfurnacefactorydirect.ca/pdf/4a7a6 Product Data.pdf · ALLEGIANCE® 16 MODELS 4A7A6024,036,048 & 060B SPLIT SYSTEM ... the Unitary Air-Conditioner

20 DATA SUBJECT TO CHANGE WITHOUT NOTICE

PRODUCT DATAAmerican Standard Inc., Tyler, TX 75711-9010

Performance DataCooling —

4A7A6048B1 WITH 4TEE3F49A1 AT 1200 CFM 1ST STAGEO.D. I.D. TOT. SENS. CAP. AT ENTERING D.B. TEMP. TOTALD.B. W.B. CAP. 72 75 78 80 KW

59 34.3 28.4 31.9 34.3 34.3 2.4185 63 35.0 23.0 26.5 30.1 32.4 2.41

67 37.7 18.1 21.7 25.3 27.7 2.4171 40.7 13.2 16.8 20.5 22.9 2.38

59 32.6 27.8 31.2 32.6 32.6 2.7795 63 33.2 22.3 25.9 29.4 31.8 2.77

67 35.8 17.4 21.1 24.7 27.1 2.7671 38.7 12.6 16.2 19.8 22.3 2.73

59 30.8 27.1 30.6 30.8 30.8 3.14105 63 31.4 21.7 25.3 28.8 31.1 3.14

67 33.9 16.8 20.4 24.1 26.4 3.1371 36.6 11.9 15.5 19.2 21.6 3.10

59 29.0 26.4 29.0 29.0 29.0 3.54115 63 29.6 21.0 24.6 28.2 29.6 3.53

67 31.9 16.1 19.8 23.4 25.8 3.5371 34.5 11.2 14.8 18.5 20.9 3.49

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITY

LOW 1050 0.98 0.93HIGH 1350 1.02 1.07

NOTE: ALL TABLES ABOVE ARE AT ARI RATING CONDITIONS RATED WITH 25 FEET OF REFRIGERANT LINES.* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE VALID ONLY FOR WET COIL. ALL TEMPERATURES IN DEGREES F.

CORRECTION FACTORS FOR OTHER COMBINATIONS (MULTIPLY DATA BY FACTOR)MBTUH MBTUH SYST

INDOOR MODEL CFM TOT SEN KWAUD080R9V4+RXC054S3 RATED 1200 0.96 0.96 1.01

LOW 1050 0.93 0.89 1.00HIGH 1350 0.97 1.03 1.02

AUD080R9V4+TXC043C4+4AYTXV-3 RATED 1200 0.93 0.93 1.01LOW 1050 0.91 0.86 1.00HIGH 1350 0.95 0.99 1.02

AUD080R9V4+TXC049C4+4AYTXV-3 RATED 1200 0.95 0.95 1.01LOW 1050 0.93 0.88 1.00HIGH 1350 0.96 1.02 1.02

AUD080R9V4+TXH054A4+4AYTXV-3 RATED 1200 0.97 0.97 1.01LOW 1050 0.95 0.90 1.00HIGH 1350 0.99 1.03 1.02

AUD100R9V5+RXC054S3 RATED 1200 0.95 0.96 1.01LOW 1050 0.93 0.89 1.00HIGH 1350 0.97 1.03 1.02

AUD100R9V5+TXC043C4+4AYTXV-3 RATED 1200 0.93 0.92 1.02LOW 1050 0.91 0.86 1.01HIGH 1350 0.94 0.99 1.03

AUD100R9V5+TXC049C4+4AYTXV-3 RATED 1200 0.95 0.95 1.01LOW 1050 0.93 0.88 1.00HIGH 1350 0.96 1.01 1.02

AUD100R9V5+TXH054A4+4AYTXV-3 RATED 1200 0.97 0.97 1.01LOW 1050 0.95 0.90 1.00HIGH 1350 0.99 1.03 1.02

AUD120R9V5+TXC050C4+4AYTXV-3 RATED 1200 0.95 0.95 1.00LOW 1050 0.93 0.88 1.00HIGH 1350 0.96 1.02 1.01

AUD120R9V5+TXH054A4+4AYTXV-3 RATED 1200 0.98 0.97 1.00LOW 1050 0.96 0.91 0.99HIGH 1350 0.99 1.04 1.01

AUD140R9V5+TXC050C4+4AYTXV-3 RATED 1200 0.95 0.96 1.00LOW 1050 0.93 0.89 1.00HIGH 1350 0.96 1.02 1.01

AUD140R9V5+TXH054A4+4AYTXV-3 RATED 1200 0.98 0.97 1.00LOW 1050 0.96 0.91 0.99HIGH 1350 0.99 1.04 1.01

AUY100R9V4+RXC054S3 RATED 1200 0.95 0.96 1.01LOW 1050 0.93 0.89 1.00HIGH 1350 0.97 1.03 1.02

4A7A6048B1

4A7A6048B1 WITH 4TEE3F49A1 AT 1600 CFM 2ND STAGEO.D. I.D. TOT. SENS. CAP. AT ENTERING D.B. TEMP. TOTALD.B. W.B. CAP. 72 75 78 80 KW

59 46.3 36.7 41.2 45.5 46.3 3.6185 63 47.7 30.0 34.6 39.1 42.1 3.62

67 51.2 23.7 28.4 33.1 36.1 3.6971 55.1 17.5 22.0 26.7 29.9 3.72

59 44.3 36.0 40.5 44.3 44.3 4.0395 63 45.7 29.3 33.9 38.4 41.4 4.05

67 49.0 23.0 27.7 32.3 35.4 4.1271 52.7 16.7 21.3 26.0 29.2 4.16

59 42.0 35.2 39.6 42.0 42.0 4.47105 63 43.3 28.5 33.1 37.6 40.6 4.49

67 46.5 22.1 26.9 31.5 34.6 4.5671 50.0 15.8 20.4 25.2 28.3 4.61

59 39.4 34.2 38.7 39.4 39.4 4.92115 63 40.6 27.6 32.2 36.7 39.6 4.94

67 43.6 21.2 25.9 30.6 33.7 5.0371 46.9 14.7 19.5 24.2 27.4 5.07

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITY

LOW 1400 0.98 0.93HIGH 1800 1.01 1.06

NOTE: ALL TABLES ABOVE ARE AT ARI RATING CONDITIONS RATED WITH 25 FEET OF REFRIGERANT LINES.* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE VALID ONLY FOR WET COIL. ALL TEMPERATURES IN DEGREES F.

CORRECTION FACTORS FOR OTHER COMBINATIONS (MULTIPLY DATA BY FACTOR)MBTUH MBTUH SYST

INDOOR MODEL CFM TOT SEN KWAUD080R9V4+RXC054S3 RATED 1600 0.94 0.95 1.00

LOW 1400 0.93 0.89 0.98HIGH 1800 0.96 1.01 1.02

AUD080R9V4+TXC043C4+4AYTXV-3 RATED 1600 0.92 0.90 1.01LOW 1400 0.91 0.85 0.99HIGH 1800 0.94 0.96 1.03

AUD080R9V4+TXC049C4+4AYTXV-3 RATED 1600 0.93 0.93 1.00LOW 1400 0.92 0.87 0.98HIGH 1800 0.95 0.99 1.02

AUD080R9V4+TXH054A4+4AYTXV-3 RATED 1600 0.97 0.95 1.01LOW 1400 0.95 0.89 0.99HIGH 1800 0.98 1.01 1.03

AUD100R9V5+RXC054S3 RATED 1600 0.94 0.94 1.01LOW 1400 0.92 0.88 0.98HIGH 1800 0.95 1.00 1.03

AUD100R9V5+TXC043C4+4AYTXV-3 RATED 1600 0.92 0.90 1.01LOW 1400 0.90 0.84 0.99HIGH 1800 0.93 0.95 1.03

AUD100R9V5+TXC049C4+4AYTXV-3 RATED 1600 0.94 0.93 1.01LOW 1400 0.92 0.87 0.99HIGH 1800 0.95 0.99 1.03

AUD100R9V5+TXH054A4+4AYTXV-3 RATED 1600 0.97 0.95 1.02LOW 1400 0.95 0.89 1.00HIGH 1800 0.98 1.00 1.04

AUD120R9V5+TXC050C4+4AYTXV-3 RATED 1600 0.94 0.94 1.00LOW 1400 0.92 0.88 0.98HIGH 1800 0.96 1.00 1.02

AUD120R9V5+TXH054A4+4AYTXV-3 RATED 1600 0.97 0.96 1.01LOW 1400 0.96 0.90 0.99HIGH 1800 0.99 1.02 1.02

AUD140R9V5+TXC050C4+4AYTXV-3 RATED 1600 0.93 0.94 0.98LOW 1400 0.92 0.88 0.97HIGH 1800 0.95 1.00 1.00

AUD140R9V5+TXH054A4+4AYTXV-3 RATED 1600 0.98 0.96 1.00LOW 1400 0.96 0.90 0.98HIGH 1800 0.99 1.02 1.02

AUY100R9V4+RXC054S3 RATED 1600 0.94 0.95 1.00LOW 1400 0.92 0.88 0.98HIGH 1800 0.95 1.01 1.02

Page 21: ALLEGIANCE 16 MODELS 4A7A6024,036,048 & 060Bfurnacefactorydirect.ca/pdf/4a7a6 Product Data.pdf · ALLEGIANCE® 16 MODELS 4A7A6024,036,048 & 060B SPLIT SYSTEM ... the Unitary Air-Conditioner

PRODUCT DATAAmerican Standard Inc., Tyler, TX 75711-9010

DATA SUBJECT TO CHANGE WITHOUT NOTICE 21

Performance DataCooling — 4A7A6048B1

4A7A6048B1 WITH 4TEE3F49A1 AT 1600 CFM 2ND STAGEO.D. I.D. TOT. SENS. CAP. AT ENTERING D.B. TEMP. TOTALD.B. W.B. CAP. 72 75 78 80 KW

59 46.3 36.7 41.2 45.5 46.3 3.6185 63 47.7 30.0 34.6 39.1 42.1 3.62

67 51.2 23.7 28.4 33.1 36.1 3.6971 55.1 17.5 22.0 26.7 29.9 3.72

59 44.3 36.0 40.5 44.3 44.3 4.0395 63 45.7 29.3 33.9 38.4 41.4 4.05

67 49.0 23.0 27.7 32.3 35.4 4.1271 52.7 16.7 21.3 26.0 29.2 4.16

59 42.0 35.2 39.6 42.0 42.0 4.47105 63 43.3 28.5 33.1 37.6 40.6 4.49

67 46.5 22.1 26.9 31.5 34.6 4.5671 50.0 15.8 20.4 25.2 28.3 4.61

59 39.4 34.2 38.7 39.4 39.4 4.92115 63 40.6 27.6 32.2 36.7 39.6 4.94

67 43.6 21.2 25.9 30.6 33.7 5.0371 46.9 14.7 19.5 24.2 27.4 5.07

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITY

LOW 1400 0.98 0.93HIGH 1800 1.01 1.06

NOTE: ALL TABLES ABOVE ARE AT ARI RATING CONDITIONS RATED WITH 25 FEET OF REFRIGERANT LINES.* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE VALID ONLY FOR WET COIL. ALL TEMPERATURES IN DEGREES F.

CORRECTION FACTORS FOR OTHER COMBINATIONS (MULTIPLY DATA BY FACTOR)MBTUH MBTUH SYST

INDOOR MODEL CFM TOT SEN KWAUY100R9V4+TXC043C4+4AYTXV-3 RATED 1600 0.92 0.90 1.00

LOW 1400 0.90 0.84 0.98HIGH 1800 0.93 0.95 1.02

AUY100R9V4+TXC049C4+4AYTXV-3 RATED 1600 0.94 0.93 1.01LOW 1400 0.92 0.87 0.99HIGH 1800 0.95 0.99 1.03

AUY100R9V4+TXH054A4+4AYTXV-3 RATED 1600 0.97 0.95 1.01LOW 1400 0.95 0.89 0.99HIGH 1800 0.98 1.00 1.03

AUY120R9V5+TXC050C4+4AYTXV-3 RATED 1600 0.94 0.94 1.00LOW 1400 0.92 0.88 0.98HIGH 1800 0.95 1.00 1.02

AUY120R9V5+TXH054A4+4AYTXV-3 RATED 1600 0.97 0.96 0.99LOW 1400 0.95 0.90 0.98HIGH 1800 0.98 1.01 1.01

4A7A6048B1 WITH 4TEE3F49A1 AT 1200 CFM 1ST STAGEO.D. I.D. TOT. SENS. CAP. AT ENTERING D.B. TEMP. TOTALD.B. W.B. CAP. 72 75 78 80 KW

59 34.3 28.4 31.9 34.3 34.3 2.4185 63 35.0 23.0 26.5 30.1 32.4 2.41

67 37.7 18.1 21.7 25.3 27.7 2.4171 40.7 13.2 16.8 20.5 22.9 2.38

59 32.6 27.8 31.2 32.6 32.6 2.7795 63 33.2 22.3 25.9 29.4 31.8 2.77

67 35.8 17.4 21.1 24.7 27.1 2.7671 38.7 12.6 16.2 19.8 22.3 2.73

59 30.8 27.1 30.6 30.8 30.8 3.14105 63 31.4 21.7 25.3 28.8 31.1 3.14

67 33.9 16.8 20.4 24.1 26.4 3.1371 36.6 11.9 15.5 19.2 21.6 3.10

59 29.0 26.4 29.0 29.0 29.0 3.54115 63 29.6 21.0 24.6 28.2 29.6 3.53

67 31.9 16.1 19.8 23.4 25.8 3.5371 34.5 11.2 14.8 18.5 20.9 3.49

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITY

LOW 1050 0.98 0.93HIGH 1350 1.02 1.07

NOTE: ALL TABLES ABOVE ARE AT ARI RATING CONDITIONS RATED WITH 25 FEET OF REFRIGERANT LINES.* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE VALID ONLY FOR WET COIL. ALL TEMPERATURES IN DEGREES F.

CORRECTION FACTORS FOR OTHER COMBINATIONS (MULTIPLY DATA BY FACTOR)MBTUH MBTUH SYST

INDOOR MODEL CFM TOT SEN KWAUY100R9V4+TXC043C4+4AYTXV-3 RATED 1200 0.93 0.93 1.01

LOW 1050 0.91 0.86 1.01HIGH 1350 0.95 0.99 1.02

AUY100R9V4+TXC049C4+4AYTXV-3 RATED 1200 0.95 0.95 1.01LOW 1050 0.93 0.88 1.00HIGH 1350 0.96 1.01 1.02

AUY100R9V4+TXH054A4+4AYTXV-3 RATED 1200 0.97 0.97 1.01LOW 1050 0.95 0.90 1.00HIGH 1350 0.99 1.03 1.02

AUY120R9V5+TXC050C4+4AYTXV-3 RATED 1200 0.95 0.95 1.00LOW 1050 0.93 0.88 1.00HIGH 1350 0.96 1.02 1.01

AUY120R9V5+TXH054A4+4AYTXV-3 RATED 1200 0.98 0.97 1.00LOW 1050 0.96 0.91 0.99HIGH 1350 0.99 1.04 1.01

Page 22: ALLEGIANCE 16 MODELS 4A7A6024,036,048 & 060Bfurnacefactorydirect.ca/pdf/4a7a6 Product Data.pdf · ALLEGIANCE® 16 MODELS 4A7A6024,036,048 & 060B SPLIT SYSTEM ... the Unitary Air-Conditioner

22 DATA SUBJECT TO CHANGE WITHOUT NOTICE

PRODUCT DATAAmerican Standard Inc., Tyler, TX 75711-9010

Performance DataCooling —

4A7A6060B1 WITH 4TEE3F65A1 AT 1500 CFM 1ST STAGEO.D. I.D. TOT. SENS. CAP. AT ENTERING D.B. TEMP. TOTALD.B. W.B. CAP. 72 75 78 80 KW

59 41.6 34.6 38.8 41.6 41.6 3.0985 63 42.2 27.9 32.3 36.6 39.4 3.09

67 45.1 21.8 26.2 30.7 33.6 3.0971 48.4 15.6 20.1 24.6 27.6 3.07

59 39.7 33.9 38.2 39.7 39.7 3.5995 63 40.3 27.2 31.6 36.0 38.8 3.59

67 43.0 21.1 25.6 30.0 32.9 3.5971 46.2 14.9 19.4 23.9 26.9 3.56

59 37.6 33.1 37.4 37.6 37.6 4.13105 63 38.2 26.5 30.9 35.2 38.1 4.13

67 40.8 20.3 24.9 29.3 32.2 4.1371 43.8 14.1 18.6 23.2 26.2 4.10

59 35.3 32.3 35.3 35.3 35.3 4.72115 63 35.8 25.7 30.1 34.4 35.8 4.72

67 38.3 19.5 24.0 28.5 31.4 4.7271 41.1 13.2 17.8 22.4 25.4 4.68

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITY

LOW 1300 0.98 0.93HIGH 1700 1.02 1.07

NOTE: ALL TABLES ABOVE ARE AT ARI RATING CONDITIONS RATED WITH 25 FEET OF REFRIGERANT LINES.* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE VALID ONLY FOR WET COIL. ALL TEMPERATURES IN DEGREES F.

CORRECTION FACTORS FOR OTHER COMBINATIONS (MULTIPLY DATA BY FACTOR)MBTUH MBTUH SYST

INDOOR MODEL CFM TOT SEN KWADD100R9V5+RXH063S3 RATED 1500 0.99 1.00 1.00

LOW 1300 0.97 0.92 0.99HIGH 1700 1.01 1.07 1.01

ADD120R9V5+RXC061S3 RATED 1500 0.96 0.98 0.99LOW 1300 0.94 0.91 0.98HIGH 1700 0.98 1.06 0.99

ADD120R9V5+RXH063S3 RATED 1500 1.00 1.00 0.98LOW 1300 0.98 0.93 0.98HIGH 1700 1.01 1.08 0.99

ADY120R9V5+RXC061S3 RATED 1500 0.95 0.96 1.02LOW 1300 0.93 0.89 1.01HIGH 1700 0.97 1.03 1.03

ADY120R9V5+RXH063S3 RATED 1500 0.99 0.98 1.02LOW 1300 0.97 0.91 1.00HIGH 1700 1.00 1.05 1.03

AUD100R9V5+RXC061S3 RATED 1500 0.96 0.97 1.00LOW 1300 0.94 0.90 0.99HIGH 1700 0.97 1.04 1.01

AUD100R9V5+RXC065S3 RATED 1500 0.95 0.97 1.02LOW 1300 0.93 0.90 1.01HIGH 1700 0.97 1.04 1.03

AUD100R9V5+RXH063S3 RATED 1500 0.99 0.99 1.00LOW 1300 0.97 0.92 0.99HIGH 1700 1.01 1.07 1.01

AUD120R9V5+RXC061S3 RATED 1500 0.96 0.98 0.99LOW 1300 0.94 0.91 0.99HIGH 1700 0.97 1.05 1.00

AUD120R9V5+RXC065S3 RATED 1500 0.95 0.98 1.01LOW 1300 0.93 0.90 1.00HIGH 1700 0.97 1.05 1.02

AUD120R9V5+RXH063S3 RATED 1500 1.00 1.00 0.99LOW 1300 0.98 0.93 0.98HIGH 1700 1.01 1.07 1.00

AUD140R9V5+RXC061S3 RATED 1500 0.96 0.98 0.99LOW 1300 0.94 0.91 0.98HIGH 1700 0.97 1.05 1.00

AUD140R9V5+RXC065S3 RATED 1500 0.96 0.98 1.00LOW 1300 0.94 0.91 0.99HIGH 1700 0.97 1.05 1.01

4A7A6060B1

4A7A6060B1 WITH 4TEE3F65A1 AT 2000 CFM 2ND STAGEO.D. I.D. TOT. SENS. CAP. AT ENTERING D.B. TEMP. TOTALD.B. W.B. CAP. 72 75 78 80 KW

59 56.6 44.6 50.1 55.3 56.6 4.8785 63 58.1 36.4 42.0 47.6 51.1 4.91

67 62.3 28.7 34.4 40.2 43.9 5.0271 67.1 21.0 26.6 32.4 36.3 5.09

59 54.1 43.8 49.2 54.1 54.1 5.4795 63 55.5 35.5 41.2 46.7 50.3 5.50

67 59.5 27.8 33.5 39.3 43.1 5.6371 64.1 20.0 25.7 31.5 35.4 5.71

59 51.2 42.8 48.2 51.2 51.2 6.08105 63 52.5 34.5 40.2 45.7 49.3 6.12

67 56.3 26.7 32.5 38.3 42.1 6.2671 60.7 18.9 24.6 30.5 34.4 6.35

59 47.8 41.6 47.0 47.8 47.8 6.71115 63 49.0 33.4 39.1 44.6 48.2 6.76

67 52.6 25.5 31.4 37.1 40.9 6.9171 56.7 17.6 23.4 29.3 33.2 7.02

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITY

LOW 1750 0.98 0.93HIGH 2250 1.01 1.06

NOTE: ALL TABLES ABOVE ARE AT ARI RATING CONDITIONS RATED WITH 25 FEET OF REFRIGERANT LINES.* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE VALID ONLY FOR WET COIL. ALL TEMPERATURES IN DEGREES F.

CORRECTION FACTORS FOR OTHER COMBINATIONS (MULTIPLY DATA BY FACTOR)MBTUH MBTUH SYST

INDOOR MODEL CFM TOT SEN KWADD100R9V5+RXH063S3 RATED 2000 1.01 1.00 0.99

LOW 1750 0.99 0.94 0.97HIGH 2250 1.02 1.06 1.01

ADD120R9V5+RXC061S3 RATED 2000 0.96 0.99 0.96LOW 1750 0.94 0.92 0.94HIGH 2250 0.97 1.05 0.97

ADD120R9V5+RXH063S3 RATED 2000 1.01 1.02 0.97LOW 1750 0.99 0.95 0.96HIGH 2250 1.03 1.08 0.99

ADY120R9V5+RXC061S3 RATED 2000 0.95 0.95 1.00LOW 1750 0.93 0.89 0.98HIGH 2250 0.96 1.00 1.02

ADY120R9V5+RXH063S3 RATED 2000 0.99 0.96 1.03LOW 1750 0.98 0.91 1.01HIGH 2250 1.01 1.02 1.05

AUD100R9V5+RXC061S3 RATED 2000 0.96 0.97 0.98LOW 1750 0.94 0.91 0.96HIGH 2250 0.97 1.03 0.99

AUD100R9V5+RXC065S3 RATED 2000 0.96 0.97 1.01LOW 1750 0.94 0.91 0.98HIGH 2250 0.97 1.03 1.03

AUD100R9V5+RXH063S3 RATED 2000 1.01 1.00 0.99LOW 1750 0.99 0.94 0.97HIGH 2250 1.02 1.06 1.01

AUD120R9V5+RXC061S3 RATED 2000 0.96 0.98 0.97LOW 1750 0.95 0.92 0.95HIGH 2250 0.97 1.04 0.99

AUD120R9V5+RXC065S3 RATED 2000 0.96 0.98 1.00LOW 1750 0.94 0.92 0.98HIGH 2250 0.97 1.04 1.02

AUD120R9V5+RXH063S3 RATED 2000 1.01 1.01 0.98LOW 1750 0.99 0.94 0.96HIGH 2250 1.02 1.07 1.00

AUD140R9V5+RXC061S3 RATED 2000 0.96 0.98 0.95LOW 1750 0.94 0.92 0.94HIGH 2250 0.97 1.04 0.97

AUD140R9V5+RXC065S3 RATED 2000 0.96 0.99 0.98LOW 1750 0.95 0.92 0.96HIGH 2250 0.97 1.05 1.00

Page 23: ALLEGIANCE 16 MODELS 4A7A6024,036,048 & 060Bfurnacefactorydirect.ca/pdf/4a7a6 Product Data.pdf · ALLEGIANCE® 16 MODELS 4A7A6024,036,048 & 060B SPLIT SYSTEM ... the Unitary Air-Conditioner

PRODUCT DATAAmerican Standard Inc., Tyler, TX 75711-9010

DATA SUBJECT TO CHANGE WITHOUT NOTICE 23

4A7A6060B1 WITH 4TEE3F65A1 AT 1500 CFM 1ST STAGEO.D. I.D. TOT. SENS. CAP. AT ENTERING D.B. TEMP. TOTALD.B. W.B. CAP. 72 75 78 80 KW

59 41.6 34.6 38.8 41.6 41.6 3.0985 63 42.2 27.9 32.3 36.6 39.4 3.09

67 45.1 21.8 26.2 30.7 33.6 3.0971 48.4 15.6 20.1 24.6 27.6 3.07

59 39.7 33.9 38.2 39.7 39.7 3.5995 63 40.3 27.2 31.6 36.0 38.8 3.59

67 43.0 21.1 25.6 30.0 32.9 3.5971 46.2 14.9 19.4 23.9 26.9 3.56

59 37.6 33.1 37.4 37.6 37.6 4.13105 63 38.2 26.5 30.9 35.2 38.1 4.13

67 40.8 20.3 24.9 29.3 32.2 4.1371 43.8 14.1 18.6 23.2 26.2 4.10

59 35.3 32.3 35.3 35.3 35.3 4.72115 63 35.8 25.7 30.1 34.4 35.8 4.72

67 38.3 19.5 24.0 28.5 31.4 4.7271 41.1 13.2 17.8 22.4 25.4 4.68

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITY

LOW 1300 0.98 0.93HIGH 1700 1.02 1.07

NOTE: ALL TABLES ABOVE ARE AT ARI RATING CONDITIONS RATED WITH 25 FEET OF REFRIGERANT LINES.* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE VALID ONLY FOR WET COIL. ALL TEMPERATURES IN DEGREES F.

CORRECTION FACTORS FOR OTHER COMBINATIONS (MULTIPLY DATA BY FACTOR)MBTUH MBTUH SYST

INDOOR MODEL CFM TOT SEN KWAUD140R9V5+RXH063S3 RATED 1500 1.00 1.00 0.99

LOW 1300 0.98 0.93 0.98HIGH 1700 1.01 1.07 0.99

AUY120R9V5+RXC061S3 RATED 1500 0.95 0.97 1.01LOW 1300 0.94 0.90 1.00HIGH 1700 0.97 1.04 1.02

AUY120R9V5+RXC065S3 RATED 1500 0.95 0.97 1.02LOW 1300 0.93 0.89 1.01HIGH 1700 0.96 1.04 1.03

AUY120R9V5+RXH063S3 RATED 1500 0.99 0.99 1.01LOW 1300 0.97 0.91 1.00HIGH 1700 1.01 1.06 1.02

Performance DataCooling — 4A7A6060B1

4A7A6060B1 WITH 4TEE3F65A1 AT 2000 CFM 2ND STAGEO.D. I.D. TOT. SENS. CAP. AT ENTERING D.B. TEMP. TOTALD.B. W.B. CAP. 72 75 78 80 KW

59 56.6 44.6 50.1 55.3 56.6 4.8785 63 58.1 36.4 42.0 47.6 51.1 4.91

67 62.3 28.7 34.4 40.2 43.9 5.0271 67.1 21.0 26.6 32.4 36.3 5.09

59 54.1 43.8 49.2 54.1 54.1 5.4795 63 55.5 35.5 41.2 46.7 50.3 5.50

67 59.5 27.8 33.5 39.3 43.1 5.6371 64.1 20.0 25.7 31.5 35.4 5.71

59 51.2 42.8 48.2 51.2 51.2 6.08105 63 52.5 34.5 40.2 45.7 49.3 6.12

67 56.3 26.7 32.5 38.3 42.1 6.2671 60.7 18.9 24.6 30.5 34.4 6.35

59 47.8 41.6 47.0 47.8 47.8 6.71115 63 49.0 33.4 39.1 44.6 48.2 6.76

67 52.6 25.5 31.4 37.1 40.9 6.9171 56.7 17.6 23.4 29.3 33.2 7.02

CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITY

LOW 1750 0.98 0.93HIGH 2250 1.01 1.06

NOTE: ALL TABLES ABOVE ARE AT ARI RATING CONDITIONS RATED WITH 25 FEET OF REFRIGERANT LINES.* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE VALID ONLY FOR WET COIL. ALL TEMPERATURES IN DEGREES F.

CORRECTION FACTORS FOR OTHER COMBINATIONS (MULTIPLY DATA BY FACTOR)MBTUH MBTUH SYST

INDOOR MODEL CFM TOT SEN KWAUD140R9V5+RXH063S3 RATED 2000 1.01 1.01 0.98

LOW 1750 0.99 0.95 0.96HIGH 2250 1.02 1.07 0.99

AUY120R9V5+RXC061S3 RATED 2000 0.95 0.96 0.99LOW 1750 0.93 0.90 0.97HIGH 2250 0.96 1.01 1.01

AUY120R9V5+RXC065S3 RATED 2000 0.95 0.96 1.01LOW 1750 0.94 0.90 0.99HIGH 2250 0.96 1.02 1.03

AUY120R9V5+RXH063S3 RATED 2000 1.00 0.97 1.02LOW 1750 0.98 0.91 1.00HIGH 2250 1.01 1.03 1.04

Page 24: ALLEGIANCE 16 MODELS 4A7A6024,036,048 & 060Bfurnacefactorydirect.ca/pdf/4a7a6 Product Data.pdf · ALLEGIANCE® 16 MODELS 4A7A6024,036,048 & 060B SPLIT SYSTEM ... the Unitary Air-Conditioner

24 DATA SUBJECT TO CHANGE WITHOUT NOTICE

PRODUCT DATAAmerican Standard Inc., Tyler, TX 75711-9010

4A7A6024B 4A7A6036B

TypicalWiring

SCHEMATIC DIAGRAMS(SEE LEGEND)

Page 25: ALLEGIANCE 16 MODELS 4A7A6024,036,048 & 060Bfurnacefactorydirect.ca/pdf/4a7a6 Product Data.pdf · ALLEGIANCE® 16 MODELS 4A7A6024,036,048 & 060B SPLIT SYSTEM ... the Unitary Air-Conditioner

DATA SUBJECT TO CHANGE WITHOUT NOTICE 25

PRODUCT DATAAmerican Standard Inc., Tyler, TX 75711-9010

4A7A6060B4A7A6048B

TypicalWiring

SCHEMATIC DIAGRAMS(SEE LEGEND)

Page 26: ALLEGIANCE 16 MODELS 4A7A6024,036,048 & 060Bfurnacefactorydirect.ca/pdf/4a7a6 Product Data.pdf · ALLEGIANCE® 16 MODELS 4A7A6024,036,048 & 060B SPLIT SYSTEM ... the Unitary Air-Conditioner

26 DATA SUBJECT TO CHANGE WITHOUT NOTICE

PRODUCT DATAAmerican Standard Inc., Tyler, TX 75711-9010

SYMBOLS

LEGEND

TypicalWiring

SCHEMATIC DIAGRAMS

Page 27: ALLEGIANCE 16 MODELS 4A7A6024,036,048 & 060Bfurnacefactorydirect.ca/pdf/4a7a6 Product Data.pdf · ALLEGIANCE® 16 MODELS 4A7A6024,036,048 & 060B SPLIT SYSTEM ... the Unitary Air-Conditioner

DATA SUBJECT TO CHANGE WITHOUT NOTICE 27

PRODUCT DATAAmerican Standard Inc., Tyler, TX 75711-9010

From Dwg. D152862 Rev. 17

4A7A6 OUTLINE DRAWINGNOTE: ALL DIMENSIONS ARE IN MM (INCHES).

DimensionalData

MODELS BASE A B C D E F G H J K

4A7A6024B 3 933 (36-3/4) 829 (32-5/8) 756 (29-3/4) 5/8 5/16 143 (5-5/8) 92 (3-5/8) 210 (8-1/4) 79 (3-1/8) 508 (20)

4A7A6036B 4 841 (33-1/8)) 946 (37-1/4) 870 (34-1/4) 3/4 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 508 (20)

4A7A6048B 4 1045 (41-1/8) 946 (37-1/4) 870 (34-1/4) 7/8 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 508 (20)

4A7A6060B 4 1045 (41-1/8) 946 (37-1/4) 870 (34-1/4) 7/8 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 508 (20)

Page 28: ALLEGIANCE 16 MODELS 4A7A6024,036,048 & 060Bfurnacefactorydirect.ca/pdf/4a7a6 Product Data.pdf · ALLEGIANCE® 16 MODELS 4A7A6024,036,048 & 060B SPLIT SYSTEM ... the Unitary Air-Conditioner

Since the manufacturer has a policy of continuous productand product data improvement, it reserves the right tochange design and specifications without notice.

Technical Literature - Printed in U.S.A.

American Standard Inc.Troup HighwayTyler, TX 75711-9010

P.I.

GeneralThese models are fully charged from thefactory for matched indoor section andup to 15 feet of piping. This unit isdesigned to operate at outdoor ambienttemperatures as high as 115°F. Coolingcapacities are matched with a wideselection of air handlers and furnacecoils that are ARI certified. The unit is ULlisted. Exterior is designed for outdoorapplication.

CasingUnit casing is constructed of heavygauge, galvanized steel and paintedwith a weather-resistant powder paintfinish on all louvered panels. Corrosionand weatherproof CMBP-G30DuraBase™ base.

Refrigerant ControlsRefrigeration system controls includecondenser fan and compressor contactor.High and low pressure controls areinherent to the compressor. Unit also hashigh pressure switch. Another standardfeature is the liquid line drier.

CompressorThe Duration™ compressor featuresinternal over temperature and pressureprotector and dipped hermetic motor.Other features include: roto lock suctionand discharge refrigerant connections,centrifugal oil pump, and low vibrationand noise. The Duration™ compressorfeatures a 10-year limited warranty.

Condenser CoilThe Spine Fin™ coil is continuouslywrapped, corrosion resistant all aluminumwith minimum brazed joints. This coil isseamless aluminum glued to acontinuous aluminum fin. Coils are labtested to withstand 2,000 pounds ofpressure per square inch.

Low Ambient CoolingAs shipped, this unit has a coolingcapability to 55°F. The addition of anevaporator defrost control permitsoperation to 40°F. The addition of anevaporator defrost control with TXVpermits low ambient cooling to 30°F.

MechanicalSpecifications

PRODUCT DATAAmerican Standard Inc., Tyler, TX 75711-9010

AccessoriesThermostats — Heat/cooling(manual and automatic changeover).Sub-base to match thermostat andlocking thermostat cover.

Evaporator Defrost Control — SeeLow Ambient Cooling.

Outdoor Thermostat —Supplemental heat outdoor ambientlockout from 46 to –10°F.