Upload
paul-j-inferrera-set
View
137
Download
3
Tags:
Embed Size (px)
Citation preview
Alarms 101
Fire Alarm Systems TrainingFire Alarm Systems Training
Paul J. Inferrera, SET, Lead InstructorCape Fear Community College
Cells Phones / PagersPlease set cell phones, PDA’s and pagers to off or silent operation. If you need to accept a call, please do so quietly and leave the room to conduct your conversation
BreaksDue to the short duration of this seminar their will not be a scheduled break. You may excuse yourself at anytime but please do so quietly
QuestionsYou may ask questions at any time, but please wait to be recognized and respect whoever has the floor.
Housekeeping
www.cfcc.edu2
www.cfcc.edu3
About the Presenter
Lead Instructor, Cape Fear Community College• Fire Alarm Systems Training Program
NICET Ambassador• Fire Alarm Systems IV• Special Hazard Suppression Systems I
ASCET Communications Manager
Over 29 years of combined experience in the FireProtection industry.
www.cfcc.edu4
Program OverviewFire Alarm Systems Training
Fire Alarm Systems Training at Cape Fear Community
College is a program to produce competent and qualified
individuals. It is our belief that properly trained and
knowledgeable fire alarm system designers and technicians
will reduce the amount of false alarms and improve the
quality of life in their community.
Codes and Standards referenced are consistent withNICET’s allowable references for level I and II FireAlarm Systems exams
NFPA 70 (2011)
NFPA 72 (2013)
Consult with your Authority Having Jurisdiction (AHJ),or Project Specifications for the edition(s) enforced
www.cfcc.edu5
Codes and Standards
Learning Objectives
Know the origin and evolution of codes andstandards related to fire alarm systems
Be familiar with common definitions andterminology
Acquire a basic understanding of the configurationand operation of the various types of fire alarmsystems
Know the requirements of NFPA 72, the NationalFire Alarm Code and NFPA 70, the NationalElectric Code or NEC.
www.cfcc.edu6
www.cfcc.edu7
Electrical Workmanship Standards
Electrical Workmanship StandardsFire alarm systems are electrical in nature and the installationmethods are governed by the National Electric Code or NEC
The NEC is distributed by the National Fire ProtectionAssociation (NFPA) and is also referred to as NFPA 70
The fire alarm code mandates how fire alarm devices andsystems are installed and commonly refers to the electricalcode for installation
All fire alarm technicians must be familiar with theinstallation requirements and methods described in theNEC.
www.cfcc.edu8
Electrical Workmanship Standards
www.cfcc.edu9
NEC Requirements Shall be grounded in accordance with Article 250
Wiring shall be installed in a workmanship-like manner
• Comply with chapters 1-4 unless modified by chapters 5-8
Fire alarm system wiring requirements are specifically listed in Article 760
Electrical requirements for classified areas or those that contain a hazardous atmosphere are listed in Article 500
Requirements for fiber optic cabling and raceways are listed in Article 770.
www.cfcc.edu10
Wiring Fundamentals
Wiring FundamentalsElectrical workmanship standards are a critical component to theproper operation of any electrical system
All electrical installations are only as good as the connectionsof wiring and devices
A loose wire or bad connection can create intermittent faultsthat are difficult to locate and correct
In some installations where workmanship is not aconsideration, it is less labor intensive to removed andreplace the wiring than try to locate the fault
Special care should be taken to make proper electricalconnections associated with a fire alarm installation.
www.cfcc.edu11
Wiring Fundamentals
www.cfcc.edu12
SafetyThe control of hazardous energy is the purpose of the Lockout/Tagout program commonly referred to as LOTO
OSHA Standard 29 CFR 1910. 147, the Control of Hazardous Energy
Requirements for isolation of both kinetic and potential energy
Authorized (Qualified) Employees are the only ones certified to lock and tag out equipment.
Wiring Fundamentals
www.cfcc.edu13
Conduit FillElectrical conduit, whether it be metal electrical metal tubing ( EMT), plastic (PVC), or flexible conduit, each have their own maximum number of electrical wires allowed in the conduit. Their fill capacities are different, even though they may be the same sized conduit
PVC is a plastic conduit that is often used for underground installations and in wet areas
EMT conduit is a metal thin walled that comes in ten foot lengths
Flexible conduit is normally made of twisted metal and is flexible
Chapter 9 of NEC contains tables to calculate conduit fill.
Wiring Fundamentals
www.cfcc.edu14
Box FillBox fill isn't just the number of wires in the box — it's the total volume of the conductors, devices, and fittings in a box
Box volume - amount of space for conductors, devices, and fittings
Calculate box fill per NEC Table 314.16(B)
Calculate box volume per NEC Table 314.16(A).
www.cfcc.edu15
Codes and Standards
Codes and StandardsCodes and standards govern products, construction,manufacturing, communication protocols and every aspect of ourlives. A uniform and agreed upon way of doing things enabledmilestones in human existence such as the production line andthe calendar
Earliest building code is thought to have been developedsometime between 1955 B.C. and 1913 B.C.
Reign King Hammurabi of Babylon or “Hammurabi’s Code”
Code didn't specify how to build a building, but laid out theconsequences of not building well
Fire alarm systems are required by code and installed perstandards.
www.cfcc.edu16
Codes and Standards
www.cfcc.edu17
CodesA code is a model or a set of rules that are recommended for others to follow Not a law, but can be adopted into law
StandardsA published document that contains a technical specification or other precise criteria designed to be used consistently as a rule, guideline or definition An agreed, repeatable way of doing something Laws and regulations may refer to certain standards and
make compliance with them compulsory.
Codes and Standards
www.cfcc.edu18
National Fire Protection Association (NFPA)NFPA has developed more than 300 codes and standards that are in use throughout the world
19th century, automatic sprinkler systems came into use as an effective way to put out fires
Designed independently and there were nine different pipe sizes
In 1895, sprinkler manufacture and fire insurance develop a uniform standard for the installation of sprinklers
Following year, as an outgrowth of that group, the NFPA was founded.
Codes and Standards
www.cfcc.edu19
NFPA 70By the end of 1895, there were five different recognized standards in the United States that addressed the safe use of electrical equipment Several national organizations held a meeting in New York
on March 18, 1896 Joint Conference of Electrical and Allied Interests Five American Codes, with the German Code, the Code of
the British Board of Trade and the Phoenix Rules of England Met again in May and June of 1897 and established an
electrical code Issued by National Board of Fire Underwriters as the
"National Electrical Code of 1897" or NEC.
Codes and Standards
www.cfcc.edu20
NFPA 72NFPA 72 specifies fire alarm systems and their components which was prepared by the Technical Committees on Fundamentals of fire alarm systems for the protection of life and property Covers the application, installation, location, performance,
inspection, testing and maintenance of fire alarm systems and emergency communications systems (ECS), and their devices
Federal, state, and local municipalities have adopted the National Fire Alarm Code as a standard
NFPA’s signaling standards date back to 1898 and represent the inclusion of other codes during its evolution.
Codes and Standards
www.cfcc.edu21
Others
NFPA 101, Life Safety Code
NFPA 170, Standard for Fire Safety and Emergency Symbols
International Building Code (IBC).
www.cfcc.edu22
Fire Alarm Symbols and Terminology
Fire Alarm Symbols and Terminology
The 1994 edition of NFPA 170 represented the completion of aneffort to combine four previously separate documents thatcovered fire safety symbols for different purposes
NFPA 171, Public Firesafety Symbols
NFPA 172, Fire Protection Symbols for Architectural andEngineering drawings
NFPA 174, Fire Protection Symbols for Risk AnalysisDiagrams
NFPA 178, Symbols for Fire Fighting Operations
Also refer to NFPA 72 Annex for fire alarm icons.
www.cfcc.edu23
Fire Alarm Symbols and Terminology
Common TermsThe following definitions can be found in NFPA 72, Chapter 3
Approved - Acceptable to the Authority Having Jurisdiction
Authority Having Jurisdiction (AHJ) - The organization,office, or individual responsible for approving equipment,materials, an installation, or a procedure
Labeled - Equipment or materials to which has been attacheda label, symbol, or other identifying mark of an organizationthat is acceptable
Listed - Equipment, materials or services included in a list.
www.cfcc.edu24
Fire Alarm Symbols and Terminology
Common Terms Fire Safety Function - Building and fire control functions
that are intended to increase the level of life safety foroccupants
Path (Pathways) - Any conductor, optical fiber, radio carrieror other means for transmitting fire alarm systeminformation between two or more locations
Protected Premise - The physical location protected by a firealarm system
Shall - Indicates a mandatory requirement
Should - Indicates a recommendation or that which is advisedbut not required.
www.cfcc.edu25
www.cfcc.edu26
Fire Alarm Systems
Fire Alarm SystemsFire Alarm Systems are installed, tested and serviced per thestandards listed in NFPA 72Purpose of fire alarm systems Provide notification of alarm, supervisory and trouble
conditions Alert the occupants Summon aid Control fire safety functions
Equipment constructed and installed shall conform with NFPA 72 Shall be listed for the purpose for which it is used Installed per manufacturers’ installation instructions and
NFPA 72, the National Fire Alarm Code.
www.cfcc.edu27
Fire Alarm SystemsDocumentation
Documentation is one of the most important concepts of NFPA72. It is also the most frequently ignored requirement All fire alarm system installations shall have a written
statement• Record of Completion
Allows you to specify any deviations from the code Building owner shall be provided with documents A record of maintenance, inspection and tests shall be
provided• Date work was performed• Test frequency from NFPA 72• Status of problems identified during test stating owner
was notified, problem was corrected and successfullyretested.
www.cfcc.edu28
DocumentationUpon final acceptance of the system, the building owner shall beprovided with the following documents
An owner's manual and installation instructions covering allsystem equipment
Record drawings
For software-based systems, a record copy of the site-specificsoftware.
Fire Alarm Systems
www.cfcc.edu29
Fire Alarm SystemsQualifications
Installation personnel shall be supervised by persons who arequalified and experienced in the installation, inspection andtesting of fire alarm systems Factory trained and certified personnel in the installation for
the specific system Personnel who are certified by a nationally recognized fire
alarm certification organization acceptable to the authorityhaving jurisdiction such as NICET
Personnel licensed or certified by a state or local authority.
www.cfcc.edu30
Fire Alarm SystemsSystem Signals
Audible alarm notification appliances for a fire alarm system shallproduce signals that are distinctive Their sound shall not be used for any other purpose Signal precedence
• Alarm – presence of fire danger• Supervisory- off normal condition• Trouble - equipment
Signals from hold-up alarms or other life-threatening signals shallbe permitted to take precedence over supervisory and troublesignals if acceptable to the authority having jurisdiction.
www.cfcc.edu31
Fire Alarm SystemsSystem Signals
Equipment shall be designed so that it is capable of performing itsintended functions Within 85 percent and at 110 percent of the nameplate
primary and secondary input voltage(s) Ambient temperatures of 32° degrees F and 120° degrees F Relative humidity of 85 percent
The installation of all wiring, cable, and equipment shall be inaccordance with NFPA 70, National Electrical Code Fire Alarm - Article 760 Grounding - Article 250.
www.cfcc.edu32
Fire Alarm SystemsElectrical Requirements
NFPA 72, The National Fire Alarm Code specifies to ensure aminimum level of reliability for fire alarm systems At least two independent and reliable power supplies
• Primary• Secondary
Monitored for integrity (supervised) Dedicated branch circuit shall be mechanically protected and
identified as "FIRE ALARM CIRCUIT“.
www.cfcc.edu33
www.cfcc.edu34
Types of Fire Alarm Systems
Types of Fire Alarm Systems
www.cfcc.edu35
Protected Premises (Local) SystemsProtected Premises systems sound an alarm at the protected facility only. This alarm is initiated from a pull station, automatic detector or activation of a suppression system
Purpose of a Protected Premise System
Protection of life and property
Notification to occupants of a fire emergency
Implementation of the evacuation / relocation plan for the building.
Types of Fire Alarm Systems
www.cfcc.edu36
Protected Premises (Local) SystemsProtected Premises fire alarm systems consist of the following
Fire alarm control equipment
Initiating devices
Notification appliances
Secondary power source
Ancillary connections or Fire Safety functions (elevator recall, fan shutdown).
Types of Fire Alarm Systems
www.cfcc.edu37
Protected Premises (Local) Fire Alarm SystemsA Protected Premises fire alarm system
Is required to use properly listed fire alarm equipment
Is not required to have a listed installation
Is not monitored at all
Is required to have regularly scheduled inspection and testing in accordance with NFPA 72
Is not required to have additional service elements provided.
Equipment Installation Monitoring Other Requirements
Local System Listed Not Listed Not Required None
Proprietary Station
Remote Station
Central Station
Auxiliary
System Requirements
Types of Fire Alarm Systems
www.cfcc.edu38
Proprietary Station Fire Alarm SystemsProprietary Station serves contiguous and non-contiguous properties under one ownership. The same company or organization that owns the protected facility and fire alarm equipment, owns the monitoring facility
Purpose of a Proprietary Station System Protection of life and property Notification to occupants of a fire emergency Evacuation / relocation of occupants Notification to a supervising station of a fire emergency Dispatch of emergency forces (fire department) to the
protected property.
Types of Fire Alarm Systems
www.cfcc.edu39
Proprietary Station Fire Alarm SystemsProprietary Station fire alarm systems consist of the following Fire alarm control equipment Initiating devices Notification appliances Secondary power source Ancillary connections or Fire Safety functions (elevator recall,
fan shutdown) Connection to a supervising station under the same ownership
as the protected facilityMost critical factor for proprietary station systems is that the protected facility and the monitoring station are under ONE OWNERSHIP.
Types of Fire Alarm Systems
www.cfcc.edu40
Equipment Installation Monitoring Other Requirements
Local System Listed Not Listed Not Required None
Proprietary Station Listed Not Listed Listed or Not
Listed Runner Service
Remote Station
Central Station
Auxiliary
System Requirements
Types of Fire Alarm Systems
www.cfcc.edu41
Remote Station Fire Alarm SystemsRemote Station fire alarm systems are designed to transmit signals from a protected facility to a remote monitoring station where appropriate action can be taken
Purpose of a Remote Station System
Protection of life and property Notification to occupants of a fire emergency Evacuation / relocation of occupants Notification to a supervising station of a fire emergency Dispatch of emergency forces (fire department) to the
protected property.
Types of Fire Alarm Systems
www.cfcc.edu42
Remote Station Fire Alarm SystemsRemote Station fire alarm systems consist of the following Fire alarm control equipment Initiating devices Notification appliances Secondary power source Ancillary connections or Fire Safety functions (elevator
recall, fan shutdown) Connection to a remote monitoring facility.
Types of Fire Alarm Systems
www.cfcc.edu43
Definition:Remote monitoring facility
A monitoring facility for fire alarm system signals whichmay or may not be listed. Remote stations are notrequired to provide the service elements that are requiredfor Central Stations as defined by NFPA 72
Remote Station Fire Alarm Systems are the most common typeof fire alarm system that most companies install.
Types of Fire Alarm Systems
www.cfcc.edu44
Equipment Installation Monitoring Other Requirements
Local System Listed Not Listed Not Required None
Proprietary Station Listed Not Listed Listed or Not Listed Runner Service
Remote Station Listed No Listed Listed or Not Listed None
Central Station
Auxiliary
System Requirements
Types of Fire Alarm Systems
www.cfcc.edu45
Central Station Fire Alarm SystemsCentral Station fire alarm systems are designed to transmit signalsfrom a protected facility to a listed central station whereappropriate action can be taken
Additionally, central station systems require specific serviceelements, contract arrangements and installation requirementswhich exceed standard industry practice
These additional requirements are intended to provide a higher levelof fire protection for certain at-risk facilities.
Types of Fire Alarm Systems
www.cfcc.edu46
Central Station Fire Alarm SystemsPurpose of a Central Station System
Protection of life and property Notification to occupants of a fire emergency Evacuation / relocation of occupants Notification to a listed monitoring facility of a fire
emergency Dispatch of emergency forces (fire department) to the
protected property Provide an increased level of system reliability than any of
the other systems.
Types of Fire Alarm Systems
www.cfcc.edu47
Central Station Fire Alarm SystemsCentral Station fire alarm systems consist of the following Fire alarm control equipment Initiating devices Notification appliances Secondary power source Ancillary connections or Fire Safety functions (elevator
recall) Connection to a listed central station monitoring facility Specific contract arrangements Specific central station system service elements Listed installation Placarding.
Types of Fire Alarm Systems
www.cfcc.edu48
Central Station Fire Alarm Systems
The specific Central Station service elements are Installation of fire alarm transmitters Alarm, guard, supervisory and trouble signal monitoring Retransmission Associated record keeping and reporting Testing and maintenance Runner Service
The specific contract arrangements are as follows Subscriber contracts with Listed Central Station Subscriber contracts with Listed Installation Company.
Types of Fire Alarm Systems
www.cfcc.edu49
Central Station Fire Alarm SystemsFor Central Station systems it is required that the contracts forall aspects of the system be directly between the subscriber and alisted company.
The listed company is called the prime contractor
The requirement for installing a central station firealarm system comes from an Authority HavingJurisdiction (AHJ), usually and Insurance Authority
For some facilities, no insurance will be provided unless thehigher standards of a Central Station Fire Alarm System areinstalled.
Types of Fire Alarm Systems
www.cfcc.edu50
Equipment Installation Monitoring Other Requirements
Local System Listed Not Listed Not Required None
Proprietary Station Listed Not Listed Listed or Not Listed Runner Service
Remote Station Listed Not Listed Listed or Not Listed None
Central Station Listed Listed Listed Runner Service
Auxiliary
System Requirements
Types of Fire Alarm Systems
www.cfcc.edu51
Auxiliary Fire Alarm SystemsAuxiliary fire alarm system connected to a municipal fire alarmsystem (old street boxes) for the purpose of transmitting alarmsignals to the public fire service communications centerPurpose of an Auxiliary System Protection of life and property Notification to occupants of a fire emergency Evacuation / relocation of occupants Notification to the public fire service communications
center Dispatch of emergency forces (fire department) Use existing street boxes to provide the transmission
means for the signal.
Types of Fire Alarm Systems
www.cfcc.edu52
Auxiliary Fire Alarm SystemsToday, most fire alarm systems use a digital communicator totransmit signals. Many years ago fire alarm systems used themunicipal street boxes to get signals to the fire dept. There arestill some communities in the country who still use this method.Auxiliary System consist of the following
Fire alarm control equipment Initiating devices Notification appliances Secondary power source Ancillary or Fire Safety functions (elev. recall, fan
shutdown) Connection to a municipal street box.
Types of Fire Alarm Systems
www.cfcc.edu53
Auxiliary Fire Alarm SystemsThere are two types of Auxiliary fire alarm systems
1. Local Energy
2. Shunt Type
Note: 14 AWG is the smallest conductor size allowed for shunttype auxiliary circuits.
Types of Fire Alarm Systems
www.cfcc.edu54
Equipment Installation Monitoring Other Requirements
Local System Listed Not Listed Not Required None
Proprietary Station Listed Not Listed Listed or Not Listed Runner Service
Remote Station Listed Not Listed Listed or Not Listed None
Central Station Listed Listed Listed Runner Service
Auxiliary Listed Not ListedPublic
Communication Center
Street Boxes
System Requirements
Types of Fire Alarm Systems
www.cfcc.edu55
www.cfcc.edu56
Circuits and Pathways
ConductorsThis term normally refers to wire and cable that will allow theflow of electrons, or "conduct" electricity
Stranded
Solid
Susceptible to transient voltages.
Circuits and Pathways
www.cfcc.edu57
Fiber OpticConsist of a glass material that transmits amplified light from atransmitter to a receiver
Thinner and less expensive than copper
Not affected by transient voltages
Connections must be made by competent person.
Circuits and Pathways
www.cfcc.edu58
WirelessWireless networks utilize radio waves and/or microwaves tomaintain communication channels between computers
Eliminates wire and cabling
Interfered by radio signals and weather
Not affected by transient voltages.
Circuits and Pathways
www.cfcc.edu59
CharacteristicsPerformance characteristics are based upon their ability toindicate alarm and trouble at the central control equipmentduring specified abnormal conditions
For years, we identified circuits as class A or class B
National Fire Alarm Code went international
The styles of circuits were included for this purpose.
Circuits and Pathways
www.cfcc.edu60
Initiating Device Circuits (IDC)Class B initiating device circuits provide one path for signaltransmission
Class B circuits are two-wire circuits
Devices on a Class B circuit will operate up to thelocation of the abnormal condition
Devices beyond the abnormal condition will not operate
Single open.
Circuits and Pathways
www.cfcc.edu61
Initiating Device Circuits (IDC)Class B
Circuits and Pathways
www.cfcc.edu62
Initiating Device Circuits (IDC)Class B
Circuits and Pathways
www.cfcc.edu63
Initiating Device Circuits (IDC)Class A initiating device circuits provide two paths for signaltransmission
Class A circuits are four-wire circuits
This allows the signal to be transmitted from all deviceseven when an abnormal condition exists
Single open
Single ground.
Circuits and Pathways
www.cfcc.edu64
Initiating Device Circuits (IDC)Class A
Circuits and Pathways
www.cfcc.edu65
Initiating Device Circuits (IDC)Class A
Circuits and Pathways
www.cfcc.edu66
Signaling Line Circuits (SLC)Class B signaling line circuits provide one path for signaltransmission
Class B circuits are two-wire circuits
Devices on a Class B circuit will operate up to thelocation of the abnormal condition
Devices beyond the abnormal condition will not operate
Single open.
Circuits and Pathways
www.cfcc.edu67
Signaling Line Circuits (SLC)Class B, Style 4
Circuits and Pathways
www.cfcc.edu68
Signaling Line Circuits (SLC)Class B, Style 4
Circuits and Pathways
www.cfcc.edu69
Signaling Line Circuits (SLC)Class A signaling line circuits provide two paths for signaltransmission
Class A circuits are four-wire circuits
This allows the signal to be transmitted from all deviceseven when an abnormal condition exists
Single open
Single ground.
Circuits and Pathways
www.cfcc.edu70
Signaling Line Circuits (SLC)Class A, Style 6
Circuits and Pathways
www.cfcc.edu71
Signaling Line Circuits (SLC)Class A, Style 6
Circuits and Pathways
www.cfcc.edu72
Signaling Line Circuits (SLC)Class A, Style 7
Circuits and Pathways
www.cfcc.edu73
Signaling Line Circuits (SLC)Class A, Style 7
Circuits and Pathways
www.cfcc.edu74
Signaling Line Circuits (SLC)Class A, Style 7
Circuits and Pathways
www.cfcc.edu75
Notification Appliance Circuit (NAC)Class B notification appliance circuits provide one path forpower to reach appliances
Class B circuits are two-wire circuits
Devices on a Class B circuit will operate up to thelocation of the abnormal condition
Devices beyond the abnormal condition will not operate
Single open
Wire-to-wire short.
Circuits and Pathways
www.cfcc.edu76
Notification Appliance Circuit (NAC)Class B
Circuits and Pathways
www.cfcc.edu77
Notification Appliance Circuit (NAC)Class B
Circuits and Pathways
www.cfcc.edu78
Notification Appliance Circuit (NAC)Class A notification appliance circuits provide two paths forvoltage and current to reach appliances
Class A circuits are four-wire circuits
This allows power to reach all devices even when anabnormal condition exists
Single open
Single ground.
Circuits and Pathways
www.cfcc.edu79
Notification Appliance Circuit (NAC)Class A
Circuits and Pathways
www.cfcc.edu80
Notification Appliance Circuit (NAC)Class A
Circuits and Pathways
www.cfcc.edu81
Circuits and Pathways“Monitoring Integrity of Installation Conductors and OtherSignaling Channels”
All means of interconnecting equipment, devices, andappliances
Interconnecting conductors
All other signaling channels
Fault and restoration to normal shall be automaticallyindicated within 200 seconds.
Circuits and Pathways
www.cfcc.edu82
Circuits and PathwaysThe class or style of signaling circuits and pathways shall bedetermined from an evaluation based on the path performancedetailed in NFPA 72 and on engineering judgment
Determining the integrity and reliability
Transmission media
Length of circuit conductors
Nature of hazard
Objectives of system.
Circuits and Pathways
www.cfcc.edu83
Initiating Devices
www.cfcc.edu84
Initiating DevicesAn initiation device initiates a signal as a result of activation.Some initiating devices initiate an alarm signal and some devicesinitiate a supervisory signal.
NFPA 72, The National Fire Alarm Code recognizes threeways to initiate an alarm signal
• Manual means
• Automatic detection
• Activation of a suppression system.
www.cfcc.edu85
Initiating DevicesRequirements
Subject to mechanical damage, device shall be protected
Shall be supported independently of their attachment to thecircuit conductors
Installed in manner that provides accessibility for periodicmaintenance
Shall be installed in all areas, compartments, or locationswhere required by other NFPA codes and standards
Duplicate terminals, leads, or connectors that provide forthe connection of installation wiring shall be provided oneach initiating device.
www.cfcc.edu86
Initiating DevicesManual
Manual fire alarm boxes shall be used only for fire alarm-initiating purposes
Each manual fire alarm box shall be securely mounted The operable part of each manual fire alarm box shall be not
less than 3½ feet and not more than 4½ feet above floorlevel
Shall be located within 5 feet of the exit doorway opening ateach exit on each floor
Shall be mounted on both sides of grouped openings over 40feet in width, and within 5 feet of each side of the opening
Additional boxes shall be provided so that the traveldistance to the nearest will not be in excess of 200 feet.
www.cfcc.edu87
Initiating DevicesSupervisory
Two separate and distinct signals shall be initiated: off-normal and restoration of the valve to its normal position
The off-normal signal shall be initiated during the first tworevolutions of the hand wheel or during one-fifth of thetravel distance of the valve control apparatus from itsnormal position
The off-normal signal shall not be restored at any valveposition except normal
An initiating device for supervising the position of a controlvalve shall not interfere with the operation of the valve,obstruct the view of its indicator, or prevent access for valvemaintenance.
www.cfcc.edu88
Automatic Detection Methods
www.cfcc.edu89
Fire SignatureA fire produces elements that can be detected
Heat Smoke (aerosol particulate) Gas Light radiation
Challenges of Detection
Not all fires produce all elements Ambient conditions may mimic elements.
Automatic Detection Methods
www.cfcc.edu90
Classified by NFPA 72Groups
Heat or Thermal – high temperature and/or rate of rise Smoke – aerosol particles Fire-Gas Sensing – detects gases produced by fire Radiant Energy – detects ultraviolet, infrared or visible
light radiationTypes
Line type Spot Type Air Sampling.
Automatic Detection Methods
www.cfcc.edu91
CombinationRespond to fire elements either
Respond to more than one fire elementEx. Smoke detector with thermal element
More than one operating principle for one elementEx. Rate of rise and fixed temperature
Detectors either Send data to control panel for processing Makes decision and signals control panel.
Automatic Detection Methods
www.cfcc.edu92
www.cfcc.edu93
Smoke Sensing Detectors
Characteristics
Provide faster response than heat detectors Actuate prior to deadly effects of fire Considered a life safety device Listed spacing is not reduced
Types Ionization Photoelectric Projected beam Air sampling.
Smoke Detectors
www.cfcc.edu94
TypesIonization
Radioactive material ionizes air in sensing chamberPhotoelectric
Light source is scattered by smoke in sensing chamberProjected Beam
Intensity of beam is reduced at receiverAir Sampling
Aspiration system induces atmosphere to sensingchamber.
Smoke Detectors
www.cfcc.edu95
Heat Sensing Detectors
www.cfcc.edu96
Heat DetectorsCharacteristics
Most reliable automatic detector Not considered a life safety device Listed spacing is reduced as height increases
Types Fixed temperature Rate of rise Rate compensation Line type.
Heat (Thermal) Detectors
www.cfcc.edu97
TypesFixed Temperature
Initiates alarm when temperature is reachedRate of Rise
Initiates alarm when temperature rises in a short timeLine Type
Initiates alarm when cable is shorted Initiates alarm upon increase in current flow Initiates alarm upon loss of pressure
Rate Compensation Initiates alarm when ambient temperature is reached.
Heat (Thermal) Detectors
www.cfcc.edu98
Operating ModesRestorable
Not normally destroyed Restoration may be manual or automatic
Non-Restorable
Element designed to be destroyed.
Heat Detectors
www.cfcc.edu99
Temperature Class Temperature Range (˚F)
Maximum Ceiling Temperature (˚F) Color Code
Low 100 - 134 20 below Uncolored
Ordinary 135 - 174 100 Uncolored
Intermediate 174 - 249 150 White
High 250 - 324 225 Blue
Extra High 325 - 399 300 Red
Very Extra High 400 - 499 375 Green
Ultra High 500 - 575 475 Orange
Required to be color coded
Heat (Thermal) Detectors
www.cfcc.edu100
Required to be listed for spacing
Ceiling Height Reduce Spacing Multiply Listed Spacing By
0 Up to & incldg 10’ 0 1 (1 x 50 = 50’ spacing)
10.1’ Up to & incldg 12’ 9% .91 (.91 x 50 = 45.5’)
12.1’ Up to & incldg 14’ 16% .84 (.84 x 50 = 42’)
14.1’ Up to & incldg 16’ 23% .77 (.77 x 50 = 38.5’)
16.1’ Up to & incldg 18’ 29% .71 (.71 x 50 = 35.5’)
18.1’ Up to & incldg 20’ 36% .64 (.64 x 50 = 32’)
20.1’ Up to & incldg 22’ 42% .58 (.58 x 50 = 29’)
22.1’ Up to & incldg 24’ 48% .52 (.52 x 50 = 26’)
24.1’ Up to & incldg 26’ 54% .46 (.46 x 50 = 23’)
26.1’ Up to & incldg 28’ 60% .40 (.40 x 50 = 20’)
28.1’ Up to & incldg 30’ 66% .36 (.36 x 50 = 18’)
Heat (Thermal) Detectors
www.cfcc.edu101
System Notification Appliances
www.cfcc.edu102
History 1971 – Space Age Electronics introduced the first visual
notification appliance
1978 – Wheelock introduced the first horn/strobe notificationappliance
1980’s – Most new installations included visual appliances
1990 – ADA required audible appliance to have strobe lightsfor the hearing impaired
1996 – ADA required strobe to be at least 15 candela and flashrate of 60 flashes per minute
Today – Synchronization of strobes to prevent seizures.
System Notification Appliances
www.cfcc.edu103
Purpose Initiate evacuation or relocation of building occupants
Alert building staff to initiate building emergency plan
Methods Audible
Visual
Combination audible / visual.
System Notification Appliances
www.cfcc.edu104
American with Disabilities Act Passed by federal government in 1990
Requires easier access for handicapped individuals
Small part of law governs audible and visual requirements forfire alarm systems
Law differs from NFPA 72• Minimum candela• Mounting requirements• Spacing.
System Notification Appliances
www.cfcc.edu105
American with Disabilities Act Strobes in same field of view to be synchronized
Minimum strobe candela of 15cd
Audible devices 5db above max, 15db above ambient
Maximum sound level of 120db
Strobes in sleeping areas for hearing impaired at least 110cd
Sleeping areas for hearing impaired may employ bed shakers.
System Notification Appliances
www.cfcc.edu106
Audible AppliancesTemporal 3 (T3) evacuation signal shall be used
Audible 15db above ambient
Audible 5db above max sound level lasting 60 seconds ormore
90” minimum height above finished floor (AFF)
Mounted at least 6” down from ceiling• Shall take precedence
Audible devices shall be red or nominal white.
System Notification Appliances
www.cfcc.edu107
Methods Use sound meter to measure ambient noise
Shut down equipment to overcome ambient noise
Add strobes when ambient noise level exceeds 105db
NFPA 72 list average ambient sound levels
Coding Pattern or tones produced by a audible notification appliance
• Controlled by panel or device
Prior to 1996 devices produced steady tone
• Pattern standardized by ANSI and NFPA.
System Notification Appliances
www.cfcc.edu108
Requirements Shall flash at rate of 1 flash per second minimum and 2 flashes
per second maximum
Entire lens is no less than 80” AFF
Spacing shall comply with NFPA 72
Combination audible and visual device shall be mounted pervisual requirements
Shall be synchronized when one or more in field of view
Maximum candela rating of 1,000 cd.
System Notification Appliances
www.cfcc.edu109
Requirements Emergency voice evacuation system separate from fire alarm
control panel
Fire Command Center shall be provided
• Located in 1-hour fire rated area
Live voice instructions shall take precedence over all previousand subsequent signals
At least two speakers shall be installed in each paging zone
Two-way communications equipment shall be for use by thefire service and listed for fire system use.
System Notification Appliances
www.cfcc.edu110
Periodic Tests and Inspections
www.cfcc.edu111
Periodic Tests and InspectionsPeriodic system testing is critical to ensuring proper operation offire alarm signaling systems during alarm situations.
Batteries that may appear adequate with primary poweravailable may fail under alarm load during an outage
Fire alarm system inspections should follow the requirementsof NFPA 72 for when and how they are to be conducted
As always, it is important to generate proper documentationof equipment and devices tested and any deficiency found isreported to the appropriate persons.
www.cfcc.edu112
Periodic Tests and InspectionsResponsibilities
The owner or the owner’s designated representative shall beresponsible for inspection, testing, and maintenance of the systemand alterations or additions to this system
Shall be permitted to be done by a person or organizationother than the owner if conducted under a written contract
Service personnel shall be qualified and experienced in theinspection, testing, and maintenance of fire alarm systems
All persons and facilities receiving alarm, supervisory, ortrouble signals and all building occupants shall be notified ofthe testing to prevent unnecessary response.
www.cfcc.edu113
Periodic Tests and InspectionsWhen?
All new systems shall be inspected and tested in accordance withthe requirements of NFPA 72
When an initiating device, notification appliance, or controlrelay is added, it shall be functionally tested
When an initiating device, notification appliance, or controlrelay is deleted, another device, appliance, or control relay onthe circuit shall be operated
When modifications or repairs to control equipmenthardware are made, the control equipment shall be tested.
www.cfcc.edu114
Periodic Tests and InspectionsRequirements
When changes are made to site-specific software, the followingshall apply
All functions known to be affected by the change, oridentified by a means that indicates changes, shall be 100percent tested
In addition, 10 percent of initiating devices that are notdirectly affected by the change, up to a maximum of 50devices, also shall be tested and correct system operation shallbe verified
A revised record of completion shall be prepared to reflectthese changes.
www.cfcc.edu115
Fire Alarm Systems Training
Questions?
www.cfcc.edu116
Contact Information
@fast_ilm
Cape Fear Community College4500 Blue Clay RoadCastle Hayne, NC 28429www.cfcc.edu
Thank You!
www.cfcc.edu117