4
www.frigopol.com MA-041-01-chiller R-290 air Aircooled Chiller FP-AC290 Cooling Capacity: 30kW—350kW Refrigerant: R-290

Aircooled Chiller FP-AC290 - Frigopol Kälteanlagen...The air-cooled chiller FP-AC290 is manufactured with two refrigerant circuits and with two compressors till a capacity of 230kW

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Aircooled Chiller FP-AC290 - Frigopol Kälteanlagen...The air-cooled chiller FP-AC290 is manufactured with two refrigerant circuits and with two compressors till a capacity of 230kW

www.frigopol.com

MA-041-01-chiller R-290 air

Aircooled Chiller FP-AC290

Cooling Capacity: 30kW—350kW

Refrigerant: R-290

Page 2: Aircooled Chiller FP-AC290 - Frigopol Kälteanlagen...The air-cooled chiller FP-AC290 is manufactured with two refrigerant circuits and with two compressors till a capacity of 230kW

The design, planning and engineering of all components and parts is specifically for the Refrigerant R-290. The characteristics of R-290 are :

• GWP (Global Warming Potential) : 3

• ODP (Ozone Depletion Potential ) : 0 • Categorization in class A3, EN 378

Cooling Capacity: 30kW—350kW

Refrigerant: R-290

Description: The air-cooled chiller is factory adjusted and ready for the on-site installation. Each device at the chiller has passed pressure tests and the unit is filled with nitrogen for delivery. The plug-in version includes in addition to the refrigeration part the electrical cabinet and the, for the application optimzed and preset, control. The air-cooled chiller FP-AC290 is manufactured with two refrigerant circuits and with two compressors till a capacity of 230kW and from 260kW to 350kW capacity with three refrigerant circuits and three compressors. Capacity control of the chiller works in 4 steps. All required components are for automatic function and assembled at the factory. The chiller is built on a base frame, made of galvanized steel. The panels and doors can be easily opened or blocked by a cabinet key. The epoxidpolyester—coating is baked at 180°C and provides the very high sur face strength optimum protection. In the machine housing is also the electric cabinet, which is accessible from the out-side by means of lockable doors. The display of the control unit is easily accessible for service purposes. The exhaust fan in accordance to EN 378 in EX-proofed version is installed in the housing and is protected for outdoor installation. The internal space of the casing is monitored by a gas detector that shuts off the power supply in case of refrige-rant leakage and starts the exhaust fan. The chiller is made for indoor or outdoor installation and is manufactured according the EN 378 Design features: - Reciprocating compressor (4 or 6-cylinder Bitzer) - Air-cooled condenser with housing mounted on base frame for indoor and outdoor installation - EC-condenser fans with appropriate control - Refrigerant collector with mounted safety valve to refrigerant migration - Liquid line with filter drier incl. replaceable insert, fill valve, sight glass and check valve - Evaporator is designed as shell & tube heat exchanger - Hydraulic side with sensors at the inlet and outlet, flange connections, a flow switch, filling and emptying possi-bility - Electronic control for evaporator - Suction side with 13mm or 19mm Kaiflex isolation - Electrical cabinet and control, including system-specific software, and optimizer - Control technology accessories and safety devices - Documentation in CAD (standard version or optional special version)

Page 3: Aircooled Chiller FP-AC290 - Frigopol Kälteanlagen...The air-cooled chiller FP-AC290 is manufactured with two refrigerant circuits and with two compressors till a capacity of 230kW

FP-AC290-XXX/06W/35A 50S2 70S2 100S2 110S2 130S2 170S2

Cooling capacity kW 40,6 62,6 95,4 109,6 125,4 168,8

EER 2,71 2,69 2,96 2,69 2,71 2,90

Condensing capacity kW 52,0 79,4 121,0 140,6 161,6 214,2

Sound pressure level (10m) dB(A) 54 55 56 58 59 60

Condensing temperature °C 45 45 45 47 48 45

Preliminary fuse A 40 63 80 100 100 125

Refrigerant circuits pce. 2 2 2 2 2 2

Number of Compressors pce. 2 2 2 2 2 2

Compressor type 4DESP-7P 4TESP-12P 4JEP-22P 4HEP-25P 4GEP-30P 6HEP-35P

Refrigerant charge kg 2x2,9 2x3,3 2x5,3 2x5,9 2x6,4 2x9,9

Width mm 1200 1200 1200 1200 1200 2500

Height mm 2100 2100 2100 2100 2100 2100

Length mm 4500 4500 4500 4500 4500 4500

Net Weight kg 1800 2000 2200 2350 2550 3500

FP-AC290-XXX/06W/35A 200S2 230S2 260S3 300S3 350S3

Cooling capacity kW 194,8 227,2 253,2 292,2 340,8

EER 2,97 2,79 2,99 2,97 2,89

Condensing capacity kW 247,2 292,4 321,3 370,8 438,6

Sound pressure level (10m) dB(A) 62 63 63 64 64

Condensing temperature °C 45 47 45 45 47

Preliminary fuse A 160 200 200 250 315

Refrigerant circuits pce. 2 2 3 3 3

Number of Compressors pce. 2 2 3 3 3

Compressor type 6GEP-40P 6FEP-50P 6HEP-35P 6GEP-40P 6FEP-50P

Refrigerant charge kg 2x10,5 2x11,5 3x10,5 3x11,0 3x12,0

Width mm 2500 2500 2500 2500 2500

Height mm 2100 2100 2100 2100 2100

Length mm 4500 6500 6500 6500 6500

Net Weight kg 3800 4000 5250 5700 6000

General data: Capacity Control: 25/50/75/100% or 33/50/83/100% Medium evaporator: water Waterinlet-Temperature: +12°C Wateroutlet-Temperature: +6°C Environment temperature: +35°C Fan: EC Power supply: 400V/3Ph/50Hz Housing color: RAL7032 / RAL6018 Frame color: RAL9005 Hydraulic connections: flange

Memo:

Page 4: Aircooled Chiller FP-AC290 - Frigopol Kälteanlagen...The air-cooled chiller FP-AC290 is manufactured with two refrigerant circuits and with two compressors till a capacity of 230kW

General data: Capacity Control: 25/50/75/100% or 33/50/83/100% Medium evaporator: water Waterinlet-Temperature: +12°C Wateroutlet-Temperature: +6°C Environment temperature: +35°C Fan: EC Power supply: 400V/3Ph/50Hz Housing color: RAL7032 / RAL6018 Frame color: RAL9005 Hydraulic connections: flange

FP-AC290-XXX/-08M/35A 30S2 40S2 60S2 70S2 80S2 100S2

Cooling capacity kW 23,1 35,6 54,0 64,2 74,8 96,4

EER 1,75 1,71 1,91 1,81 1,88 1,87

Condensing capacity kW 32,7 49,8 75,6 90,0 104,6 135,0

Sound pressure level (10m) dB(A) 54 55 56 58 59 60

Preliminary fuse A 40 63 80 100 100 125

Refrigerant circuits Stk. 2 2 2 2 2 2

Number of compressors Stk. 2 2 2 2 2 2

Compressor type 4DESP-7P 4TESP-12P 4JEP-22P 4HEP-25P 4GEP-30P 6HEP-35P

Refrigerant charge kg 2x2,9 2x3,3 2x5,3 2x5,9 2x6,4 2x9,9

Dimension and weight see 50S2 70S2 100S2 110S2 130S2 170S2

FP-AC290-XXX/-08M/35A 120S2 140S2 150S3 170S3 210S3

Cooling capacity kW 111,6 133,6 144,6 167,4 200,4

EER 1,92 1,89 1,94 1,92 1,97

Condensing capacity kW 156,6 188,0 202,5 234,9 282,0

Sound pressure level (10m) dB(A) 62 63 63 64 64 Preliminary fuse A 160 200 200 250 315

Refrigerant circuits Stk. 2 2 3 3 3

Number of compressors Stk. 2 2 3 3 3

Compressor type 6GEP-40P 6FEP-50P 6HEP-35P 6GEP-40P 6FEP-50P

Refrigerant charge kg 2x10,5 2x11,5 3x10,5 3x11,0 3x12,0

Dimension and weight see 200S2 230S2 260S3 300S3 350S3

www.frigopol.com

Feel free to ask.

Memo: