AIR CONDITIONERS AIR VOLUME CONTROL TECHNICAL MANUAL 2011 Models PEAD-RP60JAQ(L) PEAD-RP71JAQ(L) PEAD-RP100JAQ(L) PEAD-RP125JAQ(L) PEAD-RP140JAQ(L) PEFY-P63VMA(L)-E PEFY-P71VMA(L)-E PEFY-P80VMA(L)-E PEFY-P100VMA(L)-E PEFY-P125VMA(L)-E PEFY-P140VMA(L)-E CONTENTS 1. Air volume control by analog input ...................... 2 2. Air volume control by contact input ..................... 5 3. Fan characteristic curves .................................... 7 4. Restrictions ....................................................... 17 5. Wiring ............................................................... 18 6. Function settings............................................... 20

AIR VOLUME CONTROL TECHNICAL MANUALplanetaklimata.com.ua/instr/Mitsubishi_Electric/... · 2019. 1. 25. · Air volume control PEFY; SW3-6 ON Ο Ο *1 OFF MAC-397IF (Hi-Mid-Low) Note

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: AIR VOLUME CONTROL TECHNICAL MANUALplanetaklimata.com.ua/instr/Mitsubishi_Electric/... · 2019. 1. 25. · Air volume control PEFY; SW3-6 ON Ο Ο *1 OFF MAC-397IF (Hi-Mid-Low) Note

AIR CONDITIONERS

AIR VOLUME CONTROL TECHNICAL MANUAL

2011

Models PEAD-RP60JAQ(L)PEAD-RP71JAQ(L)PEAD-RP100JAQ(L)PEAD-RP125JAQ(L)PEAD-RP140JAQ(L)

PEFY-P63VMA(L)-EPEFY-P71VMA(L)-EPEFY-P80VMA(L)-EPEFY-P100VMA(L)-EPEFY-P125VMA(L)-EPEFY-P140VMA(L)-E

CONTENTS1. Air volume control by analog input ...................... 2

2. Air volume control by contact input ..................... 5

3. Fan characteristic curves .................................... 7

4. Restrictions ....................................................... 17

5. Wiring ............................................................... 18

6. Function settings ............................................... 20

Page 2: AIR VOLUME CONTROL TECHNICAL MANUALplanetaklimata.com.ua/instr/Mitsubishi_Electric/... · 2019. 1. 25. · Air volume control PEFY; SW3-6 ON Ο Ο *1 OFF MAC-397IF (Hi-Mid-Low) Note

1 2

Air volume control technical manualIndoor unit air volume can be controlled with a opening-closing of a damper by either an analog input (CN2A) or a

contact input (CN105) to the air conditioning unit.

With the PEAD series, it is possible to cut energy consumption by controlling not only the air volume but also the

compressor capacity.

■Corresponding modelAir volume can be controlled with the following models. (1) PEAD-RP60,71,100,125,140JAQ(L)(2) PEFY-P63,71,80,100,125,140VMA(L)-ENOTE:Air volume control with analog input 0-10V is not available with the following models. (a) PEAD-RP35,50JAQ(L) (b) PEFY-P20,25,32,40,50VMA(L)-E

■System configuration

PEAD

Damper System Remote controller

Damper System Controller

Indoor unitAir inlet

Bypass damper

DamperOutdoor unit

Field supply

MA Remotecontroller

MAC-397IF-E *

Analog inputContact input

CN2A

CN105

Supply connectors to CN2A and CN105 on site. (Refer to 5)* MAC-397IF-E:MA & Contact terminal interface (optional)

PEFY

Damper System Remote controller

Damper System Controller

Indoor unitAir inlet

Bypass damper

Damper

Outdoor unit

Field supply

MA Remotecontroller

MAC-397IF-E *

Analog inputContact input

M-NET

CN2A

M-NET

CN105

Damper System Remote controller

Damper System Controller

Indoor unitAir inlet

Bypass damper

Damper

Field supply

MA Remotecontroller

MAC-397IF-E *

Analog inputContact input

CN2A

CN105

Centralized controller(AG-150A)(optional)

Supply connectors to CN2A and CN105 on site. * MAC-397IF-E:MA & Contact terminal interface (optional)

Page 3: AIR VOLUME CONTROL TECHNICAL MANUALplanetaklimata.com.ua/instr/Mitsubishi_Electric/... · 2019. 1. 25. · Air volume control PEFY; SW3-6 ON Ο Ο *1 OFF MAC-397IF (Hi-Mid-Low) Note

1 2

1-1. Air volume control Indoor air volume can be controlled in 10 different stages from V1 to V10 with analog input 0-10V from

the damper system controller supplied on site.

0

10

20

30

40

50

60

70

80

90

100

V1 V2 V3 V4 V5 V6 V7 V8 V9 V10Air volume stage (0-10V analog input)

Air

volu

me

rate

(%)

PEAD-RP60,71JAQ(L)PEFY-P63,71,80VMA(L)-E

PEAD-RP100,125,140JAQ(L)PEFY-P100,125,140VMA(L)-E

*Air volume rate shows the value without change in the external static pressure. For values in different external static pressure, refer to 3. Fan characteristic curves for details.

1-2. Outdoor unit capacity control With the PEAD series, compressor capacity is controlled in accordance with air volume level in 10

stages from V1 to V10.

With the PEFY series, compressor capacity will not be controlled because numbers of indoor units are

connected. However, it is possible to reduce energy consumption with a change in the air volume

leading to compressor capacity control due to a change in condensing temperature.

0

10

20

30

40

50

60

70

80

90

100

V1 V2 V3 V4 V5 V6 V7 V8 V9 V10Air volume stage (0-10V analog input)

Out

door

uni

t cap

acity

rate

(%)

* Outdoor unit capacity rate may change depending on the outdoor temperature.

PEAD-RP60,71,100,125,140JAQ(L)

1. Air volume control by analog input

Page 4: AIR VOLUME CONTROL TECHNICAL MANUALplanetaklimata.com.ua/instr/Mitsubishi_Electric/... · 2019. 1. 25. · Air volume control PEFY; SW3-6 ON Ο Ο *1 OFF MAC-397IF (Hi-Mid-Low) Note

3 4

1-3. Analog input of voltage With analog input of voltage, fan rotation and air volume in 10 stages from V1 to V10 can be controlled.

Air volume stages Analog input voltage(V)Air volume

standard setting (Damper System OFF) *1

V1 0.0~1.5

-

V2 1.0~2.5V3 2.0~3.5V4 3.0~4.5V5 4.0~5.5V6 5.0~6.5V7 6.0~7.5 LowV8 7.0~8.5 MiddleV9 8.0~9.5V10 9.0~10.0 High

NOTE:*1 In case of PEAD-RP JAQ(L) Dip SW 1-1 OFF, PEFY-P VMA(L)-E Dip SW 3-6 OFF, refer to 6-1.

■Differentials of air volume stages V1 to V10

V2

V1

0

V6

V5

V4

V3

V10

V9

V8

V7

9.0 10.07.0 8.03.0 4.0 5.0 6.01.0 2.01.5 2.5 3.5 4.5 5.5 6.5 7.5 8.5 9.5

AirVolumestage

Input Voltage [V]

■Example of analog input of voltageWhen analog input changes 1 7.2V→ 2 7.5V→ 3 7.2V→ 4 7.0V→ 5 6.3V→ 6 6.0V→ 7 6.3V→ 8 6.5V,air volume stages are decided as 1 V7→ 2 V8→ 3 V8→ 4 V7→ 5 V7→ 6 V6→ 7 V6→ 8 V7.See drawing below for details.

V6

V8

V7

7.06.0 6.5 7.5

148

5

76

3 2

AirVolumestage

Input Voltage [V]

Page 5: AIR VOLUME CONTROL TECHNICAL MANUALplanetaklimata.com.ua/instr/Mitsubishi_Electric/... · 2019. 1. 25. · Air volume control PEFY; SW3-6 ON Ο Ο *1 OFF MAC-397IF (Hi-Mid-Low) Note

3 4

1-4. Example of air volume control 1 Air volume can be selected in the following order.■Condition:1. R1- R4 indicates the air outlet of each indoor unit. 2. R4 fully open at all times.3. Air volume designed as R1: 5m3 /min, R2: 5m3 /min, R3: 7m3 /min, R4:17m3 /min.4. Rated air volume measured when R1 - R3 is fully open. (External static pressure set as 100Pa)

[Fig.1-4-1] Example of duct system

Damper System Remote controller

Damper System Controller

Indoor unitAir inlet

Bypass damper

Damper

Air outlet

Supply connecters to CN2A and CN105 on site. (Refer to 5).* MAC-397IF-E:MA & Contact terminal interface (optional)

R4

17m3/min 7m3/min 5m3/min 5m3/min

R3 R2 R1

Field supply

MAC-397IF-E *

Analog inputContact input

CN105

CN2A

■Selecting air volume stage V1~V10Depending on the damper opening pattern R1-R3, patterns 1 ~ 8 as in the below chart is available. The air volume stage is selected from the fan characteristic curve. (Refer to [Fig. 1-4-3]) Choose the pattern closest to the required air volume and which the diagram exceeds.Duct pressure drop depends on the site conditions. Shown here are temporarily numbers in case of external static pressure 100Pa.

Air Outlet R1 R2 R3 R4Total Air volume

[m3/min]Selected

StageAir Volume [m3/min] 5 5 7 17 34 -

Air

volu

me

patte

rn

1 Open Open Open Open 34 V102 Close Open Open Open 29 V93 Open Close Open Open 29 V94 Close Close Open Open 24 V75 Open Open Close Open 27 V86 Close Open Close Open 22 V77 Open Close Close Open 22 V78 Close Close Close Open 17 V5

[Fig.1-4-2] Air volume pattern

* 1 ~ 8 in the below diagram [Fig.1-4-3] indicates the air volume pattern 1 ~ 8 shown in this chart [Fig. 1-4-2]

10 15 20 25 30 35 40 45Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

[Fig.1-4-3] Duct damper open/close

PEAD-RP100JAQ(L)(External static pressure 100Pa) 220-240V 50/60Hz

0

20

40

60

80

100

120

140

160

V1

V4V5

V6V7

V8V9V10

V3

V2

8 6 7 2 3 14 5

Limit

Limit

Page 6: AIR VOLUME CONTROL TECHNICAL MANUALplanetaklimata.com.ua/instr/Mitsubishi_Electric/... · 2019. 1. 25. · Air volume control PEFY; SW3-6 ON Ο Ο *1 OFF MAC-397IF (Hi-Mid-Low) Note

5 6

■Example of system flowThe following explains the system flow for duct damper open/close pattern 1 ~ 6 shown in [Fig.1-4-3].

Condition:Voltage decrease from 10.0V to 3.7V when duct damper changes from full-open to R1,R3 close.

On site

............<Section1-3>

.............<Section1-3>

........<Section1,3>

CN21 0-10V Analog input10.0V→3.7V

Damper System Remote Controller R1,R3close

Operation signal ON→OFF

Damper System Remote ControllerR1,R2,R3,R4 full-open operation

Air volume stepV10→V4

Damper System ControllerAnalog output 10.0V→3.7V

Air volume34m3/min→22m3/min

Outdoor unit capacity rate100%→65%

2-1. Function control by MAC-397IF-E (CN105) Following functions can be controlled from damper system controller by using MAC-397IF-E.1. ON/OFF2. Cooling/ Heating/ Fan mode 3. Air volume rate change (Hi-Mid-Lo)

PRECAUTION:Indoor unit DIP-SW setting for MAC-397IF-E connection

DIPSW setting OperationPEAD; SW1-1

ON/OFF Mode changeCooling/Heating/Fan Air volume control

PEFY; SW3-6ON

Ο Ο*1

OFF MAC-397IF (Hi-Mid-Low)

Note *1 Multistage air volume control is available from CN2A as analog input (0~10V). Without input, the air volume will be automatically set as maximum air volume. *2 In order to change function from MAC-397IF, contact input from damper system controller is required. Only one of the functions is available one at a time

because setting is made by switching DIP-SW of MAC-397IF-E. Refer to the MAC-397IF-E manual for DIP-SW setting and wiring. *3 When not using MAC-397IF-E, connect remote controller for selecting function.

2. Air volume control by contact input

Page 7: AIR VOLUME CONTROL TECHNICAL MANUALplanetaklimata.com.ua/instr/Mitsubishi_Electric/... · 2019. 1. 25. · Air volume control PEFY; SW3-6 ON Ο Ο *1 OFF MAC-397IF (Hi-Mid-Low) Note

5 6

2-2. Example of air volume control by contact input and analog input

Supply connecters to CN2A and CN105 on site. (Refer to 5).* MAC-397IF-E:MA & Contact terminal interface (optional)

Refer to the MAC-397IF-E manual for DIP-SW setting and wiring.

MAC-397IF-E input

Damper System Remote controller

Damper System Controller

Indoor unit

Bypass damper

Damper

Outdoor unit

Field supply

MA Remotecontroller

CN2A

MAC-397IF-E * CN105

CN105 CN560

Indoor unit MAC-397IF-E

Lead wires

Contact point a(about 10mA)

Damper System Controller

1. Contact input When either of the damper open/close with damper system controller, ON/OFF signal via MAC-397IF-E.2. Analog input Air volume controllable with analog input to CN2A, controlling open/close of duct damper.

* It is possible to directly command CN105 without MAC-397IF-E with serial communication. For further details, contact your nearest distributor.

1 2 3 5 64

■Dip switch (SW500) setting

(1) Contact input

ON

2 43 5 6 7 81

Air inlet

←(2) Analog input

CN591

2-3. Example of air volume control with fixed static pressure This example shows how to keep duct static pressure at a constant level with analog input.

Damper System Remote controller

Damper System Controller

Indoor unitAir inlet

Bypass damper

Damper

air outlet

Supply connecters to CN2A and CN105 on site. (Refer to 5).* MAC-397IF-E:MA & Contact terminal interface (optional)

R4

17m3/min 7m3/min 5m3/min 5m3/min

R3 R2 R1

Field supply

MAC-397IF-E *

Analog inputContact input

CN105

CN2A

Check air volume at each air outlet when R1-R4 is full open and set static pressure as target value. Then, analog input to keep the static pressure at this target value even when either of the damper closes.With MAC-397IF-E as in section 2-2, it is also possible to stop the indoor unit when all duct damper closes.

*Refer to the 1-3 for air volume differentials to prevent hunting.

Page 8: AIR VOLUME CONTROL TECHNICAL MANUALplanetaklimata.com.ua/instr/Mitsubishi_Electric/... · 2019. 1. 25. · Air volume control PEFY; SW3-6 ON Ο Ο *1 OFF MAC-397IF (Hi-Mid-Low) Note

7 8

With an analog input of 0-10V, indoor air volume can be controlled in 10 steps from V1 to V10.

Rated point

V1~4V5

V6

V7V8

V9

V10Limit

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

10 15 20 25 300

20

40

60

PEAD-RP60JAQ(L)(External static pressure 35Pa) 220-240V 50/60Hz

V1,2

V3

V4

V5 V6V7 V8

V9

V10Limit

Limit

Rated point

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

10 15 20 25 3020

40

60

120

100

80

PEAD-RP60JAQ(L)(External static pressure 100Pa) 220-240V 50/60Hz

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

10 15 20 25 300

40

20

60

80

PEAD-RP60JAQ(L)(External static pressure 50Pa) 220-240V 50/60Hz

Rated point

V1,2V3

V4

V5V6V7

V8

V9

V10Limit

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

10 15 20 25 3050

150

100

PEAD-RP60JAQ(L)(External static pressure 150Pa) 220-240V 50/60Hz

Rated point

V1,2

V3

V4

V5 V6V7V8V9V10

Limit

Limit

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

10 15 20 25 300

100

20

40

60

80

PEAD-RP60JAQ(L)(External static pressure 70Pa) 220-240V 50/60Hz

Rated point

V1,2

V3

V4

V5 V6V7V8V9

V10Limit

Limit

3. Fan characteristic curves

Page 9: AIR VOLUME CONTROL TECHNICAL MANUALplanetaklimata.com.ua/instr/Mitsubishi_Electric/... · 2019. 1. 25. · Air volume control PEFY; SW3-6 ON Ο Ο *1 OFF MAC-397IF (Hi-Mid-Low) Note

7 8

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

10 15 20 25 300

20

40

60

PEAD-RP71JAQ(L)(External static pressure 35Pa) 220-240V 50/60Hz

Rated point

V1~4

V5V6

V7

V8

V9

V10

Limit

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

10 15 20 25 3020

40

60

120

100

80

140

PEAD-RP71JAQ(L)(External static pressure 100Pa) 220-240V 50/60Hz

Rated point

Limit

Limit

V1,2

V3

V4

V5V6

V7V8V9

V10

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

10 15 20 25 300

20

40

60

80

PEAD-RP71JAQ(L)(External static pressure 50Pa) 220-240V 50/60Hz

Rated point

Limit

V1,2

V3

V4

V5V6

V7

V8

V9

V10

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

10 15 20 25 3050

100

150

PEAD-RP71JAQ(L)(External static pressure 150Pa) 220-240V 50/60Hz

Rated point

Limit

Limit

V1,2

V3

V4

V5V6V7V8V9V10

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

10 15 20 25 300

40

20

80

60

100

PEAD-RP71JAQ(L)(External static pressure 70Pa) 220-240V 50/60Hz

Rated point

Limit

Limit

V1,2

V3V4

V5V6V7

V8V9

V10

Page 10: AIR VOLUME CONTROL TECHNICAL MANUALplanetaklimata.com.ua/instr/Mitsubishi_Electric/... · 2019. 1. 25. · Air volume control PEFY; SW3-6 ON Ο Ο *1 OFF MAC-397IF (Hi-Mid-Low) Note

9 10

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

10 15 20 25 30 35 40 450

40

20

80

60

PEAD-RP100JAQ(L)(External static pressure 35Pa) 220-240V 50/60Hz

Rated point

Limit

V1,2

V3

V4V5

V6

V7

V8

V9

V10

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

10 15 20 25 30 35 40 450

40

20

80

160

140

120

100

60

PEAD-RP100JAQ(L)(External static pressure 100Pa) 220-240V 50/60Hz

Rated point

Limit

Limit

V1

V2V3V4V5

V6V7V8V9V10

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

0

40

20

80

100

60

PEAD-RP100JAQ(L)(External static pressure 50Pa) 220-240V 50/60Hz

10 15 20 25 30 35 40 45

Rated point

Limit

V1V2V3V4V5V6

V7

V8

V9

V10

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

30

130

110

90

50

70

170

190

150

PEAD-RP100JAQ(L)(External static pressure 150Pa) 220-240V 50/60Hz

10 15 20 25 30 35 40 45

Rated point

Limit

Limit

V1

V2

V3

V4 V5V6V7V8V9V10

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

0

40

20

80

120

100

60

PEAD-RP100JAQ(L)(External static pressure 70Pa) 220-240V 50/60Hz

10 15 20 25 30 35 40 45

Rated point

Limit

V1V2

V3V4V5

V6V7

V8V9

V10

Page 11: AIR VOLUME CONTROL TECHNICAL MANUALplanetaklimata.com.ua/instr/Mitsubishi_Electric/... · 2019. 1. 25. · Air volume control PEFY; SW3-6 ON Ο Ο *1 OFF MAC-397IF (Hi-Mid-Low) Note

9 10

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

0

40

20

80

100

60

PEAD-RP125JAQ(L)(External static pressure 35Pa) 220-240V 50/60Hz

15 20 25 30 35 40 45

Rated point

Limit

LimitV1V2

V3V4

V5

V6

V7

V8

V9

V10

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

20

40

80

100

180

160

140

120

60

PEAD-RP125JAQ(L)(External static pressure 100Pa) 220-240V 50/60Hz

15 20 25 30 35 40 45

Rated point

Limit

Limit

V1

V2

V3V4

V5

V6

V7

V8

V9

V10

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

0

20

40

80

100

120

60

PEAD-RP125JAQ(L)(External static pressure 50Pa) 220-240V 50/60Hz

15 20 25 30 35 40 45

Rated point

Limit

Limit

V1V2V3V4

V5

V6

V7

V8

V9

V10

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

50

100

150

200

PEAD-RP125JAQ(L)(External static pressure 150Pa) 220-240V 50/60Hz

15 20 25 30 35 40 45

Rated point

Limit

Limit

V1

V2

V3

V4V5V6

V7

V8

V9

V10

V1

V2

V3

V4V5V6

V7

V8

V9

V10

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

10

30

110

90

70

50

130

150

PEAD-RP125JAQ(L)(External static pressure 70Pa) 220-240V 50/60Hz

15 20 25 30 35 40 45

Rated point

Limit

Limit

V1V2V3V4V5

V6

V7

V8

V9

V10

Page 12: AIR VOLUME CONTROL TECHNICAL MANUALplanetaklimata.com.ua/instr/Mitsubishi_Electric/... · 2019. 1. 25. · Air volume control PEFY; SW3-6 ON Ο Ο *1 OFF MAC-397IF (Hi-Mid-Low) Note

11 12

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

0

20

100

80

60

40

PEAD-RP140JAQ(L)(External static pressure 35Pa) 220-240V 50/60Hz

15 20 25 30 35 40 45

Rated point

Limit

LimitV1

V2V3

V4V5

V6

V7

V8

V9

V10

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

30

50

170

190

110

130

150

90

70

PEAD-RP140JAQ(L)(External static pressure 100Pa) 220-240V 50/60Hz

15 20 25 30 35 40 45

Rated point

Limit

Limit

Rated point

Limit

Limit

V1

V2

V3

V4V5

V6

V7

V8

V9

V10

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

0

20

80

100

120

60

40

PEAD-RP140JAQ(L) VAV(External static pressure 50Pa) 220-240V 50/60Hz

15 20 25 30 35 40 45

Rated point

Limit

Limit

V1V2V3V4

V5

V6

V7

V8

V9

V10

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

50

100

250

200

150

PEAD-RP140JAQ(L)(External static pressure 150Pa) 220-240V 50/60Hz

15 20 25 30 35 40 45

Rated point

Limit

LimitV1

V2

V3

V4V5

V6V7

V8

V9

V10

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

10

30

150

70

90

110

130

50

PEAD-RP140JAQ(L)(External static pressure 70Pa) 220-240V 50/60Hz

15 20 25 30 35 40 45

Rated point

Limit

Limit

V1V2V3V4

V5

V6

V7

V8

V9

V10

Page 13: AIR VOLUME CONTROL TECHNICAL MANUALplanetaklimata.com.ua/instr/Mitsubishi_Electric/... · 2019. 1. 25. · Air volume control PEFY; SW3-6 ON Ο Ο *1 OFF MAC-397IF (Hi-Mid-Low) Note

11 12

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

0

20

60

40

PEFY-P63VMA(L)-E(External static pressure 35Pa) 220-240V 50/60Hz

15 205 10 25 30

Rated point

Limit

V1~4V5V6V7V8

V9

V10

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

20

120

100

80

60

40

PEFY-P63VMA(L)-E(External static pressure 100Pa) 220-240V 50/60Hz

15 205 10 25 30

Rated pointLimit

Limit

V1, 2

V3

V4

V5 V6V7 V8V9V10

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

0

20

80

60

40

PEFY-P63VMA(L)-E(External static pressure 50Pa) 220-240V 50/60Hz

15 205 10 25 30

Rated point

Limit

V1, 2V3

V4

V5V6V7V8

V9V10

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

50

70

170

110

130

150

90

PEFY-P63VMA(L)-E(External static pressure 150Pa) 220-240V 50/60Hz

15 205 10 25 30

Rated pointLimit

Limit

V1, 2

V3

V4

V5 V6V7 V8V9

V10

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

0

20

60

80

40

PEFY-P63VMA(L)-E(External static pressure 70Pa) 220-240V 50/60Hz

15 205 10 25 30

Rated point

Limit

Limit

V1, 2

V3

V4

V5V6V7V8V9V10

Page 14: AIR VOLUME CONTROL TECHNICAL MANUALplanetaklimata.com.ua/instr/Mitsubishi_Electric/... · 2019. 1. 25. · Air volume control PEFY; SW3-6 ON Ο Ο *1 OFF MAC-397IF (Hi-Mid-Low) Note

13 14

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

0

20

60

40

PEFY-P71,80VMA(L)-E(External static pressure 35Pa) 220-240V 50/60Hz

15 2010 25 30

Rated point

Limit

V1~4V5

V6V7

V8

V9

V10

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

20

40

80

100

120

60

PEFY-P71,80VMA(L)-E(External static pressure 100Pa) 220-240V 50/60Hz

15 2010 25 30

Limit

Limit

Rated point

V1, 2

V3

V4

V5 V6V7 V8

V9

V10

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

0

20

80

60

40

PEFY-P71,80VMA(L)-E(External static pressure 50Pa) 220-240V 50/60Hz

15 2010 25 30

Rated point

Limit

V1, 2V3

V4

V5V6

V7

V8

V9V10

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

50

150

100

PEFY-P71,80VMA(L)-E(External static pressure 150Pa) 220-240V 50/60Hz

15 2010 25 30

Rated point

Limit

Limit

V1, 2

V3

V4

V5 V6V7V8V9V10

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

0

20

40

60

80

100

PEFY-P71,80VMA(L)-E(External static pressure 70Pa) 220-240V 50/60Hz

15 2010 25 30

Limit

Limit

Rated point

V1, 2

V3

V4

V5V6V7V8V9

V10

Page 15: AIR VOLUME CONTROL TECHNICAL MANUALplanetaklimata.com.ua/instr/Mitsubishi_Electric/... · 2019. 1. 25. · Air volume control PEFY; SW3-6 ON Ο Ο *1 OFF MAC-397IF (Hi-Mid-Low) Note

13 14

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

0

20

40

60

80

PEFY-P100VMA(L)-E(External static pressure 35Pa) 220-240V 50/60Hz

15 2010 25 30 35 40 45

Rated point

Limit

V1, 2

V3

V4V5

V6

V7

V8

V9

V10

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

0

20

40

60

80

100

120

140

PEFY-P100VMA(L)-E(External static pressure 100Pa) 220-240V 50/60Hz

15 2010 25 30 35 40 45

Rated point

Limit

Limit

V1

V3V4V5V6V7

V8V9

V10

V2

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

0

20

40

60

80

100

PEFY-P100VMA(L)-E(External static pressure 50Pa) 220-240V 50/60Hz

15 2010 25 30 35 40 45

Rated point

Limit

V1

V3V4V5

V6V7

V8

V9

V10

V2

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

20

40

60

80

100

140

120

160

180

200

PEFY-P100VMA(L)-E(External static pressure 150Pa) 220-240V 50/60Hz

15 2010 25 30 35 40 45

Rated point

Limit

Limit

V1

V3

V4V5V6

V7V8V9

V10

V2

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

0

40

20

60

80

100

120

PEFY-P100VMA(L)-E(External static pressure 70Pa) 220-240V 50/60Hz

15 2010 25 30 35 40 45

Rated point

Limit

V1

V3V4V5V6

V7

V8

V9

V10

V2

Page 16: AIR VOLUME CONTROL TECHNICAL MANUALplanetaklimata.com.ua/instr/Mitsubishi_Electric/... · 2019. 1. 25. · Air volume control PEFY; SW3-6 ON Ο Ο *1 OFF MAC-397IF (Hi-Mid-Low) Note

15 16

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

0

40

20

60

80

100

PEFY-P125VMA(L)-E(External static pressure 35Pa) 220-240V 50/60Hz

2015 25 30 35 40 5045

Rated point

Limit

V1

V2

V3

V4V5

V6

V7

V8

V9

V10

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

10

50

30

70

90

110

130

150

170

PEFY-P125VMA(L)-E(External static pressure 100Pa) 220-240V 50/60Hz

2015 25 30 35 40 5045

Rated point

Limit

Limit

V1

V2V3

V4V5V6V7

V8

V9

V10

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

0

40

20

60

80

100

120

PEFY-P125VMA(L)-E(External static pressure 50Pa) 220-240V 50/60Hz

2015 25 30 35 40 5045

Rated point

Limit

V1V2V3V4

V5V6

V7

V8

V9

V10

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

30

70

50

90

110

130

170

150

190

210

PEFY-P125VMA(L)-E(External static pressure 150Pa) 220-240V 50/60Hz

2015 25 30 35 40 5045

Rated point

Limit

Limit

V1

V2

V3

V4V5V6V7

V8V9

V10

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

0

40

20

60

80

100

120

140

PEFY-P125VMA(L)-E(External static pressure 70Pa) 220-240V 50/60Hz

2015 25 30 35 40 5045

Rated point

Limit

Limit

V1V2V3V4

V5V6

V7

V8

V9

V10

Page 17: AIR VOLUME CONTROL TECHNICAL MANUALplanetaklimata.com.ua/instr/Mitsubishi_Electric/... · 2019. 1. 25. · Air volume control PEFY; SW3-6 ON Ο Ο *1 OFF MAC-397IF (Hi-Mid-Low) Note

15 16

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

0

40

20

60

80

100

PEFY-P140VMA(L)-E(External static pressure 35Pa) 220-240V 50/60Hz

2015 25 30 35 40 5045

Rated point

Limit

V1V2

V3

V4V5

V6

V7

V8

V9

V10

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

20

40

60

80

160

100

120

140

PEFY-P140VMA(L)-E(External static pressure 100Pa) 220-240V 50/60Hz

2015 25 30 35 40 5045

Rated point

Limit

Limit

V1

V2

V3

V4V5V6

V7

V8

V9

V10

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

0

20

40

60

80

120

100

PEFY-P140VMA(L)-E(External static pressure 50Pa) 220-240V 50/60Hz

2015 25 30 35 40 5045

Rated point

Limit

V1V2V3V4

V5V6

V7

V8

V9

V10

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

50

100

150

200

PEFY-P140VMA(L)-E(External static pressure 150Pa) 220-240V 50/60Hz

2015 25 30 35 40 5045

Rated point

Limit

Limit

V1

V2

V3

V4 V5V6V7V8V9

V10

V1

V2

V3

V4 V5V6V7V8V9

V10

Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

0

40

20

60

120

80

100

PEFY-P140VMA(L)-E(External static pressure 70Pa) 220-240V 50/60Hz

2015 25 30 35 40 5045

Rated point

Limit

Limit

V1V2V3V4V5

V6V7

V8

V9

V10

Page 18: AIR VOLUME CONTROL TECHNICAL MANUALplanetaklimata.com.ua/instr/Mitsubishi_Electric/... · 2019. 1. 25. · Air volume control PEFY; SW3-6 ON Ο Ο *1 OFF MAC-397IF (Hi-Mid-Low) Note

17 18

Damper system controller setting will be prioritized. Set function on a damper system controller.Also, settings and error codes set by a remote controller will not be reflected to the damper system controller.

Signal priority: Damper System remote controller > (analog input) > ME or MA remote controller* Analog input: only air volume control will be effected

Function Model Restrictions Cause / status

Operation mode

PEFY *1

If there are cooling/heating simultaneous operation set from damper system controller in a system of Y series outdoor unit + multiple indoor unit, damper system remote controller will display operation mode but indoor fan may stop.

Indoor unit fan will stop when a different mode from outdoor unit operation mode is selected.

PEFY *1 Operation mode cannot be controlled with M-NET system controller.

If an operation mode is prohibited, operation mode will be displayed, but indoor unit will operate in FAN mode.

Analog input PEAD Do not combine level input of indoor unit ON/OFF and IT transmission.

Level input is prioritized and damper system controller input will be invalid.

Error

PEADTransmission error cannot be detected when the IT transmission line is cutoff or the connector is not plugged in.

After the IT transmission line cut is fixed or the connector is plugged in, CN105 will automatically recover. If indoor units cannot be controlled from damper system remote controller, check the IT transmission line or the connector.

PEAD *1 Indoor unit error code will not be displayed on damper system remote controller.

Indoor unit error will be notified by CN105 transmission. To check error code when in service, setting of MA or ME remote controller is recommended.

Prohibition PEADON/OFF control from damper system remote controller is not available when ON/OFF operation is prohibited from system remote controller.

Because operation prohibition will be prioritized, setting at damper system controller will be invalid. Do not combine ON/OFF prohibition and IT transmission.

Model PEADPEFY

Damper system setting is not available for models PEAD-RP35, 50JAQ(L), PEFY-P20, 25, 32, 40, 50VMA(L)-E.

For these models, air volume will not change with damper system setting.

Damper specification PEAD *2

Use bypass damper to prevent rapid change in external static pressure. If bypass damper is not available, set a delay timer circuit which starts the damper in 1 minute after receiving damper system input to indoor unit.

In heating, to protect the unit, unit may stop due to high pressure error. When bypass damper is not used, as shown in the below figure, operation range will be limited depending on inlet temperature.

*1 Check operation. No restrictions in functions when 0-10V analog input is connected on its own.*2 Refer to the below diagram of operation temperature range when bypass damper is not available and when there is no damper delay

operation.

Operation temperature range: To protect unit, there are restrictions when bypass damper is not available and when there is no damper delay operation for 1 minute. The restriction will depend on piping length and air inlet temperature.

3530252015Suction air temperature (°C)

chan

ging

air

volu

me

step

V10→V6

V10→V7

V10→V8

V10→V5

V10→V4

V10→V3

Available

pipe length 75mpipe length 7.5m

Not available

4. Restrictions

Page 19: AIR VOLUME CONTROL TECHNICAL MANUALplanetaklimata.com.ua/instr/Mitsubishi_Electric/... · 2019. 1. 25. · Air volume control PEFY; SW3-6 ON Ο Ο *1 OFF MAC-397IF (Hi-Mid-Low) Note

17 18

Conduct electrical wiring in the following order.Wiring must be done with the power OFF.(1) Take off the cover by removing 3 screws from the controller box.

A : Screw holding cover (1pc)B : Cover

B

A

(2) Bore knockout hole for wiring.

C : Terminal boxD : Knockout holeE : Remove

D

CE

(3) Run wiring CN105 and CN2A through a knockout hole.

F : Use PG Bushing to keep the weight of the cable and force from being applied to the power supply terminal connector. Use a cable tie to secure the cable.

G : Power source wiringH : Use ordinary bushing I : Transmission wiring

M : CN2A(0-10V Analog Input), CN105 wiringN : Use ordinary bushing

M

N

G

F I

H

5. Wiring

Page 20: AIR VOLUME CONTROL TECHNICAL MANUALplanetaklimata.com.ua/instr/Mitsubishi_Electric/... · 2019. 1. 25. · Air volume control PEFY; SW3-6 ON Ο Ο *1 OFF MAC-397IF (Hi-Mid-Low) Note

19 20

(4) Plug in connector CN105 (red) and CN2A (black) to the indoor controller board. Supply connectors to CN2A and CN105 on site.

1 CN105 (RED)2 CN2A (BLACK) 0-10V analog input

Specification: Indoor unit controller board sideConnector housing ..............B05B-PARK-1

Specification: Connector side (supplied on site)Connector housing ..............PAP-05V-RContact ................................SPHD-002T-P0.5Wiring ..................................AWG22 ~ 26

5 4 3 2 1

DC12 VGNDDC5VTransmitting signal (TX)Receiving signal (RX)

1 CN105 (RED)

Specification: Indoor unit controller board sideConnector housing ..............B02B-XAKK-1

Specification: Connector side (supplied on site)Connector housing ..............XAP-02V-1-KContact ................................S-XA-001T-P0.6Wiring ..................................AWG22 ~ 26

2 1

DC0 ~ 10VDC0 ~ 10V

2 CN2A (BLACK) Analog input 0 ~ 10V

■PEAD-RP60,71,100,125,140JAQ(L)

CN22

CN41

CN32

SW1SW2

CN2L

SWE

CN51

CN3C CN90

CN44

CN4F

CN20

CNXB2CNXC2

CNXA2

CN105 CN2A

■PEFY-P63,71,80,100,125,140VMA(L)-E

CN3A

CN2M

SW4

CN32Indoor controller board

SW3

CN41CN51CN52

CN20

CN4FCN44

SWESW2

CN105 CN2A

Page 21: AIR VOLUME CONTROL TECHNICAL MANUALplanetaklimata.com.ua/instr/Mitsubishi_Electric/... · 2019. 1. 25. · Air volume control PEFY; SW3-6 ON Ο Ο *1 OFF MAC-397IF (Hi-Mid-Low) Note

19 20

Set power supply switching, external static pressure setting, and damper system switching. Setting must be done with the power OFF. External static pressure must be at the rated air volume when all the damper is full open.

6-1. Damper System switch setting ■PEAD-RP60,71,100,125,140JAQ(L)

0-10V analog input is valid by switching SW1-1 ON.With Damper System Without Damper System

SW1-1 ON OFF

SW2SW1

SWE

■PEFY-P63,71,80,100,125,140VMA(L)-E

0-10V analog input is valid by switching SW3-6 ON.With Damper System Without Damper System

SW3-6 ON OFF(Initial setting OFF)

SW4SWE

SW2

SW3

6. Function settings

Page 22: AIR VOLUME CONTROL TECHNICAL MANUALplanetaklimata.com.ua/instr/Mitsubishi_Electric/... · 2019. 1. 25. · Air volume control PEFY; SW3-6 ON Ο Ο *1 OFF MAC-397IF (Hi-Mid-Low) Note

21 22

6-2. Changing the power voltage setting ■PEAD-RP60,71,100,125,140JAQ(L)

Change power voltage setting by function selection via the remote controller

Settings Mode no. Setting no. Initial setting240V 04 1

220,230V 2 Ο

■PEFY-P63,71,80,100,125,140VMA(L)-E

Change power voltage setting by dip switch

Settings SW5 Initial setting220, 230V 220V ON

240V 240V OFF Ο

6-3. Selecting the external static pressure ■PEAD-RP60,71,100,125,140JAQ(L)

Change external static pressure setting by function selection via the remote controllerExternal static pressure

Setting no. of mode no.08

Setting no. of mode no.10 Initial setting

35Pa 2 150Pa 3 1 Ο70Pa 1 2

100Pa 2 2150Pa 3 2

■PEFY-P63,71,80,100,125,140VMA(L)-E

Change external static pressure setting by dip switch

Extemal static pressure

35 Pa

50 Pa

70 Pa

100 Pa

150 Pa

Switch operation

SWA

321

SWA

321

SWA

321

SWA

321

SWA

321

SWC

12

SWC

12

SWC

12

SWC

12

SWC

12

PRECAUTION:External static pressure must be at the rated air volume when all the damper is full open.Set a bypass damper to secure minimum air volume with a minimum damper opening.(Refer to 3.Fan characteristic curves)

Page 23: AIR VOLUME CONTROL TECHNICAL MANUALplanetaklimata.com.ua/instr/Mitsubishi_Electric/... · 2019. 1. 25. · Air volume control PEFY; SW3-6 ON Ο Ο *1 OFF MAC-397IF (Hi-Mid-Low) Note

21 22

Page 24: AIR VOLUME CONTROL TECHNICAL MANUALplanetaklimata.com.ua/instr/Mitsubishi_Electric/... · 2019. 1. 25. · Air volume control PEFY; SW3-6 ON Ο Ο *1 OFF MAC-397IF (Hi-Mid-Low) Note

New publication effective Feb. 2011.Specifications subject to change without notice.