Tel: 1-866-466-2592 | Email: [email protected] | Web: www.airsniper.ca EPA Facility Registration Number 100516-CAN-1 | UPCS 628678453081 Air Sniper Induct 300W Standard Installation Manual A Word to Air Sniper Owners Thank you for purchasing an Air Sniper Induct 300W Standard. This manual provides step-by-step instructions on how to install and operate your new equipment. Please be aware that there is a separate manual for the Air Sniper Induct 300W BAS/BACnet model. At Air Sniper, we design and build air sanitization systems with complete customer satisfaction in mind. To assure trouble-free operation of your air sanitization system, please read this manual and follow installation recommendations. An authorized Air Sniper dealer will know the system best, and if service or maintenance is needed the Air Sniper team is there to help. Our team is dedicated to providing you with the best possible service and assuring your satisfaction with our product For any questions or service requirements please contact an Air Sniper representative at the toll-free number: 1-866-466-2592 Never attempt to operate the UV-C lamps outside the ducting. UV-C radiation is extremely harmful to unprotected (uncovered) eyes and skin Always disconnect unit from power source before conducting any service or maintenance Bulb contains small amounts of Mercury. Responsible disposal is important. Bulb can always be returned to Air Sniper. Warnings

Air Sniper Induct 300W Standard-Oct8

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Air Sniper Induct 300W Standard-Oct8

Tel: 1-866-466-2592 | Email: [email protected] | Web: www.airsniper.caEPA Facility Registration Number 100516-CAN-1 | UPCS 628678453081

Air Sniper Induct 300W StandardInstallation Manual

A Word to Air Sniper Owners

Thank you for purchasing an Air Sniper Induct 300W Standard. This manual provides step-by-step instructions on how to install and operate your new equipment. Please be aware that there is a separate manual for the Air Sniper Induct 300W BAS/BACnet model.

At Air Sniper, we design and build air sanitization systems with complete customer satisfaction in mind. To assure trouble-free operation of your air sanitization system, please read this manual and follow installation recommendations.

An authorized Air Sniper dealer will know the system best, and if service or maintenance is needed the Air Sniper team is there to help. Our team is dedicated to providing you with the best possible service and assuring your satisfaction with our product

For any questions or service requirements please contact an Air Sniper representative at the toll-free number: 1-866-466-2592

• Never attempt to operate the UV-C lamps outside the ducting. UV-C radiation is extremely harmful to unprotected (uncovered) eyes and skin• Always disconnect unit from power source before conducting any service or maintenance• Bulb contains small amounts of Mercury. Responsible disposal is important. Bulb can always be returned to Air Sniper.

Warnings

Page 2: Air Sniper Induct 300W Standard-Oct8

Tel: 1-866-466-2592 | Email: [email protected] | Web: www.airsniper.caEPA Facility Registration Number 100516-CAN-1 | UPCS 628678453081

Advantages of UVC Induction Bulbs

Standard Induct 300W Features

Standard Induct 300W Features

● Longest bulb life of all UVC bulbs● Greatest UVC intensity per watt of all UVC bulbs● Greatest operating temperature parameters of all UVC bulbs

● 300 Watt induction Bulb ● Power Status Indicator Light ● Bulb Life Indicator● Standard ON/OFF switch● Airflow Differential Pressure Switch/Sensor

● Power Supply o 110 V 50/60 Hz ● Energy Consumption o 3.2 Amps @ 110V● Operating Temperature Range o -25C/+ 100C● Power Control Systems o On/Off Switch o Airflow Differential Pressure Switch/Sensor● Bulb Life o 43,800 bulb life hours of high intensity UVC● Electrical Safety Certification o ETL certified for USA and Canada● Ozone Certification o UL 867● Weight o 15lbs● Dimensions o 25”(H) x 10" (W) x 5.36"(D)● Housing Material o Aluminium

Page 3: Air Sniper Induct 300W Standard-Oct8

Tel: 1-866-466-2592 | Email: [email protected] | Web: www.airsniper.caEPA Facility Registration Number 100516-CAN-1 | UPCS 628678453081

System Operation InstructionsIndicator Lights

Audible Alarm

● The Power Status light will be lit green when the power supply is connected and the On/Off switch is ON.● The Bulb Life / Operation light will be lit green, yellow or red when air flow is detected and the UVC bulb is operational. ● The Bulb Life / Operation light has three indication colors. o Green means bulb life is within optimum operating hours o Yellow means bulb life is near the end of life cycle o Red means bulb life has exceeded its life cycle and the unit needs to be replaced.

● Reset Button - The Air Sniper 300-Watt has a reset button that allows you to turn off an audible alert which indicates end of lamp life

Check and Maintenance of the Unit● Air Sniper recommends verifying operation status while changing the HVAC standard filter every 2 to 3 months.● There is NO maintenance required for the Air Sniper Induct 300W. It has been designed for maintenance free operation.

Bulb Life

● The bulb in your Air Sniper Standard 300W Induct is part of a complete unit that will need to be replaced at 43,800 operating hours (5 years of 24/7 operation)

Replacement

● Please contact your distributor for bulb replacement of the Induct 300.

Page 4: Air Sniper Induct 300W Standard-Oct8

Tel: 1-866-466-2592 | Email: [email protected] | Web: www.airsniper.caEPA Facility Registration Number 100516-CAN-1 | UPCS 628678453081

Installation Instructions

● Air Sniper 300W unit● Power cable (plugs into unit coming from power source of 110V/220V)● Reflective panels with magnetic tape attached x 4 (22 ¾”L x 7 ¾’ W) ● Qty 12 #8 TEK screws ● The Operation/Installation Manual is uploaded when scanning the supplied QR CODE

Tools and Supplies Required● Drill for TEK screws● Drill bit to initiate cut-out puncture● Sheet metal tin snips or appropriate cutting equipment

Suggested Mounting Parameters● Depending on access to the duct work, the unit can be installed in several configurations ● Easy access for maintenance and unit replacement should be considered● Air Sniper Induct 300W can be installed on either the return or supply ducting. o Installation in line of sight of HVAC coils will promote a cleaner and better operating HVAC system ● Bulb may be positioned perpendicular or parallel to airflow o Positioning long side of bulb parallel to airflow will minimize the static pressure increase ● Bulb Placement for 2 or more units - For 1-2 units the installation options are suggested below to maximize effectiveness based on furnace design, - For 3 or more units we suggest a quick consult with Air Sniper or an engineer to ensure proper installation.

Items Provided with Your New Air Sniper Induct 300-Watt

Page 5: Air Sniper Induct 300W Standard-Oct8

Tel: 1-866-466-2592 | Email: [email protected] | Web: www.airsniper.caEPA Facility Registration Number 100516-CAN-1 | UPCS 628678453081

Page 6: Air Sniper Induct 300W Standard-Oct8

Tel: 1-866-466-2592 | Email: [email protected] | Web: www.airsniper.caEPA Facility Registration Number 100516-CAN-1 | UPCS 628678453081

Step by Step installation

a. Carefully remove your Air Sniper Standard Induct 300W unit from the box and remove all exterior packaging. b. Look for any shipping damage.c. Please report any damage immediately to your representative.

a. Decide the best location for installation. b. All exterior insulation of the HVAC duct must be cut 2” back from the point of installation.c. Using one of the reflective panels as a template, identify cut-out location for mounting the Air Sniper 300W and trace the panel of where the unit will be installed. (Refer to figure 2f)

1. Remove from box

2. Prepare location for installation

2f

Page 7: Air Sniper Induct 300W Standard-Oct8

Tel: 1-866-466-2592 | Email: [email protected] | Web: www.airsniper.caEPA Facility Registration Number 100516-CAN-1 | UPCS 628678453081

a. Drill a hole large enough on one of the corners of the outline staying within the trace line as a starting point to cut out of your duct.b. Use the sheet metal snips or cutting device to carefully follow the trace slowly cutting out where the unit will be installed. (Refer to figure 3b)c. Please note once the cut-out is complete, interior insulation of the HVAC duct must be cut back 24” from the unit.

a. Remove blue protective plastic on the provided magnetic reflective panels. (Refer to figure 4a)b. Carefully place each panel in the duct where they will be opposing and adjacent to the bulb for best reflective opportunities. Once installed, ensure the magnetic grip is secure and will not be compromised by the air flow. (Refer to figure 4b and 4c)

3. Cutting into duct

4. Placing the reflective panels

4a 4b 4c

3b

Page 8: Air Sniper Induct 300W Standard-Oct8

Tel: 1-866-466-2592 | Email: [email protected] | Web: www.airsniper.caEPA Facility Registration Number 100516-CAN-1 | UPCS 628678453081

a. Carefully place the bulb side of the unit into the cut-out of the duct work till the mounting flange meets the duct work.b. Using your drill and the 12 - #8 TEK screws, secure the unit into the duct work thought the holes on the mounting flange. (Refer to figure 5a)c. Where necessary, metal duct tape can be used to seal the flange to the ducting.

a. Verify the unit is securely attached to ductingb. Plug power cable the unit. (Refer to figure 6a)c. Plug male receptacle end into the supplied power outlet.d. Once the unit is connected to the power source, turn the power switch to ON. e. The Power On light will be lit green.f. Once the air handler is providing airflow (heating, air conditioning, or air handler fan) the unit will sense air pressure and turn on the UVC lamp. When the UVC lamp is engaged the Bulb Life / Operation light will be lit. Green (Refer to figure 6d)g. If there are any abnormal sounds, please turn the unit off immediately and contact the dealer or Air Sniper. The unit is silent when operating correctly.

5. Mounting the Air Sniper 300-Watt Induct Unit

6. Turning ON your Air Sniper Induct 300W

6a 6b

5a

Page 9: Air Sniper Induct 300W Standard-Oct8

Tel: 1-866-466-2592 | Email: [email protected] | Web: www.airsniper.caEPA Facility Registration Number 100516-CAN-1 | UPCS 628678453081

WARNING: Do not attempt to operate the UV-C lamps outside the unit. UV-C radiation is extremely harmful to unprotected (uncovered) eyes and skin

Trouble Shooting

Warranty

● Check that supplied power source is on.● Make sure unit is plugged in to supplied power source.● Check that On/Off switch is turned to on.● Once airflow is established, the Lamp Operating indicator light will be lit.

● The bulb has expired. Contact Air Sniper to replace your unit.

If Your Bulb is Not Operating

The Bulb Life / Operation Light is Red

We take pride in the quality of our products. In the case of a defective piece of equipment, AIR Alpine Innovate Research Inc. offers a limited three-year warranty on all our products (excluding bulbs). In the case of a discovered defect, we will replace or repair the unit. Extended warranty is available.

Limited Three Year Warranty AIR Alpine Innovative Research Inc. warrants the Air Sniper™ to be free from defects in the workmanship or materials under normal use and service (the “Warranty”) for a period of three (3) years (the “Warranty Period”) from the date of purchase through an AIR-authorized dealer/distributor. During the Warranty Period, should an Air Sniper™ be determined to be defective, AIR shall repair or replace the defective Air Sniper™ unit(s) (at AIR or dealer’s option) within a reasonable period.

Remedy Procedures If the Air Sniper™ proves defective within the Warranty Period, the purchaser may choose one of the following remedies, after contacting AIR for a Return Authorization Number: 1. Return the defective Air Sniper™ unit to the dealer/distributor from whom it was purchased together with a copy of the bill of sale, or dated proof of purchase thereof and the Return Authorization Number; or 2. Ship the defective Air Sniper™ unit directly to AIR Alpine Innovative Research Customer Warranty Department along with the Return Authorization Number.

Limitations This Warranty is the only representation regarding the Air Sniper™, by Alpine Innovative Research Inc. of merchantability and fitness for use and shall extend to three (3) years from the date of purchase. The warranty excludes replaceable UVC bulbs. If it is determined by either Alpine Innovative Research Inc or an authorized dealer/distributor that the defect is the result of damage caused by the purchaser, the Warranty is null and void.

Customer Warranty Department Bay 11,6565 40th Street SE Calgary, Alberta, Canada T2C 2J9 Toll Free 1 (888) 338-9549 Fax 1 (403) 279-7738