 Design of Air Condioning for control Room of Hill 65 Calculating of Cooling Load Ht = Hs + Hl where Ht = total heat lo ad(Btu/hr) Hs = Sens ible hea t( Bt u/ hr ) Hl = latent he at (Btu/hr) Hs = 1.08 q dt where Hs = Sens ible hea t( Bt u/ hr ) q = ai r v ol ume flo w( cf m) dt = temper ature dif fer enc r('F ) Room to be air conditioned, length = 3.66 m width = 2.44 m Area = 8.92 = 6.00 (from table 1) = 53.54 l/s 1 l/s = 2.119 cfm = 113.45 cfm = 36.00 'C (from table 3) = 16.00 'C (from table 2) dt = 20.00 'C dt = 68.00 'F Therefore Hs = 8,331.79 Btu/hr 1Btu/hr = 0.293 Watt Hs = 2,441.22Watt Table 1-Air Change Rate Air Shifts Airflow Outdoor per hour (l/s per m 2 Airflow (1/h) floor area) (l/s) Sheep 3 per animal Horses 40 per animal Hens 3 per animal Cows 100 per animal Chickens 2 per animal Pigs, sow 60 per animal Piglet 15 per animal Apartments 15 - 20 per person Assembly halls 5~10 14 per person Auditoriums 10 - 15 per person Production 8 Pastry room 6 Service 2~3 Archive 1 Staff 2~3 Baths 5~8 15 Barber Shops 15 - 25 per person Banks Bakeries air change rate q q outside temperature inside temperature Total Cooling Load Sensible heat Type of Building and Room Animals

Air Conditioning Unit for Control Room Hill 65

Embed Size (px)

Citation preview

  • Design of Air Condioning for control Room of Hill 65Calculating of Cooling Load

    Ht = Hs + Hlwhere

    Ht = total heat load(Btu/hr)Hs = Sensible heat(Btu/hr)Hl = latent heat(Btu/hr)

    Hs = 1.08 q dtwhere

    Hs = Sensible heat(Btu/hr)q = air volume flow(cfm)dt = temperature differencr('F)

    Room to be air conditioned,length = 3.66 mwidth = 2.44 mArea = 8.92 m

    = 6.00 (from table 1)= 53.54 l/s

    1 l/s = 2.119 cfm= 113.45 cfm

    = 36.00 'C (from table 3)= 16.00 'C (from table 2)

    dt = 20.00 'Cdt = 68.00 'F

    ThereforeHs = 8,331.79 Btu/hr

    1Btu/hr = 0.293 WattHs = 2,441.22 Watt

    Table 1-Air Change RateAir Shifts Airflow Outdoorper hour (l/s per m2 Airflow

    (1/h) floor area) (l/s)Sheep 3 per animalHorses 40 per animalHens 3 per animalCows 100 per animal

    Chickens 2 per animalPigs, sow 60 per animal

    Piglet 15 per animal

    Apartments 15 - 20 per personAssembly halls 5~10 14 per person

    Auditoriums 10 - 15 per personProduction 8

    Pastry room 6Service 2~3Archive 1

    Staff 2~3Baths 5~8 15

    Barber Shops 15 - 25 per person

    Banks

    Bakeries

    air change rateq

    q

    outside temperatureinside temperature

    Total Cooling Load

    Sensible heat

    Type of Building and Room

    Animals

  • Bars 15 - 25 per person

    Beauty Shops 15 - 25 per personBoiler rooms 4

    Bowling Alleys 15 - 20 per person

    Cafeterias 4 10 - 15 per personCinemas/Theatres 5~10 7 - 15 per person

    Sterile room 15Laboratory 15

    Packing room 4Store 1

    Churches 2 10 - 15 per person

    Clubhouses 15 - 25 per person

    Cocktail Lounges 15 - 25 per person

    Computer Rooms 15 - 20 per person

    Court Houses 10 - 15 per person

    Dance halls 15 - 30 per personDental Clinics,

    Offices 15 - 20 per personDepartment Stores

    (cfm/Sq.Ft) 0.3

    Dining Halls 10 - 15 per person

    Drug Shop 10 - 15 per personEngine rooms 4Exhibition halls 10~20

    Fire Stations 15 - 20 per personGarages 5~6 > 1

    General 25 per personTherapy 9

    Operating theatre 14Autopsy 9

    Reception 15 - 20 per personRoom 3

    Factory 20 - 30 per personCarpenter work

    shop 2~5Car repair shop 4Car repair shop, exhaust outlet 60 - 80 per car

    Mechanical work shop 3~4

    Welding 12~15Assembly 4~5

    Jails 10 - 15 per person

    Jewelry Shop 10 - 15 per person

    Libraries 10 - 15 per personLunch Rooms, Luncheonettes 10 - 15 per person

    Industries

    Chemist's shops

    Hospitals

    Hotels

  • Municipal Buildings 10 - 15 per person

    Museums 10 - 15 per personSmithies 6~7

    Small 20 - 40Large 10~20< 7 m2 15> 7 m2 20

    Industrial in general 25 - 30

    Gas ovens550/m2 outside

    wall

    Electric ovens300/m2 outside

    wall

    Grill table400/m2 outside

    wallFrying pan 300

    Boiling pan 100 l 100Boiling pan 200 l 200Coffee machine 60

    Refrigerated cabinet 7~10

    Cooling and freezer room 0.3 - 0.5

    Store 2~4Laundries 10~15Lavatories 5~10 10

    Night Clubs 15 - 25 per person

    Malls 10 - 15 per person

    Motels 15 - 20 per person

    Module 3~8 15 - 20 per personLandscape 20 per person

    Conference room 15 - 30 per person

    Lecture room 10 - 15 per person

    Dining hall 15 - 20 per personStaff, changing

    clothes 8~12Dining room 8~10

    Resting room 15 per person

    Police Stations 15 - 20 per person

    Post Offices 15 - 20 per personPrecision

    Manufacturing 15 - 20 per person

    Restaurants 5~10 10 15 - 20 per personRetail Stores (cfm/Sq.Ft) 0.3

    Schools Classroom 4~5 10 - 15 per personShops 20 per person

    Shopping Centers 10 - 15 per personSports halls 3~4

    Supermarkets 10 - 15 per personSwimming pools 5~10

    Kitchens

    Offices

  • Taverns 15 - 25 per person

    Town Halls 15 - 20 per person

    Winter Condition

    oF oCBars 64 18

    Bathrooms 72 22Bedrooms 64 18

    Changing rooms 72 22Churches 64 18

    Cloakrooms 61 16Classrooms 68 20

    Corridors 61 16Dining rooms 68 20

    Dressing rooms 70 21Exhibition halls 64 18

    Factories, sedentary work 64 18

    Factories, light work 61 16Factories, heavy

    work 55 13Gyms 59 15

    Halls, assembly 64 18Halls, entrance 61 16

    Hotel rooms 70 21Laboratories 68 20

    Lecture rooms 68 20Libraries 68 20

    Living rooms 70 21Museums 68 20

    Offices 68 20Operating theatres 75 24

    Prisons 64 18Recreation rooms 64 18

    Restaurants 64 18Shops 64 18Stores 59 15

    Swimming baths 81 27Waiting rooms 64 18

    Wards 64 18Warehouses 61 16

    Summer Condition

    Outside dry bulbtemperature

    oC oC max oC min %35 27 18.5 4432 26 18 4629 25 17.8 5227 24 17.5 5124 23 17.2 5721 22 17 57

    Hl = 0.68 q dwLatent heat

    1 dm3(litre)/s = 10-3 m3/s = 3.6 m3/h = 0.03532 ft3/s = 2.1189 ft3/min (cfm) = 13.200 Imp.gal (UK)/min = 15.852 gal (US)/min = 792 Imp. gal (UK)/h

    Type of Heated rooms

    TemperatureTable 2-Inside Temperature

    Inside air conditions withdew point constant at 14oC

    Table 3-Inside Temperature

  • whereHl = Latent heat(Btu/hr)q = air volume flow(cfm)

    dw = humidity ratio difference(lb.water/lb dry air)= 70.00 (lb.water/lb dry air)= 50.00 (lb.water/lb dry air)

    dw = 20.00 (lb.water/lb dry air)Therefore

    Hl = 1,542.92 Btu/hr1Btu/hr = 0.293 Watt

    Hl = 452.08 WattTherefore

    Ht = Hs + HlHt = 9,874.72 Btu/hrHt = 2,893.29 Watt

    2.89 KW

    Pressure Loss for Heat Load

    outside humidity ratioinside humidity ratio

    Total Cooling Load