Design of Air Condioning for control Room of Hill 65Calculating of Cooling Load
Ht = Hs + Hlwhere
Ht = total heat load(Btu/hr)Hs = Sensible heat(Btu/hr)Hl = latent heat(Btu/hr)
Hs = 1.08 q dtwhere
Hs = Sensible heat(Btu/hr)q = air volume flow(cfm)dt = temperature differencr('F)
Room to be air conditioned,length = 3.66 mwidth = 2.44 mArea = 8.92 m
= 6.00 (from table 1)= 53.54 l/s
1 l/s = 2.119 cfm= 113.45 cfm
= 36.00 'C (from table 3)= 16.00 'C (from table 2)
dt = 20.00 'Cdt = 68.00 'F
ThereforeHs = 8,331.79 Btu/hr
1Btu/hr = 0.293 WattHs = 2,441.22 Watt
Table 1-Air Change RateAir Shifts Airflow Outdoorper hour (l/s per m2 Airflow
(1/h) floor area) (l/s)Sheep 3 per animalHorses 40 per animalHens 3 per animalCows 100 per animal
Chickens 2 per animalPigs, sow 60 per animal
Piglet 15 per animal
Apartments 15 - 20 per personAssembly halls 5~10 14 per person
Auditoriums 10 - 15 per personProduction 8
Pastry room 6Service 2~3Archive 1
Staff 2~3Baths 5~8 15
Barber Shops 15 - 25 per person
Banks
Bakeries
air change rateq
q
outside temperatureinside temperature
Total Cooling Load
Sensible heat
Type of Building and Room
Animals
Bars 15 - 25 per person
Beauty Shops 15 - 25 per personBoiler rooms 4
Bowling Alleys 15 - 20 per person
Cafeterias 4 10 - 15 per personCinemas/Theatres 5~10 7 - 15 per person
Sterile room 15Laboratory 15
Packing room 4Store 1
Churches 2 10 - 15 per person
Clubhouses 15 - 25 per person
Cocktail Lounges 15 - 25 per person
Computer Rooms 15 - 20 per person
Court Houses 10 - 15 per person
Dance halls 15 - 30 per personDental Clinics,
Offices 15 - 20 per personDepartment Stores
(cfm/Sq.Ft) 0.3
Dining Halls 10 - 15 per person
Drug Shop 10 - 15 per personEngine rooms 4Exhibition halls 10~20
Fire Stations 15 - 20 per personGarages 5~6 > 1
General 25 per personTherapy 9
Operating theatre 14Autopsy 9
Reception 15 - 20 per personRoom 3
Factory 20 - 30 per personCarpenter work
shop 2~5Car repair shop 4Car repair shop, exhaust outlet 60 - 80 per car
Mechanical work shop 3~4
Welding 12~15Assembly 4~5
Jails 10 - 15 per person
Jewelry Shop 10 - 15 per person
Libraries 10 - 15 per personLunch Rooms, Luncheonettes 10 - 15 per person
Industries
Chemist's shops
Hospitals
Hotels
Municipal Buildings 10 - 15 per person
Museums 10 - 15 per personSmithies 6~7
Small 20 - 40Large 10~20< 7 m2 15> 7 m2 20
Industrial in general 25 - 30
Gas ovens550/m2 outside
wall
Electric ovens300/m2 outside
wall
Grill table400/m2 outside
wallFrying pan 300
Boiling pan 100 l 100Boiling pan 200 l 200Coffee machine 60
Refrigerated cabinet 7~10
Cooling and freezer room 0.3 - 0.5
Store 2~4Laundries 10~15Lavatories 5~10 10
Night Clubs 15 - 25 per person
Malls 10 - 15 per person
Motels 15 - 20 per person
Module 3~8 15 - 20 per personLandscape 20 per person
Conference room 15 - 30 per person
Lecture room 10 - 15 per person
Dining hall 15 - 20 per personStaff, changing
clothes 8~12Dining room 8~10
Resting room 15 per person
Police Stations 15 - 20 per person
Post Offices 15 - 20 per personPrecision
Manufacturing 15 - 20 per person
Restaurants 5~10 10 15 - 20 per personRetail Stores (cfm/Sq.Ft) 0.3
Schools Classroom 4~5 10 - 15 per personShops 20 per person
Shopping Centers 10 - 15 per personSports halls 3~4
Supermarkets 10 - 15 per personSwimming pools 5~10
Kitchens
Offices
Taverns 15 - 25 per person
Town Halls 15 - 20 per person
Winter Condition
oF oCBars 64 18
Bathrooms 72 22Bedrooms 64 18
Changing rooms 72 22Churches 64 18
Cloakrooms 61 16Classrooms 68 20
Corridors 61 16Dining rooms 68 20
Dressing rooms 70 21Exhibition halls 64 18
Factories, sedentary work 64 18
Factories, light work 61 16Factories, heavy
work 55 13Gyms 59 15
Halls, assembly 64 18Halls, entrance 61 16
Hotel rooms 70 21Laboratories 68 20
Lecture rooms 68 20Libraries 68 20
Living rooms 70 21Museums 68 20
Offices 68 20Operating theatres 75 24
Prisons 64 18Recreation rooms 64 18
Restaurants 64 18Shops 64 18Stores 59 15
Swimming baths 81 27Waiting rooms 64 18
Wards 64 18Warehouses 61 16
Summer Condition
Outside dry bulbtemperature
oC oC max oC min %35 27 18.5 4432 26 18 4629 25 17.8 5227 24 17.5 5124 23 17.2 5721 22 17 57
Hl = 0.68 q dwLatent heat
1 dm3(litre)/s = 10-3 m3/s = 3.6 m3/h = 0.03532 ft3/s = 2.1189 ft3/min (cfm) = 13.200 Imp.gal (UK)/min = 15.852 gal (US)/min = 792 Imp. gal (UK)/h
Type of Heated rooms
TemperatureTable 2-Inside Temperature
Inside air conditions withdew point constant at 14oC
Table 3-Inside Temperature
whereHl = Latent heat(Btu/hr)q = air volume flow(cfm)
dw = humidity ratio difference(lb.water/lb dry air)= 70.00 (lb.water/lb dry air)= 50.00 (lb.water/lb dry air)
dw = 20.00 (lb.water/lb dry air)Therefore
Hl = 1,542.92 Btu/hr1Btu/hr = 0.293 Watt
Hl = 452.08 WattTherefore
Ht = Hs + HlHt = 9,874.72 Btu/hrHt = 2,893.29 Watt
2.89 KW
Pressure Loss for Heat Load
outside humidity ratioinside humidity ratio
Total Cooling Load