Air Conditioning Design

Embed Size (px)

Citation preview

  • 8/2/2019 Air Conditioning Design

    1/14

    PSYCHROMETRY AND CALCULATIONS FOR AIR CONDITIONING

    DESIGN

    INTRODUCTION

    Comfort air conditioning is the process of keeping a giving space within specified conditions

    of temperature, relative humidity, etc. Maintaining these specified conditions become

    necessary as a result of the unpleasantly high temperatures from solar heat gains and heat

    gains from lighting and other equipment in the confined space. The process is quite a complex

    one requiring an understanding of the properties of air in its different conditions as it passes

    through the process. Air primarily is a mixture of two major component gases (oxygen and

    nitrogen), traces of a number of other gases and water vapour. The water vapour in the air is

    condensable (under right conditions of temperature and pressure) and where all vapour in

    the air is condensed out, the air is referred to as Dry air. The typical percentage proportionof the various components of dry air is given below:

    Gas Proportion (%)

    Nitrogen 78.048

    Oxygen 20.9476

    Carbon dioxide 0.0314

    Hydrogen 0.00005

    Argon 0.9347

    It should be noted that the composition varies slightly at different geographic locations and

    from time to time.

    The natural means of introducing water vapour into air is through evapo-transpiration (from

    plants) and evaporation (from humans in form of sweat or from water bodies). As the

    conditions of temperature, pressure vary, water molecules drop out or are added to the

    surrounding air. The rate at which these occur is dependent on temperature, pressure and

    wind velocity. Also the water vapour holding capacity of the air is temperature and pressure

    dependent. It is therefore vital for any one studying air conditioning to understand that the

    air under study is a mixture of two different gaseous substances. One of these is the dry air

    with composition as outlined above and the other, water vapour. The amount of water

  • 8/2/2019 Air Conditioning Design

    2/14

    vapour contained in moist air within the temperature range of -18 0C to 37 0C varies from 0.05

    to 3% by mass. This variation has a critical influence on the characteristics of moist air.

    BASIC AIR-CONDITIONING TERMINOLOGIES

    Dry bulb temperature, DB ( 0C or 0F): this is the ambient air temperature as measured by a

    standard temperature measuring device.

    Wet bulb temperature, WB ( 0C or 0F): this is the temperature recorded by a thermometer that

    has its bulb wrapped in moist cloth and rotated rapidly in the air to cause evaporation of its

    moisture. A fast evaporation from the cloth indicates low moisture content of the

    surrounding air while a slow evaporation indicates that the surrounding air is already

    moisture-laden. In dry air, moisture rapidly evaporates from the cloth drawing heat from thethermometer and producing a lower temperature reading usually called the wet-bulb

    depression (the difference between the DB and WB temperatures)

    Relative humidity, RH (%): As mentioned earlier, the moisture (water vapour) holding

    capacity of air varies with temperature. This therefore means that for any given temperature,

    there is an amount of moisture that will bring the air to saturation (i.e. to 100% of its water

    vapour holding capacity). This water vapour contained in the air exerts its own pressure

    (termed vapour pressure ). Relative humidity is the ratio of the vapour pressure of the moist

    air (the air being considered) to the vapour pressure of the same air if it were to be at 100%saturation at the same temperature.

    Dew point temperature, T dew (0C or 0F): this is the temperature of saturated air which has the

    same vapour pressure as the air under consideration. Note that saturated air has the same

    WB and DB temperatures. Because the air has reached saturation, condensation begins at

    this temperature and will continue if lowered further.

    Sensible heat Q S : addition or extraction of heat from a substance results in changes in the

    temperature of the substance. The sensible heat is a measure of the thermal energy

    associated with a change in the temperature of a substance. It is termed sensible because,

    this form of heat can be felt by the sense of touch.

    Latent heat Q L: this is a measure of the thermal energy associated with a change of state or

    phase of a substance. Take as an example the heating of a kettle of water. As heat of added,

    the temperature of the water is felt to rise (sensible heat). At a point, say about 100 0C, the

  • 8/2/2019 Air Conditioning Design

    3/14

    temperature stays the same even as more heat is added. The additional heat is used up in

    changing the state of the water from the liquid state to the vapour state. This added heat

    used up is the latent heat.

    Enthalpy: this is the measure of the total heat (sensible and latent heat) in a substance and isa measure of its internal energy and capacity to do work

    PSYCHROMETRY

    Water vapour, air, temperature and pressure interact with each other with consequences

    which can be exploited for heating processes or cooling processes. For example, as air

    temperature rises, its capacity to hold water vapour rises also and the warmer air becomes

    less dense. Psychrometry is the study of the behavior of air and water vapour and a soundknowledge of Psychrometrics is necessary to carry out air-conditioning calculations. The

    terminologies discussed above are particularly relevant in Psychrometry. The psychrometric

    chart is a graphical representation of the thermodynamic properties of moist air and various

    air-conditioning processes and cycles. The figure below shows the variables shown in a

    typical psychrometric chart for any given point.

    The chart helps the designer to calculate and analyze the work and energy transfer during

    various air-conditioning processes and cycles. Typical arrangement of the coordinates on the

    chart is shown below: It should be noted that psychrometric charts in use today have two

    kinds of basic coordinates. Those published by the American Society of Heating Refrigeration

    and Air-conditioning Engineers (ASHRAE) and the Charted Institution of Building Services

    http://1.bp.blogspot.com/-O080iTDK_cU/TZQyez50YZI/AAAAAAAAAD4/bUfdgYiZlVY/s1600/Untitled-1.jpg
  • 8/2/2019 Air Conditioning Design

    4/14

    Engineering (CIBSE) use the h-w coordinates, where enthalpy h and humidity ration w are the

    coordinates. Charts published by Carrier Corporation and the Trane Company use the T-

    w coordinates. An abridged ASHRAE psychrometric chart is shown below.

    To understand the use of the chart above, lets assume an air -conditioned room at sea level

    has an indoor design temperature of 75 0F and a relative humidity of 50% and we want to

    determine the humidity ratio, enthalpy h, dew point T dew of the indoor air. To do this, we

    shall follow these steps

    1. Establish the room condition of T = 75 0F and a relative humidity of 50% on the chart (point

    r). This is the point where the temperature line at 75 0F meets the 50% -line.

    2. Draw a horizontal line toward the humidity ratio scale w-line , w lb/lb. This line cuts the

    humidity ratio scale at w r = 0.0093 lb/lb.

    3. To get the enthalpy, draw a line through point r parallel to the enthalpy h-line . This gives the

    enthalpy of the room air as h r = 28.1 Btu/lb.

    http://2.bp.blogspot.com/-adLFdCn2IQY/TZQzK1CQXiI/AAAAAAAAAD8/zhxvjG7uX_w/s1600/Untitled-2.jpg
  • 8/2/2019 Air Conditioning Design

    5/14

    4. Draw a horizontal line left ward from point r to meet the saturation curve. This cuts the curve

    at 55 0F. This is the dew point temperature, T dew .

    By using the chart, we can also determine the specific volume and the wet bulb temperature

    of the room air by simply drawing lines parallel to these coordinates from the room statepoint, r. To determine these two values draw a line from the room point r, parallel to the

    specific volume line ( v-line) to get the specific volume and another line parallel to the wet

    bulb temperature line ( T *-line) . These give the room air specific volume and wet bulb

    temperatures as v r = 13.67 ft 3/lb and T * = 62.5 0F respectively.

    With our room air considered as state 1, now let us assume that a quantity of air of different

    temperature and relative humidity (in state 2) is brought into the room. What happens? Both

    streams of air will mix to form a third state point (state 3). From the principles of

    conservation of mass and conservation of energy (both well dealt with in manythermodynamics textbooks), the three state points lie on a straight line in a mass-energy

    coordinate system as in psychrometric charts published by the CIBSE and ASHRAE. It shows

    clearly that when two air streams mix adiabatically, the mixture state (state 3) lies on the

    straight line which joins state point 1 and state point 2. Also the position of state point 3 is

    such that the line is divided inversely as the ratio of the masses of dry air in the constituent

    airstreams. This is shown below.

    Since air conditioning is the treatment or conditioning of air to alter its temperature and

    moisture content to suit specific requirements, the psychrometric chart is vital in tracing,

    analyzing and predicting the changes occurring in the air as it is subjected to cooling, heating,

    humidification, dehumidification etc. Using the chart we can determine the amount of heat

    to be removed from (or added to) a space or the amount of moisture to be removed from (or

    added) to change the condition of the air in the room.

    http://3.bp.blogspot.com/-9b5mhbQTFK4/TZQ0XDFwSFI/AAAAAAAAAEA/huUog0Pijn0/s1600/Untitled-3.jpg
  • 8/2/2019 Air Conditioning Design

    6/14

    AIR-CONDITIONING LOADS

    The main purpose of the air conditioning system is to provide suitable thermal conditions of

    comfort to the occupants or to provide suitable conditions for process or manufacturingapplications. It is therefore vital to carry out cooling (or heating) load calculations to ensure

    that the cooling (or heating) equipment designed or selected serves the intended purpose of

    maintaining the required conditions in the conditioned space. For human comfort, it is

    required to keep the dry bulb temperature, the relative humidity and air velocity within

    control limits.

    Principal sources of heat transfer to a conditioned space are:

    Direct or indirect transmission of solar radiation from the sun. This accounts for a major partof the building heat gain. By proper design and orientation of the building, selection of

    suitable materials and landscaping, the overall energy cost (initial and operational) can be

    reduced.

    Conduction through building elements (roofs, walls, windows etc.)

    Infiltration of air into conditioned space through cracks

    Heat emission by building occupants

    Ventilation. This normally quoted in terms of volume is the quantity of outside air required

    to dilute contamination from all sources to an acceptable level. This is different from the

    conditioned air being supplied to the room. The later is usually quoted in terms of mass of air

    required to absorb any surplus heat or moisture within the conditioned space or conversely,

    to supply heat or moisture to keep the space within specified conditions.

    Electrical load due to lighting

    Load due to office equipment and or process machinery.

    Design challenges

    I choose to discuss the design challenges now before I go any further so as to give the reader

    an understanding of the shortcomings being encountered in the design of air conditioningsystems for a location as mine, Nigeria. Some of these challenges are:

    First, in the design of the space to be air-conditioned most architects do not take into

    consideration solar geometry for the location being considered as an energy consideration for

    the buildings orientation. This accounts for hi gh energy requirements of the air conditioning

    equipment.

  • 8/2/2019 Air Conditioning Design

    7/14

    Second, we do not have proper documentation and standards for the properties of the

    materials used in our building construction industry. This is vital as the mechanism of heat

    transfer is a function of the thermal transmittance coefficient ( U) and the temperature

    difference across the material under consideration.

    Third, for any given location the variations in temperature, humidity and wind integrate to

    provide the climate experience. A study of these interrelationships, their hourly and daily

    variations, the seasonal changes in climatic conditions give rise to design guides for each

    geographical location. These design guides as published in developed countries such as USA,

    Canada, UK etc. provide valuable data for calculating air conditioning loads. They provide

    information such as design outdoor and indoor conditions for various locations and building

    use. They also provide peak solar gain times, peak solar cooling load in watt per building area

    exposed to sunlight etc.

    With these challenges, variations will surely exist in our air conditioning load calculation and

    therefore a lot of experience is needed in applying data from imported standards and guides.

    CALCULATIONS FOR AIR CONDITIONING DESIGN

    Having outlined the various sources of heat gain above, it should be borne in mind that when

    designing air conditioning systems, the principal concern is directed towards heat gains,

    especially during the summer months. The reason for this approach is because heat gainspresent more searching demands than heat losses. The heat gain in any air conditioning

    process can be considered in two main parts sensible heat gains and latent heat gains.

    Sensible heat gains: as discussed earlier, this refers to that part of the heat which changes the

    temperature of the conditioned space. The quantity of air required to combat this heat gain is

    directly proportional to the difference in temperature between the supply air and the air in

    the conditioned space. This temperature difference is usually limited to a maximum of 20 0 in

    order to avoid draft within the space. The sensible heat gain is calculated using:

    H = M *c *T

    Where H = sensible heat gain (kW)

    M = mass of supply air (kg/s)

    C = specific heat capacity of air (kJ/kg K)

  • 8/2/2019 Air Conditioning Design

    8/14

    T = design temperature rise (K)

    Latent heat gain: these do not cause any increase in temperature but affect the moisture

    content of the air in the conditioned space. If the air in the room is not saturated, then it hasthe capacity to absorb water vapour from the room thereby causing the moisture content to

    rise. As we know, it is necessary to provide heat for any form of evapora

    tion to take place. It is therefore customary to

    consider the addition of moisture to the air in the room in terms of kW of latent heat ratherthan kg/s of water evaporated.

    From the above, the conditioned air supplied to the room has dual function: it is cool enough

    initially to suffer a temperature rise up to the room dry-bulb temperature in order to offset

    the sensible heat gains, and its initial moisture content is low enough to permit a rise to the

    value of the room moisture content as latent heat gains are offset. This is shown below

    where S is the supply state point and R is the return state point.

    Heat Gain Equations

    Having determined design outdoor and indoor conditions from necessary design guides, the

    formulae given below are employed for single space heat load considerations.

    S/N Quantity Formula Contributes to

    http://1.bp.blogspot.com/-W8-fOrE_2hc/TZQ1w2lhWGI/AAAAAAAAAEE/bVfzQOVCnz4/s1600/Untitled-4.jpg
  • 8/2/2019 Air Conditioning Design

    9/14

    1. Heat gain for roof Q r = Ur * Ar * CLTDr Sensible Heat

    2. Heat gain for walls Q w = Uw * Aw * CLTDw Sensible Heat

    3. Heat gain for glass(unshaded)

    Q g = Ug * Ag * CLTDg Sensible Heat

    4. Heat gain for glass(Shaded)

    Q gs = Ags * SC * SHGF* CLF Sensible Heat

    5. Heat gain forpartitions (walls,

    ceilings, floors)

    Q p = Up * Ap * TDp Sensible Heat

    6. Heat gain due tointernal lights

    Q SL = (3.41 * W *CLF*zone% *P)/100 Sensible Heat

    7. Sensible Heat gain

    from occupants

    Q sp = NP *SHP * CLFP * P Sensible Heat

    8. Latent Heat gain fromoccupants

    Q LP = NP * LHP * P Latent Heat

    9. Sensible Heat gainfrom equipment

    Q SEQ = 3.41 * W EQ * CLFEQ * P Sensible Heat

    10. Latent Heat gain fromequipment

    Q LEQ = Lat.Equip Latent Heat

    11. Sensible heat due to

    outside air (ventilationor infiltration)

    Q SOA = 1.1 * CFM * TD OA * AF Sensible Heat

    12. Latent Heat gain dueto outside air

    (ventilation or

    infiltration)

    Q LOA = 0.68 * CFM * g * AF Latent Heat

    Q = Heat gain, Btuh

    U = Design coefficient of thermal transmission, Btuh/ft 2-F

    A = Net area, ft 2

    CLTD = Cooling load temperature difference, F

  • 8/2/2019 Air Conditioning Design

    10/14

    SC = Shading coefficient

    SHGF = Maximum solar heat gain factor for north facing glass, Btuh/ft 2

    CLF = Cooling load factor for north facing glass, dimensionless

    TD = Design temperature difference across the partition, floor, or ceiling, F

    W = Total wattage of lighting fixtures including ballast effects for fluorescent lights, Watts

    Zone % = Percentage of lighting load to zone (100% if no plenum)

    P = Profile i.e. the internal operating loads profile at given hour, fraction

    SHP = Sensible heat gain per person, Btuh/person

    NP = Number of people in space considered

    CLFP = Cooling load factor to account for cooling system running 24 hours/day (equals to 1

    since cooling system does not run 24 hours/day)

    P = Internal operating profile percent at given hour, fraction

    WEQ = Recommended rate of heat gain, Btuh/ft 2 * ft 2 or Watts

    CLFEQ = Cooling load factor to account for hours of operation of equipment

    Lat.Equip = Latent heat gain per piece of equipment, Btuh

    CFM = Infiltration or ventilation rate, CFM

    TDOA = Inside outside temperature difference at peak time, F

    AF = Altitude factor, dimensionless

    g = Inside outside humidity ratio difference at peak time, grains of moisture.

    In considering the cooling load for a whole building, the load from the single spaces obtained

    from the above formulae are summed up and further calculations are done to determine the

    following:

    Supply fan power, Q SF

    Supply duct heat load, Q SD

  • 8/2/2019 Air Conditioning Design

    11/14

    Return air load (recirculation fan power and heat gain through extract ventilated luminaires),

    Q RA

    Reheat load, Q RH

    In that case, the design refrigeration load will be given by:

    Q R =(Q + Q SF + Q SD + Q RA + Q RH) * f P

    Where Q R = design refrigeration load and

    f P = factor to cover chilled water pump power and heat gain to pipes.

    APPLICATION OF PSYCHROMETRICS TO AIR CONDITIONING DESIGN

    Let us now look at a practical application of the psychrometric chart in the design of an air

    conditioning system. As the figure below shows, the design conditions are as follows:

    Room is to be maintained at 24 0C (75.2 0F) and a relative humidity of 50% RH

    Outdoor condition is 34 0C (93.2 0F) and 40% RH

    Total room sensible heat Q SR = 135 kW

    Total room latent heat Q LR= 30 kW

    Ventilation requirement is 1outdoor air to 3 re-circulated air (by mass)

    Outside fresh air first flows over coil 1 where it is cooled to 10 0C DBT and 85% RH.

    The air is now mixed with the re-circulated air and through the fan, passed through coil 2 and

    sensibly cooled to 12 0C DBT to be delivered to the room.

    We want to find the mass flow rates of the supply air at the grill and the outside air required

    for ventilation. Also, we would like to find the dry bulb temperature and enthalpy of the air

    handled by the fan, and the required cooling capacity of the cooling unit.

    http://1.bp.blogspot.com/-Q2eAT399oxs/TZQ4EzSNorI/AAAAAAAAAEI/vWhHFUgwKWE/s1600/Untitled-5.jpg
  • 8/2/2019 Air Conditioning Design

    12/14

    Mass flow rate of supply air.

    From the room conditions, using the chart below, locate the point at which the dry bulb

    temperature of 24 0C meets the 50% RH curve. For clarity, you can copy the chart and print it

    out in A3 sized paper. From the point located follow the horizontal line rightward to hit thehumidity ratio axis. This cuts the axis at w i = 0.0093 kg/kg. This is the humidity ratio of the

    room air.

    Assuming a difference of 12 0 between temperature of air supplied to the room and that to be

    maintained in the room, then the supply air temperature would then be 12 0C.

    The mass flow rate of air supplied is obtained from sensible energy balance,

    mSA = Q SR / (c *T)

    = 135 / (1.021 * 12)

    http://1.bp.blogspot.com/-TLwfCf4IL9A/TZQ5I7CbErI/AAAAAAAAAEM/SJyYt4uKug0/s1600/Untitled-6.jpg
  • 8/2/2019 Air Conditioning Design

    13/14

    = 11 kg/s

    The moisture content of the supply air can be obtained from latent energy balance,

    wS = w i (Q LR /( m SA * h fg))

    where h fg = latent heat of vaporization of water, 2501 J/kg. Therefore,

    wS = 0.0093 (30 / (11 * 2501) = 0.0089 kg/kg

    Back to the chart, taking a horizontal line from the humidity ratio axis at 0.0089 kg/kg to cut

    the 12 0C DBT line, gives the supply air RH to be 100%.

    Ventilation

    As noted earlier, ventilation is required to dilute contamination from all sources to an

    acceptable level. The volume of this air is usually related to the type of activity with the space

    and the number of persons in the space. Since 25% of the supply air is fresh air,

    Mass flow rate of fresh air, m o = 0.25 * 11 = 2.75 kg/s

    Mass flow rate of re-circulated air, m rc = 0.75 * 11 = 8.25 kg/s

    Condition of mixed air (handled by fan)

    Using the sensible energy balance equation, the conditions of the mixed air can be found as

    follows:

    Temperature of mixed air:

    t m = (mo* t o + m rc * t i) / (m o + m rc)

    = (2.75 * 34 + 8.25 * 24) / (2.75 + 8.25)

    = 26.5 0C

    Humidity ratio of mixed air:

    w m = (mo * wo + m rc * w i) / (m o + m rc)

  • 8/2/2019 Air Conditioning Design

    14/14

    = (2.75 * 0.0134 + 8.25 * 0.0093) / (2.75 + 8.25)

    = 0.0103 kg/kg

    Enthalpy of mixed air:

    hm = (mo * ho + m rc * h i) / (m o + m rc)

    = (2.75 * 68 + 8.25 * 48) / (2.75 + 8.25)

    = 53 kJ/kg

    Required cooling capacity of coil

    From the psychrometric chart, the enthalpy of air at the exit of the coil, h c = 34 kJ/kg

    Therefore required coil capacity, Q c = mS * (hm hc)

    = 11 * (53 34)

    = 209 kW

    If you have not yet printed a large copy of the psychrometric chart above do so now. Then on

    the chart, try locating the state points discussed in this example. You should be able to locate

    the following state points on the chart.

    Inside design condition (t i = 24 0C, 50% RH, and w i = 0.0093 kg/kg). What is the enthalpy of

    this state point from the chart?

    Outdoor design condition (t o = 340C, 40% RH). Find w o and h o

    Condition of the mixed outdoor and re-circulated air streams (t m = 26.5 0C, wm= 0.0103 kg/kg)

    Supply air condition (t s = 12 0C, ws = 0.0089 kg/kg). Can you find the enthalpy of this state

    point?

    Plotting these points on the chart will help you visualize the processes involved in air

    conditioning design.

    It is not possible to cover completely all the necessary issues of psychrometrics and air

    conditioning design in any one post. Feel free to contact me should the need arise for clarity

    on any item discussed in this post or if you need assistance on your design.