22
Air Conditioner Instruction Manual DELTA ELECTRONICS, INC. USA 46101 Fremont Blvd, Fremont, CA 94538, U.S.A. TEL : 1-510-668-5100 FAX : 1-510-668-0680 [email protected] Taiwan 252, SHANG YING ROAD, KUEI SAN TEL : 886-(03)-3591968 TAOYUAN HSIEN 333, TAIWAN, R. O. C. FAX : 886-(03)-3591991

Air Conditioner Instruction Manual - · PDF fileAir Conditioner Instruction Manual DELTA ELECTRONICS, INC. ... and follow the instructions contained within. ... flashes to help identify

  • Upload
    doannhi

  • View
    249

  • Download
    5

Embed Size (px)

Citation preview

Page 1: Air Conditioner Instruction Manual - · PDF fileAir Conditioner Instruction Manual DELTA ELECTRONICS, INC. ... and follow the instructions contained within. ... flashes to help identify

Air Conditioner

Instruction Manual

DELTA ELECTRONICS, INC.

USA

46101 Fremont Blvd, Fremont, CA 94538, U.S.A. TEL : 1-510-668-5100

FAX : 1-510-668-0680

[email protected]

Taiwan

252, SHANG YING ROAD, KUEI SAN TEL : 886-(03)-3591968

TAOYUAN HSIEN 333, TAIWAN, R. O. C. FAX : 886-(03)-3591991

Page 2: Air Conditioner Instruction Manual - · PDF fileAir Conditioner Instruction Manual DELTA ELECTRONICS, INC. ... and follow the instructions contained within. ... flashes to help identify

Table of Contents

1. Version ...................................................................................................... 1

2. Description ................................................................................................ 1

2.1 General ............................................................................................ 1

2.2 Specification ..................................................................................... 1

2.3 Environmental Condition .................................................................. 2

2.4 Model Identification .......................................................................... 2

3. Installation ................................................................................................. 4

3.1 Outline Drawing ............................................................................... 4

3.2 Mounting Panel Cutout ..................................................................... 7

4. Electrical Specification ............................................................................. 10

4.1 Function List ................................................................................... 10

4.2 Connection ..................................................................................... 16

5. Mechanical Feature ................................................................................. 16

6. Maintenance ............................................................................................ 17

6.1 Maintenance Cycle ........................................................................ 17

6.2 Replacement .................................................................................. 18

7. MTBF ....................................................................................................... 18

8. Safety Compliance .................................................................................. 18

9. Packing & Shipping ................................................................................. 20

Page 3: Air Conditioner Instruction Manual - · PDF fileAir Conditioner Instruction Manual DELTA ELECTRONICS, INC. ... and follow the instructions contained within. ... flashes to help identify

Page 1

1. Version

Rev. Description Drawn Approved Issue date

00 Issue spec. Mars CW 201602

2. Description

2.1 General

This document outlines installation and characteristics of Delta HECX1P series

air conditioners. Before installing the unit, please read this manual thoroughly,

and follow the instructions contained within. HECX1P is a DC air conditioner with

48 VDC power input, designed for IP55 sealed outdoor utility cabinets to provide

stable and optimum internal conditions for equipment, and prevent hot spots

inside the cabinet.

2.2 Specification

Model Number

Operating Temperature Range

oC(

oF)

Compressor Cooling Capacity

W (Btu/hr)

Dimension HxWxD

mm (inch) Rated

Voltage (V) Weight

Kg (lb)

1 HEC0500PA

- 10 to + 55

( 14 to + 131) DC

Compressor

500 (1700)

545 x 315 x 170

(21.5 x 12.4 x 6.7)

48 VDC

16 (35.3)

2 HEC0700PA 700 (2380)

3 HEC0800PB 800 (2720)

700x500x200

(27.6 x 19.7 x 7.9) 28 (61.7)

4 HEC1000PB 1000 (3400)

5 HEC1200PB 1200 (4080)

6 HEC1500PB 1500 (5100)

7 HEC0800PC 800 (2720)

796 x 383 x 160

(31.3 x 15.1 x 6.3) 25 (55.1) 8 HEC1000PC 1000 (3400)

9 HEC1200PC 1200 (4080)

Page 4: Air Conditioner Instruction Manual - · PDF fileAir Conditioner Instruction Manual DELTA ELECTRONICS, INC. ... and follow the instructions contained within. ... flashes to help identify

Page 2

2.3 Environmental Condition

Description Specification

Operating temperature -10°C ~ +55°C (14°F ~ 131°F)

Storage temperature -40°C ~ +70°C (-40°F ~ 158°F)

Humidity External air circuit: 0 ~ 100% RH

Internal air circuit: 0 ~ 90% RH,

Non-condensing

Ingress protection level IEC60529 IP55 on external side

2.4 Model Identification

Model number logic is as follows:

HEC 0500 P A

1 2 3 4

1. Product Code

HEX Air to Air Heat Exchanger

HET ThermoElectric Cooler

HEC Compressor Air Conditioner

HEH Heater

HEL Siphon (Liquid - Air)

2. Cooling Capacity

0500 W

0800 W

1000 W

1200 W

1500 W

3. Operation Voltage

A AC 110 V for door

B AC 220V for door

C AC 110 V for roof

Page 5: Air Conditioner Instruction Manual - · PDF fileAir Conditioner Instruction Manual DELTA ELECTRONICS, INC. ... and follow the instructions contained within. ... flashes to help identify

Page 3

D AC 220V for roof

E AC 110V for door + heater

F AC 220V for door + heater

G AC 110V for roof + heater

H AC 220V for roof + heater

I, J, K, L, M, N AC other

P DC 48V for door

Q DC 48V for roof

R DC 48V for door + AC 110V heater

S DC 48V for door + AC 220V heater

T DC 48V for roof + AC 110V heater

U DC 48V for roof + AC 220V heater

V DC 24V

W DC 12V

X, Y, Z DC other

4. Edition

A First

B Second

C Third

Page 6: Air Conditioner Instruction Manual - · PDF fileAir Conditioner Instruction Manual DELTA ELECTRONICS, INC. ... and follow the instructions contained within. ... flashes to help identify

Page 4

3. Installation

3.1 Outline Drawing

HEC0500/0700PA

(1) Material : Case SGCC Sheet

(2) Finish : Power paint 75~120um,

(3) Color : RAL 7035

(4) Dimension tolerance:

X.X [X.XX] : ± 1.0mm [0.04”]

X.XX [X.XXX] : ± 0.3mm [0.012”]

mm (inch)

Page 7: Air Conditioner Instruction Manual - · PDF fileAir Conditioner Instruction Manual DELTA ELECTRONICS, INC. ... and follow the instructions contained within. ... flashes to help identify

Page 5

HEC0800/1000/1200/1500PB

(1) Material : Case SGCC Sheet

(2) Finish : Power paint 75~120um,

(3) Color : RAL 7035

(4) Dimension tolerance:

X.X [X.XX] : ± 1.0mm [0.04”]

X.XX [X.XXX] : ± 0.3mm [0.012”]

mm (inch)

?

?

Page 8: Air Conditioner Instruction Manual - · PDF fileAir Conditioner Instruction Manual DELTA ELECTRONICS, INC. ... and follow the instructions contained within. ... flashes to help identify

Page 6

HEC0800/1000/1200PC

(1) Material : Case SGCC Sheet

(2) Finish : Power paint 75~120um,

(3) Color : RAL 7035

(4) Dimension tolerance:

X.X [X.XX] : ± 1.0mm [0.04”]

X.XX [X.XXX] : ± 0.3mm [0.012”]

mm (inch)

Page 9: Air Conditioner Instruction Manual - · PDF fileAir Conditioner Instruction Manual DELTA ELECTRONICS, INC. ... and follow the instructions contained within. ... flashes to help identify

Page 7

3.2 Mounting Panel Cutout

HEC0500/0700PA

Outside

Inside

Gasket

CL

Page 10: Air Conditioner Instruction Manual - · PDF fileAir Conditioner Instruction Manual DELTA ELECTRONICS, INC. ... and follow the instructions contained within. ... flashes to help identify

Page 8

HEC0800/1000/1200/1500PB

Inside

Outside

Gasket

?

Page 11: Air Conditioner Instruction Manual - · PDF fileAir Conditioner Instruction Manual DELTA ELECTRONICS, INC. ... and follow the instructions contained within. ... flashes to help identify

Page 9

HEC0800/1000/1200PC

Outside

Inside Gasket

CL

Page 12: Air Conditioner Instruction Manual - · PDF fileAir Conditioner Instruction Manual DELTA ELECTRONICS, INC. ... and follow the instructions contained within. ... flashes to help identify

Page 10

4. Electrical Specification

4.1 Function List

Part No. Rated

Voltage Cooling Capacity

Cooling Current

(L35/L35)

Display /LED

Indication

Self-test botton

Alarm contact

Thermal protection

HEC0500PA DC 48V 500W 3.5A Y Y Y Y

HEC0700PA DC 48V 700W 6.4A Y Y Y Y

HEC0800PB DC 48V 800W 3.9A Y Y Y Y

HEC1000PB DC 48V 1000W 5.6A Y Y Y Y

HEC1200PB DC 48V 1200W 7.3A Y Y Y Y

HEC1500PB DC 48V 1500W 12.5A Y Y Y Y

HEC0800PC DC 48V 800W 3.8A Y Y Y Y

HEC1000PC DC 48V 1000W 5.5A Y Y Y Y

HEC1200PC DC 48V 1200W 8.2A Y Y Y Y

Panel Operation

A: Display:

Indicates the temperature inside the cabinet or system parametric setup.

B: LED indicator:

Power:

When the system powers on, the LED will be solid green.

A B

C

Page 13: Air Conditioner Instruction Manual - · PDF fileAir Conditioner Instruction Manual DELTA ELECTRONICS, INC. ... and follow the instructions contained within. ... flashes to help identify

Page 11

If LED indicates alarm, the number of flashes helps identify root

cause.

Comp.:

When the compressor is running normally, the LED will be solid

green.

If the system goes into self-test mode, the LED will flash green.

Fan (In):

When the inner fan is running normally, the LED will be solid green.

Fan (Out):

When the outer fan is running normally, the LED will be solid green.

C: Touchpad controls:

↑: UP or increase

↓: DOWN or decrease

SET: Parametric setup

ON/OFF ESC: Power on/off or back

System Alarm Default Setup

Note: Operator can set N.O or N.C when alarm is indicated on the display board.

(d1.6 Dry-contact Setup).

• Specification:

Contact rating: 60 Vdc, 100mA

• Normal :

Page 14: Air Conditioner Instruction Manual - · PDF fileAir Conditioner Instruction Manual DELTA ELECTRONICS, INC. ... and follow the instructions contained within. ... flashes to help identify

Page 12

COM. and N.C(or N.O) PIN dry contact output close

• Any alarms happening :

COM. and N.C(or N.O) dry contact output open

Parametric Setup

Page 15: Air Conditioner Instruction Manual - · PDF fileAir Conditioner Instruction Manual DELTA ELECTRONICS, INC. ... and follow the instructions contained within. ... flashes to help identify

Page 13

System Default Setup

Item System Parameter Default Range

d1.3 Inside over-temp. Setup 60 oC 40 oC - 70 oC

d1.4 Auto Self Test Function Enable Enable/Disable

N/A Auto Self Test Period 1 Month 1 Month - 6 Month

d1.6 Photo Coupler Normal Status Close Close/Open

d1.7 Password 000 000~999

d2.1 Target temperature 30 oC 25 oC - 40 oC

Self-Test

1. Press the SET button to enter parametric setup mode.

2. Enter the correct password into the 7-digit display and press SET button; display

shows d01. (Default password: 000)

3. Press SET button to enter detailed parametric setup.

4. Press UP button to choose d1.4, then press SET button to execute auto self-test.

5. If system goes into self-test mode, Comp. LED will flash green.

6. Auto self-test duration is about five minutes, exlusive of three-minute compressor

test.

7. The test process checks that EEPROM, NTC sensor, inner fan, outer fan and

compressor are running correctly.

8. Watch for any alarm during test process. In case of alarm, note number of

flashes to help identify root cause.

Page 16: Air Conditioner Instruction Manual - · PDF fileAir Conditioner Instruction Manual DELTA ELECTRONICS, INC. ... and follow the instructions contained within. ... flashes to help identify

Page 14

Alarm Logs

Flash Times (Power Led)

LV1 Alarm LV2 Alarm Alarm Code

--

--

Compressor 3-min

Protection --

-- Compressor Power

Protection --

-- Low-Temp Startup

Protection --

2 Temperature Abnormal

Alarm

Eva Temperature Protection 2.1

Comp-out Temperature

Protection 2.2

PWB Temperature

Protection 2.3

IPM Temperature Protection 2.4

Amb Temperature

Protection 2.5

3 Temperature Sensor

Fault

Amb Temperature Sensor 3.1

Eva Temperature Sensor 3.2

Cond Temperature Sensor 3.3

Comp-Out Temperature

Sensor 3.4

PWB Temperature Sensor 3.5

IPM Temperature Sensor 3.6

4 Fan Fault Indoor Fan 4.1

Outdoor Fan 4.2

5 Controller Fault

EEPROM 5.1

Current Sensor 5.2

DC-Bus Voltage 5.3

6 Cooling System Fault

Power Board 6.1

Startup Fail 6.2

IPM Over Current 6.3

Compressor Lack Phase 6.4

Page 17: Air Conditioner Instruction Manual - · PDF fileAir Conditioner Instruction Manual DELTA ELECTRONICS, INC. ... and follow the instructions contained within. ... flashes to help identify

Page 15

Fault Analysis and Processing

Fault State Analysis of the Reasons Solutions

Power on, and the

cabinet temperature

is too high but the

air conditioner is not

working

• Power failure or no

power.

• The target temperature is

higher than inside

temperature.

• System failure.

• Check the power supply and

the electric circuit.

• Re-set the target temperature

according to the system

requirement.

• Please contact Delta or

authorized Delta service

agent.

The air conditioner

is running but the

cabinet temperature

is still high, no

obvious cooling

effect.

• The air conditioner

capacity is not match the

load of the system.

• The ambient

temperature is too high.

• Low efficiency of the

condenser.

• Other system failure

• Check the heating load of the

system.

• Ensure the air conditioner is

operating in correct

temperature range.

• Clean the condenser.

• Please contact Delta or

authorized Delta service

agent.

The air conditioner

stop operating, and

there is no alarm

signal.

• The inside temperature

is lower than the target

temperature.

• Other system failure.

• Re-set the target temperature

according to the system

requirement.

• Please contact Delta or

authorized Delta service

agent.

Page 18: Air Conditioner Instruction Manual - · PDF fileAir Conditioner Instruction Manual DELTA ELECTRONICS, INC. ... and follow the instructions contained within. ... flashes to help identify

Page 16

4.2 Connection

Power and Alarm Contact Connection

HEC0800PB,HEC1000PB,HEC1200PB,HEC1500PB

• Power Supply Connector

Pin Description Cable wire size

1 + 2.5 mm2 (14 AWG)

2 - 2.5 mm2 (14 AWG)

• Alarm Connector

Pin Description Cable wire size

3 Alarm+ COM.( 24 AWG)

4 Alarm- N.C or N.O( 24 AWG)

HEC0800PC,HEC1000PC,HEC1200PC,HEC0500PA,HEC0700PA

• HECX1PC Power Supply & Alarm Connector

Pin Description Cable wire size

1 + 2.5 mm2 (14 AWG)

2 - 2.5 mm2 (14 AWG)

3 N/A N/A

4 Alarm+ COM.( 24 AWG)

5 Alarm- N.C or N.O( 24 AWG)

5. Mechanical Feature

Thermal Path and Airflow Baffle

Internal and external air flow circulation is shown in below diagram. Counterflow

design prevents mixing of internal and external air flows, but waste heat can still

be dissipated from cabinet to the ambient outside air. An internal temperature

sensor has been placed in the return air stream to provide reliable temperature

measurement, and for safe operation.

Pin1 Pin5

+

-

+ -

Page 19: Air Conditioner Instruction Manual - · PDF fileAir Conditioner Instruction Manual DELTA ELECTRONICS, INC. ... and follow the instructions contained within. ... flashes to help identify

Page 17

The heated air inside the cabinet will be cooled by the evaporator. Waste heat

absorbed by the refrigerant will be dissipated through the condenser at the

external side.

HEC0500/0700PA, HEC0800/1000/1200/PC HEC0800/1000/1200/1500PB

6. Maintenance

SHUT DOWN the power before performing regular maintenance or component

replacement.

6.1 Maintenance Cycle

Use a brush and low pressure air to remove any dust or debris in the air inlet and

air outlet openings. Suggested maintenance cycle is indicated in the table below:

Check Item Step Description Maintenance Cycle

Wiring Visually check if the wiring is loose 12 months

Fan

abnormalities

Turn the fan to check for smooth rotation

and for any abnormal noise 12 months

Drainage

pipe

Visually check if the drainage opening is

blocked 6 months

Condenser Check the cleanliness of the condenser, and

clean it with compressed air 6 months

Page 20: Air Conditioner Instruction Manual - · PDF fileAir Conditioner Instruction Manual DELTA ELECTRONICS, INC. ... and follow the instructions contained within. ... flashes to help identify

Page 18

6.2 Replacement

In case of abnormal operation, consult Delta or an authorized Delta service agent

for assistance.

7. MTBF

The L10 Fan expected service life is to be at least 100,000 hours continuous

operation at 40°C with 15 ~ 65% RH @ label rated voltage and cooling.

8. Safety Compliance

General Warning & Safety Information

Please read the safety notes carefully before installing the air conditioner, and be

sure to install it correctly. After completing installation, check that the unit

operates properly during start-up operation.

Meaning of WARNING and CAUTION notices:

Warning:

Failure to follow these instructions properly may result in personal injury or

loss of life.

Caution:

Failure to observe these instructions properly may result in property damage

or personal injury, which may be serious depending on the circumstance.

Page 21: Air Conditioner Instruction Manual - · PDF fileAir Conditioner Instruction Manual DELTA ELECTRONICS, INC. ... and follow the instructions contained within. ... flashes to help identify

Page 19

Warning:

1. Installation work and electrical wiring should be done only by qualified personnel

in accordance with all applicable codes, standards and national wiring

regulations.

2. Use this unit only in the manner intended by the manufacturer. If you have

questions, please contact the manufacturer.

3. Install the air conditioner in accordance with the instructions in this installation

manual. Improper installation may result in water leakage, electric shock or fire.

4. Make sure that all wiring is secured, that specified wires are used, and there

there is no strain on the terminal connections or wires.

5. If refrigerant gas leaks during installation, ventilate the area immediately. Do not

directly touch refrigerant that has leaked from refrigerant pipes or other areas, as

there is a danger of frostbite.

6. Before serving or cleaning unit, switch power off and disconnect power supply.

7. When cutting or drilling into wall or ceiling, do not damage electrical wiring or

hidden utilities.

8. Be sure to use only the specified accessories and parts to complete installation.

9. Protective grounding connection: The enclosure must be grounded at the

protective ground terminal. Use 2.5 mm2 (14 AWG) wire and use spring washer

to avoid loosening.

10. The air conditioner should not be accessible to the general public.

11. The installation must contain a device to disconnect all poles of the air

conditioner from the power supply. The contact distance in all poles must be 3

mm minimum.

12. To reduce the risk of electrical shock: Means for disconnection must be

incorporated in the fixed wiring in accordance with the wiring rules.

13. This appliance is intended for use only by qualified personnel.

Page 22: Air Conditioner Instruction Manual - · PDF fileAir Conditioner Instruction Manual DELTA ELECTRONICS, INC. ... and follow the instructions contained within. ... flashes to help identify

Page 20

Caution :

1. Install the air conditioner on a wall or door strong enough to withstand the weight

of the unit.

2. Do not allow a child to mount onto the outdoor unit. Avoid placing any object on it.

3. Do not block the air inlets or exits.

4. Do not install the air conditioner at any place where there is a danger or

flammable gas leakage.

5. Arrange the drain to ensure complete drainage.

6. To avoid injury, do not touch the air inlet or aluminum fins of the unit.

7. Watch your step at the time of fin cleaning or air conditioner inspection.

8. Do not topple the air conditioner while moving or in storage.

9. The hole in the bottom of the air conditioner should be connected to a sealed

container through a drain pipe.

10. This appliance is not to be used by any persons with reduced physical, sensory

or mental capabilities, or lack of experience and knowledge, unless they have

been given proper supervision or instruction.

11. Children should be prevented from playing with the appliance.

9. Packing & Shipping

During handling or transport, air conditioner must be kept in upward position,

“NOT” inverted, flat, or subject to excessive tilt and collision. The air

conditioner is a precision instrument; it should be handled and transported with

care. Do not stand on the box, or place heavy objects on top of the box. Pay

attention to the below icons on the package.

If air conditioner is toppled, slanted or dropped, follow these steps: a. stand unit

up for 12 hours to ensure refrigerant pressure stability, b. power on the unit and

execute self-test to make sure no alarm condition, c. keep the air conditioner

running for 1 hour to make sure there is no abnormal acoustic noise.