Continuing Education Services This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any material of construction or any method or manner of handling, using, distributing, or dealing in any material or product. Questions related to specific materials, methods, and services will be addressed at the conclusion of this presentation. AIA Disclaimer Notice

AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

This program is registered with the AIA/CES for continuing professionaleducation. As such, it does not include content that may be deemed orconstrued to be an approval or endorsement by the AIA of any material ofconstruction or any method or manner of handling, using, distributing, ordealing in any material or product. Questions related to specific materials,methods, and services will be addressed at the conclusion of thispresentation.

AIA Disclaimer Notice

Page 2: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

This is Not proper Crack Control

Page 3: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices 1. Excessive deflection

2. Structural Overload

Causes of Concrete Masonry Cracks

TEK 10-1A

Page 4: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

3. Differential settlement

Causes of Concrete Masonry Cracks

TEK 10-1A

Page 5: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

4. Shrinkage

TEK10

• Moisture change •Temperature • Carbonation

Time (cycles)

Lengthchange

General trend = shrinkage

Causes of Concrete Masonry Cracks

Page 6: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

Shrinkage Cracking

Restraint at bottom only

Page 7: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

Restraint at top and bottom

Shrinkage Cracking

Page 8: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

Accommodating Movement

• Control Joints

– Used in concrete masonry construction

• Expansion Joints– Used with clay brick

Page 9: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

Purpose of Control Joints

• Relieve horizontal tensile stresses• Reduce restraint and permit longitudinal

movement• Separate dissimilar materials

Page 10: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

Goal of Crack Control Provisions

Restraint at top andbottom

Limit crack widths to less than 0.02 in (0.5 mm)• able to be bridged by most coatings• prevents water penetration

TEK10-

Page 11: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

• Included in C 90– Compressive Strength– Absorption– Dimensional Tolerances– Density Definitions– Linear Drying Shrinkage

Specifying Concrete Masonry Units

TEK 1-1C

C 90Standard Specification forLoadbearing ConcreteMasonry Units

Page 12: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices • NOT Included in C 90

– Color– Texture– Density– Water Repellency– Fire Ratings– Thermal Properties– Sound Properties

Specifying Concrete Masonry Units

TEK 1-1C

Most architectural concretemasonry units are custom made. Work closely with producers toget exactly what you want.

C 90Standard Specification forLoadbearing ConcreteMasonry Units

Page 13: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

Type I and Type II CMU

3.1 Types - Two types of concrete masonry units are covered as follows:3.1.1 Type I, Moisture-Controlled Units - Units designated as Type 1 shallconform to the requirements of this specification.3.1.2 Type II, Nonmoisture-Controlled Units - Units designated as Type2 shall conform to the requirements of this specification with the exceptionof Table 1.

This section was removed.Does not appear in C 90-00 & later.

TEK 1-1C

Page 14: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

• When 50% or more of the surface area isobserved to be wet, the unit is considered to beunacceptable for placement.

• Damp surfaces are not considered wet.

• Test procedure: The surface is considered wet ifmoisture is observed and the surface does notdarken when free water is applied.

Recommended Maximum Unit Moisture Content

TEK 3-1C

Page 15: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

Control Joint Spacing Recommendations

1.5 h maximum

So, for h = 8 ft, spacing < 12 feet for h = 20 ft, spacing < 30 feet

25 feet

25 feet maximum

TEK 10-2B

h

Page 16: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

1. Control joint spacings are based on the use of horizontalreinforcement having an equivalent area of no less than 0.025 in2 / ftof height to keep unplanned cracks closed.

Sum of steel area height

TEK 10-2B

Control Joint Spacing Recommendations

Page 17: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

TEK 10-2B

Control Joint Spacing Recommendations

1. Control joint spacings are based on the use of horizontalreinforcement having an equivalent area of no less than 0.025 in2 / ftof height.

i.e. 9 gage jointreinforcementevery other course (16in.) or….

Page 18: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

TEK 10-2B

Control Joint Spacing Recommendations

1. Control joint spacings are based on the use of horizontalreinforcement having an equivalent area of no less than 0.025 in2 / ftof height.

…. by the use ofbond beams and…. #3 bars at 48 in. (4 ft.)#4 bars at 96 in. (8 ft.)#5 bars at 144 in. (12 ft.)

Page 19: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

The Role of Reinforcement inControlling Shrinkage Cracking

Without horizontal reinforcement

With horizontal reinforcement

Length after shrinkage ifunrestrained

ΔL

Length after shrinkage ifunrestrained

TEK 10-2B

ΔL

Page 20: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

Joint Reinforcement

•Primary function - control wall crackingassociated with shrinkage •Secondary Functions– metal tie system for bonding

– structural reinforcement whereallowed by code

TEK 12-2B

Page 21: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

Joint Reinforcement

TEK 12-2B

Consists of two or more longitudinal wires connected with cross wiresforming a truss or ladder configuration

Ladder Type Truss Type

Page 22: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

• Must be spliced a minimum of 6 inches perMSJC

• It is permissible to lay joint reinforcementon face shell and mortar over it.

Joint Reinforcement

Page 23: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

Control Joints

Backer rod in mortarjoint raked out to adepth of at least 3/4”

Sealant- polysulfide, urethane, silicone orepoxy. Avoid oil-based caulks orother materials that dry out rapidly ordo not bond effectively to masonry.

Page 24: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

Types of Control Jointswith Shear Resistance

• Preformed gasket • Grout shear key

TEK 10-2B

Page 25: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

Types of Control Jointswith Shear Resistance

TEK10-2

• Dowels • Special unit shape

Smooth dowel - sleeved orgreased on one end

Horizontal reinforcementdiscontinuous at joint (exceptfor structural bond beams)

Page 26: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

Eliminating Control JointsWith Reinforcement

Control joints can be eliminated completely if enough horizontalreinforcement is provided. ie., where As > 0.002 AnMaximum reinforcement spacing for 8 in.CMU (not solid grouted): #4 bar - 24 inches #5 bar - 40 inches #6 bar - 48 inches

TEK 10-1A & 10-3

Page 27: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

4-hour Rated Control Joints

Ceramic fiber blanket

TEK 10-2B

Note: Special unit shape and grout shear key type control jointsare also rated 4 hours as long as they contain backer rod and jointsealant.

Page 28: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

Control Joint Locations

• Typically use above grade in concretemasonry walls– Shrinkage cracks are an aesthetic rather than

a structural concern• Generally not used below grade

– Less temperature and moisture variation

TEK 10-2B

Page 29: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

Control Joint Locations

TEK 10-2B

At maximum ofone-half controljoint spacingfrom corners

Between main andintersecting wall

At changes in wall height

Adjacentto opening

Adjacentto opening

At pilasters andchanges in wallthickness

Page 30: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

Control Joints at Openingsin Unreinforced Walls

Openings less than 6 feet

TEK 10-2B

Page 31: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

Control Joints at Openings

Openings more than 6 feet

TEK 10-2B

Control Joints at Openingsin Unreinforced Walls

Page 32: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

Control Joints at Openingsin Reinforced Walls

Preferred strengthening of opening with reinforcement -extending lintel reinforcement andjoint reinforcement under the sill

TEK 10-3

12 “ min.

Page 33: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

Control Joints at Openingsin Reinforced Walls

Opening strengthened with joint reinforcement first two courses overopening and under the sill

TEK 10-3

Page 34: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

Control Joints for Multi-wythe Walls

If wythes are unbonded...

…consider control joint requirements separately for each wythe

If wythes are bonded...

…continue control joints from back-up through faceTEK 10-1A

Page 35: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

Impact of Mortar Strength

Weak mortar

Strong mortar

Page 36: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

CMU Band in Clay Brick Veneer

TEK 5-2A

Concrete masonryaccent band

Clay brick

o.c. or equivalent16 in. (406 mm)

Adjustable ladderwall tie (hot dipped

preferred2 in. (51 mm)(25 mm), min.,

Joint reinforcement,W1.7 (9 gage)(MW 11) at

(406 mm) o.c. verticalgalvanized) @ 16 in.

Closed cell rigidinsulation, as

Air space, 1 in.

Vapor retarder, perlocal practice

Wall tie, within12 in. (305 mm)of band

of band12 in. (305 mm)Wall tie, within

required

Joint reinforcement w/ no slip plane option

Page 37: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

CMU Band in Clay Brick Veneer

TEK 5-2A

Slip plane top and bottom of band option

Concrete masonryaccent band

Clay brick Seismic clip-typewall tie

preferred2 in. (51 mm),(25 mm), min.,

Closed cell rigidinsulation, as

Air space, 1 in.

Sealant and buildingpaper or otherbond break material

Vapor retarder, perlocal practice

of band12 in. (305 mm)Wall tie, within

12 in. (305 mm)Wall tie, within

of band

requiredJoint reinforcement

Page 38: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

Clay Brick Band in CMU Veneer

TEK 5-2A

Vapor retarder, per local practiceClosed cell

Air space, 1 in.

Expansion jointAdjustable tie

Sealant and

(25 mm) min.,

Expansion Joint Plan View for Clay Brickbacker rod

o.c. or equivalent

accent bandClay brick

Joint

(MW 11) at 16 in. (406 mm)

W1.7 (9 gage)

Concrete

at 16 in. (406 mm) o.c.,as required

Adjustable ladderwall tie (hot dippedgalvanized) @ 16 in.(406 mm) o.c. vertical

local practiceVapor retarder, per

rigid insulation

reinforcement,

masonry

Closed cell rigidinsulation, asrequired

(25 mm), min.,Air space, 1 in.

2 in. (51 mm),preferred

12 in. (305 mm)Wall tie, within

of band

of band12 in. (305 mm)Wall tie, within

2 in. (51 mm),preferred

No mortar in joint

(Control joint in concrete masonry is similar,except it may contain a raked out mortar joint)

Page 39: AIA Disclaimer Notice · presentation. AIA Disclaimer Notice. Continuing Education Services This is Not proper Crack Control. Continuing Education Services 1. Excessive deflection

ContinuingEducationServices

Summary

• Better manage movement throughmasonry systems by– Proper design– Using MSJC installation standards– Proper location of control joints– Proper use of bond beams– Proper placement of joint reinforcement

NCMA