CatalogueAir Handling Units

Climate parametersCountry CHINA CZECH REPUBLIC ESTONIA KAZAKHSTAN LITHUANIA VTS Lithuania Perknkiemio g. 4A 12128 Vilnius Tel: +370 5 2636152 Fax: +370 5 2636156 e-mail: [email protected] VTS China 21st oor World Plaza, No. 855 South Pudong Road 200120 Shanghai Tel.: +86 21 5119 6890 Fax: +86 21 5119 6891 E-mail: [email protected] LATVIA GERMANY Town Peking Shanghai Prague Brno Ostrava Tallin Alma-ata Astana Vilnius Klaipeda Riga Berlin Frankfurt Hamburg Munich Warsaw Gdansk Krakow Przemysl Suwalki Above sealevel [m]

Pressure[kPa]

Summer Temperature[C]

Winter Relative Temperature Enthalpy humidity [%]* [kJ/kg] [C] 34 59 34 37 37 59 30 26 48 60 56 40 40 40 40 45 52 45 45 45 -10.4 -3.7 -12 -12 -15 -22 -25 -35 -23 -20 -20 -14 -12 -12 -16 -20 -16 -20 -20 -24 -20.7 -24.4 -35.2 -21.9 -18.2 -18.8 -18.4 -13.4 -18.4 -18.4 -22.6 Relative humidity [%]* 90 90 95 95 95 100 100 100 100 100 100 90 90 90 90 100 100 100 100 100

Optional functions and accessories

Enthalpy[kJ/kg]

55 7 366 246 256 44 847 348 156 10 3 49 113 16 529 107 38 237 280 186

100.67 101.24 97 98.4 98.29 100.8 91.56 97.33 99.46 101.2 101.29 100.74 99.97 101.13 95.13 100.05 99.68 98.51 98.01 99.11

34.2 34.4 30 29 29 23.5 31.2 31 26.1 23.8 24.3 32 33 31 32 30 28 30 30 30

64 87.3 54.1 56.2 53.2 51.1 54.4 51.1 53.2 52.2 51.1 62.9 65.8 60.4 64.5 60 59.9 60 60 60

Optional functions NElectric pre-heaterLH

VTS Polska Al. Sikorskiego 11 02-758 Warszawa Tel.: +48 22 4313700 Fax: +48 22 4313714 [email protected]

VTS Ukraine Sholudenko 3 ofce 373 04116 Kiev Tel.: +38 044 230-4760 Fax: +380 44 230-4760 E-mail: [email protected]

VTS India VTS TF Air Systems Pvt Ltd 855, 3rd Cross, 11th Main HAL 2nd Stage Indiranagar Bangalore 560 008 Tel : +080 25213418 / 19 Fax : +080 25272423 E-mail: [email protected]

E empty section

S silencer

VTS Czech Republic Tel.: +420 241 443 839 Fax: +420 241 444 118 VTS Slovakia Tel.: +421 02 43 33 96 84 Fax: +421 02 44 63 06 39 VTS Hungary Hungria krt. 162., Hermina Business Tower B 1146 Budapest Tel.: +36 1 436 0100 Fax: +36 1 439 1636 E-mail: [email protected]

VS10 15 21 30 40 55 75 100 120 150 180 230 300 400 500 650

LH [mm] 731 731 731 731 731 731 731 731 731 731 731 731 731 731 -

mH [kg] 31 37 44 49 56 67 75 86 94 105 121 133 149 182 -

VS10 15 21 30 40 55 75 100 120 150* 180* 230* 300* 400* 500* 650*

LE [mm] 731 731 731 731 731 731 731 731 731 731/1097

hxw [mm]220x500 250x660 313x821 440x821 440x1028 575x1199

h2 x w2 [mm]220x500 220x500 250x660 440x821

mE [kg] 22 25 33 36 40 47 54 60 65 72/116 81/132 89/148 100/171 125/217 136/241 150/280

VS10 15 21 30 40 55 75 100 120 150 180 230 300 400 500 650

LS [mm] 731 731 1097 1097 1097 1097 1097 1097 1097 1097 1097 1097 1463 1463 1463 1463

mS [kg] 26 31 60 68 79 101 116 141 159 178 205 243 345 510 580 702

VTS Latvia Ganibu dambis 24a LV 1005 Riga Tel.: +371 7382530 Fax: +371 7395241 E-mail: [email protected]

POLAND

695x1340 440x1028 795x1520 575x1199 832x1751 575x1199 933x1945 795x1520

731/1097 1137x1945 795x1520 731/1097 1137x2353 933x1945 731/1097 1436x2445 933x1945 731/1097 1669x2945 933x2650 731/1097 1669x3445 933x3150 731/1097 2146x3557 933x3250

RUSSIA VTS Romania Strada George Baritiu, nr 33, sector 1 011295 Bucuresti Tel: +40 31 425 44 55 Fax: +40 31 425 44 56 E-mail: [email protected] VTS Kazakhstan 32A Manas Street, Ofce 502 B 050008 Almaty Tel: +7 3272 378488 Fax: +7 3272 378487 E-mail: [email protected]

VTS Russia 13 Rusakovskaya str. Borodino Plaza 107140 Moscow Russia Tel: +7 495 981 95 52 Fax: +7 495 981 95 53 [email protected]

VTS UAE Al Garhoud, Al Sayegh Building, Ofce 105 P BOX #76849.O. Dubai Tel.: +971 (4) 2869560 Fax: +971 (4) 2869561 E-mail: [email protected]

Moscow St. Petersburg Samara Kazan Jekaterynburg Krasnodar Rostov Nizni Novogrod Krasnoiarsk Irkutsk Vladivostok Omsk Perm Novosybirsk Murmansk

156 4 44 116 237 33 77 82 277 513 184 123 172 177 51

99.46 101.28 100.8 99.94 97 100.93 100.4 100.34 98.04 95.31 99.13 99.86 99.28 99.22 100.71

28.5 24.8 29.7 27.3 28.7 30.8 31.9 26.8 25.9 26.9 23.4 27.7 26.3 28.4 22

54 51.5 55.3 54.8 51.1 63.6 60.7 54.9 51.9 53.6 61.5 53.6 53.2 54.8 42.7

40 52 38 46 34 46 38 49 46 45 81 42 48 41 49

-26 -26 -30 -32 -35 -19 -32 -30 -40 -37 -24 -37 -35 -39 -27

-25.3 -25.3 -29 -31.7 -34.6 -17.6 -20.9 29.7 -40.2 -37.1 25.3 -36.8 -34.9 -38.9 -26.6

100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

* Data regarding length and weight refers to the empty section with a horizontal or a top/bottom inlet/outlet respectively.

M mixing box

F secondary lter

www.vtsgroup.com

SLOVAKIA UKRAINE

Bratislava Kosice Kiev Doneck Odessa Dnepropietrovsk Lvov Budapest Abu-Dhabi Dubai

130 232 168 226 35 142 366 185 27 5

99.7 98.57 99.32 98.64 100.91 99.63 97 99.12 101 101.26

32 31 28.7 31.8 28.6 31 26.4 32 46 46

58.2 59.8 56.1 58.6 62 57.4 57.4 63.9 96.6 96.6

34 39 43 34 53 36 54 40 30 30

-12 -12 -22 -25 -18 -23 -19 -15 12 13

-20.7 -24.3 -18.3 -22 -17.6 27 27

95 95 100 100 100 100 100 90 70 70

VS10 15 21 30 40 55 75 100 120 150 180 230 300 400 500 650

LM [mm] 731 731 731 731 731 731 731 1097 1097 1097 1097 1097 1097 1097

h2 x w2 [mm]220x500 220x500 250x660 440x821 440x1028 575x1199 575x1199 795x1520 795x1520 933x1945

h3 x w3 [mm]213x380 313x380 313x380 413x380 413x380 613x380 613x380 713x740 913x740 913x740

mM [kg] 40 43 49 62 73 85 91 126 155 188 202 252 282 304

VS10 15 21 30 40 55 75 100 120 150 180 230 300 400 500 650

LF [mm] 731 731 731 731 731 731 731 731 731 731 731 731 731 731

mF [kg] 39 43 47 57 69 78 83 94 106 117 140 181 200 230

HUNGARY UNITED ARAB EMIRATES EUROPE

Bucharest Paris Amsterdam Minsk Vienna London Amman Riyadh Muscat Kuwait Bombay Delhi Washington Montreal Doha

91 109 -2 234 200 24 773 612 15 55 14 216 20 82 42

100.24 100.02 101.35 98.55 98.95 101.04 92.38 94.19 101.14 100.67 101.16 98.75 101.08 100.34 101.26

33 29.8 28 25.9 32 27.4 42 47 54 47 35 41.7 34.8 28.8 46

64.5 60.4 58.5 53.6 63.6 53.4 97.7 80.7 130.8 100.6 67.7 65 75.2 62.6 96.6 40 18 30 30 35 17 44 52 30 2 8 17 5 19 8 -9.3 -26.9 13 70 50 30 30 70 63 90 90 70

933x2650 1513x740 933x3250 1913x740

Accessories

AD - air damper

IndexVTSA corporation with European tradition ............................... 2 A trustworthy brand ........................................................... 3 VENTUS made of expectations ........................................... 4 Wide scope of possibilities ................................................ 5 We design for you .............................................................. 6 ClimaCAD On-Line ............................................................. 7 Guarantee of quality ........................................................... 8 Feel the difference .............................................................. 9

VENTUS Air Handling UnitsGeneral description ........................................................... 12 How to select an AHU? ...................................................... 13 Symbols and labels ............................................................. 14 Base AHUs and optional functions ...................................... 15 Quick selection ................................................................... 16 Navigation .......................................................................... 20 Base VENTUS AHUs ........................................................... 21 Supply AHUs ...................................................................... 21 Exhaust AHUs ..................................................................... 25 Supply-exhaust AHUs ......................................................... 27 Optional functions .............................................................. 53 Components ...................................................................... 54 Casing ................................................................................. 54 Filters .................................................................................. 56 Heaters ............................................................................... 58 Coolers ............................................................................... 60 Energy Recovery ................................................................. 62 Fan sets ............................................................................... 64 Mixing box, Silencers .......................................................... 66 Accessories ......................................................................... 68

AutomationControl elements ................................................................ 72 Control applications ............................................................ 78

Psychrometric chart ............................................................ 92 Optional functions, accessories .. bookmark

VTS Latvia VTS VTS Lithuania Estonia VTS Belarus VTS VTS Poland Ukraine

VTS Kazakhstan

VTS Russia

VTS Czech Republic VTS Romania

VTS Slovakia

VTS Hungary VTS China

VTS United Arab Emirates VTS India

A corporation with European traditionVTS Group is a leading supplier in the ventilation and air conditioning trade. We create and implement innovative and technologically advanced solutions for all types of industrial facilities, commercial institutions and hotels. We have been providing people in 19 countries with perfect atmosphere for 20 years now. We are an international company with European roots and tradition of reliable quality.

We monitor the market in detail and react to its changes immediately. Hence we are able to provide our clients with the best solutions that are perfectly tailored to their needs.

Latitude or climate are not important. Our ventilation and air handling units guarantee comfort regardless of a facilitys location. We are real experts in good climate

2

A trustworthy brand

The quality and parameters of VTS devices are conrmed by international Eurovent and TV certicates. We comply with all requirements stemming from European (CE) product safety standards as well as the integrated quality and environment protection system ISO 9001/ISO 14001.

EuroventIt conrms the conformity of parameters of selected devices, calculated with the use of the Clima CAD On-Line (CCOL) application, with real operating parameters.

ISO 9001, ISO 14001ISO 9001 guarantees complete repeatability of all VTS devices. ISO 14001 conrms an efcient environment management system.

EN 1886, EN 13053Two major European standards describing the performance and mechanical characteristics of Air Handling Units.

CEVTS devices comply with the safety standards in accordance with the European Unions guidelines.

VENTUS made of expectationsVENTUS is a type-line of ventilation and air conditioning units offered by VTS Group. The functionality and application of the product reect market demand and are the effect of intensive work of some experienced specialists in the trade. The AHU was designed with the use of state-of-the-art technologies, advanced material engineering and completely innovative constructional solutions. Due to that the AHU is reliable, energy-saving and fully adjusted to the expectations of the market.

We look at our AHUs from the angle of our Clients needs. They can be applied regardless of weather conditions or geographical zones. Designing devices is incredibly simple thanks to our technical and commercial advisers as well as the ClimaCAD tool that makes it possible to prepare an AHU specication in just 4 steps. We have optimized the process of delivering AHUs to the construction site and created a team of qualied specialists to assemble them. We want the operation of devices to produce some notable benets. Hence our special attention to energy recovery of our devices reaching up to 85%! That is why VENTUS type-line is made of expectations.

4

Wide scope of possibilitiesWide performance rangeAs many as 16 sizes! Adjusting an AHU size to the cubic capacity of a particular building

Frameless casingOperation in different climatic zones (-40 to +70C) Lack of thermal bridges elimination of moist condensation Durability for years sandwich type panels with polyurethane foam

Small dimensions of a deviceLow AHUs minimum height is only 36cm! Adaptation to technical and utility rooms, ventilation ducts

Air treatment functionAdjustment of air treatment functions to a required microclimate

5

We design for you

Technical and commercial adviserTop class specialists in the trade are ready to design an AHU adapted to your design. Extensive network of commercial ofces makes us more accessible. We provide advice and assistance during the whole process of selecting and purchasing a particular device.

ClimaCAD On-LineOur Clients can design an AHU themselves using a tool available at www.vtsgroup.com Designing an AHU involves 4 steps of selection and 10 seconds of calculation Calculations in the analytical module with alternative results + indicating an optimum solution

6

ClimaCAD On-Line

Step 1 selection of a base AHU

Step 2 selection of optional functions and parameters

Step 3 selection of an AHU from among several alternative options

Step 4 a ready AHU with a complete set of technical data

www.vtsgroup.com

Guarantee of quality

We care for quality on all stages of work with the product starting from AHU design through production to service assistance. VENTUS is always delivered by professional forwarders fully responsible for the quality of transport. We make sure that our ventilation and air conditioning units are always assembled by highly qualied services. Assembly is included as standard and we are responsible for performing services of the highest quality possible.

VTS Group has prepared a network of authorized service centers to work with the product. Their assistance is available 24 hours a day they are always at our Clients disposal.

We guarantee appropriate operation of our VENTUS ventilation and air conditioning AHUs.

8

Feel the difference

Silent operation of AHUsThe PLUG fan set with frequency converter Different fan sizes for one AHU size Improved shape of fan blades

Simple controlHMI (Human Machine Interface) Simple and clear interface Reading out and setting up operation parameters from any location in a building Communication with any number of AHUs

Energy recoveryDifferent types of energy recovery Efciency up to 85% Separation of the exhaust air stream from the supply air stream Sensible and latent heat recovery

BMS(Building Management System) Automation open for overriding control system Monitoring of devices performance from any place

9

Air Handling Units

10

VENTUS Air Handling UnitsGeneral description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 How to select an AHU? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Symbols and labels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Base AHUs and optional functions . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Quick selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Supply AHUs Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Heating, Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Heating, Cooling, Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Exhaust AHUs Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Filtration, Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Supply-exhaust AHUs: cross-ow exchanger Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Heating, Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Heating, Cooling, Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 Supply-exhaust AHUs: rotary exchanger Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 Heating, Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 Heating, Cooling, Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Supply-exhaust AHUs: glycol system Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Heating, Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Optional functions and accessories . . . . . . . . . . . . . . . . . . . . . . . . 53 Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 Control elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 Control applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78

Due to continuous improvement of the product VTS reserves its rights to implement modications. Some technical specication as well as descriptions may differ from the actual state. Before placing an order technical specication and operation parameters of particular devices should be conrmed with a VTS representative.

VS 21650 Capacity:

VS 1015

400 100 000 [m3 /h]Functions:A

Sizes:

10

15

21

30

40

55

75

100

120

150

180

230

300

400

500

650

12

How to select an AHU?1Start with the Quick selection page (p. 16-19): choose a type and a size of an AHU; check which AHUs provide a capacity you are interested in; choose the optimal one on the basis of air ow speed through the units window, taking the most important function into consideration; read the size of the unit , e.g. VS 21.VS unit 's size Dimensions2000

Airow [m3/h]4000 6000

[mm] [mm] [mm] [mm] [mm] [mm] [m2] [mm] [mm] [mm] [m2] [mm] [mm] 0,7 1 10 360 2 3 3,4 [m/s]

H Hs Hf W H2 H2s H2f W2 Hi Wi Ai Hf Hs

-

-

660

-

-

-

1330 280

580 0,16

-400 0,7 1 2 1960 [m3/h]

3

3,6 [m/s]

15

390

-

-

800

-

-

-

1610 310

720 0,22

-600 2900 [m3/h]

1 21

2

3 3,1 [m/s]

-

488 544* 961

544 936 992

-

368 881 0,32 40

96 1167 3658 [m3/h]

1

2

3 3,2 [m/s]

2On the Navigation page (p. 20): nd a base unit which is equipped with functions you are interested in and the corresponding automatics; move to an appropriate page.AHU TYPESUPPLY AHUsHeating Cooling Heating, Cooling Heating, Cooling, Heating

FUNCTION

PAGE NUMBER AHUs AUTOMATICSVS 1015 VS 21650 VS 1015 VS 21650

21

21 22

78 79 80

23

23 24

EXHAUST AHUs25Ventilation

25 26

81 81

26

SUPPLY EXHAUST AHUs27 27 82 84

3On the page with a description of an AHU: choose the access side; choose optional functions and accessories; read the parameters for the chosen size of a base AHU as well as optional functions (tables for optional functions are presented on page 53 and on the bookmark).VS 10 15 21 30 40 55 Vmin [m3/h] 436 648 1167 1586 1958 2878 Vmin [CFM] 257 381 687 933 1152 1694

VS 21650 sizes

HxW

HxW

Hf L L

Hf

VS -

- R - HC

VS -

- R - CH

Vmax [m3/h] 1160 1740 2200 3100 4100 6054

Vmax [CFM] 683 1024 1295 1825 2413 3563

L [mm] 1124 / 1490* 1490 1856 1856 1856 2221

L* [mm] 0 0 2221 2221 2221 2587

HH f* (H(s) / (H(f)) (H(s) / (H(f)) [mm][mm] 360 390 488 / 544Hf* 620 / 676 Hf* 620 / 676 Hf*Hf* 755 / 811

W [mm] 660 800 961 961 1168 1339

hxw [mm] 220x500 250x660 313x821 440x821 440x1028 575x1199

hxw [mm] 220x500 250x660 313x821 440x821 440x1028 575x1199

h1 x w1 [mm] 0 0 250x660 380x613 440x821 440x1028

0 0 40 / 96Hf* 40 / 96Hf* 40 / 96Hf*Hf* 40 / 96

4Write down the code of an AHU down and check the information concerning a recommended control application.

VS -

21

-

R

-

SEoptional functions before a base AHU

/

HCcode of a base AHU

/

EFoptional functions behind a base AHU

size of an AHU

access side R - right L - left

A80

Detailed technical specication is available in ClimaCAD On-Line application at www.vtsgroup.com. If you want to order a selected unit, get in touch with our Sales and technical adviser.

13

Symbols and labelsBasic functions of a base AHU Optional functions

V - Ventilator

N - Electric pre-heater

F - pre-Filter

E - Empty section

H - Heater: water, electric

S - Silencer

C - Cooler: water, with direct expansion

F - Secondary Filter

P - Plate cross-ow recuperator

M - Mixing box

AccessoriesFC - Flexible Connection R - Rotary regenerator

AD - Air Damper

MiscellaneousG - Glycol system (Run-around coil) CCOL - ClimaCAD On-Line order of exchangers in a unit (heater, cooler) order of exchangers in a unit (cooler, heater)

View of an AHUfrom a side: VS 10650 from the top: VS 1015 from a side: VS 21650 (a dominating function in a lower module)

80

page symbol

Automatics

units inlet

units outlet

14

Base AHUs and optional functionsBase AHUCross-ow exchanger Rotary exchanger Glycol system

Optional functions

Np. 62 p. 62 p. 62 p. 58

P

R

G E

Fan

Pre-lter

p. 64

p. 56

Sp. 66

V

F

Fp. 56

Mp. 66

VS -

- R - RHC

AccessoriesWater cooler Water heater p. 60 p. 58

CDirect expansion coil

FCp. 68

ADp. 68

HElectric heater

Automation p. 58 p. 60 p. 78

H

C

Coding system

VS -

75

-

R

-

SEoptional functions placed before a base unit

/

RHCcode of a base AHU

/

EFoptional functions placed behind a base unit

T the assembly method for VS 10-15 AHUs (suspended AHUs) COMPACT compact AHU

size of an AHU

access side R - right L - left

15

Quick selectionVS unit 's size Dimensions2000

Airow [m3/h]4000 6000

H*H2*Hs * W HW2 Hi Wi Ai HH(min)/H(max) [mm] 2(min)/H2(max) [mm] [mm] [mm] [m2] s(min)/Hs(max) [mm] [mm] [mm]0,7 1 2

3 3,4 [m/s]

10

360

660

-

1330 280

580 0,16

400 1960 [m3/h]

0,7 1

2

3

3,6 [m/s]

15

390

800

-

1610 310

720 0,22

600 2900 [m3/h]

1

2

3 3,1 [m/s]

21

528 / 544

961

976 / 992

-

368

881 0,32

80 / 96 1167 3658 [m3/h]

1

2

3 3,2 [m/s]

30

660 / 676

961

1240 / 1256

-

500

881 0,44

80 / 96 1586 5118 [m3/h]

1

2

3

3,4 [m/s]

40

660 / 676

1161

1240 / 1256

-

500 1088 0,54

80 / 96 1958 6700 [m3/h]

55

795 / 811

1339

1510 / 1526

-

635 1259 0,80

80 / 96

75

915 / 931

1480

1750 / 1766

-

755 1400 1,06

80 / 96

100

1015 / 1031

1660

1950 / 1966

-

855 1580 1,35

80 / 96

* - heights options details on page 54 Construction of a unit H, H(min) / H(max) height of a unit, minimal / maximal VS 1015 W - width of a unit H2, H Legend: 2(min) / H2(max) - height of an integrated unit, minimal / maximal Hi - height of a units cross section H H Wi - width of a units cross section Ai - cross section of the window inside a unit W Hs, Hs(min) / Hs(max) - height of an units support, W minimal / maximali i

VS 21650

VS 1015

VS 21650

Hs Wi W

Hi H W2

H Hs W

H2

16

Airow [m3/h]4000 6000 8000 10 000 12 000 14 000 16 000 18 000

VS unit 's size

v - air velocity in cross section of a unit Ai

10

1

2

3

4

[m/s]

cooler's operation range water heater's operation range lter's operation range

15

Vmin

Vmax

[m3/h]

V - unit's airow optimum air velocity in a unit's cross section = 2.6m/s in exchanger's cross section

21

30

40

1

2

3

3,4 [m/s]

552878 9720 [m3/h]

1

2

3

3,5 [m/s]

753805 13 470 [m3/h]

1

2

3

3,6 [m/s]

1004863 17 620 [m3/h]

Maximum air velocity vmax [m/s] functions

velocity in a units cross section velocity in a component's cross section

3,6 4,3

3,0 3,5

3,5 4,4

3,6 4,5

2,3 2,8

2,3 2,8

3,6 4,5

3,6 5,2

17

VS unit 's size

Dimensions10 000 15 000

Airow [m3/h]20 000 25 000 30 000 35 000 40 000 45 000

H*H2*Hs * 5000 W HW2 Hi Wi Ai HH(min)/H(max) [mm] 2(min)/H2(max) [mm] [mm] [mm] [m2] s(min)/Hs(max) [mm] [mm] [mm]1

2

3

3,7[m/s]

120

1052 / 1068

1891

2024 / 2040

-

892 1811 1,62

80 / 96 5815 21 410[m3/h]

1

2

3

3,7[m/s]

150

1153 / 1169

2085

2226 / 2242

-

993 2005 1,99

80 / 96 7167 26 558 [m3/h]

1

2

3

3,7 [m/s]

180

1357

2085

2714

-

1197 2005 2,40

80 8640 32 246 [m3/h]

1

2

3

3,8[m/s]

230

1357

2493

2714

-

1197 2413 2,89

80 10 398 39 630 [m3/h]

300

1656

2585

3312

-

1496 2505 3,75

80

400

1889

3085

3778

-

1729 3005 5,20

80

500

1889

3585

3778

-

1729 3505 6,06

80

650

2366

3697

4732

-

2206 3617 7,98

80

* - heights options details on page 54 Construction of a unit H, H(min) / H(max) height of a unit, minimal / maximal VS 1015 W - width of a unit H2, H Legend: 2(min) / H2(max) - height of an integrated unit, minimal / maximal Hi - height of a units cross section H H Wi - width of a units cross section Ai - cross section of the window inside a unit W Hs, Hs(min) / Hs(max) - height of an units support, W minimal / maximali i

VS 21650

VS 1015

VS 21650

Hs Wi W

Hi H W2

H Hs W

H2

18

Airow [m3/h]10 000 20 000 30 000 40 000 50 000 60 000 70 000 80 000 90 000 100 000

VS unit 's size

v - air velocity in cross section of a unit Ai

120

1

2

3

4

[m/s]

cooler's operation range water heater's operation range lter's operation range

150

Vmin

Vmax

[m3/h]

V - unit's airow optimum air velocity in a unit's cross section = 2.6m/s in exchanger's cross section

180

230

1

2

3

3,9 [m/s]

30013 491 53 010 [m3/h]

1

2

3

3,3 [m/s]

40018 704 62646 [m3/h]

1

2

3

3,6 [m/s]

50021 817 79 350 [m3/h]

1

2

3

3,5 [m/s]

65028 725 100 000 [m3/h]

Maximum air velocity vmax [m/s] functions

velocity in a units cross section velocity in a component's cross section

3,6 4,3

3,0 3,5

3,5 4,4

3,6 4,5

2,3 2,8

2,3 2,8

3,6 4,5

3,6 5,2

19

NavigationFUNCTION AHU TYPESUPPLY AHUsHeating Cooling Heating, Cooling Heating, Cooling, Heating

PAGE NUMBER AHUs AUTOMATICSVS 1015 VS 21650 VS 1015 VS 21650

21

21 22

79 80 81

23

23 24

EXHAUST AHUs25Ventilation

25 26

82 82

26

SUPPLY EXHAUST AHUs27Ventilation

27 41 52

84 89 91 84 89 91 85 90 85 90

86

29, 31Heating

29, 30, 31 42, 43 50 32, 33, 34

86

87

Cooling

44, 45 35, 37Heating, Cooling

35, 36, 37 46, 47 51 38, 39, 40

87

Heating, Cooling, Heating

48, 49

OPTIONAL FUNCTIONS:* VS 1015 AHUs are available as indoor units only. ** Optional functions are available for VS 21650 AHUs only. *** Optional function is available for VS 10650 AHUs (VS 1015 AHUs are equipped with the function of mixing defined just as a set of two air dampers). Inlet/Outlet configurations of E empty section are presented on page 53 and on the bookmark. Inlet/Outlet configurations of M mixing box are presented on page 53 and on the bookmark. Dimensions of optional functions are presented on page 53 and on the bookmark.

V MAX parameters are specified for the following: VS 10 equipped with the fan set and a motor with the following parameters n= 2790 rpm, P=0,55 kW, VS 15 equipped with the fan set and a motor with the following parameters n=2850 rpm, P=0,75 kW, VS 21VS 150 equipped with fan sets with direct drive, VS 180VS 300 equipped with double fan sets (direct driven), VS 400VS 500 equipped with triple fan sets (direct driven), VS 650 - equipped with fourfold fan sets (direct driven). VTS reserves the right to make a changes in product.

20

Detailed specication is available in the CLIMA-CAD on-line selection application at www.vtsgroup.com

Supply AHUsHeatingBase AHU VS 1015 sizes (suspended)*

A79

HxW

L

VS VS 21650 sizes

- R -H- T

HxW

Hs L

VS -

- R -HL [mm]1124 1124 1124 1490 1490 1856 1856 1856

VS 21150 sizes COMPACTVS21 30 HxW 40 55 Hs 75 100 Lf L 120 150

L2R [mm]1124 1124 1124 1124 1490 1490 1490 1490

Lf [mm]92 92 92 92 92 92 92 92

VS10 15 21 30 40 55 75 100 120 150 180 230 300 400 500 650

Vmin [m3/h]436 648 1167 1586 1958 2878 3805 4863 5815 7167 8640 10398 13491 18704 21817 28725

Vmin [CFM]257 381 687 933 1152 1694 2240 2862 3423 4218 5085 6120 7941 11009 12841 16907

Vmax* [m3/h]1655 2462 3080 4322 5661 8216 11379 13550 18079 22420 27220 33460 44760 60501 74350 98500

Vmax* [CFM]974 1449 1813 2544 3332 4836 6697 7975 10641 13196 16021 19694 26345 35610 43761 57975

L [mm]758 / 1124* 758 / 1124* 1490 1490 1490 1856 1856 2221 2221 2221 2221 2221 2587 2587 2587 2587

H*Hs* (H(min) / (H(max)) (Hs(min) / (Hs(max)) [mm][mm]360 390 528 / 544 660 / 676 660 / 676 795 / 811 915 / 931 1015 / 1031 1052 / 1068 1153 / 1169 1357 1357 1656 1889 1889 2366 0 0 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 80 80 80 80 80

W [mm]660 800 961 961 1168 1339 1480 1660 1891 2085 2085 2493 2585 3085 3585 3697

hxw [mm]220x500 250x660 313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445 2146x3557

hxw [mm]220x500 250x660 313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445 2146x3557

h1 x w1 [mm]0 0 250x660 380x613 440x821 440x1028 575x1199 695x1340 795x1520 795x1520 795x1520 740x1913 933x1945 933x2650 1199x3150 1520x3250

758/1124* - for VS- 10 and VS-15 with water heater is 758mm, with electric heater is 1124mmVmax - Parametres description on page 20 H*, Hs* - heights options details on page 54Optional functions are presented on the bookmark (in the back cover). L2R - length of AHU equipped with two-rows exchanger - VS 15 lenght for optional fan (low pressure) as well as the location of the water heater

VS -

15

-

R

-

SE

/

PHCHcode of a base AHU

/

EFoptional functions behind a base AHU

the assembly method for VS 10-15 AHUs (suspended AHUs) COMPACT compact AHU

size of an AHU

access side optional functions R - right before a base L - left (the option AHU available for VS 21-650 units)

21

Supply AHUsCooling

A80

Base AHU VS 21650 sizes

HxW

Hs L

VS -

- R -C

VS 21150 sizes COMPACT

VS21 30 HxW 40 55 Hs 75 100 Lf L 120 150

L [mm]1124 1124 1124 1490 1490 1856 1856 1856

L* [mm]1490 1490 1490 1856 1856 2221 2221 2221

Lf [mm]92 92 92 92 92 92 92 92

VS21 30 40 55 75 100 120 150 180 230 300 400 500 650

Vmin [m3/h]1167 1586 1958 2878 3805 4863 5815 7167 8640 10398 13491 18704 21817 28725

Vmin [CFM]687 933 1152 1694 2240 2862 3423 4218 5085 6120 7941 11009 12841 16907

Vmax* [m3/h]2200 3100 4100 6054 8150 10700 13300 16400 19900 24600 32900 44500 54000 71400

Vmax* [CFM]1295 1825 2413 3563 4797 6298 7828 9653 11713 14479 19364 26192 31783 42025

L [mm]1490 1490 1490 1856 1856 2221 2221 2221 2221 2221 2587 2587 2587 2587

L* [mm]1856 1856 1856 2221 2221 2587 2587 2587 2221 2221 2587 2587 2587 2587

Hs*H* (H(min) / (H(max)) (Hs(min) / (Hs(max)) [mm][mm]528 / 544 660 / 676 660 / 676 795 / 811 915 / 931 1015/1031 1052 / 1068 1153 / 1169 1357 1357 1656 1889 1889 2366 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 80 80 80 80 80

W [mm]961 961 1168 1339 1480 1660 1891 2085 2085 2493 2585 3085 3585 3697

hxw [mm]313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445 2146x3557

hxw [mm]313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445 2146x3557

h1 x w 1 [mm]250x660 380x613 440x821 440x1028 575x1199 695x1340 795x1520 795x1520 795x1520 740x1913 933x1945 933x2650 1199x3150 1520x3250

L* - Length of the supply section in conguration with drop eliminator installed behind the cooler H*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover). * VS 1015 AHUs are available as indoor units only. ** Optional functions are available for VS 21650 AHUs only. *** Optional function is available for VS 10650 AHUs (VS 1015 AHUs are equipped with the function of mixing defined just as a set of two air dampers). Inlet/Outlet configurations of E empty section are presented on page 53 and on the bookmark. Inlet/Outlet configurations of M mixing box are presented on page 53 and on the bookmark. Dimensions of optional functions are presented on page 53 and on the bookmark. Change of interrelated settings of a heater and a cooler results in changing the code of a specific AHU.

22

Supply AHUsHeating, CoolingBase AHU VS 1015 sizes (suspended)*

A81

HxW

L

VS -

- R - HC - T

VS 21650 sizes

HxWHs L

HxW

HsVS -

- R - CH

L

VS -

- R - HCVS21 30

VS 21150 sizes COMPACT

L [mm]1490 1490 1490 1856 1856 2221 2221 2221

L* [mm]1856 1856 1856 2221 2221 2587 2587 2587

Lf [mm]92 92 92 92 92 92 92 92

HxWHs

HxW

40 55 75 100 120 150

Hs Lf L

Lf

L

VS10 15 21 30 40 55 75 100 120 150 180 230 300 400 500 650

Vmin [m3/h]436 648 1167 1586 1958 2878 3805 4863 5815 7167 8640 10398 13491 18704 21817 28725

Vmin [CFM]257 381 687 933 1152 1694 2240 2862 3423 4218 5085 6120 7941 11009 12841 16907

Vmax* [m3/h]1160 1740 2200 3100 4100 6054 8150 10700 13300 16400 19900 24600 32900 44500 54000 71400

Vmax* [CFM]683 1024 1295 1825 2413 3563 4797 6298 7828 9653 11713 14479 19364 26192 31783 42025

L [mm]1124 / 1490* 1124 / 1490* 1856 1856 1856 2221 2221 2587 2587 2587 2587 2587 2953 2953 2953 2953

L* [mm]0 0 2221 2221 2221 2587 2587 2953 2953 2953 2587 2587 2953 2953 2953 2953

Hs*H* (H(min) / (H(max)) (Hs(min) / (Hs(max)) [mm][mm]360 390 528 / 544 660 / 676 660 / 676 795 / 811 915 / 931 1015/1031 1052 / 1068 1153 / 1169 1357 1357 1656 1889 1889 2366 0 0 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 80 80 80 80 80

W [mm]660 800 961 961 1168 1339 1480 1660 1891 2085 2085 2493 2585 3085 3585 3697

hxw [mm]220x500 250x660 313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445 2146x3557

hxw [mm]220x500 250x660 313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445 2146x3557

h1 x w1 [mm]0 0 250x660 380x613 440x821 440x1028 575x1199 695x1340 795x1520 795x1520 795x1520 740x1913 933x1945 933x2650 1199x3150 1520x3250

L* - Length of the supply section in conguration with drop eliminator installed behind the cooler 1124/1490* - L for VS-10 and VS-15 with water heater = 1124 mm, with electric heater = 1490 mm H*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20 Optional functions are presented on the bookmark (in the back cover).

VS -

15

-

R

-

SE

/

PHCHcode of a base AHU

/

EFoptional functions behind a base AHU

the assembly method for VS 10-15 AHUs (suspended AHUs) COMPACT compact AHU

size of an AHU

access side optional functions R - right before a base L - left (the option AHU available for VS 21-650 units)

23

Supply AHUsHeating, Cooling, Heating

A

Base AHU

VS 21650 sizes

HxW

Hs L

VS -

- R - HCH

VS21 30 40 55 75 100 120 150 180 230 300 400 500 650

Vmin [m3/h]1167 1586 1958 2878 3805 4863 5815 7167 8640 10398 13491 18704 21817 28725

Vmin [CFM]687 933 1152 1694 2240 2862 3423 4218 5085 6120 7941 11009 12841 16907

Vmax* [m3/h]2200 3100 4100 6054 8150 10700 13300 16400 19900 24600 32900 44500 54000 71400

Vmax* [CFM]1295 1825 2413 3563 4797 6298 7828 9653 11713 14479 19364 26192 31783 42025

L [mm]2221 2221 2221 2587 2587 2953 2953 2953 2953 2953 3318 3318 3318 3318

L* [mm]2587 2587 2587 2953 2953 3318 3318 3318 2953 2953 3318 3318 3318 3318

Hs*H* (H(min) / (H(max)) (Hs(min) / (Hs(max)) [mm][mm]528 / 544 660 / 676 660 / 676 795 / 811 915 / 931 1015/1031 1052 / 1068 1153 / 1169 1357 1357 1656 1889 1889 2366 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 80 80 80 80 80

W [mm]961 961 1168 1339 1480 1660 1891 2085 2085 2493 2585 3085 3585 3697

hxw [mm]313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445 2146x3557

hxw [mm]313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445 2146x3557

h1 x w1 [mm]250x660 380x613 440x821 440x1028 575x1199 695x1340 795x1520 795x1520 795x1520 740x1913 933x1945 933x2650 1199x3150 1520x3250

L* - Length of the supply section in conguration with drop eliminator installed behind the cooler H*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover). * VS 1015 AHUs are available as indoor units only. ** Optional functions are available for VS 21650 AHUs only. *** Optional function is available for VS 10650 AHUs (VS 1015 AHUs are equipped with the function of mixing defined just as a set of two air dampers). Inlet/Outlet configurations of E empty section are presented on page 53 and on the bookmark. Inlet/Outlet configurations of M mixing box are presented on page 53 and on the bookmark. Dimensions of optional functions are presented on page 53 and on the bookmark.

24

Exhaust AHUsVentilationBase AHU VS 1015 sizes (suspended)*

A82

HxW

L

VS -

- R -V- T

VS 21650 sizes

HxW

Hs L

VS -

- R -V

VS10 15 21 30 40 55 75 100 120 150 180 230 300 400 500 650

Vmin [m3/h]400 600 1167 1586 1958 2878 3805 4863 5815 7167 8640 10398 13491 18704 21817 28725

Vmin [CFM]235 353 687 933 1152 1694 2240 2862 3423 4218 5085 6120 7941 11009 12841 16907

Vmax* [m3/h]1960 2840 4814 6580 8140 12017 15884 20346 24295 30014 36231 43589 56764 62646 91861 100000

Vmax* [CFM]1154 1672 2833 3873 4791 7073 9349 11975 14300 17666 21325 25656 33410 37068 54068 58858

L [mm]758 758 758 758 758 1124 1124 1490 1490 1490 1490 1490 1856 1856 1856 1856

H*Hs* (H(min) / (H(max)) (Hs(min) / (Hs(max)) [mm][mm]360 390 528 / 544 660 / 676 660 / 676 795 / 811 915 / 931 1015/1031 1052 / 1068 1153 / 1169 1357 1357 1656 1889 1889 2366 0 0 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 80 80 80 80 80

W [mm]660 800 961 961 1168 1339 1480 1660 1891 2085 2085 2493 2585 3085 3585 3697

hxw [mm]220x500 250x660 313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445 2146x3557

hxw [mm]220x500 250x660 313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445 2146x3557

h1 x w 1 [mm]0 0 250x660 380x613 440x821 440x1028 575x1199 695x1340 795x1520 795x1520 795x1520 740x1913 933x1945 933x2650 1199x3150 1520x3250

H*, Hs* - heights options details on page 54 Optional functions are presented on the bookmark (in the back cover).

Vmax - Parametres description on page 20

VS -

15

-

R

-

SE

/

PHCHcode of a base AHU

/

EFoptional functions behind a base AHU

the assembly method for VS 10-15 AHUs (suspended AHUs) COMPACT compact AHU

size of an AHU

access side optional functions R - right before a base L - left (the option AHU available for VS 21-650 units)

25

Exhaust AHUsFiltration, Ventilation

A82

Base AHU VS 1015 sizes (suspended)*

HxW

L

VS VS 21650 sizes

- R - FV - T

HxW

Hs L

VS -

- R - FVL [mm]758 758 758 1124 1124 1490 1490 1490

VS 21650 sizes COMPACTVS21 30

Lf [mm]92 92 92 92 92 92 92 92

HxW Hs Lf LHs*H* (H(min) / (H(max)) (Hs(min) / (Hs(max)) [mm][mm]360 390 528 / 544 660 / 676 660 / 676 795 / 811 915 / 931 1015/1031 1052 / 1068 1153 / 1169 1357 1357 1656 1889 1889 2366 0 0 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 80 80 80 80 80

40 55 75 100 120 150

VS10 15 21 30 40 55 75 100 120 150 180 230 300 400 500 650

Vmin [m3/h]400 600 1167 1586 1958 2878 3805 4863 5815 7167 8640 10398 13491 18704 21817 28725

Vmin [CFM]235 353 687 933 1152 1694 2240 2862 3423 4218 5085 6120 7941 11009 12841 16907

Vmax* [m3/h]1960 2840 3658 5118 6700 9720 13470 17620 21410 26558 32246 39630 53010 62646 79350 100000

Vmax* [CFM]1154 1672 2153 3012 3943 5721 7928 10371 12601 15632 18979 23325 31201 37068 46704 58858

L [mm]758 758 1124 1124 1124 1490 1490 1856 1856 1856 1856 1856 2221 2221 2221 2221

W [mm]660 800 961 961 1168 1339 1480 1660 1891 2085 2085 2493 2585 3085 3585 3697

hxw [mm]220x500 250x660 313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445 2146x3557

hxw [mm]220x500 250x660 313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445 2146x3557

h1 x w1 [mm]0 0 250x660 380x613 440x821 440x1028 575x1199 695x1340 795x1520 795x1520 795x1520 740x1913 933x1945 933x2650 1199x3150 1520x3250

H*, Hs* - heights options details on page 54 - VS 15 lenght for optional fan (low pressure) Optional functions are presented on the bookmark (in the back cover).

Vmax - Parametres description on page 20

* VS 1015 AHUs are available as indoor units only. ** Optional functions are available for VS 21650 AHUs only. *** Optional function is available for VS 10650 AHUs (VS 1015 AHUs are equipped with the function of mixing defined just as a set of two air dampers). Inlet/Outlet configurations of E empty section are presented on page 53 and on the bookmark. Inlet/Outlet configurations of M mixing box are presented on page 53 and on the bookmark. Dimensions of optional functions are presented on page 53 and on the bookmark. Applying a priority air treatment function.

26

Supply-exhaust AHUs: cross-ow exchangerVentilationBase AHU VS 1015 sizes (suspended)*L1

A84 86

W

L

VS -

- R -P- T

VS 21650 sizesL

H Hs L

VS -

- R -P

VS10 15 21 30 40 55 75 100 120 150 180 230 300 400 500

Vmin Vmin Vmax* Vmax*L 3/h] [CFM] [m3/h] [CFM] [mm][m436 648 1167 1586 1958 2878 3805 4863 5815 7167 8640 10398 13491 18704 21817 257 381 687 933 1152 1694 2240 2862 3423 4218 5085 6120 7941 11009 12841 1655 2462 3089 4322 5661 8216 11379 13500 18079 22427 27230 33467 44767 60500 67600 974 1449 1818 2544 3332 4836 6697 7946 10641 13200 16027 19698 26349 35609 39788 1883 2248 2587 2587 2587 3318 3318 3684 3684 4050 4050 4050 5147 5147 5147

H*H2*Hs* L1(H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) W [mm][mm][mm][mm][mm]1883 2614 2587 2587 2587 3318 3318 3684 3684 4050 4050 4050 5147 5147 5147 5878 360 390 528 / 544 660 / 676 660 / 676 795 / 811 915 / 931 1015 / 1031 1052 / 1068 1153 / 1169 1357 1357 1656 1889 1889 2366 0 0 976 / 992 1240 / 1256 1240 / 1256 1510 / 1526 1750 / 1766 1950 / 1966 2024 / 2040 2226 / 2242 2714 2714 3312 3778 3778 4732 0 0 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 80 80 80 80 80 660 800 961 961 1168 1339 1480 1660 1891 2085 2085 2493 2585 3085 3585 3697

W2 [mm]1330 1610 0 0 0 0 0 0 0 0 0 0 0 0 0 0

hxw [mm]220x500 250x660 313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445

hxw [mm]220x500 250x660 313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445

h 1 x w1 [mm]0 0 250x660 380x613 440x821 440x1028 575x1199 695x1340 795x1520 795x1520 795x1520 740x1913 933x1945 933x2650 1199x3150

65028725 16907 97200 572105878 H*, H2*, Hs* - heights options details on page 54

2146x35572146x3557 1520x3250 Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover).

VS -

15

-

R

-

SE

/

PHCHcode of a base AHU

/

EFoptional functions behind a base AHU

the assembly method for VS 10-15 AHUs (suspended AHUs) COMPACT compact AHU

size of an AHU

access side optional functions R - right before a base L - left (the option AHU available for VS 21-650 units)

27

Supply-exhaust AHUs: cross-ow exchangerVentilation

A84 86

Base AHU

VS 21650 sizes

L

H Hs L

VS -

- R -P

VS21 30 40 55 75 100 120 150 180 230 300 400 500 650

Vmin [m3/h]1167 1586 1958 2878 3805 4863 5815 7167 8640 10398 13491 18704 21817 28725

Vmin [CFM]687 933 1152 1694 2240 2862 3423 4218 5085 6120 7941 11009 12841 16907

Vmax* [m3/h]3089 4322 5661 8216 11379 13500 18079 22427 27230 33467 44767 60500 67600 97200

Vmax* [CFM]1818 2544 3332 4836 6697 7946 10641 13200 16027 19698 26349 35609 39788 57210

L [mm]2587 2587 2587 3318 3318 3684 3684 4050 4050 4050 5147 5147 5147 5878

L1 [mm]2587 2587 2587 3318 3318 3684 3684 4050 4050 4050 5147 5147 5147 5878

Hs*H*H 2* (H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) W [mm][mm][mm][mm]528 / 544 660 / 676 660 / 676 795 / 811 915 / 931 1015 / 1031 1052 / 1068 1153 / 1169 1357 1357 1656 1889 1889 2366 976 / 992 1240 / 1256 1240 / 1256 1510 / 1526 1750 / 1766 1950 / 1966 2024 / 2040 2226 / 2242 2714 2714 3312 3778 3778 4732 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 80 80 80 80 80 961 961 1168 1339 1480 1660 1891 2085 2085 2493 2585 3085 3585 3697

hxw [mm]313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445 2146x3557

hxw [mm]313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445 2146x3557

h1 x w1 [mm]250x660 380x613 440x821 440x1028 575x1199 695x1340 795x1520 795x1520 795x1520 740x1913 933x1945 933x2650 1199x3150 1520x3250

H*, H2*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover). * VS 1015 AHUs are available as indoor units only. ** Optional functions are available for VS 21650 AHUs only. *** Optional function is available for VS 10650 AHUs (VS 1015 AHUs are equipped with the function of mixing defined just as a set of two air dampers). Inlet/Outlet configurations of E empty section are presented on page 53 and on the bookmark. Inlet/Outlet configurations of M mixing box are presented on page 53 and on the bookmark. Dimensions of optional functions are presented on page 53 and on the bookmark. Applying a priority air treatment function.

28

Supply-exhaust AHUs: cross-ow exchangerHeatingBase AHU VS 1015 sizes (suspended)*

A84 86

W

L

VS -

- R - PH - T

VS 21650 sizes

H Hs L

VS VminVmin Vmax* Vmax* [m3/h] [CFM] [m3/h] [CFM]436 648 1167 1586 1958 2878 3805 4863 5815 7167 8640 10398 13491 18704 21817 28725 257 381 687 933 1152 1694 2240 2862 3423 4218 5085 6120 7941 11009 12841 16907 1655 2462 3089 4322 5661 8216 11379 13500 18079 22427 27230 33467 44767 60500 67600 97200 974 1818 2544 3332 4836 6697 7946 10641 13200 16027 19698 26349 35609 39788 57210

- R - PHhxw [mm]660 800 961 961 1168 1339 1480 1660 1891 2085 2085 2493 2585 3085 3585 3697 1330 1610 0 0 0 0 0 0 0 0 0 0 0 0 0 0 220x500 250x660 313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445 2146x3557

VS10 15 21 30 40 55 75 100 120 150 180 230 300 400 500 650

L [mm]

H 2*Hs*H* L1(H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) WW2 [mm][mm][mm][mm][mm] [mm]360 390 528 / 544 660 / 676 660 / 676 795 / 811 915 / 931 1015 / 1031 1052 / 1068 1153 / 1169 1357 1357 1656 1889 1889 2366 0 0 976 / 992 1240 / 1256 1240 / 1256 1510 / 1526 1750 / 1766 1950 / 1966 2024 / 2040 2226 / 2242 2714 2714 3312 3778 3778 4732 0 0 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 80 80 80 80 80

hxw [mm]220x500 250x660 313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445 2146x3557

h1 x w1 [mm]0 0 250x660 380x613 440x821 440x1028 575x1199 695x1340 795x1520 795x1520 795x1520 740x1913 933x1945 933x2650 1199x3150 1520x3250

1883/2248* 1883 2953 2953 2953 3684 3684 4050 4050 4415 4415 4415 5513 5513 5513 6244 2587 2587 2587 3318 3318 3684 3684 4050 4050 4050 5147 5147 5147 5878

1449 2248/2614* 2248

1883/2248* - for water heater L= 1883 mm, for electric heater L= 2248 mm H*, H2*, Hs* - heights options details on page 54 Optional functions are presented on the bookmark (in the back cover).

Vmax - Parametres description on page 20

VS -

15

-

R

-

SE

/

PHCHcode of a base AHU

/

EFoptional functions behind a base AHU

the assembly method for VS 10-15 AHUs (suspended AHUs) COMPACT compact AHU

size of an AHU

access side optional functions R - right before a base L - left (the option AHU available for VS 21-650 units)

29

Supply-exhaust AHUs: cross-ow exchangerMixing box, HeatingBase AHU

VS 21650 sizes

H Hs L

VS -

- R - PMH

VS21 30 40 55 75 100 120 150 180 230 300 400 500 650

Vmin [m3/h]1167 1586 1958 2878 3805 4863 5815 7167 8640 10398 13491 18704 21817 28725

Vmin [CFM]687 933 1152 1694 2240 2862 3423 4218 5085 6120 7941 11009 12841 16907

Vmax* [m3/h]3089 4322 5661 8216 11379 13500 18079 22427 27230 33467 44767 60500 67600 97200

Vmax* [CFM]1818 2544 3332 4836 6697 7946 10641 13200 16027 19698 26349 35609 39788 57210

L [mm]3684 3684 3684 4415 4415 4781 4781 5513 5513 5513 6610 6610 6610 7341

L1 [mm]3318 3318 3318 4050 4050 4415 4415 5147 5147 5147 6244 6244 6244 6975

H 2*Hs*H* (H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) W [mm][mm][mm][mm]528 / 544 660 / 676 660 / 676 795 / 811 915 / 931 1015 / 1031 1052 / 1068 1153 / 1169 1357 1357 1656 1889 1889 2366 976 / 992 1240 / 1256 1240 / 1256 1510 / 1526 1750 / 1766 1950 / 1966 2024 / 2040 2226 / 2242 2714 2714 3312 3778 3778 4732 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 80 80 80 80 80 961 961 1168 1339 1480 1660 1891 2085 2085 2493 2585 3085 3585 3697

hxw [mm]313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445 2146x3557

hxw [mm]313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445 2146x3557

h1 x w1 [mm]250x660 380x613 440x821 440x1028 575x1199 695x1340 795x1520 795x1520 795x1520 740x1913 933x1945 933x2650 1199x3150 1520x3250

H*, H2*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover). * VS 1015 AHUs are available as indoor units only. ** Optional functions are available for VS 21650 AHUs only. *** Optional function is available for VS 10650 AHUs (VS 1015 AHUs are equipped with the function of mixing defined just as a set of two air dampers). Inlet/Outlet configurations of E empty section are presented on page 53 and on the bookmark. Inlet/Outlet configurations of M mixing box are presented on page 53 and on the bookmark. Dimensions of optional functions are presented on page 53 and on the bookmark. Applying a priority air treatment function.

30

Supply-exhaust AHUs: cross-ow exchangerHeatingBase AHU VS 1015 sizes (suspended)*

A84 86

W

L

VS -

- R - PH - T

VS 21650 sizes

H Hs L

VS Vmin Vmin Vmax* Vmax* [m3/h] [CFM] [m3/h] [CFM]436 648 1167 1586 1958 2878 3805 4863 5815 7167 8640 10398 13491 18704 21817 28725 257 381 687 933 1152 1694 2240 2862 3423 4218 5085 6120 7941 11009 12841 16907 1655 2462 3089 4322 5661 8216 11379 13500 18079 22427 27230 33467 44767 60500 67600 97200 974 1818 2544 3332 4836 6697 7946 10641 13200 16027 19698 26349 35609 39788 57210

- R - PHW2 [mm]660 800 961 961 1168 1339 1480 1660 1891 2085 2085 2493 2585 3085 3585 3697 1330 1610 0 0 0 0 0 0 0 0 0 0 0 0 0 0

VS10 15 21 30 40 55 75 100 120 150 180 230 300 400 500 650

L [mm]

H 2*Hs*H* L1(H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max))W [mm][mm][mm][mm][mm]360 390 528 / 544 660 / 676 660 / 676 795 / 811 915 / 931 1015 / 1031 1052 / 1068 1153 / 1169 1357 1357 1656 1889 1889 2366 0 0 976 / 992 1240 / 1256 1240 / 1256 1510 / 1526 1750 / 1766 1950 / 1966 2024 / 2040 2226 / 2242 2714 2714 3312 3778 3778 4732 0 0 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 80 80 80 80 80

hxw [mm]220x500 250x660 313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945

hxw [mm]220x500 250x660 313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945

h1 x w1 [mm]0 0 250x660 380x613 440x821 440x1028 575x1199 695x1340 795x1520 795x1520 795x1520 740x1913 933x1945 933x2650

1883/2248* 1883 2953 2953 2953 3684 3684 4050 4050 4415 4415 4415 5513 5513 5513 6243 2587 2587 2587 3318 3318 3684 3684 4050 4050 4050 5147 5147 5147 5878

1449 2248/2614* 2248

1137x1945 1137x1945 1137x2353 1137x2353 1436x2445 1436x2445 1669x2945 1669x2945

1669x3445 1669x3445 1199x3150 2146x3557 2146x3557 1520x3250 Vmax - Parametres description on page 20

1883/2248* - for water heater L= 1883 mm, for electric heater L= 2248 mm H*, H2*, Hs* - heights options details on page 54 Optional functions are presented on the bookmark (in the back cover).

VS -

15

-

R

-

SE

/

PHCHcode of a base AHU

/

EFoptional functions behind a base AHU

the assembly method for VS 10-15 AHUs (suspended AHUs) COMPACT compact AHU

size of an AHU

access side optional functions R - right before a base L - left (the option AHU available for VS 21-650 units)

31

Supply-exhaust AHUs: cross-ow exchangerCooling

A85 87

Base AHU

VS 21650 sizes

H Hs L

VS -

- R - PC

VS21 30 40 55 75 100 120 150 180 230 300 400 500 650

Vmin [m3/h]1167 1586 1958 2878 3805 4863 5815 7167 8640 10398 13491 18704 21817 28725

Vmin [CFM]687 933 1152 1694 2240 2862 3423 4218 5085 6120 7941 11009 12841 16907

Vmax* [m3/h]2200 3100 4100 6054 8150 10700 13300 16400 19900 24600 32900 44500 54000 71400

H2*Hs*H* Vmax*LL*L1 (H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) W [CFM] [mm] [mm] [mm][mm][mm][mm][mm]1295 1825 2413 3563 4797 6298 7828 9653 11713 14479 19364 26192 31783 42025 2953 2953 2953 3684 3684 4050 4050 4415 4415 4415 5513 5513 5513 6243 3318 3318 3318 4050 4050 4415 4415 4781 4415 4415 5513 5513 5513 6243 2587 2587 2587 3318 3318 3684 3684 4050 4050 4050 5147 5147 5147 5878 528 / 544 660 / 676 660 / 676 795 / 811 915 / 931 1015 / 1031 1052 / 1068 1153 / 1169 1357 1357 1656 1889 1889 2366 976 / 992 1240 / 1256 1240 / 1256 1510 / 1526 1750 / 1766 1950 / 1966 2024 / 2040 2226 / 2242 2714 2714 3312 3778 3778 4732 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 80 80 80 80 80 961 961 1168 1339 1480 1660 1891 2085 2085 2493 2585 3085 3585 3697

hxw [mm]313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445 2146x3557

hxw [mm]313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445 2146x3557

h1 x w1 [mm]250x660 380x613 440x821 440x1028 575x1199 695x1340 795x1520 795x1520 795x1520 740x1913 933x1945 933x2650 1199x3150 1520x3250

L* - Length of the supply section in conguration with drop eliminator installed behind the cooler H*, H2*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover). * VS 1015 AHUs are available as indoor units only. ** Optional functions are available for VS 21650 AHUs only. *** Optional function is available for VS 10650 AHUs (VS 1015 AHUs are equipped with the function of mixing defined just as a set of two air dampers). Inlet/Outlet configurations of E empty section are presented on page 53 and on the bookmark. Inlet/Outlet configurations of M mixing box are presented on page 53 and on the bookmark. Dimensions of optional functions are presented on page 53 and on the bookmark. Applying a priority air treatment function.

32

Supply-exhaust AHUs: cross-ow exchangerMixing box, coolingBase AHU

VS 21650 sizes

H Hs L

VS -

- R - PMC

VS21 30 40 55 75 100 120 150 180 230 300 400 500 650

H 2*Hs*H* VminVmin Vmax* Vmax*LL*L1 (H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) W [m3/h] [CFM] [m3/h] [CFM] [mm] [mm] [mm][mm][mm][mm][mm]1167 1586 1958 2878 3805 4863 5815 7167 8640 10398 13491 18704 21817 28725 687 933 1152 1694 2240 2862 3423 4218 5085 6120 7941 11009 12841 16907 2200 3100 4100 6054 8150 10700 13300 16400 19900 24600 32900 44500 54000 71400 1295 1825 2413 3563 4797 6298 7828 9653 11713 14479 19364 26192 31783 42025 3684 3684 3684 4415 4415 4781 4781 5513 5513 5513 6610 6610 6610 7340 4050 4050 4050 4781 4781 5147 5147 5878 5513 5513 6610 6610 6610 7340 3318 3318 3318 4050 4050 4415 4415 5147 5147 5147 6244 6244 6244 6976 528 / 544 660 / 676 660 / 676 795 / 811 915 / 931 1015 / 1031 1052 / 1068 1153 / 1169 1357 1357 1656 1889 1889 2366 976 / 992 1240 / 1256 1240 / 1256 1510 / 1526 1750 / 1766 1950 / 1966 2024 / 2040 2226 / 2242 2714 2714 3312 3778 3778 4732 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 80 80 80 80 80 961 961 1168 1339 1480 1660 1891 2085 2085 2493 2585 3085 3585 3697

hxw [mm]313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445 2146x3557

hxw [mm]313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445 2146x3557

h1 x w1 [mm]250x660 380x613 440x821 440x1028 575x1199 695x1340 795x1520 795x1520 795x1520 740x1913 933x1945 933x2650 1199x3150 1520x3250

L* - Length of the supply section in conguration with drop eliminator installed behind the cooler H*, H2*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover).

VS -

15

-

R

-

SE

/

PHCHcode of a base AHU

/

EFoptional functions behind a base AHU

the assembly method for VS 10-15 AHUs (suspended AHUs) COMPACT compact AHU

size of an AHU

access side optional functions R - right before a base L - left (the option AHU available for VS 21-650 units)

33

Supply-exhaust AHUs: cross-ow exchangerCooling

A85 87

Base AHU

VS 21650 sizes

H Hs L

VS -

- R - PC

VS21 30 40 55 75 100 120 150 180 230 300 400 500 650

Vmin [m3/h]1167 1586 1958 2878 3805 4863 5815 7167 8640 10398 13491 18704 21817 28725

Vmin [CFM]687 933 1152 1694 2240 2862 3423 4218 5085 6120 7941 11009 12841 16907

Vmax* [m3/h]2200 3100 4100 6054 8150 10700 13300 16400 19900 24600 32900 44500 54000 71400

H2*Hs*H* Vmax*LL*L1(H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) W [CFM] [mm] [mm] [mm][mm][mm][mm][mm]1295 1825 2413 3563 4797 6298 7828 9653 11713 14479 19364 26192 31783 42025 2953 2953 2953 3684 3684 4050 4050 4415 4415 4415 5513 5513 5513 6244 3318 3318 3318 4050 4050 4415 4415 4781 4415 4415 5513 5513 5513 6244 2587 2587 2587 3318 3318 3684 3684 4050 4050 4050 5147 5147 5147 5879 528 / 544 660 / 676 660 / 676 795 / 811 915 / 931 1015 / 1031 1052 / 1068 1153 / 1169 1357 1357 1656 1889 1889 2366 976 / 992 1240 / 1256 1240 / 1256 1510 / 1526 1750 / 1766 1950 / 1966 2024 / 2040 2226 / 2242 2714 2714 3312 3778 3778 4732 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 80 80 80 80 80 961 961 1168 1339 1480 1660 1891 2085 2085 2493 2585 3085 3585 3697

hxw [mm]313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445 2146x3557

hxw [mm]313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445 2146x3557

h1 x w1 [mm]250x660 380x613 440x821 440x1028 575x1199 695x1340 795x1520 795x1520 795x1520 740x1913 933x1945 933x2650 1199x3150 1520x3250

L* - Length of the supply section in conguration with drop eliminator installed behind the cooler H*, H2*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover). * VS 1015 AHUs are available as indoor units only. ** Optional functions are available for VS 21650 AHUs only. *** Optional function is available for VS 10650 AHUs (VS 1015 AHUs are equipped with the function of mixing defined just as a set of two air dampers). Inlet/Outlet configurations of E empty section are presented on page 53 and on the bookmark. Inlet/Outlet configurations of M mixing box are presented on page 53 and on the bookmark. Dimensions of optional functions are presented on page 53 and on the bookmark. Applying a priority air treatment function. Change of interrelated settings of a heater and a cooler results in changing the code of a specific AHU.

34

Supply-exhaust AHUs: cross-ow exchangerHeating, CoolingBase AHU VS 1015 sizes (suspended)*

A85 87

W

L

VS -

- R - PHC - T

VS 21650 sizes

H Hs L L

H Hs

VS Vmin Vmin Vmax* Vmax* [m3/h] [CFM] [m3/h] [CFM]436 648 1167 1586 1958 2878 3805 4863 5815 7167 8640 10398 13491 18704 21817 28725 257 381 687 933 1152 1694 2240 2862 3423 4218 5085 6120 7941 11009 12841 16907 1160 1740 2200 3100 4100 6054 8150 10700 13300 16400 19900 24600 32900 44500 54000 71400 683 1024 1295 1825 2413 3563 4797 6298 7828 9653 11713 14479 19364 26192 31783 42025

- R - PHCL [mm]2248/2614* 2980 3318 3318 3318 4050 4050 4415 4415 4781 4781 4781 5878 5878 5878 6610

VS -

- R - PCHhxw [mm]220x500 250x660 313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945

VS10 15 21 30 40 55 75 100 120 150 180 230 300 400 500 650

H 2*Hs*H* L*L1 (H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) WW2 [mm] [mm][mm][mm][mm][mm] [mm]0 0 3684 3684 3684 4415 4415 4781 4781 5147 4781 4781 5878 5878 5878 6610 1883 2614 2587 2587 2587 3318 3318 3684 3684 4050 4050 4050 5147 5147 5147 5879 360 390 528 / 544 660 / 676 660 / 676 795 / 811 915 / 931 1015 / 1031 1052 / 1068 1153 / 1169 1357 1357 1656 1889 1889 2366 0 0 976 / 992 1240 / 1256 1240 / 1256 1510 / 1526 1750 / 1766 1950 / 1966 2024 / 2040 2226 / 2242 2714 2714 3312 3778 3778 4732 0 0 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 80 80 80 80 80 660 800 961 961 1168 1339 1480 1660 1891 2085 2085 2493 2585 3085 3585 3697 1330 1610 0 0 0 0 0 0 0 0 0 0 0 0 0 0

hxw [mm]220x500 250x660 313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945

h1 x w1 [mm]0 0 250x660 380x613 440x821 440x1028 575x1199 695x1340 795x1520 795x1520 795x1520 740x1913 933x1945 933x2650

1137x1945 1137x1945 1137x2353 1137x2353 1436x2445 1436x2445 1669x2945 1669x2945

1669x3445 1669x3445 1199x3150 2146x3557 2146x3557 1520x3250

L* - Length of the supply section in conguration with drop eliminator installed behind the cooler 2248/2614* - for water heater L= 2248 mm, for electric heater L= 2614 mm H*, H2*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20 Optional functions are presented on the bookmark (in the back cover).

VS -

15

-

R

-

SE

/

PHCHcode of a base AHU

/

EFoptional functions behind a base AHU

the assembly method for VS 10-15 AHUs (suspended AHUs) COMPACT compact AHU

size of an AHU

access side optional functions R - right before a base L - left (the option AHU available for VS 21-650 units)

35

Supply-exhaust AHUs: cross-ow exchangerMixing box, Heating, CoolingBase AHU VS 21650 sizes

H Hs L

VS VS 21650 sizes

- R - PMHC - T

H Hs L

VS Vmin [m3/h]1167 1586 1958 2878 3805 4863 5815 7167 8640 10398 13491 18704 21817 28725

- R - PMCH - Thxw [mm]80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 80 80 80 80 80 961 961 1168 1339 1480 1660 1891 2085 2085 2493 2585 3085 3585 3697 313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445 2146x3557

VS21 30 40 55 75 100 120 150 180 230 300 400 500 650

Vmin [CFM]687 933 1152 1694 2240 2862 3423 4218 5085 6120 7941 11009 12841 16907

Vmax* [m3/h]2200 3100 4100 6054 8150 10700 13300 16400 19900 24600 32900 44500 54000 71400

H2*Hs*H* Vmax*LL*L1 (H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) W [CFM] [mm] [mm] [mm][mm][mm][mm][mm]1295 1825 2413 3563 4797 6298 7828 9653 11713 14479 19364 26192 31783 42025 4050 4050 4050 4781 4781 5147 5147 5878 5878 5878 6975 6975 6975 7707 4415 4415 4415 5147 5147 5513 5513 6244 5878 5878 6975 6975 6975 7707 3318 3318 3318 4050 4050 4415 4415 5147 5147 5147 6244 6244 6244 6976 528 / 544 660 / 676 660 / 676 795 / 811 915 / 931 1015 / 1031 1052 / 1068 1153 / 1169 1357 1357 1656 1889 1889 2366 976 / 992 1240 / 1256 1240 / 1256 1510 / 1526 1750 / 1766 1950 / 1966 2024 / 2040 2226 / 2242 2714 2714 3312 3778 3778 4732

hxw [mm]313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445 2146x3557

h1 x w1 [mm]250x660 380x613 440x821 440x1028 575x1199 695x1340 795x1520 795x1520 795x1520 740x1913 933x1945 933x2650 1199x3150 1520x3250

L* - Length of the supply section in conguration with drop eliminator installed behind the cooler H*, H2*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover). * VS 1015 AHUs are available as indoor units only. ** Optional functions are available for VS 21650 AHUs only. *** Optional function is available for VS 10650 AHUs (VS 1015 AHUs are equipped with the function of mixing defined just as a set of two air dampers). Inlet/Outlet configurations of E empty section are presented on page 53 and on the bookmark. Inlet/Outlet configurations of M mixing box are presented on page 53 and on the bookmark. Dimensions of optional functions are presented on page 53 and on the bookmark. Applying a priority air treatment function. Change of interrelated settings of a heater and a cooler results in changing the code of a specific AHU.

36

Supply-exhaust AHUs: cross-ow exchangerHeating, CoolingBase AHU VS 1015 sizes (suspended)*

A85 87

W

L

VS -

- R - PHC - T

VS 21650 sizes

H Hs L L

H Hs

VS -

- R - PHC

VS hxw [mm]0 0 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 80 80 80 80 80 660 800 961 961 1168 1339 1480 1660 1891 2085 2085 2493 2585 3085 3585 3697 1330 1610 0 0 0 0 0 0 0 0 0 0 0 0 0 0 220x500 250x660 313x821 440x821

- R - PCHhxw [mm]220x500 250x660 313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945

VS10 15 21 30 40 55 75 100 120 150 180 230 300 400 500 650

H 2*Hs*H* Vmin Vmin Vmax* Vmax*LL*L1 (H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) WW2 [m3/h] [CFM] [m3/h] [CFM] [mm] [mm] [mm][mm][mm][mm][mm] [mm]436 648 1167 1586 1958 2878 3805 4863 5815 7167 8640 10398 13491 18704 21817 28725 257 381 687 933 1152 1694 2240 2862 3423 4218 5085 6120 7941 11009 12841 16907 1160 1740 2200 3100 4100 6054 8150 10700 13300 16400 19900 24600 32900 44500 54000 71400 683 1024 1295 1825 2413 3563 4797 6298 7828 9653 11713 14479 19364 26192 31783 42025 2248 2980 3318 3318 3318 4050 4050 4415 4415 4781 4781 4781 5878 5878 5878 6610 0 0 3684 3684 3684 4415 4415 4781 4781 5147 4781 4781 5878 5878 5878 6610 2248 2248 2587 2587 2587 3318 3318 3684 3684 4050 4050 4050 5147 5147 5147 5879 360 390 528 / 544 660 / 676 660 / 676 795 / 811 915 / 931 1015 / 1031 1052 / 1068 1153 / 1169 1357 1357 1656 1889 1889 2366 0 0 976 / 992 1240 / 1256 1240 / 1256 1510 / 1526 1750 / 1766 1950 / 1966 2024 / 2040 2226 / 2242 2714 2714 3312 3778 3778 4732

h1 x w1 [mm]0 0 250x660 380x613 440x821 440x1028 575x1199 695x1340 795x1520 795x1520 795x1520 740x1913 933x1945 933x2650 1199x3150 1520x3250

440x1028 575x1199 695x1340 795x1520 832x1751 933x1945

1137x1945 1137x1945 1137x2353 1137x2353 1436x2445 1436x2445 1669x2945 1669x2945 1669x3445 1669x3445 2146x3557 2146x3557

L* - Length of the supply section in conguration with drop eliminator installed behind the cooler H*, H2*, Hs* - heights options details on page 54 Optional functions are presented on the bookmark (in the back cover).

Vmax - Parametres description on page 20

VS -

15

-

R

-

SE

/

PHCHcode of a base AHU

/

EFoptional functions behind a base AHU

the assembly method for VS 10-15 AHUs (suspended AHUs) COMPACT compact AHU

size of an AHU

access side optional functions R - right before a base L - left (the option AHU available for VS 21-650 units)

37

Supply-exhaust AHUs: cross-ow exchangerHeating, Cooling, HeatingBase AHU

VS 21650 sizes

H Hs L

VS -

- R - PHCH

VS21 30 40 55 75 100 120 150 180 230 300 400 500 650

Vmin [m3/h]1167 1586 1958 2878 3805 4863 5815 7167 8640 10398 13491 18704 21817 28725

Vmin [CFM]687 933 1152 1694 2240 2862 3423 4218 5085 6120 7941 11009 12841 16907

Vmax* [m3/h]2200 3100 4100 6054 8150 10700 13300 16400 19900 24600 32900 44500 54000 71400

H2*Hs*H* Vmax*LL*L1 (H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) W [CFM] [mm] [mm] [mm][mm][mm][mm][mm]1295 1825 2413 3563 4797 6298 7828 9653 11713 14479 19364 26192 31783 42025 3684 3684 3684 4415 4415 4781 4781 5147 5147 5147 6244 6244 6244 6976 4050 4050 4050 4781 4781 5147 5147 5513 5147 5147 6244 6244 6244 6976 2587 2587 2587 3318 3318 3684 3684 4050 4050 4050 5147 5147 5147 5879 528 / 544 660 / 676 660 / 676 795 / 811 915 / 931 1015 / 1031 1052 / 1068 1153 / 1169 1357 1357 1656 1889 1889 2366 976 / 992 1240 / 1256 1240 / 1256 1510 / 1526 1750 / 1766 1950 / 1966 2024 / 2040 2226 / 2242 2714 2714 3312 3778 3778 4732 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 80 80 80 80 80 961 961 1168 1339 1480 1660 1891 2085 2085 2493 2585 3085 3585 3697

hxw [mm]313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445 2146x3557

hxw [mm]313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445 2146x3557

h1 x w1 [mm]250x660 380x613 440x821 440x1028 575x1199 695x1340 795x1520 795x1520 795x1520 740x1913 933x1945 933x2650 1199x3150 1520x3250

L* - Length of the supply section in conguration with drop eliminator installed behind the cooler H*, H2*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover). * VS 1015 AHUs are available as indoor units only. ** Optional functions are available for VS 21650 AHUs only. *** Optional function is available for VS 10650 AHUs (VS 1015 AHUs are equipped with the function of mixing defined just as a set of two air dampers). Inlet/Outlet configurations of E empty section are presented on page 53 and on the bookmark. Inlet/Outlet configurations of M mixing box are presented on page 53 and on the bookmark. Dimensions of optional functions are presented on page 53 and on the bookmark. Applying a priority air treatment function.

38

Supply-exhaust AHUs: cross-ow exchangerMixing box, Heating, Cooling, HeatingBase AHU

A

VS 21650 sizes

H Hs L

VS -

- R - PMHCH

VS21 30 40 55 75 100 120 150 180 230 300 400 500 650

Vmin [m3/h]1167 1586 1958 2878 3805 4863 5815 7167 8640 10398 13491 18704 21817 28725

Vmin [CFM]687 933 1152 1694 2240 2862 3423 4218 5085 6120 7941 11009 12841 16907

Vmax* [m3/h]2200 3100 4100 6054 8150 10700 13300 16400 19900 24600 32900 44500 54000 71400

H 2*Hs*H* Vmax*LL*L1 (H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) W [CFM] [mm] [mm] [mm][mm][mm][mm][mm]1295 1825 2413 3563 4797 6298 7828 9653 11713 14479 19364 26192 31783 42025 4415 4415 4415 5147 5147 5513 5513 6244 6244 6244 7341 7341 7341 8073 4781 4781 4781 5513 5513 5878 5878 6610 6244 6244 7341 7341 7341 8073 3318 3318 3318 4050 4050 4415 4415 5147 5147 5147 6244 6244 6244 6976 528 / 544 660 / 676 660 / 676 795 / 811 915 / 931 1015 / 1031 1052 / 1068 1153 / 1169 1357 1357 1656 1889 1889 2366 976 / 992 1240 / 1256 1240 / 1256 1510 / 1526 1750 / 1766 1950 / 1966 2024 / 2040 2226 / 2242 2714 2714 3312 3778 3778 4732 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 80 80 80 80 80 961 961 1168 1339 1480 1660 1891 2085 2085 2493 2585 3085 3585 3697

hxw [mm]313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445 2146x3557

hxw [mm]313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445 2146x3557

h 1 x w1 [mm]250x660 380x613 440x821 440x1028 575x1199 695x1340 795x1520 795x1520 795x1520 740x1913 933x1945 933x2650 1199x3150 1520x3250

L* - Length of the supply section in conguration with drop eliminator installed behind the cooler H*, H2*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover).

VS -

15

-

R

-

SE

/

PHCHcode of a base AHU

/

EFoptional functions behind a base AHU

the assembly method for VS 10-15 AHUs (suspended AHUs) COMPACT compact AHU

size of an AHU

access side optional functions R - right before a base L - left (the option AHU available for VS 21-650 units)

39

Supply-exhaust AHUs: cross-ow exchangerHeating, Cooling, HeatingBase AHU

VS 21650 sizes

H Hs L

VS -

- R - PHCH

VS21 30 40 55 75 100 120 150 180 230 300 400 500 650

Vmin [m3/h]1167 1586 1958 2878 3805 4863 5815 7167 8640 10398 13491 18704 21817 28725

Vmin [CFM]687 933 1152 1694 2240 2862 3423 4218 5085 6120 7941 11009 12841 16907

Vmax* [m3/h]2200 3100 4100 6054 8150 10700 13300 16400 19900 24600 32900 44500 54000 71400

H2*Hs*H* Vmax*LL*L1 (H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) W [CFM] [mm] [mm] [mm][mm][mm][mm][mm]1295 1825 2413 3563 4797 6298 7828 9653 11713 14479 19364 26192 31783 42025 3684 3684 3684 4415 4415 4781 4781 5147 5147 5147 6244 6244 6244 6976 4050 4050 4050 4781 4781 5147 5147 5513 5147 5147 6244 6244 6244 6976 2587 2587 2587 3318 3318 3684 3684 4050 4050 4050 5147 5147 5147 5879 528 / 544 660 / 676 660 / 676 795 / 811 915 / 931 1015 / 1031 1052 / 1068 1153 / 1169 1357 1357 1656 1889 1889 2366 976 / 992 1240 / 1256 1240 / 1256 1510 / 1526 1750 / 1766 1950 / 1966 2024 / 2040 2226 / 2242 2714 2714 3312 3778 3778 4732 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 80 80 80 80 80 961 961 1168 1339 1480 1660 1891 2085 2085 2493 2585 3085 3585 3697

hxw [mm]313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445 2146x3557

hxw [mm]313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445 2146x3557

h1 x w1 [mm]250x660 380x613 440x821 440x1028 575x1199 695x1340 795x1520 795x1520 795x1520 740x1913 933x1945 933x2650 1199x3150 1520x3250

L* - Length of the supply section in conguration with drop eliminator installed behind the cooler H*, H2*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover). * VS 1015 AHUs are available as indoor units only. ** Optional functions are available for VS 21650 AHUs only. *** Optional function is available for VS 10650 AHUs (VS 1015 AHUs are equipped with the function of mixing defined just as a set of two air dampers). Inlet/Outlet configurations of E empty section are presented on page 53 and on the bookmark. Inlet/Outlet configurations of M mixing box are presented on page 53 and on the bookmark. Dimensions of optional functions are presented on page 53 and on the bookmark. Applying a priority air treatment function.

40

Supply-exhaust AHUs: rotary exchangerVentilationBase AHU

A89

VS 21650 sizesK

H Hs L

VS -

- R -R

VS21 30 40 55 75 100 120 150 180 230 300 400 500 650

Vmin [m3/h]1193 1586 2099 2878 3805 4863 5985 7415 8640 10640 13491 18704 22399 28725

Vmin [CFM]702 933 1235 1694 2240 2862 3523 4364 5085 6262 7941 11009 13184 16907

Vmax* [m3/h]3550 4530 6700 9720 12519 13550 20748 25400 25707 36886 40081 55594 77648 83241

H2*Hs*H* Vmax*LL1K(H (min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) W [CFM] [mm] [mm] [mm][mm][mm][mm][mm]2089 2666 3943 5721 7368 7975 12212 14950 15131 21710 23591 32722 45702 48994 2221 2221 2221 2587 2587 2953 2953 2953 2953 2953 3318 3318 3318 3319 2221 2221 2221 2587 2587 2953 2953 2953 2953 2953 3318 3318 3318 3319 0 0 0 366 366 731 731 731 731 731 1097 1097 1097 1097 528 / 544 660 / 676 660 / 676 795 / 811 915 / 931 1015 / 1031 1052 / 1068 1153 / 1169 1357 1357 1656 1889 1889 2366 976 / 992 1240 / 1256 1240 / 1256 1510 / 1526 1750 / 1766 1950 / 1966 2024 / 2040 2226 / 2242 2714 2714 3312 3778 3778 4732 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 80 80 80 80 80 961 961 1168 1339 1480 1660 1891 2085 2085 2493 2585 3085 3585 3697

hxw [mm]313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945

hxw [mm]313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945

h1 x w1 [mm]250x660 380x613 440x821 440x1028 575x1199 695x1340 795x1520 795x1520 795x1520 740x1913 933x1945 933x2650

1137x1945 1137x1945 1137x2353 1137x2353 1436x2445 1436x2445 1669x2945 1669x2945

1669x3445 1669x3445 1199x3150 2146x3557 2146x3557 1520x3250

L* - Length of the supply section in conguration with drop eliminator installed behind the cooler K* - Distance with the sets with drop eliminator H*, H2*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover).

VS -

15

-

R

-

SE

/

PHCHcode of a base AHU

/

EFoptional functions behind a base AHU

the assembly method for VS 10-15 AHUs (suspended AHUs) COMPACT compact AHU

size of an AHU

access side optional functions R - right before a base L - left (the option AHU available for VS 21-650 units)

41

Supply-exhaust AHUs: rotary exchangerHeating

A89

Base AHU

VS 21650 sizesK

H Hs L

VS -

- R - RH

VS21 30 40 55 75 100 120 150 180 230 300 400 500 650

VminVmin [m3/h] [CFM]1193 1586 2099 2878 3805 4863 5985 7415 8640 10640 13491 18704 22399 28725 702 933 1235 1694 2240 2862 3523 4364 5085 6262 7941 11009 13184 16907

Vmax* [m3/h]3080 4322 5661 8216 11379 13550 18079 22420 25707 33460 40081 55594 74350 83241

H2*H s*H* Vmax*LL1K(H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) W [CFM] [mm] [mm] [mm][mm][mm][mm][mm]1813 2544 3332 4836 6697 7975 10641 13196 15131 19694 23591 32722 43761 48994 2953 2953 2953 3318 3318 3684 3684 3684 3684 3684 4050 4050 4050 4050 2221 2221 2221 2587 2587 2953 2953 2953 2953 2953 3318 3318 3318 3319 731 731 731 1097 1097 1463 1463 1463 1463 1463 1829 1829 1829 1829 528 / 544 660 / 676 660 / 676 795 / 811 915 / 931 1015 / 1031 1052 / 1068 1153 / 1169 1357 1357 1656 1889 1889 2366 976 / 992 1240 / 1256 1240 / 1256 1510 / 1526 1750 / 1766 1950 / 1966 2024 / 2040 2226 / 2242 2714 2714 3312 3778 3778 4732 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 80 80 80 80 80 961 961 1168 1339 1480 1660 1891 2085 2085 2493 2585 3085 3585 3697

hxw [mm]313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445 2146x3557

hxw [mm]313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445 2146x3557

h1 x w1 [mm]250x660 380x613 440x821 440x1028 575x1199 695x1340 795x1520 795x1520 795x1520 740x1913 933x1945 933x2650 1199x3150 1520x3250

H*, H2*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover). ** Optional functions are available for VS 21650 AHUs only. *** Optional function is available for VS 10650 AHUs (VS 1015 AHUs are equipped with the function of mixing defined just as a set of two air dampers).. Inlet/Outlet configurations of E empty section are presented on page 53 and on the bookmark. Inlet/Outlet configurations of M mixing box are presented on page 53 and on the bookmark. Dimensions of optional functions are presented on page 53 and on the bookmark. Applying a priority air treatment function.

42

Supply-exhaust AHUs: rotary exchangerMixing box, HeatingBase AHU

VS 21650 sizesK

H Hs L

VS -

- R - RMH

VS21 30 40 55 75 100 120 150 180 230 300 400 500 650

VminVmin Vmax* Vmax*L [m3/h] [CFM] [m3/h] [CFM] [mm]1193 1586 2099 2878 3805 4863 5985 7415 8640 10640 13491 18704 22399 28725 702 933 1235 1694 2240 2862 3523 4364 5085 6262 7941 11009 13184 16907 3080 4322 5661 8216 11379 13550 18079 22420 25707 33460 40081 55594 74350 83241 1813 2544 3332 4836 6697 7975 10641 13196 15131 19694 23591 32722 43761 48994 3684 3684 3684 4050 4050 4415 4415 4781 4781 4781 5147 5147 5147 5147

L1 [mm]2587 2587 2587 2953 2953 3318 3318 3684 3684 3684 4050 4050 4050 4050

H 2*Hs*H* K(H (min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) W [mm][mm][mm][mm][mm]366 366 366 366 366 366 366 366 366 366 366 366 366 366 528 / 544 660 / 676 660 / 676 795 / 811 915 / 931 1015 / 1031 1052 / 1068 1153 / 1169 1357 1357 1656 1889 1889 2366 976 / 992 1240 / 1256 1240 / 1256 1510 / 1526 1750 / 1766 1950 / 1966 2024 / 2040 2226 / 2242 2714 2714 3312 3778 3778 4732 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 80 80 80 80 80 961 961 1168 1339 1480 1660 1891 2085 2085 2493 2585 3085 3585 3697

hxw [mm]313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445 2146x3557

hxw [mm]313x821 440x821 440x1028 575x1199 695x1340 795x1520 832x1751 933x1945 1137x1945 1137x2353 1436x2445 1669x2945 1669x3445 2146x3557

h1 x w1 [mm]250x660 380x613 440x821 440x1028 575x1199 695x1340 795x1520 795x1520 795x1520 740x1913 933x1945 933x2650 1199x3150 1520x3250

H*, H2*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover).

VS -

15

-

R

-

SE

/

PHCHcode of a base AHU

/

EFoptional functions behind a base AHU

the assembly method for VS 10-15 AHUs (suspended AHUs) COMPACT compact AHU

size of an AHU

access side optional functions R - right before a base L - left (the option AHU available for VS 21-650 units)

43

Supply-exhaust AHUs: rotary exchangerCooling

A90

Base AHU

VS 21650 sizesK

H Hs L

VS -

- R - RC

VS21 30 40 55 75 100 120 150 180 230 300 400 500 650

H 2*Hs*H* Vmin Vmin Vmax* Vmax*LL*L1KK* (H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) W [m3/h] [CFM] [m3/h] [CFM] [mm] [mm] [mm] [mm] [mm][mm][mm][mm][mm]1193 1586 2099 2878 3805 4863 5985 7415 8640 10640 13491 702 933 1235 1694 2240 2862 3523 4364 5085 6262 7941 2200 3100 4100 6054 8150 10700 13300 16400 1295 1825 2413 3563 4797 6298 7828 9653 2953 2953 2953 3318 3318 3684 3684 3684 3684 3684 4050 4050 4050 4050 3318 3318 3318 3684 3684 4050 4050 4050 3684 3684 4050 4050 4050 4050 2221 2221 2221 2587 2587 2953 2953 2953 2953 2953 3318 3318 3318 3319 731 731 731 1097 1097 1463 1463 1463 1463 1463 1829 1829 1829 1829 1097 1097 1097 1463 1463 1829 1829 1829 0 0 0 0 0 0 528 / 544 660 / 676 660 / 676 795 / 811 915 / 931 1015 / 1031 1052 / 1068 1153 / 1169 1357 1357 1656 1889 1889 2366 976 / 992 1240 / 1256 1240 / 1256 1510 / 1526 1750 / 1766 1950 / 1966 2024 / 2040 2226 / 2242 2714 2714 3312 3778 3778 4732 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 / 96 80 80 80 80 80 80 961 961

hxw [mm]313x821 440x821

hxw [mm]313x821 440x821

h1 x w1 [mm]250x660 380x613 440x821

1168 440x1028 440x1028

1339 575x1199 575x1199 440x1028 1480 695x1340 695x1340 575x1199 1660 795x1520 795x1520 695x1340 1891 832x1751 832x1751 795x1520 2085 933x1945 933x1945 795x1520 2085 1137x1945 1137x1945 795x1520 2493 1137x2353 1137x2353 740x1913 2585 1436x2445 1436x2445 933x1945 3085 1669x2945 1669x2945 933x2650 3585 1669x3445 1669x3445 1199x3150 3697 2146x3557 2146x3557 1520x3250 Vmax - Parametres description on page 20

19900 11713 24600 14479 32900 19364

18704 11009 44500 26192 22399 13184 540