COVER SHEET
COMED DISTRIBUTIONCONDUIT INSTALLATION
WO# 16706946155 N. CARPENTER ST. - PERM (PART 1)
W. RANDOLPH ST. FROMN. CARPENTER ST. TO N. CARPENTER ST.
CHICAGO, ILLINOIS
SHEET: OF
D
21 3 4 5 6 7
21 3 4 5 6 7
E
D
C
B
A
E
C
B
A
123 N. WACKER DRIVE SUITE 2000CHICAGO, ILLINOIS 60606TEL. (312) 857-1006 FAX. (312) 857-1056
REVISIONSDESCRIPTION BYDATEREV.
12345678
APPROVED BY:CREATED BY:
PROJ. ENGINEER:SCALE: DATE CREATED:
CHECKED BY:
07/01/2108/03/2110/12/21
FOR OUC REVIEWFOR OUC REVIEW
ISSUED FOR CONSTRUCTION
BAHBAHABM
BAH
HJM
HJMACS
12/08/2020AS SHOWN
COMED PROPOSEDCONDUIT INSTALLATION155 N. CARPENTER - PERM (PART 1)CHICAGO, ILLINOISCOMED WO#: 16706946DBS PROJECT#: 603.074EFP- 110905
THIS AND THE FOLLOWING SHEETS ARE NOT TRANSFERABLEAND ARE ONLY CONSIDERED AN OFFICIAL CONSTRUCTIONDRAWING WHEN ACCOMPANIED BY A SIGNED ENGINEERING SEAL.
THIS MATERIAL IS THE PROPERTY OF COMED AND CONTAINS CONFIDENTIALINFORMATION WHICH MUST NOT BE DUPLICATED, USED, OR DISCLOSEDOTHER THAN AS EXPRESSLY AUTHORIZED BY COMED.
An Exelon Company
DB STERLIN CONSULTANTS, INC.
14
R
Before you digin Chicago call
10-12-2021HAN
NAH J._
MARTENS062-059491
REGISTEREDPROFESSIONAL
ENGINEEROF
ST
A
T E O F I L L I N
OI S
SIGNATURE
DATE
PROFESSIONAL ENGINEEREXPIRES 11-30-2021
EFP-110905
TITLE SHEET, PROJECT LOCATION MAP
GENERAL NOTESPLAN & PROFILERESTORATION
CONSTRUCTION DETAILS 1COMED DETAILS
TRAFFIC CONTROL - STAGE 1
12345678
SHEET INDEX
9
LEGEND
TRENCH SHORING DETAILS
10
CONSTRUCTION DETAILS 2
11121314
TRAFFIC CONTROL - STAGE 2TRAFFIC CONTROL - STAGE 3TRAFFIC CONTROL - STAGE 4TRAFFIC CONTROL - STAGE 5
2
LEGEND
SHEET: OF
D
21 3 4 5 6 7
21 3 4 5 6 7
E
D
C
B
A
E
C
B
A
123 N. WACKER DRIVE SUITE 2000CHICAGO, ILLINOIS 60606TEL. (312) 857-1006 FAX. (312) 857-1056
REVISIONSDESCRIPTION BYDATEREV.
12345678
APPROVED BY:CREATED BY:
PROJ. ENGINEER:SCALE: DATE CREATED:
CHECKED BY:
07/01/2108/03/2110/12/21
FOR OUC REVIEWFOR OUC REVIEW
ISSUED FOR CONSTRUCTION
BAHBAHABM
BAH
HJM
HJMACS
12/08/2020AS SHOWN
COMED PROPOSEDCONDUIT INSTALLATION155 N. CARPENTER - PERM (PART 1)CHICAGO, ILLINOISCOMED WO#: 16706946DBS PROJECT#: 603.074EFP- 110905
THIS AND THE FOLLOWING SHEETS ARE NOT TRANSFERABLEAND ARE ONLY CONSIDERED AN OFFICIAL CONSTRUCTIONDRAWING WHEN ACCOMPANIED BY A SIGNED ENGINEERING SEAL.
THIS MATERIAL IS THE PROPERTY OF COMED AND CONTAINS CONFIDENTIALINFORMATION WHICH MUST NOT BE DUPLICATED, USED, OR DISCLOSEDOTHER THAN AS EXPRESSLY AUTHORIZED BY COMED.
An Exelon Company
DB STERLIN CONSULTANTS, INC.
14
EXISTING GAS MANHOLE
EXISTING GAS CAP
EXISTING PEDESTAL
EXISTING GARBAGE CAN
EXISTING GAS REDUCER
EXISTING ADA RAMP
EXISTING BENCH
EXISTING BUS SHELTER
EXISTING RIGHT OF WAY
EXISTING EASEMENT LINE
EXISTING AT&T
EXISTING DEO / ELECTRIC MANHOLE
EXISTING COMED MANHOLE
EXISTING SEWER MANHOLE
EXISTING WATER MANHOLE
EXISTING WATER VALVE
EXISTING WATER METER
EXISTING WATER HYDRANT
EXISTING WATER CAP
EXISTING WATER REDUCER
EXISTING MWRD MANHOLE
EXISTING CATCH BASIN
EXISTING CATCH BASIN
EXISTING GAS VALVE
EXISTING GAS METER
EXISTING CONTROL STREET LIGHT BOX
EXISTING CONTROL TRAFFIC LIGHT BOX
EXISTING STREET LIGHT HANDHOLE
EXISTING TRAFFIC LIGHT HANDHOLE
EXISTING STREET LIGHT POLE
EXISTING TRAFFIC LIGHT POLE
EXISTING DEO HANDHOLE
EXISTING WATER SHUT OFF (SMALL)
EXISTING FIRE-CISTERN MANHOLE EXISTING CTA MANHOLE
CTA TRACKSPOSSIBLE BURIED
EXISTING CROWN CASTLE
EXISTING CABLE TV MANHOLE
EXISTING COMCAST MANHOLE
EXISTING COMMUNICATIONS MANHOLE
EXISTING ZAYO GROUP MANHOLE
EXISTING SIDERA MANHOLE
EXISTING QWEST MANHOLE
EXISTING VERIZON MANHOLE
EXISTING RCN MANHOLE
EXISTING MCI/VERIZON MANHOLE
EXISTING LOOKING GLASS MANHOLE
EXISTING WOW MANHOLE
EXISTING SUNESYS MANHOLE
EXISTING XO MANHOLE
EXISTING LEVEL 3 MANHOLE
EXISTING SPRINT/NEXTEL MANHOLE
EXISTING YIPES MANHOLE
EXISTING NEXTG MANHOLE
EXISTING McLEOD MANHOLE
EXISTING JOINT BUILD MANHOLE
AT
CC
TV
CM
CO
J
L3
LG
MCI
ML
NX
QW
RN
SD
SP
SU
VZ
WO
XO
Y
ZY
EXISTING AT&T MANHOLE
EXISTING CROWN CASTLE MANHOLE
EXISTING CABLE TV
EXISTING COMMUNICATIONS
EXISTING LEVEL 3
EXISTING JOINT BUILD
EXISTING COMCAST
EXISTING LOOKING GLASS
EXISTING MCI/VERIZON
EXISTING McLEOD
EXISTING NEXTG
EXISTING QWEST MANHOLE
EXISTING RCN MANHOLE
EXISTING SIDERA MANHOLE
EXISTING SPRINT/NEXTEL MANHOLE
EXISTING SUNESYS MANHOLE
EXISTING VERIZON MANHOLE
EXISTING WOW MANHOLE
EXISTING XO MANHOLE
EXISTING YIPES MANHOLE
EXISTING ZAYO GROUP MANHOLE
EXISTING TREE
EXISTING BUSH / SHRUB
EXISTING UNKNOWN MANHOLE
EXISTING UTILITY POLE
EXISTING STREET PARKING PAY BOX
EXISTING STREET SIGN POST
EXISTING MAILBOX
EXISTING NEWSPAPER BOX
EXISTING SUPPORT COLUMN
EXISTING POST/BOLLARD
EXISTING SPRINKLER VALVE
EXISTING SPRINKLER CONTROL BOX
EXISTING GROUND LIGHT
EXISTING STANDPIPE
EXISTING BIKE RACK
EXISTING PHONE
P
M
N
S
S
B
NON-UTILITY STRUCTURES
EXISTING CTA
ZA ZA
YP YP
XO XO
WOW
VZ VZ
SN SN
SP SP
SD SD
RCN RCN
MD MD
MCI MCI
LG LG
L3 L3
JB JB
CO CO
CM CM
CTV CTV
CC CC
ATT ATT
EXISTING DEO / ELECTRIC
EXISTING TELECOM
EXISTING GAS
EXISTING SEWER
EXISTING WATER
G
BENCH
BUS SHELTER
C
FC
W
S
T
S
T
S
TLB
SLB
E
ADA
E E
/ / / G / / / G
G G
) )
W W
PROPOSED TRENCH LINE
EXISTING ELECTRIC
EXISTING GAS (ABANDONED)EXISTING GAS
EXISTING SEWER
EXISTING WATER
UNKNOWN UTILITY
?
EXISTING COMED
CE CE EXISTING COMED
PROPOSED TRENCHED CONDUIT
PROPOSED COMED EXISTING TELECOM (cont.)
QW QW
NG NG
PROPOSED DIRECTIONAL BORED CONDUIT
PROPOSED UTILITY POLE
S
PROPOSED PAD-MOUNTED TRANSFORMER
PROPOSED PAD-MOUNTED SWITCHGEAR
EXISTING PARK DISTRICT MANHOLEP
GENERAL NOTES
SHEET: OF
D
21 3 4 5 6 7
21 3 4 5 6 7
E
D
C
B
A
E
C
B
A
123 N. WACKER DRIVE SUITE 2000CHICAGO, ILLINOIS 60606TEL. (312) 857-1006 FAX. (312) 857-1056
REVISIONSDESCRIPTION BYDATEREV.
12345678
APPROVED BY:CREATED BY:
PROJ. ENGINEER:SCALE: DATE CREATED:
CHECKED BY:
07/01/2108/03/2110/12/21
FOR OUC REVIEWFOR OUC REVIEW
ISSUED FOR CONSTRUCTION
BAHBAHABM
BAH
HJM
HJMACS
12/08/2020AS SHOWN
COMED PROPOSEDCONDUIT INSTALLATION155 N. CARPENTER - PERM (PART 1)CHICAGO, ILLINOISCOMED WO#: 16706946DBS PROJECT#: 603.074EFP- 110905
THIS AND THE FOLLOWING SHEETS ARE NOT TRANSFERABLEAND ARE ONLY CONSIDERED AN OFFICIAL CONSTRUCTIONDRAWING WHEN ACCOMPANIED BY A SIGNED ENGINEERING SEAL.
THIS MATERIAL IS THE PROPERTY OF COMED AND CONTAINS CONFIDENTIALINFORMATION WHICH MUST NOT BE DUPLICATED, USED, OR DISCLOSEDOTHER THAN AS EXPRESSLY AUTHORIZED BY COMED.
An Exelon Company
DB STERLIN CONSULTANTS, INC.
143
GENERAL NOTES
1. THE CONTRACTOR SHALL COORDINATE ALL WORK WITH LOCAL, STATE, AND FEDERAL AGENCIES AS REQUIRED, AND WITH ALLADJACENT UTILITY OWNERS, WHETHER PUBLIC OR PRIVATE, INCLUDING COORDINATING ALL WORK WITH ANY OTHER PROJECTSPLANNED OR BEING CONSTRUCTED WITHIN THE PROJECT AREA AS NEEDED.
2. THE CONTRACTOR MUST COMPLY WITH ALL FEDERAL, STATE AND LOCAL CODES.
3. THE ILLINOIS DEPARTMENT OF TRANSPORTATION "STANDARD SPECIFICATIONS FOR ROAD AND BRIDGE CONSTRUCTION," LATESTEDITION, AND ALL ADDENDA THERETO, AND CITY OF CHICAGO "RULES AND REGULATIONS FOR CONSTRUCTION IN THE PUBLICWAY", LATEST EDITION, SHALL GOVERN ALL WORK UNDER THIS CONTRACT.
4. ALL WORK SHALL BE CONDUCTED IN ACCORDANCE WITH OSHA REQUIREMENTS.
5. ALL MATERIALS SHALL CONFORM TO APPLICABLE STANDARDS ESTABLISHED BY ANSI, NEMA, NBFU AND SHALL BE "U.L." LISTEDWHERE APPLICABLE. ALL MATERIALS AND EQUIPMENT SHALL BE NEW AND IN GOOD WORKING CONDITION WHEN INSTALLEDAND SHALL BE OF THE BEST GRADE AND OF THE SAME MANUFACTURER THROUGHOUT FOR EACH CLASS OR GROUP OFEQUIPMENT.
6. THE LOCATIONS AND ELEVATIONS OF EXISTING UNDERGROUND UTILITIES SHOWN OR REFERENCED ON THE PLANS AND PROFILESHAVE BEEN OBTAINED FROM DRAWINGS AND DATA RECEIVED FROM VARIOUS SOURCES. UTILITY DEPTHS ARE LABELED INPROFILES WHEN PROVIDED BY THE UTILITY. UTILITIES NOT LABELED IN PROFILES ARE DRAWN AT ASSUMED DEPTHS.CONTRACTOR TO VERIFY HORIZONTAL AND VERTICAL LOCATION OF ALL UTILITIES IN THE FIELD PRIOR TO EXCAVATION.
7. CONTRACTOR TO CALL DIGGER AT 312-744-7000 A MINIMUM OF 48 HOURS PRIOR TO ANY EXCAVATION TO HAVE EXISITNGUTILITIES LOCATED AND MARKED OR STAKED.
8. THE EXISTENCE AND LOCATION OF UNDERGROUND UTILITIES SHALL BE OBTAINED FROM ALL UTILITY COMPANIES ANDINVESTIGATED AND VERIFIED IN THE FIELD BY THE CONTRACTOR BEFORE STARTING WORK. EXCAVATION IN THE VINCINITY OFEXISTING UTILITIES AND UTILITY STRUCTURES SHALL BE PERFORMED BY HAND. THE CONTRACTOR WILL BE RESPONSIBLE FORTHE MAINTENANCE AND PRESERVATION OF THESE UTILITIES. ANY AND ALL DAMAGES TO EXISTING FACILITIES SHALL BEREPAIRED TO THE SATISFACTION OF THE UTILITY OWNER AT THE CONTRACTOR'S EXPENSE.
9. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS AFFECTING THEIR WORK WITH ACTUAL CONDITIONS AT THEJOB SITE. IF THERE ARE ANY DISCREPANCIES FROM WHAT IS SHOWN ON THE CONSTRUCTION PLAN, HE MUST IMMEDIATELYREPORT SAME TO THE ENGINEER BEFORE DOING ANY WORK, OTHERWISE THE CONTRACTOR ASSUMES FULL RESPONSIBILITY. INTHE EVENT OF DISAGREEMENT BETWEEN THE CONSTRUCTION PLANS, STANDARD SPECIFICATIONS AND/OR SPECIAL DETAILS,THE CONTRACTOR SHALL SECURE WRITTEN INSTRUCTION FROM THE ENGINEER PRIOR TO PROCEEDING WITH ANY PART OF THEWORK AFFECTED BY OMISSIONS OR DISCREPANCIES, FAILING TO SECURE SUCH INSTRUCTION, THE CONTRACTOR WILL BECONSIDERED TO HAVE PROCEEDED AT HIS OWN RISK AND EXPENSE. IN THE EVENT OF ANY DOUBT OR QUESTION ARISING WITHRESPECT TO THE TRUE MEANING OF THE CONSTRUCTION PLANS OR SPECIFICATIONS, THE DECISION OF THE ENGINEER SHALL BEFINAL AND CONCLUSIVE.
10. THE CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS AND PAY THE REQUISITE FEES TO THE CITY OF CHICAGO PRIOR TOCOMMENCING WORK.
11. ALL WORK AND MATERIALS WHICH DO NOT CONFORM TO THE SPECIFICATIONS ARE SUBJECT TO REMOVAL AND REPLACEMENTAT THE CONTRACTOR'S EXPENSE.
12. DO NOT SCALE PLANS FOR CONSTRUCTION DIMENSIONS.
13. THE CONTRACTOR SHALL OBTAIN THE ADJACENT PROPERTY OWNERS' PERMISSION BEFORE LABOR, MATERIALS, EQUIPMENT ORWORK IS STORED/PERFORMED ON THE LANDS OF OTHERS. CDOT RULES AND REGULATIONS SHALL BE FOLLOWED WITHRESPECT TO THE STORAGE OF MATERIALS IN THE PUBLIC WAY.
14. ALL UTILITY TRENCHES UNDER OR WITHIN TWO FEET OF PAVEMENT, SIDEWALK, CURB AND GUTTER, ETC. SHALL BE BACKFILLEDWITH CA-6 CRUSHED STONE (GRADE 8 OR 9), COMPACTED IN 9" LIFTS TO 95% OF MODIFIED PROCTOR.
15. UTILITY CONNECTIONS WITHIN THE STREET RIGHT-OF-WAY SHALL BE ACCOMPLISHED BY SAWCUTTING AND REMOVING THEEXISTING PAVEMENT. BACKFILL AND RESTORATION SHALL BE DONE IN ACCORDANCE WITH CDOT RULES AND REGULATIONS.
16. CONTACTOR SHALL RECORD THE LOCATION AND ELEVATION OF ALL NEW WORK INSTALLED AND OF ALL UTILITIESENCOUNTERED AS WORK PROGRESSES AND SHALL PREPARE AS-BUILT DRAWINGS BASED ON THESE RECORDS, TO BE SUBMITTEDTO COMED UPON COMPLETION OF WORK.
CHICAGO DEPARTMENT OF WATER MANAGEMENT
1. THE MINIMUM VERTICAL CLEARANCE (EDGE-TO-EDGE) FROM ALL WATER MAINS AND SERVICES IS 18-INCHES. FOR GRID MAINS(WATER MAINS LESS THAN 16-INCHES) AND WATER STRUCTURES (VALVE BASINS, SERVICE CONTROL VALVES, ETC.), THEMINIMUM HORIZONTAL CLEARANCE (EDGE-TO-EDGE) IS THREE (3) FEET. FOR FEEDER MAINS (WATER MAINS 16-INCHES ANDLARGER), THE MINIMUM HORIZONTAL CLEARANCE (EDGE-TO-EDGE) IS FIVE (5) FEET.
2. FOR ALL GENERAL CLEARANCE REQUIREMENTS (NON-WATER):DWM REQUIRES A MINIMUM HORIZONTAL CLEARANCE OF ID (INNER DIA. OF THE SEWER) + 4' CENTER-TO-CENTER OR 4 FEET EDGE-TO-EDGE, WHICHEVER IS LARGER, AND A MINIMUM VERTICAL CLEARANCE OF 18" EDGE-TO-EDGE. IF EITHER OF THESE CONDITIONS ARE NOT MET, THE SEWER MUST BE REPLACED WITH DIP OR REHABILITATED WITH AN APPROPRIATE LINER IF DIRECTED BY THE CITY.
3. IN NO CASE SHALL THE INSTALLATION OF ANY PROPOSED FACILITY BE CLOSER THAN FIVE (5) FEET AROUND A FIRE HYDRANT ORFIRE HYDRANT LEAD.
4. WHERE SHOWN ON THE PLANS, WATER MAINS TO BE TEMPORARILY SUPPORTED FOLLOWING DWM STANDARD DETAILS ANDCALCULATIONS PROVIDED ON THESE PLANS, AS REVIEWED AND APPROVED BY DWM.
5. WHEN EXISTING DRAINAGE FACILITIES ARE DISTURBED, THE CONTRACTOR SHALL PROVIDE AND MAINTAIN TEMPORARY OUTLETSAND CONNECTIONS FOR ALL DRAINS, SEWERS, AND APPURTENANCES.
6. EXTREME CAUTION MUST BE TAKEN TO AVOID DAMAGE TO ANY WATER OR SEWER FACILITIES. IF DAMAGE OCCURS TO THISDEPARTMENT'S FACILITIES, THE CONTRACTOR AND/OR OWNER WILL BE RESPONSIBLE FOR THE COST OF REPAIRING ORREPLACING THE DAMAGED FACILITIES.
7. WHERE ANY SEWER WORK IS REQUIRED, INCLUDING ADJUSTMENT OF SEWER STRUCTURES AND REMOVAL/REPLACEMENT OFFRAMES AND LIDS, THE CONTRACTOR MUST OBTAIN A PERMIT FROM DWM AND THE WORK MUST BE PERFORMED BY ALICENSED DRAIN LAYER UNDER PERMITS AND INSPECTION OF THE CITY OF CHICAGO DEPARTMENT OF WATER MANAGEMENT.A DWM SEWER INSPECTOR MUST BE PRESENT DURING THE WORK.
8. FAILURE TO COMPLY WITH THE ABOVE REQUIREMENTS MAY RESULT IN ADDITIONAL EXPENSES TO THE PROPOSED PROJECT TOVERIFY THAT ALL WORK CONFORMS TO DWM'S STANDARDS.
9. ALL SEWER INSTALLATIONS MUST MEET IEPA SEPARATION REQUIREMENTS FOR WATER AND SEWER PIPES. ALL PROPOSED/REPLACED SEWER LATERALS FROM CATCH BASINS/INLETS, SEWER MAINS, AND PRIVATE DRAINS (COLLECTIVELYKNOWN AS 'SEWER FACILITIES') THAT ARE PARALLEL TO WATER MAINS, SERVICES, OR FIRE HYDRANT LEADS (COLLECTIVELYKNOWN AS 'WATER FACILITIES') THAT ARE LESS THAN 18 INCHES BELOW THE WATER FACILITY AND HAVE LESS THAT 10 FEET OFHORIZONTAL SEPARATION FROM THE OUTSIDE EDGE OF THE WATER FACILITY MUST BE MADE OUT OF DUCTILE IRON/WATERMAIN QUALITY PIPE FOR 10 FEET ON EITHER SIDE OF THE OUTSIDE EDGE OF THE WATER FACILITY, ADDITIONALLY, ALL SEWERFACILITIES THAT CROSS PERPENDICULARLY BELOW WATER FACILITIES WITH LESS THAN 18 INCHES VERTICAL SEPARATION MUSTBE MADE OUT OF DUCTILE IRON/WATER MAIN QUALITY PIPE FOR 10 FEET ON EITHER SIDE OF THE OUTSIDE EDGE OF THE WATERFACILITY. IN ANY SEWER FACILITY CROSSES PERPENDICULARLY ABOVE A WATER FACILITY, THEN THE SEWER FACILITY SHALL BE ATLEAST 18 INCHES ABOVE THE WATER FACILITY AND THE SEWER FACILITY MUST BE MADE OUT OF DUCTILE IRON/WATER MAINQUALITY PIPE FOR 10 FEET ON EITHER SIDE OF THE OUTSIDE EDGE OF THE WATER FACILITY. SEWER LATERALS THAT REQUIREDUCTILE IRON/WATER MAIN QUALITY PIPE SHALL BE DUCTILE IRON/WATER MAIN QUALITY PIPE FROM THE CATCH BASIN TO APOINT 10 FEET BEYOND THE EDGE OF THE WATER FACILITY.
PEOPLE'S GAS
1. PEOPLES GAS FACILITIES ARE PRESENT WITHIN AREA OF CONSTRUCTION.USE EXTREME CAUTION NEAR ALL GAS FACILITIES DURING CONSTRUCTION ANDRELATED EXCAVATION ACTIVITIES. HAND EXCAVATION IS REQUIRED TO FIELD VERIFYTHE HORIZONTAL AND VERTICAL LOCATION OF GAS MAIN(S) PRIOR TO CROSSING ANDWORKING WITHIN 3 FEET OF ALL GAS FACILITIES. A MINIMUM OF 3' HORIZONTAL EDGE TOEDGE CLEARANCE IS REQUIRED FOR GAS MAINS WITH DIAMETERS OF 16" OR SMALLER, AND5FT EDGE TO EDGE CLEARANCE FOR GAS MAINS WITH DIAMETERS 18" AND LARGER.MAINTAIN A MINIMUM OF 18" EDGE TO EDGE VERTICAL CLEARANCE WHEN CROSSING GASMAINS 16" OR LESS IN DIAMETER, AND 24" EDGE TO EDGE VERTICAL CLEARANCE WHENCROSSING 18" AND LARGER DIAMETER GAS MAINS. CONTACT DIGGER 811 CHICAGO/312-744-7000FOR LOCATES 48 HOURS PRIOR TO START OF CONSTRUCTION.
2. THE USE OF CONCRETE, FLOW FILL, OR THE LIKE IS PROHIBITED WITHIN 24 INCHES OF ALL GASFACILITIES, NOR SHALL IT ENCASE ANY GAS FACILITY. A BUFFER OF 24" SAND IS TO BE USEDBETWEEN FLOW FILL AND ALL GAS FACILITIES. A MINIMUM OF 6" FA-02 OR FM-02 SAND SHALLBE USED WHEN BACKFILLING OTHER MATERIALS AROUND ANY EXPOSED GAS FACILITY. CONTRACTOREXPOSING GAS FACILITY IS RESPONSIBLE FOR PROVIDING THE SAND. ANY DAMAGES TO PEOPLESGAS FACILITIES SHALL BE THE RESPONSIBILITY OF THE INSTALLING UTILITY AND THEIRCONTRACTOR(S). CALL 866-556-6002 IMMEDIATELY FOR ANY DAMAGES TO THE GAS FACILITIES.ALL GAS FACILITIES ARE TO BE MAINTAINED.
3. HAND EXCAVATION IS REQUIRED TO LOCATE AND EXPOSE GAS MAIN(S) PRIOR TO CROSSING ANDWORKING WITHIN 3 FEET OF ALL GAS FACILITIES. CONTACT SHOP ENGINEERING SUPERVISOR TOINSPECT GAS MAIN AND COATING INTEGRITY PRIOR TO BACKFILL.
4. PEOPLES GAS CAST IRON AND DUCTILE IRON GAS MAINS MAY REQUIRE SUPPORT DURINGCONSTRUCTION AND RELATED EXCAVATION ACTIVITIES. ANY EXPOSED JOINTS MUST BESUPPORTED AND CAST IRON JOINTS SEALED BY GAS COMPANY PERSONNEL. CONTACT SHOPENGINEERING SUPERVISOR A MINIMUM OF 5 BUSINESS DAYS PRIOR TO EXCAVATION TO SET UPON-SITE INSPECTION. INSPECTION BY PEOPLES GAS IS REQUIRED PRIOR TO BACKFILL.
5. DIRECTIONAL DRILLING IS CONSIDERED A HIGH RISK EXCAVATION AS DETERMINED BY PHMSAAND NTSB; AS SUCH SPECIAL CONSIDERATIONS SHALL TAKE PLACE NEAR NATURAL GASDISTRIBUTION LINES. USE EXTREME CAUTION NEAR ALL GAS FACILITIES DURING CONSTRUCTIONAND RELATED EXCAVATION ACTIVITIES. HAND DIG PER REQUIRMENTS ABOVE AND MAINTAINHORIZONTAL AND VERTICAL CLEARANCES NOTED ABOVE. CONTRACTOR MUST OBSERVE BOREHEAD WHILE CROSSING GAS FACILITIES AND VERIFY THAT MINIMUM VERTICAL CLEARANCE ISOBTAINED. LOCATIONS OF EXISTING GAS FACILITIES MUST BE VERIFIED AT SUFFICIENT INTERVALS,OR A MAX OF DISTANCE OF 50FT, WHEN PARALLELING TO ENSURE SEPARATION IS MAINTAINED.CONTACT SYSTEM INTEGRITY OPERATIONS SUPERVISOR A MINIMUM OF 5 BUSINESS DAYS PRIORTO EXCAVATION TO SET UP ON-SITE INSPECTION.
6. NORTH SHOP: NORTH OF CHICAGO AVE/ASHLAND AVE /NORTH AVE BILL MCCAFFERTY, 773-794-6891CENTRAL SHOP: SOUTH OF CHICAGO AVE/ ASHLAND AVE / NORTH AVE TONORTH OF 87TH ST / ASHLAND AVE / CHICAGO RIVER / CERMAK RD CRISS REDMOND, 312-756-9796SOUTH SHOP: SOUTH OF 87TH ST / ASHLAND AVE / CHICAGO RIVER / CERMAK RD JACOB WEBER, 773-672-6271
COMED TRANSMISSION
1. USE EXTREME CAUTION NEAR COMED FACILITIES. HAND DIG WHILE CROSSING 69/138/345 kV TRANSMISSION LINES. COMED TRANSMISSION SHALL BE NOTIFIED 2 BUSINESS DAYS PRIOR TO THE START OF WORK. TO SCHEDULE AN ONSITE INSPECTOR DURING CONSTRUCTION,CONTACT LESLIE PASCHAL AT (630) 437-4767.
CDOT DIVISION OF ELECTRICAL OPERATIONS1. CAUTION! THE DEO HAS FACILITIES IN THE PARKWAY AND/OR THE STREET. THE CONTRACTOR IS
DIRECTED TO EXERCISE CAUTION DURING CONSTRUCTION AND/OR EXCAVATION. THE CONTRACTORASSUMES ALL LIABILITY FOR ANY DAMAGES TO DEO FACILITIES. CONTACT "DIGGER" AT 312-744-7000A MIN. OF 48HR'S PRIOR TO ANY EXCAVATION. THE CONTRACTOR IS TO HAND DIG AROUND ANDSUPPORT IN PLACE ANY BUREAU OF ELECTRICITY FACILITIES ENCOUNTERED. IF THE CONTRACTORDETERMINES THAT DEO FACILITIES NEED TO BE ADJUSTED, IT IS THE CONTRACTORS RESPONSIBILITYTO CONTACT MR. MOHAMMED RASHED AT 312-746-4636 A MINIMUM OF (3 WEEKS IN ADVANCE).
BURIED STREET CAR TRACKS1. BURIED/ABANDONED STREETCAR TRACKS MAY BE PRESENT. EXACT LOCATIONS ARE UNKNOWN.
IF SHOWN ON THE PLANS, LOCATIONS ARE APPROXIMATED BASED ON BEST AVAILABLEINFORMATION. CONTRACTOR TO VERIFY PRESENCE AND LOCATION OF BURIED STREETCAR TRACKS.
2. CAUTION MUST BE EXERCISED WHEN EXCAVATING NEAR BURIED STREETCAR TRACKS. MEMBERS OFTHE CHICAGO AREA JOINT ELECTROLYSIS COMMITTEE MAY USE STREETCAR TRACKS AS NEGATIVECABLE.CONTRACTOR MUST CONTACT MR. YOUSSEF TABIB OF COMED AT (630) 576-6952 BEFORECUTTING OR REMOVING ANY BURIED STREETCAR RAILS.
BUS ROUTES
1. CONTRACTOR TO NOTIFY CTA AT LEAST (2) TWO WEEKS IN ADVANCE OF ANY SIDEWALK, LANE, ORSTREET CLOSURES THAT COULD IMPACT CTA BUS SERVICE, INCLUDING ANY REMOVAL OF ANY BUSSTOP SIGNS, SO THAT SO THAT CTA CAN FACILITATE ANY NECESSARY DETOURS OR BUS STOPRELOCATIONS NEEDED. CONTACT MR. JACK CHALABIAN, COORDINATOR, TRAFFIC PLANNING,(312) 681-4176.
2. FOR CHANGES IN TRAFFIC PATTERNS THAT INCLUDE CTA BUS ROUTES, MAINTAIN MIN. 11' WIDELANES FOR CTA BUS TRAFFIC.
STREETSCAPE CONSIDERATIONS - DO NOT DISTURB ANY SIDEWALK MEDALLIONS, PLANTS, PAVERS ORANY OTHER STREETSCAPE ELEMENTS.IF IT IS NECESSARY TO DISTURB ANY OF THESE ELEMENTS, CONTRACTOR TO CALL BRIDGET STALLA(312-742-1259) AT LEAST 48 HOURS PRIOR TO ANY PLANNED PROPOSED IMPACT.
FORESTRY
1. TREE PROTECTION MEASURES:AT A MINIMUM, NEED TO INCLUDE ORANGE SNOW FENCE TO BE INSTALLED ALONG BACKOF THE CURB-LINE, 10 FEET FROM THE BACK OF THE CURB-LINE AND AT A DISTANCEOF 5 FEET FROM EITHER SIDE OF THE TREE. IF TRIMMING IS REQUIRED FOR LINEINSTALLATION, IT WILL BE DONE BY AN INSURED TREE SERVICE COMPANY. TRIMMING WILLBE DONE IN ACCORDANCE TO AMERICAN NATIONAL STANDARDS INSTITUTE GUIDELINES,LEAVING THE FORM AND STRUCTURE OF THE TREES INTACT.
2. WHERE REQUIRED, PROPOSED UTILITY WILL TUNNEL UNDER ANY TREES PER BUREAU OFFORESTRY SPECIFICATIONS.TUNNELING SPECIFICATIONS:
TREE SIZE * TUNNEL/TRENCH DISTANCE< 10" 5 FEET (10' TOTAL) 10" TO 19" 10 FEET (20' TOTAL) > 19" 15 FEET (30' TOTAL)* DBH = DIAMETER AT BREAST HEIGHT (4.5')WHERE TUNNELING IS NOT FEASIBLE, AIR SPADE EXCAVATION OR HAND DIGGING WITH THERETENTION OF ROOTS LARGER THAN 2 INCHES WOULD BE ACCEPTABLE FOLLOWING THESAME DISTANCE SPECIFICATIONS AS TUNNELING.
STAY OUT OF THE DRIPLINE.STOP TRENCHING WHEN ROOTS OF 2-INCHES OR LARGER ARE ENCOUNTERED.CONTACT JOSEPH McCARTHY, BOF, AT (312) 746-5254.
RESTORATION
1. ALL DISTURBED AREAS SHALL BE RESTORED BY THE CONTRACTOR ACCORDING TO THELATEST CITY OF CHICAGO DEPARTMENT OF TRANSPORTATION (CDOT) RULES AND REGULATIONS.CONTRACTOR TO MATCH EXISTING PAVEMENT AND SIDEWALK JOINTS AND MATCH COLOR,TEXTURE, AND FINISH OF EXISTING SIDEWALKS, CURBS, AND CURB AND GUTTER.
2. ADA RAMP CONSTRUCTION TO FOLLOW THE LATEST CDOT ADA CONSTRUCTION STANDARDS,AVAILABLE ON THE CITY'S WEBSITE.
3. THE CONTRACTOR IS TO REMOVE AND RESTORE STREET PAVEMENT TO THE EXTENTS REQUIREDBY CDOT RULES AND REGULATIONS.
4. CONTRACTOR TO REMOVE AND REINSTALL OR REPLACE ANY APPURTENANCES AFFECTED BYHIS CONSTRUCTION, INCLUDING BUT NOT LIMITED TO SIGNS, TRAFFIC SIGNALS, MAILBOXES,METERS, CITY LIGHTS, CONTROLLER BOXES/CABINETS, BENCHES, CANOPIES, AND PLANTERS,AND SHALL COORDINATE WITH CDOT PRIOR TO ANY REMOVAL OF SAID ITEMS. CONTRACTORSHALL ALSO BE RESPONSIBLE FOR ANY PERMITS OR FEES ASSOCIATED WITH THIS WORK.
5. ALL AREAS DAMAGED BY THE CONTRACTOR'S WORK SHALL BE REPAIRED BY THE CONTRACTORAT HIS EXPENSE AND SHALL BE MADE IN ACCORDANCE WITH CDOT RULES AND REGULATIONS.
6. IT IS CALLED TO THE CONTRACTOR'S ATTENTION THAT AREAS OF VAULTED SIDEWALK AREPRESENT WITHIN THE CITY OF CHICAGO AND MAY NOT BE SHOWN ON THE PLANS. FORSIDEWALK RESTORATION IN AREAS WHERE VAULTED SIDEWALK IS SUSPECTED, CONTRACTORTO COORDINATE WITH ADJACENT BUILDING OWNER(S) PRIOR TO ANY EXCAVATION TODETERMINE PRESENCE AND EXTENTS OF POSSIBLE VAULT AREA BENEATH SIDEWALK.RESTORATION OF VAULTED SIDEWALK AREAS REQUIRES DESIGN SIGNED AND SEALED BYAN ILLINOIS LICENSED STRUCTURAL ENGINEER AND SHALL BE COORDINATED WITH COMED.
TRAFFIC CONTROL
1. THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS TO ENSURE SAFETY OFPEDESTRIANS, ALL PEOPLE ON THE WORK SITE, INCLUDING CONTRACTOR'S OWN PERSONNEL ORSUBCONTRACTORS, VEHICULAR TRAFFIC AND ADJACENT PROPERTY THROUGHOUT THE DURATIONOF THE PROJECT, INCLUDING SAFELY SECURING THE SITE WHEN NOT PRESENT.
2. ALL SIGNING MUST BE IN ACCORDANCE WITH THE APPLICABLE PROVISIONS OF THE STATE OFILLINOIS "STANDARD SPECIFICATIONS FOR ROAD AND BRIDGE CONSTRUCTION," LATEST EDITION,THE DETAILS IN THESE PLANS, THE LATEST EDITION OF THE IDOT BUREAU OF DESIGN ANDENVIROMENT HIGHWAY STANDARDS AND THE LATEST EDITION OF THE "MANUAL ON UNIFORMTRAFFIC CONTROL DEVICES".
3. LONGITUDINAL DIMENSIONS SHOWN ON THESE PLANS MAY BE ADJUSTED TO FIT FIELD CONDITIONSAS DIRECTED BY THE ENGINEER.
4. THE CONTRACTOR IS RESPONSIBLE FOR ENSURING THAT ALL BARRICADES, SIGNS, LIGHTS ANDOTHER DEVICES INSTALLED BY HIM ARE IN PLACE AND OPERATING 24 HOURS EACH DAYINCLUDING SUNDAYS AND HOLIDAYS DURING THE TIME THIS CONSTRUCTION IS IN EFFECT.
5. ALL EXISTING SIGNING THAT IS NOT APPLICABLE WHILE THE CONSTRUCTION IS IN EFFECT MUSTBE COMPLETELY COVERED BY THE CONTRACTOR.
6. THE SIZES OF ALL SIGNS NOT SPECIFIED IN THESE PLANS MUST BE AS REQUIRED BY THEMANUAL ON UNIFORM TRAFFIC CONTROL DEVICES.
7. AS A MINIMUM, ALL AMBER FLASHING LIGHTS THAT ARE REQUIRED MUST MEET THE REQUIREMENTSFOR TYPE A - LOW INTENSITY FLASHING LIGHTS IN ARTICLE 702.04 OF THE STANDARDSPECIFICATIONS. ALL LIGHTS SHALL OPERATE DURING HOURS OF DARKNESS. ONLY LIGHTS THATHAVE BEEN APPROVED BY THE IDOT MUST BE USED.THE CONTRACTOR MUST MAINTAIN ACCESS TO ALL PRIVATE AND COMMERCIAL DRIVEWAYSAT ALL TIMES VIA STAGED CONSTRUCTION AS NEEDED. SEE IDOT DISTRICT ONESTANDARD TC-10.
8. ALL HAZARDS, DITCHES, TRENCHES, EXCAVATIONS, ETC. NEAR OR ADJACENT TO WALKWAYSMUST BE CLEARLY DELINEATED AND ADEQUATELY PROTECTED FROM MOTOR VEHICLE ORPEDESTRIAN TRAFFIC AND FREE OF ANY OBSTRUCTIONS AND HAZARDS SUCH AS HOLES,DEBRIS, MUD, CONSTRUCTION EQUIPMENT, STORED MATERIALS, ETC..
9. WHERE A HANDICAPPED PEDESTRIAN RAMP IS RESTRICTED DUE TO CLOSURE, OR IN ANYLOCATION WHERE NEEDED TO MAINTAIN PEDESTRIAN TRAFFIC, TEMPORARY RAMPS AND/ORWALKWAYS MEETING ADA GUIDELINES SHALL BE INSTALLED BY THE CONTRACTOR PER CDOTSTANDARDS.
10. PROPOSED MAINTENANCE OF TRAFFIC SIGNING MUST BE COVERED OR REMOVED WHEN NOTREQUIRED DURING A SPECIFIC STAGE OF CONSTRUCTION.
11. SEE SUGGESTED MAINTENANCE OF TRAFFIC PLAN FOR SUGGESTED SIGNING.
12. CHANGEABLE MESSAGE SIGNS TO BE PROVIDED AT CDOT'S DIRECTION.
13. THE CONTRACTOR MUST CONDUCT HIS WORK IN SUCH A MANNER THAT EMERGENCYVEHICLES WILL HAVE ACCESS TO THE AREA AT ALL TIMES.
14. THE CONTRACTOR MUST NOTIFY CDOT AND/OR IDOT BUREAU OF TRAFFIC AS REQUIRED 72HOURS IN ADVANCE OF BEGINNING WORK.
15. SIGN SPACING SHALL BE PER IDOT DISTRICT ONE DETAIL TC-21.
16. WORK SHALL NOT TAKE PLACE WITHOUT REQUIRED TRAFFIC CONTROL DEVICES ANDBARRICADES IN PLACE PER M.U.T.C.D. ANY DEFICIENCY OF SAFETY OR TRAFFIC CONTROLDEVICES SHALL BE JUST-CAUSE TO STOP THE PROJECT UNTIL SUCH TIME AS THEDEFICIENCY IS CORRECTED.
12.7' 23.3' 8.0'5.5'
67.0'
16.0'
34.5'
9.1'
3.0'
24.0'
12.0'
35.4'
10.1'
6.0'
0+00
0+50
1+00
1+50
1+83
S
W
W
E
W. RANDOLPH ST.
W
12" DI12" DI
12" DI
8" D
I
8" D
I)
)
)
)
)
)
)
)
)
)
S
54"54"
54"
)
)
)
)
)
)
)
)
)
)
6" ST6" ST
4" S
T
6" S
T
6" ST
MH #0384145
CE
CE
CE
CE
CE
CE
CE
CE
CE
CE
(2-T)
(6- T
)
(2-D)
(2-D)
(2-D)(2-D)
(2-D)
(2-D)
(2-D
)G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
WW
WW
W
W
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
AT
T
AT
T
AT
T
AT
T
AT
T
AT
T
AT
TA
TT
AT
TA
TT
AT
T
AT
T
AT
T
AT
T
AT
T
AT
T
AT
T
AT
T
AT
T
AT
T
AT
T
AT
T
AT
T
AT
T
AT
A
T
T
A
T
T
AT
TA
TT
AT
TA
TT
ATT
(24-
MTD
)(2
4-M
TD)
(4-S
TD)
(4-S
TD)
(2-M
TD)
ADA
AD
A
ADA
AD
A
SIDE
WAL
K
SIDEWALK
FACE OF CURB
FACE OF CURB
FACE
OF
CURB
FACE
OF
CURB
FACE OF CURB
DRIVEWAY
MC
I
MC
I
MC
I
MC
I
MC
I
MC
I
MC
I
MC
I
MC
I
MCI
1012 W. RANDOLPH ST.
1020 W. RANDOLPH ST.
158 N
. C
AR
PEN
TER
ST.
(UN
KNO
WN
SIZ
E)
(UN
KNO
WN
SIZ
E)
MH#5536
E
N. C
AR
PEN
TER
ST
.
12"
8" D
I
G
G
G
GG
G
G
G
G G
2" ST6"
ST
G
8" ST
CE
CE
CE
CE
CE
CE
CE
CE
CE
CE
CE
CE
CE
CE
C
E
C
E
C
E
C
E
C
E
C
E
C
E
C
E
CE
CE
CE
CE
CE
CE
CE
CE
C
E
C
E
C
E
C
E
C
E
C
E
C
E
CE
CE
CE
CE
CE
CE
CE
CE
C
E
C
E
C
E
C
E
C
E
C
E
MH#0384143
MH#0384068
(2-T)(2-T)
(6-T
)
(6-T)
(6-T)
(2-T)
(6-T)
E
)
)
AT
AT
MH#13708
MH#5432
AT
T
AT
T
AT
T
A
T
T
A
T
T
A
T
T
AT
T
AT
TA
TT
AT
T
AT
T
AT
T
AT
T
AT
T
AT
T
AT
T
AT
T
AT
T
AT
T
AT
T
AT
T
AT
T
(2-P
VC)
(24-
MTD
)
(4-M
TD)
EE
EE
E
E
E
E
E
E
E
E
E
S
E
E
E
E
E
E
E
(2-D)
(2-D)
E E E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
(2-D)(2-D)
SIDEWALK
SIDEWALK
SIDEWALK
SIDE
WAL
K
SIDE
WAL
K
FACE OF CURB
FACE OF CURB
FACE OF CURBFACE OF CURB
FACE OF CURB
FACE
OF
CURB
FACE
OF
CURB
AD
A
AD
A
ADA
ADA
S
G
G
115 N. CARPENTER ST.
W. RANDOLPH ST.
16.4'
0.00
5.00
10.00
15.00
0+00 0+50 1+501+00
20.00
COMED
MH# 0384068
8"
WATER
54"
SEWER
6"
GAS
DEO
(2-D)
DEO
(2-D)
12"
WATER
DEO
(2-D)
DEO
(2-D)
0.00
5.00
10.00
15.00
20.00
FACE OFCURB
EXISTINGGRADE
POTENTIAL BURIEDCTA ABANDON TRACKS
2.5' 3.5'
1.8' 3.0'
1.6'
7.8'7.4'
2.2'7.6'
8.6'
PLAN & PROFILE
SHEET: OF
D
21 3 4 5 6 7
21 3 4 5 6 7
E
D
C
B
A
E
C
B
A
123 N. WACKER DRIVE SUITE 2000CHICAGO, ILLINOIS 60606TEL. (312) 857-1006 FAX. (312) 857-1056
REVISIONSDESCRIPTION BYDATEREV.
12345678
APPROVED BY:CREATED BY:
PROJ. ENGINEER:SCALE: DATE CREATED:
CHECKED BY:
07/01/2108/03/2110/12/21
FOR OUC REVIEWFOR OUC REVIEW
ISSUED FOR CONSTRUCTION
BAHBAHABM
BAH
HJM
HJMACS
12/08/2020AS SHOWN
COMED PROPOSEDCONDUIT INSTALLATION155 N. CARPENTER - PERM (PART 1)CHICAGO, ILLINOISCOMED WO#: 16706946DBS PROJECT#: 603.074EFP- 110905
THIS AND THE FOLLOWING SHEETS ARE NOT TRANSFERABLEAND ARE ONLY CONSIDERED AN OFFICIAL CONSTRUCTIONDRAWING WHEN ACCOMPANIED BY A SIGNED ENGINEERING SEAL.
THIS MATERIAL IS THE PROPERTY OF COMED AND CONTAINS CONFIDENTIALINFORMATION WHICH MUST NOT BE DUPLICATED, USED, OR DISCLOSEDOTHER THAN AS EXPRESSLY AUTHORIZED BY COMED.
An Exelon Company
DB STERLIN CONSULTANTS, INC.
144
PLAN VIEW
SCALE 1" = 20'
ALL PLAN VIEW BENDS ARERADIUS = 4.0' UNLESSSPECIFIED OTHERWISE.
BEGIN CONSTRUCTION OF 8-5"PVC CONDUIT AT EXISTINGCOMED MH# 0384068 PER
COMED SPECIFICATION C4231.STA: 0+00
END CONSTRUCTION BY STUBBING 8-5"PVC CONDUITS AT NORTH LINE OFW. RANDOLPH ST FOR CUSTOMERCONNECTION.STA: 1+83
183 LINEAR FEET OF PROPOSED 8-5"PVC CONDUIT INSTALLED VIA 3'WIDTH OPEN-CUT TRENCH PERCOMED SPECIFICATION C4090.
END CONSTRUCTION BY STUBBING 8-5"PVC CONDUITS AT NORTH LINE OFW. RANDOLPH ST FOR CUSTOMERCONNECTION.STA: 1+83
BEGIN CONSTRUCTION OF 8-5"PVC CONDUIT AT EXISTINGCOMED MH# 0384068 PER
COMED SPECIFICATION C4231.STA: 0+00
PEOPLES GAS FACILITIES ARE PRESENT WITHIN AREA OF CONSTRUCTION. USEEXTREME CAUTION NEAR ALL GAS FACILITIES DURING CONSTRUCTION ANDRELATED EXCAVATION ACTIVITIES. HAND EXCAVATION IS REQUIRED TO FIELDVERIFY THE HORIZONTAL AND VERTICAL LOCATION OF GAS MAIN(S) PRIOR TOCROSSING AND WORKING WITHIN 3 FEET OF ALL GAS FACILITIES. A MINIMUMOF 3' HORIZONTAL EDGE TO EDGE CLEARANCE IS REQUIRED FOR GAS MAINSWITH DIAMETERS OF 16" OR SMALLER, AND 5FT EDGE TO EDGE CLEARANCEFOR GAS MAINS WITH DIAMETERS 18" AND LARGER. MAINTAIN A MINIMUMOF 18” EDGE TO EDGE VERTICAL CLEARANCE ON GAS MAINS 16" OR LESS INDIAMETER, AND 24" EDGE TO EDGE VERTICAL CLEARANCE ON 18" AND LARGERDIAMETER GAS MAINS. CONTACT DIGGER 312-744-7000 FOR LOCATES 48HOURS PRIOR TO START OF CONSTRUCTION.
THE USE OF CONCRETE, FLOW FILL, OR THE LIKE IS PROHIBITED WITHIN 24INCHES OF ALL GAS FACILITIES, NOR SHALL IT ENCASE ANY GAS FACILITY. ABUFFER OF 24" SAND IS TO BE USED BETWEEN FLOW FILL AND ALL GASFACILITIES. A MINIMUM OF 6” FA-02 OR FM-02 SAND SHALL BE USED WHENBACKFILLING OTHER MATERIALS AROUND ANY EXPOSED GAS FACILITY.CONTRACTOR EXPOSING GAS FACILITY IS RESPONSIBLE FOR PROVIDING THESAND. ANY DAMAGES TO PEOPLES GAS FACILITIES SHALL BE THERESPONSIBILITY OF THE INSTALLING UTILITY AND THEIR CONTRACTOR(S). NOTIFY CENTRAL SHOP ENGINEER, ERNEST CRAFTON, 773-542-7867,IMMEDIATELY FOR ANY DAMAGES TO THE GAS FACILITIES. ALL GAS FACILITIESARE TO BE MAINTAINED.
USE EXTREME CAUTION WHEN EXCAVATING / DIGGING NEAR EXISTING UTILITIES.
A
A
A A
21
11
22
12
23
13
CONSTRUCTION MAY REQUIRE REMOVAL AND DISPOSAL OF ABAND. CTA TRACKS.
SEE ADDITIONAL CDWM IEPA SEPARATION NOTES ONGENERAL NOTES, SHEET 3, UNDER "CHICAGO DEPARTMENTOF WATER MANAGEMENT, BULLET NUMBER 9.
183 LINEAR FEET OF PROPOSED 8-5"PVC CONDUIT INSTALLED VIA 3'WIDTH OPEN-CUT TRENCH PERCOMED SPECIFICATION C4090.
PROFILE VIEW
SCALE 1" = 20' HORIZONTAL
SCALE 1" = 5' VERTICAL
24
14
33.9'
64.9'
37.9'
82.5'
71.3'
W. RANDOLPH ST.
ADA
AD
A
ADA
AD
A
SIDE
WAL
K
SIDEWALK
FACE OF CURB
FACE OF CURB
FACE
OF
CURB
FACE
OF
CURB
FACE OF CURB
DRIVEWAY
1012 W. RANDOLPH ST.
1020 W. RANDOLPH ST.
158 N
. C
AR
PEN
TER
ST.
N. C
AR
PEN
TER
ST
.
SIDEWALK
SIDEWALK
SIDEWALK
SIDE
WAL
K
SIDE
WAL
K
FACE OF CURB
FACE OF CURB
FACE OF CURBFACE OF CURB
FACE OF CURB
FACE
OF
CURB
FACE
OF
CURB
AD
A
AD
A
ADA
ADA
G
G
115 N. CARPENTER ST.
W. RANDOLPH ST.
RESTORATION
SHEET: OF
D
21 3 4 5 6 7
21 3 4 5 6 7
E
D
C
B
A
E
C
B
A
123 N. WACKER DRIVE SUITE 2000CHICAGO, ILLINOIS 60606TEL. (312) 857-1006 FAX. (312) 857-1056
REVISIONSDESCRIPTION BYDATEREV.
12345678
APPROVED BY:CREATED BY:
PROJ. ENGINEER:SCALE: DATE CREATED:
CHECKED BY:
07/01/2108/03/2110/12/21
FOR OUC REVIEWFOR OUC REVIEW
ISSUED FOR CONSTRUCTION
BAHBAHABM
BAH
HJM
HJMACS
12/08/2020AS SHOWN
COMED PROPOSEDCONDUIT INSTALLATION155 N. CARPENTER - PERM (PART 1)CHICAGO, ILLINOISCOMED WO#: 16706946DBS PROJECT#: 603.074EFP- 110905
THIS AND THE FOLLOWING SHEETS ARE NOT TRANSFERABLEAND ARE ONLY CONSIDERED AN OFFICIAL CONSTRUCTIONDRAWING WHEN ACCOMPANIED BY A SIGNED ENGINEERING SEAL.
THIS MATERIAL IS THE PROPERTY OF COMED AND CONTAINS CONFIDENTIALINFORMATION WHICH MUST NOT BE DUPLICATED, USED, OR DISCLOSEDOTHER THAN AS EXPRESSLY AUTHORIZED BY COMED.
An Exelon Company
DB STERLIN CONSULTANTS, INC.
145
RESTORATION VIEW
SCALE 1" = 20'
TOTAL RESTORATION MATERIAL
CONCRETE DRIVEWAY:00 SF00 SF
00 SF
00 SF00 SF
00 SF00 SF
5784 SF9959 SF
00 LFCURB & GUTTER:
RESPONSIBILITY OF OTHER:
CONCRETE SIDEWALK:
ASPHALT STREET:
CONCRETE STREET:
ASPHALT ALLEY
CONCRETE ALLEY:
CONCRETE ALLEY APRON:
PARKWAY:
APPROX. 5784 SQUARE FEET OF ASPHALTSTREET RESTORATION
RESTORATION TO BE COMPLETEDBY OTHERS UNDER PRA 2020-222
RESTORATION SUBJECT TO CHANGE PERSIGNED PRA FOR CONFLICT 2020-222
PROPOSEDTRENCH AREA
RESTORATION SUBJECT TO CHANGE PERMOU 2021-272
180'TRANSITION
TAPERAREA
20'
20'
90'TRANSITION
TAPERAREA
20'
90'TRANSITION
TAPERAREA
14' WORK AREA12' LANE
12' LANE
35' LANE
12' MEDIAN
12' LANE
12' MEDIAN
35' LANE
12' WORKAREA
13' WORK AREA15' LANE
12' LANE
SHEET: OF
D
21 3 4 5 6 7
21 3 4 5 6 7
E
D
C
B
A
E
C
B
A
123 N. WACKER DRIVE SUITE 2000CHICAGO, ILLINOIS 60606TEL. (312) 857-1006 FAX. (312) 857-1056
REVISIONSDESCRIPTION BYDATEREV.
12345678
APPROVED BY:CREATED BY:
PROJ. ENGINEER:SCALE: DATE CREATED:
CHECKED BY:
07/01/2108/03/2110/12/21
FOR OUC REVIEWFOR OUC REVIEW
ISSUED FOR CONSTRUCTION
BAHBAHABM
BAH
HJM
HJMACS
12/08/2020AS SHOWN
COMED PROPOSEDCONDUIT INSTALLATION155 N. CARPENTER - PERM (PART 1)CHICAGO, ILLINOISCOMED WO#: 16706946DBS PROJECT#: 603.074EFP- 110905
THIS AND THE FOLLOWING SHEETS ARE NOT TRANSFERABLEAND ARE ONLY CONSIDERED AN OFFICIAL CONSTRUCTIONDRAWING WHEN ACCOMPANIED BY A SIGNED ENGINEERING SEAL.
THIS MATERIAL IS THE PROPERTY OF COMED AND CONTAINS CONFIDENTIALINFORMATION WHICH MUST NOT BE DUPLICATED, USED, OR DISCLOSEDOTHER THAN AS EXPRESSLY AUTHORIZED BY COMED.
An Exelon Company
DB STERLIN CONSULTANTS, INC.
146
TRAFFIC CONTROL - STAGE 1
NOTES:
1. CONTRACTOR SHALL NOTIFY RESIDENTS AND BUSINESSES OF ON-STREET PARKING CLOSURES.2. TRAFFIC CONTROL FOR THIS PROJECT SHALL BE DONE IN ACCORDANCE WITH THE CITY OF CHICAGO DEPARTMENT OF TRANSPORTATION'S "RULES AND
REGULATIONS FOR CONSTRUCTION IN THE PUBLIC WAY."3. THE CONTRACTOR IS RESPONSIBLE FOR THE MAINTENANCE OF TRAFFIC AND SHALL PROVIDE MATERIALS AND SIGNS TO INFORM AND PROTECT PEDESTRIANS.4. ALL TRAFFIC CONTROL DEVICES SHALL BE IN PLACE PRIOR TO WORK COMMENCING5. TRAFFIC CONTROL DEVICES SHALL CONFORM TO SECTION 701 OF THE ILLINOIS DEPARTMENT OF TRANSPORTATION STANDARD SPECIFICATIONS FOR ROAD
AND BRIDGE CONSTRUCTION, ADOPTED APRIL 1, 2016.6. TRAFFIC CONTROL DEVICE DETAILS CAN BE FOUND IN ILLINOIS DEPARTMENT OF TRANSPORTATION'S STANDARD NO. 701901-077. A 7 FOOT CLEARANCE FROM THE BOTTOM OF THE SIGN TO THE TOP OF PAVEMENT IS REQUIRED FOR SIGNS THAT WILL BE IN PLACE FOR MORE THAN 4 DAYS,
AND SHALL BE POST MOUNTED IN THE GROUND WHENEVER POSSIBLE.8. MAINTAIN ACCESS TO DRIVEWAYS AT ALL TIMES. SEE IDOT DISTRICT ONE.9. CONTRACTOR SHALL RESTORE ALL TRAFFIC LANES TO NORMAL TRAFFIC PATTERN DURING NON-WORK HOURS UNLESS OTHERWISE DIRECTED.10. SECURE ALL OPENINGS DURING NON-WORK HOURS.
LEGEND
CONSTRUCTION DRUMEXISTING TRAFFIC DIRECTIONPROPOSED TRAFFIC DIRECTIONPROPOSED WORK AREA
TYPICAL CROSS SECTIONFOR S. CARPENTER ST. - FACING SOUTH
(NORTH OF W. RANDOLPH ST.)
15'MIN.13' MIN.
12'MIN.
CONSTRUCTION DRUM
WORKAREA
TYPICAL CROSS SECTIONFOR S. CARPENTER ST. - FACING NORTH
(SOUTH OF W. RANDOLPH ST.)
12'MIN.14' MIN.
12'MIN.
CONSTRUCTION DRUM
WORKAREA
TYPICAL CROSS SECTIONFOR W. RANDOLPH ST. - FACING WEST
5'35'
LANE
12'WORKAREA 5'12' MIN.
35'LANE
CONSTRUCTION DRUMRAISED MEDIAN RAISED MEDIAN
W. RANDOLPH ST.
N. C
ARPE
NTE
R ST
.
20'
90'TRANSITION
TAPERAREA
180'TRANSITION
TAPERAREA
20'
35' LANE
12' LANE
12' MEDIAN
35' LANE
24' WORKAREA
20'
90'TRANSITION
TAPERAREA
12' WORK AREA
13' LANE13' LANE
13' WORK AREA12' LANE11' LANE
SHEET: OF
D
21 3 4 5 6 7
21 3 4 5 6 7
E
D
C
B
A
E
C
B
A
123 N. WACKER DRIVE SUITE 2000CHICAGO, ILLINOIS 60606TEL. (312) 857-1006 FAX. (312) 857-1056
REVISIONSDESCRIPTION BYDATEREV.
12345678
APPROVED BY:CREATED BY:
PROJ. ENGINEER:SCALE: DATE CREATED:
CHECKED BY:
07/01/2108/03/2110/12/21
FOR OUC REVIEWFOR OUC REVIEW
ISSUED FOR CONSTRUCTION
BAHBAHABM
BAH
HJM
HJMACS
12/08/2020AS SHOWN
COMED PROPOSEDCONDUIT INSTALLATION155 N. CARPENTER - PERM (PART 1)CHICAGO, ILLINOISCOMED WO#: 16706946DBS PROJECT#: 603.074EFP- 110905
THIS AND THE FOLLOWING SHEETS ARE NOT TRANSFERABLEAND ARE ONLY CONSIDERED AN OFFICIAL CONSTRUCTIONDRAWING WHEN ACCOMPANIED BY A SIGNED ENGINEERING SEAL.
THIS MATERIAL IS THE PROPERTY OF COMED AND CONTAINS CONFIDENTIALINFORMATION WHICH MUST NOT BE DUPLICATED, USED, OR DISCLOSEDOTHER THAN AS EXPRESSLY AUTHORIZED BY COMED.
An Exelon Company
DB STERLIN CONSULTANTS, INC.
147
TRAFFIC CONTROL - STAGE 2
NOTES:
1. CONTRACTOR SHALL NOTIFY RESIDENTS AND BUSINESSES OF ON-STREET PARKING CLOSURES.2. TRAFFIC CONTROL FOR THIS PROJECT SHALL BE DONE IN ACCORDANCE WITH THE CITY OF CHICAGO DEPARTMENT OF TRANSPORTATION'S "RULES AND
REGULATIONS FOR CONSTRUCTION IN THE PUBLIC WAY."3. THE CONTRACTOR IS RESPONSIBLE FOR THE MAINTENANCE OF TRAFFIC AND SHALL PROVIDE MATERIALS AND SIGNS TO INFORM AND PROTECT PEDESTRIANS.4. ALL TRAFFIC CONTROL DEVICES SHALL BE IN PLACE PRIOR TO WORK COMMENCING5. TRAFFIC CONTROL DEVICES SHALL CONFORM TO SECTION 701 OF THE ILLINOIS DEPARTMENT OF TRANSPORTATION STANDARD SPECIFICATIONS FOR ROAD
AND BRIDGE CONSTRUCTION, ADOPTED APRIL 1, 2016.6. TRAFFIC CONTROL DEVICE DETAILS CAN BE FOUND IN ILLINOIS DEPARTMENT OF TRANSPORTATION'S STANDARD NO. 701901-077. A 7 FOOT CLEARANCE FROM THE BOTTOM OF THE SIGN TO THE TOP OF PAVEMENT IS REQUIRED FOR SIGNS THAT WILL BE IN PLACE FOR MORE THAN 4 DAYS,
AND SHALL BE POST MOUNTED IN THE GROUND WHENEVER POSSIBLE.8. MAINTAIN ACCESS TO DRIVEWAYS AT ALL TIMES. SEE IDOT DISTRICT ONE.9. CONTRACTOR SHALL RESTORE ALL TRAFFIC LANES TO NORMAL TRAFFIC PATTERN DURING NON-WORK HOURS UNLESS OTHERWISE DIRECTED.10. SECURE ALL OPENINGS DURING NON-WORK HOURS.
LEGEND
CONSTRUCTION DRUMEXISTING TRAFFIC DIRECTIONPROPOSED TRAFFIC DIRECTIONPROPOSED WORK AREA
TYPICAL CROSS SECTIONFOR W. RANDOLPH ST. - FACING WEST
35'LANE
24'WORKAREA 12'12' MIN.
35'LANE
CONSTRUCTION DRUMRAISED MEDIAN RAISED MEDIAN
TYPICAL CROSS SECTIONFOR S. CARPENTER ST. - FACING SOUTH
(NORTH OF W. RANDOLPH ST.)
12' MIN.12' MIN. 2'
WORKAREA
CONSTRUCTION DRUM
13'
TYPICAL CROSS SECTIONFOR S. CARPENTER ST. - FACING NORTH
(SOUTH OF W. RANDOLPH ST.)
11' MIN. 12' MIN.2'
WORKAREA
CONSTRUCTION DRUM
13'
R9-11a
SIDEWALK CLOSED
CROSS HERE
R9-11a
SIDEWALK CLOSED
CROSS HERE
W. RANDOLPH ST.
N. C
ARPE
NTE
R ST
.
35' LANE
12' MEDIAN
12' LANE
18' LANE
42' WORKAREA
128'TRANSITION
TAPERAREA
20'
180'TRANSITION
TAPERAREA
SHEET: OF
D
21 3 4 5 6 7
21 3 4 5 6 7
E
D
C
B
A
E
C
B
A
123 N. WACKER DRIVE SUITE 2000CHICAGO, ILLINOIS 60606TEL. (312) 857-1006 FAX. (312) 857-1056
REVISIONSDESCRIPTION BYDATEREV.
12345678
APPROVED BY:CREATED BY:
PROJ. ENGINEER:SCALE: DATE CREATED:
CHECKED BY:
07/01/2108/03/2110/12/21
FOR OUC REVIEWFOR OUC REVIEW
ISSUED FOR CONSTRUCTION
BAHBAHABM
BAH
HJM
HJMACS
12/08/2020AS SHOWN
COMED PROPOSEDCONDUIT INSTALLATION155 N. CARPENTER - PERM (PART 1)CHICAGO, ILLINOISCOMED WO#: 16706946DBS PROJECT#: 603.074EFP- 110905
THIS AND THE FOLLOWING SHEETS ARE NOT TRANSFERABLEAND ARE ONLY CONSIDERED AN OFFICIAL CONSTRUCTIONDRAWING WHEN ACCOMPANIED BY A SIGNED ENGINEERING SEAL.
THIS MATERIAL IS THE PROPERTY OF COMED AND CONTAINS CONFIDENTIALINFORMATION WHICH MUST NOT BE DUPLICATED, USED, OR DISCLOSEDOTHER THAN AS EXPRESSLY AUTHORIZED BY COMED.
An Exelon Company
DB STERLIN CONSULTANTS, INC.
148
TRAFFIC CONTROL - STAGE 3
NOTES:
1. CONTRACTOR SHALL NOTIFY RESIDENTS AND BUSINESSES OF ON-STREET PARKING CLOSURES.2. TRAFFIC CONTROL FOR THIS PROJECT SHALL BE DONE IN ACCORDANCE WITH THE CITY OF CHICAGO DEPARTMENT OF TRANSPORTATION'S "RULES AND
REGULATIONS FOR CONSTRUCTION IN THE PUBLIC WAY."3. THE CONTRACTOR IS RESPONSIBLE FOR THE MAINTENANCE OF TRAFFIC AND SHALL PROVIDE MATERIALS AND SIGNS TO INFORM AND PROTECT PEDESTRIANS.4. ALL TRAFFIC CONTROL DEVICES SHALL BE IN PLACE PRIOR TO WORK COMMENCING5. TRAFFIC CONTROL DEVICES SHALL CONFORM TO SECTION 701 OF THE ILLINOIS DEPARTMENT OF TRANSPORTATION STANDARD SPECIFICATIONS FOR ROAD
AND BRIDGE CONSTRUCTION, ADOPTED APRIL 1, 2016.6. TRAFFIC CONTROL DEVICE DETAILS CAN BE FOUND IN ILLINOIS DEPARTMENT OF TRANSPORTATION'S STANDARD NO. 701901-077. A 7 FOOT CLEARANCE FROM THE BOTTOM OF THE SIGN TO THE TOP OF PAVEMENT IS REQUIRED FOR SIGNS THAT WILL BE IN PLACE FOR MORE THAN 4 DAYS,
AND SHALL BE POST MOUNTED IN THE GROUND WHENEVER POSSIBLE.8. MAINTAIN ACCESS TO DRIVEWAYS AT ALL TIMES. SEE IDOT DISTRICT ONE.9. CONTRACTOR SHALL RESTORE ALL TRAFFIC LANES TO NORMAL TRAFFIC PATTERN DURING NON-WORK HOURS UNLESS OTHERWISE DIRECTED.10. SECURE ALL OPENINGS DURING NON-WORK HOURS.
LEGEND
CONSTRUCTION DRUMEXISTING TRAFFIC DIRECTIONPROPOSED TRAFFIC DIRECTIONPROPOSED WORK AREA
TYPICAL CROSS SECTIONFOR W. RANDOLPH ST. - FACING WEST
5'35'
LANE12' MIN.
42'WORKAREA
35'LANE
CONSTRUCTION DRUMRAISED MEDIAN RAISED MEDIAN
R9-11a
SIDEWALK CLOSED
CROSS HERE
R9-11a
SIDEWALK CLOSED
CROSS HERE
W. RANDOLPH ST.
N. C
ARPE
NTE
R ST
.
135'TRANSITION
TAPERAREA
18' WORK AREA
17' LANE
SHEET: OF
D
21 3 4 5 6 7
21 3 4 5 6 7
E
D
C
B
A
E
C
B
A
123 N. WACKER DRIVE SUITE 2000CHICAGO, ILLINOIS 60606TEL. (312) 857-1006 FAX. (312) 857-1056
REVISIONSDESCRIPTION BYDATEREV.
12345678
APPROVED BY:CREATED BY:
PROJ. ENGINEER:SCALE: DATE CREATED:
CHECKED BY:
07/01/2108/03/2110/12/21
FOR OUC REVIEWFOR OUC REVIEW
ISSUED FOR CONSTRUCTION
BAHBAHABM
BAH
HJM
HJMACS
12/08/2020AS SHOWN
COMED PROPOSEDCONDUIT INSTALLATION155 N. CARPENTER - PERM (PART 1)CHICAGO, ILLINOISCOMED WO#: 16706946DBS PROJECT#: 603.074EFP- 110905
THIS AND THE FOLLOWING SHEETS ARE NOT TRANSFERABLEAND ARE ONLY CONSIDERED AN OFFICIAL CONSTRUCTIONDRAWING WHEN ACCOMPANIED BY A SIGNED ENGINEERING SEAL.
THIS MATERIAL IS THE PROPERTY OF COMED AND CONTAINS CONFIDENTIALINFORMATION WHICH MUST NOT BE DUPLICATED, USED, OR DISCLOSEDOTHER THAN AS EXPRESSLY AUTHORIZED BY COMED.
An Exelon Company
DB STERLIN CONSULTANTS, INC.
149
TRAFFIC CONTROL - STAGE 4
NOTES:
1. CONTRACTOR SHALL NOTIFY RESIDENTS AND BUSINESSES OF ON-STREET PARKING CLOSURES.2. TRAFFIC CONTROL FOR THIS PROJECT SHALL BE DONE IN ACCORDANCE WITH THE CITY OF CHICAGO DEPARTMENT OF TRANSPORTATION'S "RULES AND
REGULATIONS FOR CONSTRUCTION IN THE PUBLIC WAY."3. THE CONTRACTOR IS RESPONSIBLE FOR THE MAINTENANCE OF TRAFFIC AND SHALL PROVIDE MATERIALS AND SIGNS TO INFORM AND PROTECT PEDESTRIANS.4. ALL TRAFFIC CONTROL DEVICES SHALL BE IN PLACE PRIOR TO WORK COMMENCING5. TRAFFIC CONTROL DEVICES SHALL CONFORM TO SECTION 701 OF THE ILLINOIS DEPARTMENT OF TRANSPORTATION STANDARD SPECIFICATIONS FOR ROAD
AND BRIDGE CONSTRUCTION, ADOPTED APRIL 1, 2016.6. TRAFFIC CONTROL DEVICE DETAILS CAN BE FOUND IN ILLINOIS DEPARTMENT OF TRANSPORTATION'S STANDARD NO. 701901-077. A 7 FOOT CLEARANCE FROM THE BOTTOM OF THE SIGN TO THE TOP OF PAVEMENT IS REQUIRED FOR SIGNS THAT WILL BE IN PLACE FOR MORE THAN 4 DAYS,
AND SHALL BE POST MOUNTED IN THE GROUND WHENEVER POSSIBLE.8. MAINTAIN ACCESS TO DRIVEWAYS AT ALL TIMES. SEE IDOT DISTRICT ONE.9. CONTRACTOR SHALL RESTORE ALL TRAFFIC LANES TO NORMAL TRAFFIC PATTERN DURING NON-WORK HOURS UNLESS OTHERWISE DIRECTED.10. SECURE ALL OPENINGS DURING NON-WORK HOURS.
LEGEND
CONSTRUCTION DRUMEXISTING TRAFFIC DIRECTIONPROPOSED TRAFFIC DIRECTIONPROPOSED WORK AREA
TYPICAL CROSS SECTIONFOR W. RANDOLPH ST. - FACING WEST
12'
18'WORKAREA12' MIN 12'12' MIN.
35'LANE
CONSTRUCTION DRUMRAISED MEDIAN
RAISED MEDIAN
17' MIN.
R9-11a
SIDEWALK CLOSED
CROSS HERE
R9-11a
SIDEWALK CLOSED
CROSS HERE
W. RANDOLPH ST.
N. C
ARPE
NTE
R ST
.
35' LANE
12' MEDIAN
12' LANE
12' MEDIAN
27' LANE
12' LANE
8' TEMP WALK
16' LANE16' LANE
8' TEMP WALK
SHEET: OF
D
21 3 4 5 6 7
21 3 4 5 6 7
E
D
C
B
A
E
C
B
A
123 N. WACKER DRIVE SUITE 2000CHICAGO, ILLINOIS 60606TEL. (312) 857-1006 FAX. (312) 857-1056
REVISIONSDESCRIPTION BYDATEREV.
12345678
APPROVED BY:CREATED BY:
PROJ. ENGINEER:SCALE: DATE CREATED:
CHECKED BY:
07/01/2108/03/2110/12/21
FOR OUC REVIEWFOR OUC REVIEW
ISSUED FOR CONSTRUCTION
BAHBAHABM
BAH
HJM
HJMACS
12/08/2020AS SHOWN
COMED PROPOSEDCONDUIT INSTALLATION155 N. CARPENTER - PERM (PART 1)CHICAGO, ILLINOISCOMED WO#: 16706946DBS PROJECT#: 603.074EFP- 110905
THIS AND THE FOLLOWING SHEETS ARE NOT TRANSFERABLEAND ARE ONLY CONSIDERED AN OFFICIAL CONSTRUCTIONDRAWING WHEN ACCOMPANIED BY A SIGNED ENGINEERING SEAL.
THIS MATERIAL IS THE PROPERTY OF COMED AND CONTAINS CONFIDENTIALINFORMATION WHICH MUST NOT BE DUPLICATED, USED, OR DISCLOSEDOTHER THAN AS EXPRESSLY AUTHORIZED BY COMED.
An Exelon Company
DB STERLIN CONSULTANTS, INC.
1410
TRAFFIC CONTROL - STAGE 5
NOTES:
1. CONTRACTOR SHALL NOTIFY RESIDENTS AND BUSINESSES OF ON-STREET PARKING CLOSURES.2. TRAFFIC CONTROL FOR THIS PROJECT SHALL BE DONE IN ACCORDANCE WITH THE CITY OF CHICAGO DEPARTMENT OF TRANSPORTATION'S "RULES AND
REGULATIONS FOR CONSTRUCTION IN THE PUBLIC WAY."3. THE CONTRACTOR IS RESPONSIBLE FOR THE MAINTENANCE OF TRAFFIC AND SHALL PROVIDE MATERIALS AND SIGNS TO INFORM AND PROTECT PEDESTRIANS.4. ALL TRAFFIC CONTROL DEVICES SHALL BE IN PLACE PRIOR TO WORK COMMENCING5. TRAFFIC CONTROL DEVICES SHALL CONFORM TO SECTION 701 OF THE ILLINOIS DEPARTMENT OF TRANSPORTATION STANDARD SPECIFICATIONS FOR ROAD
AND BRIDGE CONSTRUCTION, ADOPTED APRIL 1, 2016.6. TRAFFIC CONTROL DEVICE DETAILS CAN BE FOUND IN ILLINOIS DEPARTMENT OF TRANSPORTATION'S STANDARD NO. 701901-077. A 7 FOOT CLEARANCE FROM THE BOTTOM OF THE SIGN TO THE TOP OF PAVEMENT IS REQUIRED FOR SIGNS THAT WILL BE IN PLACE FOR MORE THAN 4 DAYS,
AND SHALL BE POST MOUNTED IN THE GROUND WHENEVER POSSIBLE.8. MAINTAIN ACCESS TO DRIVEWAYS AT ALL TIMES. SEE IDOT DISTRICT ONE.9. CONTRACTOR SHALL RESTORE ALL TRAFFIC LANES TO NORMAL TRAFFIC PATTERN DURING NON-WORK HOURS UNLESS OTHERWISE DIRECTED.10. SECURE ALL OPENINGS DURING NON-WORK HOURS.
TEMPORARY TRAFFIC BARRIER
LEGEND
CONSTRUCTION DRUMEXISTING TRAFFIC DIRECTIONPROPOSED TRAFFIC DIRECTIONPROPOSED WORK AREA
PROPOSED TEMP WALK
TYPICAL CROSS SECTIONFOR W. RANDOLPH ST. - FACING WEST
12'
18'TEMPWALK12' MIN 12'12' MIN.
35'LANE
TRAFFIC BARRIERRAISED MEDIAN RAISED MEDIAN
27' MIN.
DETAIL 2TYPICAL HANDICAP ACCESS TO TEMPORARY WALKWAY DETAIL
NOT TO SCALE
4' X 4' LEVELLANDING AREA
7' RAMP AT1:14 SLOPE
TOP OF CURB
FACE OF CURB
STREET/GRADE
4' X 4' LEVELLANDING AREA
7' RAMP AT1:14 SLOPE
SECTION A-A
141
TEMPORARY PEDESTRIAN WALKWAYSEE DETAIL 2.
W. RANDOLPH ST.
N. C
ARPE
NTE
R ST
.
COMED DETAILS
SHEET: OF
D
21 3 4 5 6 7
21 3 4 5 6 7
E
D
C
B
A
E
C
B
A
123 N. WACKER DRIVE SUITE 2000CHICAGO, ILLINOIS 60606TEL. (312) 857-1006 FAX. (312) 857-1056
REVISIONSDESCRIPTION BYDATEREV.
12345678
APPROVED BY:CREATED BY:
PROJ. ENGINEER:SCALE: DATE CREATED:
CHECKED BY:
07/01/2108/03/2110/12/21
FOR OUC REVIEWFOR OUC REVIEW
ISSUED FOR CONSTRUCTION
BAHBAHABM
BAH
HJM
HJMACS
12/08/2020AS SHOWN
COMED PROPOSEDCONDUIT INSTALLATION155 N. CARPENTER - PERM (PART 1)CHICAGO, ILLINOISCOMED WO#: 16706946DBS PROJECT#: 603.074EFP- 110905
THIS AND THE FOLLOWING SHEETS ARE NOT TRANSFERABLEAND ARE ONLY CONSIDERED AN OFFICIAL CONSTRUCTIONDRAWING WHEN ACCOMPANIED BY A SIGNED ENGINEERING SEAL.
THIS MATERIAL IS THE PROPERTY OF COMED AND CONTAINS CONFIDENTIALINFORMATION WHICH MUST NOT BE DUPLICATED, USED, OR DISCLOSEDOTHER THAN AS EXPRESSLY AUTHORIZED BY COMED.
An Exelon Company
DB STERLIN CONSULTANTS, INC.
1411
COMED CONSTRUCTION NOTES - DISTRIBUTION
1. USE EXTREME CAUTION NEAR COMED FACILITIES. HAND DIG WHILE CROSSING 69/138/345 kV
TRANSMISSION LINES. COMED TRANSMISSION SHALL BE NOTIFIED 2 BUSINESS DAYS PRIOR TO
THE START OF WORK. TO SCHEDULE AN ONSITE INSPECTOR DURING CONSTRUCTION, CONTACT
LESLIE PASCHAL AT (630) 437-4767.
2. THE CONTRACTOR SHALL PROVIDE ALL MATERIAL, LABOR AND EQUIPMENT REQUIRED TO
FURNISH AND INSTALL THE WORK AS DESCRIBED HEREIN, AND SHALL BE RESPONSIBLE
FOR ALL JOB SITE DELIVERY COSTS AND UTILITY RELOCATION CHARGES AS REQUIRED.
3. PRIOR TO EXCAVATION, THE CONTRACTOR SHALL SAWCUT EDGES OF PROPOSED TRENCH
AND MARK THE PROPOSED CONDUIT ROUTE ON THE PAVEMENT SURFACE. IN UNPAVED
AREAS THE TRENCH SHALL BE MARKED OFF BY MEANS OF A CHALK LINE.
4. PRIOR TO THE START OF WORK, THE CONTRACTOR SHALL VERIFY LOCATIONS OF ANY
OVERHEAD OBSTRUCTIONS. PRIOR TO EXCAVATION, THE CONTRACTOR SHALL PERFORM
TEST HOLES AS NEEDED ALONG PROPOSED CONDUIT ROUTE AND AT PROPOSED OR
EXISTING MANHOLE LOCATIONS TO VERIFY HORIZONTAL AND VERTICAL LOCATION OF
EXISTING UTILITIES.
5. CONTRACTOR TO OVER-EXCAVATE 3-INCHES ALL AROUND PROPOSED STRUCTURES
AND CONDUIT.
6. THE CONTRACTOR IS RESPONSIBLE FOR SUPPORTING THE TRENCH OR EXCAVATION
IN ACCORDANCE WITH OSHA REGULATIONS IN ORDER TO PREVENT TRENCH SIDES
FROM CAVING IN. TRENCH/EXCAVATION SUPPORT SHALL BE SUITABLE TO FIELD
CONDITIONS AND SHALL BE DESIGNED, SUPPLIED, AND INSTALLED BY THE CONTRACTOR
AND SHALL BE APPROVED BY COMED.
7. WHERE EXCAVATION REQUIRES SHORING, THE CONTRACTOR SHALL INSTALL A 6"
CONCRETE MUDSLAB AT THE BASE OF EXCAVATION. CONTRACTOR SHALL DESIGN
AND PLACE SHORING SO AS NOT TO CUT OFF ANY EXISTING UTILITIES.
8. THE CONTRACTOR SHALL DEWATER ALL EXCAVATIONS SO THAT THE GROUNDWATER
TABLE REMAINS BELOW THE BASE OF EXCAVATION.
9. THE CONTRACTOR SHALL REMOVE ALL EXCAVATED MATERIAL ON A DAILY BASIS.
STOCKPILING OF MATERIAL IS NOT ALLOWED.
10. THE CONTRACTOR SHALL THOROUGHLY INSPECT ALL EXCAVATIONS PRIOR TO INSTALLING
PROPOSED CONDUIT OR STRUCTURES. ANY EXISTING INFRASTRUCTURE IN CONFLICT
SHALL BE VERIFIED ABANDONED BY THE CONTRACTOR AND REPORTED TO COMED,
THE UTILITY, AND THE ENGINEER OF RECORD PRIOR TO REMOVAL.
11. THE CONTRACTOR SHALL ASSUME ALL CABLES ARE ENERGIZED AND MUST BE
SUPPORTED SO AS NOT TO STRESS ANY PART OF THE CABLE.
12. THE CONTRACTOR SHALL CLEAN ALL DEBRIS FROM MANHOLES WORKED IN, INCLUDING ANY
DEBRIS PRESENT IN EXISTING MANHOLES PRIOR TO THE START OF WORK. CONTRACTOR TO
PUMP MANHOLES EACH DAY AS REQUIRED.
13. THE CONTRACTOR SHALL NOTIFY COMED AND THE ENGINEER OF RECORD WHEN PROPOSED
DEPTH OF EXCAVATION EXCEEDS THE DEPTH SHOWN ON THE PLANS. CONTRACTOR SHALL
ALSO NOTIFY THESE PARTIES WHEN THE REQUIRED HORIZONTAL AND/OR VERTICAL
SEPARATION FROM EXISTING UTILITIES CANNOT BE MAINTAINED. IN THESE SITUATIONS,
WORK SHALL NOT PROCEED UNTIL DIRECTION IS GIVEN BY COMED.
OWNER:
COMMONWEALTH EDISON (COMED)EVAN WALKER3500 N. CALIFORNIA AVE.CHICAGO, IL [email protected](779) 231-1617
ENGINEER:
DB STERLIN CONSULTANTS, INC.HANNAH MARTENS123 N. WACKER DRIVE, SUITE 2000CHICAGO, IL [email protected](312) 857-1006
TYPICAL 8 DUCT PVC PACKAGE NOT TO SCALE
CONCRETEENCASEMENT
CONST. DETAILS 1
SHEET: OF
D
21 3 4 5 6 7
21 3 4 5 6 7
E
D
C
B
A
E
C
B
A
123 N. WACKER DRIVE SUITE 2000CHICAGO, ILLINOIS 60606TEL. (312) 857-1006 FAX. (312) 857-1056
REVISIONSDESCRIPTION BYDATEREV.
12345678
APPROVED BY:CREATED BY:
PROJ. ENGINEER:SCALE: DATE CREATED:
CHECKED BY:
07/01/2108/03/2110/12/21
FOR OUC REVIEWFOR OUC REVIEW
ISSUED FOR CONSTRUCTION
BAHBAHABM
BAH
HJM
HJMACS
12/08/2020AS SHOWN
COMED PROPOSEDCONDUIT INSTALLATION155 N. CARPENTER - PERM (PART 1)CHICAGO, ILLINOISCOMED WO#: 16706946DBS PROJECT#: 603.074EFP- 110905
THIS AND THE FOLLOWING SHEETS ARE NOT TRANSFERABLEAND ARE ONLY CONSIDERED AN OFFICIAL CONSTRUCTIONDRAWING WHEN ACCOMPANIED BY A SIGNED ENGINEERING SEAL.
THIS MATERIAL IS THE PROPERTY OF COMED AND CONTAINS CONFIDENTIALINFORMATION WHICH MUST NOT BE DUPLICATED, USED, OR DISCLOSEDOTHER THAN AS EXPRESSLY AUTHORIZED BY COMED.
An Exelon Company
DB STERLIN CONSULTANTS, INC.
1412
CONST. DETAILS 2
SHEET: OF
D
21 3 4 5 6 7
21 3 4 5 6 7
E
D
C
B
A
E
C
B
A
123 N. WACKER DRIVE SUITE 2000CHICAGO, ILLINOIS 60606TEL. (312) 857-1006 FAX. (312) 857-1056
REVISIONSDESCRIPTION BYDATEREV.
12345678
APPROVED BY:CREATED BY:
PROJ. ENGINEER:SCALE: DATE CREATED:
CHECKED BY:
07/01/2108/03/2110/12/21
FOR OUC REVIEWFOR OUC REVIEW
ISSUED FOR CONSTRUCTION
BAHBAHABM
BAH
HJM
HJMACS
12/08/2020AS SHOWN
COMED PROPOSEDCONDUIT INSTALLATION155 N. CARPENTER - PERM (PART 1)CHICAGO, ILLINOISCOMED WO#: 16706946DBS PROJECT#: 603.074EFP- 110905
THIS AND THE FOLLOWING SHEETS ARE NOT TRANSFERABLEAND ARE ONLY CONSIDERED AN OFFICIAL CONSTRUCTIONDRAWING WHEN ACCOMPANIED BY A SIGNED ENGINEERING SEAL.
THIS MATERIAL IS THE PROPERTY OF COMED AND CONTAINS CONFIDENTIALINFORMATION WHICH MUST NOT BE DUPLICATED, USED, OR DISCLOSEDOTHER THAN AS EXPRESSLY AUTHORIZED BY COMED.
An Exelon Company
DB STERLIN CONSULTANTS, INC.
1413
TRENCH SHORING DETAILS
SHEET: OF
D
21 3 4 5 6 7
21 3 4 5 6 7
E
D
C
B
A
E
C
B
A
123 N. WACKER DRIVE SUITE 2000CHICAGO, ILLINOIS 60606TEL. (312) 857-1006 FAX. (312) 857-1056
REVISIONSDESCRIPTION BYDATEREV.
12345678
APPROVED BY:CREATED BY:
PROJ. ENGINEER:SCALE: DATE CREATED:
CHECKED BY:
07/01/2108/03/2110/12/21
FOR OUC REVIEWFOR OUC REVIEW
ISSUED FOR CONSTRUCTION
BAHBAHABM
BAH
HJM
HJMACS
12/08/2020AS SHOWN
COMED PROPOSEDCONDUIT INSTALLATION155 N. CARPENTER - PERM (PART 1)CHICAGO, ILLINOISCOMED WO#: 16706946DBS PROJECT#: 603.074EFP- 110905
THIS AND THE FOLLOWING SHEETS ARE NOT TRANSFERABLEAND ARE ONLY CONSIDERED AN OFFICIAL CONSTRUCTIONDRAWING WHEN ACCOMPANIED BY A SIGNED ENGINEERING SEAL.
THIS MATERIAL IS THE PROPERTY OF COMED AND CONTAINS CONFIDENTIALINFORMATION WHICH MUST NOT BE DUPLICATED, USED, OR DISCLOSEDOTHER THAN AS EXPRESSLY AUTHORIZED BY COMED.
An Exelon Company
DB STERLIN CONSULTANTS, INC.
1414
3.0'MAX
11.0'
1.0' 5.0' MAX. (TYP.) 5.0' MAX. (TYP.)
6" x 6" x 1 4" P (TYP.)(SEE NOTE 10)
L8" x 8" (NOMINAL) HARDWOODWALERS (TYP.) (SEE NOTE 2)
4" x 8" HARDWOOD TIMBER SHEETING(ROUGH CUT) (SEE NOTES 2 AND 9)
THREADED SCREW JACK SCHEDULE80 21
2" Ø STEEL PIPE STRUTS (TYP.)(SEE NOTE 4)
TYPICAL TIMBER 8'-7" TRENCH SHORING PLAN
TYPICAL TIMBER 8'-7" TRENCH SHORING ELEVATION
6" x 6" x 1 4" P (TYP.)(SEE NOTE 10)
L
8" x 8" (NOMINAL) HARDWOODWALERS (TYP.) (SEE NOTE 2)
FINISHED BASE OF EXCAVATION
BASE OF EXCAVATION
6" CONCRETE MUD SLAB TO BEINSTALLED SAME DAY AS BASEOF EXCAVATION IS REACHED(SEE NOTE 12)
EXISTING GRADE EXISTING GRADE
8.6'MAX
0.5'
SHEETING SHALL BE MAINTAINEDAT BASE OF EXCAVATION AT ALL
TIMES. NO EMBEDMENT REQUIRED.
2.5'
2.5'
2.1'
4" x 8" HARDWOODTIMBER SHEETING(SEE NOTE 2 & 9)
3.0' MAX
1.0'
07-01-2021HAN
NAH J._
MARTENS062-059491
REGISTEREDPROFESSIONAL
ENGINEEROF
ST
A
T E O F I L L I N
OI S
SIGNATURE
DATE
PROFESSIONAL ENGINEEREXPIRES 11-30-2021
TRENCH SHORING NOTES:1) TO ENSURE PROTECTION OF EXISTING UTILITIES, REFER TO PERTINENT INSTALLATION DRAWINGS FOR PROTECTION REQUIREMENTS.
CONTRACTOR TO PROVIDE PROTECTION OF EXISTING INFRASTRUCTURE PER CDOT AND SPECIFIC INFRASTRUCTURE OWNERSPECIFICATIONS. CONTRACTOR TO FIELD VERIFY HORIZONTAL & VERTICAL LOCATIONS OF ALL EXISTING UTILITIES.
2) TIMBER SHALL HAVE A MINIMUM EXTREME FIBER BASIC BENDING STRESS OF 1350 PSI (SHEETING) AND 1,600 PSI (TIMBER WALERS).BASIC STRESS VALUES ARE ALLOWABLE STRESS VALUES BEFORE SIZE AN USAGE COEFFICIENTS ARE APPLIED IN ACCORDANCE WITH THEAMERICAN FOREST & PAPER ASSOCIATION NATIONAL DESIGN SUPPLEMENT (2005).
3) CONTRACTOR TO ADEQUATELY SUPPORT THE SCHEDULE 80 THREADED SCREW JACKS TO MAINTAIN THE INTEGRITY OF THE SHORINGSYSTEM FOR DUCT PACKAGE INSTALLATION AND FOR SAFETY OF WORKERS IN AND AROUND THE INSTALLATION. THE 2.5" Ø SCREW JACKPIPE STRUTS WILL BE PRELOADED OR TIGHTENED TO MINIMIZE ADJACENT GROUND MOVEMENT.
4) IF NECESSARY, LOCATE WALERS AND SCREW JACK PIPE STRUTS TO AVOID CONFLICT WITH EXISTING UTILITY CROSSING OPENINGS.SPACINGS BETWEEN ADJACENT STRUTS AND WALERS SHALL NOT EXCEED MAXIMUM SPACINGS SPECIFIED ON THIS DRAWING.
5) A SURCHARGE PRESSURE OF 250 PSF VERTICAL HAS BEEN CONSIDERED IN DESIGN. ENGINEER SHALL BE CONTACTED IF THE VALUE ISEXCEEDED FOR THE TYPE OF EQUIPMENT THAT WILL BE USED.
6) GRADE ADJACENT TO EXCAVATION SHALL BE LEVEL. CONTRACTOR SHALL MAINTAIN NO MORE THAN ONE FOOT DIFFERENTIAL IN LEVELOF BACKFILL ON OPPOSITE SIDES OR ON ADJACENT SIDES OF SHORED EXCAVATION.
7) LIMIT EXCAVATION DEPTH NO MORE THAN 1'-0" BELOW EACH BRACING LEVEL UNTIL STRUTS ARE IN PLACE.8) NOTIFY DIGGER AT 312-744-7000 FOR UTILITY CLEARANCE 48 HOURS PRIOR TO COMMENCING EXCAVATION.9) SHEETING SHALL BE PUSHED IN WITH AN EXCAVATOR BUCKET DURING TRENCH EXCAVATION TO THE REQUIRED DEPTH. NOTIFY
ENGINEER IF MINIMUM SPECIFIED EMBEDMENT DEPTH CANNOT BE ATTAINED IN THE FIELD. SHEETING SHALL NOT BE DRIVEN IN.10) ALL STRUCTURAL STEEL PLATES SHALL CONFORM TO ASTM A36, UNLESS NOTED OTHERWISE.11) SEE INSTALLATION DRAWINGS FOR OPENING LOCATIONS.12) MUD SLAB CONCRETE SHALL HAVE A MINIMUM COMPRESSION STRENGTH OF 4,000 PSI AT 28 DAYS.13) GROUNDWATER SHALL BE MAINTAINED AT LEAST 2'-0" BELOW THE BASE OF EXCAVATION BY DE-WATERING.14) CONTRACTOR TO MAINTAIN A MINIMUM DISTANCE OF 2'-0" TO THE EDGE OF TRENCH FROM ALL CONSTRUCTION EQUIPMENT AND
TRAFFIC INCLUDING HS-20 RATED TRUCKS. ALL TRAFFIC CONTROL ARRANGEMENTS FOR EXCAVATION SHALL ALLOW FOR ADHERENCE TOMINIMUM CLEARANCE.
15) SHEETING INSTALLATION:15-A) CONTRACTOR TO INSTALL SHEETING IN TRENCH TO 5'-3" (MIN.) BELOW ELEVATION OF BRACE LEVEL B1.
CONTRACTOR TO EXCAVATE DOWN TO 1'-0" BELOW ELEVATION OF BRACE LEVEL B1 THEN INSTALL BRACE LEVEL B1 (UPPERMOST). CONTRACTOR TO BACKFILL VOIDS BEHIND SHEETING WITH SAND FILL OR GROUT.
15-B) CONTRACTOR TO PUSH SHEETING DOWN TO 4'-0" (MIN.) BELOW ELEVATION OF BRACE LEVEL B2. CONTRACTOR TO EXCAVATE DOWN TO 1'-0" BELOW ELEVATION OF BRACE LEVEL B2 THEN INSTALL BRACE LEVEL B2. CONTRACTORTO BACKFILL VOIDS BEHIND SHEETING WITH SAND FILL OR GROUT.
15-C) CONTRACTOR TO PUSH SHEETING DOWN TO 1'-0" (MIN.) BELOW ELEVATION OF BRACE LEVEL B3. CONTRACTOR TO EXCAVATE DOWN TO 1'-0" BELOW ELEVATION OF BRACE LEVEL B3 THEN INSTALL BRACE LEVEL B3. CONTRACTORTO BACKFILL VOIDS BEHIND SHEETING WITH SAND FILL OR GROUT.
15-D) CONTRACTOR TO PUSH SHEETING DOWN TO FINAL TOE ELEVATION AS SHOWN. CONTINUE EXCAVATION TO BASE OF EXCAVATIONBELOW GRADE. CONTRACTOR TO BACKFILL VOIDS BEHIND SHEETING WITH SAND FILL OR GROUT. POUR 0'-6" MUD SLAB BY THE END OF THE SHIFT ON THE SAME DAY AS THE COMPLETION OF THE FINAL EXCAVATION DEPTH.
B1
B2
B3